Short Circuit Ppt Latest

Embed Size (px)

Citation preview

  • 8/8/2019 Short Circuit Ppt Latest

    1/26

    SHORT CIRCUIT PHENOMENON IN

    TRANSFORMERS.

  • 8/8/2019 Short Circuit Ppt Latest

    2/26

    WHAT IS A SHORT CIRCUIT IN A TRANSFORMER?

    During the service of a transformer if secondary line to line or line

    to ground terminals or overhead lines come into contact accidentally

    by means of strong winds, tree branches, reptiles, birds or by anyother means, very high currents will flow due to low resistance

    paths. Connected distribution transformers will have to feed these

    fault currents.

  • 8/8/2019 Short Circuit Ppt Latest

    3/26

    WHAT ARE THE EFFECTS OF SHORT CIRCUIT ON A

    TRANSFORMER?

    1. Basically there are two effects of a short circuit. Thermal andmechanical. Thermal effects cause excessive heat generationwhich can be easily calculated and proper care can be takenbefore commencement of design work by selecting proper currentdensity.

    2. IS 2026-1977, PART-I, clause .9.O explains how thermalcalculations can be made.

    3. Mechanical or dynamic effects are the critical ones. Evan thoughsome calculation methods are available the same has not beenmentioned in any international standards unlike that of thermal.

    4. Customers specifications and even IS 2026 vide clause 9.2 of

    part-I,1977 recommends for demonstrating the capability byconducting type tests.

    5. This type test is critical and destructive if proper care is not takenin design, material selection, manufacturing and quality controlstages.

  • 8/8/2019 Short Circuit Ppt Latest

    4/26

    HOW SHORT CIRCUIT FORCES ARE GENERATED IN

    A TRANSFORMER?

    1. Any current carrying conductor in a magnetic field experiences

    forces as already known.

    2. These forces which are also termed as electromagnetic forces,

    are directly proportional to square of the current.

    3. During short circuits as mentioned above, RMS currents of the

    order of 12 to 40 times will flow in a distribution transformer,

    depending on the transformer rating and impedance.

    4. Since forces are proportional to square of the currents large

    forces of the order of144 times to 1600 times will be generated.

  • 8/8/2019 Short Circuit Ppt Latest

    5/26

    5. During type tests impulse short circuit current which is much higherthan RMS value is passed. Consequently this will further generate

    enormous forces due to about 2.5 times the RMS value of current.

    6. These kind of forces will cause dislocation of the windings, lead

    connections, tap changers etc. and many times even create enoughpressure to explode the tank and create fire hazards, if proper

    considerations are not taken.

  • 8/8/2019 Short Circuit Ppt Latest

    6/26

    WHAT ARE THE DIFFERENT FORCES OCCURING IN

    SUCH CASES?

    1.Two types of forces are generated.

    a) Axial

    b) Radial

    2. Axial forces are generated due to the radial component of themagnetic flux i.e. leakage flux in the region between LV & HVwindings and radial forces are generated due to the axial componentof the leakage flux.

    3. Radial forces will have the tendency to push the inner winding on thecore and burst out the outer winding. In other words there is a forceof repulsion between the windings.

  • 8/8/2019 Short Circuit Ppt Latest

    7/26

    LV HV Radial forces

    Core

    Fig.1

  • 8/8/2019 Short Circuit Ppt Latest

    8/26

    4. Axial forces are caused by interaction of current with radial

    component of the leakage flux. Due to this a force of attraction

    occurs between adjascent turns and hence the entire winding is

    subjected to a compressive force.

    LV HVMain compressive forces

    Core

    Fig.2

  • 8/8/2019 Short Circuit Ppt Latest

    9/26

    5.In case of axial forces additional forces occur due to the following

    aspects.

    a) Force due to axial displacement of one of the windings.This means that if the electrical centers are not coinciding additional

    forces are arising. Fabricational asymmetry can take place during

    manufacturing and even minute displacement will give raise to large

    forces. The effect of this force is to create further asymmetry

    LV HV

    CoreFig.3

    Centre line of LV

    Centre line of HV

  • 8/8/2019 Short Circuit Ppt Latest

    10/26

    b. Force due to symmetrical shortening of one the windings.

    If electrical height of one of the windings is shorter, additionalforces are generated.

    This force tends to compress the shorter winding and tends tostretch the longer winding. Thus as in earlier case the tendency isto create further difference in heights.

    LV HV

    CoreFig.4

  • 8/8/2019 Short Circuit Ppt Latest

    11/26

    c) Force due to tapping gap in one of the windings.

    Generally all transformers will be provided with tapping arrangement

    for adjustment towards supply variation. This will create additional

    forces due to the absence of the ampere turns in this region. Thisforce will be acting as a tensile force in the winding with tapping gap

    and as a compressive force in the other winding as can be seen

    clearly in fig.5.

    Core

    LV HV

    Fig.5

  • 8/8/2019 Short Circuit Ppt Latest

    12/26

    DESIGN CONSIDERATIONS FOR A SHORT CIRCUIT

    PROOF TRANSFORMER.

    1. From the basic short circuit force calculations it can be deducedthat Axial compressive forces are directly proportional to thesquare of number of turns, directly proportional to windingdiameters and inversely proportional to square of axial height ofcoils.

    2. It may not be always economical to design only for aboveconditions since many times we are working for optimization withcapitalization rates. Further, factor of safety, will be inbuilt in many

    cases regarding short circuit capability. specially in small range oftransformers.

  • 8/8/2019 Short Circuit Ppt Latest

    13/26

    3. Hence in critical cases it is advised to work out axial forces as above

    where there is every chance that the best short circuit proof designmay not be optimum with respect to loss parameters.

    4. At the design stage it is very essential to maintain the centers of both

    windings at same level to the mm. This will avoid additional axial

    forces as already mentioned above.

    5. In distribution transformers due to the difference in HV and LV

    voltages and corresponding end insulation, there exists a difference

    in electrical heights. This is normally permissible up to 5%. However

    in critical cases it is an improvement to maintain same electricalheights to the mm and this practice is being followed now in our

    company.

  • 8/8/2019 Short Circuit Ppt Latest

    14/26

    6. Additional forces due to the ampere turn imbalance due to tapping

    gaps can be minimized by following methods.

    a) By providing tappings in the middle of winding. This is

    practicable in case of cross over coil and continuous disc winding

    designs. But in multilayer helical designs tappings are provided in

    last layers for convenience though in amorphous core designs

    tappings are being arranged in the middle layers in our company.

    b) In case of medium sized distribution and small power

    transformers it is better to provide tappings in two groups at about

    1/4th to 1/3rd distance from top and bottom to get better ampere

    turn balance. Ref fig 6.

    This will reduce the additional forces due to tapping gap to about

    1/4th of that due to single gap.

  • 8/8/2019 Short Circuit Ppt Latest

    15/26

    C) Providing a compensating gap of about 50% of tapping gap

    exactly opposite to the tapping gap will further improve ampere

    turn balance.

    Following diagrams in fig.7(extract from J&P hand book) shows

    ampere turn diagrams in different cases as discussed above.

    LV HV

    Core

    Fig.6

  • 8/8/2019 Short Circuit Ppt Latest

    16/26

    Fig.7

  • 8/8/2019 Short Circuit Ppt Latest

    17/26

    7. For proper pressing and clamping of windings perma wood coil

    pressing rings of adequate thickness are provided in case of

    transformers generally above 500 KVA ratings.

    8. Tie rods and core clamps are to be of adequate cross section and

    section modulus to withstand predetermined forces and bending

    moments.

    9. In case of power transformers with continuous disc winding,

    failure can take place due to bending of conductors betweenspacers. Hence, number of spacers are to be matched for the

    required span of unsupported conductor

    10. Against radial forces, adequate number of supports are to be

    provided between LV and core to prevent collapse of LV against

    core or buckling of LV winding. (ref fig 8 extract from BHEL bookon power transformers)

  • 8/8/2019 Short Circuit Ppt Latest

    18/26

    Fig.8

  • 8/8/2019 Short Circuit Ppt Latest

    19/26

    PRECAUTIONS FOR MANUFACTURING SHORT

    CIRCUIT PROOF TRANSFORMERS.

    1. HV & LV coils are to be wound tight under full tension to meetdimensions as per design requirement.

    2. As already emphasized electrical centers are to be exactly matched.

    3. Coils are to be thoroughly dried and pre-compressed for designdimension. This is similar to the pre-stressed concrete principle.

    4. During assembly of core and coils care should be taken to maintainthe end insulations as per design information. All the three limbs areto be of exactly equal height so that equal pressing is obtained for all

    the three limbs.

    5. Core bolts and tie rods are to be fully tightened in order to properlysecure the windings.

  • 8/8/2019 Short Circuit Ppt Latest

    20/26

    6. All the leads are to be properly crimped, bolted or brazed as

    applicable so that the joints will not give way due to pulling forcesduring the short circuit.

    7. Long lengths of unsupported leads are to be properly secured by

    providing wooden cleat supports.

    8. CCAs are to be properly secured to the tanks by the manufacturers

    standard practice.

    9. Tanks are to be of adequate strength to withstand abnormal

    pressure created during short circuits. To meet this sheetthicknesses are to be appropriate, welding to be perfect and

    adequate stiffeners are to provided depending on the rating of

    transformer.

  • 8/8/2019 Short Circuit Ppt Latest

    21/26

    METHOD OF CONDUCTING DYNAMIC SHORT CIRCUIT

    TEST

    Brief steps followed as per IS 2026 are listed below.

    1. First following routine tests as per IS 2026 are conducted.

    a) Measurement of winding resistance.

    b) Measurement of voltage ratio.

    c) Measurement of impedance voltage/ short circuit impedanceand load losses

    d) Measurement of no load loss and current.e) Measurement of insulation resistance.

    f) Die-electric tests.- Power frequency voltage & induced overvoltage tests .

  • 8/8/2019 Short Circuit Ppt Latest

    22/26

    2. Peak value of short circuit current will be calculated.

    Distribution transformers up to 3150 KVA will fall in category 1 of

    transformers to be tested as per clause 8.1.1 of IS 2026. Hencesystem impedance is not considered for above purpose. Forhigher ratings system impedance us to added to the transformerimpedance for short circuit current calculations.

    3. Than the transformer will be subjected to actual shots afterpreliminary calibration shots. There are two methods ofconducting the test.

    a) Pre-set method where one of the winding terminals will beshorted before applying the voltage.

    b) Post-set method where the terminals will be shorted afterapplying the voltage.

  • 8/8/2019 Short Circuit Ppt Latest

    23/26

    Normally for distribution transformers Pre- set method will be followed

    by CPRI. In this case in order to avoid core saturation supply will be

    connected to the winding farther from the core which will be generally

    HV. LV terminals will be shorted.

    4. Switching on will be controlled to get maximum asymmetry of thecurrent by closing the breakers at instantaneous zero voltage.Duration of the shot will be 0.5 seconds.

    5. If the transformer is having taps number of shots will be three oneach limb that is three in highest tap position on one of the outerlimbs, three in nominal switch position on the middle limb andthree in lowest tap position on the other outer limb. After each testreactance measurement is made and tests will be continued onlyif the variation is within 2.0% of the initial value in case ofconcentric circular coils. If the same is above 2.0% it is an

    indication of major dislocation of CCA and hence test is notadvisable to be continued. For rectangular coils with impedance ofabout this reference value is 7.5%.

  • 8/8/2019 Short Circuit Ppt Latest

    24/26

    6. After the tests routine tests as per item 1 above will be repeated

    and compared with the initial values.

    7. After routine tests transformer will be opened and physical

    inspection of CCA is made.

    CPRI records the observation and does not declare categorically that

    the transformer has passed the test.

  • 8/8/2019 Short Circuit Ppt Latest

    25/26

    VELs RECENT EXPERIENCE

    S.No Transformer details Nature of failure Probable reasons Modification for successful testing

    1

    EVL 5 MVA

    Bangladesh HV winding collapse High axial forces From single group tap arrangement to double

    6.0% impedance group tap arrangement.

    2

    EVL 10 MVA

    Bangladesh LV winding Radial forces on LV high LV number of supports increased and LV

    6.0% impedance hard drawn conductor with higher tensile strength

    used.

    3PGCIL 400 kVA

    through SPIC

    1. After7th shotCore channels and tierods were found bent

    High axial forces at

    lowest tap

    1. As a precautionary measure HV round wire

    was replaced by strip conductor.

    2. LV winding dislocated

    &

    Insufficient strength of

    clamping structure 2. Electrical heights were exactly maintained

    end insulation

    damaged 3. LV conductor transposition was removed

    4. Higher size core clamp channel was used

    5. Common permawood ring was used for LV &

    HV

    6. Impedance value was raised from 4.0% to

    to 4.5% after taking customer approval.

  • 8/8/2019 Short Circuit Ppt Latest

    26/26

    THANK YOU