54
TP48300B-N04C2 V100R001 User Manual Issue Draft A Date 2013-06-21 HUAWEI TECHNOLOGIES CO., LTD.

Tp48300b-n04c2 v100r001 User Manual

Embed Size (px)

DESCRIPTION

Мануал по ИБП TP48300B компании Huawei. На английском языке.

Citation preview

  • TP48300B-N04C2

    V100R001

    User Manual

    Issue Draft A

    Date 2013-06-21

    HUAWEI TECHNOLOGIES CO., LTD.

  • Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. i

    Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved.

    No part of this document may be reproduced or transmitted in any form or by any means without prior

    written consent of Huawei Technologies Co., Ltd.

    Trademarks and Permissions

    and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

    All other trademarks and trade names mentioned in this document are the property of their respective

    holders.

    Notice

    The purchased products, services and features are stipulated by the contract made between Huawei and

    the customer. All or part of the products, services and features described in this document may not be

    within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,

    information, and recommendations in this document are provided "AS IS" without warranties, guarantees

    or representations of any kind, either express or implied.

    The information in this document is subject to change without notice. Every effort has been made in the

    preparation of this document to ensure accuracy of the contents, but all statements, information, and

    recommendations in this document do not constitute a warranty of any kind, express or implied.

    Huawei Technologies Co., Ltd.

    Address: Huawei Industrial Base

    Bantian, Longgang

    Shenzhen 518129

    People's Republic of China

    Website: http://www.huawei.com

    Email: [email protected]

  • TP48300B-N04C2

    User Manual About This Document

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. ii

    About This Document

    Overview

    This document describes the DC power system in terms of product introduction, component

    introduction, and system maintenance. The figures provided in this document are for

    reference only.

    Intended Audience

    This document is intended for:

    Sales engineers

    Technical support engineers

    Maintenance engineers

    Symbol Conventions

    The symbols that may be found in this document are defined as follows.

    Symbol Description

    Alerts you to a high risk hazard that could, if not

    avoided, result in serious injury or death.

    Alerts you to a medium or low risk hazard that could, if

    not avoided, result in moderate or minor injury.

    Alerts you to a potentially hazardous situation that could,

    if not avoided, result in equipment damage, data loss,

    performance deterioration, or unanticipated results.

    Provides a tip that may help you solve a problem or save

    time.

    Provides additional information to emphasize or

    supplement important points in the main text.

  • TP48300B-N04C2

    User Manual About This Document

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. iii

    Change History

    Changes between document issues are cumulative. The latest document issue contains all the

    changes made in earlier issues.

    Issue Draft A (2013-06-21)

    This issue is a draft.

  • TP48300B-N04C2

    User Manual Contents

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. iv

    Contents

    About This Document .................................................................................................................... ii

    1 Overview ......................................................................................................................................... 1

    1.1 Introduction ...................................................................................................................................................... 1

    1.2 Features ............................................................................................................................................................ 1

    1.3 Working Principle............................................................................................................................................. 2

    1.4 System Configuration ....................................................................................................................................... 3

    2 Components ................................................................................................................................... 4

    2.1 Interior .............................................................................................................................................................. 4

    2.2 PDU .................................................................................................................................................................. 5

    2.2.2 Battery Switch ......................................................................................................................................... 6

    2.3 Rectifier ............................................................................................................................................................ 6

    2.4 SMU ................................................................................................................................................................. 8

    2.5 UIM ................................................................................................................................................................ 12

    3 Safety Precautions ....................................................................................................................... 15

    3.1 Health and Safety ........................................................................................................................................... 15

    3.1.1 Overview ............................................................................................................................................... 15

    3.1.2 Electrical Safety .................................................................................................................................... 17

    3.1.3 Inflammable Environment .................................................................................................................... 18

    3.1.4 Battery ................................................................................................................................................... 18

    3.1.5 Mechanical Safety ................................................................................................................................. 20

    3.1.6 Bundling Signal Cables ......................................................................................................................... 21

    3.2 Equipment Safety ........................................................................................................................................... 21

    3.2.1 Electricity Safety ................................................................................................................................... 21

    3.2.2 Electrostatic Discharge.......................................................................................................................... 21

    3.2.3 Laying Out Cables ................................................................................................................................ 22

    4 Maintenance ................................................................................................................................. 23

    4.1 Routine Maintenance...................................................................................................................................... 23

    4.2 Handling Alarms ............................................................................................................................................ 24

    4.2.1 Mains Failure ........................................................................................................................................ 24

    4.2.2 AC Over Volt ......................................................................................................................................... 24

    4.2.3 AC Under Volt ....................................................................................................................................... 25

  • TP48300B-N04C2

    User Manual Contents

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. v

    4.2.4 Phase A/B/C Failure .............................................................................................................................. 25

    4.2.5 DC Over Volt ........................................................................................................................................ 25

    4.2.6 DC Under Volt ...................................................................................................................................... 26

    4.2.7 Batt Over Curr ....................................................................................................................................... 26

    4.2.8 Load Off ................................................................................................................................................ 26

    4.2.9 Batt Off ................................................................................................................................................. 27

    4.2.10 Batt Loop Trip ..................................................................................................................................... 27

    4.2.11 Amb. Over Temp ................................................................................................................................. 28

    4.2.12 Amb. Under Temp ............................................................................................................................... 28

    4.2.13 Amb. Over Humi ................................................................................................................................. 28

    4.2.14 Amb. Under Humi ............................................................................................................................... 29

    4.2.15 Batt Over Temp ................................................................................................................................... 29

    4.2.16 Batt Under Temp ................................................................................................................................. 29

    4.2.17 Rectifier Lost ...................................................................................................................................... 30

    4.2.18 Rect Fault ............................................................................................................................................ 30

    4.2.19 Rect Protect ......................................................................................................................................... 30

    4.2.20 Rect Comm Fault ................................................................................................................................ 31

    4.2.21 Load Fuse Trip .................................................................................................................................... 31

    4.2.22 AC SPD Alarm .................................................................................................................................... 31

    4.2.23 DC SPD Alarm .................................................................................................................................... 32

    4.3 Identifying Component Faults ........................................................................................................................ 32

    4.3.1 Identifying Rectifier Faults ................................................................................................................... 32

    4.3.2 Identifying SMU Faults ........................................................................................................................ 32

    4.3.3 Identifying AC SPD Faults ................................................................................................................... 32

    4.3.4 Identifying Circuit Breaker Faults ........................................................................................................ 33

    4.4 Replacing Components .................................................................................................................................. 33

    4.4.1 Replacing a Rectifier ............................................................................................................................. 33

    4.4.2 Replacing an SMU ................................................................................................................................ 34

    4.4.3 Replacing an AC SPD ........................................................................................................................... 35

    4.4.4 Replacing a Circuit Breaker .................................................................................................................. 36

    4.4.5 Replacing a UIM ................................................................................................................................... 37

    A Technical Specifications ........................................................................................................... 39

    A.1 Environmental Specifications ........................................................................................................................ 39

    A.2 Electrical Specifications ................................................................................................................................ 39

    A.3 Safety and Regulatory Specifications ............................................................................................................ 40

    A.4 EMC Specifications ....................................................................................................................................... 41

    A.5 Cabinet Specifications ................................................................................................................................... 42

    A.6 Rectifier Specifications ................................................................................................................................. 42

    B Electrical Conceptual Diagram ................................................................................................ 43

    C Associations Between Alarms and Dry Contacts on the UIM ........................................... 44

  • TP48300B-N04C2

    User Manual Contents

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. vi

    D Acronyms and Abbreviations.................................................................................................. 46

  • TP48300B-N04C2

    User Manual 1 Overview

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 1

    1 Overview 1.1 Introduction

    The TP48300B-N04C2 is an indoor communications power system that converts AC power

    into stable DC power and supplies power to and backs up power for 48 V DC communications equipment with a maximum output current of 300 A.

    Figure 1-1 shows a TP48300B-N04C2.

    Figure 1-1 TP48300B-N04C2

    1.2 Features Wide voltage range of 85 V AC to 300 V AC

    Comprehensive battery management

  • TP48300B-N04C2

    User Manual 1 Overview

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 2

    Comprehensive AC and DC surge protection design

    Network application over a fast Ethernet (FE) port and an RS485/RS232 port

    Communication with Huawei NetEco or third-party element management systems over

    protocols such as the Simple Network Management Protocol (SNMP) and Hypertext

    Transfer Protocol (HTTPS) to enable remote management and unattended working.

    NetEco is Huawei iManager NetEco data center infrastructure management system.

    Liquid crystal display (LCD) for display and operations

    Web user interface (WebUI) for display and operations

    Display in multiple optional languages, such as English, Chinese, Spanish, Portuguese,

    Italian, and Russian

    Hot swapping of rectifiers and site monitoring units (SMUs)

    Rectifier power factor up to 0.99

    Rectifier efficiency up to 96%

    1.3 Working Principle

    Figure 1-2 shows the conceptual diagram for TP48300B-N04C2.

    AC power enters rectifiers through the AC power distribution unit (PDU). The rectifiers

    convert the AC power input into -48 V DC power output, which is directed by the DC PDU to

    DC loads along different routes.

    When the AC power is normal, rectifiers power DC loads and charge batteries. When the AC

    power is absent, rectifiers stop working and batteries start to power loads. After the AC power

    resumes, rectifiers power DC loads and charge batteries again.

    The SMU monitors the operating status of each component in the power system in real time

    and performs appropriate intelligent control. When detecting a fault, the SMU generates an

    alarm. The SMU monitors and regulates the temperature control unit based on the temperature

    measured by the temperature sensor to ensure the normal operating temperature for the

    cabinet.

  • TP48300B-N04C2

    User Manual 1 Overview

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 3

    Figure 1-2 Conceptual diagram

    1.4 System Configuration

    Table 1-1 describes the TP48300B-N04C2 components.

    Table 1-1 Components

    Component TP48300B-N04C2

    Rectifier Two to six R4850G2s or R4830G2s

    SMU SMU02B

    User interface module

    (UIM)

    UIM02C

    Sensor Required: one battery temperature sensor

    Optional: one smoke sensor, one temperature and humidity

    sensor, one water sensor, one door status sensor, and two

    ambient temperature sensors

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 4

    2 Components 2.1 Interior

    Figure 2-1 shows the TP48300B-N04C2 interior.

    Figure 2-1 TP48300B-N04C2 interior

    (1) RTN+ busbar (2) Battery circuit breakers (3) Battery low voltage

    disconnection (BLVD)

    circuit breakers

    (4) AC input circuit breakers (5) AC input N terminal (6) Surge protective

    device (SPD)

    (7) SMU (8) Space for installing

    rectifiers

    (9) Load low voltage

    disconnection (LLVD)

    circuit breakers

    (10) UIM

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 5

    2.2 PDU

    Figure 2-2 and Figure 2-3 respectively show the AC PDU and DC PDU for the TP48300B-

    N04C2. Table 2-1 lists the power distribution specifications.

    Figure 2-2 AC PDU

    (1) AC input circuit

    breakers

    (2) AC input N terminal (3) SPD

    Figure 2-3 DC PDU

    (1) Battery circuit breakers (2) BLVD circuit breakers (3) LLVD circuit breakers

    Table 2-1 Power distribution specifications

    Item TP48300B-N04C2

    Input system 220/380 V AC three-phase, four-wire

    AC input circuit

    breaker

    One 3-pole 63 A circuit breaker

    Battery branch Four 1-pole 125 A circuit breakers

    DC load branch BLVD: one 1-pole 32 A circuit breaker, two 1-pole 16 A

    circuit breakers, and one 63 A circuit breaker. Space for

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 6

    Item TP48300B-N04C2

    installing two 1-pole circuit breakers of 63 A or less is

    reserved.

    LLVD: two 1-pole 80 A circuit breakers and one 1-pole 100

    A circuit breaker. Space for installing five 1-pole circuit

    breakers of 63 A or less is reserved.

    AC surge protection Level C

    NOTE

    The power distribution for the TP48300B-N04C2 can be flexibly configured. For standard configuration,

    six positions are for the BLVD and ten positions are for the LLVD (BLVD + LLVD = 6P + 10P). For optional configurations, ten positions are for the BLVD and six positions are for the LLVD (BLVD +

    LLVD = 6P + 10P). For the LLVD, a maximum of extra 12 positions can be added.

    2.2.2 Battery Switch

    Figure 2-4 Battery switch

    (1) Battery switch

    The battery switch is in the AUTO position by default before delivery, meaning the system

    is under automatic control.

    Open the panel and flip the battery switch to MANUAL only when you need to enable the

    battery power supply for commissioning. Remember to flip the battery switch back to

    AUTO after the commissioning.

    2.3 Rectifier

    Appearance

    Figure 2-5 shows a rectifier R4850G2/R4830G2.

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 7

    Figure 2-5 R4850G2/R4830G2

    Panel

    The front panel provides a power indicator, an alarm indicator, and a fault indicator. Figure 2-

    6 shows the rectifier front panel. Table 2-2 describes the indicators on the panel.

    Figure 2-6 R4850G2/R4830G2 panel

    (1) Power indicator (2) Alarm indicator (3) Fault indicator

    (4) Latch (5) Handle

    Table 2-2 Indicator description

    Indicator Color Status Description

    Power indicator Green Steady on The rectifier has an AC power

    input.

    Off The rectifier has no AC power

    input.

    The rectifier is faulty.

    Blinking at

    0.5 Hz

    The rectifier is being queried.

    Blinking at 4 The rectifier is loading an

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 8

    Indicator Color Status Description

    Hz application program.

    Alarm indicator Yellow Off No alarm is generated.

    Steady on The rectifier generates an alarm

    for power limiting due to ambient

    overtemperature.

    The rectifier generates an alarm

    for shutdown due to ambient

    overtemperature or

    undertemperature.

    The rectifier protects against AC

    input overvoltage or undervoltage.

    The rectifier is hibernating.

    Blinking at

    0.5 Hz

    The communication between the

    rectifier and the SMU is

    interrupted.

    Fault indicator Red Off The rectifier is running properly.

    Steady on The rectifier locks out due to

    output overvoltage.

    The rectifier has no output due to

    an internal fault.

    2.4 SMU

    Appearance

    Figure 2-7 shows an SMU02B.

    Figure 2-7 SMU02B

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 9

    Panel

    Figure 2-8 shows the SMU02B panel.

    Figure 2-8 SMU02B panel

    (1) Run indicator (2) Minor alarm indicator (3) Major alarm indicator

    (4) Button (5) USB port (reserved) (6) RS485/RS232 port

    (7) Handle (8) Locking latch (9) FE port

    (10) LCD

    Indicators

    Table 2-3 describes the indicators on the SMU02B panel.

    Table 2-3 SMU02B indicators

    Name Color Status Description

    Run indicator Green Off The SMU is faulty or has no

    DC input.

    Blinking at 0.5

    Hz

    The SMU02B is running

    properly and communicating

    with the host properly.

    Blinking at 4 Hz The SMU02B is running

    properly but is not

    communicating with the host

    properly.

    Minor alarm

    indicator

    Yellow Off The SMU does not generate

    any minor alarms.

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 10

    Name Color Status Description

    Steady on The SMU generates a minor

    alarm.

    Major alarm

    indicator

    Red Off No critical or major alarm is

    generated.

    Steady on A critical or major alarm is

    generated.

    Buttons

    Table 2-4 describes the buttons on the SMU02B panel.

    Table 2-4 SMU02B buttons

    Button Name Description

    Up Scrolls up menus or sets parameter values.

    Down Scrolls down menus or sets parameter values.

    Back Returns to the upper-level menu without saving

    the settings.

    Confirm Enters the main menu from the standby

    screen.

    Enters a submenu from the main menu.

    Saves the menu settings.

    Note:

    After a menu is displayed, the standby screen is displayed and the LCD screen becomes

    dark if you do not press any button within 5 minutes.

    You need to log in again if you do not press any button within 8 minutes.

    The preset user name is admin, and the preset password is 000001.

    Communications Ports

    Table 2-5 describes the communications ports on the SMU02B panel.

    Table 2-5 SMU02B communications ports

    Port Parameter Protocol

    FE port 10/100M auto-adaptation HTTPS, SNMP, and Huawei

    NetEco protocols

    RS485/RS232 port Baud rate: 9600 bit/s Huawei master/slave

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 11

    Port Parameter Protocol

    protocols

    Note:

    All these ports support the security mechanism.

    Figure 2-9 Pins in the FE port and RS485/RS232 port

    Table 2-6 Pin definitions for the FE port

    Pin Signal Description

    1 TX+ Sends data over the FE.

    2 TX-

    3 RX+ Receives data over the FE.

    6 RX-

    4, 5, 7, and 8 None None

    Table 2-7 Pin definitions for the RS485/RS232 port

    Pin Signal Description

    1 TX+ Sends data over RS485.

    2 TX-

    4 RX+ Receives data over RS485.

    5 RX-

    3 RX232 Receives data over RS232.

    7 TX232 Sends data over RS232.

    6 PGND Connects to the ground.

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 12

    Pin Signal Description

    8 None None

    2.5 UIM

    Panel

    The UIM02C provides eight dry contact outputs, six Boolean value inputs, and seven sensor

    ports.

    Figure 2-10 shows the UIM02C panel.

    Figure 2-10 UIM02C panel

    Ports

    Table 2-8 UIM02C ports

    Port Type Silk Screen Description

    Sensor port TEM-HUM Temperature and humidity sensor

    WATER Water sensor

    TEMP1 Ambient temperature sensor 1

    TEMP2 Ambient temperature sensor 2

    GATE Door status sensor

    SMOKE Smoke sensor

    BTEMP Battery temperature sensor

    Boolean value

    signal port

    NOTE

    For the associations

    between the

    Boolean value

    DIN1 Boolean value input 1.

    DIN2 Boolean value input 2

    DIN3 Boolean value input 3

    DIN4 Boolean value input 4

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 13

    Port Type Silk Screen Description

    signal ports and

    alarms, see the

    appendix.

    DIN5 Boolean value input 5

    DIN6 Boolean value input 6

    Dry contact

    NOTE

    For the associations

    between the dry

    contacts and

    alarms, see the

    appendix.

    ALM1 Dry contact output 1

    ALM2 Dry contact output 2

    ALM3 Dry contact output 3

    ALM4 Dry contact output 4

    ALM5 Dry contact output 5

    ALM6 Dry contact output 6

    ALM7 Dry contact output 7

    ALM8 Dry contact output 8

    Communication

    port

    COM port RS485 port

    Pins

    Figure 2-11 shows the pin numbers of the sensor ports. Table 2-9 defines the pins.

    Figure 2-11 UIM02C pin numbers

  • TP48300B-N04C2

    User Manual 2 Components

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 14

    Table 2-9 UIM02C pin definitions

    Silkscreen No. Pin Definition

    TEM-HUM 1 12 V

    2 ENV_TEMP

    3 12 V

    4 ENV_HUM

    WATER 1 12 V

    2 WATER

    3 GND

    4 None

    TEMP1 1 TEMP1

    2 GND

    TEMP2 1 TEMP2

    2 GND

    GATE 1 DIN7+

    2 JTD7

    SMOKE 1 12 V

    2 SMOKE

    BTEMP 1 BTEM1

    2 GND

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 15

    3 Safety Precautions 3.1 Health and Safety

    3.1.1 Overview

    Introduction

    This section describes the safety precautions you must take before installing or maintaining

    Huawei equipment.

    To ensure safety of humans and the equipment, pay attention to the safety symbols on the

    equipment and all the safety instructions in this document.

    The "NOTE", "CAUTION", and "WARNING" marks in this document do not represent

    all the safety instructions. They are only supplements to the safety instructions.

    Installation and maintenance personnel must understand basic safety precautions to avoid

    hazards.

    When operating Huawei equipment, in addition to following the general precautions in

    this document, follow the specific safety instructions given by Huawei.

    Only trained and qualified personnel are allowed to install, operate, and maintain Huawei

    equipment.

    Local Safety Regulations

    When operating Huawei equipment, you must follow the local laws and regulations. The

    safety instructions in this document are only supplements to the local laws and regulations.

    General Requirements

    To minimize risk of personal injury and damage to equipment, read and follow all the

    precautions in this document before performing any installation or maintenance.

    Ensure that the instructions provided in this document are followed completely. This section

    also provides guidelines for selecting the measuring and testing devices.

    Installation The device (or system) must be installed in an access-controlled location.

    The device can be mounted only on concrete or non-combustible surfaces.

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 16

    The device must be fixed securely on the floor or to other immovable objects such as

    walls and mounting racks before operation.

    When installing the unit, always make the ground connection first and disconnect it at

    the end.

    Do not block the ventilation while the device is operating. Keep a minimum distance of 5

    cm between the device and the wall or other objects that may block the ventilation.

    Tighten the thumbscrews by using a tool after initial installation and subsequent access

    to the panel.

    Ground Do not damage the ground conductor or operate the device in the absence of a properly

    installed ground conductor. Conduct the electrical inspection carefully.

    The device (or system) must be connected permanently to the protection ground before

    an operation. The cross-sectional area of the protective ground conductor must be at least

    10 mm2.

    Power Supply For AC-supplied models: The device applies to TN, TT, or IT power system.

    For DC-supplied models: Reinforced insulation or double insulation must be provided to

    isolate the DC source from the AC mains supply.

    For DC-supplied model: The device applies to DC power source that complies with the

    Safety Extra-Low Voltage (SELV) requirements in IEC 60950-1 based safety standards.

    Prepared conductors are connected to the terminal block, and only the appropriate

    AWG/Type of wire is secured with the lug terminals.

    Human Safety Do not operate the device or cables during lightning strikes.

    Remove the AC power connector when there is lightning. Do not use fixed terminals or

    touch terminals or antenna connectors when there is lightning.

    To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to

    telecommunication network voltage (TNV) circuits.

    Move or lift the chassis by holding its lower edge. Do not hold the handles on certain

    modules such as power supply, fans, and boards because they cannot support the weight

    of the device.

    At least two persons are required to lift the chassis. When lifting it, keep your back

    straight and move stably.

    Do not wear jewelry or watches when you operate the device.

    Operator Only qualified professional personnel are allowed to install, configure, operate, and

    disassemble the device.

    Only the personnel authenticated or authorized by Huawei are allowed to replace or

    change the device of the parts of the device (including the software).

    Any fault or error that might cause safety problems must be reported immediately to a

    supervisor.

    Only qualified personnel are allowed to remove or disable the safety facilities and to

    troubleshoot and maintain the device.

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 17

    3.1.2 Electrical Safety

    High Voltage

    The high voltage power supply provides power for the device operation. Direct or indirect

    contact (through damp objects) with high voltage and AC mains supply may result in serious

    injuries.

    During the installation of the AC power supply facility, follow the local safety

    regulations. The personnel who install the AC facility must be qualified to perform high

    voltage and AC operations.

    Do not wear conductive articles, such as watches, hand chains, bracelets, and rings

    during the operation.

    When water is found in the rack or the rack is damp, switch off the power supply

    immediately.

    When the operation is performed in a damp environment, make sure that the device is

    dry.

    Non-standard and improper high voltage operations may result in fire and electric shock.

    Therefore, you must abide by the local rules and regulations when bridging and wiring AC

    cables. Only qualified personnel are allowed to perform high voltage and AC operations.

    Before powering on a device, ground the device. Otherwise, personal injury or device damage

    may be caused by high leakage current.

    Tools

    Dedicated tools must be used during high voltage and AC operations. Avoid using ordinary

    tools.

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 18

    High Electrical Leakage

    Ground the device before powering it on. Otherwise, personal injury or device damage may

    be caused by high leakage current.

    If a "high electrical leakage" tag is present on the power terminal of the device, you must

    ground the device before powering it on.

    3.1.3 Inflammable Environment

    Operating the electrical device in an inflammable environment can be fatal.

    Do not place the device in an environment that has inflammable and explosive air or gas. Do

    not perform any operation in this environment.

    3.1.4 Battery

    Storage Battery

    Before operating storage batteries, carefully read the safety precautions for battery handling

    and connection.

    Improper handling of storage batteries causes hazards.

    When operating storage batteries, avoid short circuit and overflow or leakage of the

    electrolyte. Electrolyte overflow may damage the device. It will corrode metal parts and

    circuit boards, and ultimately damage the device and cause short circuit of circuit boards.

    Basic Precautions

    Before installing and maintaining the battery, note the following:

    Do not wear metal articles such as wristwatch, hand chain, bracelet, and ring.

    Use special insulation tools.

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 19

    Take care to protect your eyes when operating the device.

    Wear rubber gloves and a protective coat in case of electrolyte overflow.

    When handling a storage battery, ensure that its electrodes are upward. Leaning or

    reversing the storage battery is prohibited.

    Short Circuit

    Battery short circuit may cause human injuries. Although the voltage of ordinary batteries is

    low, the instantaneous high current caused by the short circuit releases a great deal of energy.

    There is danger of explosion if the battery is incorrectly replaced. Therefore, replace the

    battery only with the same or equivalent type recommended by the manufacturer.

    Keep away metal objects, which may cause battery short circuit, from batteries. If metal

    objects must be used, first disconnect the batteries in use before performing any other

    operations.

    Hazardous Gas

    Do not use unsealed lead acid storage batteries. Lead acid storage batteries must be placed

    horizontally and stably to prevent the batteries from releasing flammable gas, which may

    cause fire or erode the device.

    Lead acid storage batteries in use emit flammable gas. Therefore, ventilation and

    fireproofing measures must be taken at the sites where lead acid storage batteries are used.

    Battery Temperature

    If a battery overheats, the battery may be deformed or damaged, and the electrolyte may

    overflow.

    When the temperature of the battery is higher than 60, check the battery for electrolyte overflow. If the electrolyte overflows, absorb and counteract the electrolyte immediately.

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 20

    Battery Leakage

    If the electrolyte overflows, absorb and counteract the electrolyte immediately.

    When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte

    may hurt human bodies. When you find the electrolyte leaks, use the following substances to

    counteract and absorb the leaking electrolyte:

    Sodium bicarbonate (baking soda): NaHCO3

    Sodium carbonate (soda): Na2CO3

    Select a substance to counteract and absorb the leaking electrolyte according to the

    instructions of the battery manufacturer.

    3.1.5 Mechanical Safety

    Drilling Holes

    Do not drill the cabinet at will. Drilling holes without complying with the requirements affects

    the electromagnetic shielding performance of the cabinet and damages the cables inside the

    cabinet. In addition, if the scraps caused by drilling enter the cabinet, the printed circuit

    boards (PCBs) may be short circuited.

    Before you drill a hole in the cabinet, wear insulated gloves and remove the internal

    cables from the cabinet.

    Wear an eye protector when drilling holes. This is to prevent your eyes from being

    injured by the splashing metal scraps.

    Ensure that the scraps caused by drilling do not enter the cabinet.

    Drilling holes without complying with the requirements affects the electromagnetic

    shielding performance of the cabinet.

    After drilling, clean the metal scraps immediately.

    Sharp Objects

    Before you hold or carry a device, wear protective gloves to avoid getting injured by sharp

    edges of the device.

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 21

    Handling Fans

    When handling fans, note the following:

    When replacing a component, place the component, screws, and tools in a safe place.

    Otherwise, if any of them fall into the operating fans, the fans may be damaged.

    When replacing a component near fans, do not insert your fingers or boards into the

    operating fans until the fans are switched off and stops running.

    Lifting Heavy Objects

    When heavy objects are being lifted, do not stand or walk under the cantilever or the lifted

    object.

    3.1.6 Bundling Signal Cables

    Do not bundle signal cables with high current cables or high voltage cables.

    Maintain a minimum space of 150 mm between adjacent ties.

    3.2 Equipment Safety

    3.2.1 Electricity Safety

    High Electrical Leakage

    If a "high electrical leakage" tag is present on the power terminal of the device, you must

    ground the device before powering it on.

    3.2.2 Electrostatic Discharge

  • TP48300B-N04C2

    User Manual 3 Safety Precautions

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 22

    The static electricity generated by human bodies may damage the electrostatic-sensitive

    components on boards, for example, the large-scale integrated (LSI) circuits.

    Human body movement, friction between human bodies and clothes, friction between shoes

    and floors, or handling of plastic articles causes static electromagnetic fields on human bodies.

    These static electromagnetic fields cannot be eliminated until the static is discharged.

    To prevent electrostatic-sensitive components from being damaged by the static on human

    bodies, you must wear a well-grounded electrostatic discharge (ESD) wrist strap when

    touching the device or handling boards or application-specific integrated circuits (ASICs).

    Figure 3-1 shows how to wear an ESD wrist strap.

    Figure 3-1 Wearing an ESD wrist strap

    3.2.3 Laying Out Cables

    When the temperature is very low, violent strike or vibration may damage the cable sheathing.

    To ensure safety, comply with the following requirements:

    Cables can be laid or installed only when the temperature is higher than 0.

    Before laying out cables which have been stored in a temperature lower than 0, move the cables to an environment of the ambient temperature and store them at the ambient

    temperature for at least 24 hours.

    Handle cables with caution, especially at a low temperature. Do not drop the cables

    directly from the vehicle.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 23

    4 Maintenance 4.1 Routine Maintenance

    Routine maintenance is required periodically based on site requirements. The recommended

    maintenance interval is six months. If any fault is detected, rectify without any delay.

    Table 4-1 Routine maintenance checklist

    Item

    Maintenance Task

    Check That... By... If... Do...

    Cabinet door

    lock

    The door lock is

    proper.

    Observing, and

    locking and

    unlock the door

    The door lock

    fails.

    Replace the

    door lock.

    Fan No thick dust

    accumulates on

    the fan surface.

    Observing Thick dust

    accumulates on

    the fan surface.

    Clean up the

    dust from the

    fan.

    The fan is

    intact, and the

    rotational

    speed, noise,

    and vibration

    are within their

    normal ranges.

    Observing and

    listening

    The fan is

    damaged, the

    noise is too

    loud, or the

    vibration is

    abnormal.

    Replace the fan.

    Electrical

    connection

    The output

    voltage is

    normal.

    Using a

    multimeter

    The BLVD or

    LLVD voltage

    exceeds its

    threshold.

    For details, see

    Handling

    Alarms.

    Preventive

    inspection

    Indicators are

    normal.

    Observing An alarm is

    generated.

    Appearance The paint or the

    electroplated

    coating on the

    cabinet is

    flaking off or

    scratches occur.

    Observing The surface is

    damaged or

    distorted.

    Repaint or

    repair the shell.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 24

    Item

    Maintenance Task

    Check That... By... If... Do...

    Grounding The ground

    point connects

    to the ground

    bar in the

    equipment

    room properly.

    Observing, and

    using tools such

    as a screw

    driver or

    wrench

    The cable

    connecting the

    ground point

    and the ground

    bar in the

    equipment

    room is loose or

    damaged.

    Secure or

    replace the

    cable.

    4.2 Handling Alarms

    4.2.1 Mains Failure

    Possible Causes The AC input power cable is faulty.

    The AC input circuit breaker is OFF.

    The mains grid is faulty.

    Measures

    1. Check whether the AC input cable is loose. If yes, secure the AC input cable.

    2. Check whether the AC input circuit breaker is OFF. If yes, handle the back-end circuit failure and then switch on the circuit breaker.

    3. Check whether the AC input voltage is lower than 50 V AC. If yes, handle the mains grid fault.

    4.2.2 AC Over Volt

    Possible Causes The AC overvoltage alarm threshold is not set properly on the SMU.

    The power grid is faulty.

    Measures

    1. Check whether the AC overvoltage alarm threshold is properly set. If no, adjust it to a proper value.

    2. Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V AC by default). If yes, handle the AC input fault.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 25

    4.2.3 AC Under Volt

    Possible Causes The AC undervoltage alarm threshold is incorrectly set on the SMU.

    The power grid is faulty.

    Measures

    1. Check whether the AC undervoltage alarm threshold is correctly set. If no, adjust it to an appropriate value.

    2. Check whether the AC input voltage is below the AC undervoltage alarm threshold (180 V AC by default). If yes, handle the AC input fault.

    4.2.4 Phase A/B/C Failure

    Possible Causes The AC input power cable is faulty.

    The rectifier is in poor contact.

    The monitoring unit is faulty.

    Measures

    1. Check whether the AC input power cable is correctly and securely installed. If no, reinstall the cable. If the insulation layer deteriorates, replace the cable.

    2. Check whether a short circuit occurs in the AC input power cable or the insulation layer is damaged. If yes, replace the cable.

    3. If the AC input is normal and the Alarm indicators on certain rectifiers are steady yellow, reinstall the rectifiers.

    4. If the alarm persists, replace the monitoring unit.

    4.2.5 DC Over Volt

    Possible Causes The DC overvoltage alarm threshold is incorrectly set on the SMU.

    Rectifiers are faulty.

    The power system voltage is set too high in manual mode.

    Measures

    1. Check whether the DC overvoltage alarm threshold is correctly set. If no, adjust it to an appropriate value.

    2. Remove the rectifiers one by one and check whether the alarm is cleared. If the alarm still exists, reinstall the rectifier. If the alarm is cleared, replace the rectifier.

    3. Check whether the system voltage is set too high in manual mode. If yes, confirm the reason and adjust the voltage to a proper value after the operation.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 26

    4.2.6 DC Under Volt

    Possible Causes An AC power failure has occurred.

    The DC undervoltage alarm threshold is incorrectly set on the SMU.

    Rectifiers are faulty.

    The system configuration is not appropriate.

    The power system voltage is set too low in manual mode.

    Measures

    1. Check whether an AC power failure has occurred. If yes, resume the AC power supply.

    2. Check whether the DC undervoltage alarm threshold is correctly set. If no, adjust it to an appropriate value.

    3. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier.

    4. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power.

    5. Check whether the system voltage is set too low in manual mode. If yes, confirm the reason and adjust the voltage to a proper value after the operation.

    4.2.7 Batt Over Curr

    Possible Causes The rectifier communication is interrupted.

    The SMU is in poor contact.

    The SMU is faulty.

    Measures

    1. Check whether an alarm is generated for rectifier communication interruption. If yes, remove the rectifier and reinstall it to check whether the alarm is cleared. If the alarm

    still exists, replace the rectifier.

    2. Remove the SMU and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the SMU.

    4.2.8 Load Off

    Possible Causes An AC power failure has occurred.

    Loads are manually disconnected.

    The load disconnection voltage is set too high on the SMU.

    Rectifiers are faulty.

    The AC phase has failed.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 27

    Measures

    1. Check whether an AC power failure has occurred. If yes, resume the AC power supply.

    2. Check whether loads are manually disconnected. If yes, confirm the reason of the manual disconnection, and reconnect the loads after the operation.

    3. Check whether the load disconnection voltage is set too high on the SMU. If yes, adjust it to a proper value.

    4. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier.

    5. Check whether there is AC phase failure alarm. If yes, resume the normal AC input.

    4.2.9 Batt Off

    Possible Causes An AC power failure has occurred.

    Batteries are manually disconnected.

    The battery disconnection voltage is set too high on the SMU.

    Rectifiers are faulty.

    The system configuration is not appropriate.

    Measures

    1. Check whether an AC power failure has occurred. If yes, resume the AC power supply.

    2. Check whether batteries are manually disconnected. If yes, confirm the reason of the manual disconnection, and reconnect the batteries after the operation.

    3. Check whether the battery disconnection voltage is set too high on the SMU. If yes, adjust it to an appropriate value.

    4. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier.

    5. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power.

    4.2.10 Batt Loop Trip

    Possible Causes The battery fuse detection cable is disconnected.

    The battery circuit breaker has tripped or battery fuse is blown.

    The contactor is faulty.

    Measures

    1. Check whether the battery fuse detection cable is disconnected. If yes, reconnect the cable.

    2. Check whether the battery circuit breaker has tripped or battery fuse is blown. If yes, rectify the battery loop fault and then switch on the circuit breaker or replace the fuse.

    3. Manually switch on or switch off the battery contactor and check whether the battery current changes accordingly. If no, replace the contactor.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 28

    4.2.11 Amb. Over Temp

    This alarm is generated only for the power system that has ambient temperature sensors installed.

    Possible Causes The ambient overtemperature alarm threshold is incorrectly set on the SMU.

    The temperature control system is faulty in the cabinet where the ambient temperature

    sensor is located.

    The ambient temperature sensor is faulty.

    Measures

    1. Check whether the ambient temperature alarm threshold is correctly set on the SMU. If no, adjust it based on site requirements.

    2. Check whether the temperature control system in the cabinet is faulty. If yes, rectify the fault. The alarm is cleared when the cabinet temperature falls within the allowed range.

    3. Check whether the ambient temperature sensor is faulty. If yes, replace the temperature sensor.

    4.2.12 Amb. Under Temp

    This alarm is generated only for the power system that has ambient temperature sensors installed.

    Possible Causes The ambient undertemperature alarm threshold is incorrectly set on the SMU.

    The temperature control system is faulty in the cabinet where the ambient temperature

    sensor is located.

    The ambient temperature sensor is faulty.

    Measures

    1. Check whether the ambient undertemperature alarm threshold is correctly set on the SMU. If no, adjust it based on site requirements.

    2. Check whether the temperature control system in the cabinet is faulty. If yes, rectify the fault. The alarm is cleared when the cabinet temperature falls within the allowed range.

    3. Check whether the ambient temperature sensor is faulty. If yes, replace the ambient temperature sensor.

    4.2.13 Amb. Over Humi

    This alarm is generated only for the power system that has humidity sensors installed.

    Possible Causes The ambient overhumidity alarm threshold is incorrectly set on the SMU.

    The humidity is too high in the cabinet where the humidity sensor is located.

    The humidity sensor is faulty.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 29

    Measures

    1. Check whether the ambient overhumidity alarm threshold is correctly set on the SMU. If no, adjust it based on site requirements.

    2. Check whether water intrudes into the cabinet. If yes, wipe the water with dry cotton or other tools and rectify the fault.

    3. Check whether the humidity sensor is faulty. If yes, replace the humidity sensor.

    4.2.14 Amb. Under Humi

    This alarm is generated only for the power system that has humidity sensors installed.

    Possible Causes The ambient underhumidity alarm threshold is incorrectly set on the SMU.

    The humidity is too low in the cabinet where the humidity sensor is located.

    The humidity sensor is faulty.

    Measures

    1. Check whether the ambient underhumidity alarm threshold is correctly set on the SMU. If no, adjust it based on site requirements.

    2. Check whether the cabinet humidity is too low. If yes, adjust the cabinet humidity. The alarm is cleared when the humidity falls within the allowed range.

    3. Check whether the humidity sensor is faulty. If yes, replace the humidity sensor.

    4.2.15 Batt Over Temp

    Possible Causes The battery overtemperature alarm threshold is incorrectly set on the SMU.

    The battery compartment heat dissipation system is faulty.

    The battery temperature sensor is faulty.

    Measures

    1. Check whether the battery overtemperature alarm threshold is correctly set. If no, adjust it to a proper value.

    2. Check whether the battery compartment heat dissipation system is faulty. If yes, rectify the fault. The alarm is cleared when the battery temperature falls within the allowed

    range.

    3. Check whether the battery temperature sensor is faulty. If yes, replace the temperature sensor.

    4.2.16 Batt Under Temp

    Possible Causes The battery undertemperature alarm threshold is incorrectly set on the SMU.

    The battery compartment heating system is faulty.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 30

    The battery temperature sensor is faulty.

    Measures

    1. Check whether the battery undertemperature alarm threshold is correctly set. If no, adjust it to a proper value.

    2. Check whether the battery compartment heating system is faulty. If yes, rectify the fault. The alarm is cleared when the battery temperature falls within the allowed range.

    3. Check whether the battery temperature sensor is faulty. If yes, replace the temperature sensor.

    4.2.17 Rectifier Lost

    Possible Causes Certain rectifiers are not powered on.

    The rectifier is faulty.

    The subrack or slot connector is faulty.

    The monitoring unit is faulty.

    Measures

    1. Check whether the circuit breakers corresponding to undetected rectifiers are ON. If no, switch them on.

    2. Check whether the rectifier has been removed. If yes, find the cause and reinstall it.

    3. Replace the rectifier if it is faulty.

    4. Check whether certain rectifiers in the rectifier subrack do not work properly. If yes, remove the rectifiers that do not work and check whether their slot connectors are

    damaged or deformed. If yes, repair or replace the subrack or slot connectors.

    5. If the alarm persists after the preceding measures are taken and the monitoring unit is restarted, replace the monitoring unit.

    4.2.18 Rect Fault

    Possible Causes The rectifier is in poor contact.

    The rectifier is faulty.

    Measures

    1. Check the Fault indicator on the rectifier panel. If it is steady red, remove the rectifier, and then reinstall it after the indicator turns off.

    2. If the alarm still exists, replace the rectifier.

    4.2.19 Rect Protect

    Possible Causes The rectifier input voltage is too high.

    The rectifier input voltage is too low.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 31

    The ambient temperature is too high.

    The rectifier is faulty.

    Measures

    1. Check whether the AC input voltage exceeds the upper threshold of the rectifier working voltage. If yes, rectify the power supply fault and then resume the power supply.

    2. Check whether the AC input voltage is below the lower threshold of the rectifier working voltage. If yes, rectify the power supply fault and then resume the power supply.

    3. Check whether the ambient temperature is higher than the normal operating temperature of the rectifier. If yes, rectify the temperature unit fault.

    4. Remove the rectifier that generates the alarm and reinstall it after the indicator turns off. If the alarm still exists, replace the rectifier.

    4.2.20 Rect Comm Fault

    Possible Causes The rectifier has been removed.

    The rectifier is in poor contact.

    The rectifier is faulty.

    Measures

    1. Check whether the rectifier has been removed. If yes, reinstall it.

    2. If the rectifier is in position, remove the rectifier and reinstall it.

    3. If the alarm still exists, replace the rectifier.

    4.2.21 Load Fuse Trip

    Possible Causes The load circuit breaker has tripped or fuse is blown.

    The load fuse detection cable is disconnected.

    Measures

    1. Check whether the load circuit breaker has tripped or fuse is blown. If yes, rectify the back-end circuit fault and then switch on the circuit breaker or replace the fuse.

    2. Check whether the load fuse detection cable is disconnected. If yes, reconnect the cable.

    4.2.22 AC SPD Alarm

    Possible Causes The AC SPD is faulty.

    The AC SPD detection cable is disconnected.

    Measures

    1. Check whether the AC SPD indication window is red. If yes, replace the SPD.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 32

    2. Check whether the AC SPD detection cable is disconnected. If yes, reconnect the cable.

    4.2.23 DC SPD Alarm

    Possible Causes The DC SPD detection cable is disconnected.

    The DC SPD is faulty.

    Measures

    1. Check whether the DC SPD detection cable is disconnected. If yes, reconnect the cable.

    2. If the DC SPD detection cable is not disconnected, replace the DC SPD.

    4.3 Identifying Component Faults

    4.3.1 Identifying Rectifier Faults

    A rectifier is damaged if any of the following conditions is not met:

    When the rectifier does not communicate with the SMU and the AC input voltage is

    around 220 V, the green indicator on the rectifier is steady on and the other indicators are

    off. The rectifier output is normal.

    The SMU can perform equalized charging, float charging, and current limiting control

    for the rectifier when the communication cable to the rectifier is correctly connected and

    communication is established between the rectifier and the SMU.

    4.3.2 Identifying SMU Faults

    The following are the main symptoms of SMU faults.

    The DC output is normal while the green indicator on the SMU is off.

    The SMU breaks down or cannot be started. Its LCD has abnormal display or buttons

    cannot be operated.

    With the alarm reporting enabled, the SMU does not report alarms when the power

    system is faulty.

    The SMU reports an alarm while the power system does not experience the fault.

    The SMU fails to communicate with the connected lower-level devices while the

    communications cables are correctly connected.

    Communication between the SMU and all rectifiers fails while both the rectifiers and the

    communications cables are normal.

    The SMU cannot detect the DC power distribution while the communications cables and

    the DC power distribution is normal.

    Parameters cannot be set or running information cannot be viewed on the SMU.

    4.3.3 Identifying AC SPD Faults

    Check the color of the SPD indication window. Green indicates that the SPD is normal. Red

    indicates the SPD is faulty.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 33

    4.3.4 Identifying Circuit Breaker Faults

    The following are the main symptoms of circuit breaker faults.

    The circuit breaker cannot be switched ON/OFF after the short circuit fault for its end

    circuit is rectified.

    When the circuit breaker is switched ON and its input voltage is normal, the voltage

    between the two ends of the circuit breaker exceeds 1 V.

    When the circuit breaker is switched OFF and its input voltage is normal, the resistance

    between the two ends of the circuit breaker is less than 1 k.

    4.4 Replacing Components

    Ensure that loads are supplied with power when replacing major components. For example,

    keep the circuit breakers for primary loads in the ON position, and do not disconnect both

    the battery input and AC input from the loads.

    Seek the customer's prior consent if load disconnection is required.

    Rectifiers and the SMU are hot-swappable.

    4.4.1 Replacing a Rectifier

    Prerequisites You have obtained a pair of protective gloves, the cabinet door key, and the maintenance

    tool box.

    The new rectifier is intact.

    Protect yourself from being burnt when removing the rectifier as it has a high temperature.

    Procedure

    Step 1 Push the locking latch on the right side of the panel towards the left.

    Step 2 Gently draw the handle outwards to unlock the rectifier, and remove the rectifier from the subrack, as shown in Figure 4-1.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 34

    Figure 4-1 Removing a rectifier

    Step 3 Push the locking latch on the new rectifier towards the left, and pull out the handle.

    Step 4 Place the new rectifier at the entry to the correct slot.

    Step 5 Gently slide the rectifier into the subrack along the guide rail, and lock the handle, as shown in Figure 4-2.

    Figure 4-2 Installing a rectifier

    ----End

    Follow-up Procedure

    Send the removed rectifier for repair.

    4.4.2 Replacing an SMU

    Prerequisites You have obtained the cabinet door key and maintenance tool box.

    The new SMU is intact.

    Procedure

    Step 1 Push the locking latch towards the left.

    Step 2 Draw the handle outwards to remove the SMU, as shown in Figure 4-3.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 35

    Figure 4-3 Removing an SMU

    Step 3 Insert the new SMU into its slot, push the locking latch towards the left, and pull out the handle.

    Step 4 Slide the new SMU into the subrack slowly along the guide rail, and push the locking latch towards the right.

    Step 5 Reset SMU parameters.

    Figure 4-4 Installing an SMU

    ----End

    Follow-up Procedure

    Send the removed SMU for repair.

    4.4.3 Replacing an AC SPD

    Prerequisites You have obtained an ESD wrist strap or a pair of ESD gloves, an ESD box or bag, the

    cabinet door key, and the maintenance tool box.

    The new AC SPD is intact and the indication window is green.

    Procedure

    Step 1 Hold down the faulty AC SPD and pull it out, as shown in Figure 4-5.

    Step 2 Install the new AC SPD, as shown in Figure 4-5.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 36

    Figure 4-5 Replacing an AC SPD

    ----End

    Follow-up Procedure

    Check that the alarm for the AC SPD is cleared.

    4.4.4 Replacing a Circuit Breaker

    Prerequisites

    Before replacing an AC circuit breaker, switch off the input circuit breaker on the upper-level

    device.

    You have obtained the cabinet door key, insulation tape, and maintenance tool box.

    The new circuit breaker is intact.

    Procedure

    Step 1 Switch off the circuit breaker that is to be replaced.

    Step 2 Loosen the screws that secure the output cables and signal cable terminals using a Phillips screwdriver and remove them. Wrap the cables and terminals using insulation tape to prevent

    hazards.

    Step 3 Loosen the screws that secure the input copper bars using a Phillips screwdriver and loosen the buckle at the circuit breaker base using an insulated flat-head screwdriver.

    Step 4 Remove the circuit breaker from the guide rail. Figure 4-6 shows the procedure for removing the circuit breaker.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 37

    Figure 4-6 Removing the circuit breaker

    Step 5 Switch off the new circuit breaker. Press the buckle at the circuit breaker base using an insulated flat-head screwdriver and install the new circuit breaker. Then loosen the buckle and

    secure the circuit breaker along the guide rail.

    Step 6 Tighten the screws that secure the input copper bars.

    Step 7 Remove the insulation tape from the output cables and signal cable terminals. Then connect the output cable and signal cable terminals to the output end of the circuit breaker and tighten

    the screws.

    Step 8 Switch on the circuit breaker. Figure 4-7 shows the procedure for installing the new circuit breaker.

    Figure 4-7 Installing the circuit breaker

    ----End

    4.4.5 Replacing a UIM

    Prerequisites You have obtained an ESD wrist strap, a pair of ESD gloves, an ESD box or bag, the

    cabinet door key, and the maintenance tool box.

  • TP48300B-N04C2

    User Manual 4 Maintenance

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 38

    The new UIM is intact.

    Procedure

    Step 1 Connect the ground cable to the ESD wrist strap and put on the ESD wrist strap and ESD gloves.

    Step 2 Remove the cover of UIM02C, as shown in Figure 4-8

    Step 3 Record the position where the UIM02C panel connects to the signal cable, and then disconnect the signal cable.

    Step 4 Unscrew the UIM02C panel and take out the UIM02C, as shown in Figure 4-8

    Figure 4-8 Taking out the UIM02C

    Step 5 Record the positions where the UIM02C backplane connects to all the cables, and then disconnect the cables.

    Step 6 Take out the new UIM02C and connect all the cables to the UIM02C backplane based on the recorded information.

    Step 7 Push in the UIM02C and tighten the screws.

    Step 8 Connect the signal cable to the UIM02C panel based on the recorded information.

    Step 9 Disconnect the ground cable from the ESD wrist strap and take off the ESD wrist strap and ESD gloves.

    ----End

    Follow-up Procedure

    Send the removed UIM02C for repair.

  • TP48300B-N04C2

    User Manual A Technical Specifications

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 39

    A Technical Specifications A.1 Environmental Specifications

    Table A-1 Environmental specifications

    Item Specifications

    Operating temperature 10C to +50C

    Transportation temperature 40C to +70C

    Storage temperature 40C to +70C

    Operating humidity 5%95% RH

    Storage humidity 5%95% RH

    Altitude 04000 m

    When the altitude ranges from 2000 m to 4000 m, the

    operating temperature decreases by 1C for each

    additional 200 m.

    A.2 Electrical Specifications

    Table A-2 Electrical specifications

    Item Specifications

    AC input Input system 220/380 V AC three-phase, four-wire

    Input frequency Frequency range: 4566 Hz; nominal frequency: 50 Hz or 60 Hz.

    Power factor 0.99 (load 50%)

    Total harmonic distortion

    (THD) 5% (load 50%)

    DC output Output voltage range 4258 V DC

  • TP48300B-N04C2

    User Manual A Technical Specifications

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 40

    Item Specifications

    Default output voltage 53.5 V DC

    Output power Maximum output power = Output power

    of a single rectifier x Number of

    rectifiers

    Regulated voltage

    precision

    1%

    Ripple and noise 200mVp-p

    Noise weighting 2 mV

    Imbalance of load sharing < 5% (20%100% load)

    AC input

    protection

    AC input overvoltage

    protection threshold

    > 300 V AC

    AC input overvoltage

    recovery threshold

    When the voltage is restored to 290 V

    AC, the output resumes.

    AC input undervoltage

    protection threshold

    < 85 V AC

    AC input undervoltage

    recovery threshold

    When the voltage is restored to 90 V AC,

    the output resumes.

    DC output

    protection

    DC output overvoltage

    protection threshold

    58.560.5 V DC

    If overvoltage occurs inside a rectifier

    due to a fault, the rectifier locks out.

    If the external voltage is higher than

    63 V for more than 500 ms, the

    rectifier locks out.

    AC surge

    protection

    Level C surge protection. The nominal lightning discharge current is

    20 kA (8/20 s), and the maximum one is 40 kA (8/20 s).

    DC surge

    protection

    Differential mode: 10 kA (8/20 s)

    Common mode: 20 kA (8/20 s)

    A.3 Safety and Regulatory Specifications

    Table A-3 Safety and regulatory specifications

    Item Specifications

    Safety and regulatory design Complies with IEC/EN60950-1.

    Mean time between failures

    (MTBF)

    200,000 hours

  • TP48300B-N04C2

    User Manual A Technical Specifications

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 41

    A.4 EMC Specifications

    Table A-4 EMC specifications

    Item Specifications

    Electromagnetic

    interference

    (EMI)

    Conducted emission (CE) AC power port: Class A

    DC power port: Class A

    Reference standard: EN55022

    Radiated interference Class A

    Reference standard: EN55022

    Harmonic IEC 61000-3-12

    Fluctuation and flicker IEC 61000-3-11

    Electromagnetic

    susceptibility

    (EMS)

    Electrostatic discharge

    (ESD)

    Cabinet port contact discharge: 6 kV

    (criterion B); air discharge: 8 kV

    (criterion B)

    Signal port contact discharge: 2 kV

    (criterion R)

    Electrical fast transient

    (EFT)

    Signal port: 1 kV

    AC power port: 2 kV

    DC Power port: 2 kV (criterion B)

    Radiated susceptibility (RS) Field strength: 10 V/m (criterion A)

    Conducted susceptibility

    (CS)

    Power port: 10 V

    Signal port: 3 V (criterion A)

    Surge immunity AC power port:

    Differential mode: 6 kV

    Common mode: 6 kV

    DC power port:

    Differential mode: 2 kV

    Common mode: 4 kV

    Signal port:

    Differential mode: 0.5 kV

    Common mode: 1 kV

    Voltage dips immunity

    (DIP)

    Complies with IEC 61000-4-11.

  • TP48300B-N04C2

    User Manual A Technical Specifications

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 42

    A.5 Cabinet Specifications

    Table A-5 Cabinet specifications

    Item Specifications

    Dimensions (H x W x D) 546 mm x 442 mm x 360 mm

    Weight 50 kg (without rectifiers)

    A.6 Rectifier Specifications

    Table A-6 Rectifier specifications

    Item R4850G2 R4830G2

    Efficiency > 96% (peak point)

    95% (230 V AC, 30%100% load)

    96% (peak point)

    95% (230 V AC, 45%80% load)

    Output power 3000 W (176290 V AC)

    1250 W (85175 V AC decreased linearly)

    2000 W (176300 V AC)

    840 W (85175 V AC decreased linearly)

    Dimensions

    (H x W x D)

    40.8 mm 105 mm 281 mm

    Weight 2 kg < 1.8 kg

  • TP48300B-N04C2

    User Manual B Electrical Conceptual Diagram

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 43

    B Electrical Conceptual Diagram Table B-1 Electrical conceptual diagram

  • TP48300B-N04C2

    User Manual

    C Associations Between Alarms and Dry Contacts on the

    UIM

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 44

    C Associations Between Alarms and Dry Contacts on the UIM

    Table C-1 Associations between alarms and dry contacts

    Port Type Silk Screen Description

    Boolean value port DIN1 Boolean value input 1.

    DIN2 Boolean value input 2

    DIN3 Boolean value input 3

    DIN4 Boolean value input 4

    DIN5 Boolean value input 5

    DIN6 Boolean value input 6

    Dry contact ALM1 Reports alarms for AC power failures.

    The default setting (closed: alarm; open: normal)

    can be changed.

    ALM2 Reports alarms for DC overvoltage and

    undervoltage.

    The default setting (closed: alarm; open: normal)

    can be changed.

    ALM3 Reports alarms for rectifier faults, protection,

    communication failures, faults of multiple

    rectifiers, and communication failure of all

    rectifiers.

    The default setting (closed: alarm; open: normal)

    can be changed.

    ALM4 Reports alarms for SPD faults.

    The default setting (closed: alarm; open: normal)

    can be changed.

    ALM5 Reports fuse blown alarms.

    The default setting (closed: alarm; open: normal) can be changed.

  • TP48300B-N04C2

    User Manual

    C Associations Between Alarms and Dry Contacts on the

    UIM

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 45

    Port Type Silk Screen Description

    ALM6 Reports alarms for abnormal battery

    temperatures or ambient temperatures.

    The default setting (closed: alarm; open: normal)

    can be changed.

    ALM7 User-defined.

    The default setting (closed: alarm; open: normal)

    can be changed.

    ALM8 Reports alarms for SMU faults.

    The default setting (closed: alarm; open: normal)

    can be changed.

  • TP48300B-N04C2

    User Manual D Acronyms and Abbreviations

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 46

    D Acronyms and Abbreviations ASIC application-specific integrated circuit

    BLVD battery low voltage disconnection

    CE conducted emission

    CS conducted susceptibility

    EFT electrical fast transient

    EMC electromagnetic compatibility

    EMI electromagnetic interference

    EMS electromagnetic susceptibility

    ESD electrostatic discharge

    FE fast Ethernet

    HAU heater assembly unit

    HTTPS Hypertext Transfer Protocol Secure

    LCD liquid crystal display

    LLVD load low voltage disconnection

    LSI large-scale integrated

    IEC International Electrotechnical Commission

    MTBF mean time between failures

    PDU power distribution unit

    RS radiated susceptibility

    SELV safety extra-low voltage

    SMU site monitor unit

    SNMP Simple Network Management Protocol

    SPD surge protective device

  • TP48300B-N04C2

    User Manual D Acronyms and Abbreviations

    Issue Draft A (2013-06-21) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd. 47

    TCU temperature control unit

    THD total harmonic distortion

    TNV telecommunication network voltage

    UIM user interface module

    WebUI web user interface

    About This Document1 Overview1.1 Introduction1.2 Features1.3 Working Principle1.4 System Configuration

    2 Components2.1 Interior2.2 PDU2.2.2 Battery Switch

    2.3 RectifierAppearancePanel

    2.4 SMUAppearancePanelIndicatorsButtonsCommunications Ports

    2.5 UIMPanelPortsPins

    3 Safety Precautions3.1 Health and Safety3.1.1 OverviewIntroductionLocal Safety RegulationsGeneral RequirementsInstallationGroundPower SupplyHuman SafetyOperator

    3.1.2 Electrical SafetyHigh VoltageToolsHigh Electrical Leakage

    3.1.3 Inflammable Environment3.1.4 BatteryStorage BatteryBasic PrecautionsShort CircuitHazardous GasBattery TemperatureBattery Leakage

    3.1.5 Mechanical SafetyDrilling HolesSharp ObjectsHandling FansLifting Heavy Objects

    3.1.6 Bundling Signal Cables

    3.2 Equipment Safety3.2.1 Electricity SafetyHigh Electrical Leakage

    3.2.2 Electrostatic Discharge3.2.3 Laying Out Cables

    4 Maintenance4.1 Routine Maintenance4.2 Handling Alarms4.2.1 Mains FailurePossible CausesMeasures1. Check whether the AC input cable is loose. If yes, secure the AC input cable.2. Check whether the AC input circuit breaker is OFF. If yes, handle the back-end circuit failure and then switch on the circuit breaker.3. Check whether the AC input voltage is lower than 50 V AC. If yes, handle the mains grid fault.

    4.2.2 AC Over VoltPossible CausesMeasures1. Check whether the AC overvoltage alarm threshold is properly set. If no, adjust it to a proper value.2. Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V AC by default). If yes, handle the AC input fault.

    4.2.3 AC Under VoltPossible CausesMeasures1. Check whether the AC undervoltage alarm threshold is correctly set. If no, adjust it to an appropriate value.2. Check whether the AC input voltage is below the AC undervoltage alarm threshold (180 V AC by default). If yes, handle the AC input fault.

    4.2.4 Phase A/B/C FailurePossible CausesMeasures1. Check whether the AC input power cable is correctly and securely installed. If no, reinstall the cable. If the insulation layer deteriorates, replace the cable.2. Check whether a short circuit occurs in the AC input power cable or the insulation layer is damaged. If yes, replace the cable.3. If the AC input is normal and the Alarm indicators on certain rectifiers are steady yellow, reinstall the rectifiers.4. If the alarm persists, replace the monitoring unit.

    4.2.5 DC Over VoltPossible CausesMeasures1. Check whether the DC overvoltage alarm threshold is correctly set. If no, adjust it to an appropriate value.2. Remove the rectifiers one by one and check whether the alarm is cleared. If the alarm still exists, reinstall the rectifier. If the alarm is cleared, replace the rectifier.3. Check whether the system voltage is set too high in manual mode. If yes, confirm the reason and adjust the voltage to a proper value after the operation.

    4.2.6 DC Under VoltPossible CausesMeasures1. Check whether an AC power failure has occurred. If yes, resume the AC power supply.2. Check whether the DC undervoltage alarm threshold is correctly set. If no, adjust it to an appropriate value.3. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier.4. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power.5. Check whether the system voltage is set too low in manual mode. If yes, confirm the reason and adjust the voltage to a proper value after the operation.

    4.2.7 Batt Over CurrPossible CausesMeasures1. Check whether an alarm is generated for rectifier communication interruption. If yes, remove the rectifier and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the rectifier.2. Remove the SMU and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the SMU.

    4.2.8 Load OffPossible CausesMeasures1. Check whether an AC power failure has occurred. If yes, resume the AC power supply.2. Check whether loads are manually disconnected. If yes, confirm the reason of the manual disconnection, and reconnect the loads after the operation.3. Check whether the load disconnection voltage is set too high on the SMU. If yes, adjust it to a proper value.4. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier.5. Check whether there is AC phase failure alarm. If yes, resume the normal AC input.

    4.2.9 Batt OffPossible CausesMeasures1. Check whether an AC power failure has occurred. If yes, resume the AC power supply.2. Check whether batteries are manually disconnected. If yes, confirm the reason of the manual disconnection, and reconnect the batteries after the operation.3. Check whether the battery disconnection voltage is set too high on the SMU. If yes, adjust it to an appropriate value.4. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier.5. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power.

    4.2.10 Batt Loop TripPossible CausesMeasures1. Check whether the battery fuse detection cable is disconnected. If yes, reconnect the cable.2. Check whether the battery circuit breaker has tripped or battery fuse is blown. If yes, rectify the battery loop fault and then switch on the circuit breaker or replace the fuse.3. Manually switch on or switch off the battery contactor and check whether the battery current changes accordingly. If no, replace the contactor.

    4.2.11 Amb. Over TempPossible CausesMeasures1. Check whether the ambient temperature alarm threshold is correctly set on the SMU. If no, adjust it based on site requirements.2. Check whether the temperature control