88
WATER COOLED WATER CHILLERS -SCREW TYPE- Installation, Operation and Maintenance Instructions. Technical Catalog RCUE40WG2-240WG2 (R407C) Capacity 134 kW-696 kW Heat Pump Option Heating Capacity 161 kW-824 kW Design Information

Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

WATER COOLEDWATER CHILLERS-SCREW TYPE-

Installation, Operation and Maintenance Instructions.

Technical Catalog

RCUE40WG2-240WG2 (R407C)Capacity 134 kW-696 kWHeat Pump OptionHeating Capacity 161 kW-824 kW

Design Information

Page 2: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start
Page 3: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

0

TABLE OF CONTENTS

1. IMPORTANT NOTICE................................................................................................................. 1

2. FEATURES AND BENEFITS...................................................................................................... 12.1. NEW CHILLER PICTURE.....................................................................................................................12.2. COMPRESSOR....................................................................................................................................22.3. CONTROL ............................................................................................................................................32.4. HEAT EXCHANGER.............................................................................................................................42.5. NEW ELECTRONIC EXPANSION VALVE ...........................................................................................4

3. OPERATION INSTRUCTIONS ................................................................................................... 43.1. HITACHI WATER COOLED WATER CHILLER MODELS: RCUE 40-240 WG2 ..................................4

4. COMPONENTS OF CHILLER .................................................................................................... 54.1. STRUCTURE DRAWING .....................................................................................................................5

5. PREPARATION INITIAL CHECK ............................................................................................... 65.1. INITIAL CHECK ....................................................................................................................................65.2. PLACING THE UNIT.............................................................................................................................65.3. CENTRE OF GRAVITY ........................................................................................................................75.4. SERVICE SPACE AND FOUNDATION................................................................................................85.5. TRANSPORTATION BY RIGGING.......................................................................................................9

6. INSTALLATION .......................................................................................................................... 106.1. ELECTRICAL WIRING .........................................................................................................................106.2. WATER PIPING....................................................................................................................................126.3. MINIMUM INTERNAL SYSTEM WATER VOLUME .............................................................................136.4. WATER CONTROL ..............................................................................................................................136.5. BMS CONNECTION.............................................................................................................................156.6. CSC-5S.................................................................................................................................................216.7. INSTALLATION FINAL CHECK............................................................................................................24

7. TEST RUNNING.......................................................................................................................... 257.1. PREPARATION ....................................................................................................................................257.2. TEST RUNNING...................................................................................................................................257.3. INSTRUCTIONS AFTER TEST RUNNING ..........................................................................................26

8. CONTROLLER ADJUSTMENT .................................................................................................. 268.1. CONTROL SYSTEM.............................................................................................................................278.2. CONTROLLER ADJUSTMENT ............................................................................................................28

9. SELF-INSPECTION FUNCTIONS .............................................................................................. 309.1. ALARM INDICATION............................................................................................................................309.2. NORMAL INDICATION.........................................................................................................................319.3. FUNCTION FOR INDICATION OF OPERATION CONDITION ............................................................31

10. CONTROL SYSTEM ................................................................................................................. 36

11. MAINTENANCE ........................................................................................................................ 3911.1. COMPONENTS ..................................................................................................................................3911.2. LUBRICATION....................................................................................................................................3911.3. DEPOSITS..........................................................................................................................................3911.4. CLEANING METHOD .........................................................................................................................4011.5. WINTER SHUTDOWN........................................................................................................................4111.6. SPRING START-UP ...........................................................................................................................4111.7. PART REPLACEMENT ......................................................................................................................4111.8. REFRIGERATION CYCLE..................................................................................................................4211.9. REFRIGERANT CYCLE DIAGRAM OF HITACHI WATER COOLED CHILLER.................................4211.10. COMPRESSOR REMOVAL..............................................................................................................4411.11. SAFETY AND PROTECTION CONTROL ........................................................................................4411.12. NORMAL OPERATING PRESSURE................................................................................................4611.13. TEST RUNNING AND MAINTENANCE RECORD ...........................................................................4711.14. DAILY OPERATING RECORDS.......................................................................................................4811.15. SERVICING FOR R407C REFRIGERANT SYSTEM .......................................................................48

12. TROUBLESHOOTING .............................................................................................................. 49

Page 4: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

13. GENERAL SPECIFICATIONS..................................................................................................5113.1. GENERAL DATA................................................................................................................................5113.2. OPTION LINE UP...............................................................................................................................54

14. DRAWINGS...............................................................................................................................5514.1. DIMENSIONAL DRAWINGS ..............................................................................................................5514.2. WIRING DIAGRAMS ..........................................................................................................................60

15. MODEL SELECTION ................................................................................................................7015.1. SELECTION EXAMPLE .....................................................................................................................7015.2. PERFORMANCE TABLE ...................................................................................................................7115.3. ELECTRICAL DATA...........................................................................................................................7715.4. SOUND DATA ....................................................................................................................................78

16. APPLICATION DATA ...............................................................................................................7916.1. WORKING RANGE ............................................................................................................................7916.2. PART LOAD PERFORMANCE ..........................................................................................................7916.3. ETHYLENE GLYCOL APPLICATION.................................................................................................80

17. COMPONENTS DATA ..............................................................................................................8117.1. COMPRESSOR..................................................................................................................................8117.2. CONDENSER AND WATER COOLER ..............................................................................................81

Page 5: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

IMPORTANT NOTICE 1/1

1. IMPORTANT NOTICE

HITACHI pursues a policy of continuing improvement indesign and performance of Products. The right is thereforereserved to vary specifications without notice.HITACHI cannot anticipate every possible circumstancethat might involve a potential hazard.No part of this manual may be reproduced without writtenpermission.Signal words (DANGER, WARNING and CAUTION) areused to identify levels of hazard seriousness. Definitionsfor identifying hazard levels are provided below with theirrespective signal words.

DANGER:Immediate hazards which WILL result in severepersonal injury or death.

WARNING:Hazards or unsafe practices which COULD resultin sever personal injury or death.

CAUTION:Hazards or unsafe practices which COULD resultin minor personal injury or product or propertydamage.

NOTE:Useful information for operation and/or maintenance.

If you have any questions, contact your contractor ordealer of HITACHI.This instruction gives a common description andinformation for this water cooled water Chiller which youoperate as well as for other models.This water cooled water Chiller has been designed forthe following temperatures. Operate the water cooledwater Chiller within this range.

Working Range °CMaximum Minimum

Condenser Water

OutletTemperature

45*(55)

22

Chilled Water

OutletTemperature

155

**(-10)

(*) In case of High Condensing option and Heat Pumpoperation option.

(**) In case of low water temperature option.

This instructions should be considered as a permanentpart of the water cooled water Chiller equipment andshould remain with the water cooled water Chillerequipment.

2. FEATURES AND BENEFITS

2.1. NEW CHILLER PICTURE

HITACHI is a world leader in technology and withcontinual research and product development, now offersa screw type Water Cooled Chiller.

A wide range of capacities are available from 134 kW to696 kW.Heating operation is available for option. HeatingCapacities are available from 161 kW to 824 kW.

Page 6: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

2/2 FEATURES AND BENEFITS

2.2. COMPRESSOR

THE SAMURAI RANGEINCORPORATES THE LATESTDEVELOPMENT OF HITACHI´SSCREW COMPRESSORTECHNOLOGY FOR THE NEWMILLENNIUM.

Highly Reliable HITACHI Two-PoleMotor

Built-in Oil Separator (Cyclone oilseparator)

Oil Sight Glass

Oil Heater

High precision Twin Screw Rotors

Suction Filter

TWIN SCREW COMPRESSOR

By having so few moving parts, it has become highly reliablewith very low noise level and low vibration

PRINCIPLE OF COMPRESSION

CONTINUOUS CAPACITY CONTROL

HITACHI´s Continuous Capacity Control system usesadvanced electronic controls to position the infinitelyvariable slide valve within each compressor.This modulation allows exact load control and accuratechilled water temperature without the need forexpensive inverters.

Reciprocating Screw

AM

PL

ITU

DE

(µm

)

Time (second)

-LOW VIBRATION-

Discharge Port

Suction Port

Cooling load = continuos capacity control

CO

OL

ING

LO

AD

%

Stepcontrol

TIME (Hour)

Page 7: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

FEATURES AND BENEFITS 2/3

ENERGY SAVING

Thanks to Continuous Capacity Control, 15~20% energysaving is possible compared with current step controlsystems due to the following:-The cooling load can be more closely matched

-Continuous Capacity Control takes advantage of highefficiency part load performance.

-Frequent compressor starts and stops are eliminated.

-PART LOAD PERFORMANCE-

2.3. CONTROL

MANY FUNCTIONS

Newly developed Control Board has many functionsshown below as standard.

Forced compressor load control

2 Different temperature setting

Memory data in alarm

Automatic restart after power failure

Heating operation (Heat pump operation option)

etc...

PRECISE TEMPERATURECONTROL

Combination of "Continuous CapacityControl Compressor" and "HITACHI´sunique electronic controls" enable theChiller to control outlet water temperatureprecisely, independent of cooling load.This control benefits not only air-conditioning but also industrial processuse.

-CONTINUOUS CAPACITY CONTROL-

-CONVENTIONAL STEP CONTROL-

MO

TO

R I

NP

UT

(%

)

COOLING CAPACITY (%)

ContinuousCapacityControl

StartOutlet Water Temperature

Load Up 2

Load Up 1(Quick cooling)

Neutral =2 C Standard

(Minimum 0.5°C)

Load Down

TIME

WA

TE

R T

EM

PE

RA

TU

RE

WA

TE

R T

EM

PE

RA

TU

RE

Restart

1st step

Final step

OutletTemperature

TemperatureBand 7 C(normally)

Page 8: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

1/4

2.4. HEAT EXCHANGER

PLATE TYPE HEAT EXCHANGER

The new Samurai Chillers are equipped with plate typeHeat Exchangers, which have many advantages whencompared with conventional Shell & Tube heatexchanger as described beside:

Less Refrigerant (Small Internal Volume)-Clean (Stainless Steel)

-High efficiency (closer approach temperature)

Plate type heat exchanger can provide improved coolingcapacity for R407C

2.5. NEW ELECTRONIC EXPANSION VALVE

This unit is equipped with an electronic expansion valve toprovide sophisticated control under any temperaturecondition.The electronic expansion valve provides reduced electricalpower consumption compared to the classical system.

3. OPERATION INSTRUCTIONS

3.1. HITACHI WATER COOLED WATER CHILLER MODELS: RCUE 40-240 WG2

To Start the Unit.

1.Open the water inlet and outlet valves.

2.After assuring that all control switches have been cutOFF, and the “LOCAL/REMOTE” switch on theprinted circuit board is in the “LOCAL” position, turnON the power switch.

3.Confirm that phases R, S and T are correctlyconnected. The correct phase connection can bechecked by a phase sequence indicator. If notcorrectly connected, the compressor does not startdue to activation of a reversal phase protectiondevice. Cut the main switch and interchange two ofthree terminals, R, S and T at the main power sourceterminals.

4.Set the changeover switch to “cool” or “Heat” (In caseof Heat Pump operation option)

5.Fully open the liquid line stop valves.

6.Operate the cooling (Hot) and chilled water pump.

7.Set the Dip SW at the desired temperature

8.Depress the “ON” push button of the operation Switch

To Stop the Unit

1.Depress the “OFF” push button of the operationswitch.

2.Switch OFF the main power source when the unit isshut down for a long period of time.

Pilot Lamp

The red LED indicates the normal operation.

When the orange LED is activated, any one of thesafety devices may be functioning.

Please contact your service shop, if this condition isdetected.

Daily Checking

1.Check the power supply to ensure that it is proper.

2.Check for abnormal sounds and vibration.

3.Check the unit amperage.

4.Check the operating pressure.

Troubleshooting

Unit Does Not Start

1.Is the main switch ON?

2.Is the main fuse OK?

3.Is the cooling (Hot) and chilled water running?4.Are the setting temperature calling for the cooling

operation?

Poor Cooling (Heating) Operation

1.Is there sufficient water supplied to the condenserand the cooler?

2.Is the setting temperature correct?3.Is the operating pressures normal?

Maintenance

1.Replace the oil, if it has been deteriorated2.Clean the unit with a cleaner.

3.Clean the condenser and the water cooler . (It isrecommended that a specialist will be contacted forthis type of work.)

SHELL & TUBE PLATE

CA

PA

CIT

Y (

%)

Page 9: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

COMPONENTS OF CHILLER 4/5

4. COMPONENTS OF CHILLER

4.1. STRUCTURE DRAWING

HITACHI Water cooled Water Chiller (Example of 1 Compressor Chiller)

Re

mo

te/L

oca

l Ch

an

ge

ove

rS

witc

h is

Re

ar

Sid

e.

Nam

e

Ele

ctro

nic

Exp

an

sio

n v

alv

e

Liq

uid

Lin

e S

top

Va

lve

Drie

r

Liq

uid

Sig

ht

Gla

ss

So

len

oid

Va

lve

(o

nly

fo

r 8

0,

15

0,

24

0 H

P)

Eco

no

miz

er

(on

ly f

or

80

, 1

50

, 2

40

HP

)

Hig

h P

ress

ure

Sw

itch

Pre

ssu

re R

elie

f V

alv

e

Nam

e

Co

mp

ress

or

Wa

ter

Co

ole

r

Wa

ter

Co

nd

en

ser

Ele

ctri

cal B

ox

Po

we

r W

irin

g S

up

ply

Ch

eck

va

lve

Oil

Sig

ht

Gla

ss

Op

era

tion

Sw

itch

ST

RU

CT

UR

E D

RA

WIN

G O

F H

ITA

CH

I W

AT

ER

C

OO

LE

D-W

AT

ER

CH

ILL

ER

UN

IT (E

xa

mp

le:

RC

UE

80

WG

2)

Page 10: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

5/6 PREPARATION INITIAL CHECK

5. PREPARATION INITIAL CHECK

5.1. INITIAL CHECK

Required Materials

Measure and Architectural Information RegardingInstallation Location

Installation Location

Confirm that the final installation location is providedwith convenient piping and wiring work. Strong waterrunoff should be avoided.

Installation Space

Check for obstacles which hamper maintenance work inthe space specified in Fig.1.

Foundation

Check to ensure that the foundation is flat, level andsufficiently strong, taking into account the maximumfoundation gradient (Fig. 2) and the unit weight balance.Confirm elevation provision for the unit on a solid basewith an iron frame or concrete curbs shown in chap. 5.4.

In order to obtain proper clearance beneath the unit foron-the-ground installation, where foundation boltsshould be sunk into concrete.

Unit

Check to ensure that the unit has been transportedwithout damage. File a damage claim with thetransportation companies if mishandling due totransportation company negligence is suspected.

Transportation

Secure the route to the final installation location byconfirming the dimensions, (Refer to the “Unit GeneralData” in Catalogue).

5.2. PLACING THE UNIT

DANGER:-Do not install the unit outdoors. If installed outdoor,

an electrical leakage will occur, since the unit hasnot been designed for dew protection

-If leakage is detected, stop the unit and contact theinstaller or a service shop. Do not use a naked firenear the refrigerant gas. If a naked fire is utilisednear the refrigerant gas, refrigerant is turned into aharmful phosgene compound.

WARNING:This unit is operated with refrigerant R407C, whichis non-flammable and non-poisonous. However,refrigerant itself is heavier than the atmosphere sothat a floor is covered with refrigerant gas ifrefrigerant is leaked. Therefore, keep goodventilation to avoid choke during servicing.

CAUTION:Check to ensure that valves are correctly opened. Ifnot opened, serious damage will occur to thecompressor due to an abnormally high pressure.

Tools And InstrumentsPincers, Wrenches, Facilities to Transport andPlace The Unit.

TransportationTransportation the unit as close to the finalinstallation location as practical beforeunpacking is accomplished. Provide adequatefacilities to place the unit on the foundation, withsufficient consideration given to thoseindividuals performing the installation.

UnpackingFollow the instructions marked on the packing.

Fig. 1

Maximum Foundation GradientThe unit should be installed in an uprightposition within the gradient shown in below Fig.

Fig. 2

10 mm5 mm

ChillerUnit

Page 11: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

PREPARATION INITIAL CHECK 5/7

5.3. CENTRE OF GRAVITY

Centre of Gravity

RCUE - WG2Model

40 50 60 80 100 120 150 180 200 240

Location Weight Distribution (kg)

1234

225175215165

230175225170

245190250190

275215285225

410415415415

430440445450

445465470485

600700625730

610710645750

620735675795

Operating Weight

(kg) 780 800 875 1000 1655 1765 1865 2655 2715 2825

Location of Center of Gravity (mm)

DimensionA

DimensionB

538

490

531

490

522

490

509

482

521

815

516

813

509

803

511

1262

508

1263

501

1259

Centre of Gravity

A

Control Panel

B1

2

3

4

Page 12: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

5/8 PREPARATION INITIAL CHECK

5.4. SERVICE SPACE AND FOUNDATION

RCUE 40, 50, 60, 80WG2 RCUE 100, 120, 150WG2

RCUE 180, 200, 240WG2

Detail Of Foundation

N° Name N° Name1 4-∅ 26 (Mounting Holes) 7 Washer2 Bottom Frame 8 Nut3 Vibration proof Rubber Mat (4 positions) 9 Foundation bolt (M20)4 Vibration proof Rubber Mat (8 positions) 10 Rubber Bush (OPTION)5 Vibration proof Rubber Mat (12 positions) 11 Steel Plate (1 mm)6 Vibration proof Rubber Mat (1 mat per position) OPTION 12 Concrete

Page 13: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

PREPARATION INITIAL CHECK 5/9

5.5. TRANSPORTATION BY RIGGING

5.5.1. TRANSPORTATION BY RIGGING

Hook wire cables and apply field-supplied spreader barson the top of the unit (see below figure) to prevent theunit from damage due to cable scratches. The unitshould remain in an upright position even during rigging.The wire cable to rig the unit shall be three timesstronger than the unit weight. Check to ensure that therigging bolts are tightly fixed to the unit. The riggingangle shall be greater than 60° as shown. The weight ofthe unit is indicated on the unit label.

DANGER:Do not stand below the unit when rigging.

CAUTION:Put clothes between wires and the unit to avoiddamages.

5.5.2. TRANSPORTATION BY ROLLER

When rolling the unit, put at least 6 equal-sized rollersunder the base frames. Each roller must carry both theouter frames, and must be suited to balance the unit(see the centre of gravity in page 5/7).

5.5.3. DECLINING THE UNIT DURINGTRANSPORTATION

WARNING:

Do not decline the unit more than an angle of 15°as shown in the figure during transportation. Ifdeclined more than an angle of 15°, the unit mayfall down.

.

Smaller than 15º

N° Name

1 60° (or more)2 Electrical Box3 4 x 30 Rigging Holes4 Spreader Bar (Field supplied)5 Lifting Bracket (Field supplied)

Page 14: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/10 INSTALLATION

6. INSTALLATION

6.1. ELECTRICAL WIRING

Tools and InstrumentsOne Set of Wiring tools and Electrical Tester(Clamp Meter)

Schedule Check

WARNING:- Confirm that the field-selected electrical

components (main power switch, fuses, wires,conduit connections, wire terminals and others)are properly selected according to the “ElectricalData“ in this Technical Catalogue, and ensure thatthey comply with national and local codes.

- It is recommended that the main power switch belocked in the “OFF“ position, to prevent againstaccidental supply of power during equipmentservicing.

- Check to ensure that an earthling wire is correctlyconnected to the unit. This wire protects from anelectric shock. Utilisation of an earth leakagebreaker is necessary.

Main Power Wiring ProceduresConfirm that electrical power is not beingsupplied to the installation location prior to anyelectrical installation work.

1.Install the field-supplied main switch box (es) at aproperly selected location.

2.Install conduit connectors in the hole for the powerwiring.

3.Lead main power wires and the earthling wirethrough the connector to the screw terminals formain power and earthling in the magnetic switch box.The neutral wires for 380/50 Hz and 415 V/50 Hzpower supply should also be led through theconnector.

4.Firmly connect the wires with wire terminals to unitscrew terminals R, S, T and N according to belowfigure.

5.Connect the wires between the power source and thefield-supplied magnetic switches.

6.Consider that the main power source will not be leftturned OFF, easily, because it is necessary toenergise the oil heater even during unit stoppage.

N° Name

1 Main Power/Terminal Board (R,S,T,N)

2 Electrical Box

3 Main Power Switch

4 Main Power Wiring

5 Earth Wiring

Control Wiring

Connect the interlock wiring and control wiring betweenthe unit terminals and the magnetic switches for thewater pumps, according to the wiring label. The mainconnection to terminal N is required.

Page 15: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/11

N° Name

1In case of remote control operation this wireshall be removed.

2 R Phase

3 Neutral

4 Low Voltage / Remote Control

5 Run/Stop Signal

6 Alarm Signal

7 Alarm Lamp

8 Pump Interlock

9 Pump operation

10 Remote Control Switch (RSW-A) (OPTION)

11 2,3 cycles

12 3 cycles

N° Name

13 2 nd. Setting Temperature

14 External Thermostat Operation

15 Operation Mode (OPTION)

16Only used for:-Diff. Water Pressure switch (OPTION)-Flow Switch (OPTION)

17Force CompressorLoad Operation

18Free CoolingOutput signal (Only cycle Nº 1)

19In case of individual indication without RemoteControl Switch

20 Customer wiring

21 Force compressor load

22 Setting of low voltage control

NOTE:1.All the setting shall be performed before Power ON.

2.Remote / Local Change over Switch on OperationSwitch shall be set, to Remote.

3.Terminals 1 ~/21 are for AC220-240V,TerminalsA ~D are for DC24V. Terminals E ~F areH-link (Low signal)

Page 16: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/12 INSTALLATION

6.2. WATER PIPING

When piping connections are performed:

1. Connect all pipes as close as possible to the unit, sothat disconnection can be easily performed whenrequired.

2. Connect the condenser and water coolers in thesame unit to the same common water piping.

3. It is recommended for the piping of the chilled waterinlet and outlet that flexible joints be utilised, so thatvibration will not transmit.

4. Whenever permissible, sluice valves should beutilized for water piping, in order to minimize flowresistance and to mantain sufficient water flow.

5. Proper inspection should be performed to check forleaking parts inside and outside the system, bycompletely opening the condenser and chilled waterinlet and outlet valves to the condenser and watercooler.Additionally, equip valves to the inlet and outletpiping.Equip an air purge cock and a drain cock onthe water piping. The cock handle should be removedso that the cock can not be opened under normalcircumstances. If this cock is opened duringoperation, trouble will occur due to water blow-off.

6. Sufficiently perform insulation to keep the chilledwater piping cool and to prevent sweating of thepiping.

7. Under the condition where the ambient temperatureis low in winter, there is a case where equipment andpiping will become damaged during the shutdownperiods at night, because the water in the pump orpiping will be frozen. To prevent freezing of the water,it is effective to operate the pumps even duringshutdown period.HITACHI Chiller has the pump ON/OFF operationcontrol (see Wiring Diagram) water from piping.Additionally, in a case where measures such as waterdraining are difficult, utlize antifreeze mixture ofethylene glycol type or propylenen glycol type.

8. The common water pipes (Inlet/Outlet of condenserand cooler, field supplied, should be connected tocondenser and cooler directly.

CAUTION:-Never use an antifreeze mixture of the salt type,

because it possesses strong corrosioncharacteristics, and water equipment will bedamaged

-This product is equipped with plate type heatexchangers. In the plate heat exchanger, waterflows through a narrow space between the plates.Therefore, there is a possibility that freezing mayoccur if foreign particles or dusts are clogged. Inorder to avoid this clogging, provide a. 20 meshwater strainer at the inlet of condenser and chilledwater piping near the product. A 20 mesh waterstrainer is available as an option.

NOTE:HITACHI chiller has the pump ON/OFF operation control (see wiring diagram)

N° Name

1 Pressure Gauge

2 Strainer

3 Flexible Joint

4 Valve

Cooled Water Outlet

Chiller

Cooled Water Inlet

Condensing (Hot) Water Outlet

Condensing (Hot) Water Inlet

Page 17: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/13

CAUTION:In case of connecting some units to the samewater piping, design the water piping so that thewater distribution to each unit is equal (refer tofigure below) Imbalance of water distribution maycause a serious damage like a water freezing inthe heat-exchanger.

6.3. MINIMUM INTERNAL SYSTEM WATER VOLUME

To ensure the cooling operation at least 5 minuteswithout interruption, the internal chilled water volume inthe piping system should be greater than the minimumvolume as shown below.

NOTE:Minimum internal system water volume written belowis for standard ON/OFF differential, minimum internalsystem water volume shall be increased by thesetting of differential.

MODEL RCUE WG2 40 50 60 80 100 120 150 180 200 240

Condenser WaterFlow Range

Max. m3/h 48.1 57.4 69.8 82.3 114.9 139.6 157.8 186.2 214.9 246.8

Min. m3/h 14.3 17.1 20.7 24.7 38.0 41.4 47.4 56.0 64.0 74.2

Chilled Water Flow RangeMax. m3/h 38.6 45.9 55.8 66.6 91.9 111.4 127.8 150.8 172.3 199.9

Minimum InternalSystem Water Volume

m3 0.42 0.51 0.61 0.73 1.01 1.23 1.41 1.66 1.89 2.20

Internal Volume in Water Cooler Liter 15.1 16.7 21.5 23.9 44.8 44.8 44.8 64.4 64.4 71.6

Internal Volume in Condenser Liter 14.8 18.6 23.9 27.6 40.2 49.4 49.4 71.6 71.6 82.7

6.4. WATER CONTROL

CAUTION:When industrial water is applied for chilled waterand condenser water, industrial water rarelycauses deposits of scales or other foreignsubstances on equipment. However, well water orriver water may in most cases contain suspendedsolid matter, organic matter, and scales in greatquantities. Therefore, such water should besubjected to filtration or softening treatment withchemicals before application as chilled water.

It is also necessary to analyse the quality of water bychecking pH, electrical conductivity, ammonia ioncontent, sulphur content, and others, and to utiliseindustrial water only if problem is encountered throughthese check.

The following is the recommended standard waterquality.

Water Pump

Heat LoadSide

Chiller Unit

Page 18: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/14 INSTALLATION

Chilled Water System Tendency (1)

ItemCirculating

Water(20 ºC Less

than)

Supply Water CorrosionDepositsof Scales

Standard QualitypH (25 °C)

6.8 ~ 8.0 6.8 ~ 8.0

Electrical Conductivity (mS/m) (25°C){µS/cm} (25 °C) (2)

Less than 40Less than 400

Less than 30Less than 300

Chlorine Ion (mg CI¯/I) Less than 50 Less than 50

Sulphur Acid Ion (mg SO42¯/I) Less than 50 Less than 50

The Amount of Acid Consumption (pH 4.8)(mg CaCO3/I)

Less than 50 Less than 50

Total Hardness (mg CaCO3 /I) Less than 70 Less than 70

Calcium Hardness (mg CaCO3 /I) Less than 50 Less than 50

Silica L (mg SIO2 /I) Less than 30 Less than 30

Reference QualityTotal Iron (mg Fe/I)

Less than 1.0 Less than 0.3

Total Cupper (mg Cu/I) Less than 1.0 Less than 0.1

Sulphur Ion (mg S2¯/I) It shall not be detected.

Ammonium Ion (mg NH4+/I) Less than 1.0 Less than 0.1

Remaining Chlorine (mg CI/I) Less than 0.3 Less than 0.3

Floating Carbonic Acid (mg CO2/I) Less than 4.0 Less than 4.0

Index of Stability 6.8 ~ 8.0 -

NOTE:1. The mark “ ” in the table means the factor concerned with the tendency of corrosion or deposits of scales.2. The value showed in “{}” are for reference only according to the former unit.

Page 19: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/15

6.5. BMS CONNECTION

6.5.1. SYSTEM

BMS connection is available by usingHARC70-CE1(OP), optional BMS interface unit.

One interface HARC70-CE1 can connect up to 4Chillers from a remote place using H-Link connection(Hitachi communications protocol).Protocol used by HARC70-CE1 (OP) is LonWorks. It canconnect only one Chiller.Physical channel connection with interface is FTT-10ª

6.5.2. SIGNAL

ON/OFF Chiller All HARC’SControl Operation

Outlet Water Setting All HARC’S

ON/OFF All HARC’S

Chilled Water Outlet Setting All HARC’S

Chilled Water Outlet Temperature All HARC’S

Chilled Water Inlet Temperature. All HARC’S

Alarm Codes All HARC’S

Operation Status All HARC’S

Discharge Pressure 1,2 Only HARC OP

Suction Pressure 1,2 Only HARC OP

Discharge Temperature 1,2 Only HARC OP

Suction Temperature 1,2 Only HARC OP

Compressor Status (ON/OFF) 1,2 Only HARC OP

Outlet Water Temp. 1 Only HARC OP

State Monitoring

Water Temp. In Evap. Backside 1 Only HARC OP

Chiller 1 Chiller 2 Chiller 3 Chiller 4

HARC70-CE1

Upper Monitoring Device

H-Link

LonWorks

Chiller 1

HARC70-CE1 OP

Upper Monitoring Device

H-Link

LonWorks

Page 20: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/16 INSTALLATION

6.5.3. CAUTION ON USE HARC70-CE1 (OP)

Please use it correctly according to the following"CAUTION ON USE.”

As for the following:

“HARC” indicate “ HARC70-CE1” or“HARC70-CE1 OP”

“Monitoring Device “ indicate “ upper connectingdevice for supervise “, and “Control Panel” indicate“Control panel of Chiller unit”.

“SNVT” Indicate “Standard Network Variables Types”

1.Install HARC in a grounded metal box.

2.Install a short circuit breaker in the power supply ofHARC.

3.The transmission line between HARC and Chiller unitshould be “0.75mm2 twisted-Pair cable”. If it is notused, then it cannot communicate between HARC andChiller unit, and it does not work properly.

4.After an abnormal transmitting occurs between HARCand Chiller unit, and Chiller unit stops, in the case ofoperation starting by the hand operation, then onceturn off Chiller unit’s power supply, and turn on thepower supply. If it isn’t carried out, then Chiller unitkeeps the condition of transmission alarm.

5.After an abnormal transmitting occurs between HARCand Chiller unit, and Chiller unit stops, in the case ofoperation starting by Monitoring Device, then transmitan operation order after you transmit a stop orderonce. If it isn’t carried out, it can't start.

6.After Chiller unit, under control by HARC, is stoppedby the control panel, and operation is done from theMonitoring Device, then transmit an operation orderafter you transmit a stop order once. If it isn’t carriedout, it can’t start.

7.Don't set the setting temperature to Chiller unit, undercontrol by HARC, by the control panel. If it is done, thesetting temperature is changed. And, as for the settingtemperature, which changed in this case, transmit toMonitoring device.

8.After the setting temperature is changed by MonitoringDevice, in the case of turned off Chiller unit’s powersupply, set the setting temperature by Monitoringdevice again. If it isn’t carried out, then the settingtemperature becomes to the temperature by settingcontrol panel.

9.If power failure occurs in Chiller unit, under control byHARC, it may not revert to the condition before thepower failure. Try to detect that the operationcondition of Chiller unit changed, by the MonitoringDevice. If Chiller unit stopped due to the power failure,then transmit an operation order from the MonitoringDevice after the power supply restoration. And,transmit the setting temperature, mode from theMonitoring device. If it isn’t carried out, and thenChiller unit is stopping, and the setting temperature,mode is the initialisation value by Chiller unit.

10.When SNVT, which is transmitted from HARC, isused by other control device, premise that there istwo minutes delay between the transmitting SNVTand the movement Chiller unit . If it isn’t premised,then a problem may occurs in the control system.

11.Don't interrupt the power supply of HARC when youuse SCPT in HARC. Even if it exceedsMaxSendTime, when SNVT is not transmitted fromHARC, and SNVT is transmitted below with thesetting value of MinSendTime, then transmit SCPTagain . If it isn’t carried out, SCPT value continuesmaintaining “0”.

12.If the setting of control panel change Remote toLocally, and set Remote again, then set the settingtemperature and mode from the Monitoring Deviceagain. If it does not set, then the setting temperatureand mode continue maintaining the initialisation valueby Chiller unit.

13.When the abnormal transmitting occurs between theMonitoring Device and HARC, then the condition ofthe Monitoring Device may not correspond with thecondition of HARC. Set MaxSendTime and try thatthe condition of the Monitoring Device correspondswith the condition of HARC in the interval ofMaxSendTime .

14.It can't be used with the except for “ stop signal ofinput terminal of Chiller unit “.

6.5.4. DIMENSIONAL DRAWING ANDSPECIFICATIONS OF HITACHI GATEWAY(MODEL HARC70-CE1/HARC70-CE1 0P)

Structural Drawing

Mounting Dimensions

Terminal Cover

After OpenAfter Open

Down

ID number of NEURON CHIP

On Rear Side of Cover

Mounting by Screw

Mounting on DIN Rail

Center Line of DIN Rail

Page 21: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/17

System Wiring

N° Description Wire Size

Power SupplyPower Wire AC 220/240V(Field Supplied)

2mm2 shielded

Connection Wiring Between Chiller Signal Wiring DC 5V(Field Supplied)

0.75mm2 twisted-pair cableMax. length 1000m

Ground Earth Wire(Field Supplied)

-

Connection Wire Between LonWorks Signal Wire DC 5V(Field Supplied)

-

Marking of Terminals

Mark Indication

POW Red: Power Supply (AC220/240V)

IRPGreen: Lighted DuringTransmission Between LONWORKS

PACYellow: Lighted DuringTransmission Between Chiller

Wiring Procedures

Section Wiring Method Remark

1 220-240V PowerSource HARC70-CE1(OP)

Pow

er

Lin

e

Earthing Wire

Upper System HARC70-CE1(OP) Non-polar

Contr

ol C

ircu

it

HARC70-CE1(OP) Water Chillers Non-polar

Chiller Unitnº1

Gateway

AC / AC / E

AC / AC / E

LON / H-LINK

LON / H-LINK

Page 22: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/18 INSTALLATION

Network Variables and Setting (HARC70-CE1)

ChillerNumber

WaterCooled

Condenserless

AirCooled

AirHeat

Pump

SVNTNumber

Name TypeLONMARKSNVT No

Description Contents Remarks

0 O O O O nv0 nviChillerEnable_0 SNVT_switch 95 On/Off OrderByte 1: Value 0 (Fixed)Byte 2: State 0/1 = STOP/RUN

0 O O O O nv1 nviCoolSetpt_0 SNVT_temp_p 105Cool Water TemperatureSetting

2 Bytes: -2000 ~ 2500 = -20 ~ 25 ºC

0 O O O O nv2 nviMode_0 SNVT_hvac_mode 108 Operation Mode Setting1 byte:1 = HVAC_HEAT (Heating)3 = HVAC_COOL (Cooling)

0 - - - O nv3 nviHeatSetpt_0 SNVT_temp_p 105 Hot Water Temperature Setting 2 bytes: 3000 ~ 6000 = 30 ~ 60 ºC

Provide an interval of5 seconds of morebetween each setting

0 O O O O nv4 nvoOnOff_0 SNVT_switch 95 On/Off stateByte 1: Value 0 (Fixed)Byte 2: State 0/1 = STOP/RUN

0 O O O O nv5 nvoActiveSetpt_0 SNVT_temp_p 105 Temperature Setting 2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC

0 - - - - nv6 nvoActualCapa_0SNVT_lev_percent(Not Available)

81Operation Capacity (Not usedfor continous capacity)

NOT USED

0 O O O O nv7 nvoLvgCHWTemp_0 SNVT_temp_p 105 Chilled outlet temperature 2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC

0 O O O O nv8 nvoEntCHWTemp_0 SNVT_temp_p 105 Chilled inlet temperature 2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC

Those values areupdated each 60seconds.When setting pointsare changed fromHARC change torelated point isdetected not waiting60 seconds.If no water chiller isconnected thesevalues are set to 0

0 O O O O nv9 nvoAlarmDescr_0 SNVT_str_asc 36 Alarm code31 Bytes: 4 first bytes alarm description as shown in chiller.5th byte always 0. Others undefined

0 O O O O nv10 nvoChillerStat_0 SNVT_chlr_status 127 Chiller Status

3 bytes:Byte 1: Chiller Run Mode0: Chlr_Off (OFF Mode) 2:Chlr_Run (Run Mode)Byte 2: Chiller Operation Mode1: HVAC_HEAT (Heating) 3:HVAC_COOL (Cooling)A: HVAC_FREE_COOL (Cooling Thermostat Off)Byte 3: Chlr Statebit 0: 0/1 (no alarm / alarm)bit 1: 0/1 (run not available / run available)bit 2: 0/1 (central / local)bits 3 ~ 7: Not used

0 - - - - nv11 untest_0

0 - - - - nv12 untest_1

0 - - - - nv13 untest_2

0 - - - - nv14 untest_3

SNVT_press (NotAvailable)

30 NOT USED NOT USED Not used

1 O O O O nv15 nviChlrEnable_1 SNVT_switch 95 On/Off Order Same than nv0

1 O O O O nv16 nviCoolSetpt_1 SNVT_temp_p 105Cool Water TemperatureSetting

Same than nv1

1 O O O O nv17 nviMode_1 SNVT_hvac_mode 108 Operation Mode Setting Same than nv2

1 - - - O nv18 nviHeatSetpt_1 SNVT_temp_p 105 Hot Water Temperature Setting Same than nv3

Provide an interval of5 seconds of morebetween each setting

1 O O O O nv19 nvoOnOff_1 SNVT_switch 95 On/Off state Same than nv4

1 O O O O nv20 nvoActiveSetpt_1 SNVT_temp_p 105 Temperature Setting Same than nv5

1 - - - - nv21 nvoActualCapa_1SNVT_lev_percent(Not Available)

81Operation Capacity (Not usedfor continous capacity)

NOT USED

1 O O O O nv22 nvoLvgCHWTemp_1 SNVT_temp_p 105 Chilled outlet temperature Same than nv7

1 O O O O nv23 nvoEntCHWTemp_1 SNVT_temp_p 105 Chilled inlet temperature Same than nv8

1 O O O O nv24 nvoAlarmDescr_1 SNVT_str_asc 36 Alarm code Same than nv9

1 O O O O nv25 nvoChillerStat_1 SNVT_chlr_status 127 Chiller Status Same than nv10

Those values areupdated each 60seconds.When setting pointsare changed fromHARC change torelated point isdetected not waiting60 seconds.If no water chiller isconnected thesevalues are set to 0

1 - - - - nv26 untest_4

1 - - - - nv27 untest_5

1 - - - - nv28 untest_6

1 - - - - nv29 untest_7

SNVT_press (NotAvailable)

30 NOT USED NOT USED Not used

2 O O O O nv30 nviChlrEnable_2 SNVT_switch 95 On/Off Order Same than nv0

2 O O O O nv31 nviCoolSetpt_2 SNVT_temp_p 105Cool Water TemperatureSetting

Same than nv1

2 O O O O nv32 nviMode_2 SNVT_hvac_mode 108 Operation Mode Setting Same than nv2

2 - - - O nv33 nviHeatSetpt_2 SNVT_temp_p 105 Hot Water Temperature Setting Same than nv3

Provide an interval of5 seconds of morebetween each setting

2 O O O O nv34 nvoOnOff_2 SNVT_switch 95 On/Off state Same than nv4

2 O O O O nv35 nvoActiveSetpt_2 SNVT_temp_p 105 Temperature Setting Same than nv5

2 - - - - nv36 nvoActualCapa_2SNVT_lev_percent(Not Available)

81Operation Capacity (Not usedfor continous capacity)

NOT USED

2 O O O O nv37 nvoLvgCHWTemp_2 SNVT_temp_p 105 Chilled outlet temperature Same than nv7

2 O O O O nv38 nvoEntCHWTemp_2 SNVT_temp_p 105 Chilled inlet temperature Same than nv8

2 O O O O nv39 nvoAlarmDescr_2 SNVT_str_asc 36 Alarm code Same than nv9

2 O O O O nv40 nvoChillerStat_2 SNVT_chlr_status 127 Chiller Status Same than nv10

Those values areupdated each 60seconds.When setting pointsare changed fromHARC change torelated point isdetected not waiting60 seconds.If no water chiller isconnected thesevalues are set to 0

2 - - - - nv41 untest_8SNVT_press (NotAvailable)

30

2 - - - - nv42 untest_9 30

2 - - - - nv43 untest_10 30

2 - - - - nv44 untest_11 30

NOT USED NOT USED Not used

3 O O O O nv45 nviChlrEnable_3 SNVT_switch 95 On/Off Order Same than nv0

3 O O O O nv46 nviCoolSetpt_3 SNVT_temp_p 105Cool Water TemperatureSetting

Same than nv1

3 O O O O nv47 nviMode_3 SNVT_hvac_mode 108 Operation Mode Setting Same than nv2

3 - - - O nv48 nviHeatSetpt_3 SNVT_temp_p 105 Hot Water Temperature Setting Same than nv3

Provide an interval of5 seconds of morebetween each setting

3 O O O O nv49 nvoOnOff_3 SNVT_switch 95 On/Off state Same than nv4

3 O O O O nv50 nvoActiveSetpt_3 SNVT_temp_p 105 Temperature Setting Same than nv5

3 - - - - nv51 nvoActualCapa_3SNVT_lev_percent(Not Available)

81Operation Capacity (Not usedfor continous capacity)

NOT USED

3 O O O O nv52 nvoLvgCHWTemp_3 SNVT_temp_p 105 Chilled outlet temperature Same than nv7

3 O O O O nv53 nvoEntCHWTemp_3 SNVT_temp_p 105 Chilled inlet temperature Same than nv8

3 O O O O nv54 nvoAlarmDescr_3 SNVT_str_asc 36 Alarm code Same than nv9

3 O O O O nv55 nvoChillerStat_3 SNVT_chlr_status 127 Chiller Status Same than nv10

Those values areupdated each 60seconds.When setting pointsare changed fromHARC change torelated point isdetected not waiting60 seconds.If no water chiller isconnected thesevalues are set to 0

3 - - - - nv56 untest_12 30

3 - - - - nv57 untest_13 30

3 - - - - nv58 untest_14 30

3 - - - - nv59 untest_15

SNVT_press (NotAvailable)

30

NOT USED NOT USED NOT USED

O O O O nv60 nciMaxSendTime

O O O O nv61 nciMinSendTime

Page 23: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/19

Network Variables and Setting (HARC70-CE1 OP)

WaterCooled

Condenserless

AirCooled

Air HeatPump

SVNTNumber

Name TypeLONMARKSNVT No

Description Contents Remarks

O O O O nv0 nviChillerEnable_0 SNVT_switch 95 On/Off OrderByte 1: Value 0 (Fixed)Byte 2: State 0/1 = STOP/RUN

O O O O nv1 nviCoolSetpt SNVT_temp_p 105Cool Water TemperatureSetting

2 Bytes: -2000 ~ 2500 = -20 ~ 25 ºC

O O O O nv2 nviMode SNVT_hvac_mode 108 Operation Mode Setting1 byte:1 = HVAC_HEAT (Heating)3 = HVAC_COOL (Cooling)

- - - O nv3 nviHeatSetpt SNVT_temp_p 105 Hot Water Temperature Setting 2 bytes: 3000 ~ 6000 = 30 ~ 60 ºC

Provide an interval of 5seconds of more betweeneach setting

O O O O nv4 nvoOnOff SNVT_switch 95 On/Off stateByte 1: Value 0 (Fixed)Byte 2: State 0/1 = STOP/RUN

O O O O nv5 nvoActiveSetpt SNVT_temp_p 105 Temperature Setting 2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC

- - - - nv6 nvoActualCapaSNVT_lev_percent(Not Available)

81Operation Capacity (Not usedfor continous capacity)

NOT USED

O O O O nv7 nvoLvgCHWTemp SNVT_temp_p 105 Chilled outlet temperature 2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC

O O O O nv8 nvoEntCHWTemp SNVT_temp_p 105 Chilled inlet temperature 2 Bytes: -2000 ~ 6000 = -20 ~ 60 ºC

O O O O nv9 nvoAlarmDescr SNVT_str_asc 36 Alarm code31 Bytes: 4 first bytes alarm descriptionas shown in chiller. 5th byte always 0.Others undefined

O O O O nv10 nvoChillerStat SNVT_chlr_status 127 Chiller Status

3 bytes:Byte 1: Chiller Run Mode0: Chlr_Off (OFF Mode) 2:Chlr_Run (RunMode)Byte 2: Chiller Operation Mode1: HVAC_HEAT (Heating)3:HVAC_COOL (Cooling)A: HVAC_FREE_COOL (CoolingThermostat Off)Byte 3: Chlr Statebit 0: 0/1 (no alarm / alarm)bit 1: 0/1 (run not available / runavailable)bit 2: 0/1 (central / local)bits 3 ~ 7: Not used

O O O O n11 nvoDpress1 SNVT_press 30 Discharge Pressure 1 2 Bytes:0~30000 = 0~3,000 kPa

O O O O n12 nvoDpress1 SNVT_press 30 Discharge Pressure 2 2 Bytes:0~30000 = 0~3,000 kPa

O - O - n13 nvoDpress1 SNVT_press 30 Discharge Pressure 3 2 Bytes:0~30000 = 0~3,000 kPa

O - O - n14 nvoDpress1 SNVT_press 30 Discharge Pressure 4 2 Bytes:0~30000 = 0~3,000 kPa

- - O - n15 nvoDpress1 SNVT_press 30 Discharge Pressure 5 2 Bytes:0~30000 = 0~3,000 kPa

- - O - n16 nvoDpress1 SNVT_press 30 Discharge Pressure 6 2 Bytes:0~30000 = 0~3,000 kPa

O O O O n17 nvoSpress1 SNVT_press 30 Suction Pressure 1 2 Bytes:0~30000 = 0~3,000 kPa

O O O O n18 nvoSpress2 SNVT_press 30 Suction Pressure 2 2 Bytes:0~30000 = 0~3,000 kPa

O - O - n19 nvoSpress3 SNVT_press 30 Suction Pressure 3 2 Bytes:0~30000 = 0~3,000 kPa

O - O - n20 nvoSpress4 SNVT_press 30 Suction Pressure 4 2 Bytes:0~30000 = 0~3,000 kPa

- - O - n21 nvoSpress5 SNVT_press 30 Suction Pressure 5 2 Bytes:0~30000 = 0~3,000 kPa

- - O - n22 nvoSpress6 SNVT_press 30 Suction Pressure 6 2 Bytes:0~30000 = 0~3,000 kPa

O O O O n23 nvoDtemp1 SNVT_temp_p 105 Discharge Temp 1 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O O O O n24 nvoDtemp2 SNVT_temp_p 105 Discharge Temp 2 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - O - n25 nvoDtemp3 SNVT_temp_p 105 Discharge Temp 3 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - O - n26 nvoDtemp4 SNVT_temp_p 105 Discharge Temp 4 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

- - O - n27 nvoDtemp5 SNVT_temp_p 105 Discharge Temp 5 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

- - O - n28 nvoDtemp6 SNVT_temp_p 105 Discharge Temp 6 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O O O O n29 nvoSTemp1 SNVT_temp_p 105 Suction Temp 1 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O O O O n30 nvoSTemp2 SNVT_temp_p 105 Suction Temp 2 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - O - n31 nvoSTemp3 SNVT_temp_p 105 Suction Temp 3 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - O - n32 nvoSTemp4 SNVT_temp_p 105 Suction Temp 4 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

- - O - n33 nvoSTemp5 SNVT_temp_p 105 Suction Temp 5 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

- - O - n34 nvoSTemp6 SNVT_temp_p 105 Suction Temp 6 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

- - O O n35 nvoODtemp SNVT_temp_p 105 Outdoor Temperature 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O O O O n36 nvoCompOnOff1 SNVT_state x 16 83 Compressor Information 32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

O O O O n37 nvoCompOnOff2 SNVT_state x 16 83 Compressor Information 32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

O - O - n38 nvoCompOnOff3 SNVT_state x 16 83 Compressor Information 32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

O - O - n39 nvoCompOnOff4 SNVT_state x 16 83 Compressor Information 32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

- - O - n40 nvoCompOnOff5 SNVT_state x 16 83 Compressor Information 32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

- - O - n41 nvoCompOnOff6 SNVT_state x 16 83 Compressor Information 32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

O O O O n42nvoLvgCHWTemp1

SNVT_temp_p 105 Outlet Water Temp 1 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - O O n43nvoLvgCHWTemp2

SNVT_temp_p 105 Outlet Water Temp 2 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - O - n44nvoLvgCHWTemp3

SNVT_temp_p 105 Outlet Water Temp 3 2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O O - - n45nvoLvgCHWTemp4

SNVT_temp_p 105Water Temp in Cooler BackSide1

2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - - - n46nvoLvgCHWTemp5

SNVT_temp_p 105Water Temp in Cooler BackSide2

2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

O - - - n47nvoLvgCHWTemp6

SNVT_temp_p 105Water Temp in Cooler BackSide3

2 Bytes: -12700 ~12700 = -127 ~ 127 ºC

Those values are updatedeach 60 seconds.When setting points arechanged from HARC changeto related point is detectednot waiting 60 seconds.If no water chiller isconnected these values areset to 0

- - - - n48 unused 1 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n49 unused 2 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n50 unused 3 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n51 unused 4 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n52 unused 5 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n53 unused 6 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n54 unused 7 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n55 unused 8 SNVT_temp_p 105 NOT USED NOT USED NOT USED

- - - - n56 unused 9 SNVT_temp_p 105 NOT USED NOT USED NOT USED

O O O O nv57 nciMaxSendTime

O O O O nv58 nciMinSendTime

NOTE:

Set and use the variables in accordance with the above tables. (The variables based on "Chiller Part of LonMark FunctionProfile", however, some function and setting range have limitation)

Page 24: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/20 INSTALLATION

Space Requirements

NOTE:1.Before operating this gateway, initial settings by a

system integrator for the local LonWorks systemare necessary.

2.This gateway is designed to be connected withLonWorks network, and will not function by itselfwhen it is not connected.

3.The power lines and the signal lines shall beseparated with a minimum distance of 15cm.

4.It is necessary to set and adjust the Chillers andgateway before operating the system.

5."LonWork" "LonMark" are trademarks of EchelonCorporation registered in the USA and othercountries.

Specifications

Item Specifications

ConnectionCapacity

Maximum 4H-Link PCBs of HitachiChiller

Power Supply AC 1-PH, 220~240V±10% 50/60Hz

PowerConsumption

Maximum 10W

Ambient ConditionTemperatureRelative Humidity

0-45°C10-80% (with condition of nocondensation)

Net weight 0.6kg

Colour Grey (Munsell 5Y7/1 or similar)

Material of Box ABS resin molding material

Mounting MethodWall Mount (By 2 x M4 Screws), or onDIN Rail (35mm)

Mounting LocationIn Weather and Dust-Proofed ControlPanel

Accessories Core x 1, Capacitor x 1

Transceiver Using FTT-10A

Warranty

No warranty shall be applied for thecontrol and operation of the upper"LonWorks" side.Hitachi's liability shall cover only HitachiChillers, this gateway, and accessibilityby "LonWorks"

Transmitting Setting (On Chiller Control PCB)

Operation DSW

Before shipment, No. 1 pin of DSW10 is set atON side

ONOFF

In case that Chiller Unit quantity in the same H-Link is 2 or more, set No. 1 pin of DSW10 at theOFF side from 2nd Unit. If only one Chiller Unitis used, no setting is required.

ONOFF

In case of applying high voltage to the terminalTB1 (E,F), the fuse on the PCB is cut.In such a case, first connect the wiring to TB1(E,F) and then turn “ON” DSW-2

ONOFF

Page 25: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/21

6.6. CSC-5S

CSC-5S is a remote controller for Hitachi Water Chillers

6.6.1. SYSTEM

CSC-5S allows the individual control of a Chiller Unit as well as it allows a centralized and grouped controls of a maximumnumber of 8 chillers.

6.6.2. SIGNAL

Indication code Indication Content Unit RemarkControl

Monitoring

ON/OFF unit operation

Setting Temperature COOL °CSetting Temperature HEAT °COperation Mode

Control Data

C1Pd ~ C2Pd Discharge Pressure MPa

C1Ps ~ C2Ps Suction Pressure MPa

C1td ~ C2td Discharge Gas Temperature °CC1ts ~ C2ts Suction Gas Temperature °CC1tr ~ C2tr Liquid Refrigerant Temperature °C

Indicate Max. 6Refrigerant CircuitData

CEL Inlet Water Temperature °CCoL Outlet Water Temperature °C

CcoL Individual Water Piping Outlet Temperature °CThe display contentsdepend on chillerunit.

tSC Setting Temperature of Chilled Water °CtSH Setting Temperature of Hot Water °CtSCd Setting Analog Temperature of Chilled Water °C Not available

tSHd Setting Analog Temperature of Hot Water °C Not available

dF Differential Setting °CtA Ambient Temperature (Not available) °CCrno ROM No. of Chiller Unit

CvEr Version No. of Chiller Unit

rno ROM No. of Controller (CSC-5S)

Monitoring Data

CSC-5S

8 Chillers (Maximum)

Page 26: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/22 INSTALLATION

6.6.3. CAUTION ON USE OF CSC-5S

Follow strictly instructions of CSC-5S Installation Manual. This controls requires power supply ~1 220-240 V.

6.6.4. DIMENSIONAL DRAWING AND SPECIFICATIONS OF CSC-5S

Structural Drawing

Mounting Dimensions

System Wiring

Max. 8 Chiller Units

Chiller UnitChiller Unit

Power Supply

To TB2 of other Controller

Twist Pair Cable 1P-0.75mm2

Page 27: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

INSTALLATION 6/23

CSC-5S LAYOUT

SPACE REQUIREMENTS

TRANSMITTING SETTING (ON CHILLER CONTROL PCB)

Operation DSW

Before shipment, No. 1 pin of DSW10 is set at ON sideON

OFF

In case that Chiller Unit quantity in the same H-Link is 2 or more, set No. 1 pin ofDSW10 at the OFF side from 2nd Unit. If only one Chiller Unit is used, no setting isrequired.

ONOFF

In case of applying high voltage to the terminal TB1 (E,F), the fuse on the PCB is cut.In such a case, first connect the wiring to TB1 (E,F) and then turn “ON” DSW-2

ONOFF

More than 50 mm

ControlLine

PowerLine

Screw

(x2)

Do not run the power line and the control linethrough the same conduit tube.

Switch Box with Cover(Field-Supplied)

Power Supply Part

Page 28: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

6/24 INSTALLATION

6.7. INSTALLATION FINAL CHECK

Inspect the installation work according to all documents and drawings. Table below shows the minimum check points.

6.7.1. INSTALLATION WORK CHECK LIST

1. Is the unit solidly mounted and levelled?

2. Is the installation location adequate?

Indoor Installation

Space for Maintenance Work

Noise and Vibration

Sunshine and other Heat Sources

Appearance

3. Is the water piping system adequate?

Tube Size Water Drain

Length Water Control

Flexible Joint Air Purge

Insulation Pressure Control

Strainer

Common Pipes (for 3 cycles)

4. Is the electrical wiring system adequate?

Wire Size Tightened Connections

Switch Size Operation Control Devices

Fuse Size Safety Devices

Voltage and Hz Interlock

5. Have the R, S and T phases of the water Chillercorrectly been connected to the R, S and T phases ofthe main power source?

6. Are the stop valves for the condenser liquid line open?

7. Have the packing glands and the cap nuts for the stopvalves been tightened?

8. Is BMS connected correctly and operate as decided?

Page 29: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

TEST RUNNING 7/25

7. TEST RUNNING

7.1. PREPARATION

Tools and instrumentsHigh Pressure Compound Gauge. LowPressure Compound Gauge. Electrical Testerand General Tools.

CAUTION:- Switch On the main power switch, and energise the

oil heater for 12 hours before start-up, to sufficientlywarm the oil.

- Check to ensure that valves are correctly opened. Ifnot opened, serious damage will occur to thecompressor due to an abnormally high pressure.

- Remove the foreign particles and substances fromthe water piping without going through the watercoolers and condensers, and cleaning the waterstrainer filter before test runningg. Check to ensurethat no foreign particle and substance exists in thewater piping

7.2. TEST RUNNING

Test running should be performed as follows, when the unitis wired according to the HITACHI standard wiring label.

1. Switch ON the field-supplied pump and the coolingtower, and the pump and cooling tower will be startedimmediately. Check the condition and operation state ofthese components

2. Fully open the liquid line stop valve.

3. Set the operation switch to "ON", and the compressorwill be started in a few minutes after this operation,according to the following Operation Sequence Chart(Refer to pages 36 to 38).

Test running should be accomplished as follows.

CAUTION:

−When the unit is wired according to the HITACHIstandard wiring shown on the wiring label. Switch ONthe main power switch, and energize the oil heater for12 hours before start-up to sufficiently warm the oil.

−Each rotation direction of two rotors in the compressoris fixed so that a reversal phase protection device isequipped.

−However, the rotation direction should be checked witha following method:

−Confirm that phases R, S and T for the compressor iscorrectly connected. The correct phase connectioncan be checked by a phase sequence indicator. Ifnot, the compressor does not start due to activation ofthe reversal phase protection device.

- Cut the main switch and interchange two of threeterminals, R, S and T on the main terminals at the fieldconnection side in the unit.

1. Operate the pump for chilled water and otherauxiliary equipment such as fan coil units and airhandling units.Check to ensure that the chilled waterflows sufficiently and that other auxiliary equipmentoperate properly.

2. Set the switch at the desired temperature.

3. Depress the “ON“ push button, the compressor willbe started.

4. After system operation becomes stabilized, check thedischarge and suction pressures by 7-segment oncontrol panel.

5. Check to ensure that the thermostat functionsproperly.

6. Check to ensure that the control and protectivedevices function properly.

7. Starting timer and unload-starting timer are set at five(5), thirty (30) seconds, respectively, in accordancewith operation characteristics. Therefore, localadjustment should be avoided.

NOTE:- A loud sound occurs when this compressor is

stopped after the normal operation. However, thissound indicates no abnormalities and stops within afew seconds by the activation of the check valve.This sound is due to the reverse rotation of thescrew rotors, resulting from the pressure differencebetween the discharge and the suction pressure.

- Each compressor may show the different values ofrunning current due to individual capacity control foreach compressor. This is not abnormal.

Page 30: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

8/26 CONTROLLER ADJUSTMENT

7.3. INSTRUCTIONS AFTER TEST RUNNING

When the test running is completed, please instructcustomers about operation and periodic maintenancemethods before leaving the unit, by using Installation,Operation and Maintenance Manual. A special attention isrequired to the following caution:

CAUTION:-Do not cut off the power source switch during the

operating season. When the power source switch iscut off, the oil heater for screw compressor is notenergised, and the compressor might be damageddue to oil foaming at starting.

-When the operation season starts after longdisconnection of the power source switch, please turnon the power source switch 12 hours before startingoperation.

8. CONTROLLER ADJUSTMENT

High Cut Check (Fan Stop for Checking)(NOT AVAILABLE)

Chilled Water Temperature Setting(STANDARD: "+07")

Defrosting Set by Ambient Temperature (Heat Pump)(NOT AVAILABLE)

Continuous Capacity Control Setting(STANDARD)

Compressor starting Delay Time(STANDARD: 3 min)

Mode Set Switch A / H-LINK address(DEPEND ON MODEL)

Manual Defrost (Heat Pump)(NOT AVAILABLE)

Optional Function B(STANDARD: ALL OFF)

Optional Function C(STANDARD: ALL OFF)

Mode Set Switch B

Local/Remote Changeover Switch(STANDARD: "Local")

Cool/Heat Changeover Switch(STANDARD: "Cool", “Heat” is available only for Heat Pumpoperation Option)

Current Limitation(Not Available)

Neutral Zone Setting(STANDARD: "3")

Hot Water Temperature Setting for Heat Pump(STANDARD: "45", Available only for Heat Pump operationoption)

Optional Function A (Outernals signals, Self-Checking mode)(STANDARD: ALL OFF)

Pump Operation (STANDARD: OFF)

SWITCH POSITIONON

OFF ONON

OFF OFF

LED PUSHBUTTONSWITCH

7 SEGMENTS

Page 31: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

CONTROLLER ADJUSTMENT 8/27

8.1. CONTROL SYSTEM

Electrical Operation Control advanced HITACHI WaterChillers are as follows.

Capacity Control

All models are equipped with an unloading system for eachcompressor, in order to adjust the cooling capacity and toprovide precise temperature control for the chilled water,coupled with electronic thermostats.

Control Panel

ON switch, OFF switch, Power Supply Lamp, OperationLamp, Alarm Lamp, Operation/Alarm Indicator for eachrefrigerant cycle and check switch are mounted in theControl Panel. The Control Panel is located at a positionwhere easy access is available. Operation/Alarm indicatorcan display individual alarm codes such as High-Cut, Low-Cut etc. this function is very useful for detecting what alarmhas occurred. Check switches are for checking chilledwater temperature and alarm occurrence data. Chilledwater temperature setting switches, ON/OFF DifferentialSetting Switches, Remote-Local Switch and so on arelocated at the rear side of Control Panel, in order not toaccess during operation.

Operation Hour-Meter

This hour-meter indicates the sum of the compressoroperation

Printed Circuit Board

A micro-processor, relays and electronic components aremounted on the Printed Circuit Board. Increased reliabilityis assured due to the elimination of mechanical parts andwires. This board contains various function by applyingmicro-processor as follows:

Screw Compressor Cycling Protection Circuit.The electronic timer of the screw compressor cyclingprotection (ccp) connected in the compressor control circuitdelays the screw compressor restarting period forapproximately three (3) minutes for No.1 compressor, four(4) minutes for No.2 compressor, five (5) minutes for No.3compressor.

Electronic Thermostat Circuit.The electronic thermostat senses chilled water outlettemperature, and operate capacity control solenoid valvesof HITACHI screw compressor.

Screw Compressor Reversing Protection Circuit.This circuit is composed of a reverse-phase protectiondevices, preventing reverse operation of the screwcompressor, because the screw compressor definitelycannot be operated in the wrong direction, due to themisconnection of the main power phases.

Restart after Short Period Power-Failure.In the case that a power failure shorter than 2 secondsoccurred, compressors can be restarted automaticallywithin 3 minutes after power supply.If power failure longer than 2 seconds occurres,compressor also can be restarted by selection switchsetting.

Power SupplyAll models need only single power supply . Control circuit ispowered from main power circuit. For remote control, pumpinterlock and pump operation, see the diagram of"Customer Wiring".

Page 32: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

8/28 CONTROLLER ADJUSTMENT

8.2. CONTROLLER ADJUSTMENT

Layout of control panel of printed circuit board is shown inthe Figure of the last page.Setting functions are followings:

Chilled Water Outlet Temperature SettingSwitch = RSW1 and RSW2

= 7°C for chilled water outlet temperature isrecommended. The RSW1 and RSW2 dials are alreadyset at 7 and 0.Setting at the figures from 3 to 9 of the RSW2 dialshould not be permitted.

Hot Water Outlet Temperature Setting

Switch = RSW3 and RSW4 (Available only for HeatPump operation option) = 45ºC for hot water Outlettemperature is recommended. The RSW3 and RSW4dials are already set at 5 and 4.

Current limitation = RSW5, 6, 7

= The RSW5, RSW6 and RSW7 should not bepermitted.

Neutral Zone Setting Switch = RSW8

= 2 degrees is standard. The RSW8 dial is already set at3 = 2 degrees.The figures at the RSW8 dial means as follows:

Figure 0 1 2 3 4 5 6 7 8 9Band(degree) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Continuous Capacity Control Setting Switch =DSW5Definition of Special Terms.

Continuos Capacity Control SettingSwitch=DSW5

Temperature Band for Stop Setting Switch= 1 degree is standard. The figure 1 and 2 of the DSW5switch are already set at figure 1 = ON side, 2 = OFF side.The locations at the figure 1 and 2 of the DSW5 mean asfollows.

Figure 1 2 1 2 1 2 1 2Location ON ON ON OFF OFF ON OFF OFFBand(degree) 0.5 1.0 1.5 2.0

Temperature Band for Restart Setting Switch= 2 degree is standard. The figure 3 and 4 of the DSW5switch are already set at figure 3 = ON side, 4 = OFF side.The locations at the figure 3 and 4 of the DSW5 mean asfollows.

Figure 3 4 3 4 3 4 3 4Location ON ON ON OFF OFF ON OFF OFFBand(degree) 1.0 2.0 3.0 4.0

Differential Temperature of Load-up 2 Mode Setting Switch= 1 degree is standard. The figure 5 of the DSW5 switch isalready set at ON side.The locations at the figure 5 of the DSW5 mean as follows.

Figure 5 5Location ON OFFBand(degree) 1.0 3.0

Output Signal Time for Load-up 1 Mode Setting Switch= 12 seconds is standard. The figure 6 of the DSW5 switchis already set at ON side.The locations at the figure 6 of the DSW5 mean as follows.

Figure 6 6Location ON OFFTime(second) 12 24

Output Signal Time for Load-up 2 and Load-down ModeSetting Switch= 2 seconds is standard. The figure 7 and 8 of the DSW5switch are already set at figure 7 = ON side,8 = ON side.The locations at the figure 7 and 8 of the DSW5 means asfollows.

Figure 7 8 7 8 7 8 7 8Location ON ON ON OFF OFF ON OFF OFFTime(second) 2 4 6 8

Interval of Output Signal Time for Load-up 2 and Load-down Mode Setting Switch.=60 seconds is standard. The figure 9 and 10 of the DSW5switch are already set at figure 9=ON side, 10=ON side.The locations at the figure 9 and 10 o f the DSW5 mean asfollows.

Figure 9 10 9 10 9 10 9 10Location ON ON ON OFF OFF ON OFF OFFTime(second) 60 90 120 30

Load Up 1 Mode

WaterTemperature

Load Up 2 ModeSet byDSW5,5 pin

Set byRSW8

Set byDSW5, 1&2 pin

Neutral Zone

Water OutletTemperature

Water InletTemperature

Inlet Water Temp.when system isstopped withThermos Off mode

Setting Temperature

Load Down Mode

Thermo OffStandardSetting

6°C

7°C

9°C

10°C

Set byDSW5,3&4 pin

Page 33: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

CONTROLLER ADJUSTMENT 8/29

Setting of Compressor Cycling ProtectionStart = DSW2

* Time Delay Starting for Compressor Setting Switch *The compressor will be started after this setting time.= 3 minutes is standard. The figure 1 and 2 of the DSW2switch are already set at figure 1 = OFF side, 2 = OFF side.The locations at the figure 1 and 2 of the DSW2 mean asfollows.

Figure 1 2 1 2 1 2 1 2

Location ON ON ON OFF OFF ON OFF OFF

Time(minute) 0.5 6 10 3

Manual Set Switch A = DSW3

* Compressor Forcedly Stop Mode Setting Switch *Switches "DSW3-1" is for No.1 compressor, "DSW3-2" forNo.2, and "DSW3-3" for No.3.If necessary to stop any compressors, turn these switches(DSW3-1, DSW3-2 and DSW3-3 to the OFF side, thecompressors corresponding to these switches are turned tothe OFF side will be stopped).The figures of the DSW3 switch are initially set as followsdepend on the compressor quantity.This switch is for servicing, therefore, all the compressorsshall be ON for normal operation.

Figure 1 2 3 1 2 3Location ON OFF OFF ON ON OFFModel 1 Comp. System 2 Comp. System

Figure 1 2 3

Location ON ON ON

Model 3 Comp. System

Setting at the figures from 4 to 10 of the DSW3 switchshould not be permitted (always at OFF side).

Note: The figures 2 and 3 of DSW3 which are Notcorresponding to the equipped compressor number arealways turned to the OFF side.

Manual Set Switch B = DSW4

The figure 2, 6 and 7 of the DSW4 switch must be turned tothe ON side.Setting at the figures 1,3, 4, 5 and 8 of the DSW4 switchshould not be permitted (always at OFF side).

The figures 9 and 10 of DSW4 switch are for compressorsize setting as follows.

Figure 9 10 9 10 9 10 9 10

Location OFF ON ON OFF ON ON OFF OFF

Compressor 40 HP 50 HP 60 HP 80 HP

Selection Switch for Cooling/ HeatingOperation = SW8

The SW8 selection SW is used for selecting cooling orheating operation. However, Standard model in this seriesare for cooling only. So that Heating function is availableonly for Heat Pump operation option.Turn SW8 to the upper side for cooling operation or lowerside for heating operation.

Selection Switch for Local/ Remote Operation= SW6

= Local operation is standard. So that the SW6 selectionswitch is turned to the upper side.If Remote operation is required, the SW6 selection switchis turned to the upper side.

Selection Switch for Local/ Remote PumpOperation = SW7

= The SW7 selection switch is turned to the lower ("OFF")side as remote setting.If local operation is required, the SW7 selection switch isturned to the upper side.

Other Switches = SW5, DSW6, RSW9 andDSW1

This control panel is equipped with other switches:The SW5 selection switch for chilled water/brine water, sothat this switch must be turned to the upper side(“water”). DSW6 and RSW9 for operation mode andsetting change of these switches are not available.The figure 2 of DSW6 must be turned to the upper side.It is recommended that the setting is not changed at site.Also, the DSW1 switch is equipped with. This switch isused for only checking, resulting in easy troubleshooting.

Page 34: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

9/30 SELF-INSPECTION FUNCTIONS

9. SELF-INSPECTION FUNCTIONS

9.1. ALARM INDICATION

Alarm Indication

If the unit is operated under abnormal conditions, an alarmcode(refer to the table below) is indicated and the "Alarm"LED is lighted.Function of 7-Segment Light Emitted Diode on ControlPanel is as shown in the table below.

Code

No.1Cycle

No.2Cycle

No.3Cycle

Content

Activation of High Pressure Switch

Activation of Low Pressure Control

Activation of Thermal Relay for Compressor or Malfunction of Auxiliary Relay Arn

Activation of Discharge Gas Thermistor

Activation of Compressor Internal Thermostat

Excess Low Temperature of Cooler Inlet Refrigerant

Activation of Suction Gas Thermistor

Phase Abnormally (Only for 3 cycle unit)

Failure of Water Outlet Thermistor (Only for 3 cycle unit)

Activation of Freeze Protection Control (Only for 3 Cycle Unit)

Failure of Cooler inlet Refrigerant Thermistor (Open / Short)

Failure of Discharge Gas Thermistor (Open / Short)

Failure of Thermistor set before Expansion Valve

Failure of Water Outlet Thermistor (Rear side of Water Cooler)

Failure of Suction Gas Thermistor (Open / Short)

Failure of Discharge Gas Pressure Sensor (Open / Short)

Failure of Suction Gas Pressure Sensor (Open / Short)

Failure of Hot Water Outlet Temperature Thermistor (Only for 3 Cycle Unit of Heat PumpOperation Option)

Phase Abnormally (Only for 1 and 2 Cycle Unit)

Failure of Water Inlet Temperature Thermistor

Failure of Water Outlet Thermistor. (Only for 1 and 2 Cycle Unit)

Activation of Freeze Protection Control (Only for 1 and 2 Cycle Unit)

Failure of Hot Water Inlet Temperature Thermistor (Only for Heat Pump Operation Option)

Failure of Hot Water Outlet Temperature Thermistor (Only for 1 and 2 Cycle Unit of HeatPump Operation Option)

No Feedback Signal from Water Pump

Incorrect Operation

Error Communication between Expansion Valve PCB and Control PCB

“ “” “ Alarm of Excessively High Water Temperature

Alarm of Water Failure for Water Cooler (Differential Pressure Switch or Flow SwitchOption)

Alarm of Water Failure for Condenser (Differential Pressure Switch or Flow Switch Option)

Activation of Additional Protection Device

Error Communication between Chiller and Remote Controller (If CSC-5S is connected.)

Retry Operation (by Alarm Cx-9x or Cx-Lx, x: Cycle No.)

“”-”” : Flickering

7 Segments onControl Panel. .

SEG1 SEG2

Page 35: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

SELF-INSPECTION FUNCTIONS 9/31

9.2. NORMAL INDICATION

If the unit is operated under a normal operation condition,the operation code (refer to the table below) is indicated on7-Segment LEDs of the control panel.

Code

No.1Cycle

No.2Cycle

No.3Cycle

Content

Power Supply, After Stoppage

Cooling Operation

Heating Operation (Only for Heat Pump Operation Option)

Stoppage by Thermo-OFF or Retry by Alarm Cx-5x

Pump Operation, Warning of Pump Feedback

Initializing Electronic Expansion Valve

9.3. FUNCTION FOR INDICATION OF OPERATION CONDITION

Function for Indication of Operation Condition

The setting temperature, chilled water temperature sensedat the thermistor, the setting differential temperature andthe last alarm code are digitally indicated on the controlpanel.

Note:Each indication mode shall be changed from the normal mode.

Press the check "∆" and "∇" switchessimultaneously for more than 3 sec.It is changed to the normal mode bypressing the "∆" and "∇" switchessimultaneously for more than 3 sec.again.

Press the check "∆" switch for more than3 sec.It is changed to the normal mode bypressing the "∆" switch for more than 3sec. again.

Press the check "∇" switch for more than3 seconds at the time to display latestalarm coad.

Press the check "∇" switch for more than3 seconds.

It is changed to the normal mode bypressing the "∆" switch for more than 3sec. Again.

Indication Mode of Alarm Occurrence Data

The content of abnormal stoppage including activation ofsafety devices is memorised and indicated on thecontrol panel

Alarm Occurrence Data (Max.10 data)

∇↑↓∆

∇↑ ↓∆

NOTE:If an abnormal operation is occurred under thisindication mode, this indication mode is changed tothe alarm indication mode.

The Alarm CodeOccurrence Data

Normal OperationCondition

"88" "Co" "oF"

Second WaterTemperature Setting

CheckingIndication

In case of No. 1 cycle highpressure alarm occurrence

In case of No. 2 cycle highpressure alarm occurrence

Memory DataIndication in alarm(Latest Data only)

Page 36: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

9/32 SELF-INSPECTION FUNCTIONS

Checking Indication

Alarm Code Occurred Last (no alarm)

∆↓ ↑∇Discharge Pressure (MPa)

∆↓ ↑∇ (N° 1 Cycle = 1.92 MPa)

Discharge Pressure (MPa)

∆↓ ↑∇Discharge Pressure (MPa)

∆↓ ↑∇Suction Pressure (MPa)

∆↓ ↑∇ (N° 1 Cycle = 0.42 MPa)

Suction Pressure (MPa)

∆↓ ↑∇Suction Pressure (MPa)

∆↓ ↑∇Discharge Gas Temperature (Option) (°C)

∆↓ ↑∇ (N° 1 Cycle = 82°C)

Discharge Gas Temperature (Option) (°C)

∆↓ ↑∇Discharge Gas Temperature (Option) (°C)

∆↓ ↑∇Suction Gas Temperature (°C)

∆↓ ↑∇ (N° 1 Cycle = -2°C)

Suction Gas Temperature (°C)

∆↓ ↑∇Suction Gas Temperature (°C)

∆↓ ↑∇Evaporating Temperature (°C)

∆↓ ↑∇ (N° 1 Cycle = -2°C)

Evaporating Temperature (°C)

∆↓ ↑∇Evaporating Temperature (°C)

∆↓ ↑∇Water Inlet Temperature (°C)

∆↓ ↑∇

Back to "CPU ROM numbre"↑∇

Page 37: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

SELF-INSPECTION FUNCTIONS 9/33

Average Water Outlet Temperature (°C)

∆↓ ↑∇Water Outlet 1 Temperature (°C)

∇↑ ↓∆Water Outlet 2 Temperature (°C)

∇↑ ↓∆Water Outlet 3 Temperature (°C)

∇↑ ↓∆Setting Water Outlet Temperature (°C) (Cooling)

∇↑ ↓∆Setting Water Outlet Temperature (°C) (Heating)

∆↓ ↑∇Second Setting Water Outlet Temperature (°C) (Cooling)

∆↓ ↑∇Second Setting Water Outlet Temperature (°C) (Heating)

∆↓ ↑∇Setting Neutral Zone Temperature Difference (°C)

∆↓ ↑∇Compressor Capacity Control (°C)

∆↓ ↑∇Compressor Capacity Control (°C)

∆↓ ↑∇Compressor Capacity Control (°C)

∆ ∇

Discharge Pressure Control Not available

Suction Pressure Control Not available

Different Pressure ControlLoad Down Control (WaterOutlet Temp.)

Freeze Protection Control Not Available

Compressor Start ControlDischarge TemperatureControl

Discharge Temperature Retry Liquid Bypass (Not Available)

Not available Not Available

∆ ∇

Control Status

∆↓ ↑∇Control Status

∆↓ ↑∇Control Status

∆↓ ↑∇

Alarm Control Status

Compressor start control

Suction pressure control activated

Discharge pressure control activated

Load up

Hold

Load down

Thermo-off

Page 38: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

9/34 SELF-INSPECTION FUNCTIONS

Memory Data Indication in Alarm

Data is indicated same as Checking Indication.In addition the checking data, below data is added.

∆↓ ↑∇Evaporating Temperature (°C)

∆↓ ↑∇Water Outlet Temperature (Cooler Backside) (°C)

∆↓ ↑∇Water Outlet Temperature (Cooler Backside) (°C)

∆↓ ↑∇Water Outlet Temperature (Cooler Backside) (°C)

∆↓ ↑∇

∆↓ ↑∇Control status

∆↓ ↑∇Expansion Valve Pulse

∆↓ ↑∇Expansion Valve Pulse

∆↓ ↑∇Expansion Valve Pulse

∆↓ ↑∇

Page 39: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

SELF-INSPECTION FUNCTIONS 9/35

Second Water Temperature Setting

This temperature setting can provide another setting value for water temperature.It can be changed by external signal

Second Water Temperature Setting Procedure

1)Press the check “ “ switch for more than 3 seconds.Then, display shows the current setting value.

* This shows the setting value is 6ºC.

If press the check “ ” or “ “ in this mode, the display is changed to either “Hot Water Temperature Setting” or“Chilled Water Temperature Setting” alternatively.

2)Press the check “ “ and “ ” switches simultaneously for more than 3 seconds.The mode is changed to setting mode.

Then, the setting value can be changed by pressing the check “ “ and “ ” switches.However, the setting value shown on display, is not available in this moment.

3)Press the check “ “ and “ ” switches simultaneously for more than 3 seconds. At the same time, the setting valueshown on display is memorized and available.

* The setting is changed to 9.5ºC.

* Hot water temperature setting change is performed by same procedure mention above.

When the wiring connection shown below, this second temperature setting is available.

Press “ “

Press “ “

NotAvailable

“ “

“ “

Page 40: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

9/3

6S

ELF

-IN

SP

EC

TIO

N F

UN

CT

ION

S

Co

ntr

ol

Sta

ge

Co

ntr

ol

De

vic

es

Sta

rtin

g C

on

tro

lC

ap

acit

y C

on

tro

lS

afe

ty D

evic

es

Sh

ut

Do

wn

Mai

n P

ower

Sw

itch

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

Chi

lled

Wat

er P

ump

-O

FF

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

OF

FO

FF

Con

dens

er W

ater

Pum

p-

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

OF

F

Ope

ratio

n S

witc

h (O

N/O

FF

)-

--

ON

--

--

--

--

--

-O

FF

-O

FF

-

Load

Up

--

--

--

OO

--

--

--

--

--

Neu

tral

--

--

--

--

O-

O-

-O

O-

O-

Con

trol

ler

Load

Dow

n-

--

--

--

-O

-O

O-

--

--

Saf

ety

Dev

ices

1C

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSO

PN

CLS

CLS

CLS

CLS

Pow

er S

uppl

y La

mp

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

Ope

ratio

n Lu

mp

OF

FO

FF

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

ON

OF

FO

FF

Ala

rm L

umpr

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

Oil

Hea

ter

CH

1O

FF

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

NO

NO

NO

FF

ST

AD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LT

OF

FO

FF

OF

FO

FF

(ULD

)(U

LD)

(ULD

)(F

LD)

(FLD

)(U

LD)

(ULD

)(U

LD)

(ULD

)O

FF

OF

F(F

LD)

OF

FO

FF

Mot

or fo

r

Com

pres

sor

MC

1

15%

15%

15%

-99%

100%

100%

15%

-99%

15%

-99%

15%

OF

F15%

-99%

100%

SV

11O

FF

OF

FO

FF

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

12O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

Sol

enoi

d V

alve

SV

13O

FF

OF

FO

FF

OF

FO

FF

OF

FO

NO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

Tim

e S

ched

ule

10.CONTROL SYSTEM

Standard Operating Sequence for RCUE 40WG2, RCUE 50WG2, RCUE 60WG2 and RCUE 80WG2

5se

c.

3m

in.

30

sec.

Min

imum

3m

in.

CL

S:

Clo

se,

OP

N:

Op

en

, S

TA

: S

tar,

DL

T:

De

ltaU

LD

: U

nlo

ad

, F

LD

: F

ull

Lo

ad

10/36 CONTROL SYSTEM

Page 41: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

SE

LF

-IN

SP

EC

TIO

N F

UN

CT

ION

S9

/37

10/37

Co

ntr

ol

Sta

ge

Co

ntr

ol

De

vic

es

Sta

rtin

g C

on

tro

lC

ap

acit

y C

on

tro

lS

afe

ty D

evic

es

Sh

ut

Do

wn

Mai

n P

ower

Sw

itch

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

Chi

lled

Wat

er P

ump

-O

FF

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

OF

FO

FF

Con

dens

er W

ater

Pum

p-

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

OF

F

Ope

ratio

n S

witc

h (O

N/O

FF

)-

--

ON

--

--

--

--

--

--

--

OF

F-

OF

F-

Load

Up

--

--

--

--

OO

--

--

--

OO

--

--

Neu

tral

--

--

--

--

--

O-

--

-O

--

-O

--

Con

trol

ler

Load

Dow

n-

--

--

--

--

--

OO

OO

--

--

--

-

1C

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSO

PN

OP

NC

LSC

LSC

LSC

LSS

afet

y D

evic

esN

º 2

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

CLS

OP

NC

LSC

LSC

LSC

LS

Pow

er S

uppl

y La

mp

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

Ope

ratio

n Lu

mp

OF

FO

FF

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

ON

OF

FO

FF

Ala

rm L

umpr

OF

FO

FF

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

ON

OF

FO

FF

CH

1O

FF

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

NO

NO

NO

NO

FF

Oil

Hea

ter

CH

2O

FF

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

ON

ON

ON

ON

OF

F

ST

AD

LTS

TA

DLT

DLT

DLT

DLT

DLT

DLT

DLT

DLT

DLT

(ULD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(F

LD)

(FLD

)(U

LD)

(ULD

)(U

LD)

0FF

(ULD

)O

FF

OF

FO

FF

(FLD

)O

FF

OF

FM

C1

OF

FO

FF

OF

FO

FF

15%

15%

15%

15%

15%

-99%

100%

100%

15%

-99%

15%

-99%

15%

15%

-99%

100%

ST

AD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LT

OF

FO

FF

OF

FO

FF

OF

FO

FF

(ULD

)(U

LD)

(ULD

)(F

LD)

(FLD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(U

LD)

OF

FO

FF

(FLD

)O

FF

OF

F

Mot

or fo

r

Com

pres

sor

MC

2

15%

15%

15%

-99%

100%

100%

15%

-99%

15%

-99%

15%

OF

F15%

-99%

15%

-99%

100%

SV

11O

FF

OF

FO

FF

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

F

SV

12O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

F

SV

13O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

NO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

F

SV

21O

FF

OF

FO

FF

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

F

SV

22O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

F

Sol

enoi

d V

alve

SV

23O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

NO

NO

FF

OF

FO

FF

ON

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

F

Tim

e S

ched

ule

Standard Operating Sequence for RCUE 100WG2, RCUE 120WG2 and RCUE 150WG2

3m

in.

5se

c.

60

sec.

Min

imum

3m

in.

CL

S:

Clo

se,

OP

N:

Op

en

, S

TA

: S

tar,

DL

T:

De

ltaU

LD

: U

nlo

ad

, F

LD

: F

ull

Lo

ad

Th

e c

om

pre

sso

r w

hic

h s

tart

ed fin

ally

will

be

sta

rte

d f

irst

.

CONTROL SYSTEM

5se

c.

30

sec.

Page 42: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

9/3

8S

ELF

-IN

SP

EC

TIO

N F

UN

CT

ION

S

Co

ntr

ol

Sta

ge

Devic

es

Sta

rtin

g C

on

tro

lC

ap

acit

y C

on

tro

lS

afe

ty D

evic

es

Sh

ut

Do

wn

Mai

n P

ower

Sw

itch

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

Chi

lled

Wat

er P

ump

-O

FF

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

OF

FO

FF

Con

dens

er W

ater

Pum

p-

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

OF

F

Ope

ratio

n S

witc

h (O

N/O

FF

)-

--

ON

--

--

--

--

--

--

--

--

-O

FF

-O

FF

-

Con

trol

ler

Load

up

--

--

--

--

--

OO

--

--

--

-O

O-

--

-

Neu

tral

--

--

--

--

--

--

O-

O-

-O

O-

--

O-

-

Load

dow

n-

--

--

--

--

--

--

O-

OO

--

--

--

--

No.

1C

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSO

PN

OP

NO

PN

CLS

CLS

CLS

CLS

No.

2C

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSO

PN

OP

NC

LSC

LSC

LSC

LSS

afet

y D

evic

es

No.

3C

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSC

LSO

PN

CLS

CLS

CLS

CLS

Pow

er S

uppl

y La

mp

OF

FO

FF

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

Ope

ratio

n Lu

mp

OF

FO

FF

OF

FO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

FF

ON

OF

FO

FF

Ala

rm L

ump

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

ON

ON

OF

FO

NO

FF

OF

F

CH

1O

FF

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

NO

NO

NO

FF

ON

OF

F

CH

2O

FF

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

ON

ON

ON

OF

FO

NO

FF

Oil

Hea

ter

CH

3O

FF

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

NO

NO

FF

ON

OF

F

ST

AD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LT

OF

FO

FF

OF

FO

FF

(ULD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(F

LD)

(FLD

)(U

LD)

(ULD

)(U

LD)

OF

F(U

LD)

OF

FO

FF

OF

FO

FF

(FLD

)O

FF

OF

F

MC

1

15%

15%

15%

15%

15%

15%

15%

-99%

100%

15%

15%

15%

15%

15%

-99%

ST

AD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LT

OF

FO

FF

OF

FO

FF

OF

FO

FF

(ULD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(U

LD)

(ULD

)(U

LD)

OF

F(U

LD)

(ULD

)O

FF

OF

FO

FF

(FLD

)O

FF

OF

F

MC

2

15%

15%

15%

15%

15%

-99%

15%

-99%

15%

-99%

15%

-99%

15%

-99%

15%

15%

-99%

15%

-99%

100%

ST

AD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LTD

LT

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

(ULD

)(U

LD)

(ULD

)(F

LD)

(FLD

)(U

LD)

(ULD

)(U

LD)

OF

F(U

LD)

(ULD

)(U

LD)

OF

FO

FF

(FLD

)O

FF

OF

F

Mot

or fo

r

com

pres

sor

MC

3

15%

15%

15%

-99%

100%

100%

15%

-99%

15%

-99%

15%

15%

-99%

15%

-99%

15%

-99%

100%

SV

11O

FF

OF

FO

FF

ON

ON

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

12O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

13O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

NO

NO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

21O

FF

OF

FO

FF

ON

ON

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

22O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

23O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

NO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

31O

FF

OF

FO

FF

ON

ON

ON

ON

ON

ON

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

SV

32O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

Sol

enoi

d V

alve

SV

33O

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

OF

FO

NO

NO

FF

OF

FO

FF

OF

FO

FF

OF

FO

FF

ON

OF

FO

FF

OF

FO

FF

OF

F

Tim

e S

ched

ule

Standard Operating Sequence for RCUE 180WG2, RCUE 200WG2, and RCUE 240WG2

CONTROL SYSTEM

The

Com

pres

sor

whi

ch s

tart

ed fi

nally

will

be

rest

arte

d fir

st.

5 se

c.

3 m

in.

30 s

ec.

Min

imun

3m

in.

60 s

ec.

5 se

c.

60 s

ec.

5 se

c.

10/38 CONTROL SYSTEM

CL

S:

Clo

se,

OP

N:

Op

en

, S

TA

: S

tar,

DL

T:

De

ltaU

LD

: U

nlo

ad

, F

LD

: F

ull

Lo

ad

Page 43: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MAINTENANCE 11/39

11. MAINTENANCE

The unit should be periodically inspected according to thesame items as those described in the paragraph titled“Test Running“. In order to ensure dependableperformance and long life operation, the followingadditional items should be given for particular attention.

WARNING:If a fire accidentally occurs, turn OFF the main switchand use an extinguisher for an oil fire and an electricfire.Do not operate the unit near flammable gases suchlacquer, paint oil, etc. to avoid a fire or an explosion.Turn OFF the main switch when electrical box coversare removed for setting the temperature. Do notoperate the unit without fixing panels.

DANGER:Switch OFF main interruptor (MI) for any work insideelectrical box.

CAUTION:Perform periodical maintenance according to the“INSTRUCTIONS“ to maintain the unit in a goodcondition.Do not touch the parts at the discharge gas side byhand, since the pipes at the discharge side areheated by refrigerant and the temperature becomeshigher than 100 °C.Do not utilize this unit for cooling or heating ofdrinking water or food. Comply with local codes andregulations.Turn OFF all the main switches if refrigerant leakageor chilled / hot water leakage occurs. Also, if the unitcan not be stopped by the control switch, turn OFF allthe switches for power source.

11.1. COMPONENTS

Compressor

The semi-hermetic screw compressor requires periodicmaintenance, including replacement of parts. See theHITACHI Service Handbook for Screw Compressors, fordetails.

Electrical Equipment

Always pay careful attention to working voltage, amperageand phase balance. Check for faulty contact caused byloosened terminal connections, oxidised contacts, foreignmatter, and others.

Control and Protective Devices

Do not readjust the settings in the field unless the setting ismaintained at the point other than the point listed in thetable on chapter 11.

11.2. LUBRICATION

Compressor

The compressors are charged at the factory with thecorrect oil listed in “Component Data” and the compressornameplate. It is not necessary to add oil, if the refrigerantcycle remains sealed.

11.3. DEPOSITS

Slime and other minerals in the condenser water or chilledwater tend to deposit on inside surfaces of plates over along period of operation. As deposits of these mineralsincrease, excessive high discharge pressure or loweroperation pressure are detected, indicating evidence ofdeposits on the condenser or the water cooler. The figurein page 41 indicates the range where cleaning is required.

CAUTION:-Cleaning of plate type heat exchangers shall be

performed by specialists. Please contact yourcontractor or dealer of HITACHI.

-Clean the water strainer filter periodically according toits clogging degree. If not cleaned periodically, thewater strainer will be broken due to an excessivepressure to the strainer screen.

WARNING:-This product is equipped with plate type heat

exchangers. In the plate type heat exchanger, waterflows through a narrow space between plates.Therefore, there is a possibility that freezing mayoccur if foreign particles or dusts are clogged. Inorder to avoid this clogging, provide a 20 mesh water

strainer at the inlet of the chilled water piping near theproduct. If clogging in the plate type heat exchangeroccurs seriously, this will cause insufficient coolingperformance or local freezing in the plate type heatexchanger. It is strongly recommended that the heatexchanger be cleaned at the same time when thefilter is cleaned.

Pay attention to the following caution and normalcleaning method. For details, contact your Hitachiinstaller.

Water

Refrigerant

Page 44: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

11/40 MAINTENANCE

CAUTION:-Correctly select cleaning agent depending on scales in

the plate type heat exchangers. The cleaningchemicals are different depending on fouling degree.

-This plate type heat exchanger is made of stainlesssteel. Do not use a cleaning agent containinghydrochloric acid or fluorine compound. If used, theheat exchanger will be damaged, resulting inrefrigerant leakage.

-After cleaning with cleaning agent, clean inside ofwater piping including the heat exchangers by usingclean water. Perform water treatment (preventivetreatment) in order to prevent the water circuit fromcorrosion or re-adhering of scales after cleaning.

-In the case that a cleaning agent is used adjustconcentration of the cleaning Agent, cleaning periodand temperature according to the scale degree.

-In the case that acid cleaning is performed,neutralisation treatment is required after cleaning.Treatment for neutralisation fluid should be performedby a waste fluid contractors.

-The cleaning agent and neutralizing agent are erosiveand stimulative against eyes, skin, mucous membraneetc. Therefore use protection tools (protection glasses,protection gloves, protection shoes, protection cloth,protection mask, etc.) in order not to absorb or touchthese agents during this cleaning work.

11.4. CLEANING METHOD

N° Name N° Name

1 Chiller Unit 5 Diluted Cleaning Fluid2 Chilled Water / Inlet Piping 6 Chilled Water / Outlet Piping3 Acid-resistant Type Water Pump 7 Cleaning Water Tank4 Hose 8 Waste Fluid Tank

1. Installation of Cleaning Circuit

-Stop the water Chiller unit.-Stop the circulating water pump.-Disconnect the connections at the chilled water inlet or

cooling water inlet and install a circulating water circuit byusing an acid-resistant type water pump.

2. Check of Circulating Circuit

Pour water in the cleaning tank and operate the acid-resistant type water pump.

-Check to ensure that no water leakage exists.-Check to ensure that the water hose is firmly fixed.-Check to ensure that the cleaning Agent will not damage

equipment near the water Chiller even if bubbles occurand touch them.-Check to ensure that good ventilation is available.-Check to ensure that no abnormal sound occurs.

3. Cleaning Work

-Discharge water in the water circuit of the air conditioningsystem.-Supply diluted cleaning fluid from the cleaning water tank

by operating the acid-resistant pump.-Circulate the cleaning fluid for an appropriate period of

time (the operating time should be determined accordingto the type of cleaning Agent, concentration and foulingdegree).

4. Waste Fluid

-Stop the acid-resistant pump.-Put the waste fluid into the waste fluid tank.-Supply water into the cleaning tank and operate the pump

for water cleaning.-Put the cleaning water into the waste fluid tank as same as

the waste fluid.-Measure pH degree by using a pH test sheet and

neutralize the waste fluid by gradually adding neutralizingagent.-After neutralization ask a waste fluid treatment contractors

to handle it.

5. Neutralisation Treatment in the Water Piping

-Put water into the cleaning tank.-Operate the acid-resistant pump after air-purging.-Measure the pH degree and gradually add neutralizing

agent until the pH reaches pH = 7.-Operate the pump for a specified period of time for

neutralization.-Discharge the used water.-Operate the circulating pump and clean the circuit with

water until no fouling fluid is observed.

6. Re-starting

-Reconnect the water piping as they were so that the waterChiller can operate.

-After cleaning, perform water treatment (preventivetreatment) in order to prevent the water circuit fromcorrosion.

Page 45: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MAINTENANCE 11/41

11.5. WINTER SHUTDOWN

When shutting down the unit for winter, clean the insideand outside of the cabinet, and dry the unit. Pump downthe refrigerant to the condenser and close the liquid outletstop valves. This unit should be covered during shutdown,in order to protect it from dust and environmentalconditions. Be sure to tighten the packing glands and thecap nuts of the valves.

Remove the drain plug and drain all residual water from thecondenser and water cooler piping systems, as such watermay freeze during the cold season. It is very helpful tosupply brine (anti-freezer) to the piping systems.

11.6. SPRING START-UP

After any extended shutdown period, prepare the unit foroperation as follows.

1. Thoroughly inspect and clean the unit.

2. Clean the water piping lines and the strainer.

3. Inspect the pump, the cooling tower and/or regulatingvalve.

4. Tighten all wiring connections and access panel.

CAUTION:When the main switch for this unit has been at theOFF position for an extended period of time, it shouldbe switched ON at least 12 hours before start-up, sothat oil in the compressor discharge casing may bewarmed enough, to prevent oil foaming by the oilheater during start-up.

11.7. PART REPLACEMENT

Replacement of parts should be undertaken by orderingfrom the HITACHI Spare Parts List. CAUTION:

Do not replace with spare parts which are not theequivalent.

Area Requiring Cleaning

Saturation Line

Suct

ion G

as

Pre

ssure

(M

Pa)

Area Requiring Cleaning

Chilled Water Outlet Temperature (°C)

Saturation Line

Condenser Water Outlet Temperature (°C)

Dis

charg

e G

as

Pre

ssure

(M

Pa)

Page 46: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

11/42 MAINTENANCE

11.8. REFRIGERATION CYCLE

Strainer

Check for clogging each time when the refrigeration cycleis opened.

Refrigerant Charge

Inspect the refrigerant charge of the system by checkingthe discharge and suction pressures. Perform a leakagetest, if any leakage is suspected, and always perform sucha test after a refrigeration cycle component is replaced.When refrigerant charge is required, follow the followinginstructions given for two cases:1. When Refrigerant Gas Completely Leaked.

Before charging the entire cycle must be completelyevacuated and dehydrated. A gauge manifold orequivalent piping preparation shown in the next page isrecommended as a convenient procedure regardingboth charging and evacuation.

Fully open all the stop valves.

Connect the evacuation line to the check joints of thehigh and the low pressure sides.

Completely evacuate the entire cycle with a vacuumpump.

Charge refrigerant to the refrigeration cycle byweighing the charging cylinder. The proper refrigerantcharge is listed on the nameplate.

When charging by weight is stopped due to highambient temperature, close the valve and operate theunit after circulating the chilled water through the watercooler.

2. When Only Additional Refrigerant is Required.Connect a gauge manifold to check joint of low pressureside, and connect a charge cylinder to gauge manifold.Operate the unit after circulating the chilled water.

Repeat the following procedure until pressure becomesproper (refer to page 46)

Charge the gas refrigerant a little slowly intorefrigeration cycle from check joint for low pressure.

Check the pressure after refrigeration cycle becomesstable.

11.9. REFRIGERANT CYCLE DIAGRAM OF HITACHI WATER COOLED CHILLER

No. Name No. Name

1 Compressor 12 Stop Valve (Option)2 Check Valve 13 Pressure Sensor (Low)3 Pressure Relief Valve 14 High Pressure Switch4 Stop Valve (Option) 15 Pressure Sensor (High)5 Water Condenser 16 Compressor Safety Valve (Option)6 Stop Valve 17 Compressor Dual Safety Valve (Option)7 Stop Valve A High Pressure Gauge8 Drier B Low Pressure Gauge9 Sight Glass C Stop Valve

10 Electronic Expansion Valve D Charging Cylinder11 Water Cooler E Vacuum Pump

NOTE:R407C shall be charged by LIQUID.

Condensing Water Outlet

Condensing Water Inlet

Chilled WaterInlet

Chilled WaterOutlet Flange Connection

Flare Connection

Solder Connection

Refrigerant CycleUnit side

Charging

Evacuation

Gaugemanifold

DesignPressure

Hydrostatic TestPressure

MODEL: RCUE 40, 50, 60, 100, 120, 180, 200WG2

Page 47: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MAINTENANCE 11/43

No. Name No. Name

1 Compressor 15 Pressure Sensor (High)2 Check Valve 16 Compressor Safety Valve (Option)3 Pressure Relief Valve 17 Compressor Dual Safety Valve (Option)4 Stop Valve (Option) 18 Pressure Switch5 Water Condenser 19 Solenoid Valve6 Stop Valve 20 Capillary Tube7 Stop Valve 21 Economizer8 Drier 22 Strainer9 Sight Glass A High Pressure Gauge

10 Electronic Expansion Valve B Low Pressure Gauge11 Water Cooler C Stop Valve12 Stop Valve (Option) D Charging Cylinder13 Pressure Sensor (Low) E Vacuum Pump14 High Pressure Switch

NOTE:R407C shall be charged by LIQUID.

CAUTION:-Do not charge OXYGEN, ACETYLENE or other

flammable and poisonous gases into the refrigerationcycle when performing a leakage test or an airtighttest. These types of gases are extremely dangerous,because explosion can occur. It is recommended thatcompressed air or nitrogen be charged for thesetypes of tests.

-Mineral deposits on water cooler plates act as thermalinsulators, and also act as resistance Against waterflow, causing the water flow to decrease runningthrough them, and resulting in a decreasing of thecooling capacity. Deposits on the plates should beinspected at regular, intervals, experience with thewater Chiller will dictate accurate inspection intervals.

-These deposits should be removed by circulatingdiluted acid through the water passes after the waterhas been drained. As water in different localitiescontains different minerals, different acids arerequired, depending upon the thickness of thedeposits.

-This unit is equipped with an operation hour meter. Inthe case that the total operation time reaches 40,000hours or 5 years pass after installation, exchange thebearings of the compressor. For details, refer to theService Handbook for HITACHI Screw Compressors.

-For R407C refrigerant system, charge the refrigerantwith liquid condition to avoid its composition change.

Condensing Water Outlet

Condensing Water Inlet

ChilledWater Inlet

ChilledWater Outlet

Flange Connection

Flare Connection

Solder Connection

Refrigerant Cycle

Unit sideCharging

Evacuation

Gaugemanifold

DesignPressure

HydrostaticTestPressure

MODEL: RCUE 80, 150, 240WG2

Page 48: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

11/44 MAINTENANCE

11.10. COMPRESSOR REMOVAL

When Removing the CompressorRemove the compressor while completing thefollowing procedures.

1.Collect all refrigerant into a condenser before thiswork.

2.Turn off the switch, DSW3 of the PCB in the electricalbox in order not to operate the compressor except forthe cycle.

3.Circulate the chilled and cooling water sufficientlythrough the water cooler and condenser, and operatethe water Chiller for 10 minutes, and check to ensurethat the oil level is maintained at a stable condition.

4.Stop the water Chiller and completely close the liquidstop valve.

5.Operate the water Chiller after circulating waterthrough the water cooler and condenser.

6.Stop the water Chiller when the low pressure reachesat approximately 0.05 MPa. Do not operate at thepressure lower than 0.05 MPa. If operated, it willcause a damages to the compressor.

7.Wait for several minutes. If the low pressure increaseup to 0.15 to 0.2 MPa, repeat the above procedures 5and 6 four or five times.

8.Turn OFF the power supply to the unit.

9. Remove the bolts on the discharge and suctionflanges of the compressor.

11.11. SAFETY AND PROTECTION CONTROL

The safety and protective devices are equipped with theunit to ensure dependable and long life operation.

Their functions should be carefully noted, and fieldadjustment is not recommended, if the setting is maintainedat the point listed in the table.

Compressor protection

1. Fuse and thermal relay equipped in the control box cutout each compressor operation when the current to thecompressor exceeds the setting

2. The internal thermostat embedded in the motor windingcuts out each operation, when the temperature exceedsthe setting

3. The oil heater in the compressor prevents from oilfoaming during cold starting. This heater warms the oil,while the compressor is stopped

Refrigeration Cycle

1. The high pressure switch and low pressure controlprotect Against excessive discharge pressure andexceedingly low suction pressure. The switch andcontrol cut out compressor operation when dischargepressure or suction pressure is abnormal.

2. The pressure relief valve is equipped on discharge gasline. When high pressure exceeds the setting, gasrefrigerant will be discharged to prevent abnormal highpressure

Water Cooler

Pump interlock, freeze protection thermostat, lowpressure control and suction gas thermostat can protectwater cooler Against water cooler freezing

Page 49: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MAINTENANCE 11/45

11.11.1. SAFETY AND CONTROL DEVICE SETTING

ModelRCUE-WG2

40 50 60 80 100 120 150 180 200 240

For Compressor High Pressure Switch Manual Reset, Non-Adjustable ( One Switch for Each Compressor Motor )

Cut-Out MPa 2,74 2,74 2,74 2,74 2,74 2,74 2,74 2,74 2,74 2,74 Low Pressure Switch Electronic Control (Pressure Sensor) MPa 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05

Cut-OutInternal Thermostat for Compressor Manual Reset, Non-Adjustable ( One Switch for Each Compressor Motor )

Cut-Out °C 115 115 115 115 115 115 115 115 115 115Cut- In °C 93 93 93 93 93 93 93 93 93 93

Compressor Motor (380-415V/50Hz) Fuse A 100 100 125 125 100 125 125 100 125 125

Manual Reset, Adjustable ( One Three-Phase Set for Each CompressorMotor )

Thermal Relay A 48 55 70 75 55 70 75 55 70 75Manual Reset, Adjustable ( One Three-Phase Set for Each Compressor

Motor ) Magnetic circuit Protection (Option) A 90 107 127 127 107 127 127 107 127 127Oil Heater One Heater for Each Compressor Motor Capacity W 150 150 150 150 150 150 150 150 150 150Discharge Gas (Electronic Control) ( One for Each Cycle )

Cut-Out °C 140 140 140 140 140 140 140 140 140 140

CCP Timer Non-Adjustable ( One Timer for Each Compressor ) Setting Time S 180 180 180 180 180 180 180 180 180 180

Star-Delta S 5 5 5 5 5 5 5 5 5 5 Unloading during Starting S 30 30 30 30 30 30 30 30 30 30For Refrigerant Circuit ( One for Each Circuit ) Pressure Relief Valve Setting Pressure MPa 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0Freeze Protection Thermostat ( One for Each Water Cooler )

Cut-Out °C 2 2 2 2 2 2 2 2 2 2

Page 50: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

11/46 MAINTENANCE

11.12. NORMAL OPERATING PRESSURE

Check to ensure that Chiller is operating within the workingrange as shown below, after at least 15 minutes operation.Low Pressure: The normal operating low pressure of thewater chiller is indicated in the figure below; lower than 0.3Mpa indicates an abnormal condition.

For R407C

Discharge Pressure: Normal operating discharge pressureis indicated in the figure below; low than 0.9 Mpa or higherthan 2.2 Mpa indicates an abnormal condition

CAUTION:Periodical MaintenancePerform periodical maintenance according to the“INSTRUCTIONS“ to maintain the unit in a goodcondition.

FireIf a fire accidentally occurs, turn OFF the main switchand use an extinguisher for an oil fire and electric fire.

Flammable GasesDo not operate the unit near the flammable gasessuch as lacquer, paint, oil, etc. to avoid a fire or anexplosion.

Service Panels and Electrical Box CoverTurn OFF the main switch when service panels orelectrical box covers are removed for setting thetemperature.Do not operate the unit without fixing panels.

Heated PipeDo not touch the parts at discharge gas side by hand,since the pipes at the discharge side are heated byrefrigerant and temperature becomes higher than 100° C.

UseDo not utilize this unit for cooling of drinking water orfood. Comply with local codes and regulations.

FailureTurn OFF all the main switches if refrigerant leakageor chilled water leakage occurs. Also, if the unit cannot be stopped by the control switch, turn OFF all theswitches for power source.Activation of Safety DeviceIn the case that one of safety devices is activated andunit is stopped, remove the cause of the stoppageand restart the unit. The protection devices areutilized to protect the unit from an abnormaloperation.Therefore, if one of safety devices is activated,remove the cause by referring the “Troubleshooting“in the “INSTRUCTION“ or call the local agency.FuseUtilize a fuse with specified capacity. Do not use asteel wire or a copper wire instead of a fuse. If anincorrect wire is utilized, a serious accident such as afire will occur.Safety DevicesDo not make a short-circuit at the protection line. If ashort-circuit is made, a serious accident will occur.Setting of Safety devicesDo not change the setting of safety devices, ifchanged, a serious accident will occur.Do not touch any electrical parts except for theoperation switches during the operation.Do not press the button on the magnetic switch. Ifpressed, a serious accident will occur.

Suct

ion G

as

Pre

ssure

(M

Pa)

Standard Working Range

Chilled Water Outlet Temperature (°C)

Dis

charg

e G

as

Pre

ssure

(M

Pa)

Standard Working Range

Condenser Water Outlet Temperature (°C)

Page 51: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MAINTENANCE 11/47

11.13. TEST RUNNING AND MAINTENANCE RECORD

MODEL: RCUE MFG. NO.COMPRESSOR MFG. NO.

CUSTOMER’S NAME AND ADRESS:DATE:

1. Is there adequate water flow for the condenser and the water cooler?

2. Has all water piping been checked for leakage?

3. Have the cooling water pump, fan and motor been lubricated?

4. Has the unit been operated for at least twenty minutes?

5. Check Chilled Water Temperature:

6. Check Condenser Water Temperature:

7. Check Suction Line Temperature and Superheat:

Suction Line Temperature:

Superheat:

8. Check Pressure:

Discharge Pressure:

Suction Pressure:

9. Has the unit been checked for refrigerant leakage?

10. Is the unit clean inside and outside?

11. Are all cabinet panels free from rattling?

Inlet Outlet°C °C

Inlet Outlet°C °C

°C °C °C

°C °C °C

MPa MPa MPa

MPa MPaMPa

Page 52: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

11/48 MAINTENANCE

11.14. DAILY OPERATING RECORDS

Model:

Date:

Weather:

Time of Operation Start: Stop. ( )

DB °CAmbient Temperature

WB °C

Room Temperature °C

HighPressure

Mpa

LowPressure

Mpa

Voltage V

Compressor

Current A

Inlet °CCondenser WaterTemperature

Outlet °C

Inlet °CChilled WaterTemperature

Outlet °C

Current for Condenser Water Pump A

Current for Chilled Water Pump A

Current for Cooling Tower A

NOTES:

11.15. SERVICING FOR R407C REFRIGERANT SYSTEM

Refrigerant

This R407C refrigerant is HFC type so that it has a featureof no ozone depletion. If it is mixed with another refrigerant,the serious changing would occur on its character.Therefore notice the following point when handling thisrefrigerant.

Charge the refrigerant in LIQUID condition and NOT inGAS. As "R407C" is geotropic mixed refrigerant, if gascharging is performed, only the easy vaporisingrefrigerant would be charged into the system and thedifficult vaporising one would be remained in thecharge cylinder.

The cylinder, gauge equipped manifold and charge hoseare only used for R407C refrigerant.

Adjust the cylinder setting to charge in liquid.

Refrigerant Oil

UX300, which R407C refrigerant is easy to blend into it, isused for this system. The other oil is prohibited to use, sothat not to be mixed with another kind of oil at themaintenance and service work. This oil is very hygroscopic.Therefore minimum humidity handling is necessary.

Servicing Equipment

When servicing R407C system, servicing equipment suchas Charging Cylinder, Charging Hose, Vacuum Pump andso on, shall not be mixed with R22 equipment to avoidR407C composition change.

Page 53: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

TROUBLESHOOTING 12/49

12. TROUBLESHOOTING

The following table shows efficient checking procedures for trouble.

Fault Possible Cause Check/Corrective Action

Interlock Circuit for Chilled Water Pump isOpen

1.Check the pump contactor. Repair orreplace, if necessary.

2.Check for the faulty pump.

Electrical Protective Devices Are Tripped.1.Remove the causes, and reset the “ON”

button. See the following causes.

Compressor Does Not Operate

Incorrect Wiring Connection for CompressorPower Source

1.Interchange two of three terminals R, S andT at the main power source terminals.

Excessively High Discharge Pressure 1.See “High Discharge Pressure”Compressor Stops on HighPressure Switch Malfunction of High Pressure Switch 1.Readjust the setting or replace, if defective.

Excessively High Discharge Pressure andSuction Pressure

1.See “High Discharge Pressure” and “HighSuction Pressure”.

High or Low Voltage, Single-Phase or PhaseImbalance

1.Check the power supply line and contactors.Repair, if necessary.

Loose connection1.Tighten the loose electrical connection or

repair, if necessary.

Compressor Stops onOvercurrent Relay

Faulty Overcurrent Relay 1.Replace it, if necessary.

Excessively Low Chilled water OutletTemperature

1.Check for excessively low setting of thechilled water setting knob.

Defective Thermistor1.Check for malfunction of the thermistor.

Replace, if necessary.Shortage of Chilled Water Flow 1.Check the rotation of the pump.

Compressor Stops on FreezeProtection Control

Air in water Circuit 1.Purge air.High or Low Voltage, Single-Phase or PhaseImbalance

1.Check the power supply line and contactors.Repair, if necessary.

Excessive Superheat 1.Check for refrigerant leakage

Defective Element1.Check the contact of the internal thermostat

during the cold condition.

Compressor Stops on InternalThermostat or Discharge GasThermostat

Excessive High Discharge Pressure and LowSuction Pressure

1.See “High Discharge Pressure” and “HighSuction Pressure”.

High Discharge Pressure or Low SuctionPressure

1.See “High Discharge Pressure” and “LowSuction Pressure”.

Improper Thermostat Setting 1.Readjust the setting.Insufficient Cooling

Defective Unload Mechanism1.Adjust unload mechanism. Repair or

replace unloaded parts, if necessary.Slugging Due to Liquid Flooding Back toCompressor

1.Check the superheat of suction gas. Keepthe superheat in proper range.

Noisy CompressorWorn parts

1.Check for the sound of internal parts.Replace the compressor, if necessary.

Miscellaneous Noise Loose Fixed Screw 1.Tighten the screws of all parts.

Trouble with the Thermistor1.Adjust the setting temperature.2.Replace the thermistor.

Trouble with the Solenoid Valve1.Check the coil in the solenoid valve.2.Check oil passage for clogging.

Unloaded Does not Function

Worn Unloader Mechanism1.Check the unloaded system parts in the

compressor.Warm inlet water or Insufficient Water FlowThrough the Condenser

1.Open the valve

Gas Outlet Valve on the Condenser NotCompletely Open

1.Check the valves, capillary tubes andstrainer. Replace, if necessary.

Overcharged Refrigerant 1.Purge the refrigerant.Condenser Plates Coated with Scales, Slime,Corrosion and Others

1.Clean the Condenser water plates bychemical cleaner

High Discharge Pressure

Suction Pressure is Higher than Standard 1.See “High Suction Pressure”.

Page 54: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

12/50 TROUBLESHOOTING

Fault Possible Cause Check/Corrective Action

Too Much Water Flowing through theCondenser, or Water is too Cold

1. Adjust the water cock or the regulatingvalve.

2. Check the operation of cooling tower.

Insufficient Refrigerant Charge 1. Add Refrigerant.

Leakage from the Condenser Gas Outlet Valve1. Check to determine how long it takes to

balance high and low

Liquid Refrigerant Flooding Back from theWater Cooler, Causing Oil to Foam..

1. Check the operation and the position ofexpansion valve coil. Repair or replace ifnecessary.

2. Inlet water temperature is considerablylower than the limited temperature.

Low Discharge Pressure

Suction Pressure is lower than Standard 1. See “Low Suction Pressure”

High Discharge Pressure 1. See “High Discharge Pressure”

Refrigerant Overcharged 1. Purge the refrigerant

Liquid Refrigerant Flooding Back from theWater Cooler

1. Check the operation and the position ofexpansion valve coil. Repair or replace ifnecessary.

2. Inlet chilled water temperature to the unitis considerably higher than the standardtemperature.

Leakage from the Condenser Gas Outlet Valve 1. Check the condenser gas outlet valve

High Suction Pressure

Insufficient Insulation for the Chilled WaterPiping

1. Check the insulation of the piping

Condenser Liquid Outlet Valve Not CompletelyOpen

1. Open the valve.

Expansion Valve not properly controlled, orfaulty valve

1. Check the position of Expansion Valve coil.Repair or replace if necessary.

Inlet Chilled Water Temperature isConsiderably lower than standardTemperature.

1. Check the insulation specifications

Insufficient Refrigerant Charge 1. Add Refrigerant

Excessive Oil Circulatin in the System 1. Check the oil charge

Insufficient Chilled Water Flow through thewater cooler.

1. Check the chilled water piping lines forpressure loss.

Low Discharge Pressure 1. Adjust the water shutoff valve

Low Suction Pressure

Scales on Water Cooler Plates 1. Clean the plates

Page 55: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

GENERAL SPECIFICATIONS 13/51

13. GENERAL SPECIFICATIONS

13.1. GENERAL DATA

Model RCUE40WG2 RCUE50WG2 RCUE60WG2 RCUE80WG2

Cooling Capacity *1 kW 134 160 194 232Power Input for Cooling *1 kW 33.5 40 49.1 54.5COP - 4.0 4.0 4.0 4.3Heating Capacity *2 kW 161.1 192.3 233.9 274.7Power Input for Heating *2 kW 39.8 47.5 58.3 64.7

Height mm 1520 1520 1520 1520Outer Dimension Width mm 1105 1105 1105 1105

Depth mm 850 850 850 850Cabinet Colour - Natural GrayShipping Weight kg 750 765 830 950Compressor Type - Semi-Hermetic Screw Type Models - 40ASC-Z 50ASC-Z 60ASC-Z 60ASC-Z Quantity - 1 1 1 1 Oil Heater W 150 150 150 150

- Continuous Capacity ControlCapacity Control

% 15 100Cooler Type - Brazing Plate TypeCondenser Type - Brazing Plate TypeRefrigerant Type - R407C (Factory Charged) Flow Control - Electronic Expansion Valve Number of Independent Circuits - 1 1 1 1Oil Type - JAPAN ENERGY FREOL UX300 (Ester)Evaporator Connection Inch 3” Victaulic (1×Inlet / 1×Outlet ) Option Common Water Piping Inch -Condenser Connection Inch 3” Victaulic (1×Inlet / 1×Outlet ) Option Common Water Piping Inch -Control System - Micro-ProcessorChilled Water Outlet Temperature °C (-10) 5 15Cooling Water Outlet Temperature *3 °C 22 45 (55)Permissible Water Pressure Max. Cooler MPa 1.03 Condenser MPa 1.03

Safety and Protection Devices -

Reverse Phase Protection,Fuse and Thermal Relay for Compressor,Internal Thermostat for Compressor, Compressor Oil Heater,Control Circuit Fuse, High Pressure Switch, Low Pressure Control,Discharge Gas Temperature Control,Suction Gas Temperature Control, Freeze Protection Controland Compressor Operation Hour Meter

Power Supply - 3 , N / 380 - 415V / 50Hz

NOTES:

*1 The nominal cooling capacities are based on the European Standard EN12055.

Chilled Water Inlet / Outlet Temperature : 12 / 7 °C

Cooling Water Inlet / Outlet Temperature : 30 / 35 °C

*2 The nominal heating capacities are only for Heat Pump Operation Option and based on following conditions.

Chilled Water Inlet / Outlet Temperature : 12 / 7 °C

Hot Water (Condenser) Inlet / Outlet Temperature : 40 / 45 °C

*3 ( ) is in case of high condensing option and heat pump operation option.

Page 56: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

13/52 GENERAL SPECIFICATIONS

Model RCUE100WG2 RCUE120WG2 RCUE150WG2

Cooling Capacity *1 kW 320 388 445Power Input for Cooling *1 kW 80 98.2 104.5COP - 4.0 4.0 4.3Heating Capacity *2 kW 384.7 467.9 526.9Power Input for Heating *2 kW 95 116.6 124.1

Height mm 1700 1700 1700Outer Dimension Width mm 1105 1105 1105

Depth mm 1465 1465 1465Cabinet Colour - Natural GrayShipping Weight kg 1570 1670 1770Compressor Type - Semi-Hermetic Screw Type Models - 50ASC-Z 60ASC-Z 60ASC-Z Quantity - 2 2 2 Oil Heater W 150 x 2 150 x 2 150 x 2

- Continuous Capacity ControlCapacity Control

% 7.5, 15 100Cooler Type - Brazing Plate TypeCondenser Type - Brazing Plate TypeRefrigerant Type - R407C (Factory Charged) Flow Control - Electronic Expansion Valve Number of Independent Circuits - 2 2 2Oil Type - JAPAN ENERGY FREOL UX300 (Ester)Evaporator Connection Inch 3” Victaulic (1×Inlet / 1×Outlet ) Option Common Water Piping Inch -Condenser Connection Inch 3” Victaulic (1×Inlet / 1×Outlet ) Option Common Water Piping Inch -Control System - Micro-ProcessorChilled Water Outlet Temperature °C (-10) 5 15Cooling Water Outlet Temperature *3 °C 22 45 (55)Permissible Water Pressure Max. Cooler MPa 1.03 Condenser MPa 1.03

Safety and Protection Devices -

Reverse Phase Protection,Fuse and Thermal Relay for Compressor,Internal Thermostat for Compressor, Compressor Oil Heater,Control Circuit Fuse, High Pressure Switch, Low Pressure Control,Discharge Gas Temperature Control,Suction Gas Temperature Control, Freeze Protection Controland Compressor Operation Hour Meter

Power Supply - 3 , N / 380 - 415V / 50Hz

NOTES:

*1 The nominal cooling capacities are based on the European Standard EN12055.

Chilled Water Inlet / Outlet Temperature : 12 / 7 °C

Cooling Water Inlet / Outlet Temperature : 30 / 35 °C

*2 The nominal heating capacities are only for Heat Pump Operation Option and based on following conditions.

Chilled Water Inlet / Outlet Temperature : 12 / 7 °C

Hot Water (Condenser) Inlet / Outlet Temperature : 40 / 45 °C

*3 ( ) is in case of high condensing option and heat pump operation option.

Page 57: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

GENERAL SPECIFICATIONS 13/53

Model RCUE180WG2 RCUE200WG2 RCUE240WG2

Cooling Capacity *1 kW 525 600 696Power Input for Cooling *1 kW 123.5 148.5 163.5COP - 4.3 4.0 4.3Heating Capacity *2 kW 621.9 719.5 824.2Power Input for Heating *2 kW 146.7 176.4 194.2

Height mm 1580 1580 1580Outer Dimension Width mm 1105 1105 1105

Depth mm 2350 2350 2350Cabinet Colour - Natural GrayShipping Weight kg 2500 2580 2670Compressor Type - Semi-Hermetic Screw Type Models - 50ASC-Z 60ASC-Z 60ASC-Z Quantity - 3 3 3 Oil Heater W 150 x 3 150 x 3 150 x 3

- Continuous Capacity ControlCapacity Control

% 5, 15 100Cooler Type - Brazing Plate TypeCondenser Type - Brazing Plate TypeRefrigerant Type - R407C (Factory Charged) Flow Control - Electronic Expansion Valve Number of Independent Circuits - 3 3 3Oil Type - JAPAN ENERGY FREOL UX300 (Ester)Evaporator Connection Inch 3” Victaulic (3×Inlet / 3×Outlet ) Option Common Water Piping Inch 5” Victaulic (1×Inlet / 1×Outlet )Condenser Connection Inch 3” Victaulic (3×Inlet / 3×Outlet ) Option Common Water Piping Inch 5” Victaulic (1×Inlet / 1×Outlet )Control System - Micro-ProcessorChilled Water Outlet Temperature °C (-10) 5 15Cooling Water Outlet Temperature *3 °C 22 45 (55)Permissible Water Pressure Max. Cooler MPa 1.03 Condenser MPa 1.03

Safety and Protection Devices -

Reverse Phase Protection,Fuse and Thermal Relay for Compressor,Internal Thermostat for Compressor, Compressor Oil Heater,Control Circuit Fuse, High Pressure Switch, Low Pressure Control,Discharge Gas Temperature Control,Suction Gas Temperature Control, Freeze Protection Controland Compressor Operation Hour Meter

Power Supply - 3 , N / 380 - 415V / 50Hz

NOTES:

*1 The nominal cooling capacities are based on the European Standard EN12055.

Chilled Water Inlet / Outlet Temperature : 12 / 7 °C

Cooling Water Inlet / Outlet Temperature : 30 / 35 °C

*2 The nominal heating capacities are only for Heat Pump Operation Option and based on following conditions.

Chilled Water Inlet / Outlet Temperature : 12 / 7 °C

Hot Water (Condenser) Inlet / Outlet Temperature : 40 / 45 °C

*3 ( ) is in case of high condensing option and heat pump operation option.

Page 58: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

13/54 GENERAL SPECIFICATIONS

13.2. OPTION LINE UP

Following table shows options:

( mark shows available)

Specifications Standard Option Remarks

Outlet Temperature: 0 4 (Low1)

Outlet Temperature: -1 -5 (Low2)Low WaterTemperature

Outlet Temperature: - 6 -10 (Low3)

Compressor Extended Minimum Capacity Control DSW 7-3 ON

Compressor Circuit Breaker Protector For Each Compressor

Main Isolator Switch

Local/Remote Changeover Switch

Individual Alarm By Alarm Code

Operation Hour Meter

Pressure Sensor (High and Low)

Pump Operation Circuit Pump ON/OFF Contact

Non Voltage Contact for Remote indication Pump, Operation, Alarm

DC24V External Control Level or pulse

Short Period Power OFF Protection

Power Failure Recover Control

2 Different Temperature Setting

Remote Control Switch AC 220-240V

BMS Control (HARC-70CE1)/OP LON-WORKS

CSC-5S

ControlSystem

Number Cable

High Condensing TemperatureCondenser

Heat Pump Operation

Independent Circuit

Discharge Valve

Suction Valve

Dual safety valve

Compressor Safety Valve

Compressor Dual Safety Valve

RefrigerationCycle

Pressure Display (High and Low)Standard:Display on Operation Panel

PED Certificate (97/23/EC)PED: PressureEquipment Directive

10 bar Water Pressure

PN 16 Flange With Companion Flange

Differential Water Pressure Switch

Water Flow Switch (Field Install)

Water Cooler Heater

Water Cooler

Common Water Pipe (Only 180, 200 and 240 HP)

Witness TestOthers

Foundation Rubber Mats

Page 59: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/55

14. DRAWINGS

14.1. DIMENSIONAL DRAWINGS

RCUE 40WG2

RCUE 50WG2

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring

Inlet for Power

Supply Wiring

Cooler Water inlet

Condenser Water Outlet

Condenser Water InletCooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring

Inlet for Power

Supply Wiring

Cooler Water inlet

Condenser Water Outlet

Condenser Water InletCooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Page 60: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/56 DRAWINGS

RCUE 60WG2

RCUE 80WG2

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring

Inlet for PowerSupply Wiring

Cooler Water inlet

Condenser Water Outlet

Condenser Water InletCooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring

Inlet for Power

Supply Wiring

Cooler Water inlet

Condenser Water Outlet

Condenser Water InletCooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Page 61: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/57

RCUE 100WG2

RCUE 120WG2

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring Inlet for Power

Supply Wiring

CoolerWater inlet

CondenserWater Outlet

Condenser Water Inlet

Cooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring Inlet for Power

Supply Wiring

CoolerWater inlet

CondenserWater Outlet

Condenser Water Inlet

Cooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Page 62: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/58 DRAWINGS

RCUE 150WG2

RCUE 180WG2

Electrical Box

(cooler, welding connection)

Inlet for Control Wiring Inlet for PowerSupply Wiring

CoolerWater inlet

CondenserWater Outlet

Condenser Water Inlet

Cooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Electrical Box

(cooler, welding connection)

Inlet for Power Supply Wiring

3 x CoolerWater inlet

3 x CondenserWater Outlet

3 x Condenser Water Inlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

3 x CoolerWater outlet

Page 63: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/59

RCUE 200WG2

RCUE 240WG2

Electrical Box

(cooler, welding connection)

Inlet for PowerSupply Wiring

3 x CoolerWater inlet

3 x CondenserWater Outlet

3 x Condenser Water Inlet3 x Cooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x LiftingHoles

Electrical Box

(cooler, welding connection)

Inlet for PowerSupply Wiring

3 x CoolerWater inlet

3 x CondenserWater Outlet

3 x Condenser Water Inlet3 x Cooler Water Outlet

(cooler, 3 B victaulic connection)

(condenser, 3B Victaulic connection)

(condenser, welding connection)

4x Lifting Holes

Page 64: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/60 DRAWINGS

14.2. WIRING DIAGRAMS

POWER CIRCUIT FOR RCUE 40WG2, RCUE 50WG2, RCUE 60WG2 and RCUE 80WG2

Ma

in S

witc

h

PO

WE

R C

IRC

UIT

Mo

de

ls

RC

UE

40

WG

2

RC

UE

50

WG

2

RC

UE

60

WG

2

RC

UE

80

WG

2

Page 65: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/61

POWER CIRCUIT FOR RCUE 100WG2, RCUE 120WG2 and RCUE 150WG2

Ma

in S

witc

h

PO

WE

R C

IRC

UIT

Mo

de

ls

RC

UE

100 W

G2

RC

UE

120 W

G2

RC

UE

150 W

G2

Page 66: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/62 DRAWINGS

POWER CIRCUIT FOR RCUE 180WG2, RCUE 200WG2 and RCUE 240WG2

Ma

in S

witc

h

Mo

de

ls

RC

UE

180 W

G2

RC

UE

200 W

G2

RC

UE

240 W

G2

PO

WE

R C

IRC

UIT

Page 67: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/63

CONTROL CIRCUIT FOR RCUE 40WG2, RCUE 50WG2, RCUE 60WG2 and RCUE 80WG2

Mo

de

ls

RC

UE

40

WG

2

RC

UE

50

WG

2

RC

UE

60

WG

2

RC

UE

80

WG

2

CO

NT

RO

L C

IRC

UIT

Page 68: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/64 DRAWINGS

CONTROL CIRCUIT FOR RCUE 100WG2, RCUE 120WG2, RCUE 150WG2

Mo

de

ls

RC

UE

10

0W

G2

RC

UE

12

0W

G2

RC

UE

15

0W

G2

CO

NT

RO

L C

IRC

UIT

Page 69: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/65

CONTROL CIRCUIT FOR RCUE 180WG2, RCUE 200WG2 and RCUE 240WG2

Mo

de

ls

RC

UE

18

0W

G2

RC

UE

20

0W

G2

RC

UE

24

0W

G2

CO

NT

RO

L C

IRC

UIT

Page 70: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/66 DRAWINGS

MAIN PRINTED CIRCUIT BOARD

MA

IN P

RIN

TE

D C

IRC

UIT

BO

AR

D (

MA

ST

ER

)

For

>3 c

ycle

sunits

For

>2 c

ycle

sunits

Fie

ldsu

pply

Diff

ere

nci

al w

ate

r P

ress

ure

Sw

itch

(C

on

dense

r si

de)

(Optio

n)

Diff

ere

nci

al w

ate

r P

ress

ure

Sw

itch

(E

vap

ora

tor

side)

(Optio

n)

For

3 c

ycle

s un

its

For

3 c

ycle

s un

itsO

ptio

n

Page 71: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/67

RELAYS PRINTED CIRCUIT BOARD

1 2 3

Mo

de

l

RC

UE

40

,50

,60

, 8

0W

G2

RC

UE

100,1

20,

150W

G2

RC

UE

180,

200,

240W

G2

RE

LA

YS

PR

INT

ED

CIR

CU

IT B

OA

RD

Op

tion

Only

PC

Bd1,3

and

PC

Bd

2 in

3 c

ycle

sunits

On

ly f

or

un

its w

ithE

con

om

izer

Fre

e-c

oolin

gO

utp

ut si

gnal

(only

PC

Bd1)

Page 72: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

14/68 DRAWINGS

CUSTOMER WIRING

N° Name

1In case of remote control operation this wire shallbe removed.

2 R Phase

3 Neutral

4 Low Voltage / Remote Control

5 Run/Stop Signal

6 Alarm Signal

7 Alarm Lamp

8 Pump Interlock

9 Pump operation

10 Remote Control Switch (RSW-A) (Option)

11 2,3 cycles

12 3 cycles

N° Name

13 2 nd. Setting Temperature

14 External Thermostat Operation

15 Operation Mode (OPTION)

16Only used for:-Diff. Water Pressure switch (OPTION)-Flow Switch (OPTION)

17 Force Compressor Load Operation

18Free CoolingOutput signal (Only cycle Nº 1)

19In case of individual indication without RemoteControl Switch

20 Customer wiring

21 Force compressor load

22 Setting of low voltage control

NOTE:1. All the setting shall be performed before Power ON.2. Remote/Local Change over Switch on Operation Switch shall be set to "Remote".3. Terminals 1 ∼ n57 are for AC220-240V –Terminals A ∼ D are for DC24V. Terminals E ∼ Fare H-Link (Low signal)

Page 73: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

DRAWINGS 14/69

PARTS LIST

(n=1~N)

Mark Name Remark Mark Name Remark

MC1-n Compressor Motor EF1~5 Fuse 6A

MI Main Isolator SV11-n1 Solenoid Valve for Starting

CMC1-n Contactor for Compressor Motor SV12-n2 Solenoid Valve for Load-down

CMCs1-snContactor for Compressor Motor(Start Operation)

SV13-n3 Solenoid Valve for Load-up

CMCD1-DnContactor for Compressor Motor(Delta Operation)

TM1-n Hour Meter

PFC1-nFuse holder for CompressorMotor

or optionalCircuit Breaker

PCBA Printed Circuit Board for Display

EFC11-n3 Fuse for Compressor Motor

or optionalCircuit Breaker

PCBB Printed Circuit Board for Operation

ORC1-nOvercurrent Relay forCompressor Motor

PCBC1 Printed Circuit Board for CPU

ITC1- nInternal Thermostat forCompressor

PCBD1-Dn Printed Circuit Board for Relay

CH1-n Crankcase Heater PCB FPrinted Circuit Board for Expansionvalve

AR,h,r,1-n Auxiliary Relay WPC

Water Pressure Switch,

Water Flow Switch, EvaporatorCircuit

OPTION

PSH1-n High Pressure SwitchOFF: 2.75MpaON: ManualReset

PBSR1Push Button Switch for Starting(REMOTE)

TF 1,2,3,4,5 Transformer PBSR2Push Button Switch for Stoppage(REMOTE)

Pd1-n High Pressure Sensor RL(1-n)Pilot Lamp for Remote Indication(Unit Operation, Cool/Heat)

Ps1-n Low Pressure Sensor OL(1-n, C, H)Pilot Lamp for Remote Indication(Alarm)

EHF1-n Cooler Heater OPTION CMP1-2 Contactor for Pumps

THMiInlet Water TemperatureThermistor

TRP1-2 Thermal Relay for Pump

THMO 1,2,3Outlet Water TemperatureThermistor

WPHWater Pressure Switch, Water FlowSwitch, Condenser Circuit

FieldSupplied

THMS1-nSuction Gas TemperatureThermistor

CMT Contactor for Tower

THMd 1-nDischarge TemperatureThermistor

MVn Electronic Expansion Valve (Exp V.)

THMr2 1-nTemperature Thermistor BeforeExp. Valve

PSWn Pressure switch for Economizer

THMO 11~31Outlet Water TemperatureThermistor (Evap.)

SVEn Solenoid Valve for Economizer

THMi (h)Inlet Water TemperatureThermistor (heat)

OPTION EHn Electric Heater for Evaporator

THM O n(h)Outlet Water TemperatureThermistor (heat)

OPTION SW1~6 Switches field supplied

MFA Noise Filter (Ring Cores)

Model N

RCUE 40, 50, 60, 80 WG2 1

RCUE 100, 120, 150 WG2 2

RCUE 180, 200, 240 WG2 3

Page 74: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

15/70 MODEL SELECTION

15. MODEL SELECTION

15.1. SELECTION EXAMPLE

1. Determine the system requirements

Condenser Water Inlet Temperature: 32 °CCondenser Water Outlet Temperature: 37 °CChilled Water Inlet Temperature: 12 °CChilled Water Outlet Temperature: 7 °CCooling Load: 300 kw

2. Select Model and Read the Performance

From the cooling capacity table,model RCUE100WG2 can beselected with the followingperformance.Cooling Capacity: 316.3 kWChilled Water Flow Rate: 54.4 m³/hWater Cooler Pressure Drop: 36.9 kPaCondenser Water Flow Rate: 68.7 m³/hCondenser Pressure Drop: 67.5 kPaCompressor Input Power: 83 kW

3. Correct the Data

1. Flow RateWhen the water Inlet/Outlet temperature difference isnot 5°C, correct the flow rate by the following formula:

5(°C) × Tabulated Flow Rate (CFR)CorrectedFlow Rate

=Given Temp. Difference(°C)

The corrected Flow Rate must be confirmed to be withinthe working range.

2. Cooling Capacity and Compressor Input.When the fouling factor is taken into consideration, thecooling capacity and the compressor input will bedifferent from the value indicated in the cooling capacitytable.

Corrected Capacity = Kfc × CAP

Corrected Input = Kfi × IPT

CAP: Tabulated Cooling CapacityIPT: Tabulated Compressor InputKfc: Capacity Correction FactorKfi: Compressor Input Correction Factor

Fouling Factorm

2h °C/kcal

(m2

°C/kW)Kfc Kfi

0 1.00 1.00

0.00005(0.043) 1.00 1.00WaterCooler

0.0001(0.086) 0.99 1.01

0 1.00 1.00

0.0001(0.086) 0.98 1.03Condenser

0.0002(0.172) 0.96 1.06

4. Water Pressure Drop

Water pressure drop is given by the following formula

PD = α x Qβ

PD: Pressure Drop (kPa)Q: Water Flow (m³/h)α,β Parameters (table below)

Model: Parameter

RCUE-WG2

40 0.0764 1.912

50 0.0648 1.912

60 0.0437 1.912

80 0.0374 1.912

100 0.0188 1.897

120 0.0188 1.897

150 0.0188 1.897

180 0.0053 1.912

200 0.0053 1.912

Co

ole

r

240 0.0046 1.912

40 0.0688 1.872

50 0.0480 1.881

60 0.0328 1.897

80 0.0358 1.912

100 0.0225 1.893

120 0.0160 1.901

150 0.0160 1.901

180 0.0041 1.897

200 0.0041 1.897

Co

nd

en

ser

240 0.0044 1.912

Page 75: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MODEL SELECTION 15/71

15.2. PERFORMANCE TABLE

RCUE40WG2 RCUE50WG2 RCUE60WG2CDOT CLOT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD IPT

5,0 137,9 23,7 32,5 162,8 28,0 35,2 25,0 164,6 28,3 38,7 194,4 33,4 35,4 29,8 199,6 34,3 37,8 236,2 40,6 37,0 36,6

6,0 140,9 24,2 33,9 166,0 28,6 36,5 25,2 168,2 28,9 40,4 198,3 34,1 36,7 30,0 204,0 35,1 39,4 240,8 41,4 38,4 36,9

7,0 143,9 24,8 35,3 169,3 29,1 37,8 25,3 171,9 29,6 42,1 202,1 34,8 38,1 30,2 208,4 35,8 41,0 245,5 42,2 39,8 37,1

8,0 147,0 25,3 36,8 172,5 29,7 39,2 25,5 175,5 30,2 43,8 206,0 35,4 39,5 30,5 212,8 36,6 42,7 250,2 43,0 41,2 37,4

9,0 150,0 25,8 38,3 175,7 30,2 40,6 25,7 179,1 30,8 45,5 209,8 36,1 40,9 30,7 217,2 37,4 44,4 254,8 43,8 42,7 37,7

10,0 153,1 26,3 39,7 178,9 30,8 42,0 25,9 182,8 31,4 47,3 213,6 36,7 42,3 30,9 221,6 38,1 46,1 259,5 44,6 44,2 37,9

11,0 156,1 26,8 41,3 182,2 31,3 43,4 26,0 186,4 32,1 49,1 217,5 37,4 43,7 31,1 226,0 38,9 47,9 264,2 45,4 45,7 38,2

12,0 159,1 27,4 42,8 185,4 31,9 44,8 26,2 190,0 32,7 51,0 221,3 38,1 45,2 31,3 230,4 39,6 49,7 268,8 46,2 47,3 38,4

13,0 162,2 27,9 44,4 188,6 32,4 46,3 26,4 193,7 33,3 52,9 225,2 38,7 46,7 31,5 234,8 40,4 51,5 273,5 47,0 48,8 38,7

14,0 165,2 28,4 46,0 191,8 33,0 47,8 26,6 197,3 33,9 54,8 229,0 39,4 48,2 31,7 239,2 41,1 53,4 278,2 47,8 50,4 39,0

22,0

15,0 168,3 28,9 47,6 195,0 33,5 49,3 26,8 200,9 34,6 56,7 232,9 40,1 49,7 32,0 243,6 41,9 55,3 282,8 48,6 52,0 39,2

5,0 135,4 23,3 31,4 162,3 27,9 35,0 26,9 169,1 29,1 40,8 201,2 34,6 37,8 32,1 205,0 35,3 39,8 244,4 42,0 39,5 39,4

6,0 138,5 23,8 32,8 165,6 28,5 36,3 27,1 174,7 30,1 43,4 207,0 35,6 39,8 32,3 211,8 36,4 42,3 251,5 43,3 41,7 39,7

7,0 141,6 24,4 34,3 168,9 29,0 37,6 27,2 180,4 31,0 46,1 212,9 36,6 42,0 32,5 218,7 37,6 45,0 258,6 44,5 43,9 39,9

8,0 144,8 24,9 35,7 172,1 29,6 39,0 27,4 186,0 32,0 48,9 218,7 37,6 44,2 32,7 225,5 38,8 47,7 265,7 45,7 46,2 40,1

9,0 147,9 25,4 37,2 175,4 30,2 40,4 27,5 191,6 33,0 51,8 224,5 38,6 46,4 32,9 232,4 40,0 50,5 272,7 46,9 48,6 40,4

10,0 151,0 26,0 38,7 178,7 30,7 41,9 27,7 197,3 33,9 54,8 230,4 39,6 48,7 33,1 239,2 41,1 53,4 279,8 48,1 51,0 40,6

11,0 154,1 26,5 40,3 182,0 31,3 43,3 27,9 202,9 34,9 57,8 236,2 40,6 51,1 33,3 246,1 42,3 56,4 286,9 49,3 53,5 40,9

12,0 157,2 27,0 41,8 185,3 31,9 44,8 28,0 208,6 35,9 60,9 242,1 41,6 53,5 33,5 252,9 43,5 59,4 294,0 50,6 56,0 41,1

13,0 160,3 27,6 43,4 188,5 32,4 46,3 28,2 214,2 36,8 64,1 247,9 42,6 55,9 33,7 259,7 44,7 62,5 301,1 51,8 58,6 41,3

14,0 163,5 28,1 45,1 191,8 33,0 47,8 28,4 219,9 37,8 67,4 253,7 43,6 58,4 33,9 266,6 45,9 65,7 308,2 53,0 61,2 41,6

25,0

15,0 166,6 28,7 46,7 195,1 33,6 49,3 28,5 225,5 38,8 70,7 259,6 44,6 61,0 34,1 273,4 47,0 68,9 315,2 54,2 63,9 41,8

5,0 131,3 22,6 29,7 161,4 27,8 34,6 30,1 156,8 27,0 35,3 192,7 33,2 34,8 35,9 190,1 32,7 34,4 234,2 40,3 36,4 44,1

6,0 134,6 23,1 31,1 164,8 28,3 36,0 30,2 160,7 27,6 37,0 196,8 33,8 36,2 36,1 194,8 33,5 36,1 239,1 41,1 37,9 44,3

7,0 137,8 23,7 32,5 168,2 28,9 37,4 30,4 164,6 28,3 38,7 200,8 34,5 37,6 36,2 199,5 34,3 37,7 244,0 42,0 39,3 44,5

8,0 141,1 24,3 34,0 171,6 29,5 38,8 30,5 168,4 29,0 40,5 204,8 35,2 39,1 36,4 204,2 35,1 39,5 248,9 42,8 40,8 44,7

9,0 144,3 24,8 35,5 174,9 30,1 40,2 30,6 172,3 29,6 42,3 208,9 35,9 40,5 36,6 208,9 35,9 41,2 253,8 43,7 42,4 44,9

10,0 147,5 25,4 37,1 178,3 30,7 41,7 30,8 176,2 30,3 44,1 212,9 36,6 42,0 36,7 213,6 36,7 43,0 258,7 44,5 44,0 45,1

11,0 150,8 25,9 38,6 181,7 31,3 43,2 30,9 180,0 31,0 46,0 217,0 37,3 43,5 36,9 218,3 37,5 44,8 263,6 45,3 45,5 45,3

12,0 154,0 26,5 40,2 185,1 31,8 44,7 31,1 183,9 31,6 47,9 221,0 38,0 45,0 37,1 223,0 38,4 46,7 268,5 46,2 47,2 45,5

13,0 157,3 27,1 41,9 188,5 32,4 46,2 31,2 187,8 32,3 49,8 225,0 38,7 46,6 37,2 227,7 39,2 48,6 273,4 47,0 48,8 45,7

14,0 160,5 27,6 43,5 191,8 33,0 47,8 31,3 191,7 33,0 51,8 229,1 39,4 48,2 37,4 232,4 40,0 50,5 278,3 47,9 50,5 45,9

30,0

15,0 163,8 28,2 45,2 195,2 33,6 49,4 31,5 195,5 33,6 53,8 233,1 40,1 49,8 37,6 237,1 40,8 52,5 283,2 48,7 52,2 46,135,0 5,0 127,3 21,9 27,9 160,5 27,6 34,2 33,3 149,5 25,7 32,2 189,2 32,5 33,6 39,7 181,2 31,2 31,4 230,0 39,6 35,2 48,8

6,0 130,6 22,5 29,4 164,0 28,2 35,6 33,4 154,7 26,6 34,4 194,6 33,5 35,5 39,9 187,6 32,3 33,6 236,5 40,7 37,1 48,9

7,0 134,0 23,0 30,8 167,5 28,8 37,1 33,5 160,0 27,5 36,7 200,0 34,4 37,3 40,0 194,0 33,4 35,8 243,1 41,8 39,1 49,1

8,0 137,4 23,6 32,3 171,0 29,4 38,5 33,6 165,3 28,4 39,0 205,4 35,3 39,3 40,1 200,4 34,5 38,1 249,7 42,9 41,1 49,3

9,0 140,7 24,2 33,9 174,5 30,0 40,0 33,7 170,5 29,3 41,5 210,8 36,3 41,2 40,3 206,8 35,6 40,4 256,2 44,1 43,1 49,4

10,0 144,1 24,8 35,4 177,9 30,6 41,5 33,8 175,8 30,2 43,9 216,2 37,2 43,2 40,4 213,2 36,7 42,8 262,8 45,2 45,3 49,6

11,0 147,5 25,4 37,0 181,4 31,2 43,1 34,0 181,1 31,1 46,5 221,6 38,1 45,3 40,5 219,5 37,8 45,3 269,3 46,3 47,4 49,8

12,0 150,8 25,9 38,6 184,9 31,8 44,6 34,1 186,3 32,0 49,1 227,0 39,0 47,4 40,7 225,9 38,9 47,9 275,9 47,4 49,6 49,9

13,0 154,2 26,5 40,3 188,4 32,4 46,2 34,2 191,6 33,0 51,8 232,4 40,0 49,5 40,8 232,3 40,0 50,5 282,4 48,6 51,9 50,1

14,0 157,6 27,1 42,0 191,9 33,0 47,8 34,3 196,9 33,9 54,5 237,8 40,9 51,7 41,0 238,7 41,1 53,2 289,0 49,7 54,2 50,3

15,0 160,9 27,7 43,7 195,3 33,6 49,4 34,4 202,1 34,8 57,4 243,2 41,8 53,9 41,1 245,1 42,2 55,9 295,5 50,8 56,6 50,4

5,0 125,6 21,6 27,2 160,2 27,6 34,1 34,5 145,5 25,0 30,6 186,8 32,1 32,8 41,2 176,5 30,4 29,8 227,1 39,1 34,3 50,6

6,0 129,1 22,2 28,7 163,7 28,2 35,5 34,7 150,7 25,9 32,7 192,1 33,0 34,6 41,4 182,8 31,4 31,9 233,6 40,2 36,2 50,8

7,0 132,5 22,8 30,2 167,2 28,8 37,0 34,8 155,9 26,8 34,9 197,4 34,0 36,4 41,5 189,1 32,5 34,1 240,0 41,3 38,1 50,9

8,0 135,9 23,4 31,7 170,7 29,4 38,4 34,9 161,1 27,7 37,2 202,7 34,9 38,3 41,6 195,4 33,6 36,3 246,5 42,4 40,1 51,1

9,0 139,3 24,0 33,2 174,3 30,0 39,9 35,0 166,3 28,6 39,5 208,1 35,8 40,2 41,8 201,6 34,7 38,5 252,9 43,5 42,1 51,3

10,0 142,7 24,5 34,8 177,8 30,6 41,5 35,1 171,5 29,5 41,9 213,4 36,7 42,2 41,9 207,9 35,8 40,8 259,3 44,6 44,2 51,4

11,0 146,1 25,1 36,4 181,3 31,2 43,0 35,2 176,7 30,4 44,4 218,7 37,6 44,2 42,0 214,2 36,8 43,2 265,8 45,7 46,3 51,6

12,0 149,6 25,7 38,0 184,8 31,8 44,6 35,3 181,9 31,3 46,9 224,0 38,5 46,2 42,1 220,5 37,9 45,7 272,2 46,8 48,4 51,7

13,0 153,0 26,3 39,7 188,4 32,4 46,2 35,4 187,1 32,2 49,5 229,3 39,4 48,3 42,3 226,8 39,0 48,2 278,7 47,9 50,6 51,9

14,0 156,4 26,9 41,4 191,9 33,0 47,8 35,5 192,3 33,1 52,1 234,6 40,4 50,4 42,4 233,1 40,1 50,8 285,1 49,0 52,9 52,0

37,0

15,0 159,8 27,5 43,2 195,4 33,6 49,5 35,6 197,4 34,0 54,9 239,9 41,3 52,6 42,5 239,4 41,2 53,5 291,6 50,2 55,1 52,2

5,0 123,2 21,2 26,2 159,7 27,5 33,9 36,5 147,1 25,3 31,2 190,6 32,8 34,1 43,5 178,4 30,7 30,5 231,8 39,9 35,7 53,4

6,0 126,7 21,8 27,7 163,2 28,1 35,3 36,6 151,3 26,0 33,0 194,9 33,5 35,6 43,6 183,4 31,5 32,1 237,0 40,8 37,2 53,6

7,0 130,2 22,4 29,2 166,8 28,7 36,8 36,6 155,4 26,7 34,7 199,2 34,3 37,1 43,8 188,5 32,4 33,8 242,2 41,7 38,8 53,7

8,0 133,7 23,0 30,7 170,4 29,3 38,3 36,7 159,6 27,5 36,5 203,5 35,0 38,6 43,9 193,5 33,3 35,6 247,4 42,5 40,4 53,8

9,0 137,2 23,6 32,2 174,0 29,9 39,8 36,8 163,8 28,2 38,4 207,7 35,7 40,1 44,0 198,6 34,2 37,4 252,5 43,4 42,0 54,0

10,0 140,7 24,2 33,8 177,6 30,5 41,4 36,9 167,9 28,9 40,3 212,0 36,5 41,7 44,1 203,6 35,0 39,2 257,7 44,3 43,6 54,1

11,0 144,1 24,8 35,4 181,1 31,2 42,9 37,0 172,1 29,6 42,2 216,3 37,2 43,3 44,2 208,7 35,9 41,1 262,9 45,2 45,3 54,2

12,0 147,6 25,4 37,1 184,7 31,8 44,5 37,1 176,3 30,3 44,2 220,6 37,9 44,9 44,3 213,7 36,8 43,1 268,1 46,1 47,0 54,4

13,0 151,1 26,0 38,8 188,3 32,4 46,2 37,2 180,4 31,0 46,2 224,8 38,7 46,5 44,4 218,8 37,6 45,0 273,3 47,0 48,8 54,5

14,0 154,6 26,6 40,5 191,9 33,0 47,8 37,3 184,6 31,8 48,2 229,1 39,4 48,2 44,5 223,8 38,5 47,0 278,5 47,9 50,5 54,6

40,0

15,0 158,1 27,2 42,3 195,5 33,6 49,5 37,4 188,8 32,5 50,3 233,4 40,1 49,9 44,6 228,9 39,4 49,1 283,7 48,8 52,3 54,8

5,0 119,1 20,5 24,6 158,8 27,3 33,5 39,7 129,9 22,3 24,6 177,2 30,5 29,7 47,3 157,5 27,1 24,0 215,6 37,1 31,1 58,1

6,0 122,7 21,1 26,1 162,5 27,9 35,0 39,7 134,8 23,2 26,4 182,2 31,3 31,3 47,4 163,4 28,1 25,8 221,6 38,1 32,8 58,2

7,0 126,4 21,7 27,5 166,1 28,6 36,5 39,8 139,6 24,0 28,3 187,1 32,2 32,9 47,5 169,3 29,1 27,6 227,6 39,2 34,5 58,3

8,0 130,0 22,4 29,1 169,8 29,2 38,0 39,8 144,5 24,9 30,2 192,1 33,0 34,6 47,6 175,2 30,1 29,4 233,6 40,2 36,2 58,4

9,0 133,6 23,0 30,6 173,5 29,8 39,6 39,9 149,4 25,7 32,2 197,1 33,9 36,3 47,7 181,2 31,2 31,4 239,7 41,2 38,0 58,5

10,0 137,2 23,6 32,2 177,2 30,5 41,2 40,0 154,3 26,5 34,2 202,0 34,8 38,1 47,7 187,1 32,2 33,4 245,7 42,3 39,8 58,6

11,0 140,8 24,2 33,9 180,9 31,1 42,8 40,0 159,2 27,4 36,3 207,0 35,6 39,8 47,8 193,0 33,2 35,4 251,7 43,3 41,7 58,7

12,0 144,4 24,8 35,6 184,5 31,7 44,5 40,1 164,1 28,2 38,5 212,0 36,5 41,7 47,9 198,9 34,2 37,5 257,7 44,3 43,6 58,8

13,0 148,0 25,5 37,3 188,2 32,4 46,1 40,2 169,0 29,1 40,7 216,9 37,3 43,5 48,0 204,9 35,2 39,7 263,8 45,4 45,6 58,9

14,0 151,7 26,1 39,1 191,9 33,0 47,8 40,2 173,9 29,9 43,0 221,9 38,2 45,4 48,1 210,8 36,3 41,9 269,8 46,4 47,6 59,0

45,0

15,0 155,3 26,7 40,9 195,6 33,6 49,6 40,3 178,7 30,7 45,4 226,9 39,0 47,3 48,1 216,7 37,3 44,2 275,8 47,4 49,6 59,1

Where,CDOT: Condenser Water Outlet Temperature (°C)CLOT: Chilled Water Outlet Temperature (°C)CCAP: Cooling Capacity (kW)HCAP: Condenser Heat Rejection (Kw)

HFR: Condenser Water Flow Rate at 5°C (m3/h)HPD:Condenser Water Pressure Drop (kPa)CFR:Chilled Water Flow Rate at 5°C (m3/h)CPD: Water Cooler Pressure Drop (kPa)IPT: Compressor Input Power (kW)

Conversion Multiplier:1 kW = 860 kcal/h = 3412 Btu/h1 kPa = 0.102 mAq

Page 76: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

15/72 MODEL SELECTION

Performance Table (cont.)

RCUE80WG2 RCUE100WG2 RCUE120WG2CDOT CLOT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD IPT

5,0 238,7 41,1 45,5 279,3 48,0 58,8 40,6 329,2 56,6 39,8 388,8 66,9 64,2 59,6 399,2 68,7 57,3 472,4 81,2 68,3 73,2

6,0 243,9 42,0 47,4 284,9 49,0 61,1 40,9 336,5 57,9 41,5 396,5 68,2 66,6 60,1 408,0 70,2 59,8 481,7 82,9 70,9 73,7

7,0 249,2 42,9 49,4 290,4 50,0 63,4 41,2 343,7 59,1 43,2 404,2 69,5 69,1 60,5 416,8 71,7 62,2 491,0 84,5 73,6 74,3

8,0 254,5 43,8 51,4 296,0 50,9 65,7 41,5 351,0 60,4 44,9 411,9 70,8 71,6 60,9 425,6 73,2 64,8 500,4 86,1 76,2 74,8

9,0 259,7 44,7 53,5 301,5 51,9 68,1 41,8 358,3 61,6 46,7 419,6 72,2 74,2 61,3 434,4 74,7 67,3 509,7 87,7 79,0 75,3

10,0 265,0 45,6 55,6 307,1 52,8 70,5 42,1 365,5 62,9 48,5 427,3 73,5 76,8 61,8 443,2 76,2 69,9 519,0 89,3 81,7 75,8

11,0 270,3 46,5 57,7 312,6 53,8 73,0 42,4 372,8 64,1 50,4 435,0 74,8 79,4 62,2 452,0 77,7 72,6 528,4 90,9 84,6 76,4

12,0 275,5 47,4 59,9 318,2 54,7 75,5 42,7 380,0 65,4 52,3 442,7 76,1 82,1 62,6 460,8 79,3 75,3 537,7 92,5 87,4 76,9

13,0 280,8 48,3 62,1 323,8 55,7 78,0 43,0 387,3 66,6 54,2 450,4 77,5 84,8 63,1 469,6 80,8 78,1 547,0 94,1 90,3 77,4

14,0 286,1 49,2 64,3 329,3 56,6 80,6 43,2 394,6 67,9 56,1 458,1 78,8 87,6 63,5 478,4 82,3 80,9 556,4 95,7 93,3 77,9

22,0

15,0 291,3 50,1 66,6 334,9 57,6 83,2 43,5 401,8 69,1 58,1 465,8 80,1 90,4 63,9 487,2 83,8 83,7 565,7 97,3 96,3 78,5

5,0 234,4 40,3 44,0 278,2 47,8 58,4 43,7 323,4 55,6 38,5 387,6 66,7 63,8 64,2 392,1 67,4 55,4 470,9 81,0 67,9 78,8

6,0 239,8 41,3 45,9 283,8 48,8 60,7 44,0 330,8 56,9 40,2 395,4 68,0 66,3 64,6 401,1 69,0 57,9 480,4 82,6 70,6 79,3

7,0 245,2 42,2 47,9 289,5 49,8 63,0 44,3 338,3 58,2 41,9 403,2 69,4 68,8 65,0 410,1 70,5 60,4 489,9 84,3 73,2 79,8

8,0 250,6 43,1 50,0 295,2 50,8 65,4 44,5 345,7 59,5 43,7 411,1 70,7 71,3 65,4 419,2 72,1 62,9 499,4 85,9 76,0 80,3

9,0 256,0 44,0 52,0 300,8 51,7 67,8 44,8 353,1 60,7 45,5 418,9 72,1 73,9 65,8 428,2 73,6 65,5 508,9 87,5 78,7 80,7

10,0 261,4 45,0 54,2 306,5 52,7 70,3 45,1 360,6 62,0 47,3 426,8 73,4 76,6 66,2 437,2 75,2 68,2 518,4 89,2 81,6 81,2

11,0 266,8 45,9 56,3 312,2 53,7 72,8 45,3 368,0 63,3 49,2 434,6 74,7 79,3 66,6 446,2 76,8 70,9 527,9 90,8 84,4 81,7

12,0 272,2 46,8 58,5 317,8 54,7 75,3 45,6 375,5 64,6 51,1 442,4 76,1 82,0 67,0 455,3 78,3 73,6 537,4 92,4 87,3 82,2

13,0 277,6 47,7 60,8 323,5 55,6 77,9 45,9 382,9 65,9 53,0 450,3 77,4 84,8 67,3 464,3 79,9 76,4 546,9 94,1 90,3 82,7

14,0 283,0 48,7 63,0 329,2 56,6 80,5 46,1 390,3 67,1 55,0 458,1 78,8 87,6 67,7 473,3 81,4 79,2 556,5 95,7 93,3 83,2

25,0

15,0 288,4 49,6 65,3 334,8 57,6 83,2 46,4 397,8 68,4 57,0 465,9 80,1 90,4 68,1 482,3 83,0 82,1 566,0 97,3 96,4 83,6

5,0 227,4 39,1 41,5 276,3 47,5 57,6 48,9 313,6 53,9 36,3 385,5 66,3 63,2 71,8 380,3 65,4 52,3 468,5 80,6 67,3 88,2

6,0 233,0 40,1 43,5 282,2 48,5 60,0 49,2 321,4 55,3 38,0 393,5 67,7 65,7 72,2 389,7 67,0 54,8 478,3 82,3 70,0 88,6

7,0 238,6 41,0 45,5 288,0 49,5 62,4 49,4 329,1 56,6 39,8 401,6 69,1 68,3 72,5 399,1 68,6 57,3 488,1 83,9 72,7 89,0

8,0 244,2 42,0 47,6 293,8 50,5 64,8 49,6 336,9 57,9 41,6 409,7 70,5 70,9 72,8 408,4 70,3 59,9 497,9 85,6 75,5 89,4

9,0 249,8 43,0 49,7 299,7 51,5 67,3 49,8 344,6 59,3 43,4 417,8 71,9 73,6 73,2 417,8 71,9 62,5 507,6 87,3 78,4 89,8

10,0 255,5 43,9 51,8 305,5 52,5 69,8 50,1 352,3 60,6 45,3 425,8 73,2 76,3 73,5 427,2 73,5 65,2 517,4 89,0 81,3 90,2

11,0 261,1 44,9 54,0 311,4 53,6 72,4 50,3 360,1 61,9 47,2 433,9 74,6 79,0 73,8 436,6 75,1 68,0 527,2 90,7 84,2 90,6

12,0 266,7 45,9 56,3 317,2 54,6 75,0 50,5 367,8 63,3 49,1 442,0 76,0 81,8 74,2 446,0 76,7 70,8 537,0 92,4 87,2 91,0

13,0 272,3 46,8 58,5 323,0 55,6 77,7 50,8 375,6 64,6 51,1 450,1 77,4 84,7 74,5 455,4 78,3 73,6 546,8 94,1 90,3 91,4

14,0 277,9 47,8 60,9 328,9 56,6 80,4 51,0 383,3 65,9 53,1 458,1 78,8 87,6 74,8 464,8 79,9 76,5 556,6 95,7 93,4 91,9

30,0

15,0 283,5 48,8 63,2 334,7 57,6 83,2 51,2 391,0 67,3 55,2 466,2 80,2 90,5 75,2 474,1 81,6 79,5 566,4 97,4 96,5 92,3

35,0 5,0 220,3 37,9 39,1 274,5 47,2 56,9 54,1 303,9 52,3 34,2 383,4 65,9 62,5 79,5 368,5 63,4 49,3 466,0 80,2 66,6 97,5

6,0 226,2 38,9 41,1 280,5 48,2 59,3 54,3 312,0 53,7 35,9 391,7 67,4 65,1 79,7 378,3 65,1 51,8 476,1 81,9 69,4 97,9

7,0 232,0 39,9 43,1 286,5 49,3 61,8 54,5 320,0 55,0 37,7 400,0 68,8 67,8 80,0 388,0 66,7 54,3 486,2 83,6 72,2 98,2

8,0 237,8 40,9 45,2 292,5 50,3 64,3 54,7 328,0 56,4 39,5 408,3 70,2 70,4 80,3 397,7 68,4 57,0 496,3 85,4 75,1 98,5

9,0 243,7 41,9 47,3 298,5 51,3 66,8 54,9 336,1 57,8 41,4 416,6 71,7 73,2 80,5 407,5 70,1 59,6 506,4 87,1 78,0 98,9

10,0 249,5 42,9 49,5 304,5 52,4 69,4 55,1 344,1 59,2 43,3 424,9 73,1 76,0 80,8 417,2 71,8 62,4 516,4 88,8 81,0 99,2

11,0 255,3 43,9 51,8 310,6 53,4 72,1 55,2 352,2 60,6 45,2 433,3 74,5 78,8 81,1 427,0 73,4 65,2 526,5 90,6 84,0 99,5

12,0 261,1 44,9 54,0 316,6 54,5 74,8 55,4 360,2 62,0 47,2 441,6 75,9 81,7 81,4 436,7 75,1 68,0 536,6 92,3 87,1 99,9

13,0 267,0 45,9 56,4 322,6 55,5 77,5 55,6 368,2 63,3 49,2 449,9 77,4 84,6 81,6 446,5 76,8 70,9 546,7 94,0 90,2 100,2

14,0 272,8 46,9 58,8 328,6 56,5 80,3 55,8 376,3 64,7 51,3 458,2 78,8 87,6 81,9 456,2 78,5 73,9 556,8 95,8 93,4 100,6

15,0 278,6 47,9 61,2 334,6 57,6 83,1 56,0 384,3 66,1 53,4 466,5 80,2 90,6 82,2 466,0 80,1 76,9 566,9 97,5 96,7 100,9

5,0 217,5 37,4 38,1 273,7 47,1 56,6 56,2 300,0 51,6 33,4 382,5 65,8 62,3 82,5 363,8 62,6 48,1 465,1 80,0 66,3 101,3

6,0 223,4 38,4 40,1 279,8 48,1 59,0 56,4 308,2 53,0 35,1 390,9 67,2 64,9 82,7 373,7 64,3 50,6 475,3 81,7 69,1 101,6

7,0 229,4 39,4 42,2 285,9 49,2 61,5 56,5 316,3 54,4 36,9 399,4 68,7 67,5 83,0 383,6 66,0 53,2 485,5 83,5 72,0 101,9

8,0 235,3 40,5 44,3 292,0 50,2 64,0 56,7 324,5 55,8 38,7 407,8 70,1 70,3 83,3 393,5 67,7 55,8 495,7 85,3 74,9 102,2

9,0 241,2 41,5 46,4 298,1 51,3 66,6 56,9 332,7 57,2 40,6 416,2 71,6 73,0 83,5 403,4 69,4 58,5 505,9 87,0 77,8 102,5

10,0 247,1 42,5 48,6 304,2 52,3 69,2 57,1 340,8 58,6 42,5 424,6 73,0 75,8 83,8 413,2 71,1 61,2 516,1 88,8 80,9 102,8

11,0 253,0 43,5 50,9 310,2 53,4 71,9 57,2 349,0 60,0 44,4 433,0 74,5 78,7 84,0 423,1 72,8 64,1 526,3 90,5 83,9 103,1

12,0 258,9 44,5 53,2 316,3 54,4 74,6 57,4 357,1 61,4 46,4 441,4 75,9 81,6 84,3 433,0 74,5 66,9 536,5 92,3 87,0 103,4

13,0 264,8 45,6 55,5 322,4 55,5 77,4 57,6 365,3 62,8 48,5 449,8 77,4 84,6 84,5 442,9 76,2 69,9 546,7 94,0 90,2 103,7

14,0 270,8 46,6 57,9 328,5 56,5 80,2 57,7 373,4 64,2 50,5 458,2 78,8 87,6 84,8 452,8 77,9 72,8 556,8 95,8 93,4 104,0

37,0

15,0 276,7 47,6 60,4 334,6 57,5 83,1 57,9 381,6 65,6 52,7 466,6 80,3 90,7 85,0 462,7 79,6 75,9 567,0 97,5 96,7 104,4

5,0 213,3 36,7 36,7 272,6 46,9 56,2 59,3 294,2 50,6 32,1 381,3 65,6 61,9 87,1 356,7 61,4 46,3 463,6 79,7 65,9 106,9

6,0 219,3 37,7 38,7 278,8 48,0 58,6 59,5 302,5 52,0 33,9 389,8 67,0 64,5 87,3 366,8 63,1 48,9 474,0 81,5 68,8 107,1

7,0 225,4 38,8 40,8 285,0 49,0 61,1 59,6 310,9 53,5 35,7 398,4 68,5 67,2 87,5 376,9 64,8 51,4 484,3 83,3 71,7 107,4

8,0 231,4 39,8 42,9 291,2 50,1 63,7 59,8 319,2 54,9 37,5 406,9 70,0 70,0 87,7 387,0 66,6 54,1 494,7 85,1 74,6 107,7

9,0 237,5 40,8 45,1 297,4 51,1 66,3 59,9 327,5 56,3 39,4 415,5 71,5 72,8 87,9 397,1 68,3 56,8 505,1 86,9 77,6 107,9

10,0 243,5 41,9 47,3 303,6 52,2 69,0 60,1 335,9 57,8 41,3 424,0 72,9 75,7 88,2 407,3 70,0 59,6 515,5 88,7 80,7 108,2

11,0 249,6 42,9 49,6 309,8 53,3 71,7 60,2 344,2 59,2 43,3 432,6 74,4 78,6 88,4 417,4 71,8 62,4 525,8 90,4 83,8 108,5

12,0 255,6 44,0 51,9 315,9 54,3 74,5 60,3 352,6 60,6 45,3 441,1 75,9 81,5 88,6 427,5 73,5 65,3 536,2 92,2 87,0 108,7

13,0 261,6 45,0 54,2 322,1 55,4 77,3 60,5 360,9 62,1 47,4 449,7 77,3 84,6 88,8 437,6 75,3 68,3 546,6 94,0 90,2 109,0

14,0 267,7 46,0 56,7 328,3 56,5 80,2 60,6 369,2 63,5 49,5 458,2 78,8 87,6 89,0 447,7 77,0 71,3 556,9 95,8 93,5 109,3

40,0

15,0 273,7 47,1 59,1 334,5 57,5 83,1 60,8 377,6 64,9 51,6 466,8 80,3 90,8 89,2 457,8 78,7 74,4 567,3 97,6 96,8 109,5

5,0 206,2 35,5 34,4 270,8 46,6 55,4 64,5 284,5 48,9 30,2 379,2 65,2 61,2 94,7 344,9 59,3 43,5 461,2 79,3 65,3 116,2

6,0 212,5 36,6 36,4 277,1 47,7 58,0 64,6 293,1 50,4 31,9 388,0 66,7 63,9 94,8 355,4 61,1 46,0 471,8 81,2 68,2 116,4

7,0 218,8 37,6 38,5 283,5 48,8 60,5 64,7 301,7 51,9 33,7 396,8 68,2 66,7 95,0 365,9 62,9 48,6 482,5 83,0 71,1 116,6

8,0 225,0 38,7 40,7 289,9 49,9 63,2 64,8 310,4 53,4 35,6 405,5 69,8 69,5 95,2 376,3 64,7 51,3 493,1 84,8 74,2 116,8

9,0 231,3 39,8 42,8 296,2 51,0 65,8 64,9 319,0 54,9 37,5 414,3 71,3 72,4 95,3 386,8 66,5 54,0 503,8 86,7 77,2 117,0

10,0 237,5 40,9 45,1 302,6 52,0 68,6 65,0 327,6 56,4 39,4 423,1 72,8 75,4 95,5 397,3 68,3 56,8 514,5 88,5 80,4 117,2

11,0 243,8 41,9 47,4 309,0 53,1 71,4 65,2 336,3 57,8 41,4 431,9 74,3 78,3 95,6 407,7 70,1 59,7 525,1 90,3 83,6 117,4

12,0 250,1 43,0 49,7 315,3 54,2 74,2 65,3 344,9 59,3 43,5 440,7 75,8 81,4 95,8 418,2 71,9 62,7 535,8 92,2 86,8 117,6

13,0 256,3 44,1 52,2 321,7 55,3 77,1 65,4 353,5 60,8 45,6 449,5 77,3 84,5 95,9 428,7 73,7 65,7 546,5 94,0 90,1 117,8

14,0 262,6 45,2 54,6 328,1 56,4 80,0 65,5 362,2 62,3 47,7 458,3 78,8 87,7 96,1 439,1 75,5 68,7 557,1 95,8 93,5 118,0

45,0

15,0 268,8 46,2 57,1 334,4 57,5 83,0 65,6 370,8 63,8 49,9 467,1 80,3 90,9 96,3 449,6 77,3 71,9 567,8 97,7 97,0 118,2

Where,CDOT: Condenser Water Outlet Temperature (°C)CLOT: Chilled Water Outlet Temperature (°C)CCAP: Cooling Capacity (kW)HCAP: Condenser Heat Rejection (Kw)

HFR: Condenser Water Flow Rate at 5°C (m3/h)HPD:Condenser Water Pressure Drop (kPa)CFR:Chilled Water Flow Rate at 5°C (m3/h)CPD: Water Cooler Pressure Drop (kPa)IPT: Compressor Input Power (kW)

Conversion Multiplier:1 kW = 860 kcal/h = 3412 Btu/h1 kPa = 0.102 mAq

Page 77: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MODEL SELECTION 15/73

Performance Table (R407C) (cont.)

RCUE 150 WG2 RCUE 180 WG2CDOT CLOT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD IPT

5,0 457,8 78,7 74,4 535,7 92,1 86,8 77,9 540,1 92,9 31,0 632,2 108,7 29,8 92,1

6,0 467,9 80,5 77,5 546,4 94,0 90,1 78,5 552,0 94,9 32,3 644,7 110,9 30,9 92,7

7,0 478,0 82,2 80,7 557,0 95,8 93,5 79,0 563,9 97,0 33,7 657,3 113,1 32,1 93,4

8,0 488,1 84,0 84,0 567,7 97,6 96,9 79,6 575,8 99,0 35,1 669,9 115,2 33,2 94,0

9,0 498,2 85,7 87,3 578,3 99,5 100,4 80,1 587,8 101,1 36,5 682,5 117,4 34,4 94,7

10,0 508,3 87,4 90,7 589,0 101,3 104,0 80,7 599,7 103,1 37,9 695,0 119,5 35,6 95,4

11,0 518,4 89,2 94,2 599,7 103,1 107,6 81,3 611,6 105,2 39,3 707,6 121,7 36,9 96,0

12,0 528,5 90,9 97,7 610,3 105,0 111,2 81,8 623,5 107,2 40,8 720,2 123,9 38,1 96,7

13,0 538,6 92,6 101,2 621,0 106,8 114,9 82,4 635,4 109,3 42,3 732,8 126,0 39,4 97,3

14,0 548,7 94,4 104,9 631,6 108,6 118,7 82,9 647,3 111,3 43,8 745,4 128,2 40,7 98,0

22,0

15,0 558,8 96,1 108,6 642,3 110,5 122,6 83,5 659,3 113,4 45,4 757,9 130,4 42,0 98,7

5,0 449,7 77,3 71,9 533,6 91,8 86,1 83,9 530,5 91,2 30,0 629,6 108,3 29,6 99,1

6,0 460,0 79,1 75,1 544,4 93,6 89,5 84,4 542,7 93,3 31,3 642,5 110,5 30,7 99,7

7,0 470,4 80,9 78,3 555,3 95,5 92,9 84,9 554,9 95,5 32,7 655,3 112,7 31,9 100,3

8,0 480,7 82,7 81,6 566,1 97,4 96,4 85,4 567,2 97,6 34,0 668,1 114,9 33,1 100,9

9,0 491,1 84,5 85,0 577,0 99,2 100,0 85,9 579,4 99,7 35,5 680,9 117,1 34,3 101,5

10,0 501,4 86,2 88,4 587,9 101,1 103,6 86,4 591,6 101,8 36,9 693,7 119,3 35,5 102,2

11,0 511,8 88,0 91,9 598,7 103,0 107,2 86,9 603,8 103,9 38,4 706,5 121,5 36,8 102,8

12,0 522,1 89,8 95,5 609,6 104,8 111,0 87,5 616,0 106,0 39,9 719,4 123,7 38,1 103,4

13,0 532,5 91,6 99,1 620,5 106,7 114,8 88,0 628,2 108,1 41,4 732,2 125,9 39,3 104,0

14,0 542,8 93,4 102,8 631,3 108,6 118,6 88,5 640,4 110,2 43,0 745,0 128,1 40,7 104,6

25,0

15,0 553,2 95,1 106,5 642,2 110,5 122,5 89,0 652,6 112,3 44,5 757,8 130,3 42,0 105,2

5,0 436,2 75,0 67,9 530,0 91,2 85,1 93,8 514,6 88,5 28,3 625,5 107,6 29,2 110,9

6,0 446,9 76,9 71,1 541,2 93,1 88,5 94,3 527,3 90,7 29,6 638,7 109,9 30,4 111,4

7,0 457,7 78,7 74,3 552,4 95,0 92,0 94,7 540,0 92,9 31,0 651,9 112,1 31,6 111,9

8,0 468,5 80,6 77,7 563,6 96,9 95,6 95,1 552,7 95,1 32,4 665,1 114,4 32,8 112,4

9,0 479,2 82,4 81,1 574,8 98,9 99,2 95,6 565,4 97,2 33,8 678,3 116,7 34,0 112,9

10,0 490,0 84,3 84,6 586,0 100,8 102,9 96,0 578,1 99,4 35,3 691,5 118,9 35,3 113,5

11,0 500,7 86,1 88,2 597,2 102,7 106,7 96,4 590,8 101,6 36,8 704,7 121,2 36,6 114,0

12,0 511,5 88,0 91,8 608,4 104,6 110,6 96,9 603,5 103,8 38,3 718,0 123,5 37,9 114,5

13,0 522,3 89,8 95,5 619,6 106,6 114,5 97,3 616,2 106,0 39,9 731,2 125,8 39,2 115,0

14,0 533,0 91,7 99,3 630,8 108,5 118,4 97,7 628,9 108,2 41,5 744,4 128,0 40,6 115,5

30,0

15,0 543,8 93,5 103,1 642,0 110,4 122,5 98,2 641,6 110,3 43,1 757,6 130,3 42,0 116,035,0 5,0 422,6 72,7 63,9 526,4 90,5 84,0 103,8 498,6 85,8 26,6 621,3 106,9 28,8 122,7

6,0 433,8 74,6 67,2 538,0 92,5 87,5 104,1 511,8 88,0 28,0 634,9 109,2 30,0 123,17,0 445,0 76,5 70,5 549,5 94,5 91,1 104,5 525,0 90,3 29,4 648,5 111,5 31,3 123,5

8,0 456,2 78,5 73,9 561,0 96,5 94,8 104,9 538,2 92,6 30,8 662,1 113,9 32,5 123,9

9,0 467,4 80,4 77,4 572,6 98,5 98,5 105,2 551,4 94,8 32,3 675,7 116,2 33,8 124,3

10,0 478,5 82,3 80,9 584,1 100,5 102,3 105,6 564,6 97,1 33,8 689,3 118,6 35,1 124,8

11,0 489,7 84,2 84,5 595,6 102,5 106,2 105,9 577,7 99,4 35,3 702,9 120,9 36,4 125,2

12,0 500,9 86,2 88,2 607,2 104,4 110,1 106,3 590,9 101,6 36,8 716,6 123,2 37,8 125,6

13,0 512,1 88,1 92,0 618,7 106,4 114,2 106,7 604,1 103,9 38,4 730,2 125,6 39,1 126,0

14,0 523,2 90,0 95,8 630,3 108,4 118,2 107,0 617,3 106,2 40,0 743,8 127,9 40,5 126,5

15,0 534,4 91,9 99,8 641,8 110,4 122,4 107,4 630,5 108,4 41,7 757,4 130,3 42,0 126,9

5,0 417,2 71,8 62,4 525,0 90,3 83,5 107,8 492,2 84,7 26,0 619,6 106,6 28,7 127,4

6,0 428,6 73,7 65,6 536,7 92,3 87,1 108,1 505,6 87,0 27,3 633,4 108,9 29,9 127,7

7,0 439,9 75,7 69,0 548,3 94,3 90,7 108,4 519,0 89,3 28,7 647,1 111,3 31,1 128,1

8,0 451,3 77,6 72,4 560,0 96,3 94,4 108,7 532,4 91,6 30,2 660,9 113,7 32,4 128,5

9,0 462,6 79,6 75,9 571,7 98,3 98,2 109,1 545,8 93,9 31,6 674,7 116,0 33,7 128,9

10,0 474,0 81,5 79,4 583,4 100,3 102,1 109,4 559,2 96,2 33,1 688,5 118,4 35,0 129,3

11,0 485,3 83,5 83,1 595,0 102,3 106,0 109,7 572,5 98,5 34,7 702,2 120,8 36,3 129,7

12,0 496,6 85,4 86,8 606,7 104,4 110,0 110,1 585,9 100,8 36,2 716,0 123,2 37,7 130,1

13,0 508,0 87,4 90,6 618,4 106,4 114,0 110,4 599,3 103,1 37,8 729,8 125,5 39,1 130,5

14,0 519,3 89,3 94,5 630,0 108,4 118,2 110,7 612,7 105,4 39,5 743,5 127,9 40,5 130,8

37,0

15,0 530,7 91,3 98,4 641,7 110,4 122,4 111,0 626,1 107,7 41,1 757,3 130,3 41,9 131,2

5,0 409,1 70,4 60,1 522,9 89,9 82,9 113,7 458,3 78,8 22,6 592,7 101,9 26,4 134,4

6,0 420,7 72,4 63,4 534,7 92,0 86,5 114,0 474,9 81,7 24,3 609,7 104,9 27,8 134,7

7,0 432,3 74,4 66,7 546,6 94,0 90,2 114,3 491,6 84,6 25,9 626,7 107,8 29,3 135,1

8,0 443,9 76,4 70,2 558,5 96,1 94,0 114,6 508,2 87,4 27,6 643,7 110,7 30,8 135,4

9,0 455,5 78,3 73,7 570,4 98,1 97,8 114,9 524,9 90,3 29,4 660,7 113,6 32,4 135,7

10,0 467,1 80,3 77,3 582,2 100,1 101,7 115,1 541,6 93,1 31,2 677,6 116,6 34,0 136,1

11,0 478,7 82,3 80,9 594,1 102,2 105,7 115,4 558,2 96,0 33,0 694,6 119,5 35,6 136,4

12,0 490,3 84,3 84,7 606,0 104,2 109,7 115,7 574,9 98,9 34,9 711,6 122,4 37,3 136,7

13,0 501,9 86,3 88,5 617,9 106,3 113,8 116,0 591,5 101,7 36,9 728,6 125,3 39,0 137,1

14,0 513,5 88,3 92,5 629,7 108,3 118,0 116,3 608,2 104,6 38,9 745,6 128,2 40,7 137,4

40,0

15,0 525,0 90,3 96,5 641,6 110,4 122,3 116,6 624,8 107,5 41,0 762,6 131,2 42,5 137,7

5,0 395,6 68,0 56,4 519,3 89,3 81,8 123,7 466,7 80,3 23,5 612,9 105,4 28,1 146,2

6,0 407,6 70,1 59,7 531,5 91,4 85,5 123,9 480,9 82,7 24,8 627,3 107,9 29,3 146,4

7,0 419,6 72,2 63,1 543,7 93,5 89,3 124,1 495,1 85,1 26,3 641,7 110,4 30,6 146,7

8,0 431,6 74,2 66,5 555,9 95,6 93,1 124,3 509,2 87,6 27,7 656,1 112,9 32,0 146,9

9,0 443,6 76,3 70,1 568,1 97,7 97,1 124,5 523,4 90,0 29,2 670,5 115,3 33,3 147,1

10,0 455,6 78,4 73,7 580,4 99,8 101,1 124,7 537,5 92,5 30,7 684,9 117,8 34,7 147,4

11,0 467,6 80,4 77,4 592,6 101,9 105,2 124,9 551,7 94,9 32,3 699,3 120,3 36,1 147,6

12,0 479,6 82,5 81,3 604,8 104,0 109,3 125,1 565,9 97,3 33,9 713,8 122,8 37,5 147,9

13,0 491,7 84,6 85,2 617,0 106,1 113,5 125,3 580,0 99,8 35,5 728,2 125,2 38,9 148,1

14,0 503,7 86,6 89,1 629,2 108,2 117,9 125,5 594,2 102,2 37,2 742,6 127,7 40,4 148,4

45,0

15,0 515,7 88,7 93,2 641,4 110,3 122,2 125,7 608,4 104,6 38,9 757,0 130,2 41,9 148,6

Where,CDOT: Condenser Water Outlet Temperature (°C)CLOT: Chilled Water Outlet Temperature (°C)CCAP: Cooling Capacity (kW)HCAP: Condenser Heat Rejection (Kw)

HFR: Condenser Water Flow Rate at 5°C (m3/h)HPD:Condenser Water Pressure Drop (kPa)CFR:Chilled Water Flow Rate at 5°C (m3/h)CPD: Water Cooler Pressure Drop (kPa)IPT: Compressor Input Power (kW)

Conversion Multiplier:1 kW = 860 kcal/h = 3412 Btu/h1 kPa = 0.102 mAq

Page 78: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

15/74 MODEL SELECTION

Performance Table (cont.)

RCUE 200 WG2 RCUE 240 WG2CDOT CLOT CCAP CFR CPD HCAP HFR HPD IPT CCAP CFR CPD HCAP HFR HPD IPT

5,0 617,2 106,2 40,0 728,0 125,2 38,9 110,7 716,0 123,2 45,5 837,9 144,1 58,8 121,9

6,0 630,9 108,5 41,7 742,4 127,7 40,4 111,5 731,8 125,9 47,4 854,6 147,0 61,1 122,8

7,0 644,5 110,9 43,5 756,8 130,2 41,9 112,3 747,6 128,6 49,4 871,2 149,9 63,4 123,6

8,0 658,1 113,2 45,2 771,2 132,6 43,4 113,1 763,4 131,3 51,4 887,9 152,7 65,7 124,5

9,0 671,7 115,5 47,1 785,6 135,1 45,0 113,9 779,2 134,0 53,5 904,6 155,6 68,1 125,4

10,0 685,3 117,9 48,9 800,0 137,6 46,6 114,7 795,0 136,7 55,6 921,3 158,5 70,5 126,3

11,0 699,0 120,2 50,8 814,4 140,1 48,2 115,5 810,8 139,5 57,7 937,9 161,3 73,0 127,1

12,0 712,6 122,6 52,7 828,8 142,6 49,8 116,3 826,6 142,2 59,9 954,6 164,2 75,5 128,0

13,0 726,2 124,9 54,6 843,3 145,0 51,4 117,1 842,4 144,9 62,1 971,3 167,1 78,0 128,9

14,0 739,8 127,3 56,6 857,7 147,5 53,1 117,8 858,2 147,6 64,3 987,9 169,9 80,6 129,7

22,0

15,0 753,4 129,6 58,6 872,1 150,0 54,8 118,6 874,0 150,3 66,6 1004,6 172,8 83,2 130,6

5,0 606,3 104,3 38,7 725,5 124,8 38,7 119,2 703,3 121,0 44,0 834,6 143,5 58,4 131,2

6,0 620,3 106,7 40,4 740,2 127,3 40,2 119,9 719,5 123,8 45,9 851,5 146,5 60,7 132,0

7,0 634,2 109,1 42,2 754,9 129,8 41,7 120,6 735,7 126,5 47,9 868,5 149,4 63,0 132,8

8,0 648,2 111,5 44,0 769,6 132,4 43,2 121,4 751,9 129,3 50,0 885,5 152,3 65,4 133,6

9,0 662,1 113,9 45,8 784,2 134,9 44,8 122,1 768,1 132,1 52,0 902,5 155,2 67,8 134,4

10,0 676,1 116,3 47,6 798,9 137,4 46,4 122,8 784,3 134,9 54,2 919,5 158,2 70,3 135,2

11,0 690,0 118,7 49,5 813,6 139,9 48,1 123,6 800,4 137,7 56,3 936,5 161,1 72,8 136,0

12,0 704,0 121,1 51,5 828,3 142,5 49,7 124,3 816,6 140,5 58,5 953,5 164,0 75,3 136,8

13,0 718,0 123,5 53,4 843,0 145,0 51,4 125,0 832,8 143,2 60,8 970,5 166,9 77,9 137,6

14,0 731,9 125,9 55,4 857,6 147,5 53,1 125,7 849,0 146,0 63,0 987,5 169,8 80,5 138,4

25,0

15,0 745,9 128,3 57,5 872,3 150,0 54,9 126,5 865,2 148,8 65,3 1004,4 172,8 83,2 139,2

5,0 588,1 101,2 36,5 721,4 124,1 38,3 133,3 682,2 117,3 41,5 829,0 142,6 57,6 146,8

6,0 602,6 103,6 38,2 736,6 126,7 39,8 134,0 699,0 120,2 43,5 846,5 145,6 60,0 147,5

7,0 617,1 106,1 40,0 751,7 129,3 41,4 134,6 715,8 123,1 45,5 864,0 148,6 62,4 148,2

8,0 631,6 108,6 41,8 766,8 131,9 43,0 135,2 732,7 126,0 47,6 881,5 151,6 64,8 148,8

9,0 646,1 111,1 43,7 781,9 134,5 44,6 135,8 749,5 128,9 49,7 899,0 154,6 67,3 149,5

10,0 660,6 113,6 45,6 797,1 137,1 46,2 136,4 766,4 131,8 51,8 916,6 157,6 69,8 150,2

11,0 675,2 116,1 47,5 812,2 139,7 47,9 137,0 783,2 134,7 54,0 934,1 160,7 72,4 150,9

12,0 689,7 118,6 49,5 827,3 142,3 49,6 137,7 800,0 137,6 56,3 951,6 163,7 75,0 151,6

13,0 704,2 121,1 51,5 842,5 144,9 51,3 138,3 816,9 140,5 58,5 969,1 166,7 77,7 152,3

14,0 718,7 123,6 53,6 857,6 147,5 53,1 138,9 833,7 143,4 60,9 986,6 169,7 80,4 152,9

30,0

15,0 733,2 126,1 55,6 872,7 150,1 54,9 139,5 850,5 146,3 63,2 1004,1 172,7 83,2 153,635,0 5,0 569,9 98,0 34,4 717,3 123,4 37,8 147,5 661,0 113,7 39,1 823,4 141,6 56,9 162,4

6,0 584,9 100,6 36,1 732,9 126,1 39,4 148,0 678,5 116,7 41,1 841,5 144,7 59,3 162,97,0 600,0 103,2 37,9 748,5 128,7 41,0 148,5 696,0 119,7 43,1 859,5 147,8 61,8 163,5

8,0 615,1 105,8 39,8 764,1 131,4 42,7 149,0 713,5 122,7 45,2 877,5 150,9 64,3 164,1

9,0 630,1 108,4 41,6 779,7 134,1 44,3 149,5 731,0 125,7 47,3 895,6 154,0 66,8 164,6

10,0 645,2 111,0 43,6 795,2 136,8 46,0 150,0 748,4 128,7 49,5 913,6 157,1 69,4 165,2

11,0 660,3 113,6 45,5 810,8 139,5 47,7 150,5 765,9 131,7 51,8 931,7 160,2 72,1 165,7

12,0 675,4 116,2 47,5 826,4 142,1 49,5 151,0 783,4 134,7 54,0 949,7 163,4 74,8 166,3

13,0 690,4 118,8 49,6 842,0 144,8 51,3 151,6 800,9 137,8 56,4 967,8 166,5 77,5 166,9

14,0 705,5 121,3 51,7 857,6 147,5 53,1 152,1 818,4 140,8 58,8 985,8 169,6 80,3 167,4

15,0 720,6 123,9 53,8 873,1 150,2 55,0 152,6 835,9 143,8 61,2 1003,9 172,7 83,1 168,0

5,0 562,6 96,8 33,5 715,7 123,1 37,7 153,1 652,6 112,2 38,1 821,2 141,2 56,6 168,6

6,0 577,9 99,4 35,3 731,5 125,8 39,3 153,6 670,3 115,3 40,1 839,4 144,4 59,0 169,1

7,0 593,2 102,0 37,1 747,2 128,5 40,9 154,1 688,1 118,3 42,2 857,7 147,5 61,5 169,6

8,0 608,5 104,7 38,9 763,0 131,2 42,5 154,5 705,8 121,4 44,3 875,9 150,7 64,0 170,1

9,0 623,7 107,3 40,8 778,7 133,9 44,2 155,0 723,5 124,4 46,4 894,2 153,8 66,6 170,7

10,0 639,0 109,9 42,8 794,5 136,7 45,9 155,5 741,3 127,5 48,6 912,5 156,9 69,2 171,2

11,0 654,3 112,5 44,8 810,3 139,4 47,7 155,9 759,0 130,6 50,9 930,7 160,1 71,9 171,7

12,0 669,6 115,2 46,8 826,0 142,1 49,5 156,4 776,8 133,6 53,2 949,0 163,2 74,6 172,2

13,0 684,9 117,8 48,8 841,8 144,8 51,3 156,9 794,5 136,7 55,5 967,2 166,4 77,4 172,7

14,0 700,2 120,4 50,9 857,6 147,5 53,1 157,3 812,3 139,7 57,9 985,5 169,5 80,2 173,2

37,0

15,0 715,5 123,1 53,1 873,3 150,2 55,0 157,8 830,0 142,8 60,4 1003,7 172,6 83,1 173,7

5,0 551,6 94,9 32,3 713,3 122,7 37,4 161,6 639,9 110,1 36,7 817,8 140,7 56,2 177,96,0 567,3 97,6 34,1 729,3 125,4 39,1 162,0 658,0 113,2 38,7 836,4 143,9 58,6 178,47,0 582,9 100,3 35,9 745,3 128,2 40,7 162,4 676,2 116,3 40,8 855,0 147,1 61,1 178,8

8,0 598,5 102,9 37,7 761,3 131,0 42,4 162,8 694,3 119,4 42,9 873,6 150,3 63,7 179,3

9,0 614,1 105,6 39,6 777,4 133,7 44,1 163,2 712,4 122,5 45,1 892,1 153,4 66,3 179,7

10,0 629,8 108,3 41,6 793,4 136,5 45,8 163,6 730,5 125,7 47,3 910,7 156,6 69,0 180,2

11,0 645,4 111,0 43,6 809,4 139,2 47,6 164,0 748,7 128,8 49,6 929,3 159,8 71,7 180,6

12,0 661,0 113,7 45,6 825,5 142,0 49,4 164,4 766,8 131,9 51,9 947,8 163,0 74,5 181,0

13,0 676,7 116,4 47,7 841,5 144,7 51,2 164,8 784,9 135,0 54,2 966,4 166,2 77,3 181,5

14,0 692,3 119,1 49,9 857,5 147,5 53,1 165,2 803,1 138,1 56,7 985,0 169,4 80,2 181,9

40,0

15,0 707,9 121,8 52,0 873,6 150,3 55,0 165,6 821,2 141,2 59,1 1003,6 172,6 83,1 182,4

5,0 533,4 91,7 30,3 709,2 122,0 37,0 175,8 618,7 106,4 34,4 812,3 139,7 55,4 193,5

6,0 549,6 94,5 32,1 725,7 124,8 38,7 176,1 637,5 109,7 36,4 831,4 143,0 58,0 193,8

7,0 565,8 97,3 33,9 742,1 127,6 40,4 176,4 656,3 112,9 38,5 850,5 146,3 60,5 194,2

8,0 582,0 100,1 35,8 758,6 130,5 42,1 176,6 675,1 116,1 40,7 869,6 149,6 63,2 194,5

9,0 598,2 102,9 37,7 775,1 133,3 43,8 176,9 693,9 119,3 42,8 888,7 152,9 65,8 194,8

10,0 614,3 105,7 39,7 791,6 136,1 45,6 177,2 712,6 122,6 45,1 907,8 156,1 68,6 195,1

11,0 630,5 108,5 41,7 808,0 139,0 47,4 177,5 731,4 125,8 47,4 926,9 159,4 71,4 195,5

12,0 646,7 111,2 43,8 824,5 141,8 49,3 177,8 750,2 129,0 49,7 946,0 162,7 74,2 195,8

13,0 662,9 114,0 45,9 841,0 144,7 51,2 178,1 769,0 132,3 52,2 965,1 166,0 77,1 196,1

14,0 679,1 116,8 48,0 857,5 147,5 53,1 178,4 787,7 135,5 54,6 984,2 169,3 80,0 196,4

45,0

15,0 695,3 119,6 50,3 874,0 150,3 55,0 178,7 806,5 138,7 57,1 1003,3 172,6 83,0 196,7

Where,CDOT: Condenser Water Outlet Temperature (°C)CLOT: Chilled Water Outlet Temperature (°C)CCAP: Cooling Capacity (kW)HCAP: Condenser Heat Rejection (Kw)

HFR: Condenser Water Flow Rate at 5°C (m3/h)HPD:Condenser Water Pressure Drop (kPa)CFR:Chilled Water Flow Rate at 5°C (m3/h)CPD: Water Cooler Pressure Drop (kPa)IPT: Compressor Input Power (kW)

Conversion Multiplier:1 kW = 860 kcal/h = 3412 Btu/h1 kPa = 0.102 mAq

Page 79: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MODEL SELECTION 15/75

Performance Table (Heating Operation, Only for Heat Pump Operation Option)

RCUE40WG2 RCUE50WG2 RCUE60WG2

CLOT HOT HCAP HFR HPD CCAP CFR CPD IPT HCAP HFR HPD CCAP CFR CPD IPT HCAP HFR HPD CCAP CFR CPD IPT

5,0 25,0 162,3 27,9 35,0 135,4 23,3 31,4 26,9 193,8 33,3 35,2 161,7 27,8 37,4 32,1 235,5 40,5 36,8 196,0 33,7 36,5 39,4

30,0 161,4 27,8 34,6 131,3 22,6 29,7 30,1 192,7 33,2 34,8 156,8 27,0 35,3 35,9 234,2 40,3 36,4 190,1 32,7 34,4 44,1

35,0 160,5 27,6 34,2 127,3 21,9 27,9 33,3 191,7 33,0 34,5 152,0 26,1 33,3 39,7 233,0 40,1 36,0 184,3 31,7 32,4 48,8

40,0 157,2 27,0 32,9 120,7 20,8 25,3 36,5 187,7 32,3 33,1 144,2 24,8 30,1 43,5 228,2 39,3 34,6 174,8 30,1 29,3 53,4

45,0 154,0 26,5 31,7 114,4 19,7 22,8 39,7 183,9 31,6 31,9 136,6 23,5 27,1 47,3 223,7 38,5 33,3 165,6 28,5 26,4 58,1

50,0 151,0 26,0 30,5 108,2 18,6 20,5 42,8 180,3 31,0 30,7 129,1 22,2 24,4 51,2 219,4 37,7 32,1 156,6 26,9 23,7 62,8

55,0 148,1 25,5 29,5 102,1 17,6 18,3 46,0 176,9 30,4 29,6 121,9 21,0 21,8 55,0 215,3 37,0 31,0 147,8 25,4 21,3 67,5

7,0 25,0 168,9 29,0 37,6 141,6 24,4 34,3 27,2 201,6 34,7 37,9 169,1 29,1 40,8 32,5 245,0 42,1 39,6 205,1 35,3 39,8 39,9

30,0 168,2 28,9 37,4 137,8 23,7 32,5 30,4 200,8 34,5 37,6 164,6 28,3 38,7 36,2 244,0 42,0 39,3 199,5 34,3 37,7 44,5

35,0 167,5 28,8 37,1 134,0 23,0 30,8 33,5 200,0 34,4 37,3 160,0 27,5 36,7 40,0 243,1 41,8 39,1 194,0 33,4 35,8 49,1

40,0 164,2 28,2 35,7 127,6 21,9 28,1 36,6 196,1 33,7 36,0 152,3 26,2 33,4 43,8 238,4 41,0 37,6 184,7 31,8 32,6 53,7

45,0 161,1 27,7 34,5 121,3 20,9 25,5 39,8 192,3 33,1 34,7 144,8 24,9 30,3 47,5 233,9 40,2 36,3 175,6 30,2 29,6 58,3

50,0 158,1 27,2 33,3 115,2 19,8 23,1 42,9 188,8 32,5 33,5 137,5 23,7 27,5 51,3 229,7 39,5 35,1 166,8 28,7 26,8 62,9

55,0 155,3 26,7 32,2 109,2 18,8 20,8 46,1 185,4 31,9 32,4 130,4 22,4 24,8 55,0 225,6 38,8 33,9 158,1 27,2 24,2 67,5

10,0 25,0 178,7 30,7 41,9 151,0 26,0 38,7 27,7 213,4 36,7 42,2 180,3 31,0 46,1 33,1 259,2 44,6 44,1 218,6 37,6 44,9 40,6

30,0 178,3 30,7 41,7 147,5 25,4 37,1 30,8 212,9 36,6 42,0 176,2 30,3 44,1 36,7 258,7 44,5 44,0 213,6 36,7 43,0 45,1

35,0 177,9 30,6 41,5 144,1 24,8 35,4 33,8 212,5 36,5 41,8 172,1 29,6 42,2 40,4 258,2 44,4 43,8 208,6 35,9 41,1 49,6

40,0 174,8 30,1 40,1 137,8 23,7 32,5 36,9 208,7 35,9 40,4 164,6 28,3 38,7 44,1 253,7 43,6 42,3 199,6 34,3 37,8 54,1

45,0 171,7 29,5 38,8 131,7 22,7 29,8 40,0 205,0 35,3 39,1 157,3 27,1 35,5 47,7 249,3 42,9 41,0 190,7 32,8 34,6 58,6

50,0 168,8 29,0 37,6 125,7 21,6 27,3 43,0 201,5 34,7 37,9 150,1 25,8 32,5 51,4 245,1 42,2 39,7 182,0 31,3 31,7 63,1

55,0 166,0 28,6 36,5 119,9 20,6 24,9 46,1 198,2 34,1 36,7 143,1 24,6 29,7 55,1 241,2 41,5 38,5 173,6 29,9 28,9 67,6

15,0 25,0 195,1 33,6 49,3 166,6 28,7 46,7 28,5 233,0 40,1 49,7 198,9 34,2 55,6 34,1 283,0 48,7 52,1 241,2 41,5 54,2 41,8

30,0 195,2 33,6 49,4 163,8 28,2 45,2 31,5 233,1 40,1 49,8 195,5 33,6 53,8 37,6 283,2 48,7 52,2 237,1 40,8 52,5 46,1

35,0 195,3 33,6 49,4 160,9 27,7 43,7 34,4 233,3 40,1 49,9 192,2 33,1 52,1 41,1 283,4 48,8 52,3 233,0 40,1 50,8 50,4

40,0 192,3 33,1 48,0 154,9 26,6 40,7 37,4 229,6 39,5 48,4 185,0 31,8 48,4 44,6 279,1 48,0 50,7 224,3 38,6 47,2 54,8

45,0 189,4 32,6 46,7 149,1 25,6 37,8 40,3 226,1 38,9 47,0 178,0 30,6 45,0 48,1 274,9 47,3 49,3 215,8 37,1 43,9 59,1

50,0 186,6 32,1 45,4 143,3 24,6 35,0 43,3 222,8 38,3 45,7 171,1 29,4 41,7 51,6 270,9 46,6 48,0 207,5 35,7 40,7 63,4

55,0 183,9 31,6 44,1 137,7 23,7 32,5 46,2 219,5 37,8 44,5 164,4 28,3 38,6 55,2 267,0 45,9 46,7 199,3 34,3 37,7 67,7

RCUE80WG2 RCUE100WG2 RCUE120WG2

CLOT HOT HCAP HFR HPD CCAP CFR CPD IPT HCAP HFR HPD CCAP CFR CPD IPT HCAP HFR HPD CCAP CFR CPD IPT

5,0 25,0 278,2 47,8 58,4 234,4 40,3 44,0 43,7 387,6 66,7 63,8 323,4 55,6 38,5 64,2 470,9 81,0 67,9 392,1 67,4 55,4 78,8

30,0 276,3 47,5 57,6 227,4 39,1 41,5 48,9 385,5 66,3 63,2 313,6 53,9 36,3 71,8 468,5 80,6 67,3 380,3 65,4 52,3 88,2

35,0 274,5 47,2 56,9 220,3 37,9 39,1 54,1 383,4 65,9 62,5 303,9 52,3 34,2 79,5 466,0 80,2 66,6 368,5 63,4 49,3 97,5

40,0 268,3 46,2 54,5 209,0 36,0 35,3 59,3 375,4 64,6 60,1 288,3 49,6 30,9 87,1 456,5 78,5 64,0 349,6 60,1 44,6 106,9

45,0 262,5 45,2 52,3 198,0 34,1 31,8 64,5 367,8 63,3 57,8 273,1 47,0 27,9 94,7 447,4 76,9 61,6 331,1 57,0 40,2 116,2

50,0 256,9 44,2 50,2 187,3 32,2 28,6 69,7 360,6 62,0 55,7 258,3 44,4 25,1 102,3 438,7 75,5 59,4 313,2 53,9 36,2 125,6

55,0 251,7 43,3 48,2 176,8 30,4 25,6 74,9 353,8 60,8 53,7 243,8 41,9 22,5 109,9 430,6 74,1 57,3 295,7 50,9 32,4 134,9

7,0 25,0 289,5 49,8 63,0 245,2 42,2 47,9 44,3 403,2 69,4 68,8 338,3 58,2 41,9 65,0 489,9 84,3 73,2 410,1 70,5 60,4 79,8

30,0 288,0 49,5 62,4 238,6 41,0 45,5 49,4 401,6 69,1 68,3 329,1 56,6 39,8 72,5 488,1 83,9 72,7 399,1 68,6 57,3 89,0

35,0 286,5 49,3 61,8 232,0 39,9 43,1 54,5 400,0 68,8 67,8 320,0 55,0 37,7 80,0 486,2 83,6 72,2 388,0 66,7 54,3 98,2

40,0 280,5 48,2 59,3 220,9 38,0 39,2 59,6 392,2 67,5 65,3 304,7 52,4 34,3 87,5 476,8 82,0 69,6 369,4 63,5 49,5 107,4

45,0 274,7 47,3 57,0 210,0 36,1 35,6 64,7 384,7 66,2 62,9 289,7 49,8 31,2 95,0 467,9 80,5 67,1 351,2 60,4 45,0 116,6

50,0 269,3 46,3 54,9 199,4 34,3 32,3 69,8 377,6 64,9 60,7 275,1 47,3 28,3 102,5 459,3 79,0 64,8 333,5 57,4 40,8 125,8

55,0 264,0 45,4 52,8 189,1 32,5 29,2 74,9 370,8 63,8 58,7 260,8 44,9 25,6 110,0 451,3 77,6 62,7 316,2 54,4 36,9 135,0

10,0 25,0 306,5 52,7 70,3 261,4 45,0 54,2 45,1 426,8 73,4 76,6 360,6 62,0 47,3 66,2 518,4 89,2 81,6 437,2 75,2 68,2 81,2

30,0 305,5 52,5 69,8 255,5 43,9 51,8 50,1 425,8 73,2 76,3 352,3 60,6 45,3 73,5 517,4 89,0 81,3 427,2 73,5 65,2 90,2

35,0 304,5 52,4 69,4 249,5 42,9 49,5 55,1 424,9 73,1 76,0 344,1 59,2 43,3 80,8 516,4 88,8 81,0 417,2 71,8 62,4 99,2

40,0 298,7 51,4 66,9 238,6 41,0 45,5 60,1 417,3 71,8 73,4 329,2 56,6 39,8 88,2 507,3 87,3 78,3 399,1 68,6 57,3 108,2

45,0 293,1 50,4 64,5 228,0 39,2 41,7 65,0 410,0 70,5 71,0 314,5 54,1 36,5 95,5 498,6 85,8 75,7 381,4 65,6 52,6 117,2

50,0 287,7 49,5 62,3 217,7 37,4 38,2 70,0 403,1 69,3 68,7 300,3 51,6 33,4 102,8 490,2 84,3 73,3 364,1 62,6 48,2 126,2

55,0 282,6 48,6 60,2 207,6 35,7 34,8 75,0 396,4 68,2 66,6 286,3 49,2 30,5 110,1 482,3 83,0 71,1 347,1 59,7 44,0 135,2

15,0 25,0 334,8 57,6 83,2 288,4 49,6 65,3 46,4 465,9 80,1 90,4 397,8 68,4 57,0 68,1 566,0 97,3 96,4 482,3 83,0 82,1 83,6

30,0 334,7 57,6 83,2 283,5 48,8 63,2 51,2 466,2 80,2 90,5 391,0 67,3 55,2 75,2 566,4 97,4 96,5 474,1 81,6 79,5 92,3

35,0 334,6 57,6 83,1 278,6 47,9 61,2 56,0 466,5 80,2 90,6 384,3 66,1 53,4 82,2 566,9 97,5 96,7 466,0 80,1 76,9 100,9

40,0 329,0 56,6 80,5 268,3 46,1 56,9 60,8 459,2 79,0 88,0 370,0 63,6 49,7 89,2 558,2 96,0 93,9 448,6 77,2 71,6 109,5

45,0 323,7 55,7 78,0 258,1 44,4 52,8 65,6 452,2 77,8 85,5 356,0 61,2 46,2 96,3 549,8 94,6 91,2 431,6 74,2 66,5 118,2

50,0 318,5 54,8 75,6 248,1 42,7 49,0 70,4 445,5 76,6 83,1 342,2 58,9 42,8 103,3 541,7 93,2 88,7 414,9 71,4 61,7 126,8

55,0 313,5 53,9 73,4 238,3 41,0 45,4 75,2 439,1 75,5 80,8 328,7 56,5 39,7 110,3 534,0 91,9 86,3 398,6 68,6 57,2 135,4

Where,CLOT: Chilled Water Outlet Temperature (°C)HOT: Hot Water Outlet Temperature (°C)HCAP: Heating Capacity (kW)CCAP: Cooling Capacity (kW)

HFR: Condenser Water Flow Rate at 5°C (m3/h)HPD:Condenser Water Pressure Drop (kPa)CFR:Chilled Water Flow Rate at 5°C (m3/h)CPD:Water Cooler Pressure Drop (kPa)IPT:Compressor Input Power (kW)

Conversion Multiplier:1 kW = 860 kcal/h = 3412 Btu/h1 kPa = 0.102 mAq

Page 80: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

15/76 MODEL SELECTION

Performance Table (Heating Operation, Only for Heat Pump Operation Option)

RCUE150WG2 RCUE180WG2

CLOT HOT HCAP HFR HPD CCAP CFR CPD IPT HCAP HFR HPD CCAP CFR CPD IPT

5,0 25,0 533,6 91,8 86,1 449,7 77,3 71,9 83,9 629,6 108,3 29,6 530,5 91,2 30,0 99,1

30,0 530,0 91,2 85,1 436,2 75,0 67,9 93,8 625,5 107,6 29,2 514,6 88,5 28,3 110,9

35,0 526,4 90,5 84,0 422,6 72,7 63,9 103,8 621,3 106,9 28,8 498,6 85,8 26,6 122,7

40,0 514,7 88,5 80,4 400,9 69,0 57,8 113,7 607,4 104,5 27,6 473,0 81,4 24,1 134,4

45,0 503,5 86,6 77,1 379,8 65,3 52,2 123,7 594,2 102,2 26,5 448,1 77,1 21,7 146,2

50,0 492,8 84,8 74,1 359,2 61,8 46,9 133,6 581,7 100,0 25,4 423,7 72,9 19,5 157,9

55,0 482,7 83,0 71,2 339,1 58,3 42,1 143,6 569,7 98,0 24,4 400,0 68,8 17,5 169,7

7,0 25,0 555,3 95,5 92,9 470,4 80,9 78,3 84,9 655,3 112,7 31,9 554,9 95,5 32,7 100,3

30,0 552,4 95,0 92,0 457,7 78,7 74,3 94,7 651,9 112,1 31,6 540,0 92,9 31,0 111,9

35,0 549,5 94,5 91,1 445,0 76,5 70,5 104,5 648,5 111,5 31,3 525,0 90,3 29,4 123,5

40,0 538,0 92,5 87,5 423,7 72,9 64,2 114,3 634,9 109,2 30,0 499,8 86,0 26,7 135,1

45,0 526,9 90,6 84,1 402,8 69,3 58,4 124,1 621,9 107,0 28,9 475,3 81,7 24,3 146,7

50,0 516,4 88,8 81,0 382,5 65,8 52,9 133,9 609,5 104,8 27,8 451,3 77,6 22,0 158,2

55,0 506,4 87,1 78,0 362,7 62,4 47,8 143,7 597,7 102,8 26,8 427,9 73,6 19,9 169,8

10,0 25,0 587,9 101,1 103,6 501,4 86,2 88,4 86,4 693,7 119,3 35,5 591,6 101,8 36,9 102,2

30,0 586,0 100,8 102,9 490,0 84,3 84,6 96,0 691,5 118,9 35,3 578,1 99,4 35,3 113,5

35,0 584,1 100,5 102,3 478,5 82,3 80,9 105,6 689,3 118,6 35,1 564,6 97,1 33,8 124,8

40,0 572,9 98,5 98,6 457,7 78,7 74,4 115,1 676,1 116,3 33,8 540,0 92,9 31,0 136,1

45,0 562,1 96,7 95,1 437,4 75,2 68,2 124,7 663,4 114,1 32,6 516,0 88,8 28,4 147,4

50,0 551,8 94,9 91,8 417,5 71,8 62,5 134,3 651,3 112,0 31,5 492,6 84,7 26,0 158,7

55,0 542,0 93,2 88,7 398,1 68,5 57,1 143,9 639,7 110,0 30,5 469,7 80,8 23,7 170,0

15,0 25,0 642,2 110,5 122,5 553,2 95,1 106,5 89,0 757,8 130,3 42,0 652,6 112,3 44,5 105,2

30,0 642,0 110,4 122,5 543,8 93,5 103,1 98,2 757,6 130,3 42,0 641,6 110,3 43,1 116,0

35,0 641,8 110,4 122,4 534,4 91,9 99,8 107,4 757,4 130,3 42,0 630,5 108,4 41,7 126,9

40,0 631,1 108,5 118,5 514,5 88,5 92,8 116,6 744,8 128,1 40,6 607,0 104,4 38,8 137,7

45,0 620,8 106,8 114,9 495,0 85,1 86,3 125,7 732,6 126,0 39,4 584,0 100,5 36,0 148,6

50,0 610,8 105,1 111,4 475,9 81,9 80,1 134,9 720,9 124,0 38,2 561,5 96,6 33,4 159,5

55,0 601,3 103,4 108,1 457,2 78,6 74,2 144,1 709,7 122,1 37,1 539,3 92,8 30,9 170,3

RCUE200WG2 RCUE240WG2

CLOT HOT HCAP HFR HPD CCAP CFR CPD IPT HCAP HFR HPD CCAP CFR CPD IPT

5,0 25,0 725,5 124,8 38,7 606,3 104,3 38,7 119,2 834,6 143,5 58,4 703,3 121,0 44,0 131,2

30,0 721,4 124,1 38,3 588,1 101,2 36,5 133,3 829,0 142,6 57,6 682,2 117,3 41,5 146,8

35,0 717,3 123,4 37,8 569,9 98,0 34,4 147,5 823,4 141,6 56,9 661,0 113,7 39,1 162,4

40,0 702,2 120,8 36,3 540,6 93,0 31,1 161,6 805,0 138,5 54,5 627,1 107,9 35,3 177,9

45,0 687,8 118,3 34,9 512,1 88,1 28,0 175,8 787,5 135,5 52,3 594,0 102,2 31,8 193,5

50,0 674,2 116,0 33,6 484,3 83,3 25,2 189,9 770,8 132,6 50,2 561,8 96,6 28,6 209,1

55,0 661,3 113,7 32,4 457,2 78,6 22,5 204,1 755,0 129,9 48,2 530,3 91,2 25,6 224,7

7,0 25,0 754,9 129,8 41,7 634,2 109,1 42,2 120,6 868,5 149,4 63,0 735,7 126,5 47,9 132,8

30,0 751,7 129,3 41,4 617,1 106,1 40,0 134,6 864,0 148,6 62,4 715,8 123,1 45,5 148,2

35,0 748,5 128,7 41,0 600,0 103,2 37,9 148,5 859,5 147,8 61,8 696,0 119,7 43,1 163,5

40,0 733,7 126,2 39,5 571,2 98,3 34,5 162,4 841,5 144,7 59,3 662,6 114,0 39,2 178,8

45,0 719,5 123,8 38,1 543,1 93,4 31,3 176,4 824,2 141,8 57,0 630,1 108,4 35,6 194,2

50,0 706,0 121,4 36,7 515,7 88,7 28,4 190,3 807,8 138,9 54,9 598,3 102,9 32,3 209,5

55,0 693,2 119,2 35,5 489,0 84,1 25,6 204,2 792,1 136,2 52,8 567,3 97,6 29,2 224,8

10,0 25,0 798,9 137,4 46,4 676,1 116,3 47,6 122,8 919,5 158,2 70,3 784,3 134,9 54,2 135,2

30,0 797,1 137,1 46,2 660,6 113,6 45,6 136,4 916,6 157,6 69,8 766,4 131,8 51,8 150,2

35,0 795,2 136,8 46,0 645,2 111,0 43,6 150,0 913,6 157,1 69,4 748,4 128,7 49,5 165,2

40,0 780,8 134,3 44,5 617,2 106,2 40,0 163,6 896,1 154,1 66,9 715,9 123,1 45,5 180,2

45,0 767,0 131,9 43,0 589,8 101,4 36,7 177,2 879,3 151,2 64,5 684,1 117,7 41,7 195,1

50,0 753,8 129,7 41,6 563,0 96,8 33,6 190,8 863,1 148,5 62,3 653,0 112,3 38,2 210,1

55,0 741,2 127,5 40,3 536,8 92,3 30,6 204,4 847,8 145,8 60,2 622,7 107,1 34,8 225,1

15,0 25,0 872,3 150,0 54,9 745,9 128,3 57,5 126,5 1004,4 172,8 83,2 865,2 148,8 65,3 139,2

30,0 872,7 150,1 54,9 733,2 126,1 55,6 139,5 1004,1 172,7 83,2 850,5 146,3 63,2 153,6

35,0 873,1 150,2 55,0 720,6 123,9 53,8 152,6 1003,9 172,7 83,1 835,9 143,8 61,2 168,0

40,0 859,4 147,8 53,3 693,8 119,3 50,1 165,6 987,1 169,8 80,5 804,8 138,4 56,9 182,4

45,0 846,2 145,5 51,8 667,5 114,8 46,5 178,7 971,0 167,0 78,0 774,3 133,2 52,8 196,7

50,0 833,4 143,3 50,3 641,7 110,4 43,1 191,7 955,5 164,3 75,6 744,3 128,0 49,0 211,1

55,0 682,5 117,4 34,4 477,7 82,2 24,5 204,8 779,7 134,1 51,3 554,2 95,3 27,9 225,5

Where,CLOT: Chilled Water Outlet Temperature (°C)HOT: Hot Water Outlet Temperature (°CHCAP: Heating Capacity (kW)CCAP: Cooling Capacity (kW)

HFR: Condenser Water Flow Rate at 5°C (m3/h)HPD:Condenser Water Pressure Drop (kPa)CFR:Chilled Water Flow Rate at 5°C (m3/h)CPD:Water Cooler Pressure Drop (kPa)IPT:Compressor Input Power (kW)

Conversion Multiplier:1 kW = 860 kcal/h = 3412 Btu/h1 kPa = 0.102 mAq

Page 81: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

MODEL SELECTION 15/77

15.3. ELECTRICAL DATA

Commpressor MotorUnit Main Power

ApplicableInstantaneous

Voltage (V)Model

(V) (Hz) Maximum Minimum

STC*1(A)

RNC(A)

IPT(kW)

MaximumUnit

Current(A)

STC*2Unit

Maximum(A)

RCUE 40WG2 400 50 440 360 121 54,9 33,5 69 121

RCUE 50WG2 400 50 440 360 155 65,6 40,0 82 155

RCUE 60WG2 400 50 440 360 188 80,5 49,1 101 188

RCUE 80WG2 400 50 440 360 188 89,4 54,5 112 188

RCUE100WG2 400 50 440 360 155 131,2 80,0 164 172

RCUE120WG2 400 50 440 360 188 161,1 98,2 201 209

RCUE150WG2 400 50 440 360 188 171,4 104,5 214 209

RCUE180WG2 400 50 440 360 155 202,6 123,5 253 190

RCUE200WG2 400 50 440 360 188 243,6 148,5 304 230

RCUE240WG2 400 50 440 360 188 268,2 163,5 335 230

NOTES:

1. This data is based on the following conditionsChilled Water Inlet/Outlet Temperature: 12/7°C,AmbientTemperature: 35°C.

2. The "Maximum Unit Current" shown in the above table is the maximumtotal unit running current at the following conditions.Supply Voltage: 90% of the rated voltage, Unit Capacity: 100% at max.operating conditions

3. The power supply cables must be sized to cover this maximum currentvalue.

4. Starting Current (*1, *2) means as follows.*

1:First Compressor Starting Current*

2:Unit Maximum Starting Current, when Last Compressor starts.

5. Compressor motor is star-delta starting

VOL: Rated Unit Supply Voltage(V)

STC: Starting Current(A)

Hz: Frequency(Hz)

RNC: Running Current(A)

IPT: Input(kW)

Page 82: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

15/78 MODEL SELECTION

15.4. SOUND DATA

Standard Models

Sound Pressure Level (dB)Frequency Band (Hz)Model

63 125 250 500 1000 2000 4000 8000

Overall

RCUE40WG2 77 69 71 63 62 61 53 37 68

RCUE50WG2 74 76 71 64 65 64 51 35 69

RCUE60WG2 77 69 67 62 68 66 53 35 71

RCUE80WG2 77 70 70 71 62 64 50 39 71

RCUE100WG2 79 71 70 67 68 67 54 38 72

RCUE120WG2 80 72 70 65 71 69 56 38 74

RCUE150WG2 81 73 72 69 70 69 56 40 74

RCUE180WG2 82 74 73 71 70 69 56 41 75

RCUE200WG2 83 75 74 71 72 71 58 42 76

RCUE240WG2 84 76 75 71 73 72 59 42 77

Sound Power Level (dB)Frequency Band (Hz)Model

63 125 250 500 1000 2000 4000 8000

Overall(dBA)

RCUE40WG2 92 84 86 78 77 76 68 52 83

RCUE50WG2 89 91 86 79 80 79 66 50 84

RCUE60WG2 92 84 82 77 83 81 68 50 86

RCUE80WG2 92 85 85 86 77 79 65 54 86

RCUE100WG2 95 87 86 83 84 83 70 54 88

RCUE120WG2 96 88 86 81 87 85 72 54 90

RCUE150WG2 97 89 88 85 86 85 72 56 90

RCUE180WG2 98 90 89 87 86 85 72 57 91

RCUE200WG2 99 91 90 87 88 87 74 58 92

RCUE240WG2 100 92 91 87 89 88 75 58 93

NOTE:

1. The sound pressure is based on the following conditions.

-1 meter from the control panel surface and 1.5 meter from the floor level.

-Voltage of the power source is 380V.

-The above data was measured in an anechoic chamber, so that reflected sound should be taken into consideration inthe field.

2. Operating conditions are as follows.Standard Models: Cooler Water Inlet/Outlet Temperature 12/7 °C, Condenser Water Inlet / outlet 30°C/35°C.

Page 83: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

APPLICATION DATA 16/79

16. APPLICATION DATA

16.1. WORKING RANGE

Working Range

Item Description Remark

Working Voltage 90% 110% of Rated Voltage

Voltage ImbalanceWithin ±3% Deviation from Each Voltage

at Compressor TerminalsPower Supply

Starting Voltage Higher than 85% of Rated VoltageStandard 22 45

Condenser WaterOutlet Temperature

High CondensingTemperature and Heat Pump

operation option22 55

Standard 5 15 WaterCooler WaterOutlet Temperature

Low TemperatureOption

4 0 (Low 1)-1 -5 (Low2)

-6 -10 (Low3)Ethylene glycol

Maximum Permissible Water Pressure 1.0 MPa

16.2. PART LOAD PERFORMANCE

The European Seasonal Energy Efficiency Ratio is a weighted formula enabling to take into account the variation of EER withthe load rate and the variation of water inlet condenser temperature.

ESEER = A . EER100 + B . EER75 + C . EER50 + D . EER25

With the following weighting coefficients:

A = 0.03

B = 0.33

C = 0.41

D = 0.23

The following part-load ratings shall be considered:

Load Ratio(%)

Water temperatureat condenser inlet

(ºC)

100 3075 2650 2225 18

Model RCUE-WG2 40 50 60 80 100 120 150 180 200 240

ESEER 4,52 4,52 4,52 4,86 4,52 4,52 4,86 4,86 4,52 4,86

Page 84: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

16/80 APPLICATION DATA

16.3. ETHYLENE GLYCOL APPLICATION

Low Water Temperature Application (Option)

When utilizing water less than 5 °C, antifreezing mixture ofethylene glycol shall be input to the water system.Low water temperature Option is categorised 3 leveldepending on water outlet temperature.Therefore, please specify the level when ordering .Freeze Protection Thermostat has been set in the factory.Table shows Required Ethylene Glycol percentage for eachcategory.

1. Category

CategoryOutlet Water

Temp. (°C)

RequiredEthylene

Glycol (wt%)

EthyleneGlycol

FreezingTemp. (°C)

Low 1 4 ~ 0 20 -7Low 2 -1 ~ -5 30 -13Low 3 -6 ~ -10 40 -22

NOTE:Freeze Protection Thermostat is the electronic control,but non-adjustable.

For the performance, each value can be given by using following table. (See below example)

2. Performance

Condenser Water Outlet Temperature

(°C)

25 30 35 40 45

EthyleneGlycol

OutletWaterTemp.

Flow RateCorrection

Factor

PressureDrop

CorrectionFactor CAP IPT CAP IPT CAP CAP IPT IPT CAP IPT

(wt%) (°C) (Kf) (Kp) (%) (%) (%) (%) (%) (%) (%) (%) (%) (%)

4 1.011 1.15 97 79 94 88 91 98 88 107 84 1173 1.012 1.16 94 78 91 88 88 98 85 107 82 1172 1.013 1.17 92 78 89 88 86 97 82 107 79 1171 1.013 1.18 90 78 87 87 83 97 80 107 77 116

20

0 1.014 1.19 88 77 84 87 81 97 77 106 74 116

-1 1.034 1.30 84 77 81 86 78 96 74 106 71 116-2 1.035 1.32 82 76 79 86 75 96 71 106 68 116-3 1.037 1.34 80 76 76 86 73 96 69 106 65 116-4 1.037 1.36 78 75 74 85 70 95 66 105 63 115

30

-5 1.038 1.38 75 75 72 85 68 95 64 105 60 115

-6 1.073 1.50 72 73 69 84 65 94 61 104 57 114-7 1.075 1.52 70 73 66 83 62 93 58 103 54 114-8 1.076 1.54 68 72 64 83 60 93 56 103 52 113-9 1.076 1.56 66 72 62 82 57 93 53 103 49 113

40

-10 1.077 1.58 64 71 59 82 55 93 51 103 46 113

NOTE:

1.CAP: Cooling Capacity, IPT: Compressor Input

2.Capacity and Compressor Input show the percentageof the standard condition: Condenser Water Inlet /Outlet 30/35°c, Cooler.

3.Water Flow Rate and Pressure Drop can be calculatedby the Correction Factor Kf and Kp.

4.Example:

a)Model: RCUE120 WG2

b)Standard Condition: Capacity 388kW, CompressorInput 98.2kW

c)Outlet/Inlet Water Temperature -3/2°C, CondenserWater Outlet Temp. 30°C

- Ethylene glycol: 30%

- Capacity = 388*0.76=295 kW, Compressor Input =98.2*0.86=84.5 kW

- Water Flow(m³/h) = Kf*Capacity(kW)*0.86∆T(∆T=Inlet Temp.-Outlet Temp.)

= 1.037*295*0.86/(2-(-3))

= 52.6 m³/h

- Pressure Drop = Kp*Pressure Drop (water)

= 1.34*0.0188*52.61.897

= 46 kPa

where, Pressure Drop(water)= α x Qβ: see "WaterPressure Drop"

Page 85: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

COMPONENTS DATA 17/81

17. COMPONENTS DATA

17.1. COMPRESSOR

Model 40ASC-Z 50ASC-Z 60ASC-Z

Type Semi-HermeticRevolution rpm 2880Displacement m3/h 137.4 169.5 208.7Capacity Control % 100 15, 0Pneumatic Pressure

High Side MPa 3.0Low Side MPa 2.0

Motor Type Special Squirrel Cage, Three-Phase MotorStarting Method Star-Delta StartingNominal Output kW 30 37 45Poles 2Insulation E

Oil Name JAPAN ENERGY, FREOL UX300Charge Litre 6

Net Weight kg 400 440 460

17.2. CONDENSER AND WATER COOLER

CONDENSER

Model RCUE-WG2 40 50 60 80 100 120, 150 180, 200 240

Condenser Brazed Type Plate Heat ExchangerType (Quantity) A (1) B (1) C (1) D (1) E (1) F (1) C (3) D (3)

TYPE A B C D E F

REFRIGERANT CYCLE 40HP 50HP 60HP 80HP 100HP 120, 150HP

DimensionsHeight (H) mm 525 525 525 525 694 694Width (W) mm 243 243 243 243 304 304Depth (D) mm 272 338 431 497 441 538

Maximum Permissible PressureRefrigerant Side MPa 1.8 1.8 1.8 1.8 1.8 1.8Water Side MPa 1.0 1.0 1.0 1.0 1.0 1.0

Internal VolumeWater Side Liter 14.8 18.6 23.9 27.6 40.2 49.4

Material Stainless SteelApproval PED ( 1 )

Page 86: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

17/82 COMPONENTS DATA

WATER COOLER

Model RCUE-WG2 40 50 60 80 100, 120, 150 180, 200 240

Water Cooler Brazed Type Plate Heat Exchanger

Type (Quantity) A (1) B (1) C (1) D (1) E (1) C (3) D (3)

TYPE A B C D E

REFRIGERANT CYCLE 40HP 50HP 60HP 80HP 100, 120, 150HP

DimensionsHeight (H) mm 525 525 525 525 694Width (W) mm 243 243 243 243 304Depth (D) mm 227 305 389 431 489

Maximum Permissible PressureRefrigerant Side MPa 1.8 1.8 1.8 1.8 1.8Water Side MPa 1.0 1.0 1.0 1.0 1.0

Internal VolumeWater Side Liter 15.1 16.7 21.5 23.9 44.8

Material Stainless SteelApproval PED ( 1 )

NOTE:Pressure equipment Directive (97/23/EC)

SINGLE TYPE CONDENSER AND WATER COOLER DUAL TYPE CONDENSER AND WATER COOLER

REFRIGERANT IN

WATER OUT

WATER IN

REFRIGERANT OUT

REFRIGERANT

PLATES

WATER

No.1 REFRIGERANT

PLATES

WATER

No.2 REFRIGERANT

No.1 REFRIGERANT IN

No.2 REFRIGERANT IN

No.1 REFRIGERANT OUT

No.2 REFRIGERANT OUT

WATER OUT

WATER IN

Page 87: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start
Page 88: Technical Catalogmaynenkhia-z.com/images/HTC1.pdf · -CONTINUOUS CAPACITY CONTROL--CONVENTIONAL STEP CONTROL-MOTOR INPUT (%) COOLING CAPACITY (%) Continuous Capacity Control Start

TCGB0045 - 12/06 - Printed in Spain