Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
STRUCTURAL DESIGN
OF SUPPLEMENTARY INJECTION ANCHORS INSIDE MASONRY
Gigla, Birger1
1 Dr.-Ing., Professor, University of Applied Sciences Lübeck, Germany, [email protected]
Supplementary injection anchors are used as a repairing-system inside historic masonry for
transferring tensile-forces that cannot be transmitted by the masonry itself or for new connec-
tions. They basically consist of a tensile element - usually steel - inserted into a slightly larger
borehole and the annulus is grouted with cement. The solid plug of injection material transfers
the tensile forces to the masonry. Assuming successful grouting, considerable tensile forces
can be transferred at short bond lengths. Supplementary Injection Anchors have been utilised
since the 1920s and applied within a core philosophy of minimum intervention.
The field of application extends from the repair of small elements like stone corbels up to the
reinforcing of walls and foundations that might require prestressed tendons. In certain practi-
cal situations, e.g. when connecting two shells of masonry, extremely short bond lengths are
required. Connections are not only carried out inside masonry structures but also between
masonry and reinforced concrete slabs or frameworks.
The paper summarizes the latest development of design recommendations for supplementary
injection anchors inside masonry, based on more than 600 tests in laboratory and in situ. Main
parameters to obtain the characteristic value of bond strength are compressive strength of
grout, grouting technology and capillarity of the surrounding stone. The paper takes aspects of
the application inside low strength masonry into special consideration.
Keywords: Restoration, repair, rehabilitation and refurbishment, injection anchor
INTRODUCTION
Supplementary injection anchors (figure 1) are used as a repair-system for masonry to cover
tensile forces that cannot be sustained by the masonry alone. In Germany, such anchors have
been utilized since the 1920s and frequently applied to repair monuments within a core phi-
losophy of minimum intervention. A new field of application is the reinforcement of masonry
against dynamic loads. They are applied in the form of untensioned steel reinforcement or as
prestressed tendon. While new tensile elements like glass fibre reinforced plastic bars did not
prove successful in practice, stainless steels are used increasingly for the repair of historic
masonry. Forces are transmitted by bond between the anchor and the surrounding masonry in
axial direction. Standard borehole diameters are between 30 mm and 76 mm. Ordinary steels
require a sufficient cement-coating for corrosion protection.
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
Figure 1: Diagram of a supplementary injection anchor [Gigla 2008]
Borings for untensioned anchors are usually less than 4.0 m, whereas for prestressed tendons
they may go up to 35 m in length. The drilling method is regularly selected on the basis of
cost effectiveness and aspects of minimum intervention in the case of monuments. After
clearing and prewetting the drill hole, the anchor bar is inserted, centred with spacers, sealed
and grouted. The admissible grouting pressure has to be adjusted according to the state of the
masonry and may vary between 1 to 6 bar. Figure 2 gives examples for the utilisation of injec-
tion anchors in masonry.
Figure 2: Utilisation of injection anchors [Gigla 2004]
a), d), j) Anchors stabilising cracked or deformed masonry leaves
b), c), f) Anchors fixing cracked structures
h), k) Strengthening against dynamic loads
e, i) Joints or keys between old and new work
g) Reinforcing of walls or foundations against uneven settlement
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
Recommendations for the design of injection anchors have been given by Gigla and Wenzel
(2000, 2002) and Gigla (2004, 2008, 2010), based on a research project at Sonderforschungs-
bereich 315 (Collaborative Research Centre 315: „Care and maintenance of historic build-
ings“, Karlsruhe Institute of Technology, 1985 - 2003). Aspects of force transmission of in-
jection anchors are part of ongoing research at University of Applied Sciences, Luebeck.
Overall 600 pull-out tests have been performed to establish design recommendations.
PULL-OUT TESTING OF INJECTION ANCHORS
Pull-Out tests of injection anchors should be performed as series with a minimum of five
identical anchors each to provide a statistic evaluation. Figure 3 shows grouting works in the
laboratory with five series of total 25 injection anchors inside monolithic sandstone (variety
Maulbronn). Current parameter under investigation is the type of anchor bar at a bond length
of 200 mm and with a nominal diameter of 16 mm constantly. Anchor bars are stainless rein-
forcing bars (left), ordinary reinforcing bars (second left), and three different types of thread-
ed rods (right). In all five series the boreholes are 56 mm in diameter. Grout is a trass-cement-
suspension with a water/cement-ratio 0.6. The compressive strength of the grout of the five
series varies between 28.5 and 30.1 MPa, tested in accordance with standard DIN EN 196-1.
Figure 3: Grouting works in laboratory
The test set-up is shown in figure 4. During testing a loaded and a free anchor end have to be
distinguished. Usually, the free end is not accessible in field tests and therefore, free end dis-
placements are only to be explored in laboratory. Anchor displacements at both ends are
checked while the anchors are loaded to failure in a cyclic loading programme. The basic test
load required to ensure transfer of forces has been chosen equivalent to 20% of working
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
stress. Loading sequences are covering 50%, 75%, 100% and 125% of estimated working
load. The final loading to failure proceeds in 25% increments of estimated working load. Ob-
serving intervals are minimum 1 min at load and unload. The displacements of steel and in-
jected mortar plug at the free end and twin steel displacements and test force at the loaded end
are recorded at 1 to 10 Hz frequency via a data logger. Inductive displacement transducers
and a ring-dynamometer are used for measurement. Construction of injection anchors, test
set-up, evaluated parameters, test results and evaluation are discussed in greater scale by Gi-
gla/Wenzel (2000) and Gigla (2004).
Figure 4: Test set-up in laboratory [Gigla 2008]
In the laboratory, the bond strength is nominally defined as average bond stress at a displace-
ment level of 0.1 mm at the free steel end. Loaded end displacements of steel contain elastic
and plastic anchor bar deformations. A comparison between free end and loaded end dis-
placements during a cyclic loading programme provides additional information concerning
the current state of failure. For analysis, one diagram of structural failure of each test series is
numerically evaluated from the five curves of test force versus free end steel-displacements of
every pull-out test by skipping the cyclic parts. The diagrams of structural failure are the av-
erage of five tests and useful for the understanding of the influence of different parameters.
Design recommendations are referring to characteristic values of bond strength (5%-fractiles),
nominally defined at free-end steel displacements of 0.1 mm.
BASIC PRINCIPLES OF ANCHOR FORCE TRANSFER
Deflections inside the masonry structure are transferred to the anchor bar depending on the
specific conditions in the interfaces between masonry and grout and also between grout and
anchor bar. The most effective load transfer requires limited deflections in both interfaces. In
this case, force transfer causes cracked cone shaped segments inside the grout plug between
masonry and lengthened anchor bar (figure 5). Basic parameters for the failure load are the
bond between anchor bar and grout, the compressive strength of the grout plug, the tensile
strength of the surrounding material and the bond between masonry and grout.
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
Figure 5: Force transmission during failure, diagrammatical (left) and picture of a grout
plug in monolithic sandstone with cone-shaped cracks after pull-out testing (right)
BOND BETWEEN ANCHOR AND INJECTED GROUT PLUG
The bond between anchor and injected grout plug depends basically on the rib-spacing and
rib-sections of the anchor bar. The load transfer is comparable with the mechanisms between
reinforcing bar and concrete. Assuming injected grout with lower compressive strength than
the surrounding stone or masonry, the lengthening of a steel bar with appropriate rib-design
induces cone shaped cracking inside the grout plug, like documented in figure 5. The angle of
those segments depends on the properties of the surrounding type of stone or masonry. Inside
stone with higher water absorptive capacity like sandstone angles of around 50° have been
observed. Inside stone with low water absorptive capacity like granite the angles tend to be
around 60°.
Anchor bars without ribbing should not be used for injection anchors. Threaded rods with
nominal diameters up to 16 mm are suitable for injection anchors inside masonry. They pro-
vide an effective bond with small deflections. Remaining oil from the production process has
to be removed. Additional screws and washers will not improve force transmission, because at
higher loads the tensile strength of the grout plug will be locally exceeded underneath the
washer. Threaded rods provide a less ductile force transmission compared to reinforcing bars,
because the gaps between the threads are smaller than the gaps between the ribs of reinforcing
bars. Therefore, the smaller cone-shaped segments are easily torn off with increasing deflec-
tions (compare fig. 6).
Similar problems have to be expected during application of glass fibre reinforced plastic bars.
Dependent on the production process, the ‘ribs’ of those bars are made of plastic or coiled
fibre-rings on the surface of the bar. During different test series glass fibre reinforced plastic
bars did not develop a sufficient bond to cover their high tensile strength.
Figure 6 shows the diagram of structural failure of the test series for the investigation of the
influence of different types of anchor bars, inside the specimen documented in figure 3. The
diagram shows avarage failure-lines from five pull-out tests each with cyclic loading.
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
The force transmission of reinforcing bars and threaded rods is similar with nominal
diameters of 16 mm. The deflections of the threaded rods are slightly lower at the same level
of test force. Accordingly, injection anchors with threaded rods tend to be stiffer, but do not
offer additional load capacity at growing deflections. Reinforcing bars provide an increase of
load at growing deflections according to load redistribution inside the cone-shaped segements.
The difference in the diagrams of structural failure of stainless and standard reinforcing bars
is small. Standard reinforcing bars provide better bond at deflections below 50 μm according
to the flash rust on the surface. Stainless reinforcing bars gain a higher test force conforming
with their higher tensile strength. Additional washers with a head screw at the free end of the
threaded rods provide no additional benefit: The wheelspin of the screw is bigger then the
deflections between anchor bar and grout plug. Furthermore, the compressive strength of the
grout underneath the washer is exceeded. This is documented in the diagram of structural
failure of the threaded rod covered with coating. Though washer and nut have been added at
the free end the diagram shows plastic deformations referring to local exceedance of grout
compressive strength underneath the washer.
Figure 6: Diagram of structural failure of five series with 25 pull-out tests focussing on
the influence of the type of anchor bar. Anchor grouting shown in figure 3.
COMPRESSIVE STRENGTH OF INJECTED GROUT PLUG
The compressive strength of the grout plug is an important factor for the description of the
load transfer of injection anchors and the basic parameter of the design recommendations.
Successful grouting has to be ensured, because cavity inside the grout plug will significantly
decrease bond strength. In this context the effect of water absorption of the surrounding stone
or masonry has to be taken into account. Water absorption will increase the compressive
strength of the grout plug, if the absorbed water is replaced with sufficient grout, see Gi-
gla/Wenzel (2000) and Gigla (2004). The characteristic value of bond stress is described by
equation (1):
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
500
2
,
,,
cG
kbA
ff (1)
fA,b,k: characteristic value of bond strength of the injection anchor
fG,c: compressive strength of grout tested in accordance with standard DIN EN 196-1
The characteristic value of bond strength of the injection anchor fA,b,k is defined as test force
divided by the lateral surface of the anchor bar (nominal diameter) at 0.1 mm deflection at the
free end, based on 5%-fractiles. Terms to describe the increase of bond strength inside water
absorptive stone, the calculation of the design value of bond strength and a discussion of the
equations in greater scale can be found in Gigla (2004).
BOND BETWEEN INJECTED GROUT AND MASONRY
The bond between grout plug and surrounding stone or masonry depends on the macro porosi-
ty of the stone surface and is described by the water absorptive capacity of the material. Fig-
ure 7 shows the basic difference between water absorptive material like sandstone (left) and
non water absorptive material like granite (right). The particular interface between grout and
stone is depicted in thin layer microscopic views of 3.62 x 3.62 mm size.
Figure 7: Thin layer microscopic views of an 3.62 x 3.62 mm section of the interface be-
tween grout plug and sandstone (left) and grout plug and granite (right), Gigla 2004
The macro-porosity of the sandstone (fig. 7, left) results in an interlocking between borehole
surface and grout plug. This mechanism prevents relative displacements between grout plug
and stone and provides an effective transmission of tensile forces. The resulting angles of the
cone shaped segments during failure are around 50°. In tight and smooth stone material like
limestone or granite (fig. 7, right) the cone-shaped segments are not developing. In case of
shorter bond lengths, the whole injection anchor with grout plug will be drawn out. Therefore
higher anchor loads require long bond lengths or greater borehole diameters, if possible.
TENSILE STRENGTH OF SURROUNDING STONE OR MASONRY
Inside stone, the anchor tensile force has to be limited to avoid cracking. Based on the theory
of elasticity expression (2) describes the maximum anchor tensile force that might be sus-
tained by surrounding stone sections, Gigla (2004):
F
1, 9 fB,tL
b d
B h
S
2d
B
2
m tan d
B
2h
S
2
(2)
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
F: anchor tensile force
dB: borehole diameter
hS: stone height in relevant section
Lb: bond length
φ: angle between cracked cone shaped segments and axis of anchor bar,
approximately: φ = 50° in water absorptive stone (comp. fig. 5) and φ = 60° in non wa-
ter absorptive stone
fB,t: stone tensile strength
γm: Partial factor of safety for stone tensile strength, recommendation: γm = 1,5
Inside masonry the maximum tensile force depends on the local ratio of joints to stonework
and on the vertical stress (see Gigla 2004). This aspect is part of ongoing research. The basic
system of load transfer is shown diagrammatically in figure 8.
Figure 8: Load transfer between anchor bar and surrounding stone or masonry
fA,b: bond strength of the injection anchor; fG,c: compressive strength of grout; fB,b: bond
strength of the grout plug; fB,t: stone tensile strength; dB: borehole diameter; φ: angle
between cracked cone shaped segments and axis of anchor bar
APPLICATION OF INJECTION ANCHORS INSIDE LOW STRENGTH MASONRY
Current approaches strive to utilise injection anchors for the reinforcement of low strength
masonry. One example is the strengthening of clay masonry against dynamic loads from
earthquakes (figure 9). Before the application of injection anchors inside low masonry it
should be generally considered to improve the loadbearing structure, like to add and intercon-
nect framework elements. The minimum grout compressive strength that has been investigat-
ed during the described research program was fG,c = 16,6 MPa. With lower compressive
strength, e. g. with grout made from trass-lime suspensions with less than 20 mass-% of ce-
ment no effective transmission of tensile forces could be established. One reason is the aspect
of the particular water absorption capacity of the surrounding stone material that has been
discussed in Gigla/Wenzel (2000) und in greater scale in Gigla (2008). Figure 10 shows the
result of a grouting test in sandstone, variety Posta. This type of sandstone is high-absorptive
(absorption of 14 kg/m² water in 1h). The borehole in the picture (diameter: 48 mm) has been
completely filled with grout. Significant cavity occurred due to water absorption.
Because there is a slower increase of compressive strength after grouting, suspensions with
low content of cement are sensitive for cracking, when water is absorbed by the surrounding
material. Therefore suspensions for grouting injection anchors inside low strength masonry
have to be specially designed. Special additives are required to compensate the effect of water
absorption and also the effect of shrinkage. Furthermore, anchor bars with small diameters
around 10 mm and adequate borehole diameters of 30 to 56 mm diameter are recommended.
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
Figure 9: Grouting of a clay wall in laboratory at University of Applied Sciences Lübeck
Figure 10: Grouting test in sandstone, variety Posta. High water absorption leads to sig-
nificant cavity, if the absorbed water is not replaced with fresh grout sufficiently
The application of injection anchors inside low strength masonry is part of on-going research.
To assess the possible transmission of tensile forces, equation (2) is evaluated in figure 11.
The diagram on the left shows the maximum anchor tensile force as a function of the tensile
strength of the surrounding masonry, assuming bond length Lb = 190 mm, borehole diameter
dB = 30 mm, stone height in relevant section hS = 240 mm and φ = 50°. Under those condi-
tions in masonry with a tensile strength of fB,t = 0,5 MPa a maximum anchor force of F =
10 kN could be expected. In the diagram in figure 11 on the right the maximum anchor tensile
force is a function of the stone height in relevant section, assuming bond length Lb = 190 mm,
borehole diameter dB = 30 mm, tensile strength of the surrounding masonry fB,t = 1.0 MPa and
φ = 50°. Both diagrams are extrapolated from pull-out tests in masonry with higher compres-
sive and tensile strength and have to be evaluated by means of additional test series in clay
masonry.
Based on the current state of research it appears safe to assume that in the case of clay mason-
ry, the admissible maximum anchor tensile forces are limited. It has to be further checked, if
they cover estimated earthquake loads.
15th International Brick and Block
Masonry Conference
Florianópolis – Brazil – 2012
Figure 11: Evaluation of equation (2) for the application of injection anchors inside low
strength masonry
CONCLUSIONS
Proceeding from basic principles of force transfer, main aspects of the application of injection
anchors inside masonry have been summarised, based on the results of more than 600 tested
anchors. One focus is the latest development of design recommendations for injection anchors
to choose the appropriate anchor bar for individual applications. It is pointed out, that addi-
tional nuts and washers at the free end of the anchor are not improving the maximum anchor
tensile force. An actual demand is the utilisation of injection anchors inside low strength ma-
sonry, e. g. to strengthen clay walls against earthquake loads. To assess the underlying admis-
sible anchor tensile forces, the design-equation for the limitation of the maximum anchor ten-
sile force to avoid cracking of the surrounding stone or masonry was evaluated. It is indicated,
that in the case of clay masonry, only limited anchor tensile forces can be transferred.
Though the paper provides a detailed approach for the design of supplementary injection an-
chors, individual pull-out tests should be performed, if the anchors relate to structural safety.
REFERENCES
Gigla, B., Wenzel, F., ”Design Recommendations for Injection Anchors as supplementary
Reinforcement of Historic Masonry”, Proc. 12th Int. Brick/Block Masonry Conf., Madrid,
Spain, 2000, pp 691-706
Gigla, B., Wenzel, F. ”Instandsetzung von denkmalgeschützten Bauwerken, Verpressanker im
Mauerwerk”, Mauerwerk-Kalender 2002, Ernst & Sohn, Berlin, 2002, pp 283-317
Gigla, B., ”Bond Strength of Injection Achors as Supplementary Reinforcement inside
Historic Masonry”, Proc. 13th Int. Brick/Block Masonry Conf., Amsterdam, The Netherlands,
2004, pp 219-228
Gigla, B. ”Instandsetzung und Ertüchtigung von Mauerwerk, Teil 5: Vernadeln, Verankern
(Berechnung)”, Mauerwerk-Kalender 2008, Ernst & Sohn, Berlin, 2008, pp 283-317
Gigla, B. ”Comparison of failure of injection anchors as supplementary reinforcement inside
masonry and concrete”, Proc. 8th International Masonry Conference Dresden, 2010
Standard DIN EN 196-1 ”Methods of testing cement – Part 1: Determination of strength”,
May, 2005