T&B Conduit Fittings XTRAFLEX™ System - Conduit, Tubing, Fittings for Nonmetallic Liquidtight Conduit ® « Figure 1 Metallic Bullet® Liquidtight Connectors for T&B LTC Nonmetallic Liquidtight Conduit Type B and T&B EFC Flexible Tubing Cat. No. LT38M LT438M LT938M LT50M LT450M LT950M fcT75M LT475M LT975M LT100M LT4100M LT9100M LT125M LT4125M LT9125M LT150M LT4150M LT9150M LT200M LT4200M LT9200M Fig. 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Trade A ±.030 Size (.80) (in.) (in.) (mm) 1.156 % (29.4) 1.375 1 /2 (34.9) 1.656 3 /4 (42.1) 1.875 1 (47.6) 2.375 1 1 /4 (60.3) 2750 1 1 /2 (69.8) 3.468 2 (88.1) •B±.060 (1.50) (in.) (mm) 1.500(38.1) 1.962(49.8) 1.312(33.3) 1.562(39.7) 1.875(47.6) 1 437 (36.5) 1.625(41.2) 2.125(54.0) 1,750(44.4) 2.062 (52.4) 2.250(57.1) 1.937(49.2) 2.500 (63.5) 2.750(69.8) 2.500 (63.5) 2.687 (68.2) 2.750 (69.8) 2.812(71.4) 3.062 (77.8) 3.875(98.4) 3.500 (88.9) C ±.045 (1.15) (in.) (mm) 0.562(14.3) 0.562(14.3) 0.625 (15.9) 0.562(14.3) 0562(14.3) 0625(15.9) 0.625(15.9) 0.562(14.3) 0.625(15.9) 0.750(19.0) 0.812(20.6) 0.812(20.6) 0.812(20.6) 0.812(20.6) 0.812(20.6) 0812(20.6) 0.812(20.6) 0.812(20.6) 0.812(20.6) 0.875 (22.2) 0.875 (22.2) Thread D NPT (in.) (mm) (in.) 1 /2-14 1.375(34.9) </M4 1.562(39.7) 3 /4-14 1.750(44.4) 1-11% 2.187(55.5) 1 1 /4-11 1 /2 2.750(69.8) r/2-n!4 2.937 (74.6) 2-11/2 3.437 (87.3) * After Assembly U.L File No. E-23018 CSA File No. 52391 Suggested Specification: Where liquidtight flexible nonmetallic conduit (U.L. Type B) or liquidtight flexible nonmetallic tubing is terminated to a box or enclosure, the metallic connectors used shall be able to be installed without disassembly and provide a positive installation criteria. In the installed condi- tion, the connector must provide a seal, meeting watertight requirements of NEMA Type 4 and Type 6 enclosures with conduit and NEMA Type 4 enclosures with tubing. Installed con- nectors shall be as manufactured by Thomas & Belts LT38M series. Material: Body/Gland-Steel/Ml Insert-Nylon ThomasiBetts © 2001 Thomas & Belts Corporation. Specifications are subject to change without notice. WWW.tnb.COITI 135

T&B Conduit Fittings - Kirby Risk Corporation · PDF fileApplication A series of non-metallic connectors designed to provide a liquidtight seal when terminating liquidtight non-metal-lic

Embed Size (px)

Citation preview

Page 1: T&B Conduit Fittings - Kirby Risk Corporation · PDF fileApplication A series of non-metallic connectors designed to provide a liquidtight seal when terminating liquidtight non-metal-lic

T&B Conduit FittingsXTRAFLEX™ System - Conduit, Tubing, Fittings for Nonmetallic Liquidtight Conduit

® «

Figure 1

Metallic Bullet® Liquidtight Connectors for T&B LTC NonmetallicLiquidtight Conduit Type B and T&B EFC Flexible Tubing

Cat.No.

LT38MLT438MLT938M

LT50MLT450MLT950M

fcT75MLT475MLT975M

LT100MLT4100MLT9100M

LT125MLT4125MLT9125M

LT150MLT4150MLT9150M

LT200MLT4200MLT9200M

Fig.

123

123

123

123

123

123

123

Trade A ±.030Size (.80)(in.) (in.) (mm)

1 .156% (29.4)

1.3751/2 (34.9)

1.6563/4 (42.1)

1.8751 (47.6)

2.3751 1 /4 (60.3)

275011/2 (69.8)

3.4682 (88.1)

•B±.060(1.50)

(in.) (mm)

1.500(38.1)1.962(49.8)1.312(33.3)

1.562(39.7)1.875(47.6)1 437 (36.5)

1 .625(41.2)2 .125(54 .0)1,750(44.4)

2.062 (52.4)2.250(57.1)1.937(49.2)

2.500 (63.5)2.750(69.8)2.500 (63.5)

2.687 (68.2)2.750 (69.8)2 . 8 1 2 ( 7 1 . 4 )

3.062 (77.8)3.875(98.4)3.500 (88.9)

C ±.045(1.15)

(in.) (mm)

0.562(14.3)0.562(14.3)0.625 (15.9)

0 .562(14 .3 )0562(14.3)0 6 2 5 ( 1 5 . 9 )

0.625(15.9)0 .562(14 .3)0.625(15.9)

0.750(19.0)0.812(20.6)0.812(20.6)

0.812(20.6)0.812(20.6)0.812(20.6)

0812 (20 .6 )0.812(20.6)0.812(20.6)

0.812(20.6)0.875 (22.2)0.875 (22.2)

ThreadD NPT

(in.) (mm) (in.)

1/2-14

1.375(34.9)

</M41.562(39.7)

3/4-14

1.750(44.4)

1 - 1 1 %2.187(55.5)

1 1 /4 -11 1 /22.750(69.8)

r/2-n!42.937 (74.6)

2 - 1 1 / 2

3.437 (87.3)

* After AssemblyU.L File No. E-23018CSA File No. 52391

Suggested Specification:Where liquidtight flexible nonmetallic conduit (U.L. Type B) or liquidtight flexible nonmetallictubing is terminated to a box or enclosure, the metallic connectors used shall be able to beinstalled without disassembly and provide a positive installation criteria. In the installed condi-tion, the connector must provide a seal, meeting watertight requirements of NEMA Type 4and Type 6 enclosures with conduit and NEMA Type 4 enclosures with tubing. Installed con-nectors shall be as manufactured by Thomas & Belts LT38M series.Material: Body/Gland-Steel/Ml

Insert-Nylon

ThomasiBetts© 2001 Thomas & Belts Corporation. Specifications are subject to change without notice. WWW.tnb.COITI 135

Page 2: T&B Conduit Fittings - Kirby Risk Corporation · PDF fileApplication A series of non-metallic connectors designed to provide a liquidtight seal when terminating liquidtight non-metal-lic

T&B Conduit FittingsXTRAFLEX System - Conduit, Tubing, Fittings for Nonmetallic Liquidtight Conduit

Specification Sheet - Bullet" Liquidtight Fittings or LiquidtightFlexible Nonmetallic Conduit and Tubing ____

(4) -v

^m(6) -i

((

/Box or Conduit

Enclosure or Tubln9Wall

ApplicationA series of non-metallic connectorsdesigned to provide a liquidtight sealwhen terminating liquidtight non-metal-lic conduit (U.L. Type B) or liquidtightnon-metallic tubing to a box or enclo-sure with knockout opening or athreaded hub.

Plastic Bullef Liquidtight Fittings Feature• Connector assembles to conduit

without disassembly and is designedto be installed with a positive installa-tion criteria (gland bottoms on bodyshoulder).

• Rugged low profile non-metallic bodyand gland construction (1); the con-nector is equipped with a steel locknutto firmly secure connector to box or anenclosure and a sealing "O" ring.

• Captivated sealing "O" ring (2) withpredetermined compression for areliable seal at enclosure.

• Connector ferrule designed to acceptvariations in conduit inside diameterand is tolerant of field conduit cuts (3).

• The profile of ferrule is designed toreduce friction between conduit I.D.and ferrule (4) allowing conduit toseat properly for an effective seal.

• Outer surface of the clamping fingersprovided with friction reducing ridges(5) for ease of installation; the innersurface is designed with conduit bit-ing teeth to enhance clamping andsealing action (6).

• Performance of connectors tested tosimulate adverse installation conditions.

• Provides a double sealing action (7).• Elongated gland nut profile (8) de-

signed to provide additional strain relieffor 90° pull and an easy hand grip.

• Performance of connector unaffectedby exposure to detergents, cleaners,and sanitizers commonly encoun-tered in food processing plants andtypical industrial environment; alsounaffected by cutting fluids, wiringpulling compounds and Marine envi-ronment. The connector meets indus-try standards for cold impact andsimulated hammer blow.

Standard Material/Finish• Body Gland - weather stabilized ther-

moplastic (black).• "O" Ring - nitrile (blue).• Locknut - Steel/electro zinc plated.• Material temperature rating - thermo-

plastic-40°C to 105°C.• Material Flammability Rating:

U.L. 94-V2.

Listed/Certified by:U.L. (File* E23018);CSA(File#LR52391)

Conforms to:• CSA 22.2 #227.2 & CSA 22.2 #227.3• ANSI/U.L.514B-1988• Watertight requirements of NEMA

Type 4 and NEMA Type 6 enclosures.• Federal Standard H28 (NPT threads).• Suitable for hazardous locations -

Class I Div. 2; Class II Div. 1 & 2;Groups E.F, & G; Class III per N.E.C.;Article 501-4, 502-4 and 503-3.

Suggested Specification:Where liquidtight flexible nonmetallic conduit (U.L. Type B) or liquidtight flexible nonmetallictubing is terminated to a box or enclosure, the nonmetallic connectors used shall be able tobe installed without disassembly and provide a positive installation criteria. In the installedcondition, the connector must provide a seal meeting watertight requirements of NEMA Type4 and Type 6 enclosures. The performance of connectors shall be unaffected by exposure todetergents, sanitizers, cutting fluids, wire pulling compounds and oil base industrial paints.The connector must also be capable of withstanding Marine environment and cold impactsimulating a hammer blow. Installed connectors shall be of the elongated gland type asmanufactured by Thomas & Betts LT38P series.