Upload
bengalsac
View
217
Download
0
Embed Size (px)
Citation preview
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
1/112
Aimee Pulido, C.E.T
Fall 2013
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
2/112
Table Of Contents
Description
Functions of the SCADA system ..7
Hardware Components .8
Software Components ...13
Automatic Failover of SCADA Servers ..19
Failover of Historian Servers ..21
Starting iFIX
Starting iFIX on the Primary Dispatch Computer ..22
Starting iFIX on the Backup Dispatch Computer ..24Navigating the SCADA System
Initial Startup ...28
Normal Error Messages And Notifications Encountered 29
2
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
3/112
Table Of Contents
Navigating the SCADA System (continued)
Lower Menu Bar ....32
- Dispatch View Screen 32
- Main Menu ..33
- Help Menu 34- City Overview .34
- Report Menu ..35
- Early Warning System For High Flows At Gold Bar ..36
- Current Alarm Summary .37
- Alarm / Event History 39
- Notepad .40
- Tag List .41
- Dropdown Lists ....42
- Statuses .42
3
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
4/112
Table Of Contents
Navigating the SCADA System (continued)
City Overview Screen ..43
Station Pictures ..47
- Communication Screen .47
- Drains View Screen ..48- Annunciator Screen .49
- Trend Screen .51
- Site Info Screen 53
- Control Settings Screen .54
- Flow Diagram Screen ..55
- System Layout Screen .56
- Sectional View Screen 58
- Tank Summary Screen 59
- Schematic Screen ..60
4
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
5/112
Table Of Contents
Functions of the Dispatcher
24 hours/day, 7 days/week ....61
Task 3: Monitoring the SCADA Systems Health 63
Task 4: Monitor the SCADA System, Acknowledge and Dispatch
Alarms To the Appropriate Staff For Resolution ..66- A) Gather The Facts About The Alarm ...69
- B) Respond To The Alarm .78
Task 5: Document Steps Taken For Resolution of Alarms .92
Task 6: Verify Correct Functioning of the CommunicationsNetwork ..98
Task 7: Communicate With Pumpwells Field Staff And ContractorsDaily and Document Who Is At Site, Performing What Tasks, SoFalse Alarms Can Be Accounted For .113
5
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
6/112
Table Of Contents
Functions of the Dispatcher (continued)
Task 8: Document problems with the SCADA SystemFunctionality....117
Task 9: Communicating Problems With The Functionality Of The
Call Centers SCADA Computer Hardware or Software .120
6
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
7/112
Description
Functions of the SCADA system:
Collects and displays and monitors over 5000 real-time alarms, events,statuses and readings, and displays graphically animated and non-animated data used to verify the operation of >130 mechanical and
electrical drainage facilities, including pump stations, storm waterpond automatic gates, level sensors, odour filters, etc.
- Shows how facilities should work in accordance with the design
specification
- Shows how facilities are actually working (and if not properly working,
shows what is wrong)- Helps with the maintenance and troubleshooting of facilities
7
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
8/112
Description
Hardware components:
SCADA servers:
- Runs the SCADA application (iFIX software)
- Master KENSCA01: Located in Century Place
- Backup KENSCA02: Located in Century Place Historian servers:
- Runs Proficy Historian software
- Master COEACLA1: Located in Century Place
- Backup COEACLB1: Located in Century Place
- Servers have a shared clustered drive known as CEPACL171 for the
purposes of data management
8
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
9/112
Description
Hardware components:
SQL server:
- Runs Alarm and Events SQL database for Proficy Historian software
- CEPASQL81: Located in Century Place
- Server is shared with other SQL databases from other COE departments Terminal Services server:
- Runs iFix Terminal Services software
- CEPACTX02E: Located in Century Place
- iFIX on this server is accessed through a Citrix Session
Real-Time Information Portal server:
- Runs Proficy Real-Time Information Portal software
- CEPACTX02E: Located in Century Place
- Accessed through a webpage at http://proficy/proficyportal/ orhttp://rwa.edmonton.ca/proficy
9
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
10/112
Description
Hardware components:
T1 Switch:- Connection to the Rogers Communications GPRS cellular network
Developers workstations:
- Assembly and programming of the graphics, database, scripts, etc.- Troubleshooting of the system- In Aimee Pulidos and Tony Liaos office
View Client workstations:
- Various personal computers used to view the SCADA System
- Located in Kennedale, Coronation Yard, Century Place, EmergencyOperations Centre, Davies Yard
10
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
11/112
Description
Hardware components:
Programmable logic controllers (PLC):
- Located at remote sites (mechanical and electrical drainage facilities,
including pump stations, storm water pond automatic gates, level sensors,
odour filters, etc.)- Controls Processes at sites based on input coming from instrumentation
monitoring site conditions
- Relays all important alarms, events, statuses and readings from the site to
the SCADA system
General Packet Radio Service (GPRS) radio modems:- Connected to PLCs at remote sites and to a wireless antenna
- Transmits data received from the PLCs through the Rogers GPRS wireless
network to the City of Edmonton networks T1 switch, through the firewall
and to the SCADA servers
11
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
12/11212
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
13/112
DescriptionSoftware components:
iFIX:
- Human Machine Interface software for the Supervisory Control And DataAcquisition (SCADA) system
- Allows development and presentation of and monitoring tools and sitegraphics for alarms and processes at each station in the WastewaterCollection system.
- Contains the following sub-applications:
Proficy iFIX Workspace:
- Presents interactive animated graphics containing real-time station data fromprocesses and alarms, and allows for monitoring and dispatch of alarm condition
- Contains development tools for creation of graphics, animations, etc.
Process Database:
- Records current values of alarms, statuses and readings from sites
13
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
14/112
DescriptionSoftware components:
iFIX:
- Contains the following sub-applications:
Visual Basic Editor:
- Allows for programming computer code to automate functions and provide
additional functionality to the system, not provided for by the out-of-the-box iFIXsoftware
Fix Background Server:
- Runs on the primary and backup SCADA servers to monitor door alarms,communications alarms, transfer of PLC communications to alternate server onserver failure, database reading and writing tasks, alarm response functionality,report generation, and rain gauge calculations.
- Runs on one of the development nodes to automate the Early Warning System formonitoring and preparing for high flows at Goldbar Wastewater Treatment Plant,sends the information to Goldbars control center
14
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
15/112
DescriptionSoftware components: iFIX:
- Contains the following sub-applications
OPC Powertool:
- Programs addresses of tags in the Process Database corresponding to addresses in
the Programmable Logic Controller in each station for data transfer of real-timedata process and alarm values into iFIX
IGS Driver:
- Translates communications from Pump test tanks PLC into iFIX directly ratherthan through a modem
SCADA Sync Monitor:
- Runs on the primary and backup SCADA Servers to handle failovers of servers,synchronization of databases, pictures and alarm areas between the two servers
15
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
16/112
DescriptionSoftware components: IO Server:
- Runs on primary and backup SCADA Servers to translate communications protocolsover the Rogers network from the PLCs into iFIX
Proficy Historian:
- Runs on dedicated primary and backup Historian Servers in a virtual clusteredenvironment to archive and retrieve:
Real-time data generated from stations equipment and processes andhandled in iFIXs Process database (excluding alarm statuses from sites)
Alarms and Events generated in iFIX based on values from stations, issues withthe SCADA Servers, Historian servers, or security issues
16
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
17/112
Description
Software components: Proficy Historian:
- Contains several sub-applications for its processes:
iFIX OPC AEServer / Collector:
- Handles the transfer of alarms and events from iFIX into Proficy Historian, which
are then routed through to a SQL Server database (on a server shared with otherCOE departments SQL databases) for archival
iFIX OPC Server / Collector:
- Handles the transfer of station Real-time data values from iFIX into ProficyHistorian, which are archived in Historians proprietary formatted archive files.
Calculation Collector:
- Performs calculations on custom-made tags based on real-time values in ProficyHistorian for a given tag
17
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
18/112
Description
Software components: iFix Terminal Services:
- runs on a dedicated server to provide client iFIX sessions to field crews andremote users
- Performs the same functions as a standalone (desktop) version of iFIXwithout needing to install iFIX on that machine
- Is accessible through a secure Citrix Session (running through InternetExplorer), in which permissions for iFIX have been granted by InformationTechnology on the users profile
- Requires that Citrix Client software is installed on the computer
Real-Time Information Portal:- Runs on a web server to provide access to SCADA data and data
presentation tools for remote users and external contractors
18
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
19/112
Description
Automatic Failover of SCADA Servers:
All remote site PLCs are programmed to transmit data to KENSCA01
(the master SCADA server) at IP Address 10.191.1.51, which is
translated by the network switch and routing equipment within the
City as 162.106.222.107 The SCADA servers monitor each others status
If iFix stops running on the KENSCA01 server, KENSCA02 (the standby
server) detects this, takeover as master SCADA server, activate an
alarm, and transmit a command to all remote sites to reset their target
IP address to 10.191.1.52, the current server, which is translated by
the network switch and routing equipment within the City as
165.106.222.210
19
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
20/112
Description
Automatic Failover of SCADA Servers:
When iFix is reinstated on the KENSCA01 server, it will transmit a
command to all remote sites to reset their target IP address to
10.191.1.51
If iFix stops running on the KENSCA02 (the backup server), the masterserver will detect this and activate an alarm
20
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
21/112
Description
Failover of Historian Servers: All SCADA nodes are programmed to access archived data and
archived Alarms and Events via the CEPACL171 cluster for historian
Both COEACLA1 and COEACLB1 historian servers maintain acontinuous representation of the data in the cluster so if eitherhistorian fails, the data cluster will be unchanged.
If both COEACLA1 and COEACLB1 servers fail, archiving will cease anddata will not be available to the SCADA nodes.
Upon reinstatement of one of the historian servers:
- the collectors located on the current master SCADA Server (KENSCA01 orKENSCA02) will automatically forward the missing data to the historian
- the historical archives will be updated
- access to their data and to Alarm and Events data by the SCADA nodes will bereinstated
21
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
22/112
Starting iFIX
Starting iFIX on the Primary Dispatch SCADA Computer: The primary Dispatch computer is to be logged on and functional 24
hours/day, 7 days/week using a generic logon, which doesntautomatically log off after a given timeout period and does not havescreen saver turned on
Log onto the primary dispatch SCADA computer with the followingcredentials:
- User name: isifix
- Password: Pumpwe!!01
- Domain: COE
22
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
23/112
Starting iFIX
Starting iFIX on the Primary Dispatch Computer: The iFIX software should commence automatically
- If iFIX does not commence within about a minute, on the desktop, double-click the iFIX icon
- In the event that a dialog box pops up,
looking like the one on the right, ensure
that the checkbox at the bottom is
checked,
then click the iFIX icon at the top
left in the box
23
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
24/112
Starting iFIX
Starting iFIX on the Backup Dispatch SCADA Computer: The Backup Dispatch SCADA computer can be either a regular
workstation used by the dispatch staff or the backup dispatch SCADAlaptop
It is only used when the primary SCADA dispatch computer:
- is having technical difficulty
- is in the process of being sent away for hardware related issues withAcrodex
- is in the process of being replaced by another computer
It performs the same tasks as the primary dispatch SCADA computer,however, instead of the iFIX software being installed on the machinedirectly, access is to iFIX terminal services on the iFIX terminal serverthrough the Citrix web client.
The Citrix Web client is accessible from any computer in the worldthrough an internet browser.
24
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
25/112
Starting iFIX
Starting iFIX on the Backup SCADA Computer:Method 1: If the City network is having no problems:
On a regular dispatch workstation, login to Windows with the dispatchemployees credentials (user name and password, Domain: COE)
On the desktop, double-click the Citrix VM External
The Citrix Web Browser will open and navigate to :
http://citrix.edmonton.ca
This is a web address within the City of Edmontons network
25
http://citrix/http://citrix/http://citrix/http://citrix/http://citrix/7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
26/112
Starting iFIX
Starting iFIX on the Backup Dispatch Computer:Method 2: If the City network having problems:
On the backup SCADA laptop (Serial number:R99MD36 currentlystored in Jan Cebulas office in the far left side bottom drawer), loginto Windows with the dispatch employees credentials (user name andpassword, Domain: COE
Plug the aircard (either Rogers or Telus, pick one) into the laptop
Note: There is one is for each network provider so if one providers network is
down then you can access using the other network.
26
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
27/112
Starting iFIX
Starting iFIX on the Backup Dispatch Computer:Method 2: If the City network having problems:
IF USING ROGERS AIRCARD
- The Mobilink Lite software should open automatically.
- If it does not double-click on the Mobilink Lite icon on the desktop or press the windows key
On the taskbar at the bottom right side of the screen, right-click on themobilink icon
Select Open Mobilink Lite
- Click the Connect button and wait until the aircard is connected to the
network
27
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
28/112
Starting iFIX
Starting iFIX on the Backup Dispatch Computer:Method 2: If the City network having problems:
IF USING TELUS AIRCARD
- The Connection Manager software should open automatically.
- If it does not double-click on the Connection Manager icon on the desktop- Click the Connect button and wait until the aircard is connected to the
network
- NO MATTER WHICH AIRCARD IS USED:
- Double-click the Citrix VM External icon
- Or, in an Internet browser window, enter the address:
https://citrix.edmonton.ca/
28
https://citrix.edmonton.ca/https://citrix.edmonton.ca/7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
29/112
Starting iFIX
Starting iFIX on the Backup Dispatch Computer:Methods 1 and 2:
When prompted, enter the login credentials and click Log On
- User name: isifix
- Password: Pumpwe!!01
29
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
30/112
Starting iFIX
Starting iFIX on the Backup Dispatch Computer: The Citrix Web Interface window will open:
- Double-click the iFIX5_0 Operator icon
- Logon scripts will run, they
map the directories so that
the application will function
correctly
30
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
31/112
Navigating the SCADA system
Initial Startup: Once the iFIX software is started, the City Overview screen will be
displayed
32
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
32/112
Navigating the SCADA system
Normal Error Messages and Notifications Encountered: Occasionally an error message is
displayed similar to the one at the
right.
This tells the user that the networkhas not finished intializing its
connections and the tags are unable to get their data from the processdatabase.
There is no need to be concerned with these errors, as they will be
resolved as the system stablizes. Click the Skip All button
If any other error message is displayed, this is not normal AimeePulido should be notified during regular working hours so the problemcan be rectified. This can be done by documenting the error on the
SCADA Concerns form, as per SCADA Dispatcher Functions Task 8.32
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
33/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Dispatch View Screen
The screen where the
dispatch staff will spend the
majority of their time
Acknowledge, and document
alarms and their resolutions Place and view alarms on
hold
33
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
34/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Main Menu
Contains:
- several quick-navigation
buttons to various station
pictures
- Buttons for administrativetasks (these are only
functional with
administrative and
supervisor security
clearances, so they will
not function for thedispatchers) 34
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
35/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Help Menu
Not yet functional
Will be used to provide help information for users with respect to the SCADAsystem functionality
- City Overview
Navigates back to the City Overview (main map) screen
35
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
36/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Current Alarm Summary
A list of current alarms in the SCADA
system, which is able to be printed
Used by pumpwells staff and
supervisors to check on current alarm
statuses Clicking the View # Held Alarmsbutton opens Alarms On Hold screen:
- Clicking on an alarm row in this screen generates message, clicking Yes to this
message re-enables alarming for the tag in the selected row36
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
37/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Current Alarm Summary
Right-clicking on the alarm screen
displays a menu, which enables the
dispatcher to:
- Enable/Disable Alarm Horn - turns the
audible alarm signal on/off on thecurrent SCADA node for the entire time that the node is being
used until it is manually re-enabled/disabled
Note: menu changes depending on which option is currently
selected prior to right-clicking)
- Silence Alarm Horn silences the alarm horn for the current
alarm instance only IMPORTANT : Dont select Pause Alarm Read - alarming will cease in SCADA 37
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
38/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Alarm / Event History
Displays a list of alarms and events
in the past
Queries Historian Alarm and Events
SQL database based on:
- Start Date - End Date- Station # - Type (Alarm or
Event)
Clicking Print will print the list
Dragging column headers left/right
adjusts the width of the column
for easy reading of field values 38
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
39/112
Navigating the SCADA system
Lower Menu Bar:
Buttons are present for:
- Notepad
Used by Pumpwells staff and
supervisors to modify and save
operator message (a message that
pertains to the SCADA system in
general, rather than a particularstation)
Provides additional information
with respect to conditions in the
SCADA system, or in the field and
response requirements39
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
40/112
Navigating the SCADA system
Lower Menu Bar:
Dropdown lists are present for navigating to station pictures based on:
- Station #
- Station Name (not organized alphabetically)
Statuses (in bright blue) are read from the Process Database anddisplayed for:
- PLC Communication Path (The current server where the stationscommunications are directed to)
- KENSCA01 status
- KENSCA02 status
- Current Date and Time
40
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
41/112
Navigating the SCADA system
City Overview Screen: The City Overview screen contains:
- A right menu panel with:
Buttons that, when clicked, show (black button face text)
or hide (grey button face text) different layers on the map
to enhance its visual functionality
A Legend corresponding to the animated station icons on
the map based on:
- Station type (icon shape)
- A stations influent type (color of icon)
41
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
42/112
Navigating the SCADA system
City Overview Screen: The City Overview screen contains:
- Animated blinking red indicator for unacknowledged alarms in the DispatchView System, consisting of:
Outline around the
map
Lower Navigation Area
Background
Note to the Operator
below the navigation
buttons
42
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
43/112
Navigating the SCADA system
City Overview Screen: The City Overview screen contains:
- An animated map that displays stations, their current statuses (monitoredby the pumpwells department) and their geographic locations within theCity of Edmonton boundaries
When a station is clicked, navigates to station or system pictures A stations status will either be:
- Normal (no yellow or blinking oval
surrounding the station number)
- In alarm (a yellow or blinking oval
surrounding the station number)
43
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
44/112
Navigating the SCADA system
City Overview Screen: The City Overview Screen contains:
- An animated map that highlights (displays a box outlining) the 4 quadrantsof the city when the mouse hovers over each individual quadrant
When a quadrant is double-clicked, it will zoom in for easier clicking
on stations When a quadrant is double-
clicked a second time, it will
return to its normal size
44
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
45/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- An alarm banner (at top of picture)
outlining all current alarms within
the station
- A navigation bar with buttons for:
Communication
- A screen that allows for changing the station refresh rate (The maximum time to pass between communications from the
stations PLC to the SCADA servers. This is used to generate an automatic send of data
from the site to the SCADA Servers in the event that no process data is sent from the
site to the server prior to the expiry of this time. Therefresh rates at each station are different and depend on
the stations criticality.)
Server that the PLC is supposed to communicate to
- Allows for request of refresh of site data transmissions
- Easy viewing of heartbeats from the site to both the
primary and backup servers
45
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
46/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Drains View
- A screen that displays the site in a screenshot from the DRAINS application
- Displays flow directions and paths for the Stations incoming and outgoing flow- Has zoom in/out capability for easy identification of site details and DRAINS IDs
- Screen is not yet constructed for many stations
46
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
47/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Annunciator Screen
- Accessed by button with station address
- Allows for viewing of all tags in the Process database and their current values,which correspond to this station
- Tags are displayed by their type (as
selected by the left menu)
47
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
48/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Annunciator Screen
- Double-clicking on the individual tag
opens its tag profile (configuredsettings for the selected
tag), which is helpful to
electricians and
instrumentation staff for
troubleshooting
48
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
49/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Trend
- Displays a graph of one of more
pens (colored lines), associatedwith data for each selected tag
from Proficy Historian
- Allows for easy viewing
of potential site problems and
troubleshooting
- Displays data in text format belowthe graph for each tag, based on:
- Cursor Position (the thick vertical grey line on the trend), which can be dragged left or
right, to get reading values for any place on the trend
- Maximum reading on the screen
- Average Value of readings on the screen
- Minimum reading on the screen
49
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
50/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Trend
- Double-clicking on the trend opens chart
configuration dialog box- Allows for temporarily changing the chart
(reverts to original state when restarting iFIX) General tab:
- Change the visual appearance of the chart
Chart tab:- Data Sources section: add/remove pens (tags)
- Pens tab: change pen high/low limits, colors, linestyles and widths
- Time tab: change chart start date or start time
to a fixed date, or a number of days before now, change the duration of the chart (from
beginning to end of displayed data) based on how many days to view at a time, change the data
interval (how often the data is sampled to create the trend)
- X-Axis and Y-axis tabs: change the color, or number of labels or ticks to display on the
horizontal axis (X-axis) or vertical axis (Y-axis), add titles to axis
- Grid tab: change # vertical or horizontal lines, line color/style for the chart grid
- Legend tab: Change the pens (tags) text data values to be displayed below the chart50
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
51/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for: Site Info
- Allows for changing of operator
message viewed for a given station
(station selected in the dropdown listat the top center of the screen) , which
then is displayed in the Dispatch View
System screen in the Temporary
Notes box
- Clicking Site Description button Toggles Site Description button to a Site Notes button (takes you back to the Site Info
screen Changes text displayed in window to the description of the site, including :
- Address, and how to locate the station- General functionality of the station- Pump, rated discharge, power supply, active volume, storage volume, emergency overflow
information, and other important-to-know information pertinent to the station
The information entered in this window is displayed in the Site Info tab in the DispatchView System
51
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
52/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Control Settings
- Displays the control sequences for the
station, with values coming from thestation (in bright blue) or hardcoded
values (in black) indicating its pump
equipment and alarm setpoints, as
well as any other pertinent control
information for the site
- Values are color coded to correspondto the color of the animations on the
main station screen
52
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
53/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Flow Diagram (optional)
- Displays the layout and flow directions of chambers and/or pipe-work within the
station to enhanceunderstanding of flow
patterns
- Individual pipes or
chambers are different
colors for easy
identification
53
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
54/112
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
55/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
System Layout (optional)
- This picture contains:
Flow basin information (Layout of Pipes within the system and their corresponding flowdirections)
Clickable station icons for all stations within the system (Clicking on the station icons
opens the corresponding
station picture )
55
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
56/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Sectional View (optional)
- A sidelong view of a station with multiple flow paths
- Outlines depths and instrumentation readings for control philosophy at thevarious points throughout
the flow branches and site
components
- Provides a simplified view
of the site to assist in
better understanding of thesite layout and functionality
56
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
57/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Tank Summary (optional)
- A report screen for
stations that requirereporting on
hydrocarbon level
control within
particular stations
based on:
Gradual increases Rapid increases
Emptying of tank
Start and stop of
oil collection
57
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
58/112
Navigating the SCADA system
Station Pictures: Station Pictures contain:
- A navigation bar with buttons for:
Schematic (optional)
- Electrical and water line schematic for the site to assist in understanding
operation of the sitewhere complex
processes are
taking place
- Used by pumpwell
electricians,
instrumentationstaff, and millwrights
to troubleshoot the
site.
58
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
59/112
Functions of the Dispatcher
24 hours /day, 7 days/week: Task 1: Ensure that the dispatch monitoring computer is logged in and
iFIX is running at all times (see slides 22-30 for methodology)
Task 2: If audible signal is turned on (i.e. on evening shift, etc.), ensurethat volume is turned on and loud enough for audible alarm signals to
be heard by dispatch staff (also see slide 37)
Task 3: Monitor the SCADA systems health and Communicating withPumpwells Departments Electrical Engineer (Tony Liao) or ProcessControl Specialist (Aimee Pulido) when server or software issues arepresent (see slides 61-64 for methodology)
Task 4: Monitor the SCADA system, acknowledge and dispatch alarmsto the appropriate staff for resolution (see slides 65-90 formethodology)
Task 5: Document steps taken for resolution of alarms (see slides 91-97 for methodology)
59
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
60/112
Functions of the Dispatcher
24 hour /day, 7 days/week: Task 6: Verify correct functioning of the Rogers Communications GPRS
network. (see slides 98-105 for methodology)
Task 7: Communicate with Pumpwells Field staff and contractors dailyand document who is at what site, performing what tasks, so false
alarms can be accounted for (see slides 106-108 for methodology)
Task 8: Document problems with the SCADA system functionality (seeslides 109-110 for methodology)
Task 9: Communicating problems with the functionality of the callcenters SCADA computer hardware or software (see slide 111 for
methodology)
60
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
61/112
Functions of the Dispatcher
Task 3: Monitoring the SCADA systems health: On the lower menu bar:
- State 1: Verify SCADA system is in
Normal Operating Mode:
PLC Communication Path: KENSCA01
KENSCA01: ACTIVE KENSCA02: STANDBY
- State 2: If not in Normal Operating Mode, verify SCADA system is inMaintenance Mode (Tony or Aimee is currently working on the Servers):
PLC Communication Path: KENSCA01
KENSCA01: ACTIVE KENSCA02: ACTIVE
and it is currently in the regular working day time period (7:30am-3:30pm,Monday to Friday)
- These two states are considered normal and nothing needs to be done atthis time
61
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
62/112
Functions of the Dispatcher
Task 3: Monitoring the SCADA systems health: On the lower menu bar:
- State 1: If the SCADA system has
failed over:
PLC Communication Path: KENSCA02
KENSCA01: ?????? KENSCA02: ACTIVE
Or KENSCA01: STANDBY KENSCA02: ACTIVE
- This state indicates trouble with the primary server, however the systemhas failed over correctly and is functioning is it is intended for backup
purposes call Aimee Pulido or Tony Liao to investigate the problem if
during the working day, or wait until the next working day to call,provided no other server problems occur.
- If other SCADA is not functioning correctly in the above states, call Tonyimmediately.
62
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
63/112
Functions of the Dispatcher
Task 3: Monitoring the SCADA systems health: On the lower menu bar:
- State 1: If the SCADA system
is not functioning correctly:
PLC Communication Path: KENSCA01 or KENSCA02 or ??????
KENSCA01: ??????
And, KENSCA02: STANDBY
- State 2: If the PLC Communication Path does not match the current activeserver
KENSCA01: ACTIVE and PLC Communication Path: KENSCA02 or ??????
KENSCA02: ACTIVE and PLC Communication Path: KENSCA01 or ??????- State 3: If the SCADA system is in Maintenance Mode (see previous slide)
and it is currently outside the regular working day time period (after3:30pm and before 7:30am (Monday to Friday), or all daySaturday/Sunday)
- These three states are not considered normal call Aimee Pulido or TonyLiao immediately to investigate the problem (Tony after hours) 63
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
64/112
Functions of the Dispatcher
Task 3: Monitoring the SCADA systems health:
During Regular Working Hours:Tony Liao Office: 780-423-3257
Cell: 780-868-2469Aimee Pulido Office: 780-496-1768Cell: 780-554-0824
Outside Regular Working Hours:
Tony Liao Cell: 780-868-2469Aimee Pulido Cell: 780-554-0824
64
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
65/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
The Dispatch View Screen:
65
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
66/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
When an unacknowledged alarm is present:
- The City Overview Screen will display:
A blinking red outline
around the map A blinking red background in the
center of the lower navigation bar
A high-visibility message at the
bottom of the screen indicating
the presence of an
unacknowledged alarm
66
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
67/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
When an alarm is present:
- If the Alarm Horn is enabled, beeping will sound from the computer
- A row in the alarm banner at the top of the screen will blink yellow/blue,
indicating the tag that is in alarm- A row that is solid yellow indicates that a tag is still in alarm, but that the
alarm has been acknowledged (as viewed also by the in the Ack column
of the alarm banner)
A rows text will go green and then disappear once an alarm condition
has cleared (see next slide) 67
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
68/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution:
A) Gather the facts about the alarm:
- Step 1: Double-click on the blinking alarm row
If the Alarm Horn is enabled, the audible beeping will stop, provided there areno other unacknowledged alarms in the alarm banner
The alarm will be changed to a solid yellow row, and the will be populatedinto theAckcolumn of the alarm banner.
The Date In and Time In columns will be populated with the current Date andTime when the alarm was generated. If the alarm was previously on hold thistime is the time the alarm was re-enabled (came off hold).
68
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
69/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
The Description column indicates the tag that is in alarms english description,rather than its technical name and is used in conjunction with the Value (thecurrent state of the tag in question) to determine the alarm condition
TheAlarm Extension Field2 column indicates the last task performed with
respect to alarm resolution for this tags current state to determine the alarmcondition
The alarm information below the alarm banner will be updated to theselected tags information
69
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
70/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 2: Carefullyread the information in the Dispatch Info tab
This outlines the steps the dispatcher is to take to resolve the alarm Each tag has different dispatch information, depending on the requirements
of the site, the severity of the alarm, the influent type, and many otherpertinent considerations
The selected tags dispatch information depends on the day, the current timeof day, and the season, and changes automatically
70
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
71/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 3: Carefullyread the information in the Temporary Notes
This informs the dispatcher of any temporary concerns or changed conditionsat the station that correspond to this alarm
It provides additional temporary alarm handling and response procedures,which supplement or overrule the Dispatch Info
If the note is more than 6 months old, contact the writer of the note durign
regular working hours to verify its accuracy and have them change the date totodays date 71
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
72/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 4: If there is no expiry date on a note, assume that the note is stillpertinent and:
Verify the alarm type:- For MECHANICAL ALARM, send
an email to the Pumpwell
Millwright Foreman (Denis Hillier) requesting that an expiry date is added to the
temporary notes for this station
- For ELECTRICAL ALARM, send an
email to the Electrical Engineer(Tony Liao) and the Electrical foreman (Heng Khey) requesting that an expiry date
is added to the temporary notes for this station
Document this deficiency for this tag value on the SCADA Concerns form inthe the SCADA Dispatch Forms Binder (Section 2) as per Functions of theDispatcher, Task 8
72
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
73/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 5: Read the information in the Site Info
This provides the dispatcher a basic understanding of :
- The stations address- Directions to get to the station
- The stations control philosophy (basic expectations of the sites function)
- The stations major equipment
- Interactions with other stations
- Other important information pertaining to the station
This information helps the dispatcher to understand the potential impact ofan alarm at the site and its surrounding areas
73
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
74/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 6: If, based on the Site Info and the Temporary Notes, the DispatchInfo seems incorrect or strange:
Respond to the alarm with due diligence, using the information provided asan outline for guiding your response decision (err on the side of safety)
Document the steps taken for alarm response and the reasons for deviatingfrom the listed procedure by typing the steps taken in the Log Note Box, andclicking the Log Only button
Document this deficiency for this tag value on the SCADA Concerns form inthe the SCADA Dispatch Forms Binder (Section 2) as per Functions of the
Dispatcher, Task 8
74
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
75/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 7: Carefullyread the information in the Calling Info
This outlines a list of people to call in order to report the alarm It is important to follow these steps fully and in sequential order
Pay close attention to call only the people on the list
75
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
76/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
A) Gather the facts about the alarm:
- Step 8: Review the information in the Employee/Contractor Working InPumpwell Stations documentation for in the SCADA Dispatch FormsBinder (Section 1)
This outlines a list of employees or contractors
currently working at sites
Look for the station # to verify if anyone is listed
as working at that site
If an employee or contractor is on site:
- call them first prior to verify if the alarm isgenerated by the work they are completing
- Call them first for any alarms of the same type (electrical or mechanical)
At that site
76
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
77/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
a) Determine if this is the initial alarming of the tag:
- In the alarm banner, Date In and Time In will be the current date and time
- TheAlarm/Event History will have no previous record of this alarm in the past 112hours
b) If it is the initial alarming of the tag, follow the Dispatch Info instructions todetermine how long to place the alarm on hold
c) Determine if the alarm waspreviously placed on hold (indicated by):
- Date In and Time In will be anywhere from 5 minutes to 112 hours ago (dependingon how long the alarm was placed on hold previously)
- TheAlarm/Event History will have record of this alarm being placed on hold in thepast 112 hours
d) If it was previously placed on hold, DO NOT PLACE IT ON HOLD A SECONDTIME, follow callout procedure.
77
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
78/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
To check the Alarm/Event History for records of this alarm:
- The Alarm/Event History comprises several fields of data queried from the ProficyHistorian, outlining any alarms or events that were generated in SCADA in a giventime frame
- Click theAlarm / Event History button on the bottom menu bar
- On theAlarm/ Event HistoryScreen, click the Down Arrow besideAlarm Typeuntil the Alarm Type reads Events
78
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
79/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
To check the Alarm/Event History for records of this alarm:
- Click the dropdown arrowbeside the Select Station dropdown box, scroll downand select the station pertaining to the alarm in question
- Change the start date to 4 days prior to today (the end date), using the startdatesdown arrow
79
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
80/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
To check the Alarm/Event History for records of this alarm:
- Drag the right edge of the column headers for the following columns to the left toshrink the columns
alarmid
source
eventcategory,
subcondition
start_value
end_value
acktime
acked
80
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
81/112
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
82/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
To check the Alarm/Event History for records of this alarm:
- If an alarm was previously placed on hold, the following lines will appear for thegiven alarm (in this case, the alarm was PW131_P1_PHASE):
- They are read from the bottom up, as the newest time is at the top
e) Click the Place On Hold Button
82
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
83/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
f) Select the correct date and time
(including AM|PM) according tothe instructions reviewed on the
Dispatch Info tab, Temporary Notes, or
Instructions received from person
called to deal with the alarm
g) Click OK
83
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
84/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 1: If the Dispatch Info states toplace the alarm on hold
i) Confirm the disabling of the alarm by clicking OK
j) If the incorrect amount of time was selected, click Cancel and repeat theprevious process of placing the alarm on hold, using the correct amount oftime
- The alarm will be placed in the Held Alarms list and alarming will be disabled in theProcess Database until the end of the hold time
- The alarm will be logged automatically and the log status will be updated with thehold time selected
84
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
85/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 2: If the Dispatch Info states to call someone, determine who to callusing the Calling Info, and determine their phone number
During regular working hours:
- pick a NAME from the dropdown box, to where the call will be made
- The phone number will be displayed below the name selection box
85
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
86/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 2: If the Dispatch Info states to call someone, determine who to callusing the Calling Info, and determine their phone number
Outside regular working hours:
- Click the View Weekly Standby Listbutton
- The Weekly Off-Hours Response Information document will be opened in aseparate window
- This document provides a primary and an alternate phone number for each personon call for the week (commencing Wednesday at 3:30pm and ending the followingWednesday at 7:30am)
- The list changes weekly
- If the Alarm Type is Mechanical Alarm:
The first contact on the list will be the Pumpwell Millwright
The second contact on the list will be the Pumpwell Repairman
- If the Alarm Type is Electrical Alarm:
The primary contact on the list will be the Electrician 86
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
87/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 3: Make the phone call
Inform the contact of the:
- Alarm Description (in the Alarm Banner)
- Its current Value (in the Alarm Banner)
- Its start Date and Start Time (in the Alarm Banner)
- If it has previously been placed and come off the hold list
87
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
88/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 3: Make the phone call
During regular working hours:
- The names in the dropdown list will change based on whether the alarm ismechanical or electrical in nature
- If the first person on the name dropdown list doesnt answer, according to theCalling Info instructions, try the next number on the dropdown list
- In the event that nobody on the list can be reached:
Leave a message. Wait 5 minutes and call through the list again
Repeat calling at 5 minute intervals until someone is reached
- In the event that nobody on the list can be reached after 20 minutes: Contact Pumpwells General Supervisor (Sid Lodewyk)
If the Pumpwells General Supervisor cannot be contacted, then contact the Director ofDrainage Services (Derek Melmoth)
Phone numbers for these are listed at the end of the name and phone numberdropdown lists
88
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
89/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 3: Make the phone call
Outside regular working hours:
- The standby crews are listed on the standby list, according to the weekly standbyschedule
- For Mechanical Alarms:
Call the Pumpwell Millwright Primary #
If no answer, leave a message, call the Pumpwell Millwright Alternate #
If no answer, leave a message, call the Pumpwell Repairman Primary #
If no answer, leave a message, call the Pumpwell Repairman Alternate#
Repeat calling at 5 minute intervals until someone is reached- For Electrical Alarms:
Call the Electrician Primary #
If no answer, leave a message, call the Electrician Alternate #
Repeat calling at 5 minute intervals until someone is reached
89
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
90/112
Functions of the Dispatcher
Task 4: Monitor the SCADA system, acknowledge and dispatchalarms to the appropriate staff for resolution :
B) Respond to the Alarm
- Step 3: Make the phone call
Outside regular working hours:
- In the event that nobody on the above list can be reached:
Leave a message. Wait 5 minutes and call through the list again
Repeat calling at 5 minute intervals until someone is reached
- In the event that nobody on the above list can be reached after 20 minutes:
Contact the Standby Supervisor listed on the Weekly Off Hours Response Informationdocument
90
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
91/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE list:
- Notified Millwright Foreman:
If the millwright was spoken to, and it was stated that he would take care of it
- Notified Electricians:
The alarm was listed as an electrical alarm, the electrician was contacted and will betaking care of the problem
- Notified Maintenance Crew:
The millwright foreman could not be contacted, the alarm was listed as an mechanicalalarm, so a pumpwell maintenance crew was contacted and will be taking care of theproblem
- Notified Carmacks:
For stations PW5016, PW5017, PW5018 alarms 91
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
92/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE list:
- Notified Edmonton Catholic Schools
- Notified Edmonton Public Schools:
For high levels in ponds on school properties, as per alarm response instructions on
certain stations- Notified Bob Richards/ Greg Bergsten:
For alarm response with respect to Rain Gauges
- Notified Shaune Rivard:
For alarm response with respect to certain alarms at PW5024
- Notified Tony Liao
- Notified Aimee Pulido
For alarm response with respect to SCADA or server issues 92
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
93/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE dropdown list:
- Notified Supervisor:
If the responsible personnel could not be contacted and the pumpwell supervisor(during regular working hours) or the standby supervisor (outside regular workinghours) was contacted instead
- Notified Director:
If the responsible personnel could not be contacted and the pumpwell supervisor(during regular working hours) or the standby supervisor (outside regular workinghours) could not be contacted, and the director was contacted instead
- Notified Standby Crew:
If it is outside normal working hours, standby personnel was spoken to and it wasmentioned that they would go and take care of the issue
93
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
94/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE list:
- Notified Drainage Operations Preventative Maintenance
If the alarm is related to:
- high water level on the North Saskatchewan River
- Notified EPCOR dispatch: If the alarm is related to:
- high water level on the North Saskatchewan River
- EWSs (Early Warning Systems) Mix chemical now or high level alarms
- No Answer:
Telephoning personnel resulted in no answer (telephone line rang (was not busy),nobody answered the call)
94
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
95/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE list:
- Busy Phoneline
Unable to speak with the required personnel, as the phone line is busy
Wait 2 minutes and try the call again
If unable to get through, then call the next person on the list- As Instructed by Supervisor:
If the supervisorinstructed the alarm to be placed on hold
- As Instructed by Temp Notes:
If the instructions in the Temporary Notes were followed rather than the instructions inthe Dispatch Info
95
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
96/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE list:
- Crew On Site:
A crew has called in and is working at the site (as documented on theEmployee/Contractor Working In Pumpwell Stations form, and they have generatedthe alarm
- Central Station Fault- False Alarm:
A false alarm was generated by an error in SCADA or on the servers
- Contractor Tripped False Alarm:
A contractor is working at the specified site, they have been contacted (i.e. as instructedby temporary notes), and they have mentioned that it is a false alarm caused by theirwork
- Accidental Trip:
The personnel on site has mentioned that they accidentally tripped the alarm 96
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
97/112
Functions of the Dispatcher
Task 5: Document steps taken for resolution of alarms- Step 1: Log the resolution:
Select from the LOG NOTE list:
- Testing
A new alarm is being implemented and tested or an existing alarm is being tested , asnotified by the contacted personnel
- Point Message Not Configured
Message for the alarm states Point Message Not Configured, which indicates that
there are no current procedures documented for this alarm in the Dispatch Info If this message is displayed in the Dispatch Info, document this deficiency for this tag
value on the SCADA Concerns form in the the SCADA Dispatch Forms Binder (Section 2)as per Functions of the Dispatcher, Task 8.
Send an email to Denis Hiller or Tony Liao outlining the alarm, the current state of thealarm and the Point Message Not Configured status in Dispatch Info for that particularalarm
Tony and Denis, will review the email, and will make the change in the system
97
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
98/112
Functions of the Dispatcher
Task 6: Verify correct functioning of Communications network All communications from the PLCs at remote stations are transmitted
via the Rogers Mobility General Packet Radio Service cellular network
Communications are monitored by the SCADA system for everyremote station
The Communications refresh rate
(minimum time between PLC to
SCADA Server communications) is
set in the communications settings
picture of each given site Each station has a different refresh
rate depending on the criticality of the
site
98
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
99/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network If the SCADA servers fail to receive station communications after 4
times the refresh rate, a COMMUNICATION FAILURE ALARM will begenerated for that station
There are a quite few possible causes for a Communication FailureAlarm
99
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
100/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network Cause 1: Simultaneous occurrences of communication failure alarms
over a large geographic area of sites is unusual, and is likely a networkfailure with:
- The Rogers Mobility Cellular Network
If the progression of faults appears to stall at a dozen or so sites, it is more likely theproblem is in the Rogers Communications network, where an individual cellular towerhas a fault
If the entire city is in communication failure (and you are able to use your computer toaccess your H:\ drive or another network location, indicating that the Citys network isstill fine) It is likely a larger outage with Rogers network
- The City of Edmonton Network A complete breakdown may occur in the event of failure of the City of Edmonton
- Access point
- Networking equipment
- Extended Power failure
100
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
101/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network For network-related communications failure:
- Immediately Call Tony Liao (for entire city in alarm) or one of theelectricians (if not entire city in alarm), working your way through theelectricians callout list
- If they require the Rogers APN Customer Support phone number, provideit to them: 1-877-939-3282 (24 hours)
101
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
102/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network Cause 2: Simultaneous occurrences of a few communication failure
alarms of sites (excluding rain gauge RG### communicationfailures) in no specific geographic pattern is not unusual, and is likely aproblem with:
- The modems or PLCs at the affected stations- Radio signal interference
For site-related communications failures:
-Step 1: On the station dropdown menu in the lower menu bar of the SCADAwindow, select the station affected by the alarm.
- Step 2: If a system graphic opens, click on the affected station
- Step 3: Once the station graphic opens, click the COMMUNICATION button
102
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
103/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network For site-related communications failure:
- Step 4: On the Communications Settings Window check that the refreshrate matches the refresh rate in the note at the bottom of the screen
- Step 5: In the event of a discrepancy, type the number of minutes into therefresh rate minutes box
103
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
104/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network For site-related communications failure:
- Step 6: On the lower menu bar, verify which SCADA Server is ACTIVE
- Step 7: If KENSCA01: Click the button
- If KENSCA02: Click the button
- Step 8: Click the button
- Step 9: Return to the Dispatch View system and continue monitoringalarms
- Step 10: If alarm doesnt go away after 5 minutes, follow instructions aslisted in the Dispatch Info
104
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
105/112
Functions of the Dispatcher
Task 6: Verify correct functioning of the Communications network Cause 3: Rain gauge (RG###) communication failures in no specific
geographic pattern is notunusual, and is likely a problem with:
- The modems or PLCs at the rain gauge sites
- Radio signal interference
- For rain gauge-related (sites RG037, RG038, RG039) communicationsfailures:
- Step 1: During Regular working hours, call
- Bob Richards or Greg Bergsten 780-4965697
After Hours:
Place on hold until next working day , as per alarm response instructions
105
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
106/112
Functions of the Dispatcher
Task 7: Communicate with Pumpwells Field staff andcontractors daily and document who is at what site,performing what tasks, so false alarms can be accountedfor
When an employee or contractor calls to informdispatch that an entry into a site will take place:
- Use the Employee/Contractor Working In PumpwellStations documentation for in the SCADA DispatchForms Binder (Section 1) to document the following:
Date In/Out
Time In/Out
Pumpstation # Employee/Contractor Name
Work Being Performed
- Remind the employee / contractor to call when theyare leaving the site
- Inform other dispatchers of the person on site, so
modifications in alarm response can be made 106
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
107/112
Functions of the Dispatcher
107
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
108/112
Functions of the Dispatcher
Task 7: Communicate with Pumpwells Field staff andcontractors daily and document who is at what site,performing what tasks, so false alarms can be accountedfor
When a sheet is full:
- Place it in the Completed Employee/Contractor InStations Forms section (section 3) of the SCADADispatch Forms Binder
- Start a new sheet
If new sheets are needed for printing:
- The template is located in:
N:\Operations\Customer Services\HIGH PRIORITYREPAIRS\Call Management Centre\SCADA TrackingForms\Employee or Contractor Working In PumpwellStations Tracking Form.pdf
108
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
109/112
Functions of the Dispatcher
Task 8: Document problems with the SCADA system functionality The SCADA Concerns that are to be documented on this form are:
- If an alarm has a point message not configured
- If an alarm has a strange response message in the Dispatch Info
- If an alarm has missing information either in the Dispatch Info or the Site
Info- If there are problems with acknowledging an alarm
- If there are error messages generated
- If there are extra features that would work well, or make the job easier
109
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
110/112
Functions of the Dispatcher
Task 8: Document problems with the SCADA system functionality
110
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
111/112
Functions of the Dispatcher
Task 8: Document problems with the SCADA system functionality When a sheet is full:
- Place it in the Completed SCADA Concern Forms section (section 4) of theSCADA Dispatch Forms Binder
- Start a new sheet
- On a monthly basis, give these sheets to Aimee Pulido or Tony Liao forreview
If new sheets are needed for printing:
- The template is located in:
N:\Operations\Customer Services\HIGH PRIORITY REPAIRS\CallManagement Centre\SCADA Tracking Forms\SCADA Concerns TrackingForm.pdf
111
7/26/2019 SCADA System Call Center Training Manual-Revised Sept 2013
112/112
Functions of the Dispatcher
Task 9: Communicating problems with the functionality of the callcenters SCADA computer hardware or software When a problem arises with respect to the functionality of the call centers
SCADA computer (hardware/software) or the communications network:
- During normal working hours, contact Aimee Pulido or Tony Liao forsupport
- Outside regular working hours, contact the Standby Technologist