Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Technical Evaluation Report
TER 0910-01
QuickTie™ System (QTS)
QuickTie™ Products, Inc.
Product:
QuickTie™ System (QTS)
Issue Date:
October 20, 2009
Revision Date:
June 29, 2020
Subject to Renewal:
April 1, 2021
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 2 OF 48
COMPANY
INFORMATION:
QuickTie™ Products, Inc.
13300 Vantage Way Jacksonville, FL 32218-2378
904-281-0525
904-281-0526 (fax)
quicktieproducts.com
DIVISION: 06 00 00 - WOOD, PLASTICS AND COMPOSITES
SECTION: 06 05 23 - Wood, Plastic, and Composite Fastenings
1 PRODUCTS EVALUATED1
1.1 QuickTie™ System (QTS)
1.1.1 QTB(L) Blue 3/16" QuickTie™
1.1.2 QTG(L) Green ¼" QuickTie™
1.1.3 QTO(L) Orange 5/16" QuickTie™
1.1.4 QTR(L) Red 3/8" QuickTie™
1.2 Quick Connectors
1.2.1 HA4, HA6, HA8, and HA10 Hurricane and Seismic Anchors
1.2.2 MS and LS Straps
1.2.3 MTS and HTS Twist Straps
1.2.4 CS20-250, CS18-200, CS16-150, and CS14-100 Coiled Straps
1.2.5 CMST16-54, CMST14-52.5, and CMST12-40 Coiled Straps
1.2.6 SC35 Framing Angle and SC35F Framing Plate
1.2.7 HGA and HGAM Gusset Angles
1.2.8 PBA44, PBA46, PBA66, PBA77, and PBA88 Post Base Anchors
1.2.9 SPArtan™ Sill Plate Anchor
1.2.10 PCM and EPCM Post Caps
1.2.11 QGC QuickTie™ Girder Connector
1 Building codes require data from valid research reports be obtained from approved sources. Agencies who are accredited through ISO/IEC 17065 have met the code requirements for
approval by the building official. DrJ is an ISO/IEC 17065 ANAB-Accredited Product Certification Body – Accreditation #1131.
Through ANAB accreditation and the IAF MLA, DrJ certification can be used to obtain product approval in any jurisdiction or country that has IAF MLA Members & Signatories to meet the Purpose of the MLA – “certified once, accepted everywhere.”
Building official approval of a licensed registered design professional (RDP) is performed by verifying the RDP and/or their business entity complies with all professional engineering laws of the relevant jurisdiction. Therefore, the work of licensed RDPs is accepted by building officials, except when plan (i.e., peer) review finds an error with respect to a specific section of the code. Where this TER is not approved, the building official responds in writing stating the reasons for disapproval.
For more information on any of these topics or our mission, product evaluation policies, product approval process, and engineering law, visit drjcertification.org or call us at 608-310-6748.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 3 OF 48
1.2.12 LTT20B Light Tension Tie
2 APPLICABLE CODES AND STANDARDS2,3
2.1 Codes
2.1.1 IBC—12, 15, 18: International Building Code®
2.1.2 IRC—12, 15, 18: International Residential Code®
2.1.3 FBC-B—17: Florida Building Code – Building
2.1.4 NCBC—18: North Carolina Building Code
2.2 Standards and Referenced Documents
2.2.1 ACI 318: Building Code Requirements for Structural Concrete and Commentary
2.2.2 ACI 355.2: Qualification of Post-Installed Mechanical Anchors in Concrete and Commentary
2.2.3 AISI S100: North American Specification for the Design of Cold-Formed Steel Structural Members
2.2.4 AISI S904: Test Standard for Determining the Tensile and Shear Strengths of Steel Screws
2.2.5 ANSI/AISC 360: Specification for Structural Steel Buildings
2.2.6 ANSI/AWC NDS: National Design Specification (NDS) for Wood Construction
2.2.7 ASCE/SEI 19: Structural Applications of Steel Cables for Buildings
2.2.8 ASCE/SEI 7: Minimum Design Loads and Associated Criteria for Buildings and Other Structures
2.2.9 ASTM A1011: Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-
Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength
2.2.10 ASTM A1023: Standard Specification for Carbon Steel Wire Ropes for General Purposes
2.2.11 ASTM A36: Standard Specification for Carbon Structural Steel
2.2.12 ASTM A653: Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated
(Galvannealed) by the Hot-Dip Process
2.2.13 ASTM D7147: Standard Specification for Testing and Establishing Allowable Loads of Joist Hangers
2.2.14 ASTM F1575: Standard Test Method for Determining Bending Yield Moment of Nails
2.2.15 ASTM F1667: Standard Specification for Driven Fasteners: Nails, Spikes, and Staples
3 PERFORMANCE EVALUATION
3.1 Performance for use in buildings of light-frame construction and masonry in accordance with the codes listed in
Section 2.
3.2 Structural performance of connectors under uplift and lateral load conditions.
3.3 Compliance for use in buildings assigned to Seismic Design Categories A through E.
3.4 Compliance for use in buildings located where the design wind speed is less than or equal to 170 mph in
accordance with ASCE 7-05 and 215 mph in accordance with ASCE 7-10 and ASCE 7-16.
3.5 Compliance for use as an alternative to the Portal Frame with Hold-Down (PFH) as prescribed in IRC Section
R602.10.6.2.
3.6 Any code compliance issues not specifically addressed in this section are outside the scope of this TER.
2 Unless otherwise noted, all references in this TER are from the 2018 version of the codes and the standards referenced therein (e.g., ASCE 7, NDS, ASTM). This material, design, or
method of construction also complies with the 2000-2015 versions of the referenced codes and the standards referenced therein.
3 All terms defined in the applicable building codes are italicized.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 4 OF 48
3.7 Any engineering evaluation conducted for this TER was performed on the dates provided in this TER and within
DrJ’s professional scope of work.
4 PRODUCT DESCRIPTION AND MATERIALS
4.1 QuickTie™ System (QTS) - Description
4.1.1 The QTS is a wall anchoring system for conventional light-frame construction and masonry projects that
involve a Registered Design Professional (RDP).
4.1.1.1 For use of the QTS wall anchoring system in masonry construction, see TER 1404-06.
4.1.2 The QTS provides a continuous load path from the top of the wall to the foundation by resisting and
transferring wind uplift and/or laterally applied loads that result in overturning uplift forces.
4.1.3 The QTS consists of a galvanized aircraft wire rope (cable) with threaded studs swaged to each end.
4.1.4 Primary Connection (Epoxy):
4.1.4.1 QuickTie™ cable with threaded stud at bottom is connected to the foundation via a formed or drilled hole
in the foundation. The hole is filled with epoxy and the QuickTieTM cable is inserted into the hole and left
to set.
4.1.4.2 The other end of QuickTie™ with threaded stud is extended vertically within the wood stud wall to the top
of the wall, inserted through a hole drilled through the wood top plate(s) and attached to a steel plate
washer using a nut. The nut is tightened to post-tension the QTS.
4.1.5 Alternative Connection (Mechanical):
4.1.5.1 QuickTie™ cable with threaded stud at bottom is connected to the foundation via a cast-in-place
embedded anchor bolt or embedded steel plate with headed studs. The QuickTie™ cable is attached to
the embedded anchor bolt or steel plate by a mechanical coupling.
4.1.5.2 The other end of QuickTieTM cable with threaded stud is extended vertically within the wood stud wall to
the top of the wall, inserted through a hole drilled through the wood top plate(s) and attached to a steel
plate washer using a nut. The nut is tightened to post-tension the QTS.
4.1.6 Trusses, headers, and bottom plates are connected with Quick Connectors to provide distribution of load
through the QTS to the foundation.
4.1.7 Where one QuickTie™ cable does not provide sufficient capacity, multiple cables of the same type may be
installed to increase the pre-stressing force and transfer of accumulated loads to the foundation.
4.2 QuickTie™ System (QTS) – Types & Materials
4.2.1 The QTS consists of the following wood frame QuickTieTM [QTX(L), where X is the QuickTieTM type/cable
diameter and L is the length in feet]:
4.2.1.1 QTB(L) – QuickTieTM Blue, 3/16” diameter made of 7x19, galvanized steel wire rope with a minimum
breaking force of 4,200 lb per ASTM A1023. Refer to Figure 1 for the details of swaged threaded studs,
steel plate washer and nut.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 5 OF 48
FIGURE 1. TYPICAL QUICKTIE™ PART DETAIL – QTB(L) BLUE, 3/16" DIAMETER
4.2.1.2 QTG(L) – QuickTieTM Green, 1/4″ diameter made of 7x19, galvanized steel wire rope with a minimum
breaking force of 7,000 lb per ASTM A1023. Refer to Figure 2 for the details of swaged threaded studs,
steel plate washers and nut.
FIGURE 2. TYPICAL QUICKTIE™ PART DETAIL – QTG(L) GREEN, 1/4" DIAMETER
4.2.1.3 QTO(L) – QuickTieTM Orange, 5/16" diameter made of 7x19, galvanized steel wire rope with a minimum
breaking force of 9,800 lb per ASTM A1023. Refer to Figure 3 for the details of swaged threaded studs,
steel plate washers and nut.
FIGURE 3. TYPICAL QUICKTIE™ PART DETAIL – QTO(L) ORANGE, 5/16" DIAMETER
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 6 OF 48
4.2.1.1 QTR(L) – QuickTieTM Red, 3/4" diameter made of 7x19, galvanized steel wire rope with a minimum
breaking force of 14,400 lb per ASTM A1023. Refer to Figure 4 for the details of swaged threaded studs,
steel plate washer and nut.
FIGURE 4. TYPICAL QUICKTIE™ PART DETAIL – QTR(L) RED, 3/4" DIAMETER
4.2.2 Individual wires of the rope (cable) are 0.030″ diameter, or smaller, with minimum Fu = 268,000 psi and
galvanized with a minimum of 0.10 ounces per square foot of uncoated wire surface.
4.2.3 The steel plate washers are made of ASTM A36 or A653, Grade 33 steel, with a minimum yield and ultimate
strengths of 33 ksi and 45 ksi, respectively
4.2.4 The hex nuts are made of SAE J995 Grade 2 or equivalent material.
4.2.5 The length of QTS varies in 1″ increments from 2' to 62'.
4.2.6 Tension Indicator Device: Tension Indicator Devices (TIDs) are inserted between the steel plate washer and
the hex nut for visually identifying the pre-tension in the cable. TIDs are made from the following materials.
4.2.6.1 Blue: ASTM A653, Grade 33 structural steel, 14 gauge, min. thickness 0.0821″, painted
4.2.6.2 Green: ASTM A653, Grade 33 structural steel, 12 gauge, min. thickness 0.1120″, painted
4.2.6.3 Orange: ASTM A653, Grade 33 structural steel, 10 gauge, min. thickness 0.1419″, painted
4.2.6.4 Red: ASTM A653, Grade 33 structural steel, 8 gauge, min. thickness 0.1718″, painted
4.2.7 Quick Connectors Description:
4.2.7.1 Trusses, joists, rafters, headers, beams, studs, and plates are connected with manufactured Quick
Connector anchors and straps to provide a load path from the roof through to the foundation.
4.2.8 Quick Connectors:
4.2.8.1 HA4, HA6, HA8, and HA10 Hurricane & Seismic Anchors: These 18 gauge (minimum thickness with
coating 0.0466″) steel clips are used to fasten rafters and trusses to wall top plates. The clips resist uplift
loads and forces applied parallel to and perpendicular to the top plates. The HA4 clip is 4½″ long, the HA6
clip is 6¼" long, the HA8 is 8″, and the HA10 is 6½" in length. The clips are manufactured from ASTM
A653, Structural Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with a G90 or better
zinc coating (Figure 5 and Figure 6).
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 7 OF 48
FIGURE 5. HA4, HA6, AND HA8 HURRICANE/SEISMIC ANCHORS
FIGURE 6. HA10 HURRICANE/SEISMIC ANCHOR
4.2.8.2 LS & MS Series Straps: Light Straps (LS) are 20 gauge (minimum thickness with coating 0.0356″) steel;
Medium Straps (MS) are 16 gauge (0.0575″) steel. The straps are manufactured in lengths varying from
95/8″ to 485/8″. Each strap is 1¼″ wide with nail holes punched at intervals of 1½″ along its length. The nail
holes are staggered across the width of the strap. At the mid-length of each strap is a 3″ long area without
any holes. The purpose of this space is to provide a distance of 1½″ between the joint in the wood being
joined and the first nail hole on either side of the joint. The last three nails on each end of the strap are
spaced ¾″ apart and are staggered across the width of the strap. The straps are manufactured from
ASTM A653, Structural Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with a G90 or
better zinc coating (Figure 7).
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 8 OF 48
FIGURE 7. LS AND MS STRAP
4.2.8.3 MTS & HTS Series Twist Straps: The Medium Twist Straps (MTS) are manufactured in a length of 12″
and the Heavy Twist Straps (HTS) are manufactured in lengths of 16″, 20″, 24″, and 28″. The straps have
an offset shape to allow for twisting and bending. Each strap is 1¼″ wide with nail holes punched at
intervals of 1″ along its length. The nail holes are staggered across the width of the strap. The MTS12 is
16 gauge (minimum thickness with coating 0.0575″). The HTS16, HTS20, HTS24, and HTS28 are 14
gauge (minimum thickness with coating 0.0705″). The straps are manufactured from minimum ASTM
A653, Structural Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with a G90 or better
zinc coating (Figure 8).
FIGURE 8. MTS AND HTS TWIST STRAP
4.2.8.4 CS20-250, CS18-200, CS16-150, and CS14-100 Coiled Straps: Coiled Straps (CS) are either 20 gauge
(minimum thickness with coating 0.0356″) steel (CS20-250), 18 gauge (minimum thickness with coating
0.0466″) steel (CS18-200), 16 gauge (minimum thickness with coating 0.0575″) steel (CS16-150), or 14
gauge (minimum thickness with coating 0.0705″) steel (CS14-100). Each strap is 1¼″ wide with 0.177″
diameter nail holes punched at ¾″ intervals along its length. The straps are manufactured from ASTM
A653 Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with a G90 or better zinc coating. The
CS20-250 is manufactured from a 250′ coil, the CS18-200 is manufactured from a 200′ coil, the CS16-150
is manufactured from a 150′ coil, and the CS14-100 is manufactured from a 100’ coil (Figure 9).
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 9 OF 48
FIGURE 9. CS20-250, CS18-200, CS16-150, AND CS14-100 COILED STRAPS
4.2.8.5 CMST16-54, CMST14-52.5, and CMST12-40 Coiled Straps: Coiled Straps (CMST) are either 16 gauge
(minimum thickness with coating 0.0575″) steel (CMST16-54), 14 gauge (minimum thickness with coating
0.0705″) steel (CMST14-52.5), or 12 gauge (minimum thickness with coating 0.0994″) steel (CMST12-
40). Each strap is 3″ wide with 0.177″ diameter nail holes punched at 1½″ intervals along its length
(Figure 10). The straps are manufactured from ASTM A653, Structural Steel, Grade 50, Class 3 (Fu = 70
ksi, Fy = 50 ksi) steel galvanized with a G90 or better zinc coating. The CMST16-54 is manufactured from
a 54′ coil, the CMST14-52.5 is manufactured from a 52.5’ coil, and the CMST12-40 is manufactured from
a 40′ coil.
FIGURE 10. CMST16-54, CMST14-52.5, AND CMST12-40 COILED STRAPS
4.2.8.6 SC35 Framing Angle & SC35F Framing Plate: The SC35 anchors floor and ceiling joists to headers while
the SC35F anchors solid blocking to top plates. The SC35 uses a 90° framing angle to join posts to
beams and to make other right-angle connections. The anchors are 18 gauge (0.0466″) steel
manufactured from ASTM A653, Structural Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel
galvanized with a G90 or better zinc coating (Figure 11).
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 10 OF 48
FIGURE 11. SC35 FRAMING ANGLE AND SC35F FRAMING PLATE
4.2.8.7 HGA & HGAM Gusset Angles: The HGA and HGAM are 90° framing angles used to connect truss/rafter
joists to wall top plates (HGA) and the top of masonry walls (HGAM). The HGA and HGAM are 14 gauge
(minimum thickness with coating is 0.0705″) steel manufactured from ASTM A653, Structural Steel,
Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with a G90 or better zinc coating (Figure 12).
The HGA is anchored to the joist with four ¼″ diameter x 1½″ long screws and to the top plate with four
¼″ diameter x 3″ long screws. The HGAM is anchored to the joist with four ¼″ diameter x 1½″ long screws
and to the masonry block wall with four ¼″ x 2¼″ concrete screws. See the notes on Table 19 for
minimum screw requirements.
FIGURE 12. HGA AND HGAM GUSSET ANGLE
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 11 OF 48
4.2.8.8 PBA Post Base Anchor: Post Base Anchors (PBAs) are used to attach the base of a wood post to a
concrete foundation. The PBAs are comprised of a Post Base Strap and Stand-Off (SO) plate (Figure 13
and Figure 14). The SO plate is designed to provide a 1" clearance between the bottom of the wood post
and top of foundation in order to meet IBC Section 2304.124 and IRC Section R317 requirements for
protection of wood-based products against decay. The PBA44, PBA77, and PBA88 Post Base Strap and
SO Plate are 12 gauge steel (minimum thickness with coating is 0.0994″). The PBA46 and PBA66 Post
Base Strap is 10 gauge steel (minimum thickness with coating is 0.1250″) and the SO Plate is 12 gauge
steel (minimum thickness with coating is 0.0994″). The PBA is manufactured from ASTM A653, Structural
Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with G185 (min.) zinc coating. See
Table 20 for fastening schedules.
FIGURE 13. PBA44, PBA46, AND PBA6
FIGURE 14. PBA77 AND PBA88
4 2012 IBC Section 2304.11
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 12 OF 48
4.2.8.9 SPArtan™ Sill Plate Anchor: SPArtan™ Sill Plate Anchors are post-installed anchors used to attach the
sill plate of a wood framed wall to a concrete foundation. SPArtan™ anchors are designed to resist shear
loads due to wind and seismic forces. The SPArtan™ are 7.5″ long and manufactured from AISI 1018
carbon steel, hot dipped galvanized (HDG) or equivalent to meet ASTM A153, Class C. The diameter of
the portion of the anchor that embeds in concrete is 3/8″. The diameter of the portion of the anchor in
contact with the sill plate is 5/8″ (Figure 15 and Figure 16). SPArtan™ anchors are compliant with IBC
Section 1901.3. See Table 21 for allowable shear resistance values.
FIGURE 15. SPARTAN™ SILL PLATE ANCHOR MEASUREMENTS
FIGURE 16. SPARTAN™ SILL PLATE ANCHOR SECTION AND PLAN VIEWS
4.2.8.10 Post Cap (PCM) & End Post Cap (EPCM): Post Cap (PCM) and End Post Cap (EPCM) connectors are
used for post-to-beam connection applications. PCM and EPCMs are designed to resist uplift and shear
loads due to wind and seismic forces. The PCM and EPCM are 16 gauge (minimum thickness with
coating is 0.0575) and 12 gauge (minimum thickness with coating is 0.0994) steel manufactured from
ASTM A653, Structural Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi) steel galvanized with G185
(min.) zinc coating (Figure 17). The PCM and EPCM are attached to the post and beam with 16d nails.
See Table 22 for fastener schedules.
FIGURE 17. POST CAP (PCM) AND END POST CAP (EPCM)
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 13 OF 48
4.2.8.11 QuickTie™ Girder Connector (QGC): QuickTie™ Girder Connectors are used for truss and rafter to top
plate connections where uplift load design requirements are high. The QGC is 12 gauge (minimum
thickness with coating is 0.0994") steel manufactured from ASTM A653, Structural Steel, Grade 40 (Fu =
55 ksi, Fy = 40 ksi) steel galvanized with G90 or better zinc coating (Figure 18). The QGC is attached to
the top plate with a 5/8" threaded rod or QuickTie™ Orange Cable [QTO(L)] and is attached to the
truss/rafter with ¼" screws. See Table 23 for fastener schedules and minimum fastener requirements.
FIGURE 18. QUICKTIE™ GIRDER CONNECTOR (QGC)
4.2.8.12 Light Tension Tie (LTT20B): Light Tension Tie (LTT) is manufactured in a length of 20″. The ties are used
to connect wall bottom plates to studs or joist/purlin-to-wall attachment applications. Each strap is 2″ wide
with nail holes. The LTT is 12 gauge (minimum thickness with coating 0.0994″). The LTT20B is
manufactured from minimum ASTM A653, Structural Steel, Grade 50, Class 3 (Fu = 70 ksi, Fy = 50 ksi)
steel galvanized with G90 or better zinc coating (Figure 19). See Table 24 for fastener schedules.
FIGURE 19. LIGHT TENSION TIE (LTT20B)
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 14 OF 48
5 APPLICATIONS
5.1 The QTS is used to anchor walls and floors to the foundation.
5.2 Where the application exceeds the limitations set forth herein, design shall be permitted in accordance with
accepted engineering procedures, experience, and technical judgment.
5.3 QuickTie™ System (QTS)
5.3.1 The RDP responsible for the design of the building shall provide a connection to attach the QTS to the
foundation. The anchorage shall be sufficient to resist the design loads imposed by uplift and/or overturning
plus the pre-stress tension in the cable.
5.3.2 Installation of the QTS to the foundation will depend on the connection design chosen by the RDP. The QTS-
to-foundation design considerations include but are not limited to the following:
5.3.2.1 The connection between the QTS and foundation is applied/installed per the RDP’s specifications.
5.3.2.2 The QTS is pre-tensioned as specified per the QuickTie™ published installation instructions. The pre-
tensioned level is dependent on the uplift requirements determined by the RDP but shall not exceed the
allowable tensile capacity of the QTS listed in Section 5.4 of this TER.
5.3.2.3 In addition to providing positive anchorage for the walls and floors, the pre-tensioning of the QTS provides
immediate verification of the adequacy of the connection between the QTS and the foundation, because
the initial pre-tension load provides a proof test verification of this connection.
5.3.2.4 The RDP shall verify that the structural framing material is adequate to resist the compression forces
induced by the pre-stressing of the QTS. In some locations, additional framing or reinforcement may be
required.
5.4 Design
5.4.1 Where the application exceeds the limitations set forth herein, design shall be permitted in accordance with
accepted engineering procedures, experience, and technical judgment.
5.4.2 Table 1 lists the allowable tensile loads (based on Allowable Stress Design (ASD) basis) of the QTS. See
Figure 20 for concrete connection details.
TABLE 1. ALLOWABLE TENSILE LOADS OF THE QTS
Cable Type Cable Diameter (in) Minimum Edge
Distance (ca1) (in) Minimum Embedment
Depth (hef) (in) Allowable QTS Tension
Loads1,2,3 (lbs)
QTB(L) Blue 3/16 2¼ 4 1,910
QTG(L) Green ¼ 2¼ 4 3,180
QTO(L) Orange 5/16 3 65/8 4,455
QTR(L) Red 3/8 3½ 75/8 6,545
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Allowable QTS loads are based on cables installed in uncracked concrete with no supplementary reinforcement in accordance with ASCE 19.
2. Minimum end distance (ca2) is 6 inches (See Figure 20).
3. Minimum 28-day concrete compressive strength is 2,500 psi.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 15 OF 48
Elevation View Plan View
FIGURE 20. CONCRETE CONNECTION DETAIL
5.4.2.1 Multiple QTS cables may be used together to transfer the applied load, where one QTS cable is not
sufficient.
5.4.2.2 Allowable loads are based on the published strength of the cables per ASTM A1023 using a safety factor
of 2.2.
5.4.2.3 Construction documents shall include the information required by ASCE 19 Section 2 (Appendix B: ASCE
19 Section 2 Contract Documents and Shop Drawings).
5.4.2.4 See “Appendix C: Design Loads for QTB(L) and QTG(L)” for additional details on design loads for uplift
resistance.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 16 OF 48
5.4.3 Quick Connector HA4, HA6, HA8, and HA10 Hurricane & Seismic Anchor: Allowable loads and fastener
schedules for the HA4 anchor are provided in Table 2. Allowable loads and fastener schedules for the HA6
anchor are provided in Table 3. Allowable loads and fastener schedules for the HA8 anchor are provided in
Table 4. Allowable loads and fastener schedules for the HA10 anchors are provided in Table 5.
TABLE 2. HA4 HURRICANE & SEISMIC ANCHOR ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load1,2,3 (lbs)
Uplift Lateral – F16 Lateral – F27
Type To Rafter/Truss4 To Plates5 Load Duration Factor, 1.60
Southern Pine (SP) (0.55)
8d x 11/2 (0.131 x 1.5″)
5 4 662 180 120
10d x 11/2 (0.148 x 1.5″)
5 4 662 180 120
Douglas Fir-Larch (DF-L) (0.50)
8d x 11/2 (0.131 x 1.5″)
5 4 599 158 120
10d x 11/2 (0.148 x 1.5″)
5 4 599 158 120
Spruce-Pine-Fir (SPF) (0.42)
8d x 11/2 (0.131 x 1.5″)
5 4 514 135 106
10d x 11/2 (0.148 x 1.5″)
5 4 514 135 106
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer also to Appendix A: General Notes for Tables.
2. Clips may be installed on both sides of the framing member for twice the load.
3. The tabulated loads are valid for clips installed on the inside or the outside of the wall. However, to maintain a continuous load path for uplift connections in close proximity to one another, such as truss-to-plate and plate-to-stud, clips should be installed on the same side of the wall.
4. Nails attaching clip to rafter or truss are 8d x 1½″ (0.131 x 1.5″) or 10d x 1½″ (0.148 x 1.5″) nails.
5. Nails attaching clip to wall plates are 8d (0.131 x 2.5″) or 10d (0.148 x 3″) nails.
6. Loading in the F1 direction indicates shear forces parallel to the plane of the wall. Refer to manufacturer’s literature for further details (See Figure 21).
7. Loading in the F2 direction indicates shear forces perpendicular to the plane of the wall. Refer to manufacturer’s literature for further details (See Figure 21).
FIGURE 21. HA4 LOAD DIRECTIONS
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 17 OF 48
TABLE 3. HA6 HURRICANE & SEISMIC ANCHOR ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load1,2,3,4 (lbs)
Uplift Lateral – F15 Lateral – F26 Lateral – F37 Lateral – F48
Type To Rafter/Truss4 To Plates5 Load Duration Factor
1.00 1.60
SP (0.55)
8d x 1½ (0.131 x 1.5″)
5 5
520 650 145 140 70 90
DF-L (0.50) 480 600 125 125 60 80
SPF (0.42) 415 515 80 100 45 65
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
4. Refer also to Appendix A: General Notes for Tables.
5. Clips may be installed on both sides of the framing member for twice the load.
6. The tabulated loads are valid for clips installed on the inside or the outside of the wall. However, to maintain a continuous load path for uplift connections in close proximity to one another, such as truss-to-plate and plate-to-stud, clips should be installed on the same side of the wall.
7. Allowable loads are provided for load duration factor (CD) of 1.60. No further increase is permitted.
8. Loading in the F1 direction indicates shear forces parallel to the plane of the wall, connection to rafter in withdrawal (See Figure 22).
9. Loading in the F2 direction indicates shear forces parallel to the plane of the wall, connection to rafter in compression (See Figure 22).
10. Loading in the F3 direction indicates shear forces perpendicular to the plane of the wall, connection to top plate in withdrawal (See Figure 22).
11. Loading in the F4 direction indicates shear forces perpendicular to the plane of the wall, connection to top plate in compression (See Figure 22).
FIGURE 22. HA6 LOAD DIRECTIONS
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 18 OF 48
TABLE 4. HA8 HURRICANE & SEISMIC ANCHOR ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load1,2,3 (lbs)
Uplift Lateral – F16 & F27
Type To Rafter/Truss4 To Plates5 Load Duration Factor, 1.60
SP (0.55)
8d x 11/2 (0.131 x 1.5″)
5 5 600 61
10d x 11/2 (0.148 x 1.5″)
5 5 815 94
DF-L (0.50)
8d x 11/2 (0.131 x 1.5″)
5 5 600 61
10d x 11/2 (0.148 x 1.5″)
5 5 705 69
SPF (0.42)
8d x 11/2 (0.131 x 1.5″)
5 5 485 61
10d x 11/2 (0.148 x 1.5″)
5 5 540 69
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer also to Appendix A: General Notes for Tables.
2. Clips may be installed on both sides of the framing member for twice the load.
3. The tabulated loads are valid for clips installed on the inside or the outside of the wall. However, to maintain a continuous load path for uplift, connections in close proximity to one another, such as truss-to-plate and plate-to-stud, clips should be installed on the same side of the wall.
4. Nails attaching clip to rafter or truss are 8d x 1½″ (0.131 x 1.5″) or 10d x 1½″ (0.148 x 1.5″) nails.
5. Nails attaching clip to wall plates are 8d (0.131 x 2.5″) or 10d (0.148 x 3″) nails.
6. Loading in the F1 direction indicates shear forces parallel to the plane of the wall. Refer to manufacturer’s literature for further details (See Figure 23).
7. Loading in the F2 direction indicates shear forces perpendicular to the plane of the wall. Refer to manufacturer’s literature for further details (See Figure 23).
FIGURE 23. HA8 LOAD DIRECTIONS
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 19 OF 48
TABLE 5. HA10, HA10-2, AND HA10R HURRICANE & SEISMIC ANCHOR ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load2 (lbs)
Rafter/Truss Top Plates Uplift Lateral – F13 Lateral – F24
Type Quantity Type Quantity 1.0 1.6 1.6 1.6
SP (0.55)
10d x 11/2 (0.148 x 1.5″)
9
10d x 11/2 (0.148 x 1.5″)
8 1,005
1,140
560
335
10d common (0.148 x 3")
1,350 300
DF-L (0.50) 9
10d x 11/2 (0.148 x 1.5″)
8 930
1,055
515
310
10d common (0.148 x 3")
1,245 280
SPF (0.42) 9
10d x 11/2 (0.148 x 1.5″)
8 800
910
335
220
10d common (0.148 x 3")
1,075 230
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer also to Appendix A: General Notes for Tables.
2. Allowable loads are provided for load duration factor (CD) of 1.6. No further increase is permitted.
3. Loading in the F1 direction indicate shear forces parallel to the plane of the wall, one side of connection to rafter/truss in withdrawal (see Figure 24).
4. Loading in the F2 direction indicate shear forces perpendicular to the plane of the wall, connection to top plate in withdrawal (see Figure 24).
FIGURE 24. HA10 LOAD DIRECTIONS
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 20 OF 48
5.4.4 Quick Connector LS & MS Series Straps, and MTS & HTS Series Twist Straps: Allowable loads for the LS &
MS straps and the MTS & HTS twist straps are provided in Table 6 through Table 9. The nail sizes and nailing
schedules are provided in Table 6 for the LS Series Straps, Table 7 for the MS Series Straps, Table 8 for the
MTS Series Twist Straps, and Table 9 for the HTS Series Twist Straps.
TABLE 6. LS SERIES STRAP ALLOWABLE TENSION LOADS
Model Number
Fasteners Allowable Tension Load1,2,3 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size Number of Nails
Each End of Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
LS9
8d
(0.1
31 x
2.5
")
4 416 666 384 614 328 525
LS12 5 520 832 480 768 410 656
LS18 7 728 1,165 672 1,075 574 918
LS21 8 832 1,295 768 1,229 656 1,050
LS24 9 936 1,295 864 1,295 738 1,181
LS9
10d
x 1½
(0.1
48 x
1.5
")
4 500 800 460 736 392 627
LS12 5 625 1,000 575 920 490 784
LS18 7 875 1,295 805 1,288 686 1,098
LS21 8 1,000 1,295 920 1,295 784 1,254
LS24 9 1,125 1,295 1,035 1,295 882 1,295
LS9
10d
(0.1
48 x
3")
4 504 806 464 742 396 634
LS12 5 630 1,008 580 928 495 792
LS18 7 882 1,295 812 1,295 693 1,109
LS21 8 1,008 1,295 928 1,295 792 1,267
LS24 9 1,134 1,295 1,044 1,295 891 1,295
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. Allowable tension loads for load durations of two months (i.e., 115%) and seven days (i.e., 125%) may be obtained by multiplying the corresponding allowable tension load in the load duration factor column marked “1.00” by 1.15 or 1.25 respectively, with a maximum of 1,295 lbs.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 21 OF 48
TABLE 7. MS SERIES STRAP ALLOWABLE TENSION LOADS
Model Number
Fasteners Allowable Tension Load1,2,3 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size Number of Nails
Each End of Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
MS24
8d
(0.1
31 x
2.5
″)
9 981 1,570 909 1,454 783 1,253
MS27 10 1,090 1,744 1,010 1,616 870 1,392
MS30 11 1,199 1,918 1,111 1,778 957 1,531
MS36 13 1,417 2,118 1,313 2,101 1,131 1,810
MS39 14 1,526 2,118 1,414 2,118 1,218 1,949
MS48 14 1,526 2,118 1,414 2,118 1,218 1,949
MS24
10d
x 11 /
2
(0.1
48 x
1.5
″)
9 1,152 1,843 1,062 1,699 909 1,454
MS27 10 1,280 2,048 1,180 1,888 1,010 1,616
MS30 11 1,408 2,118 1,298 2,077 1,111 1,778
MS36 13 1,664 2,118 1,534 2,118 1,313 2,101
MS39 14 1,792 2,118 1,652 2,118 1,414 2,118
MS48 14 1,792 2,118 1,652 2,118 1,414 2,118
MS24
10d
(0.1
48 x
3″)
9 1,179 1,886 1,089 1,742 936 1,498
MS27 10 1,310 2,096 1,210 1,936 1,040 1,664
MS30 11 1,441 2,118 1,331 2,118 1,144 1,830
MS36 13 1,703 2,118 1,573 2,118 1,352 2,118
MS39 14 1,834 2,118 1,694 2,118 1,456 2,118
MS48 14 1,834 2,118 1,694 2,118 1,456 2,118
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. Allowable tension loads for load durations of two months (i.e., 115%) and seven days (i.e., 125%) may be obtained by multiplying the corresponding allowable tension load in the load duration factor column marked “1.00” by 1.15 or 1.25 respectively, with a maximum of 2,118 lbs.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 22 OF 48
TABLE 8. MTS TWIST STRAP ALLOWABLE TENSION LOADS
Model Number
Fasteners Allowable Load1,2,3 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Type Min No. of Nails per
Strap4
Min No. of Nails at Each
End
Load Duration Factor
1.00 1.60 1.00 1.60 1.00 1.60
MTS12 10d x 11/2 (0.148 x 1.5″)
14 7 895 1085 825 1000 715 865 MTS16
MTS20 10d (0.148 x 3″) MTS24
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Straps do not have to be wrapped over the truss or rafter to achieve the loads shown.
3. Straps may be installed on either side of the framing member.
4. The number of fasteners shown in the table is the minimum required to achieve the loads shown.
TABLE 9. HTS TWIST STRAP ALLOWABLE TENSION LOADS
Model Number
Fasteners Allowable Load1,2,3 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Type Min No. of Nails per
Strap4
Min No. of Nails at Each
End
Load Duration Factor
1.00 1.60 1.00 1.60 1.00 1.60
HTS16 10d x 11/2 (0.148 x 1.5″)
22 11 1445 1665 1340 1540 1160 1330 HTS20
HTS24 10d (0.148 x 3″) HTS28
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Straps do not have to be wrapped over the truss or rafter to achieve the loads shown.
3. Straps may be installed on either side of the framing member.
4. The number of fasteners shown in the table is the minimum required to achieve the loads shown.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 23 OF 48
5.4.5 Quick Connector CS20-250, CS18-200, S16-150, and CS14-100 Coiled Straps: Allowable loads for the
CS20-250, CS18-200, CS16-150, and CS14-100 Coiled Straps are provided in Table 10 through Table 13.
The nail sizes and nailing schedules are provided in Table 10 for the CS20-250, Table 11 for the CS18-200,
Table 12 for the CS16-150, and Table 13 for the CS14-100.
TABLE 10. CS20-250 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
8d x 1½ (0.131 x 1.5")
& 8d Common (0.131 x 2.5")
4 3 417 668 385 615 331 530
6 41/2 626 1001 577 923 497 794
8 6 834 1335 769 1231 662 1059
10 71/2 1043 1343 962 1343 828 1324
11 81/4 1147 1343 1058 1343 910 1343
12 9 1252 1343 1154 1343 993 1343
13 93/4 1343 1343 1250 1343 1076 1343
14 101/2 1343 1343 1343 1343 1159 1343
15 111/4 1343 1343 1343 1343 1241 1343
16 12 1343 1343 1343 1343 1324 1343
17 123/4 1343 1343 1343 1343 1343 1343
10d x 1½ (0.148 x 1.5")
& 10d Common (0.148 x 3")
4 3 504 806 464 743 399 639
6 41/2 755 1209 696 1114 599 958
8 6 1007 1343 928 1343 799 1278
9 63/4 1133 1343 1044 1343 898 1343
10 71/2 1259 1343 1160 1343 998 1343
11 81/4 1343 1343 1277 1343 1098 1343
12 9 1343 1343 1343 1343 1198 1343
13 93/4 1343 1343 1343 1343 1298 1343
14 101/2 1343 1343 1343 1343 1343 1343
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 24 OF 48
FIGURE 25. COILED STRAPS – TOTAL CUT LENGTH
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 25 OF 48
TABLE 11. CS18-200 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
8d x 1½ (0.131 x 1.5")
& 8d Common (0.131 x 2.5")
4 3 426 682 393 629 339 543
6 41/2 639 1022 590 944 509 814
8 6 852 1363 787 1258 678 1085
10 71/2 1065 1704 983 1573 848 1356
12 9 1278 1777 1180 1777 1017 1628
14 101/2 1491 1777 1376 1777 1187 1777
16 12 1704 1777 1573 1777 1356 1777
17 123/4 1777 1777 1671 1777 1441 1777
18 131/2 1777 1777 1770 1777 1526 1777
19 141/4 1777 1777 1777 1777 1611 1777
20 15 1777 1777 1777 1777 1695 1777
21 153/4 1777 1777 1777 1777 1777 1777
10d x 1½ (0.148 x 1.5")
& 10d Common (0.148 x 3")
4 3 512 820 473 757 408 652
6 41/2 769 1230 709 1135 611 978
8 6 1025 1640 946 1513 815 1304
10 71/2 1281 1777 1182 1777 1019 1630
11 81/4 1409 1777 1300 1777 1121 1777
12 9 1537 1777 1419 1777 1223 1777
13 93/4 1665 1777 1537 1777 1324 1777
14 101/2 1777 1777 1655 1777 1426 1777
15 111/4 1777 1777 1773 1777 1528 1777
16 12 1777 1777 1777 1777 1630 1777
17 123/4 1777 1777 1777 1777 1732 1777
18 131/2 1777 1777 1777 1777 1777 1777
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 26 OF 48
TABLE 12. CS16-150 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
8d x 1½ (0.131 x 1.5")
& 8d Common (0.131 x 2.5")
4 3 438 701 405 648 350 560
6 41/2 658 1052 608 972 525 840
8 6 877 1403 810 1296 700 1120
10 71/2 1096 1754 1013 1621 875 1400
12 9 1315 2104 1215 1945 1050 1679
14 101/2 1534 2206 1418 2206 1225 1959
16 12 1754 2206 1621 2206 1400 2206
18 131/2 1973 2206 1823 2206 1575 2206
20 15 2192 2206 2026 2206 1749 2206
21 153/4 2206 2206 2127 2206 1837 2206
22 161/2 2206 2206 2206 2206 1924 2206
24 18 2206 2206 2206 2206 2099 2206
26 191/2 2206 2206 2206 2206 2206 2206
10d x 1½ (0.148 x 1.5")
& 10d Common (0.148 x 3")
4 3 525 840 485 776 419 670
6 41/2 788 1261 728 1164 628 1005
8 6 1050 1681 970 1553 838 1340
10 71/2 1313 2101 1213 1941 1047 1675
12 9 1576 2206 1456 2206 1256 2010
14 101/2 1838 2206 1698 2206 1466 2206
16 12 2101 2206 1941 2206 1675 2206
18 131/2 2206 2206 2183 2206 1885 2206
20 15 2206 2206 2206 2206 2094 2206
22 161/2 2206 2206 2206 2206 2206 2206
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 27 OF 48
TABLE 13. CS14-100 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
8d x 1½ (0.131 x 1.5")
& 8d Common (0.131 x 2.5")
4 3 457 732 423 677 366 586
6 41/2 686 1098 635 1015 549 878
8 6 915 1464 846 1354 732 1171
10 71/2 1143 1829 1058 1692 915 1464
12 9 1372 2195 1269 2031 1098 1757
14 101/2 1601 2561 1481 2369 1281 2050
16 12 1829 2718 1692 2708 1464 2343
18 131/2 2058 2718 1904 2718 1647 2635
20 15 2287 2718 2115 2718 1830 2718
22 161/2 2515 2718 2327 2718 2013 2718
24 18 2718 2718 2539 2718 2196 2718
25 183/4 2718 2718 2644 2718 2288 2718
26 191/2 2718 2718 2718 2718 2379 2718
27 201/4 2718 2718 2718 2718 2471 2718
28 21 2718 2718 2718 2718 2562 2718
29 213/4 2718 2718 2718 2718 2654 2718
30 221/2 2718 2718 2718 2718 2718 2718
10d x 1½ (0.148 x 1.5")
& 10d Common (0.148 x 3")
4 3 545 872 504 806 436 697
6 41/2 818 1308 756 1210 654 1046
8 6 1090 1744 1008 1613 872 1395
10 71/2 1363 2180 1260 2016 1090 1743
12 9 1635 2616 1512 2419 1307 2092
14 101/2 1908 2718 1764 2718 1525 2441
16 12 2180 2718 2016 2718 1743 2718
18 131/2 2453 2718 2268 2718 1961 2718
20 15 2718 2718 2520 2718 2179 2718
21 153/4 2718 2718 2646 2718 2288 2718
22 161/2 2718 2718 2718 2718 2397 2718
23 171/4 2718 2718 2718 2718 2506 2718
24 18 2718 2718 2718 2718 2615 2718
25 183/4 2718 2718 2718 2718 2718 2718
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 28 OF 48
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
5.4.6 Quick Connector CMST16-54, CMST14-52.5, and CMST12-40 Coiled Straps: Table 14, Table 15, and Table
16 provide allowable loads for the CMST16-54, CMST14-52.5, and CMST12-40 Coiled Straps. The nail sizes
and nailing schedules are provided in Table 14 for the CMST16-54, Table 15 for the CMST14-52.5, and Table
16 for the CMST12-40.
TABLE 14. CMST16-54 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
10d Common (0.148 x 3")
6 41/2 788 1,261 728 1,164 628 1,005
12 9 1,576 2,521 1,456 2,329 1,256 2,010
18 131/2 2,364 3,782 2,183 3,493 1,885 3,015
24 18 3,151 5,042 2,911 4,658 2,513 4,021
30 221/2 3,939 5,295 3,639 5,295 3,141 5,026
36 27 4,727 5,295 4,367 5,295 3,769 5,295
42 311/2 5,295 5,295 5,095 5,295 4,397 5,295
48 36 5,295 5,295 5,295 5,295 5,026 5,295
54 401/2 5,295 5,295 5,295 5,295 5,295 5,295
16d Common (0.162 x 3.5")
6 41/2 933 1,493 861 1,378 743 1,189
12 9 1,866 2,985 1,723 2,757 1,486 2,378
18 131/2 2,799 4,478 2,584 4,135 2,229 3,567
24 18 3,732 5,295 3,446 5,295 2,972 4,755
30 221/2 4,665 5,295 4,307 5,295 3,715 5,295
36 27 5,295 5,295 5,169 5,295 4,458 5,295
42 311/2 5,295 5,295 5,295 5,295 5,201 5,295
48 36 5,295 5,295 5,295 5,295 5,295 5,295
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 29 OF 48
TABLE 15. CMST14-52.5 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
10d Common (0.148 x 3")
6 41/2 818 1,308 756 1,210 654 1,046
12 9 1,635 2,616 1,512 2,419 1,307 2,092
18 131/2 2,453 3,925 2,268 3,629 1,961 3,138
24 18 3,270 5,233 3,024 4,839 2,615 4,184
30 221/2 4,088 6,524 3,780 6,049 3,269 5,230
36 27 4,906 6,524 4,536 6,524 3,922 6,276
42 311/2 5,723 6,524 5,293 6,524 4,576 6,524
48 36 6,524 6,524 6,049 6,524 5,230 6,524
54 401/2 6,524 6,524 6,524 6,524 5,884 6,524
60 45 6,524 6,524 6,524 6,524 6,524 6,524
16d Common (0.162 x 3.5")
6 41/2 962 1,540 889 1,423 768 1,229
12 9 1,924 3,079 1,779 2,846 1,537 2,459
18 131/2 2,887 4,619 2,668 4,269 2,305 3,688
24 18 3,849 6,158 3,558 5,692 3,074 4,918
30 221/2 4,811 6,524 4,447 6,524 3,842 6,147
36 27 5,773 6,524 5,336 6,524 4,611 6,524
42 311/2 6,524 6,524 6,226 6,524 5,379 6,524
48 36 6,524 6,524 6,524 6,524 6,147 6,524
54 401/2 6,524 6,524 6,524 6,524 6,524 6,524
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 30 OF 48
TABLE 16. CMST12-40 COILED STRAPS ALLOWABLE TENSION LOAD
Fasteners Minimum Required End
Length3 (in)
Allowable Tension Load1,2 (lbs)
SP (0.55) DF-L (0.50) SPF (0.42)
Size # Each End of
Strap
Load Duration Factor2
1.00 1.60 1.00 1.60 1.00 1.60
10d Common (0.148 x 3")
6 41/2 906 1,449 839 1,342 727 1,164
12 9 1,811 2,898 1,678 2,684 1,455 2,328
18 131/2 2,717 4,347 2,517 4,027 2,182 3,492
24 18 3,622 5,795 3,356 5,369 2,910 4,656
30 221/2 4,528 7,244 4,194 6,711 3,637 5,820
36 27 5,433 8,693 5,033 8,053 4,365 6,984
42 311/2 6,339 9,256 5,872 9,256 5,092 8,148
48 36 7,244 9,256 6,711 9,256 5,820 9,256
54 401/2 8,150 9,256 7,550 9,256 6,547 9,256
60 45 9,055 9,256 8,389 9,256 7,275 9,256
66 491/2 9,256 9,256 9,228 9,256 8,002 9,256
72 54 9,256 9,256 9,256 9,256 8,730 9,256
78 581/2 9,256 9,256 9,256 9,256 9,256 9,256
16d Common (0.162 x 3.5")
6 41/2 1,051 1,681 973 1,557 843 1,349
12 9 2,102 3,363 1,946 3,114 1,687 2,698
18 131/2 3,153 5,044 2,919 4,671 2,530 4,048
24 18 4,204 6,726 3,892 6,228 3,373 5,397
30 221/2 5,254 8,407 4,866 7,785 4,216 6,746
36 27 6,305 9,256 5,839 9,256 5,060 8,095
42 311/2 7,356 9,256 6,812 9,256 5,903 9,256
48 36 8,407 9,256 7,785 9,256 6,746 9,256
54 401/2 9,256 9,256 8,758 9,256 7,589 9,256
60 45 9,256 9,256 9,256 9,256 8,433 9,256
66 491/2 9,256 9,256 9,256 9,256 9,256 9,256
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable tension loads apply for uplift when the straps are installed vertically.
3. The total strap cut length is equal to the Clear Span + 2 x End Length. See Figure 25 for more detail.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 31 OF 48
5.4.7 Quick Connector SC35 Framing Angle & SC35F Framing Plate: Allowable loads for the SC35 Framing Angle
and SC35F Framing Plate are provided in Table 17 and Table 18. The nail sizes and nailing schedules are
provided in Table 17 for the SC35 and Table 18 for the SC35F.
TABLE 17. SC35 FRAMING ANGLE ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load1,3,4 (lbs)
Load Direction F1 Load Direction F2 Load Direction F32
Type Total Load Duration Factor
1.00 1.60 1.00 1.60 1.00 1.60
SP (0.55)
10d x 11/2 (0.148 x 1.5″)
12 756 842 294 294 756 1,075
10d (0.148 x 3″)
12 768 942 262 262 768 1,013
DF-L (0.50)
10d x 11/2 (0.148 x 1.5″)
12 696 763 267 267 696 974
10d (0.148 x 3″)
12 708 842 234 234 708 905
SPF (0.42)
10d x 11/2 (0.148 x 1.5″)
12 594 651 201 228 594 831
10d (0.148 x 3″)
12 606 721 200 200 606 775
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Tabulated loads are per connector.
3. Connectors are required on both sides of the joist to achieve the F3 loads in both directions.
4. When connectors are installed directly across from each other on both sides of the joist, the thickness of the joist should be twice the length of the fastener.
5. Refer to Figure 26 for an illustration of directions F1, F2, & F3.
FIGURE 26. ILLUSTRATION OF LOAD DIRECTIONS F1, F2, & F3 FOR THE SC35 FRAMING ANGLE
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 32 OF 48
TABLE 18. SC35F FRAMING PLATE ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load1,2 (lbs)
Uplift – F5 Lateral – F4
Type Total Load Duration Factor
1.00 1.60 1.00 1.60
SP (0.55)
10d x 11/2 (0.148 x 1.5″)
12 502 502 756 773
10d (0.148 x 3″)
12 552 552 733 733
DF-L (0.50)
10d x 11/2 (0.148 x 1.5″)
12 431 431 655 655
10d (0.148 x 3″)
12 468 468 614 614
SPF (0.42)
10d x 11/2 (0.148 x 1.5″)
12 368 368 559 559
10d (0.148 x 3″)
12 401 401 525 525
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Refer to Figure 27 for an illustration of directions F4 & F5.
FIGURE 27. ILLUSTRATION OF LOAD DIRECTIONS F4 & F5 FOR THE SC35F FRAMING PLATE
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 33 OF 48
5.4.8 Quick Connector HGA Gusset Angle: The screw sizes, screw schedules, and allowable loads for the HGA
and HGAM gusset angles are provided in Table 19.
TABLE 19. HGA & HGAM GUSSET ANGLE ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load1 (lbs)
Uplift F12 F23 F34
To Rafter/Truss To Wood or Concrete Load Duration Factor
Type Quantity Type Quantity 1.00 1.60 1.60 1.60
DF-L (0.50) 1/4″ x 11/2″
(Note 9) 4
Wood, 1/4″ x 3″ (Note 11)
4 1085 1160 955 1150
Concrete, 1/4″ x 21/4″ (Note 13)
4 815 1005 955 1005
SPF (0.42) 1/4″ x 11/2″ (Note 10)
4
Wood, 1/4″ x 3″ (Note 12)
4 740 805 505 825
Concrete, 1/4″ x 21/4″ (Note 13)
4 815 805 505 825
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Loading in the F1 direction indicates shear forces parallel to the plane of the wall (Figure 28).
3. Loading in the F2 direction indicates shear forces perpendicular to the plane of the wall, acting towards the gusset angle (Figure 28).
4. Loading in the F3 direction indicates shear forces perpendicular to the plane of the wall, acting away from the gusset angle (Figure 28).
5. Minimum fastener penetration must be equal to the screw length less the thickness of the metal side plate.
6. Minimum Specified Wood Screw Requirements: Major Diameter = 0.25″, Minor (Root) Diameter = 0.185″, Thread Length (including tip) = 1.25″, Bending Yield Strength = 180,000 psi
7. Minimum Specified Wood Screw Requirements: Major Diameter = 0.25″, Minor (Root) Diameter = 0.185″, Thread Length (including tip) = 2.25″, Bending Yield Strength = 180,000 psi
8. Minimum Specified Masonry screws Requirements: Major Diameter = 0.25″, Thread Length = 1.75″, Min. Fy and Fu = 80,000 psi and 100,000 psi
9. Minimum Reference Lateral Design Value (Z) = 182 lbs, Minimum Reference Withdrawal Value (W) = 164 lbs/in
10. Minimum Reference Lateral Design Value (Z) = 136 lbs, Minimum Reference Withdrawal Value (W) = 103 lbs/in
11. Minimum Reference Lateral Design Value (Z) = 244 lbs, Minimum Reference Withdrawal Value (W) = 179 lbs/in
12. Minimum Reference Lateral Design Value (Z) = 210 lbs, Minimum Reference Withdrawal Value (W) = 126 lbs/in
13. Minimum Allowable Tension (T) and Shear (S) Capacities When Installed in Concrete, T = 204 lb and S = 219 lb, Min. Edge Distance = 2″, Min. Spacing = 1″, Min End Distance = 2.65″, Min. Embedment = 1½″, Min. Concrete Compression Strength, f'c = 2,500 psi, Load combination 1.2D+1.6L with D = 0.3, L = 0.7 and α = 1.48.
FIGURE 28. HGAM LOAD DIRECTIONS FOR WOOD & MASONRY APPLICATIONS
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 34 OF 48
5.4.9 Quick Connector PBA Post Base Anchor: The PBA Post Base Anchor dimensions, nails schedules, anchor
schedules, and allowable loads are provided in Table 20.
TABLE 20. PBA POST BASE ANCHOR ALLOWABLE LOADS
Species (Specific Gravity)
Part No.
Strap Dimensions (in) Stand-Off Dimensions
(in) Nominal Post Size
Steel Thickness
(gauge) Fasteners
Allowable Loads1,2,3 (lb)
Width (W)
Length (L)
Height (H)
Width (W)
Length (L)
Height (H)
Strap Stand-
Off
Post Anchor Bearing Uplift
Qty Size Qty Size CD=1.0 CD=1.6
SP (0.55) or
DF-L (0.50)
PBA44 39/16 31/2 51/2 31/2 35/16 1 4x4 12 12 12 16d 1 5/8 11,140 2,335
PBA46 39/16 5 6 31/2 43/4 1 4x6 10 12 12 16d 1 5/8 13,000 2,335
PBA66 51/2 5 6 57/16 43/4 1 6x6 10 12 12 16d 1 5/8 16,485 2,545
PBA77 71/8 71/16 71/4 7 67/8 1 7x7 12 12 14 16d 2 5/8 16,485 3,590
PBA88 71/2 71/16 71/16 73/8 67/8 1 8x8 12 12 14 16d 2 5/8 27,065 3,590
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable load values provided are for wet service condition, no further reduction required.
3. The square washer shall be installed below the heavy hex nut. The heavy hex nut shall be installed flush with the bottom of the stand-off plate. See Section 6.4 for installation instructions. See Figure 29 for three-dimensional view of post base installed in concrete.
FIGURE 29. PBA POST BASE ANCHOR (PBA 77 & PBA 88 SHOWN)
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 35 OF 48
5.4.10 Quick Connector SPArtan™ Sill Plate Anchor: The SPArtan™ anchor allowable shear loads for concrete and
wood are provided in Table 21.
TABLE 21. SPARTAN™ ANCHOR ALLOWABLE SHEAR VALUES (ASD) – CONCRETE & WOOD
Applied Load on Sill Plate
Allowable Shear Resistance (lb)
Concrete (f'c = 2,500 psi)1,2,3 Wood4,5,6
Edge Distance (in) Uncracked Cracked Southern Pine (0.55) Douglas Fir-Larch (0.50)
F1 (Parallel) 21/4
1,395 800 1,320 1,275 31/4
F2 (Perpendicular) 21/4 725 520
610 530 31/4 1,260 900
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Allowable shear resistance determined using a conversion factor (αASD) of 1.48. The conversion factor is based on the controlling load case: 1.2D + 1.6L, where Dead Load (D) = 30% and Live Load (L) = 70%. Adjustments shall be made where other load combinations control.
2. Minimum end distance = 6 inches. Minimum anchor spacing = 6.75 inches. Minimum embedment = 6 inches
3. Anchor design conforms to ACI 318 with no supplementary reinforcement considered.
4. Allowable anchor lateral resistance calculated per NDS Part 12.3.
5. Anchor bending yield strength, Fyb = 100,000 psi & Concrete dowel bearing strength = 7,500 psi.
6. Load duration factor 1.0. Appropriate reduction factors per NDS shall be taken for treated or wet (moisture content greater than 19%) wood.
7. See Figure 30 for load directions.
FIGURE 30. SILL PLATE ANCHOR LOAD DIRECTIONS (F1 & F2)
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 36 OF 48
5.4.11 Quick Connector Post Caps (PCM) and End Post Caps (EPCM): The PCM and EPCM dimensions, nails
schedules, and allowable loads are provided in Table 22.
TABLE 22. PCM & EPCM ALLOWABLE LOADS
Part Name
Part No. Member Size Post Cap Dimensions (in)
Fasteners Allowable Load (lb)
Beam Post SP (0.55) DF-L (0.50)
Beam Post W1 W2 H1 L1 L2 Qty Size Qty Size Uplift F1 F2 Uplift F1 F2
12 g
a P
ost C
ap
PCM44
4x
4x
3-9/16
3-9/16
3-9/16 2-
7/16
11
12 16d 8 16d 2120 2050 1955 2085 1855 1795
PCM46 6x 5-9/16 13
PCM48 8x 7-9/16 15
PCM64
6x
4x
5-1/2
3-9/16
3-1/2 3-
13/16
11
PCM66 6x 5-9/16 13
PCM68 8x 7-9/16 15
PCM77 7-1/8 7-1/8 7-1/8 7-1/8 3-11/16 5-5/8 14-9/16
PCM84
8x
4x
7-1/2
3-9/16 3-1/2
5-5/8
11
PCM86 6x 5-9/16 3-3/8 13
PCM88 8x 7-9/16 3-1/2 15
16 g
a P
ost C
ap
PCM44-16
4x
4x
3-9/16
3-9/16
3-9/16 2-
7/16
11
12 16d 8 16d 1875
1815
1730
1845
1640
1590
PCM46-16 6x 5-9/16 13
PCM48-16 8x 7-9/16 15
PCM64-16
6x
4x
5-1/2
3-9/16
3-1/2 3-
13/16
11
PCM66-16 6x 5-9/16 13
PCM68-16 8x 7-9/16 15
PCM84-16 8x 4x 7-1/2 3-9/16 3-1/2 5-5/8 11
PCM86-16
4x
6x
3-9/16
5-9/16 3-3/8 2-
7/16
13
PCM88-16 8x 7-9/16 3-1/2 15
PCM44-16 4x 3-9/16 3-9/16 11
12 g
a E
nd P
ost
Cap
EPCM44
4x
4x
3-9/16
3-9/16
3-9/16 2-
7/16
7-1/4
8 16d 8 16d 2120 2050 1955 2085 1855 1795
EPCM46 6x 5-9/16 9-1/4
EPCM48 8x 7-9/16 11-1/4
EPCM64
6x
4x
5-1/2
3-9/16
3-1/2 3-
13/16
7-1/4
EPCM66 6x 5-9/16 9-1/4
EPCM68 8x 7-9/16 11-1/4
EPCM77 7-1/8 7-1/8 7-1/8 7-1/8 3-11/16 5-5/8 10-
13/16
EPCM84
8x
4x
7-1/2
3-9/16 3-1/2
5-5/8
7-1/4
EPCM86 6x 5-9/16 3-3/8 9-1/4
EPCM88 8x 7-9/16 3-1/2 11-1/4
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 37 OF 48
Part Name
Part No. Member Size Post Cap Dimensions (in)
Fasteners Allowable Load (lb)
Beam Post SP (0.55) DF-L (0.50)
Beam Post W1 W2 H1 L1 L2 Qty Size Qty Size Uplift F1 F2 Uplift F1 F2
16 g
a E
nd P
ost
Cap
EPCM44-16
4x
4x
3-9/16
3-9/16
3-9/16 2-
7/16
7-1/4
8 16d 8 16d 1875
1815
1730
1845
1640
1590
EPCM46-16
6x 5-9/16 9-1/4
EPCM48-16
8x 7-9/16 11-1/4
EPCM64-16
6x
4x
5-1/2
3-9/16
3-1/2 3-
13/16
7-1/4
EPCM66-16
6x 5-9/16 9-1/4
EPCM68-16
8x 7-9/16 11-1/4
EPCM84-16
8x
4x
7-1/2
3-9/16 3-1/2
5-5/8
7-1/4
EPCM86-16
6x 5-9/16 3-3/8 9-1/4
EPCM88-16
8x 7-9/16 3-1/2 11-1/4
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Nails designated as 16d shall be 16d common nails (0.162" x 3.5", Fyb = 90,000 psi).
3. Allowable load values provided are for wet service condition and for a load duration factor (CD) of 1.60, no further reduction required.
4. Loading in the F1 direction indicates shear forces parallel to the beam (Figure 31).
5. Loading in the F2 direction indicates shear forces perpendicular to the beam (Figure 31).
FIGURE 31. PCM & EPCM LOAD DIRECTIONS (UPLIFT, F1 & F2)
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 38 OF 48
5.4.12 Quick Connector QuickTie™ Girder Connector (QGC): Allowable uplift and lateral loads, and fastener
schedules for the QGC are provided in Table 23.
TABLE 23. QGC ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load2,3,10 (lbs)
Rafter/Truss Top Plates Uplift Lateral – F1 Lateral – F2
Type4,5,6 Quantity Type7,8,9 Quantity 1.0 1.6 1.0 1.6 1.0 1.6
SP (0.55)
¼" x 3" (wood screw)
16
QTO
1
4,350 4,455 1,665 2,040 935 935
5/8" TR 5,445 770 1,235 480 770
DF-L (0.50) QTO
4,015 4,455 1,630 1,910 885 885
5/8" TR 5,085 740 1,185 440 705
SPF (0.42) QTO
3,465 4,390 1,370 1,570 765 765
5/8" TR 4,455 685 1,090 345 550
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables
2. Loading in the F1 direction indicates shear forces parallel to the plane of the wall, connection to truss/rafter in withdrawal (see Figure 32).
3. Loading in the F2 direction indicates shear forces perpendicular to the plane of the wall, connection to truss/rafter in shear (see Figure 32).
4. Minimum specified screw requirements: Major diameter = 0.24", Minor (root) diameter = 0.185", Thread length (including tip) = 2.25" & Bending yield strength = 180,000 psi
5. Minimum reference lateral design value for wood screws, Z = 272 lb (SP), 251 lb (DF-L) & 217 lb (SPF)
6. Minimum reference withdrawal value for wood screws, W = 168 lb (SP), 132 lb (DF-L) & 86 lb (SPF)
7. The minimum allowable tensile strength of QTO (5/16" QuickTie™ Orange Cable) is 4,455 lbs and threaded rod is 5,445 lbs.
8. QTO cable shall be installed per QuickTie™ installation instructions. 5/8" threaded rod and nut at top shall be finger tight at a minimum.
9. QTO cable or threaded rod shall be installed before connecting QGC to truss/rafter.
10. Tabulated values are applicable to a single sided connection, as shown in Figure 32.
FIGURE 32. QGC LOAD DIRECTIONS UPLIFT, F1 & F2)
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 39 OF 48
5.4.13 Quick Connector Light Tension Tie (LTT): Allowable uplift loads and fastener schedules for the LTT20B are
provided in Table 24. LTT20B Allowable Loads. Figure 33 shows the LTT20B in the installed condition.
TABLE 24. LTT20B ALLOWABLE LOADS
Species (Specific Gravity)
Fasteners Allowable Load2,3,4 (lbs)
Nail Anchor Bolt5,6 Uplift
Type Quantity Type Quantity 1.0 1.6
SP (0.55)
10d x 11/2 (0.148 x 1.5″)
10 ¾" 1"
1,120 1,120
DF-L (0.50) 1,050 1,050
SPF (0.42) 920 920
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. Refer to Appendix A: General Notes for Tables.
2. Allowable loads based on connector attached to 2x4 member from 1" above the base (i.e. no resistance from prying action).
3. Total deflection of connector assembly at allowable loads are 0.153" (SP), 0.148" (DF-L), and 0.138" (SPF).
4. Anchor bolt installation into any substrates should be designed to resist the allowable uplift loads.
5. Washer size is 2¼" x 2" x 3/16" with a 13/16" diameter hole.
FIGURE 33. INSTALLED LTT20B
5.4.14 The allowable loads provided in this TER are for the QTS only. The adequacy of the connected structural
framing members to resist the loads applied to them by the QTS, building type and occupancy and/or the
environment shall be verified in accordance with the requirements of the building code adopted by the
jurisdiction in which the project is to be constructed.
5.4.15 Portal Frame with Hold-Downs (PFH)
5.4.15.1 Use of Method PFH shall be in accordance with IRC Section R602.10 and Section R602.10.6.2.
5.4.15.2 The maximum allowable tensile loads (based on Allowable Stress Design) of the QTS are presented in
Table 1.
5.4.15.3 Two QuickTie™ Orange cables shall be used to meet the required two (2) 3500 lb hold-downs, with one
(1) QuickTie™ Orange on each side of the pier. QuickTie™ Blue cables shall be used on the non-pier
end of the portal frame where only a single 1000 lb hold-down is required. The detail below using QTS is
considered equivalent to the Method PFH detail of the IRC (Figure 34).
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 40 OF 48
FIGURE 34. DESIGN FOR PORTAL FRAME WITH QUICKTIE™ CABLES
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 41 OF 48
6 INSTALLATION
6.1 The QTS and Quick Connectors shall be installed in accordance with the manufacturer’s published installation
instructions and this TER. In the event of a conflict between the manufacturer’s installation instructions and this
TER, the more restrictive shall govern.
6.2 A copy of the manufacturer’s published installation instructions shall be available at all times on the jobsite during
installation.
6.3 SPArtan™ Sill Plate Anchor Installation:
6.3.1 Clean the top surface of sill plate and mark the SPArtan™ anchor location(s).
6.3.2 Use a rotary hammer drill and SPArtan™ stepped drill bit (sold by QuickTie™ Products, Inc., see Figure 35)
to drill a hole in the sill plate. Stop and remove wood dust as necessary (see Figure 36).
FIGURE 35. PROPRIETARY SPARTAN™ DRILL BIT (SUPPLIED BY QUICK TIE PRODUCTS, INC.)
FIGURE 36. INSTALLATION OF SPARTAN™
6.3.3 Once the drill bit hits concrete, take precaution not to overwork the drill and/or drill bit. Intermittently, stop and
clean concrete dust from the hole. If necessary, use compressed air (or other means) to remove debris
around hole. Stop drilling when the wood bit stopper hits the top surface of sill plate. Over drilling may
damage the carbide tips of wood bit.
6.3.4 Install SPArtan™ anchor using an impact gun with square drive bit. Stop once the anchor flange hits the top
surface of sill plate. Note: Appropriate Personal Protection Equipment (PPE) must be worn.
6.4 PBA (Post Base Anchor) Installation:
6.4.1 Use all fasteners as specified in Table 18 to achieve the full capacity.
6.4.2 The designer or specifier shall check the requirements and capacity of wood post and concrete (embedment,
edge distance, and end distance) for resisting uplift loads.
6.4.3 Nails (16d common) and fastener assembly [⅝″ threaded rod with heavy hex nut (or anchor bolt) and washer
(2¾″ x 2¾″ x ⅜″)] are not included.
6.4.4 Clean concrete surface, place PBA Strap, and install fastener assembly.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 42 OF 48
6.4.5 Place stand-off plate and then the wood post. The top of the heavy hex nut must be installed flush with
underside of stand-off plate with a square washer below the hex nut.
6.4.6 Use specified fasteners to attach wood post to PBA Strap.
6.5 QuickTie™ Girder Connector (QGC):
6.5.1 The QTO cable shall be installed per manufacturer installation instructions.
6.5.2 Threaded rod and nut shall be installed finger tight, at a minimum.
6.5.3 QTO cable or threaded rod shall be connected to the top plate prior to fastening the QGC to the truss/rafter.
7 TEST ENGINEERING SUBSTANTIATING DATA
7.1 Test Reports for Evaluation of QuickTie™ (QT) System and Quick Connectors for QT Assembly’s Tension Load
Strength and Elongation Properties (Pre-load and 30+ Day Relaxation), by SBC Research Institute (SBCRI).
7.2 Engineering calculations and Allowable Load Verification Reports on the QuickTie™ System (QTS) for Allowable
Design Loads, prepared by Qualtim, Inc.
7.3 Letter of Justification for HA8 Seismic & Hurricane Clip Allowable Load.
7.4 Engineering report for QuickTie™ used in a portal frame application, prepared by Qualtim, Inc.
7.5 Test Reports for Evaluation of HTS and MTS connectors by Product Testing, Inc.
7.6 Test Reports for connector uplift and lateral loads by SBCRI.
7.7 Test report for QTS assemblies by Adhesives Technology Corporation.
7.8 Some information contained herein is the result of testing and/or data analysis by other sources which conform to
IBC Section 1703 and relevant professional engineering law. DrJ relies on accurate data from these sources to
perform engineering analysis. DrJ has reviewed and found the data provided by other professional sources to be
credible.
7.9 Where appropriate, DrJ’s analysis is based on design values that have been codified into law through codes and
standards (e.g., IBC, IRC, NDS®, and SDPWS). This includes review of code provisions and any related test data
that aids in comparative analysis or provides support for equivalency to an intended end-use application. Where
the accuracy of design values provided herein is reliant upon the published properties of commodity materials
(e.g., lumber, steel, and concrete), DrJ relies upon the grade mark, stamp, and/or design values provided by raw
material suppliers to be accurate and conforming to the mechanical properties defined in the relevant material
standard.
8 FINDINGS
8.1 When used and installed in accordance with this TER and the manufacturer’s installation instructions, the
product(s) listed in Section 1.1 are approved for the following:
8.1.1 QTS and Quick Connectors are approved for use in Seismic Design Categories A through E.
8.1.2 QTS and Quick Connectors are approved for use where the maximum wind speed is not more than 170 mph,
in accordance with ASCE/SEI 7-05, and 215 mph, in accordance with ACSE/SEI 7-10 and ASCE/SEI 7-16.
8.2 IBC Section 104.11 (IRC Section R104.11 and IFC Section 104.9 are similar) states:
104.11 Alternative materials, design and methods of construction and equipment. The provisions of this code are not
intended to prevent the installation of any material or to prohibit any design or method of construction not specifically prescribed
by this code, provided that any such alternative has been approved. An alternative material, design or method of construction
shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the
provisions of this code, and that the material, method or work offered is, for the purpose intended, not less than the equivalent
of that prescribed in this code…Where the alternative material, design or method of construction is not approved, the building
official shall respond in writing, stating the reasons the alternative was not approved.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 43 OF 48
8.3 This product has been evaluated in the context of the codes listed in Section 2 and is compliant with all known
state and local building codes. Where there are known variations in state or local codes applicable to this TER,
they are listed here.
8.3.1 No known variations
9 CONDITIONS OF USE
9.1 Loads applied shall not exceed those recommended by the manufacturer or as defined in this TER.
9.2 Structural framing members (e.g., wood, masonry, concrete, steel, etc.) connected with the QTS and Quick
Connectors shall be designed in accordance with the requirements of their specific design standards/
specifications as referenced in the building code adopted by the jurisdiction in which the project is to be
constructed.
9.3 Each QTS and/or Quick Connector shipment shall contain the manufacturer’s installation instructions. A copy of
the installation instructions must be available at the jobsite at all times during installation.
9.4 The QTS shall be installed by contractors trained and certified by QuickTie™ Products, Inc.
9.5 Each QTS and Quick Connectors that are exposed directly to weather, or subject to salt corrosion in coastal
areas, as determined by the local building official, shall be protected in accordance with the building code adopted
by the jurisdiction in which the project is to be constructed.
9.6 Where required by the building official, also known as the authority having jurisdiction (AHJ) in which the project is
to be constructed, this TER and the installation instructions shall be submitted at the time of permit application.
9.7 Any generally accepted engineering calculations needed to show compliance with this TER shall be submitted to
the AHJ for review and approval.
9.8 Design loads shall be determined in accordance with the building code adopted by the jurisdiction in which the
project is to be constructed and/or by the Building Designer (e.g., owner or registered design professional).
9.8.1 Design loads on the QuickTie™ System (QTS) and Quick Connectors are determined based on the most
critical load combination resulting from the load combinations in IBC Section 1605.3.1.
9.9 At a minimum, this product shall be installed per Section 6 of this TER.
9.10 This product is manufactured under a third-party quality control program in accordance with IBC Section 104.4
and 110.4 and IRC Section R104.4 and R109.2.
9.11 The actual design, suitability, and use of this TER, for any particular building, is the responsibility of the owner or
the owner's authorized agent. Therefore, the TER shall be reviewed for code compliance by the building official
for acceptance.
9.12 The use of this TER is dependent on the manufacturer’s in-plant QC, the ISO/IEC 17020 third-party quality
assurance program and procedures, proper installation per the manufacturer’s instructions, the building official’s
inspection, and any other code requirements that may apply to demonstrate and verify compliance with the
applicable building code.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 44 OF 48
10 IDENTIFICATION
10.1 The product(s) listed in Section 1.1 are identified by a label on the board or packaging material bearing the
manufacturer’s name, product name, TER number, and other information to confirm code compliance.
10.2 Additional technical information can be found at quicktieproducts.com.
11 REVIEW SCHEDULE
11.1 This TER is subject to periodic review and revision. For the most recent version of this TER, visit
drjcertification.org.
11.2 For information on the current status of this TER, contact DrJ Certification.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 45 OF 48
APPENDIX A: GENERAL NOTES FOR TABLES
1. Allowable loads are in pounds.
2. Unless noted otherwise, nails are common wire nails of the pennyweight noted in the tables. Nails shall
comply with ASTM F1667 and shall have the following minimum bending yield strengths, Fyb.
8𝑑, 𝐷 = 0.131 𝑖𝑛. , 𝐹𝑦𝑏 = 100,000 𝑝𝑠𝑖
10𝑑, 𝐷 = 0.148 𝑖𝑛. , 𝐹𝑦𝑏 = 90,000 𝑝𝑠𝑖
16𝑑, 𝐷 = 0.162 𝑖𝑛. , 𝐹𝑦𝑏 = 90,000 𝑝𝑠𝑖
3. Nails designated as 8d x 1½ are assumed to be 0.131″ x 1.5″ nails, nails designated as 8d are assumed to be
0.131″ x 2.5″ nails, nails designated as 10d x 1½ are assumed to be 0.148″ x 1.5″ nails, and nails designated
as 10d are assumed to be 0.148″ x 3″ nails. The number of fasteners shown is the minimum required to
achieve the loads shown.
4. Tabulated allowable loads listed for a load duration factor of 1.00 (i.e. “Normal” load duration) are to be used
in applications in which the shortest load duration in the combination of loads is 10 years. These values may
be increased for applications in which the governing load duration factor is 1.15 or 1.25 in accordance with
NDS up to the tabulated allowable loads for load duration factors of 1.33 and 1.60 or in accordance with the
building code adopted by the jurisdiction in which the project is to be constructed.
5. The allowable loads included in this Technical Evaluation Report are for QuickTie™ Connectors only. All
framing members shall be designed in accordance with the building code adopted by the jurisdiction in which
the project is to be constructed.
6. Load capacities in the design tables are valid for the species shown. For other species, adjust values in
accordance with NDS.
7. Unless indicated otherwise, the allowable loads provided in these tables assume the connector is attached to
a wood member with a minimum nominal thickness of 2″.
8. Allowable simultaneous loads in more than one direction on a single connector must be evaluated using the
following equation:
𝐷𝑒𝑠𝑖𝑔𝑛 𝐿𝑜𝑎𝑑 𝑈𝑝𝑙𝑖𝑓𝑡
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝐿𝑜𝑎𝑑 𝑈𝑝𝑙𝑖𝑓𝑡+
𝐷𝑒𝑠𝑖𝑔𝑛 𝐿𝑜𝑎𝑑 𝑃𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑡𝑜 𝑊𝑎𝑙𝑙 𝑃𝑙𝑎𝑡𝑒
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝐿𝑜𝑎𝑑 𝑃𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑡𝑜 𝑊𝑎𝑙𝑙 𝑃𝑙𝑎𝑡𝑒+
𝐷𝑒𝑠𝑖𝑔𝑛 𝐿𝑜𝑎𝑑 𝑃𝑒𝑟𝑝𝑒𝑛𝑑𝑖𝑐𝑢𝑙𝑎𝑟 𝑡𝑜 𝑊𝑎𝑙𝑙 𝑃𝑙𝑎𝑡𝑒
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝐿𝑜𝑎𝑑 𝑃𝑒𝑟𝑝𝑒𝑛𝑑𝑖𝑐𝑢𝑙𝑎𝑟 𝑡𝑜 𝑊𝑎𝑙𝑙 𝑃𝑙𝑎𝑡𝑒< 1.0
9. The building designer is responsible for determining the simultaneous loading conditions.
10. When cross-grain bending or cross-grain tension cannot be avoided in the members, mechanical
reinforcement to resist such forces should be considered.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 46 OF 48
APPENDIX B: ASCE 19 SECTION 2 CONTRACT DOCUMENTS AND SHOP DRAWINGS
2.1 Contract Documents
2.1.1 Contract drawings. The Contract Drawings shall indicate the horizontal and vertical location of the cables and their
connections for a specified load and temperature, typically the final dead load condition at the ambient temperature.
Dimensions and loading data shall be shown to enable the computation of cable lengths under the specified condition. Required
prestressing at erection shall be shown.
Terminations, fittings, anchorages, and other support details shall be fully detailed or sufficient data shall be provided to enable
their selection and procurement. The required camber of supporting structural members and the required initial out-of-plumb
of columns shall be shown on the drawings. The erection procedure modeled in the structural analysis and design shall be
outlined in the contract documents with a statement indicating whether it is a suggested procedure or is mandatory because
of controlling loadings or displacements of the cables or the supporting structure.
2.1.2 Contract specifications. For each cable in the proposed cable structure, the Contract Specifications shall indicate the
diameter (size), the type of cable, the wire coating, the grade of cable, prestretching requirements and the applicable material
or testing specification. If there are additional design requirements for cables, they shall be included in the contract
specifications. The required tension on the cables when length and diameter measurements are made shall be indicated. Cable
and fitting manufacturing tolerances required for design or erection conditions shall also be given. The Construction Documents
shall also state the erection tolerances, both for the final geometry of the system and the prestressing forces. The Contract
Specifications shall identify all other required submittals, including shop drawings and test reports.
2.2 Shop Drawings
Drawings for the fabrication of cables and fittings shall reflect the requirements indicated in the Contract Documents. Exact
locations, material, sizes, and lengths of all cables and fittings shall be shown, as well as fabrication and preparation procedures
for cables and fittings. Where approved substitutions or changes from the contract documents are made, an alternate member
or fitting shall be detailed, that will satisfy the loading and configurations indicated in the Contract Documents
As part of the Shop Drawings, Separate erection drawings shall be prepared to show the critical sequence, procedures, and
methods of erection. The Erection Drawings shall be accompanied by an erection analysis; see section 3.4.5.
Shop Drawings and test reports shall be submitted to the Engineer for review.
3.4.5 Erection Analysis
A structural analysis shall be performed for the suggested or mandatory erection procedure considering the effects listed in
section 3.4.1. Should deviations be made in the suggested erection procedure, the erector shall have an independent
professional engineer experienced in cable-system erection perform an erection analysis to match the revised methods,
equipment, and sequence.
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 47 OF 48
APPENDIX C: DESIGN LOADS FOR QTB(L) AND QTG(L)
For uplift resistance, on-center spacing, allowable loads and design notes are provided in Table 25 and Figure 37 for the
QTB(L) Blue 3/16″ System and the QTG(L) Green ¼″ System.
TABLE 25. QUICKTIE™ SYSTEM (QTS) ALLOWABLE LOADS FOR UPLIFT RESISTANCE
Uplift (lbs) per Truss (assumes trusses @ 2 ft o.c.)
QTB(L) Blue 3/16″ Spacing1 QTG(L) Green ¼″ Spacing1
3,180 N/A 2'-0"
2,800 N/A 2'-3"
2,600 N/A 2'-5"
2,400 N/A 2'-8"
2,200 N/A 2'-11"
2,000 N/A 3'-2"
1,910 2'-0" 3'-4"
1,800 2'-1" 3'-6"
1,700 2'-3" 3'-9"
1,600 2'-5" 4'-0"
1,500 2'-7" 4'-3"
1,400 2'-9" 4'-3"
1,300 2'-11" 4'-5"
1,200 3'-2" 4'-7"
1,100 3'-6" 4'-10"
1,000 3'-10" 5'-1"
950 4'-0" 5'-2"
900 4'-3" 5'-4"
850 4'-6" 5'-6"
800 4'-9" 5'-8"
775 4'-11" 5'-9"
750 5'-1" 5'-10"
725 5'-3" 5'-11"
700 5'-5" 6'-1"
675 5'-8" 6'-2"
650 5'-11" 6'-3"
625 6'-1" 6'-5"
600 6'-4" 6'-6"
575 6'-8" 6'-8"
550 6'-10" 6'-10"
TER 0910-01: QUICKTIE™ SYSTEM (QTS)
SUBJECT TO RENEWAL 4/1/2021
© 2020 DRJ ENGINEERING, LLC
PAGE 48 OF 48
Uplift (lbs) per Truss (assumes trusses @ 2 ft o.c.)
QTB(L) Blue 3/16″ Spacing1 QTG(L) Green ¼″ Spacing1
525 7'-0" 7'-0"
500 7'-2" 7'-2"
475 7'-4" 7'-4"
450 7'-7" 7'-7"
425 7'-9" 7'-9"
≤ 400 8'-0" 8'-0"
SI: 1 in = 25.4 mm, 1 lb = 4.45 N
1. The exact location can change slightly if the maximum spacing between any two QuickTie™ Systems does not exceed 8′ +/- 3″ on either side. Therefore, an absolute maximum spacing of 8′ – 6″ is acceptable.
2. The allowable design load with edge distance equal to or greater than 2-1/4″: QTB(L) Blue 3/16″ QuickTie™ = 1,910 lbs. / QTG(L) Green ¼″ QuickTie™ = 3,180 lbs.
3. Space all QuickTie™ Systems as specified in this table for all walls subject to uplift loads.
4. All QuickTie™ Systems shall be installed according to these specifications unless designed and certified by a registered design professional.
5. QTB(L) Blue 3/16″ QuickTie™ / QTG(L) Green ¼″ QuickTie™ specified in this table are embedded 4″ into minimum 2,500 psi concrete using an epoxy capable of resisting the given loads.
6. Loads require a minimum ½″ thick gypsum wall board on each side of the wall fastened to studs with 1½″ long wallboard nails spaced at 6″ o.c. at edges and 12″ o.c. in the field.
7. Use only QuickTie™ System materials as specified and supplied by QuickTie™ Products, Inc.
FIGURE 37. QUICKTIE™ SYSTEM (QTS) ALLOWABLE LOADS FOR UPLIFT RESISTANCE