Upload
abhishek-srivastava
View
320
Download
50
Tags:
Embed Size (px)
DESCRIPTION
Tp48300b-n16b2 Tp48600b-n16b2 User Manual
Citation preview
TP48300B-N16B2 & TP48600B-N16B2 V300R001C05
User Manual
Issue 01
Date 2012-02-20
HUAWEI TECHNOLOGIES CO., LTD.
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
i
Copyright © Huawei Technologies Co., Ltd. 2012. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: http://www.huawei.com
Email: [email protected]
TP48300B-N16B2 & TP48600B-N16B2
User Manual About This Document
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
ii
About This Document
Purpose
This document describes the TP48300B-N16B2 & TP48600B-N16B2 in terms of features,
installation, commissioning, maintenance, and monitoring module operations.
Intended Audience
This document is intended for:
Sales engineers
Technical support personnel
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Alerts you to a high risk hazard that could, if not avoided,
result in serious injury or death.
Alerts you to a medium or low risk hazard that could, if not
avoided, result in moderate or minor injury.
Alerts you to a potentially hazardous situation that could, if not
avoided, result in equipment damage, data loss, performance
deterioration, or unanticipated results.
Provides a tip that may help you solve a problem or save time.
Provides additional information to emphasize or supplement
important points in the main text.
TP48300B-N16B2 & TP48600B-N16B2
User Manual About This Document
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
iii
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 01 (2012-02-20)
This issue is used for first office application (FOA).
TP48300B-N16B2 & TP48600B-N16B2
User Manual Contents
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
iv
Contents
About This Document .................................................................................................................... ii
1 Overview ......................................................................................................................................... 1
1.1 Designation Explanation .................................................................................................................................. 1
1.2 Typical Networking .......................................................................................................................................... 1
1.3 Configuration ................................................................................................................................................... 2
1.4 Features ............................................................................................................................................................ 5
1.5 Working Principles ........................................................................................................................................... 5
2 Component Description ............................................................................................................... 7
2.1 Cabinet ............................................................................................................................................................. 7
2.2 Rectifier ............................................................................................................................................................ 8
2.2.1 Appearance .............................................................................................................................................. 8
2.2.2 Panel........................................................................................................................................................ 8
2.3 Monitoring System ........................................................................................................................................... 9
3 Safety Precautions ....................................................................................................................... 16
3.1 Overview ........................................................................................................................................................ 16
3.2 Local Safety Regulations ............................................................................................................................... 16
3.3 Grounding Requirements ............................................................................................................................... 16
3.4 Human Safety ................................................................................................................................................. 17
3.5 Equipment Safety ........................................................................................................................................... 17
3.6 Electrical Safety ............................................................................................................................................. 17
4 Installation and Commissioning.............................................................................................. 20
5 System Maintenance................................................................................................................... 21
5.1 Routine Maintenance...................................................................................................................................... 21
5.2 Troubleshooting .............................................................................................................................................. 22
5.2.1 Troubleshooting Common faults ........................................................................................................... 22
5.2.2 Troubleshooting Components ............................................................................................................... 29
5.3 Component Replacment ................................................................................................................................. 32
5.4 Querying Alarms ............................................................................................................................................ 36
A Appendix ..................................................................................................................................... 38
A.1 Technical Specifications ................................................................................................................................ 38
TP48300B-N16B2 & TP48600B-N16B2
User Manual Contents
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
v
A.2 LCD Menu..................................................................................................................................................... 41
B Acronyms and Abbreviations .................................................................................................. 46
TP48300B-N16B2 & TP48600B-N16B2
User Manual 1 Overview
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
1
1 Overview
1.1 Designation Explanation
Figure 1-1 shows the definition of the product name TP48300B-N16B2 & TP48600B-N16B2.
Figure 1-1 Definition of the product name
1.2 Typical Networking
The TP48300B-N16B2 & TP48600B-N16B2 is installed on the scenarios. It supplies power
to the -48 V DC communication equipments. The TP48300B-N16B2 & TP48600B-N16B2
TP48300B-N16B2 & TP48600B-N16B2
User Manual 1 Overview
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
2
power system, AC power supply, ATS, storage batteries, and related devices constitute the site
power solution. Figure 1-2 shows the application of the TP48300B-N16B2 &
TP48600B-N16B2 power system in the typical site power solution.
Figure 1-2 TP48300B-N16B2 & TP48600B-N16B2 in the typical site power solution
1.3 Configuration
The TP48300B-N16B2 uses 50 A rectifiers and outputs a maximum of 300 A current. The
TP48600B-N16B2 uses 50 A rectifiers and outputs a maximum of 600 A current.
Figure 1-3 shows the TP48300B-N16B2 configuration. Figure 1-4 shows the
TP48300B-N16B2 configuration.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 1 Overview
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
3
Figure 1-3 TP48300B-N16B2 cabinet interior
(1) Positive direct current(DC)
output busbar
(2) Battery fuse (3) Load low voltage disconnection
(LLVD) route fuse
(4) Battery low voltage disconnect
(BLVD) circuit breaker
(5) Power supply unit
(PSU)
(6) LLVD circuit breaker
(7) Power monitor unit
(PMU)
(8) Surge protection
device (SPD)
(9) Alternating current (AC)
input circuit breaker
TP48300B-N16B2 & TP48600B-N16B2
User Manual 1 Overview
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
4
Figure 1-4 TP48600B-N16B2 cabinet interior
(1) Positive direct current(DC)
output busbar
(2) Battery fuse (3) Load low voltage disconnection
(LLVD) route fuse
(4) Battery low voltage disconnect
(BLVD) circuit breaker
(5) Power supply unit
(PSU)
(6) LLVD circuit breaker
(7) Power monitor unit
(PMU)
(8) Surge protection device
(SPD)
(9) Alternating current (AC)
input circuit breaker
TP48300B-N16B2 & TP48600B-N16B2
User Manual 1 Overview
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
5
1.4 Features Easy PSU Installation
The PSU is hot-swappable, which simplifies installation and reduces the maintenance time
and operational expenditure (OPEX).
Intelligent PSU Hibernation
Based on the actual load power, the TP48300B-N16B2 & TP48600B-N16B2 automatically
enables one or more PSUs to enter the hibernation mode.
Network Management over the NetEco
The TP48300B-N16B2 & TP48600B-N16B2 perform comprehensive power management and
battery management functions. The power monitoring unit (PMU) communicates with the
PSU over RS485 protocol, with HUAWEI communications equipment over a COM port, or
with the NetEco over an SNMP module.
The NetEco is a new-type intelligent element management system (EMS) developed by
Huawei. It works in client/server mode, which allows you to perform operations on the client
if you successfully log in to the server from the client.
Wide Range of AC Input Voltages
The AC input voltage of the TP48300B-N16B2 & TP48600B-N16B2 ranges from 90 V AC to
290 V AC phase voltage.
1.5 Working Principles
The TP48300B-N16B2 & TP48600B-N16B2 working principles are described as follows:
The TP48300B-N16B2 & TP48600B-N16B2 is energized by three- phase four-line mode
(Ll, L2, L3, N).
Rectifiers convert AC power into –48 V DC power.
The direct currents (DCs) generated by rectifiers converge on a busbar and then divide
into multiple routes to power loads.
The PMU monitors operating parameters of the TP48300B-N16B2 & TP48600B-N16B2
in real time, analyzes the operating status, and generates alarms when necessary.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 1 Overview
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
6
Figure 1-5 TP48300B-N16B2 Conceptual Diagram
Figure 1-6 TP48600B-N16B2 Conceptual Diagram
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
7
2 Component Description
2.1 Cabinet
Dimensions (H x W x D) of the TP48300B-N16B2 & TP48600B-N16B2 cabinet are 1600
mm x 600 mm x 400 mm (62.99 in. x 23.62 in. x 15.75 in.). The protection level of the
cabinet is IP20. The cabinet supports the ground installation and front maintenance. Figure
2-1 shows the TP48300B-N16B2 & TP48600B-N16B2 cabinet.
Figure 2-1 TP48300B-N16B2 & TP48600B-N16B2 cabinet
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
8
2.2 Rectifier
2.2.1 Appearance
The rectifier converts the AC input power into stable –48 V DC power.
Figure 2-2 shows the rectifier.
Figure 2-2 Rectifier
2.2.2 Panel
The rectifier panel provides the run indicator, alarm indicator, and fault indicator.Figure 2-3
shows the rectifier panel.
Figure 2-3 Rectifier panel
(1) Run indicator (2) Alarm indicator (3) Fault indicator
Table 2-1 Indicator description
Indicator Color Abnormal Status
Exception Causes Suggestion
Run
indicator
Green Off No AC input exists Check that the AC input
voltage is normal.
The rectifier is faulty Replace the rectifier.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
9
Indicator Color Abnormal Status
Exception Causes Suggestion
Alarm
indicator
Yellow Steady on Overtemperature
pre-alarm
Ensure that the vent of the
rectifier is unblocked.
The rectifier hibernates -
AC input undervoltage
or overvoltage occurs
-
Fault
indicator
Red Steady on Output overvoltage
occurs
Remove the rectifier and
then install it again. If there
is still no output, replace the
rectifier.
The fan is faulty Replace the rectifier.
Overtemperature occurs Ensure that the vent is
unblocked and that the
ambient temperature is
within the specified range.
No output exists
because of a fault inside
the rectifier
Replace the rectifier.
2.3 Monitoring System
The PMU consists of the monitoring board and panel.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
10
Monitoring board
The TP48300B-N16B2 & TP48600B-N16B2 implements the monitoring function using a
monitoring board. The monitoring board has strong expandability. The monitoring board is
installed on the cabinet door and is covered by an aluminum shell that is closed. Cables are
routed out of the left side of the aluminum shell. The movable window can be removed for
user connecting cables. Figure 2-4 shows the monitoring board.
Figure 2-4 Monitoring board
Table 2-2 Structural specifications of the monitoring board
Item Description
Dimensions (W x D) 127.90 mm x 270 mm (5.04 in. x 10.63 in.)
Installation position On the cabinet door
Maintenance mode Replace the whole monitoring board.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
11
Figure 2-5 shows user port screen.
Figure 2-5 User port screen
Table 2-3 User ports
Port Type Silkscreen Description Remarks
Sensor port GATE Door status detection Reserved
SMOKE Smoke detection None
TEM_BAT Battery temperature
detection
None
TEM2 Ambient temperature
detection
None
TEM_HUM Ambient temperature and
humidity detection
Reserved
WATER Water detection Reserved
Analog value
detection port
AIN Middle point voltage
detection for storage
batteries
Battery in position
detection
Boolean value
detection port DIN1 Boolean value input 1 None
DIN2 Boolean value input 2 None
DIN3 Boolean value input 3 AC SPD alarm detection
DIN4 Boolean value input 4 DC SPD alarm detection
DIN5 Boolean value input 5 None
DIN6 Boolean value input 6 None
DIN7 Boolean value input 7 None
Dry contact
output port
ALM1 AC power failure None
ALM2 DC undervoltage alarm None
ALM3 PSU fault None
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
12
Port Type Silkscreen Description Remarks
ALM4 Fuse blown None
ALM5 PMU fault None
Electronic
identification
(eID) tag
PELU eID tag input Reserved
Communications
port
COM Communication with the
host
None
Figure 2-6 Sensor ports
Table 2-4 Pin definition of sensor ports
Silkscreen Pin Definition
SMOKE 1 SMOKE
2 12V
TEM BAT 1 12V
2 VBTEM1
TEM2 1 12V
2 VTEM2
AIN 1 SIM1
2 SIM2
DIN1 1 12V
2 JTD1
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
13
Silkscreen Pin Definition
DIN2 1 12V
2 JTD2
DIN3 1 JTD3
2 12V
DIN4 1 JTD4
2 12V
DIN6 1 12V
2 JTD6
DIN7 1 12V
2 JTD7
Table 2-5 PMU functions
Function Description
Power supply
management
Intelligent PSU hibernation
Adjusting the output voltage and current of the PSU
Switching between boost charge and floating charge
Controlling the power-on and power-off of storage batteries and
loads
Alerting by the buzzer
Site mains quality
Battery
intelligent
management
Management of storage batteries inside the power supply cabinet and
outdoor battery cabinet
Battery temperature compensation, charge current limiting, battery
capacity calculation, and battery protection
Battery in position detection
Controlling storage batteries in manual or automatic mode
Battery operating temperature
Amount of electricity discharged by storage batteries.
Alarm reporting
and recording
The monitoring system generates audible and visual alarms and
reports the alarms to the host.
Alarms are classified into major alarms and minor alarms by
severity. Alarm severities can be set as required.
Records are kept for alarms. A maximum of 1000 historical alarms
are reserved.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
14
Function Description
Communications The PMU provides the functions of local management and alarm
reporting.
The PMU communicates with the host and third-party equipment.
The PMU supports NetEco NetEco network management by
connecting to the SNMP module.
Dry contact
output
The monitoring system has five dry contact outputs.
The association between dry contact outputs and alarm signals can
be set. When an alarm is generated, an alarm signal is set through the
corresponding dry contacts.
Digital parameter
input
The PMU has seven Boolean value inputs.
Sensor port The PMU has various sensor ports.
Monitoring Panel
The monitoring panel has indicators, liquid crystal display (LCD) panel, and buttons. The
monitoring panel is installed on the front door of the cabinet and is connected to the
monitoring board over the flat cable. Figure 2-7 shows the monitoring panel.
Figure 2-7 Monitoring panel
Table 2-6 Indicator descriptions
Silkscreen Color Meaning Status Description
Run
indicator
Green Run
indicator
Off The PMU is faulty or has no DC
input.
Blinking (0.5 Hz) The PMU communicates with
the host normally.
Blinking (4 Hz) The PMU communicates with
the host abnormally.
Alarm Red Alarm Off No alarm occurred.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 2 Component Description
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
15
Silkscreen Color Meaning Status Description
indicator indicator On Major alarms are generated on
the PMU
Table 2-7 Button descriptions
Button Description
▲ or ▼ Allows you to scroll the menu or set the value of a menu item.
Cancel Returns to the previous menu
Enter Enters the main menu from the standby screen, enters a submenu
from the main menu, or saves the settings of a submenu item.
The default customer password is 0#, and Huawei engineer
password is11#.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 3 Safety Precautions
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
16
3 Safety Precautions
3.1 Overview
The safety precautions described in this section are also applicable to other Huawei
equipment.
To minimize the risk of personal injury and damage to equipment, read and follow all the
precautions in this document before performing any installation or maintenance. The "NOTE",
"CAUTION", and "WARNING" marks in other documents do not represent all the safety
instructions. They are only supplements to the safety instructions. Only trained and qualified
personnel are allowed to install, operate, and maintain Huawei equipment, and they must
understand basic safety precautions to avoid hazards.
To ensure safety of humans and the equipment, pay attention to the safety symbols on the
equipment and all the safety instructions in this document. Huawei will not be liable for any
consequence caused by the violation of the safety operation regulations and design,
production, and usage standards.
3.2 Local Safety Regulations
When operating Huawei equipment, you must follow the local laws and regulations. The
safety instructions in this document are only supplements to the local laws and regulations.
3.3 Grounding Requirements
Equipment to be grounded must meet the following requirements:
When installing the device, always make the ground connection first and disconnect it at
the end.
Do not damage the ground conductor.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 3 Safety Precautions
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
17
Do not operate the device in the absence of a properly installed ground conductor.
Conduct the electrical inspection carefully.
The device (or system) must be connected permanently to the protection ground before
an operation. Before operating the device, check the electrical connection of the device
to ensure that it is securely grounded.
3.4 Human Safety Do not operate the device or cables during lightning strikes.
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
Before operating the device, wear electrostatic discharge (ESD) clothes, ESD gloves, and
an ESD wrist strap. Do not wear jewelry or watches when you operate the device.
In the case of fire, immediately leave the building or the equipment room, and turn on
the fire alarm bell or make an emergency call. Do not enter a building that is on fire.
3.5 Equipment Safety The device must be fixed securely on the floor or to other immovable objects such as
walls and mounting racks before operation.
Do not block the ventilation while the device is operating.
Tighten the thumbscrews by using a tool after initial installation and subsequent access
to the panel.
After the installation, remove packing materials from the equipment area.
3.6 Electrical Safety
High Voltage
The high voltage power supply provides power for the device operation. Direct or indirect
contact (through damp objects) with high voltage and alternating current (AC) mains
supply may result in serious injury.
Non-standard and incorrect high voltage operations may result in fire and electric shock.
The personnel who install the AC facility must be qualified to perform high voltage and
AC operations.
You must abide by the local rules and regulations when bridging and wiring AC cables.
During the installation of the AC power supply facility, follow the local safety
regulations.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 3 Safety Precautions
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
18
Dedicated tools must be used during high voltage and AC operations. Avoid using
ordinary tools.
When the operation is performed in a damp environment, ensure that the device is dry.
When water is found in the rack or the rack is damp, switch off the power supply
immediately.
High Electrical Leakage Ground the device before powering it on. Otherwise, personal injury or device damage
may be caused by high leakage current.
If a "high electrical leakage" tag is present on the power terminal of the device, you must
ground the device before powering it on.
Power Cable Do not install or remove power cables when the device is on. Transient contact between
the core of the power cable and the conductor may generate electric arcs or sparks, which
may cause fire or hurt human eyes.
Before installing or removing the power cable, turn off the power switch.
Before connecting a power cable, check that the label on the power cable is correct.
Power Output
All output circuits are evaluated as SELV circuits.
Outputs are energy hazards (>240 VA)
Electrostatic Discharge
The static electricity generated by human bodies may damage the electrostatic-sensitive
components on boards, for example, the large-scale integrated (LSI) circuits.
Human body movement, friction between human bodies and clothes, friction between
shoes and floors, or handling of plastic articles causes static electromagnetic fields on
human bodies. These static electromagnetic fields cannot be eliminated until the static is
discharged.
To prevent electrostatic-sensitive components from being damaged by the static on
human bodies, you must wear a well-grounded ESD wrist strap when touching the
device or handling boards or application-specific integrated circuits (ASICs).
Figure 3-1 shows how to wear an ESD wrist strap.
CAUTION
TP48300B-N16B2 & TP48600B-N16B2
User Manual 3 Safety Precautions
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
19
Figure 3-1 Wearing an ESD wrist strap
TP48300B-N16B2 & TP48600B-N16B2
User Manual 4 Installation and Commissioning
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
20
4 Installation and Commissioning
The detailed installation and commissioning refer to the TP48300B-N16B2 Quick Installation Guide and TP48600B-N16B2 Quick Installation Guide.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
21
5 System Maintenance
5.1 Routine Maintenance
The TP48300B-N16B2 & TP48600B-N16B2 is maintained every six months. If faults are
identified, clear them immediately.Routine maintenance checklist
Maintenance Item
Maintenance Task
Check Whether
Check Method
Repair When Measures
Electricity The voltage
output is
normal.
Using a
multimeter
The BLVD or
LLVD voltage
exceeds the
threshold.
For details, see
section 5.2
"Troubleshooting
Common Faults."
Preventive
maintenance
inspection
(PMI)
Indicators are
normal.
Observing
indicators
Alarms are
generated.
Cabinet
appearance
The paint or
the
electroplated
coating on the
cabinet are
flaking off or
scratches
occur.
Observing
the cabinet
The cabinet
surface is damaged
or distorted.
Repaint and repair
the cabinet.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
22
5.2 Troubleshooting
5.2.1 Troubleshooting Common faults
Table 5-2 Common faults and troubleshooting methods
Fault Type Fault Analysis Handling Method
AC phase loss AC input cable
fault
Grid fault or D.G.
fault
1. Check whether the DC input cable is
correctly and securely connected. If the
cable is not correctly and securely
connected, reconnect the cable. If the
insulation layer is aged, replace the
cable.
2. Check whether the AC input voltage is
excessively low using a multimeter, and
check whether the AC undervoltage
(lower than 180V AC) alarm is
generated. If the AC input voltage is
excessively low and the AC
undervoltage alarm is generated, check
whether there is short-circuit or electric
leakage on the AC input loop. If there is
short-circuit or electric leakage, replace
the cable.
3. If the AC input is the mains supply,
contact the mains supplier for
troubleshooting. If the AC input is from
the D.G., check the D.G. by referring to
the Diesel Generator User Manual.
AC power off AC input cable
fault
Grid fault or D.G.
fault
1. Check whether the DC input cable is
correctly and securely connected. If the
cable is not correctly and securely
connected, reconnect the cable.
2. Check whether the AC input is
available. If the AC input is not
available, check whether faults such as
short-circuit or open circuit exist on the
AC input loop. If the AC input loop is
proper, contact the mains supplier for
troubleshooting. If the AC input is from
the D.G., check the D.G. by referring to
the Diesel Generator User Manual.
3. If the power-off duration is short,
supply DC power using batteries. If the
power-off duration is long, start other
systems for power supply.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
23
Fault Type Fault Analysis Handling Method
AC overvoltage
and undervoltage
Improper setting of
PMU AC
undervoltage or
overvoltage
threshold
Mains supply grid
fault or D.G. fault
1. Check whether the AC undervoltage or
overvoltage alarm threshold is properly
set. If the threshold is excessively high
or low, lower or raise the threshold
according to the actual conditions.
2. If the AC input is the mains supply,
contact the mains supplier for
troubleshooting. If the AC input is from
the D.G., check the D.G. by referring to
the Diesel Generator User Manual.
DC overvoltage
and undervoltage
Improper setting of
PMU DC
undervoltage or
overvoltage
threshold
1. Check the alarm thresholds of the DC
overvoltage and undervoltage. If the
thresholds are not proper, reset the
thresholds according to the actual
conditions.
2. When the storage battery is powering
the load, remove all the PSUs, and then
insert each PSU one by one. If an
overvoltage alarm is generated after a
PSU is inserted, the voltage of the PSU
exceeds the upper threshold. Then
Replace the PSU.
Charging
overcurrent
Communication
failure between
modules
Battery loop fault
1. Check whether the rectifier module is in
position or whether contact is proper. If
the PMU is inserted in an incorrect
position, insert it correctly. If the
contact is not proper, remove and then
insert it.
2. Check whether the communication
cables between the rectifier module and
the monitoring signal transfer board is
correctly and securely connected. If the
connection is proper, restart the rectifier
module.
3. Check whether the battery loop is
short-circuited or has other faults.
4. Check whether the batteries are faulty.
If the batteries are faulty, replace them.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
24
Fault Type Fault Analysis Handling Method
Load shutdown Load circuit
breaker set to OFF
Contactor fault
Excessively high
setting of PMU
load shutdown
voltage
Output
undervoltage due
to greater load
power than
configured rectifier
module power
1. Check whether the load detection cable
(as shown in Figure 5-1 and Figure
5-2 )is securely connected. If the cable
is not connected securely, connect it
correctly.
2. Check whether the load circuit breaker
is turned off. Checking method: Check
the position of the handle on the circuit
breaker. If the circuit breaker is turned
off, turn on the circuit breaker.
3. Check whether the contactor is faulty
and whether it can be connected and
disconnected. If the contactor is faulty,
replace it.
4. Check whether the PMU load shutdown
voltage is set excessively high. If it is
set excessively high, set it according to
the actual situation.
5. Check whether the load power is higher
than the configured rectifier module
power. If the load power is higher than
the configured rectifier module power,
add a rectifier module. If the load
power exceeds the maximum supported
power of the system, lower the load
power.
Battery shutdown Improper setting of
PMU battery
parameters
Contactor fault
1. Check whether the mains supply is off
or the voltage of storage batteries is
lower than the “Battery Shutdown
Voltage”.
2. Check whether the battery shutdown
permission is set.
3. Check whether the battery cables or the
connectors are faulty. If the cables or
connectors are faulty, replace them.
4. Check whether the contactor is faulty
and whether it can be connected and
disconnected. If the contactor is faulty,
replace it.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
25
Fault Type Fault Analysis Handling Method
Battery loop
failure
Battery loop fault
Contactor fault
Battery fault
1. Check whether cables of the battery
loop or connectors are faulty. If the
cables or connectors are faulty, replace
them.
2. Check whether the contactor is faulty
and whether it can be connected and
disconnected. If the contactor is faulty,
replace it.
3. Check whether batteries are faulty. If
the batteries are faulty, replace them.
Ambient
overtemperature or
undertemperature
alarm
(The alarm is
generated only
when the
temperature sensor
is installed.)
Improper setting of
PMU temperature
alarm parameters
Overtemperature
or
undertemperature
in the shelter with
the temperature
sensor
Temperature
sensor fault
1. Check whether PMU temperature alarm
thresholds are set according to local
conditions. If the thresholds are not
proper, set the thresholds accordingly.
2. Check whether the temperature control
device in the shelter is faulty. If the
temperature control device is faulty,
repair it. The alarm is automatically
cleared when the temperature in the
shelter is adjusted to the proper range.
3. If the alarm persists when the
temperature is proper, check whether
the temperature sensor is faulty.
Ambient
overhumidity or
underhumidity
alarm
(The alarm is
generated only
when the humidity
sensor is installed.)
Improper setting of
PMU humidity
alarm parameters
Overhumidity or
underhumidity in
the shelter with the
humidity sensor
Humidity sensor
fault
1. Check whether PMU humidity alarm
thresholds are set according to local
conditions. If the thresholds are not
proper, set the thresholds accordingly.
2. Check whether the floor of the shelter is
wet. If the floor is wet, use a cotton
cloth to wipe the floor and ensure it is
dry or use other dehumidifiers.
3. If the alarm persists when the humidity
is proper, check whether the humidity
sensor is faulty.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
26
Fault Type Fault Analysis Handling Method
Battery
overtemperature or
undertemperature
alarm
Battery cabin
overtemperature
Improper setting of
PMU battery
temperature alarm
parameters
Battery charging
overcurrent
Temperature
sensor fault
1. Check whether PMU battery
temperature alarm thresholds are
properly set. If the thresholds are not
proper, set the thresholds accordingly.
2. Check whether the temperature in the
battery room is excessively high. If the
temperature is excessively high, the
alarm can be cleared when the
temperature is lowered.
3. Check the charging current. If the
current is excessively strong, switch
equalized charging to float charging
and check whether the charging current
is weakened. If the charging current is
still excessively strong, adjust the
current suppression to reduce the
charging current. If the preceding steps
do not work, replace the faulty battery.
Water immersion
alarm
(The alarm is
generated only
when the water
sensor is installed.)
Shelter water
accumulation
Water sensor fault
1. Check whether the floor of the shelter is
wet. If the floor is wet, use a cotton
cloth to wipe the floor and ensure it is
dry or use other dehumidifiers.
2. If the alarm persists after the water is
drained, check whether the water sensor
is faulty.
Smoke alarm
(The alarm is
generated only
when the smoke
sensor is installed.)
Smoke in the
shelter
Smoke sensor fault
1. Check whether the smoke caused by
fire pervades in the shelter. If there is
fire, extinguish the fire and ventilate the
shelter.
2. If the alarm persists when there is no
smoke, check whether the smoke sensor
is faulty.
Module fault Poor contact of the
rectifier module
Rectifier module
fault
1. Check whether the ALM indicator on
the panel of the rectifier module blinks.
If the ALM indicator blinks, it indicates
that the rectifier module is faulty.
Replace the rectifier module.
2. Disconnect AC input to the rectifier
module and restart the rectifier module
later on. If the alarm persists, replace
the rectifier module.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
27
Fault Type Fault Analysis Handling Method
Module shutdown
Module protection
Input overvoltage
or undervoltage of
the rectifier
module
Rectifier module
fault
1. Check whether the mains voltage is
over the AC overvoltage alarm
threshold (300 V) of the rectifier
module or below the AC undervoltage
alarm threshold (85 V). For the power
supply network with long-time
overvoltage or undervoltage, negotiate
with the maintenance personnel of the
electricity department to improve the
power supply network.
2. If the alarm persists when the input
voltage of the rectifier module is
proper, check whether the rectifier
module is proper. If the rectifier module
is faulty, replace it.
Communication
failure between
modules
Signal cable
connection fault of
the rectifier
module
Rectifier module
out of position
Poor contact of the
rectifier module
Rectifier module
fault
Monitoring signal
transfer board fault
1. Check whether the rectifier module is in
position or whether contact is proper. If
the PMU is inserted in an incorrect
position, insert it correctly. If the
contact is not proper, remove and then
insert it.
2. Check whether the communication
cables between the rectifier module and
the monitoring signal transfer board is
correctly and securely connected. If the
connection is proper, restart the rectifier
module.
3. If the alarm persists, replace the
rectifier module.
4. If the alarm is not cleared after the
rectifier module is replaced, replace the
monitoring signal transfer board.
D.G. fault DG signal cable
fault
Improper setting of
the PMU
D.G. fault
1. Check whether the signal cable of the
DG is correctly and securely connected.
If the signal cable is not correctly and
securely connected, connect it correctly.
2. Check whether the start permission of
the DG in the PMU is set to NO and
whether the diesel generator is started
manually. If the permission is set to NO
and the DG is started manually, this is
normal. The alarm is cleared after the
DG is shut down.
3. Check whether the DG is faulty by
referring to the Diesel Generator User Guide delivered with the DG.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
28
Fault Type Fault Analysis Handling Method
Disconnection of
the load fuse
Load circuit
breaker set to OFF
1. Check whether the load circuit breaker
is set to OFF. If it is set to OFF, set it to
ON.
2. If the circuit breaker is automatically
set to OFF after you set it to ON, check
whether the load branch is overloaded
or short-circuited. Check and rectify the
load loop fault.
AC surge protector
fault
AC surge protector
fault
Monitoring signal
transfer board fault
1. Check the observation window on the
AC surge protector. If the color of the
window is red, replace the surge
protector. If the color is not red, check
whether the fault detection cables of the
AC surge protector are correctly
connected or whether the cables are in
good condition. If the cables are not in
good condition, replace and reconnect
them. If the cable connection is proper,
it indicates that the alarm loop is faulty.
Replace the PMU.
2. If the alarm persists after the PMU is
replaced, replace the monitoring signal
transfer board.
DC surge protector
fault
DC surge protector
fault
1. Check whether the fault detection
cables of the DC surge protector are
correctly and securely connected. If the
cables are not correctly and securely
connected, reconnect them.
2. If the cables are correctly connected,
replace the DC surge protector.
3. If the alarm persists after the surge
protector is replaced, replace the PMU.
If the alarm cannot be cleared after the
PMU is replaced, replace the
monitoring signal transfer board.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
29
If you rectify the corresponding faults, the alarms in the PMU are automatically cleared and saved in
history alarm information.
After the PMU is replaced, set parameters again. For details, see the TP48300B-N16B2 Quick
Installation Guide and TP48600B-N16B2 Quick Installation Guide.
The PMU and rectifier module are hot-swappable.
Take anti-static measures when replacing the monitoring board. For example, wear ESD wrist strap.
Figure 5-1 TP48300B-N16B2 detection cables to loads
Figure 5-2 TP48600B-N16B2 detection cables to loads
5.2.2 Troubleshooting Components
AC SPD
Observe the indication window on the surge protection module. If the indication window
turns red, the surge protection module is damaged. In this case, replace the surge protection module. If the indication window remains green, the SPD runs properly.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
30
Circuit Breaker
The circuit breaker fault is usually caused by overcurrent or short circuits. Circuit breaker
faults are caused by overcurrent or short circuits. To check whether a circuit break is faulty,
perform the following steps:
Step 1 Switch the circuit breaker to the ON position.
Step 2 Measure the resistance at the two ends of the circuit breaker using a multimeter. If the
resistance is infinity, the circuit breaker is damaged.
DC Contactor
Table 5-3 DC contactor description
Position Type Check Method
Load
Disconnected
Branch
Closed type, (when the
contactor without electricity,
the state is closed)
When there is no voltage at the control
poles of the contactor, check whether
the input and output poles of the
contactor are proper by using the
multimeter. For example, the contactor
of the power system is closed type
contactor as shown in Figure 5-3.
When there is no voltage at control
poles 1 and 2 but measuring shows that
the input and output poles 3 and 4 are
disconnected, it indicates that the
contactor is faulty.
When there is voltage at the control
poles of the contactor, check whether
the input and output poles of the
contactor are proper by using the
multimeter. For example, the contactor
of the power system is a closed type
contactor as shown in Figure 5-3.
When there is voltage at control poles 1
and 2 but measuring shows that the
input and output poles 3 and 4 are
connected, it indicates that the
contactor is faulty.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
31
Position Type Check Method
Battery Fuse
or battery
circuit breaker
Branch
Open type, (when the
contactor without electricity,
the state is open)
When there is no voltage at the control
poles of the contactor, check whether
the input and output poles of the
contactor are proper by using the
multimeter. For example, the contactor
of the power system is an open type
contactor as shown in Figure 5-3.
When there is no voltage at control
poles 1 and 2 but measuring shows that
the input and output poles 3 and 4 are
connected, it indicates that the
contactor is faulty.
When there is voltage at the control
poles of the contactor, check whether
the input and output poles of the
contactor are proper by using the
multimeter. For example, the contactor
of the power system is an open type
contactor as shown in Figure 5-3.
When there is voltage at control poles 1
and 2 but measuring shows that the
input and output poles 3 and 4 are
disconnected, it indicates that the
contactor is faulty.
Figure 5-3 DC contactor
Rectifier
The rectifier is damaged if either of the following conditions is not met:
The Run indicator of the rectifier is steady on and the Fault indicator is off when the
rectifier does not communicate with the PMU and the input AC voltage is around 220 V.
The rectifier outputs power normally.
The PMU can perform control on the charge mode (boost charge or floating charge) and
current for the rectifier when the rectifier communications cable is properly connected
and the rectifier communicates with the PMU normally.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
32
PMU
If any of the following occurs, the PMU is faulty:
1. The PMU breaks down or fails to start, or its LCD or keyboard fails.
2. The PMU does not generate an alarm when a fault occurs in the system.
3. The PMU generates an alarm (false alarm) when the system runs properly.
4. Communication between the PMU and all subordinate equipment is interrupted.
5. The PMU fails to control or monitor all the modules when these modules run properly
and communications cables are connected properly.
6. The PMU fails to monitor or control AC or DC distribution when AC/DC power is
distributed normally and communications cables are connected properly.
7. Parameters cannot be set or operating information cannot be viewed on the PMU.
5.3 Component Replacment
Describe how to replace the main components of the power system.
Load disconnection is prohibited when you replace the main components. Take measures to ensure
that important loads are always connected during the replacement. For example, keep the circuit
breaker of important loads set to ON and storage batteries and AC input are not cut off.
If a load must be disconnected, ask for the customer's prior permission.
The rectifier and the PMU are hot-swappable.
For more safety precautions, see 3 Safety Precautions.
Replacing a PSU
To replace a PSU, perform the following steps:
1. Loosen the screws on the PSU to be replaced and open the handle.
2. Pull the handle to disengage the latch from the subrack, as shown in Figure 5-4.
3. Insert a new PSU into the subrack. Then loosen the screws on the handle and open the
handle.
4. Push the PSU slowly into the subrack along the guide rail and lock the handle.
5. Tighten the screws on the handle, as shown in Figure 5-5.
Figure 5-4 Removing a PSU
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
33
Figure 5-5 Installing a PSU
Replacing the Monitoring Board
To replace the monitoring board, perform the following steps:
1. Loosen the screws on the shell of the monitoring board and remove the shell.
2. Remove all external cables and screws and take out the monitoring board, as shown in
Figure 5-6.
3. Insert a new monitoring board, fasten screws, and connect external cables.
4. Set parameters on the PMU panel.
Figure 5-6 Replacing a monitoring board
Replacing an AC SPD
To replace an AC SPD, perform the following steps:
1. Remove the faulty AC SPD.
2. Insert a new AC SPD.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
34
Figure 5-7 Replacing an AC SPD
Replacing Circuit breakers
To replace a circuit breaker, perform the following steps:
Step 1 Disconnect the power supply of a circuit breaker. For example, disconnect the DC input and
set the circuit breaker to OFF before replacing the input circuit breaker.
Step 2 Remove the cables or copper bars connected to the circuit breaker using a Phillips screwdriver,
and then wrap the cables or copper bars using black PVC insulation tape to avoid hazards.
Step 3 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver. Then,
remove the circuit breaker, as shown in Figure 5-8.
Step 4 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver again
to install the new circuit breaker in the correct position. Then, push the contact plate upwards
using the screwdriver.
Step 5 Install the cables or copper bars to the circuit breaker using a Phillips screwdriver in the same
way.
Step 6 Set the circuit breaker to ON and connect power supply of this circuit breaker, as shown in
Figure 5-9.
----End
Figure 5-8 Removing the circuit breaker
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
35
Figure 5-9 Installing the circuit breaker
Replacing a Fuse
To replace a fuse, perform the following steps:
1. Disconnect the fuse loop.
2. Remove the damaged fuse using a fuse extracting unit, as shown in Figure 5-10.
3. Install a new fuse, as shown in Figure 5-11.
4. Connect the fuse loop.
Figure 5-10 Removing a fuse(take the TP48300B-N16B2 as an example)
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
36
Figure 5-11 Installing a fuse(take the TP48300B-N16B2 as an example)
5.4 Querying Alarms
When the ALM indicator on the PMU is steady on, query the alarm on the LCD screen of the
PMU or in the EMS, and then clear the alarm. For details about how to query the alarm, see
Figure 5-12,Figure 5-13.
TP48300B-N16B2 & TP48600B-N16B2
User Manual 5 System Maintenance
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
37
Figure 5-12 Querying alarms on the PMU
Figure 5-13 Querying alarms on the NetEco net work management UI
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
38
A Appendix
A.1 Technical Specifications
Table A-1 Technical specifications
Category Item Specifications
Environm
ental
conditions
Operating
temperature
–10ºC to +50ºC (14ºF to +122.0ºF)
Storage
temperature
–40°C to +70°C (–40°F to +158°F)
Transportation
temperature
–40°C to +70°C (–40°F to +158°F)
Operating
humidity
5%–95% RH (non-condensing)
Storage
humidity
5%–95% RH (non-condensing)
Altitude 0-4000 m (0-13123.2 ft)
When the altitude ranges from 2000 m (6561.6 ft) to 4000 m
(13123.2 ft), the operating temperature is derated by 1ºC
(1.8ºF) for each additional 200 m (656.16 ft).
AC input Input mode Three-phase, four-wire (L1, L2, L3, N)
Input voltage 90–290 V AC (rated voltage: 220 V AC)
Input frequency 45–66 Hz (rated frequency: 50/60 Hz)
Power factor ≥ 0.99 (50%–100% load)
DC output Output voltage
range
–43.2 V DC to –57.6V DC
Default output
voltage
–53.5 V DC
Maximum
output power
Number of rectifiers multiplied by the output power of a
single rectifier
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
39
Regulated
voltage
precision
≤ 1%
Peak-to-peak
noise voltage
≤ 200 mV (0–20 MHz)
AC input
protection
AC input
overvoltage
protection
threshold
Overvoltage protection is performed when the single-phase
AC input voltage exceeds the AC input overvoltage
protection threshold (300 V AC by default).
AC input
overvoltage
recovery
threshold
When the voltage is restored to 290 V AC, the output
resumes.
AC input
undervoltage
protection
threshold
Undervoltage protection is performed when the single-phase
AC input voltage is below the AC input undervoltage
protection threshold (85 V AC by default).
AC input
undervoltage
recovery
threshold
When the voltage is restored to 90 V AC, the output
resumes.
DC output
protection
DC output
overvoltage
protection
threshold
58.5–60.5 V DC
Rectifier Efficiency R4850G1:≥96.0%(30%~60% load)
R4850N1:≥91.5%(35%~80% load)
Output power R4850G1:
3000W (176V AC-300V AC)
1200W (85V AC-175V AC)
R4850N1:
2900W (176V AC-300V AC)
1200W (85V AC-175V AC)
Output soft
start
At the moment when the rectifier is powered on, the output
voltage rises slowly.
Overvoltage
protection
Voltage range: 58.5–60.5 V DC
If overvoltage occurs inside the rectifier due to a fault,
the rectifier experiences a deadlock.
External overvoltage:
If the external voltage is less than 63 V, the rectifier is in
the standby state. If overvoltage disappears, the rectifier
output resumes.
If the external voltage is greater than 63 V for more than
500 ms, the rectifier experiences a deadlock.
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
40
EMC CE/RE CISPR 22/EN 55022 class A
Harmonic IEC 61000-3-12
Fluctuation and
blinking
IEC 61000-3-11
ESD Contact discharge voltage: 6kV (Class B); air discharge
voltage: 8 kV (Class B); standard: IEC61000-4-2
EFT The voltage at signal ports is 1 kV, and the voltage at the
power ports is 2 kV (criterion B).
RS 10 V/m (criterion A)
CS The voltage at signal ports and power ports is 10 V
(criterion A).
SURGE It complies with the IEC61000-4-5 standard. The voltage at
the AC power ports in differential mode is ±2 kV. The
voltage at the AC power ports in common mode is ±4 kV
(criterion B).
Others AC surge
protection
Level-B surge protection
Standard surge discharge current: 20 kA, 8/20 µs
Maximum surge discharge current: 40 kA, 8/20 µs
DC surge
protection
Differential mode: 10 kA, 8/20 µs
Common mode: 20 kA, 8/20 µs
Safety and
regulatory
design
IEC/EN 60950-1, and CE
MTBF 250,000 hours
Structure Dimensions (H
x W x D)
1600 mm (62.99 in.) x 600 mm (23.62 in.) x 400 mm
(15.75 in.)
Weight
(including
modules)
≤ 100 kg (without rectifier modules and storage batteries)
Protection level IP20 (after being covered with a top cover)
Installation On a concrete floor or an ESD floor
Maintenance Maintained from the front and located along a wall with at
least 100 mm (3.94 in.) slack
Cabling Routing cables from the top or bottom.
Cooling Natural ventilation
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
41
A.2 LCD Menu
Figure A-1 Menu tree
Figure A-2 LCD Menu
Main Menu Second Menu
Third Menu
Forth Menu Fifth Menu
Default Value
Status Active - - - -
History - - - -
Rectifiers ID ID - -
* V - -
* A - -
Curr Limit - -
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
42
Main Menu Second Menu
Third Menu
Forth Menu Fifth Menu
Default Value
Status - -
Batt Test
Result - - - -
Version
Display - - - -
Maintenance
Mgmt
Mode - - - Auto
Start - - - FC
Rect - - - -
PMU
Reset - - - No
Settings
System
Settings
Address - - 0
Text - - Chinese
M/S - - -
Baud - - 9600
Data - - -
Time - - -
Batt 2 Shunt - - Yes
Disp
Contrast - - 3
System
Type
- - TP48600B
IP Address - - 192.168.0.10
Subnet
Mask - - 255.255.255.0
Gateway - - 192.168.0.1
Server Port - - 31220
Server IP
Addr1 - - 192.168.0.1
Server IP
Addr2 - - 192.168.0.2
Engineer
Settings
Modify
Password - No
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
43
Main Menu Second Menu
Third Menu
Forth Menu Fifth Menu
Default Value
Initial
parameter - No
Initial info - No
Alarm
Settings
Alarm Level Alarm -
Level -
Digital
Alarm
DI No. -
Mode -
Set DI Name -
Alarm
Control
Audible Alarm - Yes
Clr Hist Alarm - No
Redundant
Enable - Disable
Alarm
Relate
Relate relay - -
Relay Type - Open
AC
Settings
Over Volt - - 280V
Under Volt - - 180V
State
Measure - - No
DC
Settings
Over Volt - - 58.0V
Under Volt - - 45.0V
Batt
Settings
Batt
Selection
Batt String - 1
Capacity 1 - 400AH
Capacity 2 - 0Ah
Install Date - 2001-01-01
LVD
Setting
LLVD Enable - Yes
BLVD Enable - Yes
LLVD Mode - Yes
Load OFF time - 300min
LLVD - 44.0V
BLVD - 43.0V
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
44
Main Menu Second Menu
Third Menu
Forth Menu Fifth Menu
Default Value
Charge Float - 53.5V
Boost - 56.5V
Cyc BC
Duration - 60 days
Curr Limit - 0.10C10
Batt Test Auto Test AutoTest
Enable
Discharge test
Cycle 120 days
Test End
Volt
45.6V
Duration 10 hours
Test
Delay
14 days
Short test Test end
voltage
45.0V
Duration 60minutes
Temperature
co
efficiency
BHTD enable - No
BHTD
temperature
- 53°C
Low
temperature
alarm
- 0°C
High
temperature
alarm
- 50°C
Temperature
compensation
- 80mV/°C
AMB.
Settings
High Alarm - - 50°C
Low Alarm - - 0°C
Generator
Generator
Status - - No
Rect
Sleep
Rect Sleep - - Yes
Best Effi
Point - - 70%
TP48300B-N16B2 & TP48600B-N16B2
User Manual A Appendix
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
45
Main Menu Second Menu
Third Menu
Forth Menu Fifth Menu
Default Value
Rect Exch
Sleep - - 7 days
Rect Mini
Num - - 1
TP48300B-N16B2 & TP48600B-N16B2
User Manual B Acronyms and Abbreviations
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
46
B Acronyms and Abbreviations
A
ATS automatic transfer switch
ACDB alternating current distribution box
B
BLVD battery low voltage disconnection
D
D.G. diesel generator
E
EMC electromagnetic compatibility
EMI electromagnetic interference
EMS element management system
electromagnetic susceptibility
L
LLVD load low voltage disconnection
I
IEC International Electrotechnical Commission
M
MTBF mean time between failures
TP48300B-N16B2 & TP48600B-N16B2
User Manual B Acronyms and Abbreviations
Issue 01 (2012-02-20) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
47
O
OPEX operational expenditure
P
PSU power supply unit
PMU power monitor unit
PDU power distribution unit
R
RoHS restriction of the use of certain hazardous
substances
S
SNMP Simple Network Management Protocol
SPD surge protection device
T
TCU temperature control unit
U
UIM user interface module