Smitty’s Speed Drills2008 Code Drills

Health Care Facilities

(C) Copyright 2008 Ted "Smitty" Smith 1

Page 2: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

InstructionsClick on the slide show ICON in the lower left hand

corner of this screen to start the slide show. A question will appear and stay on the screen for 2 minutes. The

question will then be replaced with the correct answer and code reference. This process will repeat until you reach a slide with a stop sign. You can then click on the slides and the questions and answers will be repeated without the timer so you can look up the answers or take notes.

Do not worry about writing down the answers until after the timed portion of the program.

Concentrate on finding the answer and improving your speed using the NEC. This drill is focused on changes to the 2008 NEC.

(C) Copyright 2008 Ted "Smitty" Smith 2

Page 3: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment.

(C) Copyright 2008 Ted "Smitty" Smith 3

Page 4: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Entirely independent 517.30(C)(1)

(C) Copyright 2008 Ted "Smitty" Smith 4

Page 5: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly.

(C) Copyright 2008 Ted "Smitty" Smith

5

Page 6: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• An effective ground-fault current path 517.13(A)

(C) Copyright 2008 Ted "Smitty" Smith 6

Page 7: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason.

(C) Copyright 2008 Ted "Smitty" Smith 7

Page 8: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Limited amount 517.25

(C) Copyright 2008 Ted "Smitty" Smith 8

Page 9: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility?

• Generator located on the premises• Battery system• A second external utility service, separate from the

main external utility provided service• An external utility service when the normal source of

power consists of a generating unit located on premises.

(C) Copyright 2008 Ted "Smitty" Smith 9

Page 10: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• A second external utility service 517.35(A)

• An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises.

(C) Copyright 2008 Ted "Smitty" Smith 10

Page 11: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________.

(C) Copyright 2008 Ted "Smitty" Smith 11

Page 12: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• X-ray control

• 517.72(B)

(C) Copyright 2008 Ted "Smitty" Smith 12

Page 13: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source.

(C) Copyright 2008 Ted "Smitty" Smith 13

Page 14: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Delayed automatic 517.43(A)

(C) Copyright 2008 Ted "Smitty" Smith 14

Page 15: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation.

(C) Copyright 2008 Ted "Smitty" Smith 15

Page 16: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Equipment 517.30(B)(3)

(C) Copyright 2008 Ted "Smitty" Smith 16

Page 17: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment.

(C) Copyright 2008 Ted "Smitty" Smith 17

Page 18: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Critical care 517.19(F)

(C) Copyright 2008 Ted "Smitty" Smith 18

Page 19: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor.

(C) Copyright 2008 Ted "Smitty" Smith 19

Page 20: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• 100 517.13(B)

(C) Copyright 2008 Ted "Smitty" Smith 20

Page 21: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current.

(C) Copyright 2008 Ted "Smitty" Smith 21

Page 22: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Line isolation monitor 517.160(B)

(C) Copyright 2008 Ted "Smitty" Smith 22

Page 23: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater.

(C) Copyright 2008 Ted "Smitty" Smith 23

Page 24: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• 50 percent 517.72(A)

(C) Copyright 2008 Ted "Smitty" Smith 24

Page 25: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 25

Page 26: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Life safety 517.32(A)

(C) Copyright 2008 Ted "Smitty" Smith 26

Page 27: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Nurse call systems shall be provided power from the __________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 27

Page 28: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Critical branch 517.33(A)(5)

(C) Copyright 2008 Ted "Smitty" Smith 28

Page 29: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Each patient bed location shall be provided with a minimum of __________ receptacles.

(C) Copyright 2008 Ted "Smitty" Smith 29

Page 30: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Four 517.18(B)

(C) Copyright 2008 Ted "Smitty" Smith 30

Page 31: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG.

(C) Copyright 2008 Ted "Smitty" Smith 31

Page 32: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• 10 517.14

(C) Copyright 2008 Ted "Smitty" Smith 32

Page 33: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

End of Drill

• This is the end of the timed portion of the drill.

• You can now click on each slide and take your time reviewing the questions and answers.

(C) Copyright 2008 Ted "Smitty" Smith 33

Page 34: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment.

(C) Copyright 2008 Ted "Smitty" Smith 34

Page 35: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Entirely independent 517.30(C)(1)

(C) Copyright 2008 Ted "Smitty" Smith 35

Page 36: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly.

(C) Copyright 2008 Ted "Smitty" Smith

36

Page 37: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• An effective ground-fault current path 517.13(A)

(C) Copyright 2008 Ted "Smitty" Smith 37

Page 38: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason.

(C) Copyright 2008 Ted "Smitty" Smith 38

Page 39: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Limited amount 517.25

(C) Copyright 2008 Ted "Smitty" Smith 39

Page 40: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility?

• Generator located on the premises• Battery system• A second external utility service, separate from the

main external utility provided service• An external utility service when the normal source of

power consists of a generating unit located on premises.

(C) Copyright 2008 Ted "Smitty" Smith 40

Page 41: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• A second external utility service 517.35(A)

• An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises.

(C) Copyright 2008 Ted "Smitty" Smith 41

Page 42: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________.

(C) Copyright 2008 Ted "Smitty" Smith 42

Page 43: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• X-ray control

• 517.72(B)

(C) Copyright 2008 Ted "Smitty" Smith 43

Page 44: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source.

(C) Copyright 2008 Ted "Smitty" Smith 44

Page 45: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Delayed automatic 517.43(A)

(C) Copyright 2008 Ted "Smitty" Smith 45

Page 46: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation.

(C) Copyright 2008 Ted "Smitty" Smith 46

Page 47: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Equipment 517.30(B)(3)

(C) Copyright 2008 Ted "Smitty" Smith 47

Page 48: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment.

(C) Copyright 2008 Ted "Smitty" Smith 48

Page 49: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Critical care 517.19(F)

(C) Copyright 2008 Ted "Smitty" Smith 49

Page 50: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor.

(C) Copyright 2008 Ted "Smitty" Smith 50

Page 51: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• 100 517.13(B)

(C) Copyright 2008 Ted "Smitty" Smith 51

Page 52: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current.

(C) Copyright 2008 Ted "Smitty" Smith 52

Page 53: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Line isolation monitor 517.160(B)

(C) Copyright 2008 Ted "Smitty" Smith 53

Page 54: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater.

(C) Copyright 2008 Ted "Smitty" Smith 54

Page 55: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• 50 percent 517.72(A)

(C) Copyright 2008 Ted "Smitty" Smith 55

Page 56: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 56

Page 57: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Life safety 517.32(A)

(C) Copyright 2008 Ted "Smitty" Smith 57

Page 58: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Nurse call systems shall be provided power from the __________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 58

Page 59: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Critical branch 517.33(A)(5)

(C) Copyright 2008 Ted "Smitty" Smith 59

Page 60: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Each patient bed location shall be provided with a minimum of __________ receptacles.

(C) Copyright 2008 Ted "Smitty" Smith 60

Page 61: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• Four 517.18(B)

(C) Copyright 2008 Ted "Smitty" Smith 61

Page 62: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG.

(C) Copyright 2008 Ted "Smitty" Smith 62

Page 63: Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1

• 10 517.14