Study of Elements of a 22013233kv Substation

  • Upload
    arvind

  • View
    221

  • Download
    0

Embed Size (px)

Citation preview

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    1/67

    In our project we are going to study about the operation of different equipments in

    substation. It includes study of transmission lines, bus bars, circuit breakers, isolators,

    earth switches, various types of transformers such as power transformer, capacitor

    voltage transformer, current transformers, lightning arresters, wave traps and grounding

    system of substation. We will also discuss about the various protection scheme applied in

    the substation for this equipments.

    The protection system is designed to limit the effects of disturbances in power

    system, which when allowed persisting, may damage the substation and interrupt the

    supply of electrical energy. It covers various types of protection used in substation for

    220/132/33 KV transmission lines such as bus bar protection relays, auto reclosing

    schemes, etc.,

    The present day electrical power system is AC i.e., electric power is generated,

    transmitted and distributed in the form of alternating current. The electric power is

    produced at the power stations which are located at favourable places, generally quite

    away from the consumers. It is delivered to the consumers through a large network of

    transmission and distribution. At many places in the line of the power, it may be desirable

    and necessary to change some characteristics of power supply. This is accomplished by

    suitable apparatus called Substation.

    Generating voltage at the power station is stepped upto high voltage for

    transmission of electric power. The assembly of apparatus used for this purpose is the

    substation. Similarly,near the consumers localities, the voltage may have to be stepped

    down to utilization level. This job is again accomplished by a suitable apparatus called

    substation. The type of equipment needed in the substation will depend upon the servicerequirement.

    1

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    2/67

    2.1 Introduction

    An electrical substation is a subsidiary station of an electricity generation,

    transmission and distribution system where voltage is transformed from high to low or

    the reverse using transformers. Electric power flows through several substations between

    generating plant and consumer changing the voltage level in several stages.

    A substation that has a step-up transformer increases the voltage with decreasing

    current, while a step-down transformer decreases the voltage with increasing the current

    for domestic and commercial distribution. The word substation comes from the days

    before the distribution system became a grid. At first substations were connected to only

    one power station where the generator was housed and were subsidiaries of that powerstation.

    2.2 Elements of Substation

    Substations generally contain one or more transformers and have switching,

    protection and control equipment. In a large substation, circuit breakers are used to

    interrupt any short-circuits or overload currents that may occur on the network. Smaller

    distribution stations may use re-closer circuit breakers or fuses for protection of branch

    circuits. A typical substation will contain line termination structures, high-voltage

    switchgear, one or more power transformers, low voltage switchgear, surge protection,

    controls, grounding (earthing) system, and metering. Other devices such as power factor

    correction capacitors and voltage regulators may also be located at a substation.

    Substations may be on the surface in fenced enclosures, underground, or located in

    special-purpose buildings.

    High-rise buildings may have indoor substations. Indoor substations are usually

    found in urban areas to reduce the noise from the transformers, to protect switchgear

    from extreme climate or pollution conditions.

    2

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    3/67

    2.3 Types of Substation

    Substations are of three types. They are:

    a) Transmission Substation

    b) Distribution Substation

    c) Collector Substation

    a) Transmission Substation

    A transmission substation connects two or more transmission lines. The simplestcase is where all transmission lines have the same voltage. In such cases, the substation

    contains high-voltage switches that allow lines to be connected or isolated for fault

    clearance or maintenance. A transmission station may have transformers to convert the

    voltage from voltage level to other, voltage control devices such as capacitors, reactors or

    Static VAR Compensators and equipment such as phase shifting transformers to control

    power flow between two adjacent power systems. The largest transmission substations

    can cover a large area (several acres/hectares) with multiple voltage levels, many circuit

    breakers and a large amount of protection and control equipment (voltage and current

    transformers, relays and SCADA systems). Modern substations may be implemented

    using International Standards such as IEC61850.

    b) Distribution Substation

    A distribution substation transfers power from the transmission system to the

    distribution system of an area. It is uneconomical to directly connect electricity

    consumers to the high-voltage main transmission network, unless they use large amounts

    of power. So the distribution station reduces voltage to a value suitable for local

    distribution. The input for a distribution substation is typically at least two transmission

    or sub transmission lines. Input voltage may be, for example, 220KV or whatever is

    3

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    4/67

    common in the area. Distribution voltages are typically medium voltage, between 33 and

    66 kV depending on the size of the area served and the practices of the local utility.

    Besides changing the voltage, the job of the distribution substation is to isolate

    faults in either the transmission or distribution systems. Distribution substations may also

    be the points of voltage regulation, although on long distribution circuits (several

    km/miles), voltage regulation equipment may also be installed along the line.

    Complicated distribution substations can be found in the downtown areas of large

    cities, with high-voltage switching and, switching and backup systems on the low-voltage

    side. Most of the typical distribution substations have a switch, one transformer, and

    minimal facilities on the low-voltage side.

    c) Collector substation

    In distributed generation projects such as a wind farm, a collector substation may

    be required. It somewhat resembles a distribution substation although power flow is in

    the opposite direction. Usually for economy of construction the collector system operates

    around 35 KV, and the collector substation steps up voltage to a transmission voltage for

    the grid. The collector substation also provides power factor correction, metering and

    control of the wind farm.

    2.4 Substation Transformer Type

    Further, transmission substations are mainly classified into two types depending on

    changes made to the voltage level. They are:

    a) Step-Up Transmission Substations.

    b) Step-Down Transmission Substations.

    4

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    5/67

    a) Step-Up Transmission Substation

    A step-up transmission substation receives electric power from a near by

    generating facility and uses a large power transformer to increase the voltage for

    transmission to distant locations.

    There can also be a tap on the incoming power feed from the generation plant to

    provide electric power to operate equipment in the generation plant.

    b) Step-Down Transmission Substation

    Step-down transmission substations are located at switching points in an electrical

    grid. They connect different parts of a grid and are a source for sub transmission lines or

    distribution lines.

    2.5 General Considerations

    The general considerations regarding the substation that are discussed are

    functions,design and different layouts of the substation.

    a) The Functions of the substation are:

    i. To Change voltage from one level to another.

    ii.To Regulate voltage to compensate for system voltage changes.

    iii. To Switch transmission and distribution circuits into and out of the grid system.

    iv. To Measure electric power quantity flowing in the circuits.

    v. To Connect communication signals to the circuits.

    vi. To Eliminate lightning and other electrical surges from the system.

    vii. To Connect electric generation plants to the system.

    5

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    6/67

    viii. To Make interconnections between the electric systems of more than one utility.

    b) Design

    The main issues facing a power engineer are reliability and cost. A good design

    attempts to strike a balance between these two to achieve sufficient reliability without

    excessive cost. The design should also allow easy expansion of the station, if required .

    Selection of the location of a substation must consider many factors. Sufficient

    land area is required for installation of equipment with necessary clearances for electrical

    safety and for access to maintain large apparatus such as transformers. Where land is

    costly such as in urban areas, gas insulated switchgear may save money overall. The site

    must have room for expansion due to load growth or planned transmission additions.

    Environmental effects of the substation must be considered such as drainage, noise and

    road traffic effects. Grounding (earthing) and ground potential rise must be calculated to

    protect passers-by during a short-circuit in the transmission system. And of course, the

    substation site must be reasonably central to the distribution area to be served.

    c) Different Layouts for Substation

    i) Single Bus Bar: With this design, there is an ease of operation of the substation.

    This design also places minimum reliance on signaling for satisfactory operation of

    protection. Additionally there is the facility to support the economical operation of future

    feeder bays.

    Fig 2.1 shows single bus bar Substation

    6

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    7/67

    Such a substation has the following characteristics.

    a. Each circuit is protected by its own circuit breaker and hence plant outage does

    not necessarily result in loss of supply.

    b. A fault on the feeder or transformer circuit breaker causes loss of the transformer

    and feeder circuit, one of which may be restored after isolating the faulty circuit

    breaker.

    c. A fault on the bus section circuit breaker causes complete shutdown of the

    substation. All circuits may be restored after isolating the faulty circuit breaker.

    d. A bus-bar fault causes loss of one transformer and one feeder. Maintenance of one

    bus-bar section or isolator will cause the temporary outage of two circuits.

    e. Maintenance of a feeder or transformer circuit breaker involves loss of the circuit.

    ii) Mesh Substation

    The general layout for a full mesh substation is shown in the schematic Fig2.2

    The characteristics of such a substation are as follows

    a. Operation of two circuit breakers is required to connect or disconnect a circuit,

    and disconnection involves opening of a mesh.

    b. Circuit breakers may be maintained without loss of supply or protection, and no

    additional bypass facilities are required.

    c. Bus-bar faults will only cause the loss of one circuit breaker. Breaker faults will

    involve the loss of a maximum of two circuits.

    d. Generally, not more than twice as many outgoing circuits as infeeds are used in

    order to rationalise circuit equipment load capabilities and rating.

    Mesh substation

    7

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    8/67

    Fig 2.2 shows mesh substation.

    2.6 Layout

    a) Principle of Substation Layouts

    Substation layout consists essentially in arranging a number of switchgear

    components in an ordered pattern governed by their function and rules of spatial

    separation.

    b) Spatial Seperation

    i. Earth Clearance: This is the clearance between live parts and earthed structures,

    walls, screens and ground.

    ii. Phase Clearance: This is the clearance between live parts of different phases.

    iii. Isolating Distance: This is the clearance between the terminals of an isolator and

    the connections.

    iv. Section Clearance: This is the clearance between live parts and the terminals of a

    work section. The limits of this work section, or maintenance zone, may be the

    ground or a platform from which the man works .

    8

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    9/67

    c) Separation of maintenance zones

    Two methods are available for separating equipment in a maintenance zone that

    has been isolated and made dead.

    i. The provision of a section clearance

    ii. Use of an intervening earthed barrier

    The choice between the two methods depends on the voltage and whether horizontal

    or vertical clearances are involved.

    i. A section clearance is composed of the reach of a man taken as 8 feet plus an

    earth clearance.

    ii. For the voltage at which the earth clearance is 8 feet the space required will be the

    same whether a section clearance or an earthed barrier is used.

    2.7 Maintenance

    Maintenance plays a major role in increasing the efficiency and decreasing the

    breakdown. The rules and basic principle are discussed.

    Separation by earthed barrier = Earth Clearance + 50mm for barrier + Earth Clearance

    Separation by section clearance = 2.44m + Earth clearance

    i. For vertical clearances it is necessary to take into account the space occupied by

    the equipment and the need for an access platform at higher voltages.

    ii. The height of the platform is taken as 1.37m below the highest point of work.

    Maintenance is done through two ways:

    a) By Establishing Maintenance Zones.

    b) By Electrical Separations.

    9

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    10/67

    a) Establishing Maintenance Zones

    Some maintenance zones are easily defined and the need for them is self evident

    as in the case of a circuit breaker. There should be a means of isolation on each side of

    the circuit breaker, and to separate it from adjacent live parts when isolated either by

    section clearances or earth barriers

    b) Electrical Separations

    Together with maintenance zoning, the separation, by isolating distance and phase

    clearances, of the substation components and of the conductors interconnecting them

    constitute the main basis of substation layouts.

    There are at least three such electrical separations per phase that are needed in a

    circuit:

    i. Between the terminals of the bus bar isolator and their connections.

    ii. Between the terminals of the circuit breaker and their connections.

    iii. Between the terminals of the feeder isolator and their connections.

    2.8 Conclusion:

    We have studied in detail about the substation description and in the next chapter

    we are going to discuss about the line diagram of shapurnagar 220/132/33KV substation.

    10

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    11/67

    3.1 Introduction

    We are going to discuss about the line diagram and number of feeders of 220KV

    substation and the voltage that has been transmitted to other substations and inter

    connection of 220 KV line and also about the lines that feeds this substation from

    generating units.

    3.2 Line diagram:

    In power engineering, a one-line diagram or single-line diagram is a simplified

    notation for representing a three-phase power system. The one-line diagram has its

    largest application in power flow studies. Electrical elements such as circuit breakers,

    transformers, capacitors, bus bars, and conductors are shown by standardized schematic

    symbols. Instead of representing each of three phases with a separate line or terminal,

    only one conductor is represented. It is a form of block diagram graphically depicting the

    paths for power flow between entities of the system. Elements on the diagram do not

    represent the physical size or location of the electrical equipment, but it is a common

    convention to organize the diagram with the same left-to-right, top-to-bottom sequence as

    the switchgear or other apparatus represented.

    We are getting power supply from two thermal power plants one is KTPS1 and

    the other from which have two lines, named as Malkaram1 & Malkaram 2.

    The single line diagram of 220/132/33 kV SHAPUR NAGAR sub station is

    shown at the end of this report.

    3.3 The interconnection of 220 KV Grid Substations

    The interconnection of 220KV to different grid substations is given below,220 KV SHAPURNAGAR - GACHIBOWLI circuit No. 1.

    220 KV SHAPURNAGAR - GACHIBOWLI circuit No. 2.

    220 KV SHAPURNAGAR - GACHIBOWLI circuit No. 3.

    220 KV SHAPURNAGAR - GACHIBOWLI circuit No. 4.

    11

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    12/67

    3.4 Feeders

    Feeder circuits are the connections between the output terminals of a

    distribution substation and the input terminals of primary circuits. The distribution feeder

    circuit conductors leave the substation from a circuit breaker via underground cables,

    called substation exit cables. The underground cables connect to a nearby overhead

    primary circuit outside the substation. This eliminates multiple circuits on the poles

    adjacent to the substations there by improving the overall appearance of the substation.

    Fig.3.1 shows 3-phase distribution feeder bay

    This substation has two types of feeder i.e. 132 KV and 33 KV feeder. They are

    12 feeders of 132 KV which are basically collector substation and it has 16 feeders of33KV which are industries and for domestic user.

    a) The interconnection of 132KV Grid Substations

    The interconnection of 132KV to different grid substations is given below,

    i. SHAPURNAGAR - MEDCHAL- I circuit No.1.ii. SHAPURNAGAR - MEDCHAL-I circuit No. 2.

    iii. SHAPURNAGAR - R.C.PURAM.

    iv. SHAPURNAGAR - NARSAPUR.

    v. SHAPURNAGAR - ALER.vi. SHAPURNAGAR - GUMMADI DALA.

    vii. SHAPURNAGAR - BHONIGIR.viii. SHAPURNAGAR - GUNROCK.

    ix. SHAPURNAGAR - MOULALI.

    x. SHAPURNAGAR - IDPL.xi. SHAPURNAGAR - SANATHNAGAR RAILWAY.

    xii. SHAPURNAGAR - BOLLARAM.

    12

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    13/67

    b) The interconnection of 33KV Grid Substations

    The interconnection of 33KV to different substations is given below,

    i. SHAPURNAGAR - SHAPURNAGAR

    ii. SHAPURNAGAR - JEEDIMETLA circuit No.1iii. SHAPURNAGAR - JEEDIMETLA circuit No.2iv. SHAPURNAGAR - JEEDIMETLA circuit No.3

    v. SHAPURNAGAR - JEEDIMETLA circuit No. 4

    vi. SHAPURNAGAR - SATYAM circuit No. 1vii. SHAPURNAGAR - SATYAM circuit No. 2

    viii. SHAPURNAGAR - JAIRAJ circuit No.1

    ix. SHAPURNAGAR - JAIRAJ circuit No. 2x. SHAPURNAGAR - AIRFORCE ACADEMY circuit No. 1

    xi. SHAPURNAGAR - AIRFORCE ACADEMY circuit No. 2

    xii. SHAPURNAGAR - RCC

    xiii. SHAPURNAGAR - B.PALLIYxiv. SHAPURNAGAR - H.A.L

    xv. SHAPURNAGAR - IDPL

    xvi. SHAPURNAGAR - H.M.T

    3.5 Conclusion

    We have discussed about the line diagram of 220 KV Shapurnagar substation and

    interconnection of this substation with other grid and number of feeders that are

    connected to this substation and in the next chapter we are going to discuss about the

    transformers.

    13

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    14/67

    4.1 Introduction

    We are going to discuss about the basic principle of transformer, working,

    construction, losses, application and the transformers used in substation and their tapping

    details.

    a) Definition

    A transformer is a device that transfers electrical energy from one circuit to

    another through inductively coupled conductors through the transformer's coils or

    windings. Except for air-core transformers, the conductors are commonly wound around

    a single iron-rich core, or around separate but magnetically-coupled cores. A varying

    current in the primary winding creates a varying magnetic field in the core (or cores) of

    the transformer. This varying magnetic field induces a varying electromotive force

    (EMF) or voltage in the secondary winding. This effect is called mutual induction.

    b) Basic Principle

    The transformer is based on two principles. Firstly, an electric current can produce a

    magnetic field (electromagnetism) and secondly that a changing magnetic field within

    the a coil of wire induces a voltage across the ends of the coil (electromagnetic

    induction). Changing the current in the primary coil changes the magnitude of the

    magnetic field. The changing magnetic flux link with the secondary coil where a voltage

    is induced across its ends.

    Fig 4.1 shows step down transformer

    14

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    15/67

    A simplified transformer design is shown in Fig 4.1. A current passing through

    the primary coil creates a varying magnetic field. The primary and secondary coils are

    wrapped around a core of very high magnetic permeability, such as iron, This ensures

    that most of the magnetic field lines produced by the primary current are within the iron

    core and pass through the secondary coil as well as the primary coil. Transformers are

    essential for high voltage power transmission, which makes long distance transmission

    economically practical.

    c) Practical Considerations

    i. Effect of frequency

    The time-derivative term in Faraday's Law shows that the flux in the core is the

    integral of the applied voltage. Hypothetically an ideal transformer would work with

    direct-current excitation, with the core flux increasing linearly with time. In practice, the

    flux would rise to the point where magnetic saturation of the core occurs, causing a huge

    increase in the magnetizing current and overheating the transformer. All practical

    transformers must therefore operate with alternating current.

    ii. Transformer universal EMF equation

    If the flux in the core is sinusoidal, the relationship for either winding between its

    Voltage of the winding E, and the supply frequency f, number of turns N, core cross-

    sectional area a and peak magnetic flux density B is given by the universal EMF

    equation:

    The EMF of a transformer at a given flux density increases with frequency. By

    operating at higher frequencies, transformers can be physically more compact because a

    given core is able to transfer more power without reaching saturation and fewer turns are

    needed to achieve the same impedance.

    15

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    16/67

    However properties such as core loss and conductor skin effect also increase with

    frequency. Aircraft and military equipment employ 400 Hz power supply which reduce

    core and winding weight.

    iii. Energy Losses

    An ideal transformer would have no energy losses, and would be 100% efficient.

    In practical transformers energy is dissipated in the windings, core, and surrounding

    structures. Larger transformers are generally more efficient, and those rated for electricity

    distribution usually perform better than 98%.Experimental transformers using

    superconducting windings achieve efficiencies of 99.85%, while the increase in

    efficiency is small, when applied to large heavily-loaded transformers the annual savings

    in energy losses are significant.

    Transformer losses are divided into losses in the windings, termed copper loss, and

    those in the magnetic circuit, termed iron loss. Losses in the transformer arise from:

    i. Winding resistance

    ii. Hysteresis losses

    iii. Eddy currents

    iv. Magnetostriction

    v. Mechanical losses

    vi. Stray losses

    16

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    17/67

    4.2 Construction

    The constructional details of the transformer are

    a.) Cores

    i Laminated steel cores

    ii Solid cores

    iii Toroidal cores

    iv Air cores

    b) Windings

    Windings are usually arranged concentrically to minimize flux leakage.

    Fig. 4.2(i) shows windings of transformer

    The Fig 4.2 (i) shows Cut view through transformer windings. White: insulator.

    Green spiral: Grain oriented silicon steel. Black: Primary winding made of oxygen-free

    copper. Red: Secondary winding. Top left: Toroidal transformer. Right: C-core, but E-

    core would be similar. The black windings are made of film.

    Top: Equally low capacitance between all ends of both the windings. Since most

    cores are at least moderately conductive they also need insulation at Bottom.

    17

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    18/67

    c) Coolant

    The oil reservoir is visible at the top. Radioactive fins aid the dissipation of heat

    Fig 4.2(ii) shows coolant of transformer

    High temperatures will damage the winding insulation. Power transformers rated

    up to several hundred KVA can be adequately cooled by natural convective air-cooling,

    sometimes assissted by fans. Some power transformers are immersed in transformer oil

    that both cools and insulates the windings. The oil is a highly refined mineral oil that

    remains stable at transformer operating temperature. The oil-filled tank often hasradiators through which the oil circulates by natural convection some large transformers

    employ forced circulation of the oil by electric pumps, aided by external fans or water-

    cooled heat exchangers.

    Oil-filled transformers undergo prolonged drying processes to ensure that the

    transformer is completely free of water vapuor before the cooling oil is introduced. This

    helps to prevent electrical breakdown under load. Oil-filled transformers may be

    equipped with Buchholz relays, which detect gas evolved during internal arcing and

    rapidly de-energize the transformer to avert catastrophic failure.

    Experimental power transformers in the 2 MVA range have been built with

    superconducting windings which eliminates the copper losses, but not the core steel loss

    but these are cooled by liquid nitrogen or helium.

    18

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    19/67

    d) Tappings

    No-load tap changers (NLTC) or load tap changers (LTC) can be obtained on

    power transformers.

    The addition of no-load taps in the primary of a substation transformer makes it

    possible to adapt the transformer to a range of supply voltages (usually a 10 percent

    overall range of which 5 percent is above nominal and 5 percent below nominal, usually

    in 2.5 percent steps). Since no-load taps are not capable of interrupting any current

    including transformer charging current, the transformers have to be de-energized when

    the manual no-load tap position is changed. All taps should have full capacity ratings.

    Any decision to use load tap changing transformers should be based on a carefulanalysis of the particular voltage requirements of the loads served and consideration of

    the advantages and disadvantages including costs of alternatives such as separate voltage

    regulators.

    e) Terminals

    Very small transformers will have wire leads connected directly to the ends of the

    coils and brought out to the base of the unit for circuit connections. Larger transformers

    may have heavy bolted terminals, bus bars or high-voltage insulated bushings made of

    polymers or porcelain.

    A large bushing can be of complex structure since it must provide careful control

    of the electric field gradient without letting the transformer leak oil.

    4.3 Types and Classification Factors

    A wide variety of transformer designs are used for different applications though

    they share several common features. Important common transformer types include:

    a. Auto transformer

    b. Poly Phase transformers

    19

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    20/67

    c. Leakage transformer

    d. Resonant transformers

    Instrument transformers

    Classification of Transformers is based on following factors.

    i. By power capacity: from a fraction of a volt-ampere (VA) to over a thousand

    MVA.

    ii. By frequency range: power, audio, or radio frequency.

    iii. By voltage class: from a few volts to hundreds of kilovolts.

    iv. By cooling type: air cooled, oil filled, fan cooled, or water cooled.

    v. By application: such as power supply, impedance matching, output voltage and

    current stabilizer, or circuit isolation.

    vi. By end purpose: distribution, rectifier, arc furnace, amplifier output.

    vii. By winding turns ratio: step-up, step-down, isolating (equal or near-equal ratio),

    and variable.

    Among the above mentioned transformers only instrument transformers are widely

    used in the sub station. Hence only instrument transformers are discussed in this

    section.

    4.3.1 Instrument Transformer:

    Instrument transformers are used to step-down the current or voltage to

    measurable values. They provide standardized, useable levels of current or voltage in a

    variety of power monitoring and measurement applications.

    Both current and voltage instrument transformers are designed to have

    predictable characteristics on overloads.

    Proper operation of over-current protection relays requires that current

    transformers provide a predictable transformation ratio even during a short circuit.

    20

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    21/67

    These are further classified into two types which are discussed below.

    a) Current Transformers

    b) Voltage Transformers

    a) Current Transformers:

    i. Principle of Operation

    A current transformer is defined as as an instrument transformer in which the

    secondary current is substantially proportional to the primary current (under normal

    conditions of operation) and differs in phase from it by an angle which is approximatelyzero for an appropriate direction of the connections. This highlights the accuracy

    requirement of the current transformer but also important is the isolating function, which

    means no matter what the system voltage the secondary circuit need to be insulated only

    for a low voltage.

    The current transformer works on the principle of variable flux. In the ideal current

    transformer, secondary current would be exactly equal (when multiplied by the turns

    ratio) and opposite to the primary current.

    But, as in the voltage transformer, some of the primary current or the primary

    ampere-turns are utilized for magnetizing the core, thus leaving less than the actual

    primary ampere turns to be transformed into the secondary ampere-turns. This naturally

    introduces an error in the transformation. The error is classified into current ratio error

    and the phase error.

    ii. Definitions:

    Typical terms used for specifying current transformer are,

    Rated primary current: The value of current which is to be transformed to a

    lower value. In CT parallence, the load of the CT refers to the primary current.

    21

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    22/67

    Rated secondary current: The current in the secondary circuit and on which the

    performance of the CT is based. Typical values of secondary current are 1 A or 5 A.

    Rated burden:The apparent power of the secondary circuit in Volt-amperes

    expressed at the rated secondary current and at a specific power factor.

    Composite Error: The RMS value of the difference between the instantaneous

    primary current and the instantaneous secondary current multiplied by the turns ratio,

    under steady state conditions.

    Accuracy limit factor:The value of primary current up to which the CT compiles

    with composite error requirements. This is typically 5, 10 or 15, which means that the

    composite error of the CT has to be within specified limits at 5, 10 or 15 times the rated

    primary current.

    Short time rating: The value of primary current (in kA) that the CT should be able

    to withstand both thermally and dynamically without damage to the windings with the

    secondary circuit being short-circuited. The time specified is usually 1 or 3 seconds.

    Class PS/ X CT: In balance systems of protection, CT s with a high degree of

    similarity in their characteristics are required. These requirements are met by Class PS

    (X) CT s. Their performance is defined in terms of a knee-point voltage (KPV), the

    magnetizing current (Image) at the knee point voltage or 1/2 or 1/4 the knee-point

    voltage, and the resistance of the CT secondary winding corrected to 75C. Accuracy is

    defined in terms of the turns ratio.

    Knee point voltage: The point on the magnetizing curve where an increase of

    10% in the flux density (voltage) causes an increase of 50% in the magnetizing force

    (current).

    Summation CT: When the currents in a number of feeders need not be

    individually metered but summated to a single meter or instrument, a summation current

    transformer can be used.

    22

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    23/67

    The summation CT consists of two or more primary windings which are

    connected to the feeders to be summated, and a single secondary winding, which feeds a

    current proportional to the summated primary current. A typical ratio would be 5+5+5/

    5A, which means that three primary feeders of 5 are to be summated to a single 5A

    meter.

    Core balance CT (CBCT): The CBCT, also known as a zero sequence CT, is used

    for earth leakage and earth fault protection. The concept is similar to the RVT. In the

    CBCT, the three core cable or three single cores of a three phase system pass through the

    inner diameter of the CT. When the system is fault free, no current flows in the secondary

    of the CBCT. When there is an earth fault, the residual current (zero phase sequence

    current) of the system flows through the secondary of the CBCT and this operates therelay. In order to design the CBCT, the inner diameter of the CT, the relay type, the relay

    setting and the primary operating current need to be furnished.

    Interposing CTs (ICTs): Interposing CTs are used when the ratio of

    transformation is very high. It is also used to correct for phase displacement for

    differential protection of transformer.

    iii. Standards: The Indian and international standard references for CT s are asgiven in the table 4.1.

    Table 4.1 shows standard reference for CTs

    iv. Typical specification for a 11 kV CT

    System voltage:11 kV

    StandardStandard Number Year

    Indian IS 2705 1992

    British BS 3938 1973

    American ANSI C.57.13 1978

    23

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    24/67

    Insulation level voltage (ILV) : 12/28/75 kV

    Ratio: 200/1 - 1 - 0.577 A

    Core 1: 1A, metering, 15 VA/class 1, ISF= 150 V,Img at Vk/2

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    25/67

    In a practical transformer, errors are introduced because some current is drawn for

    the magnetization of the core and because of drops in the primary and secondary

    windings due to leakage reactance and winding resistance. One can thus talk of a voltage

    error which is the amount by which the voltage is less than the applied primary voltage

    and the phase error which is the phase angle by which the reversed secondary voltage

    vector is displaced from the primary voltage vector.

    ii. Definitions

    Typical terms used for specifying a voltage transformer (VT) are:

    a. Rated primary voltage: This is the rated voltage of the system whose voltage is

    required to be stepped down for measurement and protective purposes.

    b. Rated secondary voltage: This is the voltage at which the meters and protective

    devices connected to the secondary circuit of the voltage transformer operations.

    c. Rated burden: This is the load in terms of volt-amperes (VA) posed by the

    devices in the secondary circuit on the VT. This includes the burden imposed by

    the connecting leads. The VT is required to be accurate at both the rated burden

    and 25% of the rated burden.

    d. Rated voltage factor: Depending on the system in which the VT is to be used,

    the rated voltage factors to be specified are different. The table 4.2 below is

    adopted from Indian and International standards.

    Table 4.2 shows rated votage factor for VTs

    Rated

    voltage

    factor

    Rated

    timeMethod of connecting primary winding in

    system

    1.2 Continuous Between phases in any network.

    Between transformer star-point and earth in any

    network.

    1.2

    1.5

    Continuous Between phase and in an effectively earthed

    neutral system.

    25

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    26/67

    1.2

    1.9

    Continuous

    for 30

    seconds

    Between phase and earth in a non-effectively

    earthed neutral system with automatic fault

    tripping.

    1.2

    1.9

    Continuous

    for 8 hours

    Between phase and earth in an isolated neutral

    system without automatic fault tripping or in aresonant earthed system without automatic fault

    tripping.

    e. Temperature class of insulation: The permissible temperature rise over the

    specified ambient temperature. Typically, classes E, B and F.

    f. Residual voltage transformer (RVT): RVTs are used for residual earth fault

    protection and for discharging capacitor banks. The secondary residual voltage

    winding is connected in open delta. Under normal conditions of operation, there is

    no voltage output across the residual voltage winding. When there is an earth

    fault, a voltage is developed across the open delta winding which activates the

    relay. When using a three phase RVT, the primary neutral should be earthed, or

    otherwise third harmonic voltages will appear across the residual winding. phase

    RVTs typically have 5 limb constructions.

    iii. Standards

    The Indian and international standard references for VT s are as given in the table

    below 4.3

    Table 4.3 shows standard references for VTs

    Standard

    Standard

    NumberYear

    26

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    27/67

    Indian IS 3156 1992

    British BS 3841 1973

    American ANSI C.57.13 1978

    Typical specification for a 11 kV VT

    System voltage: 11 kV

    Insulation level voltage (ILV): 12 /28/75 kV

    Number of phases: Three

    Vector Group: Star / Star

    Ratio: 11 kV/ 110 V

    Burden: 100 VA

    Accuracy: Class 0.5

    Voltage Factor: 1.2 continuous and 1.5 for 30 secondswith provision for fuse

    c) Coupling capacitor voltage transformers:

    Coupling capacitor voltage transformers, commonly termed capacitor voltage

    transformers (CVTs), are devices used for coupling to a power line to provide low

    voltage for the operation of relays and metering instruments.

    Power line carrier accessories or provisions for future installation of carrier

    accessories may be included in the base. Coupling capacitor voltage transformers are

    commonly supplied without carrier accessories, especially at voltages above 11 kV, as a

    more economical alternative to inductive voltage transformers. Coupling capacitor

    voltage transformers can be provided with the same ratings and accuracy as inductive

    voltage transformers

    Fig 4.2(iii)showing Coupling capacitor voltage transformers

    27

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    28/67

    However, because of the energy-storage capability of capacitors, sudden

    reductions in the power line voltage may result in momentary distortion of the CCVT

    secondary voltage. The amount of distortion is related to CCVT capacitance and the

    burden (secondary load) value and configuration. Modern CCVT designs are available to

    minimize this problem.

    4.3.2 Power Transformers

    Power transformers convert power-level voltages from one level or phase

    configuration to another. They can include features for electrical isolation, power

    distribution, and control and instrumentation applications

    EHV power transformers are usually oil immersed with all three phases in one

    tank. Auto transformers can offer advantage of smaller physical size and reduced losses.

    The different classes of power transformers are:

    i. O.N.: Oil immersed, natural cooling.

    ii. O.B.: Oil immersed, air blast cooling.

    iii. O.F.N.: Oil immersed, oil circulation forced.

    iv. OF.A.: Oil immersed, oil circulation forced, air blast cooling.

    Power transformers are usually the largest single equipment in a substation. For economy

    of service roads, transformers are located on one side of a substation and the connection to

    switchgear is by bare conductors. Because of the large quantity of oil, it is essential to take

    precaution against the spread of fire. Hence, the transformer is usually located around a sump

    used to collect the excess oil.

    4.4 TestsA number of routine and type tests have to be conducted on VT s and CTs before

    they can meet the standards specified above. The tests can be classified as:

    i. Accuracy tests

    ii. Dielectric insulation tests

    28

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    29/67

    iii. Temperature rise tests

    iv. Short circuit tests.

    4.5 Commissioning

    Once the unit is received and packing is opened first thing is to check whether

    there are any transit damages.

    In case of minor damages, such as loose screws or likewise, they can be attended

    immediately. In case of major damages, the report for this is to be sent to the supplier

    who can immediately attend these.

    Once the unit is found to have received in good condition, the following need to be

    checked

    i. Check the primary terminals.

    ii. Check the secondary terminals.

    iii. Check Earthing.

    iv. Check oil level

    v. Check Insulation Resistance: For primary (H.T) winding it should be minimum

    500m ohms with 1000V.D.C.Meggar and for secondary (L.T) winding. It should

    be minimum 25M ohms with 500V.D.C Merger.

    vi. Check Ratio- for this (a) Pass the rated primary current through primary

    (b) Check the secondary current across the respective Terminals.

    If everything is all right, put transformer into operation verification of terminal

    markings and polarity

    4.6 Applications and General Instructions

    There are certain applications of transformers and general instructions for

    erection, uses and maintenance.

    29

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    30/67

    a) Applications

    A major application of transformers is to increase voltage before transmitting

    electrical energy over long distances through wires. Wires have resistance and so

    dissipate electrical energy at a rate proportional to the square of the current through the

    wire. By transforming electrical power to a high-voltage (and therefore low-current) form

    for transmission and back again afterward, transformers enable economic transmission of

    power over long distances.

    b) General Instructions for erection

    These instructions should be adhered to with all types of instrument transformers

    regardless of their technical characteristics.

    i. The transformer can be lifted and moved only in vertical direction by means of

    transport equipment (crane, fork truck etc.).

    ii. It is forbidden to move transformer grasping it from insulator, head or high

    voltage connections.

    iii. It is required to undertake all necessary steps to prevent any metal part of

    transport equipment (ropes, chains and similar) from getting in touch with

    insulator thus avoiding damaging of glaze or insulator itself.

    iv. Transformers should be mounted on corresponding supports or base and firmly

    tightened for this purpose.

    v. Check up whether base to which transformer is fixed is in horizontal position.

    vi. Connecting cables/conductors by means of which transformer is connected to

    high voltage bus-bar or supply system should be correctly dimensioned placed

    and mounted not to cause additional over stresses of transformer connections.

    vii. Prior to the connection of transformer compare connection diagram with

    indications on the transformer and carryout connection in compliance with

    corresponding indications.

    viii.Properly carryout earthing on all intended spots on boxes and or base frame of

    transformers.

    30

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    31/67

    ix. Upon completion of above check up prior to putting in operation if assembly

    properly done.

    x. Put connected transformer on line.

    xi. Compare instrument indicated with operational condition in supply system.

    c) General Instructions for use

    i. Regular periodical inspection

    ii. Check up of all sealed spots in order to ascertain oil leak, if any

    iii. Cleaning of insulator and possible painting of transformer.

    iv. Check up of all placement of diaphragm and oil level in oil level indicators.

    v. In case of damage of diaphragm or if there is no oil level indicators,

    transformer should be thoroughly checked up by the service mechanic since

    probably more serious defect occurred. This should be carried out at least

    once a year or in two.

    vi. Check up of primary and secondary connections. their cleaning and tightening

    is precaution.

    vii. Check up of sealed places consists of detection of oil around connections,

    flanges etc. no case transformer should be opened.

    viii. All earthed parts should be checked and if required, they should be cleaned

    and tightened.

    ix. Painting of originally painted transformer parts is advisable if required during

    regular check-ups.

    x. Transformer should not be opened barring in service workshop.

    d) General Instructions for Maintenance

    31

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    32/67

    The maintenance of transformer is usually done in specialized workshops, but if

    possible also on the spot.

    After the maintenance,

    i. Follow all steps as said under erection, commissioning & inspection.

    ii Measure insulation resistance and loss angle after major maintenance.

    4.7 Conclusion

    We have discussed in detailed about the working and malignances of transformers

    and in the next chapter we are going to discuss about the various instrument used in

    substation for protection of substation.

    5.1 Introduction

    We are going to discuss about the various equipment used in the substation like

    lightning arresters, Control and Relay panel ,Circuit Breakers, conductor systems ,DC

    Battery and Charger ,Wave Taper ,Bus bar and Isolators and their working principle and

    maintenances.

    32

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    33/67

    5.2 Types of Instruments

    a) Lightning Arresters

    Surge arrester protects the costly outdoor electrical

    equipment from over voltages caused by atmospheric

    disturbances due to lightning and internal disturbances due to

    switching surges.

    i. Construction: The assembly consists of stack of Metal

    Oxide elements with contact plates between discs and held

    rigidly by a tie rod assembly. The striking aspect of this

    arrester is its simplicity of construction with no grading

    components, no gaps either in series or in parallel.

    A system of silicone bumpers on each contact plate provides

    dissipation of the heat generated in the elements for Temporary

    Over Voltages and Transmission Line Discharges in addition to

    rugged support to prevent damage in shipping. Doubling Gaskell

    seal and pressure relief vents are provided as in convention

    design.

    Fig 5.2(i) lightning arresters

    The Pressure Relief arrangement transfers the internal arc to outside in the remote event

    of arrester failure.

    ii. Installation of Lightning Arresters

    Three simple rules to be followed in installing lightning arresters for the effective

    protection of the equipment

    33

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    34/67

    i. The arrester should be connected to a ground of low resistance for effective

    discharge of the surge current.

    ii. The arrester should be mounted close to equipment to be protected and connected

    with shortest possible leads. On both the line and ground side to reduce the

    inductive effects of the leads while discharging large surge currents.

    iii. To protect the transformer windings. It is desirable to interconnect the ground

    lead of the arrester with the tank and also the neutral of the secondary. This

    interconnection reduces the stress imposed on the transformer winding by the

    surge currents to the extent of the drop across the ground.

    iii. Maximum Continuous Operating Voltage

    Under actual service conditions METOVAR functions as insulators at the

    maximum line to ground operating voltage. For each arrester rating there is a limit to the

    magnitude of the voltage that may be continuously applied. There for M.C.O.V is the

    designated maximum permissible power frequency voltage that may be applied

    continuously across the arrester terminal.

    iv. Caution

    Under no circumstances, the Maximum Continuous Power Frequency Voltage

    between phase and ground appearing the arrester should exceed the arrester M.C.O.V as

    specified in the name plate.

    v. Packing

    Each arrester is packed in a wooden box with proper cushioning material. The

    terminal connectors are also packed in the same wooden box taken to see that the arresterhousing is not damaged due to rough handling

    b) Control and Relay Panel

    34

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    35/67

    The control and relay panel is of cubical construction suitable for floor mounting.

    All protective, indicating and control elements are mounted on the front panel for ease of

    operation and control. The hinged rear door will provide access to all the internal

    components to facilitate easy inspection and maintenance. Provision is made for

    terminating incoming cables at the bottom of the panels by providing separate line-up

    terminal blocks. For cable entry provision is made both from top and bottom.

    The control and relay panel accepts CT, PT aux 230 AC and 220V/10V DC

    connections at respective designated terminal points. 220V/10V DC supply is used for

    control supply of all internal relays and timers and also for energizing closing and

    tripping coils of the breakers. 230V AC station auxiliary supply is used for internal

    illumination lamp of the panel and the space heater. Protective HRC fuse are providedwith in the panel for P.T secondary. Aux AC and battery supplies.

    Each Capacitor Bank is controlled by breaker and provided with a line ammeter with

    selector switch for 3 phase system & Over current relay (2 phase and 1 Earth fault for 3

    ph system). Under voltage and over voltage Relays.

    Neutral Current Unbalance Relays are for both Alarm and Trip facilities breaker

    control switch with local/remote selector switch, master trip relay and trip alarms

    acknowledge and reset facilities.

    c) Protective Relaying

    Protective relays are used to detect defective lines or apparatus and to initiate the

    operation of circuit interrupting devices to isolate the defective equipment. Relays are

    also used to detect abnormal or undesirable operating conditions other than those caused

    by defective equipment and either operate an alarm or initiate operation of circuit-

    interrupting devices. Protective relays protect the electrical system by causing the

    defective apparatus or lines to be disconnected to minimize damage and maintain service

    continuity to the rest of the system

    There are different types of relays.

    35

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    36/67

    i. Over current relay

    ii. Distance relay

    iii. Differential relay

    iv. Directional over current relay

    i. Over Current Relay

    The over current relay responds to a magnitude of current above a specified value.

    There are four basic types of construction: They are plunger, rotating disc, static, and

    microprocessor type. In the plunger type, a plunger is moved by magnetic attraction when

    the current exceeds a specified value. In the rotating induction-disc type, which is a

    motor, the disc rotates by electromagnetic induction when the current exceeds a specified

    value.

    Static types convert the current to a proportional D.C mill volt signal and apply it to a

    level detector with voltage or contact output. Such relays can be designed to have various

    current-versus-time operating characteristics. In a special type of rotating induction-disc

    relay, called the voltage restrained over current relay.

    The magnitude of voltage restrains the operation of the disc until the magnitude of

    the voltage drops below a threshold value. Static over current relays are equipped with

    multiple curve characteristics and can duplicate almost any shape of electromechanical

    relay curve. Microprocessor relays convert the current to a digital signal. The digital

    signal can then be compared to the setting values input into the relay. With the

    microprocessor relay, various curves or multiple time-delay settings can be input to set

    the relay operation. Some relays allow the user to define the curve with points or

    calculations to determine the output characteristics.

    ii. Distance Relay

    36

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    37/67

    The distance relay responds to a combination of both voltage and current. The

    voltage restrains operation, and the fault current causes operation that has the overall

    effect of measuring impedance. The relay operates instantaneously (within a few cycles)

    on a 60-cycle basis for values of impedance below the set value. When time delay is

    required, the relays energizes a separate time-delay relay or function with the contacts or

    output of this time-delay relay or function performing the desired output functions.

    The relay operates on the magnitude of impedance measured by the combination of

    restraint voltage and the operating current passing through it according to the settings

    applied to the relay. When the impedance is such that the impedance point is within the

    impedance characteristic circle, the relay will trip. The relay is inherently directional. The

    line impedance typically corresponds to the diameter of the circle with the reach of the

    relay being the diameter of the circle.

    iii. Differential Relay

    The differential relay is a current-operated relay that responds to the difference

    between two or more device currents above a set value.

    The relay works on the basis of the differential principle that what goes into the

    device has to come out .If the current does not add to zero, the error current flows tocause the relay to operate and trip the circuit.

    The differential relay is used to provide internal fault protection to equipment such

    as transformers, generators, and buses. Relays are designed to permit differences in the

    input currents as a result of current transformer mismatch and applications where the

    input currents come from different system voltages, such as transformers. A current

    differential relay provides restraint coils on the incoming current circuits. The restraint

    coils in combination with the operating coil provide an operation curve, above which the

    relay will operate. Differential relays are often used with a lockout relay to trip all power

    sources to the device and prevent the device from being automatically or remotely re-

    energized. These relays are very sensitive. The operation of the device usually means

    major problems with the protected equipment and the likely failure in re-energizing the

    equipment

    37

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    38/67

    iv. Directional Over current Relay

    A directional over current relay operates only for excessive current flow in a given

    direction. Directional over current relays are available in electromechanical, static, and

    microprocessor constructions. An electromechanical overcorrect relay is made directional

    by adding a directional unit that prevents the over current relay from operating until the

    directional unit has operated. The directional unit responds to the product of the

    magnitude of current, voltage, and the phase angle between them or to the product of two

    currents and the phase angle between them. The value of this product necessary to

    provide operation of the directional unit is small, so that it will not limit the sensitivity of

    the relay (such as an over current relay that it controls). In most cases, the directional

    element is mounted inside the same case as the relay it controls. For example, an overcurrent relay and a directional element are mounted in the same case, and the

    combination is called a directional over current relay. Microprocessor relays often

    provide a choice as to the polarizing method that can be used in providing the direction of

    fault, such as applying residual current or voltage or negative sequence current or voltage

    polarizing functions to the relay.

    d) Circuit Breakers

    A circuit breaker is an automatically-operated electrical switch designed to

    protect an electrical circuit from damage caused by overload or short circuit. Its basic

    function is to detect a fault condition and these by interrupting continuity, to immediately

    discontinue electrical flow.

    i. Principle of Operation

    All circuit breakers have common features in their operation, although details vary

    substantially depending on the voltage class, current rating and type of the circuit

    breaker.

    The circuit breaker must detect a fault condition in low-voltage circuit breakers this

    is usually done within the breaker enclosure. Circuit breakers for large currents or high

    38

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    39/67

    voltages are usually arranged with pilot devices to sense a fault current and to operate the

    trip opening mechanism. The trip solenoid that releases the latch is usually energized by a

    separate battery, although some high-voltage circuit breakers are self-contained with

    current transformers, protection relays and an internal control power source.

    Once a fault is detected, contacts within the circuit breaker must open to interrupt the

    circuit. Some mechanically-stored energy (using something such as springs or

    compressed air) contained within the breaker is used to separate the contacts, although

    some of the energy required may be obtained from the fault current itself. The circuit

    breaker contacts must carry the load current without excessive heating, and must also

    withstand the heat of the arc produced when interrupting the circuit. Contacts are made of

    copper or copper alloys, silver alloys and other materials. Service life of the contacts islimited by the erosion due to interrupting the arc. Miniature circuit breakers are usually

    discarded when the contacts are worn, but power circuit breakers and high-voltage circuit

    breakers have replaceable contacts.

    When a current is interrupted, an arc is generated - this arc must be contained, cooled,

    and extinguished in a controlled way, so that the gap between the contacts can again

    withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating

    gas, or oil as the medium in which the arc forms. Different techniques are used to

    extinguish the arc including:

    i. Lengthening of the arc

    ii. Intensive cooling (in jet chambers)

    iii. Division into partial arcs

    iv. Zero point quenching

    v. Connecting capacitors in parallel with contacts in DC circuits

    Finally, once the fault condition has been cleared, the contacts must again be

    closed to restore power to the interrupted circuit.

    ii. Arc Interruption

    39

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    40/67

    Miniature low-voltage circuit breakers use air alone to extinguish the arc. Larger

    ratings will have metal plates or non-metallic arc chutes to divide and cool the arc.

    Magnetic blowout coils deflect the arc into the arc chute.

    In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast

    a jet of oil through the arc.

    Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a

    magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF 6)

    to quench the stretched arc.

    Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than

    the contact material), so the arc quenches when it is stretched a very small amount (

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    41/67

    Miniature circuit breakers used to protect control circuits or small appliances may not

    have sufficient interrupting capacity to use at a panelboard. These circuit breakers are

    called "supplemental circuit protectors" to distinguish them from distribution-type circuit

    breaker.

    iv. High-voltage circuit breakers

    400KV SF6 circuit breakers

    Electrical power transmission networks are protected and controlled by high-voltage

    breakers. The definition of "high voltage" varies but in power transmission work is

    usually thought to be 72,500 V or higher according to a recent definition by the

    International Electro technical Commission (IEC).

    High-voltage breakers are nearly always solenoid-operated, with current sensing

    protective relays operated through current transformers. In substations the protection

    relay scheme can be complex, protecting equipment and busses from various types of

    overload or ground/earth fault.

    High-voltage breakers are broadly classified by the medium used to extinguish the

    arc.

    i. Bulk oil

    ii. Minimum oil

    iii. Air blast

    iv. SF6

    Fig.5.2 (iii) shows

    circuit breaker

    High-voltage circuit breakers used on transmission systems may be arranged to

    allow a single pole of a three-phase line to trip, instead of tripping all three poles.For

    some classes of faults this improves the system stability and availability.

    41

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    42/67

    e) Conductor Systems

    An ideal conductor should fulfill the following requirements:

    i. Should be capable of carrying the specified load currents and short time currents.

    ii. Should be able to withstand forces on it due to its situation. These forces comprise

    self weight, and weight of other conductors and equipment, short circuit forces

    and atmospheric forces such as wind and ice loading.

    iii. Should be corona free at rated voltage.

    iv. Should have the minimum number of joints.

    v. Should need the minimum number of supporting insulators.

    vi. Should be economical.vii. The most suitable material for the conductor system is copper or aluminum. Steel

    may be used but has limitations of poor conductivity and high susceptibility to

    corrosion.

    Fig.5.2(iii) shows Conductor systems

    In an effort to make the conductor ideal, three different types have been utilized,

    and these include:

    i. Flat surfaced Conductors.

    ii. Stranded Conductors.

    iii. Tubular Conductors.

    f ) DC Power Supply

    42

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    43/67

    i. DC Battery and Charger

    All but the smallest substations include auxiliary power supplies. AC power is

    required for substation building small power, lighting, heating and ventilation, some

    communications equipment, switchgear operating mechanisms, anti-condensation heaters

    and motors. DC power is used to feed essential services such as circuit breaker trip coils

    and associated relays, supervisory control and data acquisition (SCADA) and

    communications equipment. This describes how these auxiliary supplies are derived and

    explains how to specify such equipment.

    ii. Battery and Charger configurations

    Capital cost and reliability objectives must first be considered before defining the

    battery and battery charger combination to be used for a specific installation. The

    comparison given in Table 5.1 describes the advantages and disadvantages of three such

    combinations.

    Table 5.1: Capital cost and reliability objectives must first be considered before defining

    the battery/battery charger combination to be used for a specific installation. The

    comparison given describes the advantages and disadvantages of three such combinations

    Type Advantages Disadvantages

    1. Single

    100% battery

    and 100%

    charger

    Low capital cost

    No standby DC System outage for

    maintenance Need to isolate

    battery/charger combination from load

    under boost charge conditions in order to

    prevent high boost voltages appearing on

    DC distribution system2. Semi-

    duplicate

    50% batteries

    and

    Medium capital cost Standby DC

    provided which is 100% capacity

    on loss of one charger Each

    battery or charger can be

    ------------------------------

    43

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    44/67

    Table 5.1: Capital cost and reliability objectives must first be considered before defining

    the battery/battery charger combination to be used for a specific installation. The

    comparison given describes the advantages and disadvantages of three such combinations

    Type Advantages Disadvantages

    100%

    chargers

    maintained in turn. Each battery

    can be isolated and...

    iii. 220V DC Battery

    Make: Exide, Capacity: 300 AH at 27

    No. of Cells: 110 No. , Date of installation: 06/200

    Make: Universal, Sr. No. : BC 1020/82

    Date of installation: 1983

    Input Rating: Voltage: 415 V + 10 %

    Frequency: 50 Hz. 3 Phase

    Output Rating:

    Float: 220 V, 10 Amp Fig.5.2(iv) shows 220V Battery Charger

    Boost: 180 V, 30Amp

    g) Wave Trapper

    This is relevant in Power Line Carrier Communication (PLCC) systems for

    communication among various substations without dependence on the telecom company

    network. The signals are primarily teleportation signals and in addition, voice and data

    communication signals. Line trap also is known as Wave trap.

    h) Bus Bar

    44

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    45/67

    A bus bar in electrical power distribution refers to thick strips of copper or

    aluminum that conduct electricity within a switchboard, distribution board, substation, or

    other electrical apparatus.

    The size of the bus bar is important in determining the maximum amount of current

    that can be safely carried. Bus bars are typically either flat strips or hollow tubes as these

    shapes allow heat to dissipate more efficiently due to their high surface area to cross-

    sectional area ratio. The skin effect makes 50-60 Hz AC bus bars more than about 8 mm

    (1/3 in) thick inefficient, so hollow or flat shapes are prevalent in higher current

    applications. A hollow section has higher stiffness than a solid rod of equivalent current-

    carrying capacity, which allows a greater span between bus bar supports in outdoor

    switchyards. A bus bar may either be supported on insulators or else insulation maycompletely surround it. Bus bars are protected from accidental contact either by a metal

    enclosure or by elevation out of normal reach.

    Neutral bus bars may also be insulated. Earth bus bars are typically bolted directly

    onto any metal chassis of their enclosure. Bus bars may be enclosed in a metal housing,

    in the form of bus duct or bus way, segregated-phase bus, or isolated-phase bus.

    i. Protection

    Bus bars are vital parts of a power system and so a fault should be cleared as fast

    as possible. A bus bar must have its own protection, although they have high degrees

    of reliability. Bearing in mind the risk of unnecessary trips, the protection should be

    dependable, selective and should be stable for external faults, called 'through faults'.

    The most common fault is phase to ground, which usually results from human

    error.

    There are many types of relaying principles used in bus bar.

    A special attention should be made to current transformer selection since

    measuring errors need to be considered.

    45

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    46/67

    i) Isolators

    Isolators are used to connect and disconnect high voltage power systems under no

    load conditions.

    These are essentially off load devices although they are capable of dealing with small

    charging currents of bus bars and connections. The design of isolators is closely related to

    the design of substations. Isolator design is considered in the following aspects:

    i. Space Factor

    ii. Insulation Security

    iii. Standardization

    iv. Ease of Maintenance

    v. Cost

    Some types of isolators include:

    i. Horizontal Isolation types

    ii. Vertical Isolation types

    iii. Moving Bushing types

    i. Properties

    The isolators comprises three identical poles (in the case of the three phase system

    only) each pole consisting of

    i. A Galvanized Fabricated Base out of MS Channel having one supporting

    insulation mounting stool.

    ii. Three post insulators stacks one for mounting one the centre rotating stool and

    other two stacks on both ends of the base channel.

    iii. Moving contact assembly for mounting on the centre rotating insulator stack and

    the fixed contact assembly with terminal pad or two outer insulator stacks.

    iv. Tandem pipe for interlinking the three poles and operating down pipe to link the

    tandem pipe with the bottom operating mechanism of 3 phase system.

    46

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    47/67

    v. Bottom operating mechanism box.

    vi. Earthing switch moving contact assembly

    vii. Earthing switch fixed contact assembly for fixing to the main switch fixed

    contacts.

    viii. Earthing switch operating down pipe to link earth switch tandem pipe to the

    bottom

    ix. Bottom operating mechanism box

    x. Mechanical interlock between main switch and earthling switch.

    5.3 Conclusion

    We have discussed about the various types of instrument used in substances and for

    protection of substation in detailed. In the next chapter we are going to discusses about

    the insulators and they importances in substation

    6.1 Introduction

    This chapter describes the different types of overhead line and substation

    insulators, their design characteristics and their application. Conductors are attached to

    47

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    48/67

    their support by means of an insulator unit. For overhead lines up to 33 kV and for

    outdoor substation equipment, the insulator is typically of the post insulator type. For

    overhead lines above 33 kV and substation aerial conductor bus bars, suspension or

    tension cap and pin or long rod insulator units are employed. Insulators must be capable

    of supporting the conductor under the most onerous loading conditions. In addition,

    voltage flashover must be prevented under the worst weather and pollution situations

    with leakage currents kept to negligible proportions

    a) Principle

    The principle dielectric used on overhead power lines is air at atmospheric

    pressure. The air surrounding the bare high voltage threshold. It is however necessary to

    attach the conductors at certain points onto the cross arms of the pylons. The problem of

    reliably suspending the conductors of high voltage transmission lines has therefore been

    with us since the turn of the century. The task is particularly complex, bearing in mind

    the multiple extreme stresses present are mechanical, electrical and environmental

    stresses.

    6.2 Types of Insulators

    a) Porcelain pin type

    insulators

    These were originally used for

    telephone lines and lightning conductors, have

    been adapted for power transmission and some

    variations are still in use for medium voltage

    systems. A pin-type insulator is shownschematically in figure 6.2(i)and 6.2(ii)

    Fig. 6.2(i)

    Porcelain Insulator

    b) Cap and Pin Type Insulators

    48

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    49/67

    The pin-type insulator is so called because in use it is screwed onto a galvanized

    forged steel 'pin' which mounted vertically on a metal or wooden cross arm.

    For low voltage systems, 6.6 to 11 kV, it is usual to have a one-piece insulatorshed in which the porcelain is loaded largely in compression. A typical pin-type insulator

    is shown in Figure 6.2(ii). The sketches show that the top of the porcelain body is formed

    into a groove into which the conductor is bound by means of wire or fixed with the aid of

    special clips. Toughened glass pin-type insulators require a metal cap; this holds together

    the 'diced' pieces of glass which result if the glass becomes shattered.

    Fig.62 (ii): shows cap & pin insulator

    c) Post Type Insulator

    These insulators consist of a solid porcelain cylinder, corrugated to increase the

    leak- age length, with metalware on each end. They are used to support the high voltage

    conductor and are mounted on pedestals or on the power line cross arms. Post insulators

    are tall and are mainly used in substations. These insulators are Class A; the shortest

    distance through the porcelain exceeds 50% of the shortest distance through air between

    the electrodes. They are therefore un puncturable. A typical example of a post insulator is

    shown schematically in figure 6.2(iii)

    49

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    50/67

    Fig.6.2(iii)post insulator

    d) Porcelain Long Rod Insulators

    Long rod insulators are similar to post insulators but are lighter, slimmer and are

    used as suspension insulators.

    Long rod insulators have the apparent advantage over cap and pin insulators in

    that metal fittings exist only at the ends of the insulators.

    6.3 Bushings

    Bushings are used to insulate the conductors of the high voltage terminals

    of a transformer as is shown schematically in figure 5. 3 Traditionally,

    transformer bushings are manufactured using porcelain. Capacitive grading, using

    foil cylinders is often used to improve the axial and radial field distribution.

    Fig.6.3 shows bushings

    6.4 Terminology

    When applying insulators, it is necessary to describe the insulator dimensions,

    using the following terms:

    50

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    51/67

    Creep agedistance: The shortest distance between the metal ware at the two ends of the

    insulator, when following the contours of the insulator, excluding intermediate metal

    fittings. This distance is easily measured by sticking masking tape to the insulator

    surface.

    Specific Creep age distance:The quotient of the creep age distance in mm and the line-to-

    line rms. voltage of the three phase system in kV.

    Connecting length: The axial length of the insulator between the end terminals.

    Arcing distance:The distance between the metal ware, measured as the length of a tightly

    pulled piece of string.

    Inter shed spacing:The distance between corresponding points on adjacent sheds.

    6.5 Pollution Deposition Process

    Insulators exposed to the environment collect pollutants from various sources.

    Pollutants that become conducting when moistened are of particular concern.

    Two major sources are:

    i. Coastal pollution: the salt spray from the sea or wind-driven salt laden solid

    material such as sand collects on the insulator surface. These layers become

    conducting during periods of high humidity and fog. Sodium chloride is the main

    constituent of this type of pollution.

    ii. Industrial pollution: substations and power lines near industrial complexes are

    subject to the stack emissions from nearby plants. These materials are usually dry

    when deposited; they may then become conducting when wetted. The materials

    will absorb moisture to different degrees, and apart from salts, acids are also

    deposited on the insulator.

    a) The role of the weather

    Wind is instrumental in the deposition process. High humidity, fog or light rain

    cause wetting of the pollution layers. Heavy rain removes the pollution layer especially

    51

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    52/67

    on the upper sides of the sheds

    b) Air flashover versus pollution flashover

    If the electric stress in air at atmospheric pressure exceeds 3 kV mm, ionization can

    occur. Depending on the gap configuration, flashover may follow. The power flashover

    voltage of a clean dry single cap and pin insulator with a 280 mm creep age distance is 72

    kV. Leakage current flows over the insulator surface and the heating effect of the current

    causes drying out of the layer at certain spots and the formation of dry bands. Arcs

    occur across these bands and if the pollution is of sufficient severity, the insulator may

    flash over

    6.6 Failure Modes of InsulatorsFlashovers, caused by air breakdown or pollution, generally do not cause physical

    damage to the insulators and the system can often be restored by means of auto closing.

    Some other events, however cause ir-repairable damage to the insulators .

    a) Puncture

    As previously mentioned, porcelain pin-type and cap and pin insulators may suffer

    punctures between the pin and the either the pin or the high voltage conductor.

    These occurrences are usually caused by very steep impulse voltages, where the

    time delay for air flashover exceeds that of puncture of porcelain. Punctures caused by

    severe stress over dry bands also occur on composite insulators on sheds and through the

    sheath. A puncture of the sheath is particularly serious as this exposes the glass fiber rod

    to the environment .

    b) Shattering

    Glass insulators shatter when exposed to severe arcing or puncturing due to

    vandalism. One advantage is that they retain their mechanical integrity.

    52

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    53/67

    c) Erosion

    Prolonged arcing of glass insulators leads to erosion of the surface layer of the

    glass. This may lead to shattering of the glass discs - a result of the tempering process

    used during manufacture. Arcing and corona over long periods may cause removal ofshed or sheath material in the case of polymeric insulators. Severe erosion may lead to

    the exposure of the glass fiber core.

    d) Tracking

    Tracking occurs when carbonized tracks form because of arcing. These tracks are

    conductive. This phenomenon only occurs in carbon-based polymers.

    e) Brittle Fracture

    Water entry into the glass fiber core of composite insulators, coupled with the

    influence of weak acids, has been shown to lead to brittle fracture of the rod. The by-

    products of partial discharges in the presence of water can lead to the formation of weak

    acids. The integrity of the metal/polymer and glass/polymer interfaces is therefore

    extremely important - especially if acid-resistant glass is not used.

    6.7 Remedies

    There are certain remedies provided for different equipments available in substation

    from being damaged.

    They are ,

    a) Washing

    b) Greasing

    c) Choice of Creep age length

    a) Washing

    Substation or line insulators can be washed when de-energized or when

    energized. Automatic washing schemes and helicopters have been used for this purpose.

    53

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    54/67

    The costs are usually prohibitive. A thin layer of silicone grease, when applied

    to ceramic insulators increases the hydro-phobicity of the insulators.

    b) Greasing

    Room temperature cured silicone rubber coatings are available to be used on

    ceramic substation insulators. These coatings have good hydrophobic properties when

    new. Research is still in progress to evaluate their aging processes. We face Pollution

    particles that are deposited on the insulator surface are also encapsulated by the grease

    and protected from moisture. The disadvantage of greasing is that the spent grease must

    be removed and new grease applied, usually annually.

    c) Choice of Creep age Length

    When using non-ceramic insulators, it is advisable to use a shorter creepage length

    especially in locations of severe pollution. Recent research indicates that under conditions

    of severe research results or revised specifications are available it is considered a safe

    approach to use IEC 815 for non-ceramic insulators as well.

    6.8 Conclusion:

    We have discussed about the insulator used in substation and various types ofinsulators.

    7.1 Introduction

    We are going to discusses about the various earthing techniques used in sub station

    54

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    55/67

    a) Grounding

    A properly designed and installed grounding system ensures reliable performance

    of electrical substations .

    Just how important is substation reliability? Fast clearing of faults, made possible

    by good grounding, improves the overall safety and reliability of an electrical system.

    Therefore, substation reliability must be as "built-in" as possible because of the high

    available fault current levels present and unlikely occurrence of follow-up grounding

    inspections.

    Fig.7.1 shows grounding

    7.2 Types and Methods of Grounding

    There are different types and methods of grounding which ensures the reliable

    performance of a substation.

    a) Types

    Grounding of earth may be classified as (i) Equipment grounding (ii) System

    grounding and (iii) Neutral grounding.

    Equipment grounding deals with earthing the non current carrying metal parts of

    the electrical equipment. On the other hand, system grounding means earthing some part

    of the electrical system e.g. earthing of neutral point of star connected system in

    generating stations and substations.

    55

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    56/67

    i. Equipment Grounding

    The process of connecting non current carrying metal parts of the electrical

    equipment to earth in such a way that in case of insulation failure, the enclosure

    effectively remains at earth potential is called Equipment grounding.

    ii. System Grounding

    The process of connecting some electrical part of the power system (neutral point of

    a star connected system, one conductor of the secondary of a transformer) to earth is

    called System grounding.

    iii. Neutral Grounding

    The process of connecting neutral point of 3-phase system to earth either directly

    or through some circuit element (e.g. resistance or reactance etc.) is called Neutral

    grounding.

    Neutral grounding provides protection to personal and equipment. It is because

    during earth fault the current path is completed through the earthed neutral and the

    protective devices operate to isolate the faulty conductor from the rest of the system.

    b) Methods of Grounding

    The methods commonly used for grounding the neutral point of a 3-phase system

    are:

    (i) Solid or effective grounding (ii) Resistance grounding

    (iii) Reactance grounding (iv) Resonant grounding

    i. Solid Grounding

    When the neutral point of a 3-phase system is directly connected to earth through a

    wire of negligible resistance and reactance is called Solid or Effective grounding. Under

    fault conditions, the voltage of any conductor to earth will not exceed the normal phase

    voltage of the system.

    56

  • 8/9/2019 Study of Elements of a 22013233kv Substation

    57/67

    Advantages:

    a) The neutral is effectively held at earth potential.

    b) No arcing phenomenon or over voltage condition can occur.

    c) Permits the easy operation of earth fault relay.

    Disadvantages:

    a) It causes the system to become unstable.

    b) The increased earth fault current results in greater interference in the neighboring

    communication lines.

    ii. Resistance Grounding

    When the neutral point of a 3-phase system is connected to earth through a resistor,

    it is called Resistance grounding. The value of R should be neither v