Upload
yong
View
234
Download
11
Embed Size (px)
Citation preview
CHAPTER88
Subsea Power SupplyContents
8.1. Introduction 2258.2. Electrical Power System 227
8.2.1. Design Codes, Standards, and Specifications 2288.2.2. Electrical Load Calculation 2288.2.3. Power Supply Selection 230
8.2.3.1. Power Supply from Topside UPS 2318.2.3.2. Power Supply from a Subsea UPS 2338.2.3.3. Power Supply from Subsea Generators 233
8.2.4. Electrical Power Unit (EPU) 2348.2.5. Electrical Power Distribution 235
8.3. Hydraulic Power System 2378.3.1. Hydraulic Power Unit (HPU) 239
8.3.1.1. Accumulators 2418.3.1.2. Pumps 2418.3.1.3. Reservoir 2428.3.1.4. Control and Monitoring 244
References 244
8.1. INTRODUCTION
The power supply for a subsea production system is designed according to
the subsea control system (Chapter 7). Different control system types (direct
hydraulic, electrohydraulic, all-electric, etc.) require different power system
designs. However, basically two types of power systems are used: an elec-
trical power system or a hydraulic power system.
The power system supplies either electrical or hydraulic power to the
subsea equipment: valves and actuators on subsea trees/manifolds, trans-
ducers and sensors, SCM, SEM, pumps, motors, etc.. The power sources
can come from either an onshore factory (in a subsea-to-beach field
layout), as shown in Figure 8-1, or from the site (platform or subsea
generators).
Figure 8-2 illustrates the subsea power distribution when the power
sources are coming from a surface vessel.
Subsea Engineering Handbook � 2012 Elsevier Inc.ISBN 978-0-12-397804-2, doi:10.1016/B978-0-12-397804-2.00008-4 All rights reserved. 225 j
Figure 8-1 Power Supply from Onshore to Subsea (Courtesy of Vetco Gray)
Figure 8-2 Typical Subsea Power Distribution [1]
226 Y. Bai and Q. Bai
Subsea Power Supply 227
8.2. ELECTRICAL POWER SYSTEM
The electrical power system in a typical subsea production system that
provides power generation, power distribution, power transmission, and
electricity from electric motors. The power is either generated on site (from
a platform) or onshore (in a subsea-to-beach filed layout). To ensure
continuous production from a subsea field, it is of utmost importance that the
subsea system’s associated electrical power system be designed adequately.
Figure 8-3 shows the design process for an electrical power system.
Subsea Field DevelopmentFEED
Subsea Power SystemDesign
Electrical PowerSystem
Hydraulic PowerSystem
Electrical Load Calculation
Sizing & Selection of Power Supply
OutputCurrent
OutputVoltage
Electrical Power Distribution
Umbilical/CableLayout
ElectricalEquipment
Arrangement
Voltage DropCalculation
Power Management
Design Codes, Standards, & Specifications
Figure 8-3 Electrical Power System Design Process
228 Y. Bai and Q. Bai
8.2.1. Design Codes, Standards, and SpecificationsVarious organizations have developed many electrical codes and standards
that are accepted by industries throughout the world. These codes and
standards specify the rules and guidelines for the design and installation of
electrical systems. Tables 8-1 to 8-4 list some of the major international
codes and standards used for subsea field development.
8.2.2. Electrical Load CalculationElectrical load calculation is one of the earliest tasks during electrical power
system design. Engineers should estimate the required electrical load of all of
the subsea elements that will consume the electricity so that they can select
an adequate power supply.
Each local load may be classified into several different categories, for
example, vital, essential, and nonessential. Individual oil companies often
Table 8-1 American Petroleum Institute
API RP 14F Recommended Practice for Design and Installation of
Electrical Systems for Fixed and Floating Offshore
Petroleum Facilities for Unclassified and Class I,
Division 1 and Division 2 Locations
API RP 17A Recommended Practice for Design and Operation of
Subsea Production Systems
API RP 17H Draft ROV Interfaces with Subsea Equipment
API RP 500 Recommended Practice for Classification of Locations for
Electrical Installations at Petroleum Facilities Classified
as Class I, Division 1 and Division 2
API SPEC 17D Specification for Subsea Wellhead and Christmas Tree
Equipment
API SPEC 17E Specification for Subsea Production Control Umbilicals
Table 8-2 International Electrotechnical Commission
IEC 50 (426) International Electrotechnical Vocabulary (IEV)-Chapter 426-
Electrical Apparatus for Explosive Atmosphere
Table 8-3 Institute of Electrical and Electronics Engineers
Std. 100 Standard Dictionary of Electrical and Electronics Terms
Std. 141 Electrical Power Distribution or Industry Plants
Std. 399 Recommended Practice for Power Systems Analysis
Table 8-4 International Standards Organization
ISO 13628-5 Petroleum and Natural Gas IndustriesdDesign and
Operation of Subsea Production SystemsdPart 5:
Subsea Control Umbilicals
ISO 13628-6 Petroleum and Natural Gas IndustriesdDesign and
Operation of Subsea Production SystemsdPart 6:
Subsea Production Control Systems
Table 8-5 Typical Electrical Load Categories [2]Load Categories Classification Questions
Vital Will the loss of power jeopardize safety of personnel or
cause serious damage within the platform/vessel? (YES)
Essential Will the loss of power cause a degradation or loss of the
oil/gas production? (YES)
Nonessential Does the loss have no effect on safety or production?
(YES)
Subsea Power Supply 229
use their own terminology and terms such as “emergency” and “normal”
are frequently encountered. In general terms, there are three ways of
considering a load or group of loads and these may be cast in the form of
questions as shown in Table 8-5.
All of the vital, essential, and nonessential loads can typically be divided
into three duty categories [2]:
• Continuous duty;
• Intermittent duty;
• Standby duty (those that are not out of service).
Hence, each particular switchboard (e.g., from the EPU) will usually cover
all three of these categories. We will call these C for continuous duty, I for
intermittent duty, and S for standby duty. Let the total amount of each at this
particular switchboard be Csum, Isum, and Ssum. Each of these totals will
consist of the active power and the corresponding reactive power.
To estimate the total consumption for this particular switchboard, it is
necessary to assign a diversity factor to each total amount. Let these factors
beD. The total load can be considered in two forms, the total plant running
load (TPRL) and the total plant peak load (TPPL), thus:
TPRL ¼Xn
ðDc �Csum þDi � IsumÞ kW (8-1)
Xn
TPPL ¼ ðDc � Csum þDi � Isum þDs � SsumÞ kW (8-2)where
230 Y. Bai and Q. Bai
n: number of switchboards;
Dc: diversity factor for sum of continuous duty (Csum);
Di: diversity factor for sum of intermittent duty (Isum);
Ds: diversity factor for sum of standby duty (Ssum).
Oil companies that use this approach have different values for their
diversity factors, largely based on experience gained over many years of
designing plants. Besides, different types of host facilities may warrant
different diversity factors [2]. Typically,
Dc ¼ 1.0–1.1;
Ds ¼ 0.3–0.5;
Di ¼ 0.0–0.2.
The continuous loads are associated with power consumption that
remains constant during the lifetime of the system regardless of the opera-
tion taking place at any one time. Such consumers would include the subsea
production communication unit (SPCU, located on the platform) and the
monitoring sensors.
Intermittent loads are considered the loads that depend on the opera-
tional state of the system. A typical example would be a load due to valve
actuation or HPU system activation. For the duration of each operation, the
power requirement for the system increases to accommodate the operation.
For the definition of the momentary loads, apart from the corresponding
power requirement, it is essential to identify the duration and frequency of
operations as well as a statistical description of operating occurrences in
a specified time period.
Note that at no point during its lifetime should the subsea power system
run idle (without load), except for the case of a temporary production
shutdown. Tables 8-6 and 8-7 present typical values for continuous and
intermittent loads during the operation of electrohydraulic and all-electric
production systems, respectively. The data are presented in terms of elec-
trical loads. Note that the use of a choke valve can be either continuous or
intermittent, depending on field requirements.
8.2.3. Power Supply SelectionAfter the load has been carefully estimated, the ratings for the power supply
sources must be selected. For the electrical system applied in offshore oil/gas
Table 8-6 Load Schedule for an Electrohydraulic Control System [3]
Operation TypePowerRequirement
Frequency(per day) Duration
HPU Intermittent 11 kW/pump 2 2 min
Single valve
actuation
Intermittent 10 W 1e3 2 sec
Choke valve
actuation
Intermittent or
continuous
10 W (int) N/A 2 sec (int)
SEM Continuous Max of 80 W d dSensors Continuous Max of 50 W d d
Table 8-7 Load Schedule for an All-Electric Control System [3]
Operation TypePowerRequirement
Frequency(/day) Duration
Single valve
actuation
Intermittent 3e5 kW 1~3 45e60 sec.
Single valve
normal
operation
Continuous 20e50 W d d
Choke valve
actuation
Intermittent or
continuous
1e2 kW (int)
60 W (cont)
N/A 2 sec (int)
SEM Continuous Max of 80 W d dSensors Continuous Max of 50 W d d
Subsea Power Supply 231
fields, the power transmission can be from onshore or offshore. Offshore
power transmission can occur on the surface or subsea.
8.2.3.1. Power Supply from Topside UPSTypically, the electrical power supply for a subsea production system is from
the UPS, which has its own rechargeable batteries.
Figure 8-4 shows that for an electrohydraulic control system type, the
UPS supplies electrical power to the MCS, EPU, and HPU, which then
combines the power and other data to the TUTU.
Figure 8-5 shows a picture of a UPS and battery rack. The UPS protects
the system from electrical power surges and blackouts. Electric power
should be supplied from the host platform main supply. The UPS typically
operates by rectifying and smoothing the incoming supply, converting it to
DC, which can then be used to charge associated batteries. The output from
the batteries is then converted back to AC and is ready for use to power the
Figure 8-4 Electrical Power Supply from UPS for Subsea Production System
Figure 8-5 UPS and Battery Rack
232 Y. Bai and Q. Bai
subsea system. In the case of failure of the main incoming supply, the output
from the batteries is quickly switched to power the DC-to-AC converter,
thus ensuring a constant supply.
UPS systems are well known in industry, offices, and today even at home
in situations where a power-consuming device must not lose its power
supply. UPSs are available in small versions which are able to provide power
from about 100 W up to several hundred kilowatts for from a few minutes
Subsea Power Supply 233
up to many hours. During this time span the critical equipment supplied
with power has either to be transferred into a power-off tolerable state or
external power has to be resupplied; that is, grid power has to return or
alternative power has to be provided. Usually the UPS is purchased from
a specialist manufacture of such devices and is not built by a subsea control
system supplier.
8.2.3.2. Power Supply from a Subsea UPSAUPS is always located as close as possible to the power-consuming device
to avoid as many fault sources as possible and is usually under control of the
responsible operator of the power-consuming device.
By installing a subsea UPS system, costs may be reduced because fewer
cables are required compared to having the UPS located topside because the
UPS can be fed from the subsea main power supply. The short-circuit level
of a UPS is low and the challenge of having enough short-circuit power
available in a subsea installation to achieve the correct relay protection and
discrimination philosophy can be solved by having the UPS subsea close to
the power consumers.
In general, a subsea UPS can be used in all applications where distri-
bution of low voltage (typically 400 V) is required subsea. The following are
typical consumers of low-voltage subsea power supplied by a UPS:
• Several control systems located in a geographically small area;
• Electric actuators for valves;
• Magnetic bearings;
• Switchgear monitoring and control;
• Measuring devices for current and voltage in switchgear, transformers,
motors, and other electrical installations.
A conventional UPS comprises an energy storage means and two power
converters. A control and monitoring system is also a part of a UPS. Because
power conversion involves losses resulting in heat, UPS systems may need
cooling systems to transfer the heat to a heat sink [4].
The UPS should be designed to operate safely in the sited environment.
The UPS is designed to enable the system to ride through short (seconds to
minutes) power losses and to permit sufficient time for a graceful shutdown
if necessary.
8.2.3.3. Power Supply from Subsea GeneratorsElectrical power can also come from subsea generators. Several types of
subsea generators have been used in subsea field developments.
234 Y. Bai and Q. Bai
Autonomous systems consist of an electrical power source, which is
typically seawater batteries or thermoelectric couplers. The power source
utilizes the difference in temperature between the well stream and ambient
seawater. The seawater battery solution requires a DC-to-AC converter to
transform the voltage from, for example, 1 to 24 V (e.g., an SEM requires
a 24-Velectrical power supply). A seawater battery should have the capacity
to operate the system for 5 years or more. The thermocoupler solution
requires an accumulator to be able to operate the system when the well is
not producing.
8.2.4. Electrical Power Unit (EPU)The EPU shown in Figure 8-6 supplies dual, isolated, single-phase power
for the subsea system through the composite service umbilical, together
with power supply modules for the MCS and HPU.
Figure 8-6 Electrical Power Unit (EPU)
Subsea Power Supply 235
The EPU supplies electrical power at the desired voltage and frequency
to subsea users. Power transmission is performed via the electrical umbilical
and the subsea electrical distribution system.
The EPU should be designed to operate safely in the sited environment
and allow for individual pair connection/disconnection and easy access to
individual power systems for maintenance and repair. The EPU should
contain redundant communication modems and filters to allow user defi-
nition of system monitoring, operation, and reconfiguration unless those
modems reside in the MCS. The EPU prevents the potential damage (to
subsea control modules and MCS) caused by voltage spikes and fluctuations
and receives input voltage from a UPS.
The EPU usually has two outputs: a DC busbar and an AC line. The
energy storage units are tapped to the DC busbar, whereas the AC output is
connected to the SEM.
The typical features of the EPU are as follows [5]:
• Fully enclosed, proprietary powder-coated steel enclosure, incorporated
into the MCS suite, with front and rear access;
• Standard design suitable for safe area, that is, a nonhazardous gases area
and air-conditioned environment;
• Dedicated dual-channel power supplies, including fault detection to the
subsea electronics module;
• Modems and signal isolation to effect the “communications on power”
transmission system;
• Control and monitoring to the master control station;
• Electrical power backup input terminal in the event of a power supply
outage to both the MCS and EPU.
8.2.5. Electrical Power DistributionThe subsea electrical distribution system distributes electrical power and
signals from the umbilical termination head to each well. As introduced in
Chapter 3, electrical power (as well as hydraulic pressure, chemical supply,
and communications) is provided to a subsea system through an electro-
hydraulic umbilical.
The SUTA is the main distribution point for the electrical supplies (also
hydraulic and chemical) to various components of a subsea production
system. The SUTA is permanently attached to the umbilical. Hydraulic and
chemical tubes from the umbilical can have dedicated destinations or may be
shared between multiple subsea trees, manifolds, or flowline sleds.
236 Y. Bai and Q. Bai
Electrical cables from the umbilical can also have dedicated destinations
to electrical components of a subsea production system or may be shared by
multiple SCMs or other devices. The electrical connection is made through
electrical connectors on electrical flying leads (EFLs). The number of
electrical connectors in series should be kept to a minimum. Redundant
routing should, if possible, follow different paths. To minimize electrical
Figure 8-7 Electrical Distribution in Subsea Production System
Subsea Power Supply 237
stresses on conductive connectors, voltage levels should be kept as low as
practical. Figure 8-7 shows the electrical as well as hydraulic power distri-
bution in subsea production system.
Connection of electrical distribution cabling and electrical jumpers
should be made by ROV or diver using simple tools, with minimum
implications on rig/vessel time. Manifold electrical distribution cabling and
jumper cables from the umbilical termination to the SCM should be
repairable or reconfigurable by the ROVor diver.
The subsea electrical power distribution system differs from a topside
system by being a point-to-point system with limited routing alternatives.
The number of components shall be kept to a minimum, without losing
required flexibility. Detailed electrical calculations and simulations are
mandatory to ensure operation/transmission of the high-voltage distribu-
tion network under all load conditions (full load, no load, rapid change in
load, short circuits).
8.3. HYDRAULIC POWER SYSTEM
The hydraulic power system for a subsea production system provides a stable
and clean supply of hydraulic fluid to the remotely operated subsea valves.
The fluid is supplied via the umbilical to the subsea hydraulic distribution
system, and to the SCM to operate subsea valve actuators. Figure 8-8
illustrates a typical hydraulic power system.
Hydraulic systems for control of subsea production systems can be
categorized in two groups:
• Open circuits where return fluid from the control module is exhausted
to the sea;
• Closed circuits where return fluid is routed back to the HPU through
a return line.
Open circuits utilize simple umbilicals, but do need equipment to
prevent a vacuum in the return side of the system during operation.
Without this equipment, a vacuum will occur due to a check valve in the
exhaust line, mounted to prevent seawater ingress in the system. To avoid
creating a vacuum, a bladder is included in the return line to pressure
compensate the return line to the outside water.
The hydraulic system comprises two different supply circuits with
different pressure levels. The LP supply will typically have a 21.0-MPa
differential pressure. The HP supply will typically be in the range of 34.5 to
Figure 8-8 Typical Hydraulic Power System
238 Y. Bai and Q. Bai
69.0 Mpa (5000 to 10,000 psi) differential pressure. The LP circuits are used
for subsea tree and manifold functions, whereas the HP circuit is for the
surface-controlled subsurface safety valve (SCSSV).
The control valves used in a hydraulic control system will typically be
three-way, two-position valves that reset to the closed position on loss of
hydraulic supply pressure (fail-safe closed). The valves will typically be pilot
operated with solenoid-operated pilot stages to actuate the main selector
valve. To reduce power consumption and solenoid size, but increase
Subsea Power Supply 239
reliability, it is common practice to operate the pilot stages for the HP valves
on the lower pressure supply.
8.3.1. Hydraulic Power Unit (HPU)The HPU is a skid-mounted unit designed to supply water-based biode-
gradable or mineral oil hydraulic fluid to control the subsea facilities that
control the subsea valves. Figure 8-9 shows a typical HPU.
The HPU normally consists of the following components:
• Pressure-compensated reservoir;
• Electrical motors;
• Hydraulic pumps;
• Accumulators;
• Control valves;
• Electronics;
• Filters;
• Equipment to control start and stop of pumps.
Figure 8-10 shows a typical hydraulic power unit schematic. As introduced
before, the hydraulic power unit includes two separate fluid reservoirs. One
reservoir is used for filling of new fluid, return fluid from subsea (if
implemented), and return fluid from depressurization of the system. The
other reservoir is used for supplying clean fluid to the subsea system.
Figure 8-9 Hydraulic Power Unit (HPU) (Courtesy of Oceaneering)
Figure 8-10 Typical Hydraulic Power Unit Schematic
240Y.Baiand
Q.Bai
Subsea Power Supply 241
The HPU also provides LP and HP hydraulic supplies to the subsea
system. Self-contained and totally enclosed, the HPU includes duty and
backup electrically driven hydraulic pumps, accumulators, dual redundant
filters, and instrumentation for each LP and HP hydraulic circuit. The unit
operates autonomously under the control of its dedicated programmable
logic controller (PLC), which provides interlocks, pump motor control, and
an interface with the MCS.
Dual hydraulic supplies are provided at both high pressure (SCSSV
supply) and low pressure (all other functions). LP supplies are fed to the
internal SCM headers via a directional control changeover valve. The
changeover valve should be independently operated from the HMI, such
that the header can be connected to either supply. Supply pressure
measurement should be displayed. HP supplies should be controlled and
monitored in a similar manner. The hydraulic discharge pressure of each
function is monitored and displayed on the HMI.
8.3.1.1. AccumulatorsAccumulators on the HPU should provide pump pressure damping
capabilities. They should have sufficient capacity for the operation of all
valves on one subsea tree with the HPU pumps disabled. Accumulators
would also be of sufficient capacity to accommodate system cycle rate
and recharging of the pumps. If all electric power to pumps was lost,
the accumulator would have sufficient capacity to supply certain
redundancies.
8.3.1.2. PumpsAll pumps should be operational when initially charging the accumulators
or initially filling the system on start-up. The pump (and accumulator)
sizes should be optimized to avoid excessive pump cycling and premature
failure.
The quantity of pumps (and other components) per supply circuit
should be determined through a reliability analysis. Pump sizing is deter-
mined by hydraulic analysis. Both analyses are performed prior to starting
the detailed design for the HPU. Pulsation dampeners are provided
immediately downstream of the pumps, if required, for proper operation of
the HPU.
All pumps should be electrically driven, supplied from the platform
electrical power system. Pumps should have the capacity to quickly regain
operating pressures after a hydraulic depressurization of all systems.
242 Y. Bai and Q. Bai
There are different types of pumps, but the most common type uses
accumulators that are charged by fixed pumps. These pumps, which start
and stop at various preprogrammed pressures, are controlled by a PLC.
8.3.1.3. ReservoirThe HPU has a low-pressure fluid storage reservoir to store control
fluid and a high-pressure (3000-psi) storage reservoir. One of the two
separate fluid reservoirs is used for filling of new fluid, return fluid from
subsea (if implemented), and return fluid from depressurization of the
system. The other reservoir is used for supplying clean fluid to the subsea
system.
Fluid reservoirs should be made from stainless steel and equipped with
circulating pumps and filters. Sample points should be made at the lowest
point of the reservoir and at pump outlets [6]. The hydraulic fluid reservoirs
should also be equipped with visual level indicators. Calibration of level
transmitters should be possible without draining of tanks.
The HPU reservoir should contain level transmitters, level gauges, drain
ports, filters, air vents, and an opening suitable for cleanout. The supply and
return reservoirs may share a common tank structure utilizing a baffle for
separation of clean and dirty fluid. The baffle should not extend to the top of
the reservoir so that fluid from overfilling or ESD venting can spill over into
the opposite reservoir.
Level SensorThe reservoir level-sensing system should meet the following requirements:
• The low-level switch should be at a level sufficient to provide
a minimum of 5 min of pump operating time.
• The low-level switch should be located at a level above the drain port to
prevent the pumps from ingesting air into the suctions.
• The high-level switch should be located at a level equal to 90% of the
reservoir capacity.
Control FluidThe control fluids are oil-based or water-based liquids that are used to
convey control and/or hydraulic power from the surface HPU or local
storage to the SCM and subsea valve actuators. Both water-based and oil-
based fluids are used in hydraulic systems.
The use of synthetic hydrocarbon control fluids has been infrequent in
recent years, and their use is usually confined to electrohydraulic control
Subsea Power Supply 243
systems. Water-based hydraulic fluids are used most extensively. The char-
acteristics of high water content–based control fluids depend on the
ethylene glycol content (typically 10% to 40%), and viscosity varies with
temperature (typically 2� to 10�C). Because government regulations do not
allow venting of mineral-based oil into the sea, if the system uses this type of
fluid, it must be a closed-loop system, which adds an extra conduit in the
umbilical, making it more complex. Required fluid cleanliness for control
systems is Class 6 of National Aerospace Standard (NAS) 1638 [7].
The water-based hydraulic fluid should be an aqueous solution. The
oil-based hydraulic fluid should be a homogeneous miscible solution. The
fluid should retain its properties and remain a homogeneous solution,
within the temperature range, from manufacture through field-life
operation.
The first synthetic hydrocarbon control fluid was utilized on Shell’s
Cormorant Underwater Manifold Centre in the early 1980s. This type of
control fluid has low viscosity, great stability, and excellent materials
compatibility, and is tolerant of seawater contamination. This fluid requires
the control system to incorporate return lines and an oil purification system
(filter, vacuum dehydration to remove water). The cost of synthetic
hydrocarbon control fluids is approximately four times that of mineral
hydraulic oils.
The first water-based control fluid was utilized on Statoil’s Gullfaks
development in the early 1980s. This type of control fluid has a very low
viscosity and is discharged to the sea after use. This fluid requires the control
system to incorporate higher specification metals, plastics, and elastomers.
The cost of water-based control fluids is approximately twice that of mineral
hydraulic oils.
Control fluid performance influences control system safety, reliability,
and cost of ownership. Control fluids also affect the environment. The
control fluid performances are as follows:
• The control fluid must be capable of tolerating all conditions and be
compatible with all materials encountered throughout the control
system.
• The control fluid is a primary interface between components and
between subsystems. It is also an interface between different but con-
nected systems.
• To maintain control system performance, system components must
continue to function within their performance limits for the life of the
systemdand that includes the control fluid.
244 Y. Bai and Q. Bai
• Any reduction in control fluid performance can have an adverse effect
throughout the control system. The factors that can reduce the
performance of a control fluid in use are as follows:
• Conditions exceeding the operating parameters of the control fluid;
• Poor product stability, resulting in a reduction in control fluid
performance over time;
• Contaminants interfering with the ability of the control fluid to
function.
8.3.1.4. Control and MonitoringThe HPU is typically supplied with an electronic control panel, including
a small PLC with a digital display, control buttons, and status lamps. The
electronics interface with other system modules, for remote monitoring and
control.
The HPU parameters monitored from the safety automation system
should typically be:
• Nonregulated supply pressure;
• Regulated supply pressure;
• Fluid levels;
• Pump status;
• Return flow (if applicable).
The control panel may be a stand-alone or an integral part of the HPU.
It utilizes a series of valves to direct the hydraulic and/or electric signals or
power to the appropriate functions.
Displays should be required to indicate hydraulic power connections
from the HPU to the topside umbilical termination (or distribution) units,
riser umbilicals, and subsea distribution to the individual hydraulic supplies
to the SCMs. Links should be provided to individual hydraulic circuit
displays.
REFERENCES[1] U.K. Subsea, Kikeh – Malaysia’s First Deepwater Development, Subsea Asia, 2008.[2] A.L. Sheldrake, Handbook of Electrical Engineering: For Practitioners in the Oil, Gas
and Petrochemical Industry, John Wiley & Sons Press, West Sussex, England, 2003.[3] M. Stavropoulos, B. Shepheard, M. Dixon, D. Jackson, Subsea Electrical Power
Generation for Localized Subsea Applications, OTC 15366, Offshore TechnologyConference, Houston, 2003.
[4] G. Aalvik, Subsea Uninterruptible Power Supply System and Arrangement, Interna-tional Application No. PCT/NO2006/000405, 2007.
Subsea Power Supply 245
[5] Subsea Electrical Power Unit (EPU). http://www.ep-solutions.com/solutions/CAC/Subsea_Production Control_System_SEM.htm., 2010.
[6] NORSOK Standards, Subsea Production Control Systems, NORSOK, U-CR-005,Rev. 1. (1995).
[7] National Aerospace Standard, Cleanliness Requirements of Parts Used in HydraulicSystems, NAS, 1638, 2001.