SCALABILITY EFFICIENCY RELIABILITY Make in India
Company
UNINTERRUPTIBLEPOWER SUPPLIES
Upto 2400 kVA
Autometers Alliance Ltd
Autometers Alliance Ltd
manufacturing online Pegasus UPS systems upto 2400 kVA (8×300 kVA) based on European
Technology sourced from Powertronix S.p.A, Italy and adapted to Indian operating conditions.
Autometers Alliance Ltd offers MODULAR and STAND ALONE systems designed as GREEN
POWER SOLUTION, a boon for the company's expanding list of satisfied customers.
Powertronix S.p.A. Italy is Europe's leading designer and manufacturer of online UPS systems
for over 20 years having presence in six continents across the globe. Based on its research
philosophy, strong design elements and strict testing procedures, Powertronix delivers high
quality and reliable products conforming to International Standards as well as meeting regional
specifications. Powertronix continuously supports Autometers Alliance Ltd in technology
upgradation and customized application endeavors.
ranks amongst the premier UPS manufacturers in the country,
ABOUT PEGASUS UPS
1
PRODUCT RANGE
PRODUCT SERIES CONFIGURATION RATING
3Ø 3Ø INPUT - OUTPUT
3Ø INPUT - 1Ø OUTPUT
3Ø INPUT 1Ø I - OUTPUT
3Ø 3ØINPUT - OUTPUT
3Ø 3Ø INPUT - OUTPUT
ALPHA 31 SERIES
PGS-31 SERIES
ALPHA 33 SERIES
GAMMA SERIES
ALPHA RM SERIES
BETA SERIES 3Ø 3Ø INPUT - OUTPUT
10-500 kVA *
10-40 kVA
10-60 kVA
10-400 kVA*
10-600 kVA *
60-300 kVA*
*Parallelable systems
Customised UPS solutions & / or client ‘Load Analysis’ offered on demand
2
SALIENT FEATURESFPGA (DSP) BASED DOUBLE CONVERSION TOPOLOGY
ACTIVE POWER FACTOR CORRECTION AT UPS INPUT
HIGH FREQUENCY PWM BASED INVERTER USING IGBTS
PARALLEL REDUNDANCY
AUTO RE-TRANSFER STATIC SWITCH
ENERGY SAVING MODE
HIGH POWER DENSITY
INDEPENDENT LCD
FLEXIBILITY / UPGRADABILITY
At input stage AC supply is converted to controlled DC and in second stage DC is converted to controlled AC which is used to support the critical loads. Due to double conversion the load is completely protected against spikes, surges and brownouts. Use of FPGA (DSP) ensures low component count and reliability of the circuit.
At input stage, conversion from AC to controlled DC is achieved through high frequency PWM based Converter using IGBTs. This technology offers following benefits to the user.
• Input power factor >0.99
• Very low input current distortion (<3%), input current waveform similar to pure sinewave. No harmonics will be reflected back to mains, thus no pollution of the input mains
• UPS can operate with almost same capacity Generator
• Auto correction for input phase sequence reversal
• Reduced size of cabling and switchgear at the input stage
Conversion from DC to controlled and pollution free AC is achieved through high frequency PWM based Inverter using IGBTs with instantaneous sinewave control. The technology offers following benefits to the users.
• High efficiency
• Low noise
• Compact size
• Faster transient response
The Alpha, Beta & Gamma series of UPS systems can be used in parallel configuration. Paralleling can be done for the purpose of either redundancy or capacity enhancement. These systems can be configured in hot stand-by, 100% parallel redundant and N+1 redundant mode.
These UPS systems have a unique feature of re-transferring load automatically back to inverter as long as inverter is healthy and the load is within the capacity of the UPS.
This feature is very helpful for starting of loads, which draw starting in-rush current more than capacity of the UPS. The UPS goes to bypass on sensing over load and comes back on inverter supply automatically once the load current is settled to normal level. In addition to static switch, manual bypass switch is also provided for easy maintenance.
The UPS can operate in line-interactive mode simply by changing a jumper. The efficiency in this mode is up tp 98% leading to a big energy saving in applications where UPS is used as standby power source.
The Alpha RM series of UPS provides the most compact footprint by having a best in class Power Density of 409
2KW/m .
In RM Series each Power Module has independent LCD which displays Status and Alarms in real time.
a) Inherent N+X Redundancy
b) Hot swappable power module, bypass and monitoring module
c) Additional charging module can be added for longer back-up applications.
3
SMART SLEEP
This function enables some power modules to go to sleep when load is
relatively low, improving the efficiency of the remaining power modules.
The modules can also be made to work in a rotation mode by customer.
PHANTOM LOADING
This is an advanced function which can test the UPS under different load
situations without real load, saving more than 90% energy. Simulation of
load can be done for load testing at factory as well as at site.
UPS MANAGEMENT SOFTWAREUPS-Management Software is a client/server application for local, global
networks and also for single workstation. The server module of the UPS
Management Software is called UPSMAN, which communicates with the
UPS in RS232 mode via cable, or through the network, by a SNMP
adapter.
BENEFITS OF FPGA APPROACH
Scalability / Expandability Unlimited potential for growth & flexibility
Parallel processing Single or multi-systems on one chip
Deterministic Design Won't impact the part of the design already in place
Limitless Performance Out performs traditional DSP or Micro controller
Bus-bridging & peripheral functions
Allows high level of system integration
State-of-art Ready to use, re-configurable in the field
THE FPGA ADVANTAGE
Core functions of PEGASUS UPS are controlled by state-of-art high
performance FPGA based DSP, ensures multiple parallel processing and
expandability.
Comparison of processing 256 data samples by DSP & FPGA is illustrated
in Figure 1. Traditional DSP or microcontroller is processing sequentially,
whereas FPGA is processing simultaneously by means of dedicated
registers & multipliers, hence FPGA can be configured for faster response.
+
256-tap Filter Example
Conventional DSP Processor - Serial implementation
FPGA - Fully parallel implementation
Data In
C2 C3 C4 C5 C255
256 operations
in 1 clock cycle
Reg
XX XXX X
Data Out
Figure 1: FPGAs Parallel approach to DSP enables
Higher Computational Throughput
X
Data In
256 loops
needed
to process
samples
Data Out
Reg
MAC Unit
+
Coefficients
C0 C1X
Reg Reg Reg Reg Reg
The FPGA Advantage
UPS Management Software
Phantom Loading
Smart Sleep
3Ø Input - 1Ø Output
ALPHA 31 SERIES
10-40 kVA
Standard Features :
• Wide I ange
• High Input Power Factor
• Protection against Over Voltage, Short Circuit and Over Temperature
• Auto Fan Speed Adjustment
• LCD Display Monitoring all the operational status
nput Voltage R
Optional Features :
• SNMP for Remote Monitoring
• Dry Contacts
• Parallel Kit
• AS/400 Interface
• Battery Cold Start
4
ENVIRONMENTAL CONDITIONS
OUT PUTVoltage
Voltage Regulation
Total Harmonic Distortion
Power Factor
Crest Factor
Overload (inverter Mode)
DC LINK
Battery Voltage
Efficiency (Overall)
Efficiency (Inverter)
Efficiency (Eco Mode)
Display
Interface
Degree of Protection
Audible Noise
220/230/240 (Selectable)
1.50%
1% Linear Load, 5% Non Linear Load
0.9
3:1
110% for 10 min, 130% for 1 minute150% for 30 second
192VDC ±240VDC
95%93.50%
95%92%
98%
LED + LCD
RS232,RS485,USB
RS232,EPO
IP20
65dB
Operating Temperature
Storage Temperature -20°C to 70°C
Relative Humidity
0-40°C
0-95% (Non - Condensing)
PHYSICAL PARAMETERS
Dimensions(WxDxH) in mm
600x980x950
250x562x710
250x562x650
Approx.Weight (in Kg.) 170342725
53dB@<70% Load, 66dB@>70 % Load
1000 Meters without deratingMaximum Altitude Above Sea Level
Ratings (kVA/KW)
INPUTNominal Voltage
Voltage Range
Current Distortion
Frequency Range
380/400/415 V AC (Selectable)
320 to 480V@100% Load
4%
Power Factor 0.99 0.95
40Hz - 70Hz
40/3620/1815/13.510/9
Frequency 50 or 60 Hz (Selectable)
SYSTEM
PGS-31 SERIES 3Ø Input - 1Ø Output
10-60 kVA
5
200 250 300 350 425 450380Approx. Weight (kg.)
GENERAL
INPUT
Ratings (kVA/KW) 15/13.5 20/18 30/27 40/36 50/45 60/54
Nominal Voltage 3ø, 380 / 400 / 415V
Voltage Range 350 to 460
Frequency 50 or 60 Hz (Selectable)
Frequency Range 40 to 60Hz
Current Distortion <9% (Optional)
Power Factor 0.99 (Optional)
Battery Voltage
± 1%
< ± 1%
Voltage Tolerance
Voltage Ripple
384 Volts
Switching TimeInverter Failure : 2 ms
Other Modes : 0
STATIC BYPASS
Voltage Regulation
Overload
Voltage Distortion
OUTPUT
Nominal Voltage
50 or 60 Hz (Selectable)
0.9
Frequency
Power Factor
220V/230V/240V
< 3% at Linear Load
125% for 10 Minutes
Crest Factor 3:1
EfficiencyInverter : 93%
Overall : 91%
ENVIRONMENTAL CONDITIONOperating Temperature
-20°C to +70°C (Not for Batteries)
95% Non-condensing
Storage Temperature
Relative Humidity
0-40°C
1000 Meters without deratingMaximum Altitude Above Sea Level
PHYSICAL
Dimensions (WxDxH) mm
< 60dBA
Forced AirCooling
Audible noise at 1 Mtr.
Ingress protection IP – 21
10/9
390×910×630 530×920×860 700x740x1800
Static : ±1%
Dynamic : ± 5%
DC LINK
Standard Features :
• High Frequency PWM Using IGBTs• Inbuilt Isolation Transformer• Auto Re -Ttransfer Static Switch• Manual Bypass• Extended Battery Back-Up
Optional Features :
• SNMP for Remote Monitoring
• Active Power Factor Correction
• Software for Auto Shutdown
• Potential Free Contacts for Remote
Indications & Shutdown
• Management Software
3Ø Input - 3Ø Output
GAMMA SERIES
10-400 kVA
6
Overload
50 or 60 Hz (Selectable)Frequency
0.9Power Factor
125% for 10 Minutes
Crest Factor 3:1
EfficiencyInverter : 94%Overall : 92%
OUTPUT
INPUT
Ratings (kVA/KW)
Nominal Voltage
Voltage Range 350 to 460
Frequency 50 or 60 Hz (Selectable)
Frequency Variation 40 to 60Hz
3ø, 380 / 400 / 415V (Selectable)
3ø, 380 / 400 / 415V (Selectable)
10 - 400 kVA
Nominal Voltage
Voltage Regulation Balanced Load ±1%Unbalanced Load ± 5%
Phase Displacement Balanced Load 120° ± 1°Unbalanced Load 120° ± 3°
Voltage Distortion < 3% at Linear Load
Frequency Synchronization Range
±1%, ±2%, ±5%, ±10% (Selectable)
DC LINKBattery Voltage
± 1%
< ± 1%
Voltage Regulation
Voltage Ripple
384 Volts
Switching Time Inverter Failure : 2 ms
Other Modes : 0
STATIC BYPASS
ENVIRONMENTAL CONDITION
GENERAL
Operating Temperature
-20°C to +70°C (Not for Batteries)
95% Non - Condensing
Storage Temperature
Relative Humidity
0-40°C
1000 Meters without deratingMaximum Altitude Above Sea Level
Ingress Protection IP – 20
Forced AirCooling
<45 <45 <50 <50
440 x 900 x 1015
<50 <50 <50 <55 <55
500 x 1025 x 1075 700 x 725 x 1800
10/9
180 205 250 300 325 385 610 700355
15/13.5 20/18 30/27 40/36 50/45 60/64 80/72 100/90
<65
900
120/108
<65
1100
160/144
<65 <70 <70
1000 x 905 x 1965 1600 x 950 x 2100
1200 1800 1850
200/180 300/270 400/360
Weight (kg)
Dimensionsin mm (WxDxH)
kVA/KW Ratings
Noise Levelin db
Standard Features :
• High Frequency PWM Using IGBTs• Inbuilt Isolation Transformer• Auto Re-Transfer Static Switch• Energy Saving Mode• Parallel Redundancy
Optional Features :
• SNMP for Remote Monitoring
• Management Software
• Remote Monitor for Alarms / Indications
• Remote Emergency Power Off
• Potential Free Contacts for Remote Indications
• Voltage Stabiliser in Bypass Line
• Battery Management System
BETA SERIES 3Ø Input - 3Ø Output
60-300 kVA
7
410 x 835 x 1510 1000 x 900 x 2000 1600 x 950 x 2100
60/54
425
<50 <55 <60
580 650 900 1080 1200 1750 1850
80/72 100/90 120/108 160/144 200/180 250/225 300/270
Weight (kg)
Dimensionsin mm (WxDxH)
kVA / KWRatings
Noise Levelin db
Standard Features :
• Active Power Factor Correction at UPS Input• FPGA (DSP) Based Double Conversion Topology• Parallel redundancy• Energy Saving Mode
Optional Features :
• SNMP for Remote Monitoring.
• Isolation Transformer at UPS Input and Output
• Management Software
• Remote Monitor for Alarms/ Indications
• Remote Emergency Power Off
• Potential Free Contacts for Remote Indications
• Voltage Stabiliser in Bypass Line
• Battery Management System
50 or 60 Hz (Selectable)Frequency
0.9Power Factor
OUTPUT
Nominal Voltage
Voltage Regulation Static : ±1% Dynamic : ± 5%
380 / 400 / 415 V AC (Three Phase+N)
Parallelability Upto 8 Systems
Overload 125% for 10 Minutes
Crest Factor 3:1
EfficiencyInverter : 95%
Overall : 93%
Voltage Distortion < 3% at Linear Load
672 Volts
DC LINKBattery Voltage
Switching Time Inverter Failure : 2 ms
Other Modes : 0
STATIC BYPASS
ENVIRONMENTAL CONDITION
GENERAL
Operating Temperature
-20°C to +70°C (Not for Batteries)
95% Non - Condensing
Storage Temperature
Relative Humidity
0-40°C
1000 Meters without deratingMaximum Altitude Above Sea Level
Ingress Protection IP – 20
0.99Power Factor
Current Distortion <3%
380 / 400 / 415 V AC (Three Phase+N)
INPUT
Ratings (kVA/KW)
Nominal Voltage
Voltage Range
Frequency 50 or 60 Hz (Selectable)
Frequency Range 40Hz to 60Hz
60 - 300 kVA
330 to 480
ALPHA 33 SERIES 3Ø Input - 3Ø Output
10-500 kVA
8
Standard Features :• High Efficiency upto 96%• High Input PF>0.99, Input current THDI<3%• Multi Protections : Over Temperature Protection with 8 Sensors,
Overload, Battery Under Voltage, Fan Failure, Short - Circuit• Battery Cold Start• Modular Design of Subsystem, Convenient for Field Maintenance• Intelligent Battery Management with Smart Charging Control• High Power Density
Input CurrentDistortion
<4%
<4%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
<3%
RatingkVA/KW
10/10
15/15
20/18
30/27
40/36
60/54
80/72
90/81
100/90
120/108
150/135
200/180
250/225
300/270
400/360
500/450
System Efficiency
Over all Inverter
95%
95%
95%
95%
96%
96%
96%
96%
96%
96%
96%
96%
96%
95.50%
95.50%
95.50%
94.50%
94.50%
95%
95%
96%
96%
96%
96%
96%
96%
96%
96%
96%
95%
95%
95%
Output PowerFactor
1
1
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
Weight(Kg.)
DimensionWxDxH (mm) Noise
31
31
50
52
61
170
210
210
231
266
305
350
445
490
810
900
250x660x530
250x660x530
250x680x770
250x680x770
250x836x770
600x980x950
600x980x1150
600x980x1150
600x980x1400
600x980x1400
600x960x1600
600x960x1600
600x960x2000
600x960x2000
1300x1100x2000
1300x1100x2000
<55dB
68dB
72dB
DC LINK
Voltage
50 Hz or 60Hz (Selectable)
40-70Hz
Technology Double Conversion True Online Topology
Frequency range
Frequency
OUTPUT
Voltage Regulation 1% for Balanced Load, 1.5% for Unbalanced Load.
Voltage Distortion <1% (Linear Load) <5.5% (Non-Linear Load)
110% for 60 Minutes, 125% for 10 Minutes,150% for 1 Minutes.
± 240 VDCBattery Voltage
SYSTEM
>0.99Power Factor
INPUT Voltage
Voltage Range
10-500 kVARatings (kVA/KW)
304-478 V AC
3Ph+N+PE 380 / 400 / 415 V (Line-Line)
380 / 400 / 415 V (Line-Line Nominal), Selectable at Site
Display LCD & LED
Charging Current
Low Battery Cut-off
20% of System Power
1.7V/ Cell
Overload Capacity
±0.01% (in Free-Running Mode)Frequency Variation
Degree of Protection IP20
Interface : Standard RS-232, RS-485, Dual Input Kit
Temperature range of Operation 0 – 40°C
Relative Humidity 0 – 95% (Non - Condensing)
Interface : Optional SNMP, Dry Contacts
3ØInput - 3Ø Output
ALPHA RMS (RACK-MOUNTED SERIES)
10-600 kVA
9
Note:
*
10KW module can be set as 1/1, 3/1, 3/3 and 1/3 Power connection. 15KW onwards modules can only be set as 3/3 connection. For 10KW&15KW Modules input current distortion is <4%.
Frequency
Frequency Variation(in Free-Running Mode)
Phase Tolerance
Crest Factor
Overload
50Hz or 60Hz (Selectable)
±0.01%
120°±0.5° (Balanced and Unbalanced Load)
3:1
110%,60 minutes
125%,10 minutes
150%, 1 minute
Battery Voltage
Charge Power
Low Battery Cut-Off
±240VDC
20% of System Power
1.7V/ Cell
DC LINK
SYSTEMOverall Efficiency in Normal Mode
95%
Efficiency in ECO Mode
99%
Efficiency in Battery Mode 94.50%
Display 7” Touch Colour LCD & LED
Degree of Protection IP20
Interface : Standard RS-232, RS-485, EPO, Dry Contacts
Temperature Range of Operation 0 – 45°C
Relative Humidity 0 – 95% (Non-Condensing)
Audible Noise (1 Meter away)
56dB(One Module)
Interface : Optional SNMP
Voltage
Technology Double Conversion True Online Topology
40-70HzFrequency Range
OUTPUT
Voltage Distortion<1% (linear load) <5.5% (Non-Linear Load)
>0.99Power Factor
INPUT Phase
Voltage Range
10kVA - 600kVARatings (kVA/KW)
276-480V
3Ph+N+PE 380 / 400 / 415 V (Line-Line)
380 / 400 / 415 V (Line-Line Nominal)
Input Current Distortion <3%*
Voltage Regulation 1.50%
Standard Features :• Modular design convenient for field maintenance, upgradation and redundancy • High power density • Independent LCD• Isolated Air Flow• Flexibility / Scalability• Waveform Recording• Smart Sleep• Phantom Loading• Programmable Potential Free Contacts
Bypass & Monitoring Module
Power Module
Man-Machine Interface
3Ø Input - 3Ø Output
ALPHA RMS (RACK-MOUNTED SERIES)
10-600 kVA
Cabinet SizeWxDxH (mm)
485X697X398
485X751X575
485X697X575
485X751X1033
485X697X398
485X751X575
485X751X1033
600X900X1100
600X900X1600
600X900X2000
600X1100X1600
600X1100X2000
2000X1050X2000
600X1100X1600
600X1100X2000
2000X1050X2000
1300X1100X2000
20kVA/20KW
30kVA/30KW
60kVA/60KW
30kVA/30KW
45kVA/45KW
90kVA/90KW
120kVA/108KW
200kVA/180KW
150kVA/150KW
250kVA/250KW
500kVA/500KW
40kVA/40KW
180kVA/162KW
300kVA/270KW
600kVA/540KW
400kVA/400KW
500kVA/450KW
Maximum kVARating
ModuleRating
(kVA/KW)Model
RM020/10X
RM030/10X
RM040/10X
RM060/10X
RM030/15X
RM090/15X
RM045/15X
RM060/20
RM120/20
RM200/20
RM150/25X
RM250/25X
RM500/25X
RM180/30X
RM300/30X
RM600/30X
RM400/40X
RM500/50X
ModuleWeight(Kg.)
15.3
15.5
22
32
34
44
45
Module SizeWxDxH (mm)
436X590X85 (2U)
440X590X134 (3U)
460X790X134 (3U)
510X700X178 (4U)
CabinetWeight(Kg.)
42
51
55
85
42
55
85
105
145
179
165
220
660
165
220
660
900
10
20
10
10
10
20
2
3
3
3
4
6
6
6
10
2
6
6
MaximumNo.of
Modules
10/10
10/10
10/10
10/10
15/15
15/15
15/15
20/18
20/18
20/18
25/25
25/25
25/25
30/27
30/27
30/27
40/40
50/45
60kVA/54KW
ISOLATED AIR FLOW
The PCB Boards and Heat sinks are mounted on two different layers which ensures satisfactory performance of the UPS even in dusty environment.
CRITICAL WAVEFORM RECORDINGUPS can record the data of the critical parameters automatically when faults occurs. The recorded wave forms and data can be utilised for fault analysis later on.
Autometers Alliance Ltd
DisclaimerAutometers Alliance Ltd reserves the right to introduce changes and improvements made possible by advances in technology and functionality without prior intimation or justification up to the time of both parties endorsing this document with their signatures, or up to the time when the product is actually completed. This document is a 'Quick Reference' and does not mention all features of the equipment.
Corporate Office: C 63, Sector 57, Noida 201 307 (U.P.) India,
Tel.: +91 (0) 120-2583603, 2583545-46, E-mail: [email protected], www.autometers.com
Autometers Alliance Ltd., Noida