Commercial Air Conditioning SERVICE MANUAL Models AS072XVERA AS092XVERA AS122XVERA AU182XFERA AU222XFERA z Features z High energy efficiency z Newly designed V-appearance for wall mounted unit, step or stepless air flow control z New outdoor unit with valve cover plate, also the grille is changed from metal one to plastic one z Adjustable heating temperature compenstation z Free combination, multiple connection types with different types of indoor unit, total indoor load can be up to 135% than the standard match z Infrared control type z Central control and full automation, if connected with a central controller z New friendly refrigerant R410a, zero ODP, environment protection z Advanced technology, DC inverter control function z Health airflow and sterilize function for wall mounted unit, more healthy z Weekly timer (standard) z Group control function z Auto restart function z Low ambient temperature heating (-15 degree) function z Room card function Manual code: SYJS-013-05REV.3 Edition: 2007-04-14

SERVICE MANUAL - · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Embed Size (px)

Citation preview

Page 1: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioning

SERVICE MANUAL

Models AS072XVERA AS092XVERA AS122XVERA AU182XFERA AU222XFERA

Features

High energy efficiency Newly designed V-appearance for wall mounted unit, step or stepless air flow

control New outdoor unit with valve cover plate, also the grille is changed from metal

one to plastic one Adjustable heating temperature compenstation Free combination, multiple connection types with different types of indoor

unit, total indoor load can be up to 135% than the standard match Infrared control type Central control and full automation, if connected with a central controller New friendly refrigerant R410a, zero ODP, environment protection Advanced technology, DC inverter control function Health airflow and sterilize function for wall mounted unit, more healthy Weekly timer (standard) Group control function Auto restart function Low ambient temperature heating (-15 degree) function Room card function

Manual code: SYJS-013-05REV.3 Edition: 2007-04-14

Page 2: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

CONTENTS Contents………………………………………………………....2 1. Description of products & features………………………...3 2. Specification………………………………………………….6 3. Safety precaution……………………………………………104. Net dimension of indoor and outdoor……………………..12 5. Installation instructions………..……………………………136. Parts and functions………………………….………………367. Remote controller YR-H65...……………………………….378. Refrigerant diagram…………………………………………459. Electrical control functions………………………………….4710. Diagnostic information and trouble shooting...………….5911. Electrical data………………………………………………6512. Performance curves.......................................................7113. Noise level.....................................................................7514. Air velocity distribution...................................................78

-2-

Page 3: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA 1.Description of products & features 1.1. Products code explanation A U 18 2 X F E R A

Climate type: T1 (see table 1)

Design number (R stands for design sequence, DC inverter

type) Product type: A stands for heat pump type, refrigerant is R22

B stands for heat pump type, refrigerant is R407C

E stands for heat pump type, refrigerant is R410A

N stands for cool only type, refrigerant is R407C

Appearance character

Product series: X stands for multi-split series

Applicable voltage: 2 stands for 220-230V/50Hz,

4 stands for 220V/60Hz,N stand for 380-400V/50Hz

Cooling / Heating capacity,18=18000BTU/h

Product type : “B” stands for cassette type, “C” stands for

convertible type, ”D” stands for duct, “S” stands for wall

mounted type, "E" stands for ceiling concealed type, “U”

stands for outdoor unit

Air Conditioner

1.2 Brief Introduction for T1、T2、T3 working condition

1.3 Operating Range of Air Conditioners Working temperature range

Rated Maximum Minimum Indoor DB 27 32 18 WB 19 23 14 outdoor DB 35 43 10

Cooling

WB 24 26 6 Indoor DB 20 27 15 WB 14.5 -- -- outdoor DB 7 24 -15

Heating

WB 6 18 --

Climate type Type of Air Conditioner

T1 T2 T3

Cooling Only 18 ~43 10~35 21~52

Heat pump -7~43 -7~35 -7~52

Electricity Heating ~43 ~35 ~52

-3-

Page 4: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

1.4 Product features

High efficienct, universal outdoor unit The outdoor unit can match with wall mounted type, duct and cassette type indoor unit. One set

outdoor can match with multiple indoor units, up to 3 sets. Even when you have already installed

the air conditioner, if you want to add or reduce one unit, go ahead freely as long as your operation

complies with our design. Greatly convenient for designer and installer.

Total indoor load can be up to 135% than the standard match

The total capacity of all indoor units can be 135% more than the mominal cooling capacity, but the

total indoor cooling capacity will not be increased.

Newly designed V- appearance indoor unit

The wall mounted type indoor unit adopts the newly designed V appearance, more fashion, more

beautiful. The unit is designed with the health airflow and sterilize function, which will make the air

more healthy. Also the air blow direction can be set as step or stepless control, much convenient to

control.

Newly designed guarding plate of valve

In order to protect the valve against the dust, the rain or the snow, etc. we add a

guarding plate to the valve.

Adopt the much friendlier refrigerant R410a

The air conditioner system adopts the greatly friendly refrigerant R410a, which is protective for the

ozone layer and is good to avoid the earth getting warmer. Benefit for the environment.

Adopt the advanced DC inverter technology The system adopts the advanced DC inverter technology, which can consume less power energy to

realize the equal efficiency, saving money for you.

With air inlet filter, enhance the air quality

The high efficiency filter can collect the dirt and remove the bacterium, which can be installed on the

easy-to-unload place, convenient to be cleaned.

Convenient infrared remote controller This remote controller YR-H65 can realize the healthy air flow and sterilize function, it is mobile type

appearance, so smart and compact.

And the infrared controller can be equipped with the controller holder, convenient to fix

the remote controller.

-4-

Page 5: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Auto–restart function (optional) All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will

automatically recover the previous running mode once the power supply is on.

Self-diagnostic function In the course of operation, if the failure occurs, the failure code will display on the wired controller or

on the operation panel. Then according to the failure code chart, you can eliminate the failure soon.

Central control function, if connected with a detector and a central controller That is convenient for building management.

Weekly timing function, if connected with a detector and a weekly timer

Adjustable heating temperature compensation In heating mode, the temperature compensation can be adjusted by the remote controller. If you do

not want the compensation, you can set the compensation as 0 degree.

-5-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

ONOFF

OFFON

When room card function is available,indoor will be controlled as below figure:

When room card is disconnected When room card is connected

Page 6: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

2. Specification

-6-

—— Cooling HeatingW 5300 7000W 1650 1800

W/W 3.21 3.88W 1500 1800W 500 500W 5800 7400W 2300 2300

——A / A 10.2 10.2—— 99% 99%

AModel / Manufacture ——Oil charge and type ——Type ——Number ——Type × Number ——Speed r/minMotor output power WAir-flows (H/M/L) m³/hType / Diameter mmFace area m²External mmPackage mm

————W

Noise level H/M/L dB(A)Weight Net / Shipping kg / kg

Type / Charge kgNo need to recharge mRecharge g/mLiquid mmGas mm

——Drop between IU & OU mPiping length between IU & OU mTotal liquid piping length mDrop between indoor units mMax.Drop between IU & OU mMax.Drop between IU & OU mMax.Drop between indoor units mMax.Piping length between IU & mMax.Total liquid piping length m

Power input

Minimum capacityPower input

Power facor(under rating power input)Max.Running current

Fan

Item Model AU182XFERAFunction

Power source 1PH, 220-230V~, 50Hz

Rating capacity

Maximum capacityPower input

EER / COP

Fuse size (recommended size)TNB175FLBM1 / MISTUBISHI ELEC.

Twin Rotary (DC inverter)1

25

Out

door

uni

t

Compressor

Dimension(L×W×H)

Heat exchanger

Crankcase heater power

Axial × 1

670CC, MEL 56

928/288/6801015/405/760

850/ 700/ 50035

about 3000TP2M / 7.0about 0.52

35

Refrigerant control method PMVDefrosting method Automatic by reversible cycle

Pipe 3* Φ6.353* Φ9.52

≤10≤5

45

3020

≤30

10(indoor unit lower than outdoor unit)

25

15 (indoor unit higher than outdoor unit)

≤1

5

2. Large drop and long piping installation will obviously reduce the totao capacity.1. The above performance data are from the combination of AU182XFERA+2*AS092XVERA+AS122XVERA.

51/-/-54 / 60

Pip

ing

Refrigerant R410A / 2.0

Connecting method FlaredBetween I.D &O.D

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 7: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

—— Cooling HeatingW 6400 7300W 2100 2000A 9.3 8.9

W/W 3.04 3.65W 1500 1800W 500 500W 6800 7500W 2900 2900

——A / A 12.9 12.9—— 99% 99%

AModel / Manufacture ——Oil charge and type ——Type ——Number ——Type × Number ——Speed r/minMotor output power WAir-flows (H/M/L) m³/hType / Diameter mmFace area m²External mmPackage mm

————W

Noise level H/M/L dB(A)Weight Net / Shipping kg / kg

Type / Charge kgNo need to recharge mRecharge g/mLiquid mmGas mm

——Drop between IU & OU mPiping length between IU & OU mTotal liquid piping length mDrop between indoor units mMax.Drop between IU & OU mMax.Drop between IU & OU mMax.Drop between indoor units mMax.Piping length between IU & mMax.Total liquid piping length m

2545

1. The above performance data are from the combination of AU222XFERA+AS092XVERA+2*AS122XVERA.2. Large drop and long piping installation will obviously reduce the total capacity.

Connecting method FlaredBetween I.D &O.D ≤5

≤10≤30≤1

10(indoor unit lower than outdoor unit)15 (indoor unit higher than outdoor

5

55/-/-54 / 60

Pip

ing

Refrigerant R410A / 2.03020

Pipe 3* Φ6.353* Φ9.52

Defrosting method Automatic by reversible cycleCrankcase heater power 35

Dimension(L×W×H)

928/288/6801015/405/760

Refrigerant control method PMV

about 3200Heat exchanger TP2M / 7.0

about 0.52

Out

door

uni

t

Compressor TNB175FLBM1 / MISTUBISHI670CC, MEL 56

Twin Rotary (DC inverter)1

Fan Axial × 1960/ 700/ 500

35

Max.Running currentPower facor(under rating power input)Fuse size (recommended size) 25

Maximum capacity Power inputPower source 1PH, 220-230V~, 50Hz

Power input

EER / COPMinimum capacity Power input

Current input

Item Model AU222XFERAFunctionRating capacity

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-7-

Page 8: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

-8-

—— Cooling Heating Cooling HeatingBTU/h 7000 8000 9000 10000

W 2000 2300 2500 2900————

10‐³×m³/h 1.0 / 1.0 /N, V, Hz

A / A 0.15 0.15 0.15 0.15Type × Number ——Speed r/minMotor output power WAir-flows (H/M/L) m³/hType / Diameter mmTotal area m²External mmPackage mm

Drainage pipe material, diameter mm————

Noise level H/M/L dB(A)Weight Net / Shipping kg / kgRefrigerant Type ——

Liquid mmGas mm

——

——BTU/h

W10‐³×m³/h

————

N, V, HzA / A

Type × Number ——Speed r/minMotor output power WAir-flows (H-M-L) m³/hType / Diameter mmTotal area m²External mmPackage mm

Drainage pipe material, diameter mm————

Noise level H/M/L dB(A)Weight Net / Shipping kg / kgRefrigerant Type ——

Liquid mmGas mm

——

R410A6.359.52

Flared

1250/1150/105027

550/480/430

about 0.20

/

0.15 0.15CROSS×1

AS122XVERACooling1100032001.6

Heating130003800

Pip

ing Pipe

Connecting method

39/36/337.6/10.6

PVC, 11.4/16.4Controller type Infrared (YR-H65)Refrigerant control PMV on outdoor unit

Dimension(L×W×H)

795×197×265880×315×330

Heat exchanger TP2M / 7×0.35

Power source 1, 220~230, 50Running current

Fan

Power cable 3 × (1.0~1.5mm2 )Communication cable 2x(0.75~1.25mm2 ), must be shielded

FunctionCapacityCapacityDehumidifying capacity

FlaredItem

Pip

ing

R410A R410APipe 6.35 6.35

9.52 9.52Connecting method Flared

PMV on outdoor unit36/33/30 38/34/317.6/10.6 7.6/10.6

795×197×265880×315×330 880×315×330

PVC, 11.4/16.4

520/450/390Heat exchanger TP2M / 7×0.35

about 0.15 about 0.15

CROSS×11150/1050/950 1200/1100/1000

27 27

Running currentFan CROSS×1

480/430/380

Dimension(L×W×H)

795*197*265

Controller type Infrared (YR-H65)Refrigerant control

Communication cable 2x(0.75~1.25mm2 ), must be shieldedDehumidifying capacityPower source 1,220-230~, 50

CapacityCapacityPower cable 3 × (1.0~1.5mm2 )

Item Model AS072XVERA AS092XVERAFunction

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 9: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WBThe noise level will be measured in the third octave band limited values, using a Real Time Analysercalibrated sound intensity meter. It is a sound pressure noise level. The detailed method please refer tothe following information:

Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction.Testing method:

outdoor unit:1.air outlet from side: the noise level is the average sound pressure level measured from front, left, rightdirections.2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, rightdirections.measured point:H ( height to the ground) = (h (unit height) + 1m) /2and, it is 1m to each side.

mounting-on-wall unit:

Note: ⊙ is the real time analyser position

0.8m

1m

h

1m1m

1m1m

-9-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 10: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

3. Safety precaution

Carefully read the following information in order to operate the airconditioner correctly .Below are listed three kinds of Safety Cautions and Suggestions.

WARNING!CAUTION! Incorrect operations may result in injuries or machine damages; in some cases may

cause serious consequences.

Incorrect operations may result in severe consequences of death or serious injuries.

INSTRUCTIONS: These information can ensure the correct operation of the machine.

Be sure to conform with the following important Safety Cautions.The Safety Cautions should be at hand so that they can be checked at any time when needed.If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.

WARNING!

If any abnormal phenomena is found(e. g.smell of firing), please cut off thepower supply immediately , and contactthe dealer to find out the handlingmethod.

Don't dismantle the outlet of theoutdoor unit.

The exposed fan is very dangerouswhich may harm human beings.

switchoff

In such case, to continue using theconditioner will damage the conditioner,and may cause electrical shock or firehazard.

Incorrect maintenance and repairmentmay cause water leak, electrical shockand fire hazard.

When the unit needs maintenance andrepairment, please call dealer to handle it.

After the unit being used for a long time,the base should be checked for anydamages.

If the damaged base is not repaired, the

unit may fall down and cause accidents.

-10-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 11: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Air-conditioner can't be installed inthe environment with inflammablegases because the inflammable gasesnear to air-conditioner may cause firehazard.

Connect earthing wire.

Use discharge pipe correctly to ensureefficient discharge.

Earthing wire should not be con-nected to the gas pipe, water pipe,lightning rod or phone line, in-correctearthing may cause shock.

Incorrect pipe use may cause waterleaking.

Earthing

WARNING!

Installed electrical-leaking circuitbreaker .

It easily cause electrical shock withoutcircuit breaker.

Please let the dealer be responsible forinstalling the conditioner .

Incorrect installation may cause waterleak, electrical shock and fire hazard.

Call the dealer to take measures to prevent the refrigerant from leaking.

If conditioner is installed in a small

room be sure to take every measure in

order to prevent suffocation accident

even in case of refrigerant leakage.

When conditioner is removed or

reinstalled, dealer should be responsible

for them.Incorrect installation may cause water

leaking, electrical shock and fire hazard.

Nothing or nobody is permitted toplaced on or stand on outdoor unit.

The falling of goods and people maycause accidents.

Don't operate the air-conditioner withdamp hands.

Otherwise will be shocked.

Only use correctly-typed fuse.

May not use wire or any other materialsreplacing fuse, other-wise may causefaults or fire accidents.

-11-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 12: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

4. Net dimension of indoor and outdoor AU18/222XFERA:

870

305

225

Wall mounted unit:

-12-

18

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 13: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

5. Installation Instructions R410A The working pressure of R410A is approximately 1.6 times higher than R22. Because the oil in the

refrigerant is different, please do not mix them.

Refrigerant R22 (single) R410A (mixed) R407C (mixed)

Oil Mineral oil (SONTEX 200LT) Synthetic oil (POE oil) Synthetic oil (POE oil)

Pressure ratio 1 Approx. 1.6 Approx. 1.1

Operation flow

1. Calculate the refrigerant additional charging amount, and charge a suitable amount.

1. Air purging by refrigerant is prohibited seriously2. Use a special vacuum pump with reverse check mechanism

1. Charge the nitrogen to the set pressure2. 24 hours later,check if the pressure in the pipe has reduced

1. Do not connect the power supply

1. Use piping material of the specified thickness2. Do not use dirty pipe 3. Always flow nitrogen during welding work

hand over

trial running and adjustment

maintenance panel installation

gas leakage check

additional refrigerant charging

evacuation and drying

leakage test

refrigerant piping connection

outdoor unit installation

outdoor unit foundation work

electric wiring work

remote controller installation

insulation work

duct work

drain piping work

refrigerant piping work

indoor unit installation

operation chart preparation

1. Always inspect the used refrigerant2. Always use the specified refrigerantrefrigerant inspection

prepare work schedule

-13-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 14: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Piping material 1. Use the correct refrigerant piping and materials for R410A

2. For the pipe wall thickness, see the table below:

Pipe diameter Φ6.35 Φ9.52 Φ12.7 Φ15.88 Φ19.1

Pipe wall thickness 0.8 0.8 0.8 1.0 1.2

Note: Always observe and comply with the local regulations when installing the refrigerant piping.

Tools R410A work requires a number of special tools (* symbol). Since the tools used in R22 work

cannot be used for R410A, provide the tools separately.

Tool name Process and application

Pipe cutter Piping cutting

*Flaring tool Pipe flaring work

*Torque wrench Flare nut connection

Expander Expansion at pipe connection

Pipe bender Pipe bending work

Refrigerant piping work

Nitrogen gas Pipe oxidation prevention

Welder Pipe brazing

Air tightness test

*Gauge manifold

*Charging hose

Vacuum evacuation and refrigerant

charging operation check

Air tightness test

Refrigerant additional

charging

*Vacuum pump (with

adapter)

Vacuum drying

Electronic scale

Gas leakage detector Gas leakage test

Refrigerant additional

charging

Work precautions Refrigerant check: Before work, check the used refrigerant and prepare materials matched to the

refrigerant.

Refrigerant piping: Observe the basics of refrigerant piping to avoid the unnecessary problems. In

addition, when performing the welding work, seal in the nitrogen gas to the pipes, and prevent it

from the oxidation.

Leak pressure detection: Perform seal detection and make sure there is no refrigerant leakage.

Vacuum drying: If the vacuum pump has not the reverse flow check mechanism, use the pump

together with a reverse flow check adapter.

Additional refrigerant: Charge a suitable amount of refrigerant with a special R410A gauge

manifold and charging hose.

-14-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 15: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

-15-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

!"#$ %

&'

()*# + ,

-..

& ./ . 0

1 ...2 3 . 3 / .3 . .0

11.4

1./

)

5&

6

!"#$ %

%/. 3 .

#/78).#5&4%9&8%&4%9&87 )

&:5;%<"= &

8.

&:%%%<"= &

8

/

>

/

>

6, 1?4@? #%84%#86 1?4@? 5;8458

6, 1? #84%(86 1?

6, 1? %-86 1? %86, 1?4@? %845;86 1?4@? 58

3..&3.. !""#$ %"$ / .0 * .

/ .0

584(8

Page 16: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

@A ? . 1 - 2 @A ? 2 2 @ 2A+ 2 (

% 2 2 6 (> ( (% 7 . (

. ( -2 --. (2 ( -. . (2 ((> = 2 (2 (2( -5 =2 -/? 2 ( . - % ( -+ . B - ((% < + ( 6 -(% - -!+ - 2 ((. ( 2( 7( > ( / . - (

2( 482 -@. - 24 A0 @A = + 2( 22 -2 (@A ? 7 - (

-16-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 17: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

62 2 - -62 - -2 62 -2 62 -62- 2 @ A62 4 22 . + 2

"

4

$

"

#

4

4

0

Clamp7

$

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-17-

Page 18: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

40 -- ( 5( $. -> $

?

7 2( 1

4

4

' $

%

. 2+ 2

. 2 @ A

. ! - (

>

&

%

5

5 4

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-18-

Page 19: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-19-

! ! "

#$%

#$&

'''

!"!'

%( ) ! ( &*

#+! %,

! ! "

,- #.,/ #%,/ #.# #%,- ,- ,/,- ,- #%,- ,/ ,/,- ,/ #%,/ ,/ ,/,/ ,/ #%

#$%

#$&

''',/ #% #%

'

#$

Page 20: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

$7

%- 2 7 -((

(

&4

&$

&"

D

)

2

0 *

%2>27

%2>27#

. 5+9

&4@-A

&$@-A

&"@-A

D

*B

6

0 -

0

C4

C4

C

C

3

3*B

6

6 -

0

'"

E$

C4

C4

C"

C

C4

C4

C"

C"

&4D&$D&" C" C

&

#

'"@4311A+:

E$@"3:11A+:

4*

2 - 9

"& (

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-20-

Page 21: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

-21-

!" #$

%$&'()!*+,," *-.

/&0)1!(+-,," )2.

( 34

5

63

5

#$&

)7,

6

% #

8 &9!"

%$

/

'()!*+:"

0)1!(+-:"

2-;*)

*2;*)

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 22: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

.(2

.

( 2

'

' *

$-

"-

*

E'

'0 2

$-"- (

-

&

$-

"-

#

#@4%A

8@4%A

=

7

$-

"-

$-

"-8

8*

&

. -

. .

6 2 - . 2-

40 1"-2

1$-"-2

/ @A

/

@ A

$= 2

. @A

2(4

"8B4%(

456@,'A

% B2

1&1 7(

4$. (

2((2

"

= $-

(E% '2 $

-( (

(H

. (2

% (B2

-

, (2 2

$-"-1

-

-22-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 23: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

4< 2- - 7 (( % ?2 ( = 2 2 -6-462$$$"8G2B I . 2 ( (2 - !"4%$8%7$%$8%7@6( A6(

(

$? ? ! 2 2 2 ( ? ! 2 2 - (2 * - -

7

?5 >(

7 6 ?6

(

6

7

0

0

$-

"-

%

$-

"-

$-

"-

>

7

7%9.=

. (2 -

( 8B 2

(

-23-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 24: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

"?

& - ? - 2- 0 . 0 . J = 2 0 .

?

7 % 2 - 2 ? 2 -.

(

?%

?>

8

6 %2 2 2 (-% 2 7 &2 >2 (-% 2 > 6 -

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-24-

Page 25: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

!"# $%"# $&"# $'" $"# ( # %&)*

+, -

# ,

!.%%)/%&)*0).1 2

-.)34/5&6')%

# 78 "-.)34/5%9!%

# 78 "-.)34/5&6%%

: )

42

,

#

( 8 43

-25-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 26: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

4A. 4'72 2 "72 $A 2 4'7 2 2 "7"A6( - ( A% $ 2( A% 2(2 - " 'A0 2 - 2 ,A= 6(-+

#( H H% - (H. -+H.-H. -- H.- - H. -H0-H0 -H

7( 2 (FF

-26-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 27: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Indoor unit installation

! "# $

% &&

' (

) &

*+, & &

& - & .

/ & & & 0 1 & 1 - &1 & &.

/ / & 2

/ & -

*

(- &1 &

" - 34 1 &"*2(+54

4

6

-

7 8$8(%"(*'*)("*""*+(((+(%**%(**'

/94:94/94:94

-

/94:94

/94:94

8

6+7;<"=((#+%(>5?7#+)(>5?7#*((>5?7

4 @A

6+7;<(>*(

-27-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 28: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

:7;-;=B

4& &9 # &4 #

-;#7C4-D;# 9 # &4 # &4 & & - 1

4C-D;#B

/0 & 1 11 1 1 &

D

D 0

-&@A1 & &1

-1 1& E

:& 1 - & 1 E

3 - & 1 E

/0 & 2

9 &&.

4

- 1 &

:

- & 1 E

/0 & 10

:7;-;=B - & .4C-D;B - & .!&

-28-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 29: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

$&&

- &

! "

- 1 &

#

&

$ D

%

8& & 1 &

&

#

! ""

D &

D &

!'(%#)

3 1 &&

- & 1 E$

!'(%#%#(#!**!(%#

! +

( " "

' - &

? 1 1 1 &

- &

?

-29-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 30: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

,* -

,-

,% -

& @A3 @A# @A; @A &1 @A-@AF & &@A; @A3 1 511 *& 1 1&1 11 &

1 &

&

4 @A4 10 @A6 0 ;

-30-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 31: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

./ %

C & : & G3G1 - 1 & & 1 1 :&1 !1 &

/ 0

& C *41 4 1 & G3G 1& G6G7 &

3 & 1 ! G3G1 & : 1 &

/ &

/0 /0

*D (/ "C - $ & &1 : &4 4 / +41 & : &4 1 & - & &1 1 /0

1$ -

%34 *7 D

# *"#<

# # *(8

-6$# ** 4 #

"+/ *+4

(# # )F

*#/@ 11 A '3?$

-31-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 32: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

23 /4$

4 ; 4

$

5 4

*4& 1 1 $

1 &

(8 1&

1 &

"8 6 < 6

H'+

35

+(

: 1 $

* (7 "3 ?$6

6?$

?$#E6 #E@A

+'**+*

"@*2A

)(@"2'A

#

6!

;3

; 9 4 / ? <;

4 6

=&

/6

7

-

-

- & &

- &

-

- 5 1 1 1 &

- 1

8 + 1 & - &

-32-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 33: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

6

/

3

-2

4

-2 &

8(

<$

9% 4 &1 1 :1 4 2 1 &6& & 8 & & $- $ & 1 & &

!'(%#):!(*%%;(&;/'#((**#%%<=

/7/ 1 1- 1 &1 1 - 1 @*A- @(A- 2 1 1 @"A4 4 &1 $

- D

:

%+

@# A3

* C @ A9C 349( # & 1 !93 & !43 1 #;/9,!/3 - 1 *!- 91 (!- 41 "!??$ *

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-33-

Page 34: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

--& 1 ? =I 1 & D & FD & 1 & " /-3 #:+*#:+(/-3 #:+*#:+( 34999& 1 & 4 1 1 349 349/4 /-3*#:+*D<< D;1 1 &#:+( ?C#:+( @/D;D46;=?D6?7/-3#:-46?#A

>( " 4 & /34 :1 1 ! & $

>( "

4 & & *1 EE @3-3-3-3-A 1 9 4/& <C 1 D<< D;1 4/&&J*K &1 =3 J#??3K 1 & & 1 3 J#??3K 1 J*K1 4/&J*K!3 J#??3K 1 J(K1 4/&J(K!3 J#??3K 1 J"K1 4/&J"K!6C 1 1 D;

6 L(necessary procedure): 1 & #;/9, & & & EE @33333A1 4/& 3& & 1 $

-& L- & L & L-& L L- $& L- $&L-L

*("%'

*("%'

!"

*

(

"

*("%'

*("%'

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-34-

Page 35: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

>. - . &L/ L: 3 3 11 354 ;

-35-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 36: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

6. Parts and Functions

Front panel

Air inlet grille

Air inlet grille

Louver

Display board

-36-

Page 37: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

!"#

$% & &

&'

$ ( &&)' &

& *++*,++

&')- &.

*++

%/*,++0-

& 1-21+1*

3

$ 0&'

%

1

& (&( -- 0 ( &&4)'-&( - & (/ (0 ()-55

& ( 0-

+1* & 016+1*+1*+1*

%,6* ,+

& (&.&. /( & ( 0-

7 . .&.&./( (& /0 () .-00

*,++&.+ &.

$/ &. -&.

$ &5&.8(0- &9

-0.&.&'&.

-&. &. ( -

' &.

$& &.

& &.

$6*

$:

+(1 &.

8(0- &9

6 1

"

;

<

=

>

?

#

3

"

;

7 1

* (& (@ (0&&/& &.0- > 3

11+6 (& (0&/1,7&

+ (- & 1

3" 3=

7.

<

=>?3#

3333"

3;3<

3 3=

3>

3?

"#

"

$% $6*

$

$

$: 3 "

11+6

+$

!"6(- 0 (0 0 &) &&&'(-&)A- 0&&/%)- B1BB%B0&(% (/&&0 ()- ' /&&(C-'&.10 0$B1BB%B 0&(/(&&' /'

#"$%&6(-- (& ( &. (@(& (- ( ) / (& ( (@(&(-&)/ (=/ (- .)&/&&4 (/ ( &&@ 0)6(& D .0&- &(D@ .0&- &/& &( && ( (@ ) -)@ (& ( (- (-&)(

-37-

Page 38: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

3D#".)

*

$

0 & () & (/) 0 <* (/ ) (-&)&.- //D .) /(&0 ( &&E 0- &&.E /' &&-(D ( '. @ () - /E )-0&0 (.&.0 'D- A- '.6( (//. (/ ) &0/ ( (&&-&

%'&()*+%,$&( &.BB-(/ (@ () &&- 3D#".) 8.&97- ( (&&/ ( (BFB,BDB&C- &&- %- (@

-$%&

3

%*,++)- -(@- - (&.8G $%9

%)- +( (0&&/

;

&&

%*,++)- -

%+1*+( (0&&/

&&

- (&.6(01 (- &&. ( -

* -1- - /&&)(/&.- /&&& ( &0 (

1 2 +1* 1

$& 1- -BB- -

6 1

<

$& )- %%)- @. ()- @. ()- 0 ()- ' /&&C-'&.

"

*++

%

1 +1*

$% $6*

$

$

$:

11+6

$

3

<

"

;

1

-38-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 39: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

&($%&%*,++)- -(@- - (&.8G $%9

%)- +( (0&&/

$& )- %%)- @. ()- @. ()- 0 ()- ' /&&C-'&.

%*,++)- -/( . (0 (G /&&(/ (@-

- (&.6(01 (- &&. ( -

<

"

3

$& & $(/BB &

%+1*)- +(0(0&&/;

&&

&& 1 2 +1* 1

6 1

1

*++

%

1 +1*

$% $6*

$

$

3

"

$:

11+6

+$

<

"

;

1

,$%&

%*,++)- -(@- - (&.8G $%9

%)- +( (0&&/

$& . (/BB.

$& )- %%)- @. ()- @. ()- 0 ()- ' /&&C-'&.

%+1*)- +(0(0&&/

"

3

;

*++

%

1 +1*

$% $6*

$

$

3

"

&& 1 2 +1* 1

&& 6 1

$:

11+6

+$

<

"

;

-39-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 40: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

1

%*,++)- -/( (0 (G /&&(/ (@-

- (&.2/( )3&/ ( - /&&- &. 6&0+1*

<& D&/0&/

F3

(3&/ ( - /&&-&2

/( (( (

%$%&%*,++)- -(@- - (&.8G $%9

%)- +( (0&&/

$& + (/BB+

%*,++)- -/( (0 (G /&&(/ (@-

;

3

" %+1*)- +(0(0&&/

* ( 4 )& /&& )(/&.+ B1B0 @&)& .&0&&/

6

- (&.

6

*++

%

1 +1*

$% $6*

$

$

3

$:

11+6

+$

";

&& 1 2 +1* 1

%&($%&

%*,++)- -(@- - (&.8G $%9

%)- +( (0&&/

$& BB

3

* +&&. . (0- @&

1 2 +1* 1

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-40-

Page 41: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

&).%'/-"

1

$/&-@8H &&-@9

/ $0

*++

%

1 +1*

$% $6*

$

$

85 &&-@9

3$:

11+6

+$

%

% 3

% "

% ;

% <

%

% =

% >

I,2,+1*,1891H*J

81$6*9

%

% 3

% "

% ;

% <

%

%+1*)- +(0(0&&/;

" $& )- %%)- @. ()- @. ()-

0 ()- ' /&&C-'&.

%*,++)- <

-/( (0 (G /&&(/ (@-

( //&&)&/- 0 ( 0 - &D0 @ 0-

6 1

1

*++

%

1 +1*

$% $6*

$

$

3

"

$:

11+6

+$

;<

"

-41-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 42: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

%- &-@ - &/ ( (/&&)(&0-& '@

*

&. 4 - (5 &&-@ // 0& - & &&( 0 4 G.-' &/0&

*

$0

+G

% ($6* 0G ((5 &&-@ .-

$/

%$6* ((5 &&-@@0- /

+G

% ($6* 0G (@ &&-@ .-

$/

%$6* (@ &&-@@0

$$%&

&-

0 ($&0- 10 (- ($&)-

-01&(%'',

10 0 ($& ( -/&&)0(( ( ( -(-& )00 ((- -- ( 0 (- ( ((/&&)/ ( 00 ( - (( ( ( - @ (&&

21*%&(8 (&D& (@ (0- 910 ($&- ( -/&&030 ((-( -/&&00 "(--- ()@ - ( /&&)&/0 -0"(-( - &/ ( ( - @-&

31%-%&-&(( /&&--- &&.& /'0&

41%-&(($&0- @&

1)- (-

($&- ($&-

$ ( -

&/ ((

&.

(-

(-

70 ) .- ($&)- ( /&& 0 )&& '.-&0 )&

-42-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 43: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

1

*++

%

1 +1*

$% $6*

$

$

$:

11+6

+$

03

03

1)- "(-

($&- ($&-

$ ( -

&/ ((

(

(-

(-

"(-

5$%& &- $ &' &.)0 80 392-& - - &&. 0&&/ 70.-/'- ( )'0- 0 .-0&&& (

*,++607)-&"%8",-'"&'$%&'1 /&&)&.

627'"&%)- (@. ()- &.(0&&/

&&

$& .-8*++9*++/&&0&(

637&"&(%,)- @. ()- 0)- ' /&&(C-'&. @. ()- 0)- ' /&&(C-'&./&&)(/ )A- / (3;(-

647)&&(,-"&(10 $)- 0BBBB 0&(&. G(-G8*++9 - &( -

* ++ *D++

1 3## % 3## % 3##1 3##71*

1

3

" $:

11+6

+$

; <

*++

%

1 +1*

$% $6*

$

$

-43-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 44: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

%'K- )- @& - &

&"10 &) /0&-( (-&) &&.0- /(-G A- %$)- 0 & 0 (@-

1

1

%

+1*

*++

1

$% $6*

$

$

$:

11+6

+$

10 - (- (/'% (& ( )- ( /&& &. B B ( - ) (& ( 8 ( @ @9 % ( & ()- ( B B &. ( (& ( &&8 -00 ( @ @9

* 6(0 /' (- /&&- &&. -00 @ @

& (

10 ( 0& ( ( @ /&& &- 0 @/((00 @&.)& (- 0 @ L @ ( ( ( ) D'&& & (- 0 ( ' (0((& (.

1)- & (

%*9"*&$%&

-44-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 45: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

8. Refrigerant Diagram

TOC

I

TaiA

TaiB

TaiC

TmA

TmB

TmC

Tc2C

Tc2B

Tc2A

Tc

Te

Tao

TsTd

CAP

ILLA

RY

ACC

UM

ULA

TOR

4-W

AY

VALV

E

WAY

-C

WAY

-B

WAY

-A

PMV-

C

PMV-

B

PMV-

AST

RAI

NER

MU

FFLE

R

HEA

TER

CO

MPR

ESSO

R

LP S

WIT

CH

HP

SWIT

CH

Tc1C

Tc1D

Tc1C

-45-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 46: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Mai

n pa

rt e

xpla

natio

n:

No

.M

ain

Par

t Nam

eS

pec

ific

atio

nF

or

wh

at p

urp

ose

?

1H

eate

r22

0V, 3

5WH

eat u

p th

e co

mpr

esso

r w

hen

syst

em s

tops

to a

void

liqu

id c

ompr

essi

ng a

nd li

quid

flo

od-b

ack

2C

ompr

esso

rdc

inve

rter

Driv

e th

e sy

stem

to r

ealiz

e th

e re

frig

eran

t circ

ulat

ion

3T

d se

nsor

50K

@80

@F

or ta

rget

SH

con

trol

and

hig

h di

scha

rge

tem

prat

ure

prot

ectio

n

4H

P s

witc

h4.

5 / 3

.7M

paC

ut o

ff th

e sy

stem

whe

n di

scha

rge

pres

sure

is to

o hi

gh to

pro

tect

sys

tem

54-

WA

Y v

alve

/C

oolin

g / h

eatin

g sw

tichi

ng

6T

oci s

enso

r10

K@

25@

For

targ

et s

uper

hea

ting

cont

rol w

hen

heat

ing

7T

c se

nsor

10K

@25

@F

or h

igh

pres

sure

/ fre

quen

cy/ o

utdo

or f

an s

peed

con

trol

whe

n co

olin

g

8T

ao s

enso

r23

K@

25@

For

targ

et f

requ

ency

ran

ge a

nd h

eate

r co

ntro

l

9T

e se

nsor

10K

@25

@F

or d

efro

st o

pera

tion

and

low

pre

ssur

e co

ntro

l whe

n he

atin

g

10P

MV

s1.

5mm

, 500

PLS

Ref

riger

ant d

istr

ibut

ioin

and

targ

et S

H(c

oolin

g) a

nd S

C(h

eatin

g) c

ontr

ol

11LP

sw

itch

0.05

/ 0.

15M

paC

ut o

ff th

e sy

stem

whe

n su

ctio

n pr

essu

re is

too

low

or

syst

em s

erio

us le

akag

e to

pro

tect

sys

tem

12A

ccum

ulat

or1.

5LS

epar

ate

the

liqui

d re

frig

eran

t and

gas

ref

riger

ant i

n su

ctio

n lin

e to

avo

id li

quid

flo

od-b

ack

13T

s se

nsor

10K

@25

@T

o ca

lcul

ate

the

targ

et S

H a

nd S

C, a

nd c

ontr

ol th

e st

art u

p of

the

com

pres

sor

14T

c210

K@

25@

To

calc

ulat

e th

e re

al s

uper

hea

ting

valu

e to

geth

er w

ith T

out t

o op

erat

e th

e P

MV

s, f

or ta

rget

com

pres

sor

freq

uenc

y co

ntro

l and

low

pre

ssur

e pr

otec

tion

whe

n co

olin

g

15T

m10

K@

25@

To

calc

ulat

e th

e re

al s

uper

coo

ling

valu

e to

geth

er w

ith T

in to

ope

rate

the

PM

Vs,

for

targ

et c

ompr

esso

rfr

eque

ncy

cont

rol a

nd h

igh

pres

sure

con

trol

whe

n he

atin

g

16T

c110

K@

25@

To

calc

ulat

e th

e re

al s

uper

hea

ting

valu

e to

geth

er w

ith T

in to

ope

rate

the

PM

Vs

17T

ai23

K@

25@

To

calc

ulat

e th

e te

mpe

ratu

re d

iffer

ence

bet

wee

n th

e in

let a

nd o

utle

t of

the

indo

or u

nit t

o co

ntro

l the

targ

et r

requ

ency

and

TH

ER

MO

. ON

or

OF

F.

-46-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 47: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

9. Electrical Control Functions

3.1 Refrigerant diagram

Outdoor electric control functions:

-47-

1. Switch setting and functions: No Item

A8 Set in factory Switch function: SW5-1---outdoor fan motor selection, ON: DC fan motor; OFF: AC fan motor

C1 Switch function: SW5-2---defrosting data setting, ON=6degree, OFF=8degree (set when out of factory). For the place where is easy to frost, it is 6 degree; for the place hard to frost, it is 8 degree.

C2 Switch function: SW5-3,SW5-4---piping length selection, the set data is M when out of factory. S(SW5-3=OFF SW4=ON) L(SW5-3=ON SW4=OFF) - (SW5-3=ON SW4=ON) M(SW5-3=OFF SW4=OFF)

C3 Switch function: SW5-5,SW5-6---outdoor horse power selection (for different outdoor, the current limitation is different too. The corresponding selection must be taken, or the module protection will occur. )

2HP(SW5-5=OFF SW5-6=ON) 2.5HP(SW5-5=ON SW5-6=OFF) 3HP (SW5-5=ON SW5-6=ON) 3.5HP(SW5-5=OFF SW5-6=OFF)

C4 Switch function: SW5-7,SW5-8: SW5-7-pre-set, set as OFF when out of factory. SW5-8-silent operation function, ON---available, OFF---not available (set when out of factory) When it is ON, the max. fan speed is Class-6, and the max. running frequency is 10Hz.

C8 Set in factory 2. Defination of 4-bit dip switch SW5 on failure indicator board:

1 2 3 4 Defination OFF OFF OFF OFF State when out of factory (normal state)

OFF ON OFF OFFCompulsory cooling: frequency 60HZ, outdoor fan motor Class-7, fixed open angle

300, the others are in normal state

ON OFF OFF OFFCompulsory heating: frequency 50HZ, outdoor fan motor Class-5, fixed open angle

300, the others are in normal state

OFF OFF ON OFF

Rated operation: auto changeover for cool/heat, max. frequency 53HZ(E) in cooling,

and max. frequency 72HZ(E) in heating, the frequency is set automatically in other

states.

3. Main control functions 3.1 Refrigerant diagram

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 48: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

TdTs

TaoTc

Te

TmC

TinC

TaiC

Toci

TouC

TinB

TmB

TaiB

TouB

TinA

TmA

TaiA

TouAHPSW

LPS W

3.2 Outdoor frequency control 3.2.1 Compressor running frequency range: 20~90RPS 3.2.2 Defination of high-efficiency operation and its frequency control In order to meet the cooling request at high ambient temperature and the heating request at low ambient temperature, we set the high-efficiency operation. Entering condition: cooling mode, Tao≥33(E), heating mode, Tao≤5(E). 3.3 Electronic expansion valve (EEV) control 3.3.1 Electronic characteristic

Max. open angle 500 pulse Driving speed PPS

3.3.2 Initialization of EEV EEV driving speed: open direction: 32MS; close direction: 32MS 3.3.3 Open angle limitation of EEV

Unit stop Adjustable upper limitation

Thermostat ON Thermostat OFF

Adjustable lower limitation

Cool/dry 5(E) 450(E) standard open angle+tolerance

5(E) 80(E)

heat 60(E) 450(E) standard open angle+tolerance

60(E) 80(E)

3.3.4 Standard open angle control In Cool/Dry mode, standard open angle: outdoor ambient temp.≥20, 250 pulse(E);

Outdoor ambient temp.<20, 210 pulse(E); In Heat mode, standard open angle: outdoor ambient temp.≥10, pulse (E);

outdoor ambient temp.<10, 210 pulse (E). 3.3.5 When discharging temp. Td is too high, modify the EEV angle. In order to cooperate the compressor discharging temp. over high protection, the system will enlarge the EEV open angle. Within 5 minutes after compressor starts up, it will not modify. The detecting period is 30 seconds.

Cooling mode Indoor modification angle

100<discharging temp. +50degree/30seconds, it will stop until up to the max. permitted

opening angle 90< discharging temp.<=100 Keep the angle

-48-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 49: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

<=90 -5degree/30seconds, and reduce to 0 degree gradually

Heating mode Indoor modification angle

100< discharging temp. +50degree/30seconds, it will stop until up to the max. permitted

opening angle 90< discharging temp.<=100 Keep the angle

<=90 -5degree/30seconds, and reduce to 0 degree gradually 3.4 4-way valve control in heating Protection when 4-way valve can not reverse in heating: 10 minutes later after compressor startup, if indoor coil average temp. is below 15degree and keeps for 1 minute, the unit will stop and occur the 4-way valve protection. compressor ON OFF 4-way valve ON OFF 15s(E) 2minutes and 55s 3.5 Electric heater control If compressor has not run for a long time, the refrigerant will deposit on the bottom of compressor and mix with the refrigeranr oil. When re-startup, because low pressure reduces, refrigerant will be segregated from the refrigerant oil and cause soam in the oil, which will make compressor exhaust a lot of oil. Therefore please stop heating the compressor bottom to ensure the low pressure in startup period should not go down greatly. Ambient temp. TA≤27degree, when compressor stops, the electric heater will be electrified. When TA≥32degree, or compressor running, the electric heater will be off.

Heater ON OFF Ambient temp. TA() 27 32 3.6 Control of liquid spray valve SV2: According to the compressor discharging temp., open or close the SV2. ①Control condition: A. In every mode (including defrosting and oil return operation), the control can work. B. In 3 minutes after compressor startup, ignore the abnormal compressor suction and discharging value. ②3 minutes later after compressor startup, according to the discharging temp., the following procedure

will be taken: Td≤90, SV2 close; Td>110, SV2 open. ③In 150 seconds when compressor stops, in order to keep the system in balanc, please open the liquid

spray valve SV2. 150 seconds later after compressor stops, SV2 close. 3.7 Control of defrosting in heating In heating mode, defrosting temp. sensor will check the frosting condition of outdoor heat exchanger and make defrosting control. 3.7.1 Enter condition: ①In heating mode, if the compressor has run for 10 minutes continously and run for 45 minutes in all, the

system will measure the defrosting temperature sensor Te and outdoor ambient temp. sensor TA, if the below condition can be met for continous 5 minutes, the unit will enter defrosting operation:

-49-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 50: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Te≤C×TA-α Herein: C:TA<0,C=0.8 TA≥0,C=0.6

According to SW2, the setting is as follow: in the place easy to frost, it is H; when out of factory, it is M. Jumper

selection M(out of factory) H

α() 8(E) 6(E) ②Defrosting entering condition: -15≤C×TA-α≤-2 ③Stop and Pause condition of compressor running accumulative time in heating mode: Checking Stop: running operation changes from heating to cooling. Checking Pause: thermostat OFF, or the unit stops. 3.7.2 Cancel condition: It will take the max. 10 minutes from beginning defrosting to quit it. Te sensor will measure the condition of outdoor heat exchanger, if the temp. is over 7 for 60 seconds in all or is up to 12 for 30 seconds in all, the defrosting will be over. 3.7.3 Compulsory defrosting control Enter condition: in heating mode, after receiving the compulsory defrosting signal from indoor unit, the unit will perform the compulsory defrosting operation. Cancel condition: Te≥12 and keep for 1 minute or the defrosting time is over 10 minutes. The manual defrosting signal of indoor unit will remain until the outdoor enters defrosting mode. Note: When outdoor compressor not running, the unti still can enter manual defrosting, but it will comply with the 3-minute protection of compressor.

-50-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 51: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

3.7.4 Defrosting operation flow chart

beginning end

fixed frequency indicated FQY 60s defrosting FQY 80 Hz(E) 60s soft startup

compressor

0HZ 0HZ

5s

outdoor motor ON send defrosting signal to indoor Auto

OFF

4-way valve ON

OFF 15s

ON

Spray valve SV2 OFF

450-pulse 450-pulse

350-pulse(E)

all EEVs auto open angle auto open angle

all indoor motors ON

OFF anti-cold air function

-51-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 52: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

3.8 Frequency control when Td is too high Purpose: make compressor frequency control if the discharging temp. is too high, to lower the discharging temp. efficiently and ensure the system can run normally. 3.9 Frequency control when there is CT over current protection

1.0 I 0.95I 0.93I 0.90I 0.88I 0.85I

Stop immediately, if abnormal stop 3 times in 1 hour, theunit will stop and alarm.

Reduce FQY rapidly 2HZ/S Reduce FQY rapidly 1HZ/S Reduce FQY slowly 1HZ/10S Remain FQY Increase FQY slowly 1HZ/10S

Dis

char

ging

tem

p. T

D

If keeping for 10s, the unit stops, 3 minutes later, the unit canre-startup. If in 60 minutesthe unit occurs alarm for 3 times, thefailure can be eliminated. Reduce FQY rapidly 2HZ/S Reduce FQY rapidly 1HZ/S Reduce FQY slowly 1HZ/10S Remain FQY Increase FQY slowly 1HZ/10S

120 115 110 105 100 95

-52-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 53: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

3.10 High pressure protection When the input signal of pressure switch is high level:1, that shows there is no protection. When the input signal of pressure switch is low level: 0 for 1 minute, that shows high pressure protection works. At this time, compressor stops, outdoor will send the alarm signal. The alarm can be resumable. If in 60 minutes, the failure occurs 3 times, the failure can be confirmed and send failure code to indoor. Meanwhile, by controling the max. condensate temp. Tc (cooling) or TmAVE (heating), please confirm as follow: In nominal cooling/dry/heating mode, high pressure can be controlled by limiting the max. frequency. 3.11 Low pressure protection (1) When compressor is running, if output signal of low pressure switch is low level: 0 for 1 minute

continously, compressor will stop,outdoor alarms. The alarm can be resumable. If in 60 minutes, the failure occurs 3 times, the failure can be confirmed and send failure code to indoor.

(2) When compressor no running, if output signal of low pressure switch is low level: 0 for 30 seconds continously, alarm will occur.

·When unit stops, the reason that system still checks the low pressure : in a long time stop, make protection for the compressor on the condition of great refrigerant leakage.

·The reason that low pressure switch action time is 30 seconds: when compressor stops, low pressure does not change, so it will be shorter than the set time in operation. (3) When compressor starts up, in 8 minutes, low pressure switch signal will be shielded. (4) In defrosting, low pressure switch will be shielded. (5) In oil return procedure, low pressure switch will be shielded. (6) In the refrigerant discharging procedure after the oil return in cooling is over, low pressure switch will be shielded. In addition, the system will control low pressure through the evaporator temp. TE to realize the low pressure protection function.

Con

dens

ing

tem

p.

Keep for 5 seconds, stop to alarm, after 3-minute standby, theunit can restartup. In 3 minutes it occurs 3 times continously,unit will stop to alarm and the failure can be resumed after beingelectrified again. Reduce FQY rapidly 2HZ/S Reduce FQY rapidly 1HZ/S Reduce FQY slowly 1HZ/10S Remain FQY Increase FQY slowly 1HZ/10S

70 68 66 64 62 60

-53-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 54: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

In cooling, confirm through Tc2AVE:

In heating, confirm through defrosting temp. Te: If the failure is not confirmed as the permanent protection, outdoor will not send failure code to indoor, and indoor will not alarm.

TinA

VE

-25 -30 -35 -40 -45

Normal operation Min. running FQY 20HZ SV2 OFF & 20HZ SV2 ON & 20HZ Keep for 5 seconds, unit stops and alarmoccurs. 3 minutes later, restart up. If itoccurs 3 times in 1 hour, it will alwaysalarm and stop, electrify again and failurewill be cleared.

Te -30 -35 -40 -45 -50

Normal operation Min. running FQY 20HZ SV2 OFF & 20HZ SV2 ON & 20HZ Keep for 5 seconds, unit stops andalarm occurs. 3 minutes later, restartup. If it occurs 3 times in 1 hour, it willalways alarm and stop, electrify againand failure will be cleared.

-54-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 55: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Indoor electric control functions: Note: The following functions are applicable for the unit in normal state. 1. Parameter input: 1.1 Analog data input: 1.1.1 Indoor temperature sensor input (TA): 1-way, 23KΩ at 25 1.1.2 Indoor coil outlet temp/inlet temp (TC1: gas pipe, TC2: liquid pipe): 2-way, 10KΩ at 25

1.1.3 Indoor middle coil temp. (Tm): 1-way, 10KΩ at 25.

1.2 Functional switch setting: 1.2.1 Central control address setting and indoor communication address setting: 8-way (SW01), the detailed definition is as follow: 0-OFF, 1-ON AS072~AS122XVERA: SW01

[1] [2] [3] [4] [5] [6] [7] [8] description

-- 0 0 0 0 0 0 0 Central control address=1 -- 0 0 0 0 0 0 1 Central control address =2

---- ---- -- 1 1 1 1 1 1 0 Central control address =127 -- 1 1 1 1 1 1 1 Central control address =128 0 -- -- -- -- -- -- -- Indoor communication address set by

remote controller 1 -- -- -- -- -- -- -- Indoor communication address set by dip

switch SW02

[1] [2] [3] [4] [5] [6] [7] [8] description

0 0 -- -- -- -- -- -- AS072 capacity selection 0 1 -- -- -- -- -- -- AS092 capacity selection 1 0 -- -- -- -- -- -- AS122 capacity selection -- -- 0 0 -- -- -- -- LCD display board (LCD remote

receiver) -- -- 1 1 -- -- -- -- LED display board (LED remote

receiver) -- -- -- -- 0 -- -- -- Room card function valid -- -- -- -- 1 -- -- -- Room card function unavailable -- -- -- -- -- 0 0 0 Indoor communication address 1 -- -- -- -- -- 0 0 1 Indoor communication address 2 -- -- -- -- -- 0 1 0 Indoor communication address 3 -- -- -- -- -- 0 1 1 Indoor communication address 4 -- -- -- -- -- 1 0 0 Indoor communication address 5 -- -- -- -- -- 1 0 1 Indoor communication address 6 -- -- -- -- -- 1 1 0 Indoor communication address 7 -- -- -- -- -- 1 1 1 Indoor communication address 8

-55-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 56: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Note: The above dip switches are correlative to the system security, so please confirm the conformity between the unit and the dip switch. The incorrect dip switch setting will result in the system wrong operation or the wrong failure diagnosis. 2. Cooling operation 2.1 The set temperature in cooling: TS=the set temp. on remote controller 2.2 After cooling startup, indoor unit will send the frequency code to outdoor according to the temp. difference between the set temp. and the ambient temp. 3. Heating operation 3.1 In heating operation, the set temp. TS=the set temp. on remote controller 3.2 After heating startup, indoor unit will send the frequency code to outdoor according to the temp. difference between the set temp. and the ambient temp. 4. Dry operation Room temp.-(set temp.+ tolerance) >2, indoor operation is identical to the cooling operation, and sends the cooling operation signal to outdoor. Room temp.-(set temp.+ tolerance) ≤2, indoor unit sends the dry operation signal to outdoor. Room temp. <16, indoor unit stops running and sends stop-unit signal to outdoor. 5. Fan operation Indoor fan motor will run as the fan speed set on the remote controller and indoor unit will send the stop-unit signal to outdoor. 6. Auto operation If the unit enters Auto mode for the first time, the system will adjust the operation mode according to the room temp. and the set temp. When room temp.≥set temp., entering cooling mode; When room temp.<set temp., entering heating mode. Mode conversion will be confirmed after compressor has stopped for 15 minutes. 7. Abnormal operation When outdoor modes from the request of indoor unit conflict, the one entering firstly will take priority. After indoor receives the ON command from remote controller, it will firstly confirm the outdoor current operation mode. If they are the same mode, indoor unit will run as the request of remote controller. If they are different modes, the system will forbid to operate, and indoor will keep the OFF mode. After setting on remote controller, if the buzzer sounds two times, that shows abnormal operation. Indoor will run until the outdoor mode and the requested mode of remote controller are the same. 8. Compensation control for discontinuous operation After the unit starts up in cooling/heating mode, in 3 minutes, the compressor run/stop will not be controlled by the room temp., but after changing the set temp., if compressor stop condition can be met, the system will stop compressor immediately. 9. Anti-cold air control In heating mode, after compressor startup, the system will control indoor fan motor according to indoor coil temperature. At the beginning of startup, the indoor fan motor can run only when indoor mid-coil temp. is over 28(±2). When indoor mid-coil temp. goes down to 18(±2), indoor fan motor will stop running.

-56-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 57: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

In defrosting period, indoor fan motor will stop running; In heating mode, if unit shutoff, indoor fan motor will stop after running for 30 seconds at super low speed. Note: The above temp. point has taken fuzzy control, and has tolerance ±2 according to the different state. 10. Fan motor control in defrosting 10.1 On receiving outdoor defrosting signal, indoor unit will stop after blowing remaining heat at slow speed for 20 seconds. 10.2 In defrosting period, indoor fan motor stops running. 10.3 Defrosting is over, and indoor motor will run as anti-cold air state. 11. Blowing remaining heat operation When the unit shuts off in heating mode or the thermostat is OFF, indoor motor will stop running after running at super low speed for 30 seconds. 12. Anti-freezed protection (invalid in heating mode) When compressor has run for over 5 minutes, to prevent indoor evaporator freezing (in cooling/dry mode), if indoor mid-coil temp. is below 0 degree, compressor will stop. When indoor mid-coil temp. is over about 10 degree, the unit can run. After compressor has stopped for 3 minutes, the unit can re-start up. Note: The above temp. point has taken fuzzy control, and has tolerance ±1 according to the different state. 13. Overload protection in heating mode It is valid only in heating mode, if indoor mid-coil temp. is over about 65 degree continuously for 10 seconds, indoor will stop; while when indoor mid-coil temp. is below 52 degree, indoor will resume. Note: The above temp. point has taken fuzzy control, and has tolerance ±1 according to the different state. 14. Timer operation TIMER ON/TIMER OFF/TIMER ON/OFF. Timer will count according to the time difference between the TIMER clock and the present clock. In TIMER state, TIMER indicator will be ON. 15. SLEEP function In cooling/dry mode, after running for 1 hour, the set temp. will increase 1, another 1 hour later, the set temp. will increase 1 again, then 6 hours later, it will stop. In heating mode, after running for 1 hour, the set temp. will reduce 2, another 1 hour later, the set temp. will reduce 2 again, then 3 hours later, the set temp. will increase 1, and another 3 hours, it will stop. 16. Auto-restart function In 5 seconds, press SLEEP button 10 times continuously, the buzzer will sound 4 times and enter auto-restart function. In 5 seconds, press SLEEP 10 times continuously, the buzzer will sound twice and quit auto-restart function. If no SLEEP button, press SWING as the same method. 17. Setting indoor unit number In OFF state, press emergency switch until 15 seconds later, the buzzer sounds 4 times, indoor will enter the indoor unit number setting state, the set method is as follow:

-57-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 58: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Press ON/OFF button (from OFF mode to ON mode), the times of SLEEP button to be pressed is the set unit number, then press ON/OFF button to quit unit number setting state, at this time, indoor unit is at OFF state, the display panel will display this unit number. For example, press SLEEP button once, it is No. 1 unit; press twice, it is No. 2 unit, and so on. In OFF state, press emergency switch until 15 seconds later, the buzzer sounds 5 times, the display panel will display this unit number and you can check if there are repeated numbers. 18. Setting method of temperature compensation Set the temperature compensation in heating mode with the remote controller. No compensation in cooling mode. In 24 heating mode, press SLEEP button 8 times continuously, indoor buzzer sounds 5 times, that shows temp. compensation works. Switch on the unit in heating mode by the remote controller, press TEMP button to set the set temp., so temperature compensation=the current set temp. - 24. For example, if the set temp. is 24, the temp. compensation is 0; if the set temp. is 25, the temp. compensation is 1. Please do not set the minus temp. compensation, that is to say the min. temp. compensation is 0. If setting is finished, press ON/OFF button, then indoor buzzer will sound 4 times, that shows the unit quits the temp. compensation.

-58-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 59: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

10. Diagnostic information and troubleshooting

!"

# $ !

# $ !

# $ !

# % $ !

#&&'() * #

+ ,

- ###

. / -

0 - 1

# ! #

#2 #

) 0 !

-59-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 60: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

!"##$#"! $#"!%#&"$$&'"!(!")$'"!#*"!&%!&%

#$#"! $#"!%#&"$$&'"!(!")$'"!#*"!&%!&%

#$#"! $#"!%#&"$$&'"!(!")$'"!#*"!&%!&%

#$#"! $#"!%#&"$$&'"!(!")$'"!#*"!&%!&%

$+",!&!!$,!&!!$" *##-'"!(!")$" *&!!$#$#"!'"!- $&%"$.%* %$""!"!"""! $-""!#'"! /

($"!- &"--$%&%"$(.$%$""!$"""!$%#

0!"$1&"$$&%"$'"!*.%!#(%#&"$$&'"!.!"$1!###%$1" %$""!$%#'"! '"! +".!#++

2

#-*%1*+!##!+!"&%"$

%1* +!##! #.%&* %# %#&"$$&' "! *%1*+!##!#.%&*."!)'"! &""*%1*$ """! $-""!.*$&""%$1'"! %$""! $-""!#.*$*%$1'"!! !%1!$",!($$&

3

#-".+!##!+!"&%"$

". +!##! #.%&* %# %#&"$$&' "! ".+!##!#.%&*."!)'"! "" ".$ """! $-""!#.*$*%$1'"! %$""! $-""!.*$&""%$1'"!! !%1!$#*"!1

4

5+!"&%"$5 ",! &!!$' "! #*"! &%!&%' "! 5-+!!""*%1*'"!5%$+,"1""".'"! /

5 """!$%

,!*"+!"&%"$" &"-+!##"!

!%"#&)" ! !%1!$" *##-'"!*-(%$ -+!! "" *%1*' "! 56# (("&)

$-""! $%#("&)'"!*!-%$%#%#&"$$& !"-*

. ,,#.%&*%$1"$

"%" .,, %#%#&"$$&'"! """!

#$#"! $#"!%#&"$$&'"!(!")$'"!#*"!&%!&%

#$#"! $#"!%#&"$$&'"!(!")$'"!#*"!&%!&%

($"!-&"--$%&%"$(.$ -%$ $

"--$%&%"$&(#(!")$'"!$"(.&"$$&'"! -%$'"!

"-+!##"!"&)!""! &"-+!##"!"!"-+!##"!*,,%(!%"$ &"-+!##"!"-+!##"!"#+"#%%"$ &"-+!##"!#! &"-+!##"!"! +"#%%"$ &*&)%$1&%!&%

"-+!##"!(!")$ &"-+!##"!"! )" *+#%&,,&",!'"&$ %$*#$!"*&"--$%&%"$!-%$/-("-$#*%#/-("-$#*%#/

2

7

2783

4

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

-60-

Page 61: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Troubleshooting:

replace the fuse and check again

replace power wiring and check again

display panel circuit is damaged, replace it

PCB is faulty, replace

check if fuse is burnt

yesyesyes

check if power wiring is in open circuit

nononocheck if display panel is 12V power supply

PCB is faulty, replace it

check the terminal block and the power supply

if the power terminal block is 220V input

yesyes

if the red diode and green diode on indoor PCB flash in turn

replace display panel and check again

yes

nono

check if display panel and the unit matched well

Trouble 1: No display on the operation panel

no

start

PCB is faulty and repalce it, check again

replace sensor and check again

replace sensor and check again

check if sensor resistor value is correct

nono

yesyes

yes

check if sensor is in open circuit or PCB port is not in good condition

re-fix the sensor and check again

as per the wiring diagram,check the connection between sensor and PCB is correct

Trouble 2: Sensor failure

no

start

-61-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 62: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

adjust the distance and check again

replace the communication connection wire, check again

PCB is faulty, replace and check again

if the power cable and the communication wire are too close, resulting in the wrong commission data

check if the communication port connecting to the indoor/outdoor PCB is in open circuit

re-wiring, and check again

nono

yesyes

yes

as per the wiring diagram, check if communication wiring is correct

start

Trouble 3: Communication failure between indoor and outdoor

no

replace fan motor feedback port, cut off power supply and be electrified again

replace fan motor input port, cut off power supply and be electrified again

PCB is faulty and replace it

check the fan motor feedback wire is fixed badly (CN23 on PCB)

yesyes

nonocheck if the fan

motor input connection is fixed badly(CN3 on PCB)

Trouble 6: Indoor fan motor failure, AC fan motor has not 50Hz zero-crossing detection

Trouble 5: Indoor repeated unit number

Trouble 4: Indoor PCB EEPROM data is wrong1.If the failure occurs when being electrified for the first time, that shows EEPROM (8-bit pin) not fixed firmly or damaged.2.If the failure occurs when running, that shows EEPROM is faulty and need to be replaced.

1.Firstly query the unit number: switch off the unit, press SLEEP for about 15 seconds until the buzzer sounds 5 times, on the display panel there will be digit, which is indoor number. By this method,you can check if there is repeated unit number, if yes, please re-set the number as per the unit number setting procedure.2.Re-set the unit number directly, the unit with outdoor pipe A is No. 1; the unit with outdoor pipe B is No. 2; the unit with pipe C is No.3

start

-62-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 63: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Trouble 9: AC current over current protection or current transducer damaged, or compressor blocked rotor, compressor great vibration, compressor abnormal startup, state detecting curcuit abnormal or compressor damaged.

yes

PCB is faulty and repalce it, check again

replace sensor and check again

replace sensor and check again

check if the sensor resistor value is correct

check if the sensor is in open circuit or the connection port to PCB is in good condition

re-fix the sensor and check again

as per the wiring diagram, check if connection port between sensor and PCB is correct

yes

nono

yes

no

Trouble 8: Outdoor unit alarms sensor failure

Check the failure code on outdoor indicator board (5-lamp)Trouble 7: Outdoor unit failure

start

The former twice failure can be resumed automatically, if outdoor board occurs this failure always, and can not be resumed for a long time, that shows: 1. Power module (SPDU) damaged, please replace the power module, then re-wiring as per the wiring diagram (70%possibility)2. Short circuit in power board results in the power module damaged (15% possibility)3. Damaged compressor results in this failure (10% possibility)4. Main control board is faulty, replace it (5% possibility)

replace outdoor motor and check again

check if the outdoor motor has power input

replace pressure switch connector, shut off and be electrified again, re-check

replace pressure switch connector, shut off and be electrified again, re-check

replace main control board and check again

if outdoor fan motor cannot startup normally in cooling mode

check if the 2 straight lugs on the pressure switch are in good condition

yesyesyes

no

nonocheck if the connector between pressure switch and PCB is fixed badly or damaged

Trouble 10: High pressure failureReasons: 1. Over high system pressure results that the unit stop, and the compressor protection will work. The failure can be resumed.2. Pressure switch wire is not fixed well or in open circuit.

no

start

-63-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 64: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

replace indoor motor and check again

check if the indoor motor has power input

replace pressure switch connector, shut off and be electrified again, re-check

replace pressure switch connector, shut off and be electrified again, re-check

yesyesyes

replace main control board and check again

if indoor fan motor cannot startup normally in heating mode(except for defrost)

check if the 2 straight lugs on the pressure switch work badly

no

nonocheck if the connector between pressure switch and PCB is fixed badly or damaged (CN20 on PCB)

no

Failure 11: Low pressure switch failureReason: 1. Too low system pressure causes that the unit stops and the compressor protection works, the failure can be resumed.2. Pressure switch wire is not fixed well or in open circuit.

start

-64-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 65: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

11. Electric data 11.1 Wiring diagram

Outdoor unit wiring diagram

PIPINGTEMPER-ATURE SENSOR

AMBIENT TEMPERATURE SENSOR

SWING MOTOR CN18 CN19

SW03

CN16

SW02

SW01

CN8

SWING MOTOR

SWING MOTOR

CN22CN21

SWING MOTOR

CN23

AC FAN MOTOR

M¡«

B: BLACK BR: BROWNR: RED W : WHITEY/G : YELLOW/GREENBL:BLUE Y:YELLOW

CN3

CN2FUSE1

IONGENERATOR

CN25 LEDCN12

CN1

CN11

FRESH CONTROLLER

CN10

TO OUTDOOR UNIT

BW R BR

Y/GULTRAVIOLETRADIATION

T3.15A250VAC

CN4

CN17 CN20

LED2 LED1CN14

CN13

NOTE:WHEN THE UNIT HAS NOT THE FUNCTION OF HEALTH WITHOUTTHE PARTS IN THE DOTTED LINE.

BL B W

W W W W

W

W

W

R

W

R

W

220_L

220_N

CN5

CN9

1(L)2(N)

CN24R

CN26

3 4

Y

M M M

M

PIPINGTEMPER-ATURE SENSOR

Wall mounted unit wiring diagram

-65-

CN25

BTU22000

BTU18000

ON

ON

SW5-6SW5-5

SW5-6SW5-5

reactorcapacitor

capacitor

BL : BLUE

BL OR

B W

Y/G

Y/GBW

SPDU

- +

P(+)

N(-)

RO

ACL

RI

ACN

WVU

RL1

POWER

BOARD CIRCUIT

CN7

CN8

220VAC-L

CN3CN4

BOARD

CIRCUIT

CONTROL

CN5

LN

CN1

TO SPDU

4WV

DEBUG_LED

LED

CN7CN2CN1

CN13CN14

CN5CN3

H

CN23

CN20HP LP

CN19

Y/G : YELLOW/GREEN W : WHITE OR : ORANGE

R : RED B : BLACK

stop/downstart/up

SW1 SW2

SW4SW3

1 2 3 4

ON

NCN8

L

BUS

PTC

87654321

ON

CN6SV2

PMV_A PMV_DPMV_CPMV_BCN18

CN22

MLN CN4

MM

TOCI PIPING TEMPERATURE SENSOR

TOCI

0010576926

TA AMBIENT TEMPERATURE SENSOR

TE DEFROSTING TEMPERATURE SENSOR

TC CONDENSING TEMPERATURE SENSORTS: COMPRESSOR INHALE SENSOR

FUSE1

CN26

To Power Supply

SW5

TD: COMPRESSOR VENT SENSOR

SW5

250VAC T3.15A

CN21

To Indoor Units

RRM

LED2

LED1

LED4

LED3

LED5

FUSET25A 250VAC

C1C2

220VAC-N

CN2

W B

V

R

COMPRESSOR

U W

AC FAN MOTOR4-WAY VALVE

Y/G

CN9

CN10

CRANKCASE HEATER

CN11

CN12

LED1

LED2

CN15CN16

TC

TA

TS

TE

TD

CN17

M

L N

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 66: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

11.2 Circuit diagram Outdoor circuit diagram:

-66-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 67: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Indoor circuit diagram:

-67-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 68: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

11.3 Sensor part number and their resistor value

model name code sub-part code characteristic

suction temp. sensor 0010451513 001A3900059

1.R25=10KΩ±3%B25/50=3700K±3%2.R25=23KΩ±2.5%B25/50=4200K±3%

coil temp. sensor 001A3900059

1.R25=10KΩ±3%B25/50=3700K±3%2.R25=23KΩ±2.5%B25/50=4200K±4%

liquid pipe temp. sensor 001A3800103 001A3900004 R25=10KΩ±3%B25/50=3700K±3%

discharging temp. sensor R80=50KΩ±3%B25/80=4450K±3%

mid-condensor temperature sensor R25=10KΩ±3%B25/50=3700K±3%

outdoor ambient temp. sensor R25=10KΩ±3%B25/50=3700K±3%

AS072XVERAAS092XVERAAS122XVERA

AU182XFERA

-68-

AU222XFERA

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 69: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

T() Rnom(KΩ) T() Rnom(KΩ) T() Rnom(KΩ) T() Rnom(KΩ)-30 11600 24 536.6 -20 90.79 34 6.95-29 10860 25 511.1 -19 85.72 35 6.68-28 10170 26 486.9 -18 80.96 36 5.43-27 9529 27 464 -17 76.51 37 5.6-26 8932 28 442.3 -16 72.33 38 5.59-25 8375 29 421.7 -15 68.41 39 5.73-24 7856 30 402.1 -14 64.73 40 5.52-23 7372 31 383.6 -13 61.27 41 5.32-22 6920 32 366 -12 58.02 42 5.12-21 6498 33 349.3 -11 54.97 43 4.93-20 6104 34 333.5 -10 52.1 44 4.9-19 5736 35 318.4 -9 49.4 45 4.58-18 5392 36 304.1 -8 46.86 46 4.42-17 5071 37 290.5 -7 44.46 47 4.26-16 4770 38 277.6 -6 42.21 48 4.11-15 4488 39 265.3 -5 40.08 49 3.97-14 4225 40 253.6 -4 38.08 50 3.83-13 3978 41 242.5 -3 36.19 51 3.7-12 3747 42 232 -2 34.41 52 3.57-11 3531 43 221.9 -1 32.73 53 3.45-10 3328 44 212.3 0 31.14 54 3.33-9 3138 45 203.2 1 29.64 55 3.22-8 2960 46 194.5 2 28.22 56 3.11-7 2793 47 186.3 3 26.4 57 3.11-6 2636 48 178.4 4 25.61 58 2.9-5 2489 49 170.9 5 24.41 59 2.81-4 2351 50 163.7 6 23.27 60 2.72-3 2221 51 155.9 7 22.2 61 2.63-2 2099 52 150.4 8 21.18 62 2.54-1 1984 53 144.2 9 20.21 63 2.490 1877 54 138.3 10 19.3 64 2.381 1775 55 132.7 11 18.43 65 2.32 1680 56 127.3 12 17.61 66 2.233 1590 57 122.1 13 16.83 67 2.164 1506 58 117.2 14 16.09 68 2.095 1426 59 112.5 15 15.38 69 2.036 1351 60 108 16 14.71 70 1.967 1280 61 103.8 17 14.08 71 1.98 1214 62 99.68 18 13.48 72 1.859 1151 19 12.9 73 1.7910 1092 20 12.36 74 1.7311 1036 21 11.84 75 1.6812 983.2 22 11.34 76 1.6313 933.4 23 10.87 77 1.5814 886.4 24 10.43 78 1.5415 841.9 25 10 79 1.4916 800 26 9.59 80 1.4517 760.8 27 9.2118 722.8 28 8.8419 687.3 29 8.4820 653.8 30 8.1521 622 31 7.8322 592 32 7.5223 553.6 33 7.23

R80=50KΩ±3%B25/80=4450K±3%

R25=10KΩ±3%B25/50=3700K±3%

R80=50KΩ±3%B25/80=4450K±3%

R25=10KΩ±3%B25/50=3700K±3%

-69-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 70: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

T() Rnom(KΩ) T() Rnom(KΩ)

-20 281.34 22 26.54

-19 263.56 23 25.3

-18 247.04 24 24.12

-17 231.66 25 23

-16 217.35 26 21.94

-15 204.02 27 20.94

-14 191.61 28 19.99

-13 180.04 29 19.09

-12 169.24 30 18.23

-11 159.17 31 17.42

-10 149.77 32 16.65

-9 140.99 33 15.92

-8 132.78 34 15.22

-7 125.11 35 14.56

-6 117.93 36 13.93

-5 111.22 37 13.34

-4 104.93 38 12.77

-3 99.04 39 12.23

-2 93.52 40 11.71

-1 88.35 41 11.22

0 83.5 42 10.76

1 78.94 43 10.31

2 74.67 44 9.89

3 70.65 45 9.49

4 66.88 46 9.1

5 63.33 47 8.74

6 60 48 8.39

7 56.86 49 8.05

8 53.91 50 7.73

9 51.13 51 7.43

10 48.51 52 7.14

11 46.04 53 6.86

12 43.72 54 6.6

13 41.52 55 6.34

14 39.45 56 6.1

15 37.5 57 5.87

16 35.66 58 5.65

17 33.92 59 5.44

18 32.27 60 5.24

19 30.72

20 29.25

21 27.86

R25=23KΩ±2.5%B25/50=4200K±3%

R25=23KΩ±2.5%B25/50=4200K±3%

-70-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 71: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

12. Performance curves The data in the curves are measured with three indoor unit AS07+AS09+AS12 and AU182.

Heating capacity curves

4000

5000

6000

7000

8000

9000

10000

16/10 18/12 20/14.5 21/15 22/16 24/17 26/18

indoor WB/DB

Hea

ting

capa

city

(W)

-6/-7-4/-5-1/-21/06/57/612/1016/15

Power input curves in heating mode

1700

1900

2100

2300

2500

2700

2900

16/10 18/12 20/14.5 21/15 22/16 24/17 26/18indoor WB/DB

Pow

er in

put (

W)

-6/-7-4/-5-1/-21/06/57/612/1016/15

-71-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 72: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Cooling capacity curves

2000

3000

4000

5000

6000

7000

8000

18/12 20/14 22/16 25/18 27/19 30/22 32/24

indoor DB/WB

Coo

ling

capa

city

(W)

-52025323540

Power input curves in cooling mode

0

500

1000

1500

2000

2500

3000

18/12 20/14 22/16 25/18 27/19 30/22 32/24

indoor DB/WB

Pow

er in

put (

W) -5

2025323540

-72-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 73: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

-73-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

EE

R(W

/W)

Uni

tA

Uni

tB

Uni

tC

Uni

tD

min

.da

tara

ted

data

max

.da

tam

in.

data

rate

dda

tam

ax.

Dat

am

in.

data

rate

dda

tam

ax.

Dat

ara

ted

capa

city

07+1

2co

olin

g an

d he

atin

g2.

03.

2—

—1.

005.

205.

800.

471.

752.

302.

157.

8010

.20

2.97

C09

+09

cool

ing

and

heat

ing

2.5

2.5

——

1.00

5.00

5.40

0.47

1.75

2.30

2.15

7.80

10.2

02.

86C

09+1

2co

olin

g an

d he

atin

g2.

32.

9—

—1.

005.

205.

800.

471.

752.

302.

157.

8010

.20

2.97

C12

+12

cool

ing

and

heat

ing

2.6

2.6

——

1.00

5.20

5.80

0.47

1.75

2.30

2.15

7.80

10.2

02.

97C

07+0

7+07

cool

ing

and

heat

ing

1.73

1.73

1.73

—1.

505.

205.

800.

501.

702.

302.

297.

6210

.20

3.06

B07

+07+

09m

ainl

y co

olin

g1.

601.

602.

00—

1.50

5.20

5.80

0.50

1.70

2.30

2.29

7.62

10.2

03.

06B

07+0

7+12

mai

nly

cool

ing

1.39

1.39

2.42

—1.

505.

205.

800.

501.

702.

302.

297.

6210

.20

3.06

B07

+09+

09m

ainl

y co

olin

g1.

481.

861.

86—

1.50

5.20

5.80

0.50

1.70

2.30

2.29

7.62

10.2

03.

06B

07+0

9+12

mai

nly

cool

ing

1.30

1.63

2.27

—1.

505.

205.

800.

501.

652.

302.

297.

6210

.20

3.15

B09

+09+

09m

ainl

y co

olin

g1.

731.

731.

73—

1.50

5.20

5.80

0.50

1.65

2.30

2.29

7.62

10.2

03.

15B

09+0

9+12

mai

nly

cool

ing

1.56

1.56

2.18

—1.

505.

305.

800.

501.

652.

302.

297.

4010

.20

3.21

A07

+14

cool

ing

and

heat

ing

2.0

4.1

——

1.00

6.10

6.50

0.47

2.20

2.90

2.20

9.76

12.9

02.

77D

09+1

2co

olin

g an

d he

atin

g2.

53.

2—

—1.

005.

706.

200.

472.

002.

902.

208.

8712

.90

2.85

C09

+14

cool

ing

and

heat

ing

2.4

4.0

——

1.00

6.40

6.50

0.47

2.20

2.90

2.20

9.76

12.9

02.

91C

12+1

2co

olin

g an

d he

atin

g3.

23.

2—

—1.

006.

406.

500.

472.

202.

902.

209.

7612

.90

2.91

C07

+07+

09co

olin

g an

d he

atin

g2.

02.

02.

4—

1.50

6.40

6.50

0.50

2.15

2.90

2.30

9.54

12.9

02.

98C

07+0

7+12

mai

nly

cool

ing

1.78

1.78

2.84

—1.

506.

406.

500.

502.

152.

902.

309.

5412

.90

2.98

C07

+09+

09m

ainl

y co

olin

g1.

702.

352.

35—

1.50

6.40

6.50

0.50

2.15

2.90

2.30

9.54

12.9

02.

98C

07+0

9+12

mai

nly

cool

ing

1.66

2.07

2.66

—1.

506.

406.

500.

502.

152.

902.

309.

5412

.90

2.98

C09

+09+

09m

ainl

y co

olin

g2.

132.

132.

13—

1.50

6.40

6.50

0.50

2.15

2.90

2.30

9.54

12.9

02.

98C

09+0

9+12

mai

nly

cool

ing

1.95

1.95

2.50

—1.

506.

406.

500.

502.

152.

902.

309.

5412

.90

2.98

C09

+12+

12m

ainl

y co

olin

g1.

802.

32.

3—

1.50

6.40

6.50

0.50

2.05

2.90

2.30

9.32

12.9

03.

12B

AU

222

XFE

RA

BI (

1x2)

TRI (

1x3)

EN

ER

GY

LAB

EL

AU

182

XFE

RA

BI (

1x2)

TRI (

1x3)

Rat

ed c

apac

ityO

utpu

t/kW

(Nom

. coo

ling)

tota

l coo

ling

capa

city

(kW

)to

tal p

ower

inpu

t(k

W)

tota

l cur

rent

(A)@

230V

Out

door

unit

Com

b.C

ompa

tible

indo

or u

nits

App

licat

ion

Page 74: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

-74-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

EE

R(W

/W)

Uni

tA

Uni

tB

Uni

tC

Uni

tD

min

.da

tara

ted

data

max

.da

tam

in.

data

rate

dda

tam

ax.

Dat

am

in.

data

rate

dda

tam

ax.

Dat

ara

ted

capa

city

07+1

2co

olin

g an

d he

atin

g2.

303.

80—

—1.

206.

106.

500.

551.

902.

302.

508.

4310

.20

3.21

C09

+09

cool

ing

and

heat

ing

2.90

2.90

——

1.20

5.80

6.50

0.55

1.90

2.30

2.50

8.43

10.2

03.

05C

09+1

2co

olin

g an

d he

atin

g2.

803.

80—

—1.

206.

606.

800.

551.

902.

302.

508.

4310

.20

3.47

B12

+12

cool

ing

and

heat

ing

3.30

3.30

——

1.20

6.60

7.00

0.55

1.90

2.30

2.50

8.43

10.2

03.

47B

07+0

7+07

cool

ing

and

heat

ing

2.20

2.20

2.20

—1.

506.

607.

000.

551.

852.

302.

508.

2110

.20

3.57

B07

+07+

09m

ainl

y co

olin

g2.

052.

052.

55—

1.50

6.65

7.00

0.55

1.85

2.30

2.50

8.21

10.2

03.

59B

07+0

7+12

mai

nly

cool

ing

1.85

1.85

2.95

—1.

506.

657.

000.

551.

852.

302.

508.

2110

.20

3.59

B07

+09+

09m

ainl

y co

olin

g1.

852.

402.

40—

1.50

6.65

7.00

0.55

1.85

2.30

2.50

8.21

10.2

03.

59B

07+0

9+12

mai

nly

cool

ing

1.70

2.15

2.80

—1.

506.

657.

000.

551.

852.

302.

508.

2110

.20

3.59

B09

+09+

09m

ainl

y co

olin

g2.

202.

202.

20—

1.50

6.60

7.00

0.55

1.85

2.30

2.50

8.21

10.2

03.

57B

09+0

9+12

mai

nly

cool

ing

2.05

2.05

2.55

—1.

506.

657.

000.

551.

802.

302.

507.

9910

.20

3.69

A07

+14

cool

ing

and

heat

ing

2.30

4.60

——

1.20

6.90

7.20

0.55

2.20

2.90

2.50

9.76

12.9

03.

14C

09+1

2co

olin

g an

d he

atin

g2.

903.

80—

—1.

206.

707.

200.

552.

202.

902.

509.

7612

.90

3.05

C09

+14

cool

ing

and

heat

ing

2.75

4.45

——

1.20

7.20

7.20

0.55

2.20

2.90

2.50

9.76

12.9

03.

27C

12+1

2co

olin

g an

d he

atin

g3.

603.

60—

—1.

207.

207.

200.

552.

202.

902.

509.

7612

.90

3.27

C07

+07+

09co

olin

g an

d he

atin

g2.

202.

202.

80—

1.50

7.20

7.40

0.55

2.15

2.90

2.50

9.54

12.9

03.

35C

07+0

7+12

mai

nly

cool

ing

2.00

2.00

3.20

—1.

507.

207.

400.

552.

152.

902.

509.

5412

.90

3.35

C07

+09+

09m

ainl

y co

olin

g2.

102.

552.

55—

1.50

7.20

7.40

0.55

2.10

2.90

2.50

9.32

12.9

03.

43B

07+0

9+12

mai

nly

cool

ing

1.85

2.30

3.05

—1.

507.

207.

400.

552.

102.

902.

509.

3212

.90

3.43

B09

+09+

09m

ainl

y co

olin

g2.

402.

402.

40—

1.50

7.20

7.40

0.55

2.10

2.90

2.50

9.32

12.9

03.

43B

09+0

9+12

mai

nly

cool

ing

2.18

2.18

2.84

—1.

507.

207.

400.

552.

052.

902.

509.

0912

.90

3.51

B09

+12+

12m

ainl

y co

olin

g2.

002.

602.

60—

1.50

7.20

7.40

0.55

2.05

2.90

2.50

9.09

12.9

03.

51B

AU

222

XFE

RA

BI (

1x2)

TRI (

1x3)

EN

ER

GY

LAB

EL

AU

182

XFE

RA

BI (

1x2)

TRI (

1x3)

Rat

ed c

apac

ityO

utpu

t/kW

(Nom

. hea

ting)

tota

l hea

ting

capa

city

(KW

)to

tal p

ower

inpu

t(W

)to

tal c

urre

nt(A

)@23

0VO

utdo

orun

itC

omb.

Com

patib

lein

door

uni

tsA

pplic

atio

n

Page 75: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

13. Noise level

1/3

oct

ave

band n

ois

e le

vel-A

U182X

FE

RA

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

25.0

31.5

40.0

50.0

63.0

80.0

100.

012

5.0

160.

020

0.0

250.

031

5.0

400.

050

0.0

630.

080

0.0

1000

.012

50.0

1600

.020

00.0

2500

.031

50.0

4000

.050

00.0

6300

.080

00.0 10

000.

0 1250

0.0 16

000.

0 2000

0.0

third

oct

ave

band

freq

uenc

y H

z

sound pressure level DB

cool

ing

high

cool

ing

med

cool

ing

low

fan

high

fan

med

fan

low

heat

ing

high

heat

ing

med

heat

ing

low

1/3

oct

ave

ba

nd

no

ise

leve

l-A

S0

72

XV

ER

A

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

25.0

31.5

40.0

50.0

63.0

80.0

100.

012

5.0

160.

020

0.0

250.

031

5.0

400.

050

0.0

630.

080

0.0 10

00.0

1250

.016

00.0

2000

.025

00.0

3150

.040

00.0

5000

.063

00.0

8000

.0 1000

0.0 12

500.

0 1600

0.0 20

000.

0

third

oct

ave

band

freq

uenc

y H

z

Sound pressure level DB

cool

ing

high

cool

ing

med

cool

ing

low

fan

high

fan

med

fan

low

heat

ing

high

heat

ing

med

heat

ing

low

-75-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 76: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

1/3

octa

ve b

and

nois

e le

vel-A

U18

2XF

ER

A

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

25.0

31.5

40.0

50.0

63.0

80.0

100.

012

5.0

160.

020

0.0

250.

031

5.0

400.

050

0.0

630.

080

0.0

1000

.012

50.0

1600

.020

00.0

2500

.031

50.0

4000

.050

00.0

6300

.080

00.0 10

000.

0 1250

0.0 16

000.

0 2000

0.0

third

oct

ave

band

freq

uenc

y H

z

sound pressure level DB

cool

ing

high

cool

ing

med

cool

ing

low

fan

high

fan

med

fan

low

heat

ing

high

heat

ing

med

heat

ing

low

1/3

octa

ve b

and

nois

e le

vel-A

S09

2XV

ER

A

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

25.0

31.5

40.0

50.0

63.0

80.0

100.

012

5.0

160.

020

0.0

250.

031

5.0

400.

050

0.0

630.

080

0.0

1000

.012

50.0

1600

.020

00.0

2500

.031

50.0

4000

.050

00.0

6300

.080

00.0 10

000.

0 1250

0.0 16

000.

0 2000

0.0

third

oct

ave

band

freq

uenc

y H

z

Sound pressure level DB

cool

ing

high

cool

ing

med

cool

ing

low

fan

high

fan

med

fan

low

heat

ing

high

heat

ing

med

heat

ing

low

-76-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 77: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

1/3

octa

ve b

and

nois

e le

vel-A

U18

2XF

ER

A

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

25.0

31.5

40.0

50.0

63.0

80.0

100.

012

5.0

160.

020

0.0

250.

031

5.0

400.

050

0.0

630.

080

0.0

1000

.012

50.0

1600

.020

00.0

2500

.031

50.0

4000

.050

00.0

6300

.080

00.0 10

000.

0 1250

0.0 16

000.

0 2000

0.0

third

oct

ave

band

freq

uenc

y H

z

sound pressure level DB

cool

ing

high

cool

ing

med

cool

ing

low

fan

high

fan

med

fan

low

heat

ing

high

heat

ing

med

heat

ing

low

1/3

octa

ve b

and

nois

e le

vel-A

S12

2XV

ER

A

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

25.0

31.5

40.0

50.0

63.0

80.0

100.

012

5.0

160.

020

0.0

250.

031

5.0

400.

050

0.0

630.

080

0.0

1000

.012

50.0

1600

.020

00.0

2500

.031

50.0

4000

.050

00.0

6300

.080

00.0 10

000.

0 1250

0.0 16

000.

0 2000

0.0

third

oct

ave

band

freq

uenc

y H

z

Sound pressure level DB

cool

ing

high

cool

ing

med

cool

ing

low

fan

high

fan

med

fan

low

heat

ing

high

heat

ing

med

heat

ing

low

-77-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 78: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

14. Air velocity and distribution

m

Fig 1top viewflow control panel horizallourer:center

Fig 3top viewflow control panel horizontallourer:center

0.250.51.02.0

Fig 4top viewflow control panel verticallourer:center

ConditionFan speed:highOperation mode:fanVoltage:230V,50Hz

Fig 2top viewflow control panel horizontallourer:right and left

1098765432

1

1

1

2

2

0

m

0.250.51.02.0

m109876543210

3

1.8

1

0.25

unit m /sm

0 1 2 3 4 5 6

0.5

m

1.0

2.0

3.0

1.8

3 m109876543210

m 3

2

0

1

2

1

2.0

1.00.5 0.25

1.00.5

0.25

unit m/s

unit m/s

unit m/sm

-78-

Commercial Air Conditioner Model: AU18/222XFERA AS072/092/122XVERA

Page 79: SERVICE MANUAL -  · PDF file12. Performance curves ... That is convenient for building management. Weekly timing function, if connected with a detector and a weekly timer

Commercial Air Conditioner Model: AU182XFERA AS072/092/122XVERA

Sincere Forever

Haier Group Haier Industrial Park, No.1, Haier Road

266101, Qingdao, China

http://www.haier.com