Page 1: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Two Minute Drill #10

Copyright 2005 Ted "Smitty" Smith

Page 2: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide.

Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 10 seconds. You may also left click on the slide to manually transition.

Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill

Good luck Remember to start the slide show to activate the

timer.

Copyright 2005 Ted "Smitty" Smith

Page 3: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

This drill is a mixture of calculations and code look up questions. You have seen many of them before. Focus on time. Try to find all the answers before the slide transitions.

Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then.

Click on the slide to proceed.

Copyright 2005 Ted "Smitty" Smith

Page 4: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Where handhold enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for ____________. Corosive atmospheres Special locations Wet locations None of the above

Page 5: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

wet locations      314.30(D)

Page 6: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

What is the minimum headroom of working space required above a motor control center? 10 feet 3 feet 6.5 feet 5 feet

Copyright 2005 Ted "Smitty" Smith

Page 7: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

6.5 ft 110.26(E)

Copyright 2005 Ted "Smitty" Smith

Page 8: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized service required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 100 A 110 A 125 A 150 A

Page 9: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

125 A               Article 220 Part III

Page 10: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

How thick must sealing compound be in a ½” seal off in a class I, div. 1 area? ½” 5/8” ¾” 1”

Copyright 2005 Ted "Smitty" Smith

Page 11: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

5/8 “ 501.15(C)(3)

Copyright 2005 Ted "Smitty" Smith

Page 12: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

The non-heating leads on heating cables must be a minimum of _______________ in length. 2 feet 3 feet 6 feet 7 feet

Copyright 2005 Ted "Smitty" Smith

Page 13: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

7 ft 424.34

Copyright 2005 Ted "Smitty" Smith

Page 14: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Each unit length of heating cable shall have a lead wire with a color code of ______________ if it is rated to operate at 208V. Yellow Blue Orange Red

Copyright 2005 Ted "Smitty" Smith

Page 15: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Blue 424.35

Copyright 2005 Ted "Smitty" Smith

Page 16: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

The requirement of “shall be listed” indicates that a piece of material or equipment must ______________. be accepted by an authority having jurisdiction be tested by a qualified person be listed in a publication that is produced by an

organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose.

Copyright 2005 Ted "Smitty" Smith

Page 17: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose.

Article 100

Copyright 2005 Ted "Smitty" Smith

Page 18: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Where submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit __________ conductor. Equipment grounding Bonding jumper Grounded conductor None of the above

Page 19: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Equipment grounding     250.112(M)

Page 20: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A single grounding electrode conductor can be used to connect multiple grounding electrodes. True False

Page 21: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True  250.64(F)

Page 22: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A single rod or pipe electrode shall have a resistance of _________ ohms or less to ground. 10 ohms 15 ohms 25 ohms 50 ohms

Page 23: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

25     250.56

Page 24: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________. Disconnecting means Switching means Thermal protection None of the above

Page 25: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Thermal Protection          410.73(E)(4)

Page 26: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors? Yes No

Page 27: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

NO   240.21(C)

Page 28: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system. Present Approved Required Inspected

Page 29: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Present     250.50

Page 30: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than ______________________ in size and shall be securely fastened in place. 25 cubic inches 50 cubic inches 75 cubic inches 100 cubic inches

Page 31: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

100 cubic inches       314.23(D)

Page 32: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Sheet metal boxes not over 100 cubic inches in size shall be made from steel not less than ______ inches thick. 1 inches .5 inches .0814 inches .0625 inches

Page 33: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

.0625 inches        314.40(B)

Page 34: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized main bonding jumper, copper, required if a conductor is used and the supply conductors consist of 4 parallel runs of 500 kcmil copper conductors? 1/0 AWG 3/0 AWG 250 kcmil 500 kcmil

Page 35: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

250 kcmil   250.28(C) and Table 8

500 x 4= 2000 kcmil. 12.5% of 2000 kcmil is 250 A minimum of 250 kcmil wire is needed.

Page 36: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The service entrance of a building may be located less than three feet from a window as long as the conductors are installed so that they___________ of the window. Run parallel to the vertical edge Run above the top level Run along the bottom leve None of the above

Page 37: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Run above the top level    230.9(A)Ex

Page 38: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the maximum sized duel element time delay fuse that can be used to provide branch circuit short circuit protection for a 40 hp, 208V, three-phase, induction motor, that has a nameplate full load current of 96.5 amperes? The motor is a design B motor with a marked service factor of 1.15. 100 A 150 A 200 A 225 A

Page 39: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

200A         430.52 Table and Exception

Page 40: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Sheet metals screws shall not be used to connect grounding conductors or _______________ to enclosures as applied to grounding requirements. Connection devices Neutral bus bars Mounting hardware None of the above

Page 41: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

connection devices   250.8

Page 42: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Which of the following best describes the definition of accessible as applied to wiring methods: Easy Do not have to leave ground to access Can be rendered accessible without

damaging the structure or finish No sweat

Copyright 2005 Ted "Smitty" Smith

Page 43: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Can be rendered accessible without damaging the structure or finish

Article 100

Copyright 2005 Ted "Smitty" Smith

Page 44: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized grounding electrode conductor required for a service that is supplied by (4) parallel runs of 500 kCMIL service entrance conductors? The conductors are copper and the grounding electrode conductor will also be copper. 3/0 AWG 300 kcmil 500 kcmil 1/0 AWG

Page 45: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

3/0  Table 250.66

Page 46: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized main bonding jumper that can be used for a service that is supplied by (3) parallel runs of 750 kcmil service entrance conductors? The service entrance conductors are copper. 1/0 AWG 2/0 AWG 300 kcmil 500 kcmil

Page 47: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

300 kcmil  250.28(D) and Table 8 for circular mills

Page 48: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized equipment grounding conductor that is required for a circuit that is protected by a 50 ampere overcurrent protective device if the ungrounded conductors are increased in size from a number 6 AWG, THHN to a number 2 AWG, THHN? All conductors are copper. 10 AWG 8 AWG 6 AWG 4 AWG

Page 49: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

4 AWG  250.22(B) and Table 8 for circular mills

Page 50: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A junction box that is 18" x 18" x 6" that has two 1 1/2" EMT conduits entering and exiting through concentric knockouts and the conduits contain conductor that are number 4 AWG, THHN must be equipped with grounding bushings, threaded bosses or bonding lock nuts to accommodate the bonding and continuity requirements of article 250 of the NEC. The circuits in the junction box are operating at 208 volts, three-phase. True False

Page 51: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

False  250.96 and 250.97 would only be required if circuits were operating at more than 250 volts to ground.

Page 52: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The earth shall not be considered as an effective ground fault current path. True False

Page 53: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True                               250.4(A)(5)

Page 54: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Only those conduit bodies that are durably and visibly marked by the manufacturer with __________ shall be permitted to contain splices, taps, or devices. Their size Their volume allowance Their dimensions Their manufacturer

Page 55: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

their volume allowance    314.16(C)(2)

Page 56: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

An emergency system shall be suitable for the ___________________ available fault current at its terminals. Minimum Maximum Listed rated

Page 57: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Maximum   700.5

Page 58: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

When grounding the outer conductive shield of a coaxial cable the maximum sized ground required shall be ______________ AWG copper 2 AWG 4 AWG 6 AWG 8 AWG

Page 59: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

6    820.100(A)(3)

Page 60: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

If a system is a three phase, three wire Delta configured system, operating at 230 Volts, is it required to be a grounded system? Yes No

Page 61: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

No 250.20(B)

Page 62: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? 8000 VA 8800 VA 9600 VA 10000 VA

Page 63: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

8800 VA   Table 220.55 Note 1

Page 64: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum number of 15 ampere lighting circuits required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 1 2 3 5

Page 65: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

3               4500 VA of lighting load/120= 37.5A

Page 66: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Raceways that carry service-conductors that are embedded in masonry shall be __________. Sealed Arranged to drain Weatherproof None of the above

Page 67: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Arranged to drain     230.53

Page 68: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized grounding electrode conductor that can be used if the service entrance conductors are 250 kCMIL copper? 1 AWG 2 AWG 3 AWG 3/0 AWG

Page 69: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

2 AWG     T250.66

Page 70: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A cable tray may serve to carry service-entrance conductors along with other conductors as long as there is a ________. Constraint Listed device Approved means None of the above

Page 71: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

None of the above. The actual answer is: Barrier    

230.44Ex

Page 72: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service. True False

Page 73: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True 230.71(A)

Page 74: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet. 1 feet 2 feet 3 feet 8 feet

Page 75: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

2 feet       230.54(C) Ex

Page 76: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel. 250.122, 250.122(F) 110.14(C), 130.4 220.55, 310.16 None of the above

Page 77: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

250.122, 250.122(F)        215.2(A)

Page 78: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________. Phase Color code System supply

Page 79: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

System                          210.5(C)

Page 80: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Each of the slides will now be repeated. They are not timed in this segment. To

change a slide, click on the side with your left mouse button.

Be sure to physically look up the answers in your code book to improve your look up speed and skill.

Copyright 2005 Ted "Smitty" Smith

Page 81: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Where handhold enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for ____________. Corosive atmospheres Special locations Wet locations None of the above

Page 82: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

wet locations      314.30(D)

Page 83: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

What is the minimum headroom of working space required above a motor control center? 10 feet 3 feet 6.5 feet 5 feet

Copyright 2005 Ted "Smitty" Smith

Page 84: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

6.5 ft 110.26(E)

Copyright 2005 Ted "Smitty" Smith

Page 85: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized service required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 100 A 110 A 125 A 150 A

Page 86: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

125 A               Article 220 Part III

Page 87: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

How thick must sealing compound be in a ½” seal off in a class I, div. 1 area? ½” 5/8” ¾” 1”

Copyright 2005 Ted "Smitty" Smith

Page 88: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

5/8 “ 501.15(C)(3)

Copyright 2005 Ted "Smitty" Smith

Page 89: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

The non-heating leads on heating cables must be a minimum of _______________ in length. 2 feet 3 feet 6 feet 7 feet

Copyright 2005 Ted "Smitty" Smith

Page 90: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

7 ft 424.34

Copyright 2005 Ted "Smitty" Smith

Page 91: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Each unit length of heating cable shall have a lead wire with a color code of ______________ if it is rated to operate at 208V. Yellow Blue Orange Red

Copyright 2005 Ted "Smitty" Smith

Page 92: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Blue 424.35

Copyright 2005 Ted "Smitty" Smith

Page 93: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

The requirement of “shall be listed” indicates that a piece of material or equipment must ______________. be accepted by an authority having jurisdiction be tested by a qualified person be listed in a publication that is produced by an

organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose.

Copyright 2005 Ted "Smitty" Smith

Page 94: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose.

Article 100

Copyright 2005 Ted "Smitty" Smith

Page 95: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Where submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit __________ conductor. Equipment grounding Bonding jumper Grounded conductor None of the above

Page 96: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Equipment grounding     250.112(M)

Page 97: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A single grounding electrode conductor can be used to connect multiple grounding electrodes. True False

Page 98: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True  250.64(F)

Page 99: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A single rod or pipe electrode shall have a resistance of _________ ohms or less to ground. 10 ohms 15 ohms 25 ohms 50 ohms

Page 100: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

25     250.56

Page 101: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________. Disconnecting means Switching means Thermal protection None of the above

Page 102: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Thermal Protection          410.73(E)(4)

Page 103: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors? Yes No

Page 104: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

NO   240.21(C)

Page 105: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system. Present Approved Required Inspected

Page 106: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Present     250.50

Page 107: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than ______________________ in size and shall be securely fastened in place. 25 cubic inches 50 cubic inches 75 cubic inches 100 cubic inches

Page 108: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

100 cubic inches       314.23(D)

Page 109: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Sheet metal boxes not over 100 cubic inches in size shall be made from steel not less than ______ inches thick. 1 inches .5 inches .0814 inches .0625 inches

Page 110: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

.0625 inches        314.40(B)

Page 111: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized main bonding jumper, copper, required if a conductor is used and the supply conductors consist of 4 parallel runs of 500 kcmil copper conductors? 1/0 AWG 3/0 AWG 250 kcmil 500 kcmil

Page 112: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

250 kcmil   250.28(C) and Table 8

500 x 4= 2000 kcmil. 12.5% of 2000 kcmil is 250 A minimum of 250 kcmil wire is needed.

Page 113: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The service entrance of a building may be located less than three feet from a window as long as the conductors are installed so that they___________ of the window. Run parallel to the vertical edge Run above the top level Run along the bottom leve None of the above

Page 114: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Run above the top level    230.9(A)Ex

Page 115: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the maximum sized duel element time delay fuse that can be used to provide branch circuit short circuit protection for a 40 hp, 208V, three-phase, induction motor, that has a nameplate full load current of 96.5 amperes? The motor is a design B motor with a marked service factor of 1.15. 100 A 150 A 200 A 225 A

Page 116: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

200A         430.52 Table and Exception

Page 117: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Sheet metals screws shall not be used to connect grounding conductors or _______________ to enclosures as applied to grounding requirements. Connection devices Neutral bus bars Mounting hardware None of the above

Page 118: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

connection devices   250.8

Page 119: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Which of the following best describes the definition of accessible as applied to wiring methods: Easy Do not have to leave ground to access Can be rendered accessible without

damaging the structure or finish No sweat

Copyright 2005 Ted "Smitty" Smith

Page 120: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Can be rendered accessible without damaging the structure or finish

Article 100

Copyright 2005 Ted "Smitty" Smith

Page 121: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized grounding electrode conductor required for a service that is supplied by (4) parallel runs of 500 kCMIL service entrance conductors? The conductors are copper and the grounding electrode conductor will also be copper. 3/0 AWG 300 kcmil 500 kcmil 1/0 AWG

Page 122: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

3/0  Table 250.66

Page 123: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized main bonding jumper that can be used for a service that is supplied by (3) parallel runs of 750 kcmil service entrance conductors? The service entrance conductors are copper. 1/0 AWG 2/0 AWG 300 kcmil 500 kcmil

Page 124: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

300 kcmil  250.28(D) and Table 8 for circular mills

Page 125: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized equipment grounding conductor that is required for a circuit that is protected by a 50 ampere overcurrent protective device if the ungrounded conductors are increased in size from a number 6 AWG, THHN to a number 2 AWG, THHN? All conductors are copper. 10 AWG 8 AWG 6 AWG 4 AWG

Page 126: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

4 AWG  250.22(B) and Table 8 for circular mills

Page 127: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A junction box that is 18" x 18" x 6" that has two 1 1/2" EMT conduits entering and exiting through concentric knockouts and the conduits contain conductor that are number 4 AWG, THHN must be equipped with grounding bushings, threaded bosses or bonding lock nuts to accommodate the bonding and continuity requirements of article 250 of the NEC. The circuits in the junction box are operating at 208 volts, three-phase. True False

Page 128: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

False  250.96 and 250.97 would only be required if circuits were operating at more than 250 volts to ground.

Page 129: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The earth shall not be considered as an effective ground fault current path. True False

Page 130: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True                               250.4(A)(5)

Page 131: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Only those conduit bodies that are durably and visibly marked by the manufacturer with __________ shall be permitted to contain splices, taps, or devices. Their size Their volume allowance Their dimensions Their manufacturer

Page 132: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

their volume allowance    314.16(C)(2)

Page 133: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

An emergency system shall be suitable for the ___________________ available fault current at its terminals. Minimum Maximum Listed rated

Page 134: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Maximum   700.5

Page 135: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

When grounding the outer conductive shield of a coaxial cable the maximum sized ground required shall be ______________ AWG copper 2 AWG 4 AWG 6 AWG 8 AWG

Page 136: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

6    820.100(A)(3)

Page 137: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

If a system is a three phase, three wire Delta configured system, operating at 230 Volts, is it required to be a grounded system? Yes No

Page 138: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

No 250.20(B)

Page 139: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? 8000 VA 8800 VA 9600 VA 10000 VA

Page 140: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

8800 VA   Table 220.55 Note 1

Page 141: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum number of 15 ampere lighting circuits required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 1 2 3 5

Page 142: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

3               4500 VA of lighting load/120= 37.5A

Page 143: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Raceways that carry service-conductors that are embedded in masonry shall be __________. Sealed Arranged to drain Weatherproof None of the above

Page 144: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Arranged to drain     230.53

Page 145: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

What is the minimum sized grounding electrode conductor that can be used if the service entrance conductors are 250 kCMIL copper? 1 AWG 2 AWG 3 AWG 3/0 AWG

Page 146: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

2 AWG     T250.66

Page 147: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

A cable tray may serve to carry service-entrance conductors along with other conductors as long as there is a ________. Constraint Listed device Approved means None of the above

Page 148: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

None of the above. The actual answer is: Barrier    

230.44Ex

Page 149: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service. True False

Page 150: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

True 230.71(A)

Page 151: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet. 1 feet 2 feet 3 feet 8 feet

Page 152: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

2 feet       230.54(C) Ex

Page 153: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel. 250.122, 250.122(F) 110.14(C), 130.4 220.55, 310.16 None of the above

Page 154: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

250.122, 250.122(F)        215.2(A)

Page 155: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________. Phase Color code System supply

Page 156: Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith

Copyright 2005 Ted "Smitty" Smith

System                          210.5(C)