2
Ratings Damper Maximum System Maximum System Width Pressure Velocity 12" (305) 5.0 in. wg (1.2 kPa) 3000 fpm (15.2 m/s) 24" (610) 4.0 in. wg (1.0 kPa) 3000 fpm (15.2 m/s) 36" (914) 3.0 in. wg (0.8 kPa) 2500 fpm (12.7 m/s) 48" (1219) 2.5 in. wg (0.6 kPa) 2000 fpm (10.2 m/s) Leakage (with seals): 8.0 cfm/ft 2 @ 4 in. wg (0.04m 3 /s/ m 2 @ 1.00 kPa) 4.0 cfm/ft 2 @ 1 in. wg (0.02m 3 /s/ m 2 @ 0.25 kPa) Temperature: –25°F to 180°F (–32°C to +83°C) model CD-41, CD-42 control damper tripleV blade Control Dampers CD41, CD42 (1/2) June 2013 Application CD41 and CD42 control dampers employ tripleV blades and a rugged hat channel frame for automatic air control and manual balancing in medium pressure and velocity applications. Standard Construction Frame: 5" × 1" (127 × 25) galvanized steel hat channel with interlocking corner gusset. Equivalent to 13 gauge (2.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high. Blades: 6" × 16 gauge (152 × 1.5) galvanized steel — tripleV. Parallel (model CD41) or opposed (model CD42) action. Axles: 1 /2" (13) diameter plated steel hex. Linkage: Concealed in frame. Bearings: Synthetic Control Shaft: 1 /2" × 6" (13 × 152) round drive axle with outboard shaft support bracket and bearing supplied on all single section dampers for field installation. Factory installed jackshaft supplied with all multiple section dampers: 1 /2" (13) dia. for W>48" (1219) or H>72" (1829), 3 /4" (19) dia. for W >96" (2438). Minimum Size: Model CD41 (one blade): 5" × 5" (127 × 127) Model CD41 and CD42 (two blades): 5" × 10" (127 × 254) Maximum Size: Single section: 48" × 72" (1219 × 1829) Multiple sections: Unlimited Options o Factory installed actuators: o Manual locking quadrant (supplied loose) o 24 VAC  o 120 VAC  o 230 VAC o Pneumatic  o Modulating o External mount (requires sleeve or sideplate option) o Internal mount (requires jackshafting) o Factory installed sleeve. o Factory installed side plate. Gauge: o 20 (1.0) o 16 (1.6) Length: o 16" (406) o 24" (610) o Other_____ o Transitions (sleeve required): o Flanged o Round o Oval o Duct connections: o DM25 o DM35 o S & Drive o Flanged frame: o One side  o Both sides o Low leakage seals: PVC blade edge and flexible stainless steel jamb. o PI50 – Dual position indicator switch package. o Actuator/Quadrant standoff bracket — accommodates up to 3" (76) thick insulated duct. o Stainless steel oilite sleevetype bearings. o Type304 stainless steel construction. o Jackshafting (required with internal mounted actuators and standard on all multiple section dampers). o Vertical mounted blades. o Face and bypass assemblies: o Model MDFBR  o Model MDFBH  o Model MDFBV Air Performance Pottorff certifies that the model CD41 and CD42 shown herein is licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. 6" (152) Std. Model CD-42 (standard) *Damper dimensions furnished approximately 1/4" (6) undersize. (Drive axle supplied loose for field installation) POTTORFF ® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters. 12" (305) Std. + + 12" (305) Std. + + Sleeve (optional) + Damper dimensions furnished approximately 1/4" (6) undersize (sleeve thickness not included. Sideplate (optional) CD-41 CD-42 1-1/2" (38) Std. Flanged Frame

tripleV blade - Pottorff cd-42.pdf · Model CD41 and CD42 (two blades): 5" × 10" (127 × 254) Maximum Size: Single section: 48" × 72" (1219 × 1829) Multiple sections: Unlimited

Embed Size (px)

Citation preview

Page 1: tripleV blade - Pottorff cd-42.pdf · Model CD41 and CD42 (two blades): 5" × 10" (127 × 254) Maximum Size: Single section: 48" × 72" (1219 × 1829) Multiple sections: Unlimited

RatingsDamper Maximum System Maximum SystemWidth Pressure Velocity

12" (305) 5.0 in. wg (1.2 kPa) 3000 fpm (15.2 m/s)24" (610) 4.0 in. wg (1.0 kPa) 3000 fpm (15.2 m/s)36" (914) 3.0 in. wg (0.8 kPa) 2500 fpm (12.7 m/s)48" (1219) 2.5 in. wg (0.6 kPa) 2000 fpm (10.2 m/s)

Leakage (with seals): 8.0 cfm/ft2 @ 4 in. wg (0.04m3/s/ m2 @ 1.00 kPa)4.0 cfm/ft2 @ 1 in. wg (0.02m3/s/ m2 @ 0.25 kPa)

Temperature: –25°F to 180°F (–32°C to +83°C)

model CD-41, CD-42control damper

triple­V blade

Con

trol D

ampe

rs CD41

, CD42

(1/2

) Jun

e 20

13

ApplicationCD­41 and CD­42 control dampers employ triple­V blades anda rugged hat channel frame for automatic air control and manualbalancing in medium pressure and velocity applications.

Standard ConstructionFrame: 5" × 1" (127 × 25) galvanized steel hat channel with

interlocking corner gusset. Equivalent to 13 gauge (2.4)channel frame. Low profile head and sill are used on sizesless than 13" (330) high.

Blades: 6" × 16 gauge (152 × 1.5) galvanized steel — triple­V.Parallel (model CD­41) or opposed (model CD­42) action.

Axles: 1/2" (13) diameter plated steel hex.

Linkage: Concealed in frame.

Bearings: Synthetic

Control Shaft: 1/2" × 6" (13 × 152) round drive axle with outboardshaft support bracket and bearing supplied on all singlesection dampers for field installation. Factory installedjackshaft supplied with all multiple section dampers: 1/2" (13)dia. for W>48" (1219) or H>72" (1829), 3/4" (19) dia. for W >96"(2438).

Minimum Size: Model CD­41 (one blade): 5" × 5" (127 × 127)Model CD­41 and CD­42 (two blades): 5" × 10"(127 × 254)

Maximum Size: Single section: 48" × 72" (1219 × 1829)Multiple sections: Unlimited

Optionso Factory installed actuators:

o Manual locking quadrant (supplied loose)o 24 VAC  o 120 VAC  o 230 VAC

o Pneumatic  o Modulatingo External mount (requires sleeve or sideplate option)o Internal mount (requires jackshafting)

o Factory installed sleeve. o Factory installed side plate.Gauge: o 20 (1.0) o 16 (1.6)Length: o 16" (406) o 24" (610) o Other_____

o Transitions (sleeve required): o Flangedo Round o Ovalo Duct connections: o DM­25 o DM­35 o S & Drive

o Flanged frame: o One side  o Both sides

o Low leakage seals: PVC blade edge and flexible stainless steeljamb.

o PI­50 – Dual position indicator switch package.

o Actuator/Quadrant standoff bracket — accommodates up to 3"(76) thick insulated duct.

o Stainless steel oilite sleeve­type bearings.

o Type­304 stainless steel construction.

o Jackshafting (required with internal mounted actuators andstandard on all multiple section dampers).

o Vertical mounted blades.

o Face and by­pass assemblies:o Model MDFBR  o Model MDFBH  o Model MDFBV

Air PerformancePottorff certifies that the model CD­41 and CD­42shown herein is licensed to bear the AMCA seal.The ratings shown are based on tests and proceduresperformed in accordance with AMCA publication 511and comply with the requirements of the AMCACertified Ratings Program. The AMCA CertifiedRatings Seal applies to air performance ratings only.

6" (152)Std.

Model CD-42 (standard)*Damper dimensions furnished

approximately 1/4" (6) undersize.(Drive axle supplied loose for field

installation)

POTTORFF® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com

Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters.

12" (305)Std.

+

+

12" (305)Std.

+

+

Sleeve (optional)+Damper dimensions furnished

approximately 1/4" (6) undersize(sleeve thickness not included.

Sideplate (optional)

CD-41 CD-42

1-1/2" (38)Std.

Flanged Frame

Page 2: tripleV blade - Pottorff cd-42.pdf · Model CD41 and CD42 (two blades): 5" × 10" (127 × 254) Maximum Size: Single section: 48" × 72" (1219 × 1829) Multiple sections: Unlimited

Con

trol D

ampe

rs CD41

, CD42

(2/2

) Jun

e 20

13

5D 6D

5D

Air PerformancePottorff certifies that the model CD­41and CD­42 shown herein is licensedto bear the AMCA seal. The ratingsshown are based on tests andprocedures performed in accordancewith AMCA publication 511 andcomply with the requirements of theAMCA Certified Ratings Program.The AMCA Certified Ratings Sealapplies to air performance ratingsonly.

Pressure drop testing was performedin accordance with AMCA Standard500­D using the three configurationsshown. All data has been corrected torepresent air density of 0.075 lb/ft.Actual pressure drop in any ductedHVAC system is a combination ofmany elements. This information,along with analysis of other systeminfluences, should be used toestimate actual pressure losses for adamper installed in a given HVACsystem.

Typical Damper Dimensional Details

Airflow Performance DataPressure Loss vs. Velocity

Figure 5.3 — Ducted Inlet and Outlet Figure 5.2 — Ducted Inlet Figure 5.5 Plenum Mount

Ducted Inlet and OutletAMCA Figure 5.3 Illustrates a fully ducteddamper. This configuration represents thelowest pressure drop of the three testconfigurations because entrance and exitlosses are minimized by straight duct runsupstream and downstream of the damper.

Ducted InletAMCA Figure 5.2 Illustrates a ducteddamper exhausting air into an open area.This configuration has a lower pressuredrop than Figure 5.5 because entrancelosses are minimized by a straight duct runupstream of the damper.

Plenum MountAMCA Figure 5.5 Illustrates a plenummounted damper. This configuration hasthe highest pressure drop because ofextremely high entrance and exit lossesdue to the sudden changes of area in thesystem.

POTTORFF® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com

Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters.

1"(25)

5"(127)

3/4"(19)

J

H1*

H*

W*

W*W1*

H1*

H*

W*

H* Multi­Section

Vertical Bladed

Note: J = 2" (51) for H < 8" (203)J = 33/8" (86) for H ≥ 8" (203)

Dampers are designed to be self­supporting in the maximum single section size. When dampersare installed in multiple section assemblies, bracing may be required to support the weight of thedampers and to ensure structural integrity against system pressures. It is recommended thatmultiple sections be appropriately braced. In horizontal installations, it is recommended thatsuitable supports be installed every 8 feet of damper width. Dampers installed in vertical multipleassemblies and/or higher system pressures, may require additional bracing.