9
HiQ Solar, Inc. Page 1 of 9 Taking the Nuisance Tripping out of AFCI - Useful Changes to Testing of PV Inverters 2 August 2016 Contents Introduction .................................................................................................................................... 1 Code Requirements ........................................................................................................................ 2 Existing Test Method vs. Real World .............................................................................................. 2 Changing the Way AFCI Circuits are Tested .................................................................................... 3 Improving the Test Arc Signature ............................................................................................... 4 New Methods of Testing............................................................................................................. 5 Other System Topologies ............................................................................................................ 7 HiQ Solar TrueString Inverters and AFCI ......................................................................................... 8 Customer Testing Example ......................................................................................................... 9 Summary ......................................................................................................................................... 9 Introduction The ability of a PV inverter to detect and interrupt series arcs (AFCI, or Arc Fault Circuit Interrupter) is a useful safety feature. In the US the National Electrical Code (NFPA 70) requires PV systems to be capable of detecting high voltage DC arcs, whether through functionality built into the inverter or by other means. However, the testing of this has been a controversial topic. 1. The NEC requires series arc detection functionality, but does not dictate how the AFCI should be measured and certified. UL1699B OOI (Outline of Investigation) describes some suggested test methods, but is not a standard and is not directly referenced by the NEC. 2. The test methods described in UL1699B are not optimal as we’ll see later 3. Real installations are suffering nuisance tripping, which is leading to frustration and wasted time and money. Some installations even have the AFCI functionality switched off to prevent such issues from reoccurring.

Taking the Nuisance Tripping out of AFCI Useful PV

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Taking the Nuisance Tripping out of AFCI Useful PV

HiQSolar,Inc. Page1of9

TakingtheNuisanceTrippingoutofAFCI-UsefulChangestoTestingofPVInverters2August2016ContentsIntroduction....................................................................................................................................1CodeRequirements........................................................................................................................2ExistingTestMethodvs.RealWorld..............................................................................................2ChangingtheWayAFCICircuitsareTested....................................................................................3

ImprovingtheTestArcSignature...............................................................................................4NewMethodsofTesting.............................................................................................................5OtherSystemTopologies............................................................................................................7

HiQSolarTrueStringInvertersandAFCI.........................................................................................8CustomerTestingExample.........................................................................................................9

Summary.........................................................................................................................................9

IntroductionTheabilityofaPVinvertertodetectandinterruptseriesarcs(AFCI,orArcFaultCircuitInterrupter)isausefulsafetyfeature.IntheUStheNationalElectricalCode(NFPA70)requiresPVsystemstobecapableofdetectinghighvoltageDCarcs,whetherthroughfunctionalitybuiltintotheinverterorbyothermeans.However,thetestingofthishasbeenacontroversialtopic.1. TheNECrequiresseriesarcdetectionfunctionality,

butdoesnotdictatehowtheAFCIshouldbemeasuredandcertified.UL1699BOOI(OutlineofInvestigation)describessomesuggestedtestmethods,butisnotastandardandisnotdirectlyreferencedbytheNEC.

2. ThetestmethodsdescribedinUL1699Barenotoptimalaswe’llseelater

3. Realinstallationsaresufferingnuisancetripping,whichisleadingtofrustrationandwastedtimeandmoney.SomeinstallationsevenhavetheAFCIfunctionalityswitchedofftopreventsuchissuesfromreoccurring.

Page 2: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page2of9

We’lltakeabrieflookattheissueswitharcdetection,andtheprogressbeingmadeinchangingtestmethodstoimprovethesituation.WewillalsolookathowHiQ'sTrueStringinvertersareuniquelyengineeredtosolvetheissuesofAFCIfunctionality.

CodeRequirementsTheNationalElectricalCode(NFPA70)specifiestherequiredfunctionalityofanarc-detectioncapabilityin690.11.Notethatinthe2011editionthisappliedtorooftops,butin2014thiswasextendedtoincludeallarrays,notjustthosemountedonbuildings.690.11Arc-FaultCircuitProtection(DirectCurrent).Photovoltaicsystemswithdcsourcecircuits,dcoutputcircuits,orboth,onorpenetratingabuildingoperatingataPVsystemmaximumsystemvoltageof80voltsorgreater,shallbeprotectedbyalisted(dc)arc-faultcircuitinterrupter,PVtype,orothersystemcomponentslistedtoprovideequivalentprotection.ThePVarc-faultprotectionmeansshallcomplywiththefollowingrequirements:(1)Thesystemshalldetectandinterruptarcingfaultsresultingfromafailureintheintendedcontinuityofaconductor,connection,module,orothersystemcomponentinthedcPVsourceandoutputcircuits.(2)Thesystemshalldisableordisconnectoneofthefollowing:

a.Invertersorchargecontrollersconnectedtothefaultcircuitwhenthefaultisdetected

b.Systemcomponentswithinthearcingcircuit(3)Thesystemshallrequirethatthedisabledordisconnectedequipmentbemanuallyrestarted.(4)Thesystemshallhaveanannunciatorthatprovidesavisualindicationthatthecircuitinterrupterhasoperated.Thisindicationshallnotresetautomatically.ThebasicmethodsusedtoinvestigateproductsinthiscategoryarecontainedinULSubject1699B,“OutlineofInvestigationforPhotovoltaic(PV)DC-Arc-FaultCircuitProtection.”

ExistingTestMethodvs.RealWorldArcfaulttestingmethodsareimportant,andinmanywaysshortcomingsofthemethodshaveleadtothemismatchbetweencomplianceandreliableperformanceinthefield.UL1699BwasanattempttospecifytestingofarcdetectioninPVsystems,whichisnowbeingrevisedaswe’llseelater.Initscurrentform,thetestisnotveryarduousorrepresentativeofreal-worldarcs.ThetestasdescribedinUL1699Busesatestfixturethatappliesahighvoltageacrossasmallpieceofsteelwool.ThearcfixtureisinsertedinserieswiththeDCinputneartheinverterDCinputterminals.SeeFigure1(a).

Page 3: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page3of9

Figure1:Testpractice(a)vs.real-worldconditions(b)

Figure1(b)showsthekindofsituationaninverterAFCIsystemmightseeinthefield.Itismountedsomedistancefromthearray(i),andthePVmodulesinthearrayareaseriesstring(ii).Thewiresandmodulesaddsignificantinductanceandcapacitancetothepicture.Thearcmightoccuratanypointinthestringorwiring,theworstcasebeingatthemid-pointofthestring(iii).Itisalsolikelytohavemuchloweramplitudethanthetestarc.Inadditiontoallofthis,theinitiationofthearcisquitedifferentfromanarcinitiatedbyburningthesteelwool(iv&v).Theprimaryissueisthatintherealworld,thearcthattheinverterislookingforwillbeginmuch,muchsmallerwithadifferentinitialsignature.AsarealPVstringpresentssignificantseriesinductanceandcapacitance,thesereactivecomponentscanprovidesubstantialfilteringofthearcsignaturemakingitmoredifficulttodetectwhenanarcispresent.AddtoallofthisthefactthatmostPVsystemsusedincommercialapplicationsconnectstringsinparallel,andtheproblemjustgotevenworse.Thisstartstoexplainwhyinvertersstruggletodetectarcseventhoughtheypassthetest.Thelogicalresponsefrommostinvertercompaniesistoincreasethegainofthedetectioncircuittolookforthosesmallerarcsignatures.However,thisresultsinamuch-increasedlikelihoodoffalsealarms,whilealsomissingthepresenceofrealarcproblemsuntilitistoolate.

ChangingtheWayAFCICircuitsareTestedUL1699BTaskGroup1isworkingonupdatingthetestmethodstobemorerepresentativeofrealworldconditionsandmorerepeatable.Thissectiongivesahighleveloverviewofthedevelopmentofproposalsthatareinprocessandareusefultounderstand.WhilethisisaworkinprocesstheyarecorrectasofJuly2016.

Inverter' PSU'

Inverter'L'

C'

Wool'

b)'

a)'

(i)'

t'

t'

V,'I'

V,'I'

(ii)'

(iii)'

(iv)'

(v)'

Page 4: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page4of9

Problemstobetackled:1. Theoldmethodoftestingresultedinlistedproductsthatdidnotdetectsomearcsin

realworldconditions2. And,somelistedproductssufferedfromunwantednuisancetripping

Objectives:

• Redefinetestmethodandfixturetomorecloselyrepresentreal-worldconditions(discussedhere)

• Developmethodtotestunwantednuisancetripping(notdiscussedhere)

TaskGroupGuidelines

• Testshouldrepresentreal-worldconditions• Testshouldrepresentworst-case• Testmustberepeatable• Shallbetestmethodagnostic

ImprovingtheTestArcSignatureOnechangebeingdiscussedistoalterthewaythearciscreated.Insteadofaburningfilamentofsteelwooltoinitiatethearc,thenewproposalusesaballandringorpairofrodsmountedonatracksuchthatthearcgapcanbeincreasedatacontrolledrate.Theideaisthatthearcbeginsataverylowlevelandincreasesatacontrolledrate,asiscommonintherealworld.Boththeavailablearccurrentandrateofseparationarenowspecified.Incontrast,thesteelwoolmethodisnotveryrepeatable,witharccharacteristicschangingdependinguponthetypeofwoolused,theofwoolquantityandhowitisplacedinthegap.Figure2showstheoldandnewmethods.1.Showstheoldfixturewithsteelwoolinserted.2.Showsthefixturegeneratinganarc.3.Showsthespentfixture.4.Showstheproposedballandring,and5.Showsitgeneratinganarc.

Page 5: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page5of9

Figure2:Existing(1-3)andexampleproposed(4-5)arcgenerationfixtures

Theballandringandcopperrodswithacontrolledpull-apartaremorerepresentativeofareal-worldarc,andgivesmorerepeatabletestresults.

NewMethodsofTestingInFigure1(b)wesawthattherealworldismorecomplexthanthetestsetupbeingusedtotestperUL1699BOOI.TheblockdiagramfortheoriginaltestisshowninFigure3(a)andisbeingeliminated.However,thesetupinFigure3(c)isbeingproposedforthetestingofAFCIcircuitsin,forexample,stringinverters;conceptuallyitrelatesbacktoourPVstringascanbeseenin(b).Whilethetestingwillbeharder,theresultswillbemuchimproved,andthetestset-upisdiscussedfurtherbelow.

Page 6: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page6of9

Figure3:Legacy(a)andnew(b&c)arctestingapparatus

InFigure3(c)thearctestfixturewillbeplacedateachofthreepositions,designated“Arc”inthediagram.TheseriesinductancerepresentsthewirebetweentheAFCIandthePVstring.Amaximumwirelengthof250feet(80m)wasconsideredreasonable1,andwillprobablyendupbeingthedefault.PVmoduleshavenormalmodecapacitancebetween+and–terminalsandcommonmodecapacitancetoground.Thesecharacteristicscanvarywidelybetweenmoduletypesandinstallations.Groundmountedmoduleshaveverylowcapacitance(ontheorderof150pF);thinfilmmodulescanactuallybeadhesivelyattachedtoastructuresuchasametalbuilding,givingacapacitancethatcanbeseveralnFpermodule.Inaddition,thewiringwillhavecapacitancetogroundthatwillincreasewithwirelength,andishigherwhenthewireisinametalraceway.And,thereiscapacitancebetweenconductorsthatvariesbywirelength,type,andorientation.

1Itisexpectedthatmanufacturerswillbeabletoshortenthisdistancetomakethetaskofcomplianceeasier;however,theywillneedtoprovidearatingofmaximumdistanceinalldocumentationandaccordinglyrestricthowcustomersinstalltheirproductinordertomaintainAFCIcompliance.

High%Voltage%Power%Supply%

Inverter%–%Device%Under%Test%(DUT)%

Ballast%Resistor%%

(As%Needed)%

S1%

Arc%Generator%

(a)%

(c)ProposedTestSetupforStringInverters

Par7alString

Par7alString

DUT

Arc

(b)Concept

Array&lineimpedancesimulator&generator

Networkwithseriesinductance,resistanceandcapacitancetoground

DUT

Arc

DCSource

DCSource (Asabove)

Arc

Arc Arc

Arc

Page 7: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page7of9

ForinverterswithasinglestringperAFCIcircuitthesituationissimple,andthecomponentvaluesintheelectricalnetworkreflectthis.ForinvertersthatparallelstringsintoasingleAFCIcircuitthecomponentvaluesinthenetworkreflectthis,withmorecapacitance,parallelinductanceandresistanceshroudingthearcsignal,makingthetestcommensuratelyhardertopass.

OtherSystemTopologiesItcouldbearguedthatastringinverterwithAFCIfunctionalityisoneofthemorestraightforwardscenariostotest.Systemtopologiesvarywidely,andtestmethodshavebeencreatedtodealwithAFCIcircuitsembeddedinstringcombinerboxes(seeFigure4),externalAFCIcircuits,andseveraldealingwithdifferentDC/DCoptimizers(anexampleisinFigure5).AFCIcircuitsembeddedinindividualPVmodulesarenotaddressed.Asanexample,theconfigurationofa1MWcentralinverterwithstringcombinersandstringre-combinerswillbeverycomplextotest,andtodesignAFCIcircuitsthatwillpass.

Figure4:Proposedtestset-upforasysteminvolvingstringcombiners

(d)ProposedTestSetupforStringCombiners

Array&lineimpedancesimulator&generator

Arc

Arc

Arc

Arraysimulator

Arraysimulator

DUT

LineImpedanceSimulatorII

“RepresentaBve”Inverter

NetworkSource

NetworkSource

NetworkSource

NetworkSource

Page 8: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page8of9

Figure5:Proposedtestset-upforAFCItestingofaDC/DCoptimizersystem

The2017NECcoderemovesallreferencetodetecting,annunciating,andmanualresetrequirements.Itisleftentirelytothesafetystandard,whichwillbeUL1699Bonceitisaffirmativelyballoted.

HiQSolarTrueStringInvertersandAFCIOurTrueStringinverterstartsoffwithsomeadvantagescomparedtocommon3-phasestringinverters.Theseinclude:• TrueStringinvertersare

commonlymountedunderthearray.ThismeansthatthelengthofDCwiringbetweentheinverterandthearrayisminimal,helpingtomakedetectionmorereliable.

• TrueStringinvertershaveindividualstringinputs.Reducingtheproblemtoasinglestringoneachinputinsteadofparallelingmanymakesdetectionmucheasierandmorereliable.

• Ourinvertersweretestedwithboththesteelwoolandballandringtestfixtures.• Ourdetectionmethodisuniqueandemploystimeandfrequencydomainanalysisofthearc

signal.• Thedetectionofarcsisintegratedintotheinverter,whichhelpstominimizenuisance

tripping.WemeetandexceedtherequirementsofNEC690.11andminimizenuisancetrippingwhileremainingfocusedonthedetectionofreal-worldarcs,asillustratedinthenextsection.

(e)ProposedTestSetupforDC/DCOp4mizerSystem

PVModule

Arc

Arc

Arc

Op4mizer

Middleofstring

Inverter

LongRun

Page 9: Taking the Nuisance Tripping out of AFCI Useful PV

ChangestoAFCITesting 2August2016

HiQSolar,Inc. Page9of9

CustomerTestingExampleAgoodillustrationofwhymountingastringinverternexttothestringsitserves,alongwiththebenefitsofanarchitecturewhereeachstringhasit’sowndedicatedAFCIcircuitryisshowninthiscustomer-suppliedexample.Thecustomerwantedtosetupvalidationtestingofagroupofdifferentstringinverters.Thetestset-upusedanarcgeneratoremployingtwocopperrodssteadilydrawnapartasdescribedpreviously;italsoplacedthearcfixtureinthemiddleofastringofPVmodulestobeasreal-worldrepresentativeaspossible.Avarietyofwell-knownstringinvertersweretested,alongwiththeHiQTrueStringinverter.Thepartofthetestset-upwiththetwocopperrodsisshownshowninFigure6.(a)showsaproductbeingtested(notethatitpassedandislistedtothecurrentUL1699BOOI);thearcburnedcontinuouslyuntilthesourcewasremoved,withtheinverterundertestunawareofdangerousarcing.TheseresultswereconsistentexceptfortheHiQproduct.(b)showsanexampletestperformedwiththeHiQTrueString–thearcisquicklydetectedandthestringsafelyshutdownasmandatedpertheNEC.

SummarySignificantimprovementstoAFCItestingarecoming.Theresultwillbemorereliabledetectionofreal-worldarcs,andthereductionoreliminationofnuisancetripping.Nuisancetrippingispartlytheconsequenceoftheoverlysimplistictestmethodrecommendedinthepast.CopyrightHiQSolar,Inc.,2016www.hiqsolar.com

Figure6:ScreenshotsofcustomerAFCItesting