8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 1/19
A9 Check and ensure that the received materials are new and unused.Schedule "G"
Sec. 4.1
A13
Each cabinet shall be provided with removable lifting rings. 6.3.9 Cabinet
doors shall be full-height. All doors shall be dust-tight and reinforced
against buckling. The maximum door width shall be 900 mm (36 inches)
unless otherwise specified in the Purchase Order.
34-SAMSS-820,
Sec. 6.3.8
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUI
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
TRAVEL TIMSAUDI ARAMCO USE ONLY
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
PLANT NO.EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID.
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
PASS
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Schedule Q
Attachment lV
Sec.7.1
FAIL
A. General Material and Storage Requirements
N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
A2
Purchase Order and Instrument specification sheet criteria shall be
confirmed and compared with instrument stainless steel tags / labels
and nameplates, and shipment checked for damage, prior to acceptance
of the shipment
Schedule Q
Attachment lVSec.7.1
A1
Incoming material shall be visually inspected for damage and
conformance to all applicable inspection releases with Material Test
Report (MTR).
A4
Storage Environment: All control cabinet equipment and wiring shall be
designed for continuous operation at 50°C, and relative humidity 80%
maximum (non-condensing) and 20% minimum.Commentary Note: The
temperature of 50°C allows for a 35°C room ambient plus a 15°C rise
within the cabinet.
34-SAMSS-820,
Sec. 5.2
A3Ensure that Equipment Storage and Protection is as per Manufacturer’s
Recommendation
Schedule Q
Attachment lV
Sec.5
A5 The cabinet shall be a NEMA Type 1 per NEMA 250 and NEMA ICS634-SAMSS-820,
Sec. 6.3.1
A8
Louvers installed at the top of cabinets shall be protected by a screen or
shroud to prevent debris from falling into the cabinet. Filters shall slide
into preformed grooves or be fastened with removable, corrosion
resistant hardware.
34-SAMSS-820,
Sec. 6.3.4
A6 Cabinets requiring heat dissipation shall be convection-ventilated.34-SAMSS-820,
Sec. 6.3.2
A7
Convection-ventilated cabinets shall be provided with readily accessible,
removable filter screens inserted behind slotted louver inlets. Louvers
and filters installed within cabinet doors are acceptable.
34-SAMSS-820,
Sec. 6.3.3
A10
A11Where two or more front sections are required for a Control Panel, the
interior shall be an open-frame construction.
34-SAMSS-820,
Sec. 6.3.6
Fans may be used within Cabinets or Power supplies to assist in heat
removal and cabinet ventilation provided that they are installed in a
redundant configuration with fan failure or over-temperature detectioncircuitry including alarm status indication and contacts for external alarm
annunciation.
34-SAMSS-820,
Sec. 6.3.5
A12Cabinet support bracing shall not restrict maintenance access to chassis,
modules or components.
34-SAMSS-820,
Sec. 6.3.7
Page 1 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 2/19
B12
Each cabinet, front and rear, shall be identified with a nameplate located
above each door or pair of doors. The nameplate, as minimum, shall be
the cabinet name/number as given in the cabinet drawings.
B13
Unless otherwise specified in the Purchase Order, each cabinet shall be
provided with the following spare capacity to allow for future system
modifications: a) 20% installed spare terminal blocks of each terminal
block type used. Spare terminal blocks are to be distributed to match the
layout of required spare I/O modules, field termination assemblies,
relays, etc. b) 10% spare relay bases (if any).
34-SAMSS-820,
Sec. 6.6.1
34-SAMSS-820,
Sec. 6.5.6
34-SAMSS-820,
Sec. 6.5.3
B11Nameplates shall be made from laminated plastic, white-black-white
(information engraved into the black core) with white surface, dull finish.
34-SAMSS-820,
Sec. 6.5.5
B1
B2
The marshalling cabinets, from the front surface to the surface of rear
terminal blocks, shall not be more than 46 cm (18 inches) deep to
provide for safe access. The preferred design is to divide a 76 cm (30
inch) deep cabinet into 38 cm (15 inch) sections with front and rear
access.
34-SAMSS-820,
Sec. 6.3.10
Cabinet doors shall be full-height. All doors shall be dust-tight andreinforced against buckling. The maximum door width shall be 900 mm
(36 inches) unless otherwise specified in the Purchase Order.
34-SAMSS-820,
Sec. 6.3.9
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
B3 All doors must be capable of swinging at least 90-degrees open at the
installed location.
34-SAMSS-820,
Sec. 6.3.11
B10
PASS FAIL
B. Fabrication Requirements
N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
B4
Rotating Equipment cabinets or other cabinets, which require diagnostic
equipment to be connected for long periods of time, shall have hand
removable doors unless otherwise stated in the Purchase Order.
34-SAMSS-820,
Sec. 6.3.12
B7
B6Interior cabinet color shall be white (preferred) or of a light color such as
light gray, off-white, etc.
34-SAMSS-820,
Sec. 6.4.2
B5
Cabinet Finish: The exterior and interior cabinet finish shall be the
Cabinet Fabricator's standard finish, unless otherwise specified in the
Purchase Order. A minimum of primer, undercoat and finishing coat of
enamel or lacquer is required. Electrostatic applied powder paint
coatings which are then baked (such as polyester urethane) is
acceptable.
34-SAMSS-820,
Sec. 6.4.1
Nameplates: Nameplates for cabinets and panels letter height and
spacing shall follow ISA RP60.6, Appendix A and C, unless otherwise
specified in the purchase order. (Attachments 3,4, 5,& 6)
34-SAMSS-820,
Sec. 6.5.1
Instruments and accessories mounted inside the cabinet shall be
identified with a nameplate showing the tag number. Individual rack
modules are not required to have permanent nameplates attached.
34-SAMSS-820,
Sec. 6.5.4
B8
Where possible, nameplate abbreviations shall be avoided. Where
abbreviations are used, they shall be consistent with facility practices.
ISA RP60.6 (Appendix B) shall be used to keep abbreviations consistentwhere facility practice is not established.(12 pages of this are available
from inspection dept. on request)
34-SAMSS-820,Sec. 6.5.2
B9
Control panel pushbuttons, switches, indicating lights and other through-
mounted devices shall be identified with the service description on the
front. The rear of the above devices shall be identified with the device tag
number. The nameplates shall be permanently attached. Adhesives are
allowed for indoor panels.
Page 2 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 3/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
34-SAMSS-820,
Sec. 8.2.8
C10Wire Installation: Splices are not permitted in wiring. When wiring must
be extended, connections shall be made via terminal blocks.
34-SAMSS-820,
Sec. 8.3.1
C8Power supply outputs shall be individually fused or protected by a circuit
breaker.
C9
Power Supply terminal block distribution wiring shall not be daisy-
chained using wires or crimp connectors. Jumper bars or preformed
jumper combs designed for the specific terminal blocks being used are
acceptable methods of distributing power supply wiring.
C7Power supplies shall be identical whenever possible for
interchangeability and spare part requirements.
34-SAMSS-820,
Sec. 8.2.6
C6Supplies to DC instrument loads: Voltage stabilization shall be provided
to maintain the output voltage within tolerable limits of the loads served.
34-SAMSS-820,
Sec. 8.2.5
C5
Where multiple on-line DC power supplies are connected to a single
power bus, diode auctioning shall be used to facilitate load balancing in
the event of a single power supply failure. Where multiple DC power
supplies are an integral part of a manufacturer's standard product, the
manufacturer's standard method of load sharing shall apply.
34-SAMSS-820,
Sec. 8.2.4
C4Equipment shall operate at the supply voltages shown in Table 1.
(Attachment -1)
34-SAMSS-820,
Sec. 8.2.3
C3
Power wiring for field instruments, all input and output points, two-wire
analog transmission loops, field switch contacts, etc., shall be
individually fused and provided with a means of disconnecting the power
without disturbing terminated wiring (e.g., knife-switch-type terminal
blocks). Exceptions: 1) Wiring connected to I/O modules or interfaces
containing individual current-limiting circuit protection does not require
fuses. 2) Low Voltage wiring connected directly to I/O. (See paragraph8.7) Commentary Note: Fuse application, location, and Ampacity ratings
must be properly sized and coordinated, taking into account the
maximum expected load at the maximum operating temperature of the
cabinet (50°C).
34-SAMSS-820,
Sec. 8.2.2
C2
Power Supply: All process instruments shall be powered from
instrument circuit power distribution panels. Each distribution panel shall
be dedicated to a single voltage level. These panels shall not provide
power to non-instrumentation circuits. Distribution panels shall be
furnished with a minimum of 20% spare circuit breakers.
34-SAMSS-820,
Sec. 8.2.1
C1
Electrical- Area Classificati on: Ensure that the Indoor cabinets built
in accordance with this specification are to be installed in rooms, within
a general purpose, non classified area per ANSI/NFPA 70 National
Electrical Code (NEC), Article 500. Instrument and control wire and cable
systems shall be designed and installed in accordance with ANSI/NFPA70 National Electrical Code (NEC) unless otherwise supplemented by
this specification..
34-SAMSS-820,
Sec. 8.1
B15
The Cabinet Fabricator shall supply a minimum of two (2) spare fuses or
10% (whichever is greater) for each type of general power and
termination strip fuses used within each cabinet. This requirement
includes supplying spares for fuses integral to installed electronics (i.e.,
flow computers, field termination assemblies, etc.).
34-SAMSS-820,
Sec. 6.6.3
B14
These additional requirements apply to Control Panels only: a) Sufficient
spare panel width shall be provided for at least 20% additional future
instruments. b) No spare cut-outs shall be provided unless specified. c)
Spare panel space shall be left accessible for future installation of
instruments.
34-SAMSS-820,Sec. 6.6.2
C. Electrical Area Classification / Power supply Requirements
34-SAMSS-820,
Sec. 8.2.7
Page 3 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 4/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
D1
Annunciator Wi ring: Each annunciator shall have a horn relay wired to
terminals for connection to the remote horn system, unless otherwise
specified in the Purchase Order.
34-SAMSS-820,
Sec. 8.6.1
C21
Terminal strip spacing shall allow ample room for plastic wire ducts and
permit training and lacing of cables, and fanning of individual wires to
termination points. Each terminal strip shall be labeled above or below
with the terminal strip number, as shown on wiring diagrams. Terminals
for similar (AC or DC) current service shall be grouped together and
physically separated from terminals for different service by means of
dividers, separate mounting rails or separate enclosures.
34-SAMSS-820,
Sec. 8.8.2
C20
When screw-type terminals are provided on instruments and other
electrical devices, solder less crimp/compression connectors shall be
used for connecting stranded copper conductors. Insulated ring lugs,
locking-fork or flanged- fork connectors, specifically designed to hold the
connector on the terminal in the event of loosening of the terminal screw,shall be used on all such connections.
34-SAMSS-820,
Sec. 8.5.3
C19
Exposed electrical connections with voltages greater than nominal 48
volts AC/DC, mounted on cabinet doors, shall have exposed
wiring/terminations shrouded by transparent, removable, insulating
plastic covers (or equivalent).
34-SAMSS-820,
Sec. 8.5.2
C18
The following are exempted from the above rule: Wiring for mill volt,micro amp, pulse and frequency signals under 1 Volt such as
thermocouples, resistance temperature detectors (RTD), vibration
elements, analyzer elements, thermistor elements and transmitters with
pulse outputs shall be directly connected to the I/O unless otherwise
specified in the Purchase Order.
34-SAMSS-820,
Sec. 8.7
C17
Wiring Methods : Cabinets containing electronic equipment with field
inputs/outputs (I/O) (e.g., field termination assemblies, I/O modules, etc.)
shall
1) have the I/O device pre-wired to intermediate terminal strips within the
same cabinet shipping section, or;
2) to intermediate terminals within the same building by the use of
manufactured multi-conductor cable and plug connectors .
34-SAMSS-820,
Sec. 8.5.1
C16
Electronic signal wire shall be stranded copper, minimum size 20 AWG,
300 V for single conductors or a minimum 22 AWG, 300 V for multicore
cable. Wire insulation shall be cross-linked polyethylene, PVC, or PTFE,
with a minimum temperature rating of 75°C. Special electronic signal
wires shall be as described in the Purchase Order.
34-SAMSS-820,
Sec. 8.4.2
C15
Wire Specifications: General 120 VAC power wiring shall be minimum
14 AWG stranded, copper, PVC-insulated or cross-linked polyethylene.Wire insulation shall be rated for 600 volts, 75°C, minimum.
34-SAMSS-820,
Sec. 8.4.1
C14
Wiring that is required to be segregated shall cross at right angles and
the spacing shall be maintained as close as practicable to that shown in
Table 2.(Attachment 2)
34-SAMSS-820,
Sec. 8.3.3.2
C13
Separate plastic ducts are preferable for all Signal Categories that
require separation for organization and noise reduction. Signal
Categories with upper values of zero separation may be mixed in a
plastic duct. Signal Categories shall not be mixed within any single
multicore cable. Example: 24 VDC digital and 24 VDC 4-20 mA may be
run in the same plastic duct, but not within a single multicore cable.
34-SAMSS-820,
Sec. 8.3.3.1
C12
Segregation of parallel wiring internal to cabinets shall adhere to the
following Table 2. (Attachment-2) All dimensions are shown in
millimeters.
34-SAMSS-820,
Sec. 8.3.3
C11Twist-on wire nut connectors shall not be used for making any electrical
instrumentation terminations.
34-SAMSS-820,
Sec. 8.3.2
D. Annunciator / Terminal Strip Requirements
Page 4 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 5/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
D17
Wires terminated on these terminal blocks shall not have the bare ends
coated with or dipped in solder ("tinned"). However, termination of wiring
which has individual strands of the copper conductor tinned during
manufacture (typical of shield drain wires or for corrosion protection) is
acceptable.
34-SAMSS-820,
Sec. 8.9.6
D16The disconnect levers for fused terminals and knife-switch terminals
shall be hinged.
34-SAMSS-820,
Sec. 8.9.5
D15
A fused terminal block shall have a blown-fuse indicator. This may be a
Light Emitting Diode (LED), visual sight indication through a port, or
equivalent
34-SAMSS-820,
Sec. 8.9.4
D14
Terminals shall be made of fire retardant, halogen free, high strength
material such as polyamide or equivalent in accordance with UL 94, V0.
Brittle materials such as melamine shall not be used.
34-SAMSS-820,
Sec. 8.9.3
D13
All terminal blocks shall be channel (rail)-mounted, strip-type, with a
tubular box clamp connector and compression bar or yoke for wire
termination. As a minimum, the thickness of the terminals shall be 5 mm
or higher.
34-SAMSS-820,
Sec. 8.9.2
D11No more than two bare wires shall be connected to each side of a single
terminal block.
34-SAMSS-820,
Sec. 8.9.1
D10
Terminals for various types of general wiring (AC or DC), annunciator
points and signal wiring shall be separately grouped and separated by
dividers.
34-SAMSS-820,
Sec. 8.8.6
D9
Wiring for a given instrument loop shall be terminated on adjacent
terminals on the terminal strip in order to organize and group all loop
wiring. Exception: For digital 48 VDC or 125 VDC wiring, terminations
may be grouped with all the (+) positive wires adjacent to each other and
all of the (-) negative wires adjacent.
34-SAMSS-820,
Sec. 8.8.5
D7
Where special cases of mixed ESD / Non-ESD signals occur in one
cabinet or control panel (e.g., Solid State / Relay Control Cabinets or
Control Panels with ESD pushbuttons ), terminal strips for Emergency
Shutdown (ESD) wiring shall be completely separate from all other wiring
including power, control and instrumentation.
34-SAMSS-820,
Sec. 8.8.4
D6
Terminal Strips: Standoffs for terminal strips are preferred to bring the
terminal blocks forward to be flush with the top of the plastic wire duct.
This wiring method assures that all wires can be accessed without
interference from other wires as the wire duct is filled.
34-SAMSS-820,
Sec. 8.8.3
D4Terminal Strips: The termination method shall be channel (rail)-
mounted terminal blocks.
34-SAMSS-820,
Sec. 8.8.1
D3
Wiring for Mill volt, Micro amp, Pulse and Frequency Signals Wiring for
mill volt, micro amp, pulse and frequency signals under 1 Volt such as
thermocouples, resistance temperature detectors (RTD), vibration
elements, analyzer elements, thermistor elements and transmitters with
pulse outputs shall be directly connected to the I/O unless otherwise
specified in the Purchase Order.
34-SAMSS-820,
Sec. 8.7
D2 Annunciator (s) shall have a lamp/horn test, acknowledge and reset
button unless otherwise specified in the Purchase Order.
34-SAMSS-820,
Sec. 8.6.2
D5
Terminal strip spacing shall allow ample room for plastic wire ducts and
permit training and lacing of cables, and fanning of individual wires to
termination points. Each terminal strip shall be labeled above or below
with the terminal strip number, as shown on wiring diagrams. Terminals
for similar (AC or DC) current service shall be grouped together and
physically separated from terminals for different service by means ofdividers, separate mounting rails or separate enclosures.
34-SAMSS-820,
Sec. 8.8.2
Page 5 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 6/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
E. Wire Tagging / Terminal coding and Relay Requirements
D3134-SAMSS-820,
Sec. 8.11
D 29Vendor-installed cables shall be supported and provided with a strain-
relief mechanism for cable connectors.
23-SAMSS-010
Sec, 7.4.1
and 34-SAMSS-
820, Sec. 8.10.8
D28Wiring shall not be threaded through undressed access holes. Glands or
protective grommets shall be used.
34-SAMSS-820,
Sec. 8.10.7
D27 Loomed wiring shall not be installed near sharp-edged surfaces.34-SAMSS-820,
Sec. 8.10.6
D26
Where space limitations preclude the use of plastic wire ducts, wiring
shall be neatly loomed and secured with plastic spiral wrapping or tie-wraps and anchors. Wiring between movable parts such as doors shall
be installed in flexible hoses..
34-SAMSS-820,Sec. 8.10.5
D25Plastic wire ducts shall be mounted using screws. Double-sided tape is
unacceptable.
34-SAMSS-820,
Sec. 8.10.4
D23In addition to the above, the maximum plastic wire duct fill (including
spare capacity) shall not exceed 75% of its depth.
34-SAMSS-820,
Sec. 810.3
D22The maximum conduit/plastic wire duct fill (including spare capacity)
shall not exceed the heat requirements of NFPA 70 Section 300 17. ..
34-SAMSS-820,
Sec. 8.10.2
D21
Wire Ducts and Looms : Plastic wire ducts with removable covers shall
be installed in cabinets as required to provide a means of routing and
organizing wiring. A minimum of 50 mm shall be maintained between the
duct and terminal strips. Wire markers shall be completely presented
34-SAMSS-820,
Sec. 8.10.1
D20
Multiple-deck terminal blocks shall not be used. Exception: When
provided as an integral part of manufactured electronic equipment,
multiple-deck terminal blocks are allowed, but never for direct termination
of field cabling.
34-SAMSS-820,
Sec. 8.9.9
D19
Terminal blocks with a narrow, recessed screw entrance which require a
special screwdriver or wrench may be used only if the insulation material
is as per the requirements cited above.(D2- 34-SAMSS-820, Sec 8.9.2)
34-SAMSS-820,
Sec. 8.9.8
D18
Direct termination of the bare wire end is acceptable. The terminal block
must be suited for the wire size. The use of crimp-on ferrules shall followthe manufacturer's guidelines and the following:
a) Only one conductor shall be terminated per ferrule. (The use of
ferrules to daisy chain is not acceptable).
b) Only one ferrule shall be connected to each side of a single terminal
block.
c) Ferrules shall be provided with plastic insulating collars.
34-SAMSS-820,
Sec. 8.9.7
D30 Wire ducts for ESD wiring shall not contain any other types of wiring.
34-SAMSS-820,
Sec. 8.10.9
Page 6 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 7/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
E11
Numerical terminal identification and coding shall be assigned
sequentially (in ascending order, from top to bottom or left to right). Each
vertical row and group of rows shall be labeled separately.
34-SAMSS-820,
Sec. 8.13.3
E10
In addition to above,( 8.13.1), each row of Power supply and bus
terminals shall be marked with voltage type and level. (e.g., +24 VDC, or
120 VAC, etc.)
34-SAMSS-820,
Sec. 8.13.2
E9
Terminal Coding: Each row of terminals shall be clearly identified with
an alphanumeric label. Each row of ESD terminals shall additionally be
marked to show ESD service.
34-SAMSS-820,
Sec. 8.13.1
E8
Per NEC 310-11 all conductors and cables shall be marked to indicate
the following information: 1) Maximum rated voltage for which the
conductor was listed, 2) The letter designators for type of wire or cable,
3) Manufacture's name or trade mark, 4) The AWG size or circular mil
area. Exception: If the wire insulation is not marked then a permanent
placard must be attached to the inside cabinet door showing the aboveinformation and location of where the wiring is used.
34-SAMSS-820,
Sec. 8.12.7
E7
Spare pairs/triads in multi-pair/triad cables shall be labeled "SPARE" in
addition to the destination and source terminal numbers. All spares are
to be terminated.
34-SAMSS-820,
Sec. 8.12.6
E6
Wire tags shall be installed and oriented such that the tags are easily
read. (Upside down or covering of tag information by plastic duct covers
is not acceptable).
34-SAMSS-820,
Sec. 8.12.5
E5 Wire tags shall not be handwritten.34-SAMSS-820,
Sec. 8.12.4
E4
Wire tag information shall be permanently marked in block alpha numeric
or typed on tubular; heat shrinkable, slip-on sleeves. Wrap-around, snap-
on or self-adhesive markers shall not be used. Where shrink fit cable
markers cannot be installed over pre-made cable and connectors, a
suitable tie-wrap or equivalent type permanent marker shall be used.
Exceptions: 1) Alternate wire tagging schemes, which conform to
established local practice, may be used for extensions to existing
facilities with the prior approval of the operating facility Manager.2)
Plastic sleeves that are specifically designed to fit on a specific wire
gauge and come with pre-printed alpha/numeric inserts (such as
Grafoplast Trasp System) may be used for wire tags with prior approval
of the operating facility Manager.
34-SAMSS-820,
Sec. 8.12.3
E3
Identification shall be in accordance with designations shown on
instrument loop diagrams (ILDs). Where wires terminate on instrument ordevice terminals, the instrument tag number and terminal designation (+)
or (-) (if applicable) will be used in lieu of terminal strip identification.
34-SAMSS-820,Sec. 8.12.2
E2
I/O and interconnecting wiring shall be tagged at each end with two
identification tags (or the two may be combined into one tag with
sufficient separation between wire numbers). The first tag (closest to the
end of the wire) shall identify the terminal number to which the wire is
physically connected. The second tag shall identify the terminal number
to which the opposite end of the wire is connected. Commentary Note:
Where jumpers are installed between terminal blocks in the same row or
column and are clearly visible, wire tagging is not necessary.
34-SAMSS-820,
Sec. 8.12.2
E1
Wire Tagging : Cables with connector plugs shall be tagged at each end.
Each cable tag shall have two labels. The first label (closest to the plugconnector) shall identify the device and socket to which the plug is to be
connected. The second label shall identify the device and socket to
which the opposite end of the cable is connected.
34-SAMSS-820,
Sec. 8.12.1
Page 7 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 8/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
F8 Individual circuit breakers shall be provided for each power supply unit. 34-SAMSS-820,
Sec. 8.17.3
F7Fuses and circuit breakers shall be readily accessible for maintenance
with sufficient clearance from obstructions.
34-SAMSS-820,
Sec. 8.17.2
F6
Circuit Breakers and Fuses: Tandem type (dual) circuit breakers in a
single molded case shall not be used, as the failure of one breaker
requires complete replacement of the assembly.
34-SAMSS-820,
Sec. 8.17.1
F5
Lamp Test Facilities For all control panel and console indicating lights,a lamp test button shall be installed per panel or console section.
Exceptions: LED or other lamps integral to a manufacturer's electronic
instrumentation do not require the lamp test button. Power status-
indicating lights that are normally "on" where it is not desirable to "cross-
feed" lamp test power from an alternative source (Such as UPS power
status).
34-SAMSS-820,
Sec. 8.16
F4
Push Buttons and Lights: Push buttons and lights shall be industrial
quality. Push buttons shall have protective mechanisms to prevent
accidental activation as required by the detailed design specification.
Long-life type derated lamps or LED cluster lamps shall be used. The
color of the pushbuttons or lights shall be green for "ON"/"OPEN" and
red for "OFF/"CLOSE" positions. Only screw terminals shall be provided
on push buttons. Exception: Existing facilities that currently deviate from
the above light color specification may use other conventions in order to
keep the lighting philosophy consistent within the facility.
34-SAMSS-820,
Sec. 8.15
34-SAMSS-820,
Sec. 8.14.7
F3Relay configuration and pertinent operating information shall be
imprinted on the case.
34-SAMSS-820,
Sec. 8.14.8
F. Push Buttons , Light s , Grounding- Requirements
F1Coil voltage shall be as specified in the Purchase Order. Pull-in voltage
shall be 80% or less of nominal voltage.
34-SAMSS-820,
Sec. 8.14.6
E16Integral socket modules for mounting 8 and 11 pin octal base relays onto
a DIN rail are acceptable.
34-SAMSS-820,
Sec. 8.14.5
34-SAMSS-820,Sec. 8.14.3
E15
The mounting socket shall be provided with a plastic label, color black-
white (relay number engraved into the black core with white surface, dull
finish). The relay number shall be shown as presented in the detailed
cabinet drawings.
34-SAMSS-820,
Sec. 8.14.4
E14
The 8-pin contact arrangement is double-pole, double-throw (DPDT),
wired in accordance with the following list. Looking at the base of the
relay with key cam straight-down and the cam between 1 and 8; theconnections are clockwise numbered 1 through 8.a) Coil is between
connectors 2 and 7 b) Common connector 1 is normally closed to
connector 4 and normally open to connector 3 c) Common connector 8 is
normally closed to connector 5 and normally open to connector 6
E13
The 11-pin contact arrangement is three-pole, double-throw (3PDT),
wired in accordance with the following list. Looking at the base of the
relay with the key cam straight-down and the cam between 1 and 11; the
connections are clockwise numbered 1 through 11. a) Coil is between
connectors 2 and 10 b) Common connector 1 is normally closed to
connector 4 and normally open to connector 3 c) Common connector 6 is
normally closed to connector 5 and normally open to connector 7 d)
Common connector 11 is normally closed to connector 8 and normally
open to connector 9
34-SAMSS-820,
Sec. 8.14.2
E12
Relays: Relays shall be of the dust-tight, 11-pin or 8-pin plug-in type.
Exception: Relays provided as an integral part of manufactured
electronic equipment installed within cabinets may use that
manufacturer's standard offering.
34-SAMSS-820,
Sec. 8.14.1
F2 When inductive loads are switched, suppression diodes shall be used
Page 8 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 9/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
F22
Incandescent lamps shall have a guard to help protect the lamp from
accidental breakage. Fluorescent lamps shall have clear plastic sleeve
guards to help contain broken glass in case of an accident.
34-SAMSS-820,
Sec. 8.20.3
F21
If specified, cabinet lights shall be 120 Volt, 60-watt incandescent lamps,
size IEC, type E27 or ES (Edison Medium Screw Base) fitting or 15-watt
minimum industrial grade, fluorescent lighting fixture (s) oriented in such
a manner that the majority of the interior portions of the cabinet are
illuminated.
34-SAMSS-820,
Sec. 8.20.2
F20
Lighting, Convenience and Power Distribution Receptacle Outlets:
Cabinet lights shall be installed where practical and necessary, as
specified in the Purchase Order.
34-SAMSS-820,
Sec. 8.20.1:
F19
AC power receptacle outlets shall be grounded using ground wire
terminated on the receptacle grounding terminal. (e.g., A receptacle
utilizing the faceplate as a ground path is not permitted.)
34-SAMSS-820,
Sec. 8.19.7
F18
"INSTRUMENT CIRCUIT GROUND" for connecting cable and wire
shields and DC Common. Interconnections between shield consolidation
points and the bus bar shall be minimum 14 AWG copper wire, green or
green with yellow tracer insulation. This bus bar shall be electrically
insulated from the cabinet structure.
34-SAMSS-820,
Sec. 8.19.6
F17
The ground bus bars shall be labeled and wired as follows:
"AC SAFETY GROUND" for all exposed metal surfaces of cabinets,
racks, chassis GND connections, etc. Individual wiring interconnections
shall be minimum 14 AWG copper wire, green or green with yellow tracer
insulation. This bus shall be directly bolted to the cabinet without the use
of insulators.
34-SAMSS-820,
Sec. 8.19.6
F16
A No. 2 AWG screw-type compression lug shall be provided on either
end of each ground bar for interconnection with other ground buses or to
the Instrument System Ground Node (ISGN).
34-SAMSS-820,
Sec. 8.19.5
F15The preferred location of the ground bus bars is at the bottom of the
cabinet.
34-SAMSS-820,
Sec. 8.19.4
F14
All ground buses shall be made of a solid copper measuring the following
nominal dimensions 6mm x 35mm x (y length), suitably drilled and
tapped for screw terminals and wire lugs, or fitted with screw-type
compression lugs.
34-SAMSS-820,
Sec. 8.19.3
F13Separate, electrically isolated grounding bars shall be provided, as
required.
34-SAMSS-820,
Sec. 8.19.2
F12
Grounding: Both safety ground and instrumentation circuit ground must
conform to NEC, Article 250. Grounding system recommendations andrequirements provided by manufacturers of instrumentation and control
systems (e.g., Distributed Control Systems) shall be followed.
34-SAMSS-820,Sec. 8.19.1
F11
Cable shields must have a continuous path to ground. Acceptable
methods of consolidating shields are as follows: a) Special grounding
terminals in intimate contact with an electrically isolated DIN Rail. b)
Terminal Block jumper bars designed for the selected terminal blocks. c)
Preformed jumper combs designed for the selected terminal blocks. d)
Electrically isolated bus bars running parallel to terminal blocks.
34-SAMSS-820,
Sec. 8.18.3
F9Marshalling Cabinet Shielding: Cable shields must have a single,continuous path to ground. Ground loops and floating shields shall be
avoided. Shields shall be consolidated and ultimately connected to the
Instrument Circuit Ground Bar as detailed in paragraph 8.19.6.
34-SAMSS-820,
Sec. 8.18.1
F10Shield drain wires shall not be daisy-chained using bare wires or crimp
connectors to the ground connection.
34-SAMSS-820,
Sec. 8.18.2
Page 9 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 10/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
G6
In outdoor non-industrial areas, enclosures shall be:
(a) NEMA Type 3R, 3 or 4; or
(b) IEC 60529 Type IP34 or better.
34-SAMSS-821
Sec, 5.1.4
G5
Enclosures shall meet the requirements of this Section. In outdoor plant
and other industrial areas located in severe corrosive environments as
defined in Paragraph 4.2, enclosures shall be:
(a) NEMA Type 4X (except galvanized and/or painted or coated carbon
steel sheet metal enclosures are not permitted); or
(b) NEMA Type 3 or 4, manufactured of copper free cast aluminum (0.4
of 1% copper maximum), or plastic (including fiberglass); or
(c) IEC 60529 Type IP65 or better, manufactured of stainless steel (Type
304 or better), copper free cast aluminum, or plastic (including
fiberglass). Commentary Note 5.1.3: In outdoor plant and other industrial
areas located in severe corrosive 5.1.3 supersedes Paragraphs 5.1.1
and 5.1.2
34-SAMSS-821
Sec, 5.1.3
G4
Enclosures shall meet the requirements of this Section.
In outdoor plant areas, outside the perimeter of process units, and
other industrial areas, enclosures shall be:
(a) NEMA Type 3 or 4; or
(b) IEC 60529 Type IP54 or better.
34-SAMSS-821
Sec, 5.1.2
G3
Enclosures shall meet the requirements of this Section.
In outdoor plant areas, within the perimeter of process units,
enclosures shall be:
(a) NEMA 250/NEMA ICS 6 Type 4; or
(b) NEMA Type 3 manufactured copper free cast aluminum (0.4 of 1%maximum), or plastic (including fiberglass); or
(c) IEC 60529 Type IP65 or better.
34-SAMSS-821
Sec, 5.1.1
G2
Portions of Equipment that are mounted externally on the Outdoor
Cabinet shall operate continuously under the conditions sporadic water
spray such as from rain.
34-SAMSS-821
Sec, 4.1.2
G1
Equipment Mounted Internal to the Outdoor Cabinet shall operate
continuously under the following humidity conditions. Relative Humidity:
Minimum 5% Maximum 95% (non-condensing)
34-SAMSS-821
Sec, 4.1.1
34-SAMSS-820,Sec. 9
F26Multiple AC power receptacle outlets shall be wired so that any
receptacle can be removed without affecting the operation of the others.
34-SAMSS-820,
Sec. 8.20.7
F25 A switch in the cabinet shall control each lamp where the lamp is
installed. Automatic door switches for lamps are allowed.
34-SAMSS-820,
Sec. 8.20.6
F24
thermal/magnetic circuit breakers which shall be powered from a Saudi
Aramco-furnished AC distribution panel, independent of the UPS power
34-SAMSS-820,
Sec. 8.20.5
F23
Convenience outlets shall be duplex-type and rated at 120 VAC, 15 amp.
They shall be installed where practical and necessary, as specified in the
Purchase Order.
34-SAMSS-820,
Sec. 8.20.4
G Outdoor Requirements , PLC, Cabinets etc
34-SAMSS-820,
Sec. 8.21F27
Communication System The Purchase Order shall specify the
communication system required for each cabinet installation.
F28
Graphic Display Requirements A graphic or semigraphic display shall be
provided as and when specified in the Purchase Order. Graphics and
colors shall be as specified in the Purchase Order.
Page 10 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 11/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
H25 A switch in the cabinet shall control each lamp where the lamp is
installed. Automatic door switches for lamps are allowed.
34-SAMSS-820,
Sec. 8.20.6
H24
Interior lamps and convenience outlets shall be wired to separate
thermal/magnetic circuit breakers which shall be powered from a Saudi
Aramco-furnished AC distribution panel, independent of the UPS power
supply.
34-SAMSS-820,
Sec. 8.20.5
H23
Convenience outlets shall be duplex-type and rated at 120 VAC, 15 amp.
They shall be installed where practical and necessary, as specified in the
Purchase Order.
34-SAMSS-820,
Sec. 8.20.4
H22
Incandescent lamps shall have a guard to help protect the lamp from
accidental breakage. Fluorescent lamps shall have clear plastic sleeve
guards to help contain broken glass in case of an accident.
34-SAMSS-820,Sec. 8.20.3
H21
If specified, cabinet lights shall be 120 Volt, 60-watt incandescent lamps,
size IEC, type E27 or ES (Edison Medium Screw Base) fitting or 15-watt
minimum industrial grade, fluorescent lighting fixture (s) oriented in such
a manner that the majority of the interior portions of the cabinet are
illuminated.
34-SAMSS-820,
Sec. 8.20.2
H20
Lighting, Convenience and Power Distribution Receptacle Outlets:
Cabinet lights shall be installed where practical and necessary, as
specified in the Purchase Order.
34-SAMSS-820,
Sec. 8.20.1:
H19
AC power receptacle outlets shall be grounded using ground wire
terminated on the receptacle grounding terminal. (e.g., A receptacle
utilizing the faceplate as a ground path is not permitted.)
34-SAMSS-820,
Sec. 8.19.7
H18
"INSTRUMENT CIRCUIT GROUND" for connecting cable and wire
shields and DC Common. Interconnections between shield consolidation
points and the bus bar shall be minimum 14 AWG copper wire, green or
green with yellow tracer insulation. This bus bar shall be electrically
insulated from the cabinet structure.
34-SAMSS-820,
Sec. 8.19.6
G15Nameplates shall be attached to the cabinets using stainless steel
screws.
34-SAMSS-821
Sec, 6
G14Solenoid Valves: Solenoid Valves shall be equipped with Viton Soft
Goods.
34-SAMSS-821
Sec, 5.2.6
G13Cabinet Lights and Convenience Outlets: Cabinet Lights and
Convenience Outlets shall be provided.
34-SAMSS-821
Sec, 5.2.5
G12
Pushbuttons and Lights: Pushbuttons, pilot lights and switches shall be
heavy duty, oil tight, and shall meet the area classification of the installed
location.
34-SAMSS-821
Sec, 5.2.4
G11 Relays shall be hermetically sealed.34-SAMSS-821
Sec, 5.2.3
G10Elevated outdoor control cabinets shall normally have conduit entry from
the bottom.
34-SAMSS-821
Sec, 5.2.2.2.
G9
Conduit Entry: The entry (on non-explosion proof cabinets) shall have a
removable blank gland plate as specified in the Purchase Order for
Buyer's conduit entry.
34-SAMSS-821
Sec, 5.2.3
G8
The classification of the area in which the panel will be used, shall be
specified in the Purchase Order. The panel, materials, and equipment
required for the electrical wiring and installation within the control panel
shall be suitable for use in the specified area.
34-SAMSS-821
Sec, 5.2.1
G7
Enclosures that are rated (a) NEMA Type 3, 4 or 4X, or (b) IEC 60529
Type IP54, or better, shall have Type 300 Series stainless steel
hardware. Exception: Aluminum enclosures may have aluminum or
aluminum alloy hinges.
34-SAMSS-821
Sec, 5.1.5
Page 11 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 12/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
K7
Enclosures shall meet the requirements of this Section.
In outdoor plant areas, outside the perimeter of process units, and
other industrial areas, enclosures shall be:
(a) NEMA Type 3 or 4; or
(b) IEC 60529 Type IP54 or better.
34-SAMSS-821
Sec, 5.1.2
K6
Enclosures shall meet the requirements of this Section.
In outdoor plant areas, within the perimeter of process units,
enclosures shall be:
(a) NEMA 250/NEMA ICS 6 Type 4; or(b) NEMA Type 3 manufactured copper free cast aluminum (0.4 of 1%
maximum), or plastic (including fiberglass); or
(c) IEC 60529 Type IP65 or better.
34-SAMSS-821Sec, 5.1.1
K5
Offshore and Near shore Environment Equipment which is not enclosed
or hermetically sealed, but is situated offshore or near shore, shall be
protected against corrosion and operational failure due to wind-borne sea
water spray and the accumulation of wetted salt (NaCl). Near shore is
defined as any outdoor, onshore location within one kilometer from the
shoreline of the Arabian Gulf; all of the Ras Tanura Refinery and
Terminal; and within three kilometers from the shoreline of the Red Sea.
34-SAMSS-821
Sec, 4.2
K4
34-SAMSS-821
Sec, 4.1.2
K334-SAMSS-821
Sec, 4.1.2
K2
Portions of Equipment that are mounted externally on the Outdoor
Cabinet shall operate continuously under the conditions sporadic water
spray such as from rain.
34-SAMSS-821
Sec, 4.1.2
K1
Equipment Mounted Internal to the Outdoor Cabinet shall operate
continuously under the following humidity conditions. Relative Humidity:
Minimum 5% Maximum 95% (non-condensing)
34-SAMSS-821
Sec, 4.1.1
K Outdoor Requirements , PLC, Cabinets etc
H28
Graphic Display Requirements A graphic or semigraphic display shall be
provided as and when specified in the Purchase Order. Graphics and
colors shall be as specified in the Purchase Order.
34-SAMSS-820,
Sec. 9
H27Communication System The Purchase Order shall specify the
communication system required for each cabinet installation.
34-SAMSS-820,
Sec. 8.21
H26Multiple AC power receptacle outlets shall be wired so that any
receptacle can be removed without affecting the operation of the others.
34-SAMSS-820,
Sec. 8.20.7
Page 12 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 13/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
5. 23-SAMSS-010 Distributed Control Systems, 31 October, 1999.
K18Nameplates shall be attached to the cabinets using stainless steel
screws.
34-SAMSS-821
Sec, 6
1. Schedule G -- Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), July 1993
4. NEC 2002- National Electric Code 2002
3. SAES-J-902, Electrical Systems for Instrumentation, 31 July 2004
K17Solenoid Valves Solenoid Valves shall be equipped with Viton Soft
Goods.
34-SAMSS-821
Sec, 5.2.6
K16Cabinet Lights and Convenience Outlets: Cabinet Lights and
Convenience Outlets shall be provided.
34-SAMSS-821
Sec, 5.2.5
K15
Pushbuttons and Lights: Pushbuttons, pilot lights and switches shall be
heavy duty, oil tight, and shall meet the area classification of the installed
location.
34-SAMSS-821
Sec, 5.2.4
K14 Relays shall be hermetically sealed.34-SAMSS-821
Sec, 5.2.3
K13Elevated outdoor control cabinets shall normally have conduit entry from
the bottom.
34-SAMSS-821
Sec, 5.2.2.2.
K12
Conduit Entry: The entry (on non-explosion proof cabinets) shall have a
removable blank gland plate as specified in the Purchase Order for
Buyer's conduit entry.
34-SAMSS-821
Sec, 5.2.3
K11
The classification of the area in which the panel will be used, shall be
specified in the Purchase Order. The panel, materials, and equipment
required for the electrical wiring and installation within the control panel
shall be suitable for use in the specified area.
34-SAMSS-821
Sec, 5.2.1
K10
Enclosures that are rated (a) NEMA Type 3, 4 or 4X, or (b) IEC 60529Type IP54, or better, shall have Type 300 Series stainless steel
hardware. Exception: Aluminum enclosures may have aluminum or
aluminum alloy hinges.
34-SAMSS-821
Sec, 5.1.5
K9
In outdoor non-industrial areas, enclosures shall be:
(a) NEMA Type 3R, 3 or 4; or
(b) IEC 60529 Type IP34 or better.
34-SAMSS-821
Sec, 5.1.4
K8
Enclosures shall meet the requirements of this Section. In outdoor plant
and other industrial areas located in severe corrosive environments asdefined in Paragraph 4.2, enclosures shall be:
(a) NEMA Type 4X (except galvanized and/or painted or coated carbon
steel sheet metal enclosures are not permitted); or
(b) NEMA Type 3 or 4, manufactured of copper free cast aluminum (0.4
of 1% copper maximum), or plastic (including fiberglass); or
(c) IEC 60529 Type IP65 or better, manufactured of stainless steel (Type
304 or better), copper free cast aluminum, or plastic (including
fiberglass). Commentary Note 5.1.3: In outdoor plant and other industrial
areas located in severe corrosive 5.1.3 supersedes Paragraphs 5.1.1
and 5.1.2
34-SAMSS-821
Sec, 5.1.3
REFERENCE DOCUMENTS:
6. 34-SAMSS-820- Instrument Control Cabinets - Indoor 29, May 2002
REMARKS:
2. Schedule Q -- Quality Requirements (Pro Forma Contract), November 2003
7.34-SAMSS-821- Instrument Control Cabinets - Outdoor 29, May 2002
ATTACHMENTS:
Page 13 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 14/19
CONTRACTOR / SUBCONTRACTOR
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER
PASS FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE
QC Record Reviewed Work Veri fied
Name, Sign and Date:
Quality Record Approved:Name, Organization,
Initials and Date:
T&I Witnessed
QC Supervisor Proponent and Others
Name, Initials and Date:
Performed Inspection
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listin
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
Work VerifiedT&I Wi tnessed QC Record Reviewed
QC Inspector PID Representative
indicates compliance with appropriate standards or performance in a specified manner.
Construction Representative*
Name, Initials and Date:
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
Attachment -3 ISA RP 60.6 -Name plate, letter size and space guide - Appendix A 3 , 1984
NOTES:
Attachment -4 ISA RP 60.6 Appendix A - Wire terminal identification A-4
Attachment -5 ISA RP 60.6 Appendix C - Character Heights
Attachment 6 Appendix A- Name plates( usable area) A-2
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
Attachment -2 Segregation of parallel wiring internal to cabinets shall adhere to table 2, 34-SAMSS-820, Sec. 8.3.3
Contractor / Third-Party
QC Record Reviewed
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
Work Verified
Saudi Aramco
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
PMT RepresentativeT&I WitnessedWork is Complete and Ready for Inspection:
Name, Initials and Date:
*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FA
Attachment -1 Equipment shall operate at supply voltages shown below 34-SAMSS-820- Table -1
Attachment-7 Air -borne dust concentration and contaminant levels 34-SAMSS-821 Sec 4.3
Work / Rework May Proceed
Name, Initials and Date:
Page 14 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 15/19
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
Attachment -2 Segregation of paral lel wiring internal to cabinets shall adhere to table 2, 34
Attachment -1 Equipment shal l operate at supply vol tages shown below 34-SAMSS-820- Ta
Att achment 2 --Segregat ion of paral lel wi ring in ternal to cabinets
Page 15 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 16/19
Attachment 3: Appendix A- Name plate Letter Size and spacing guide A-3
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 16 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 17/19
Attachment -4 ISA RP 60.6 Appendix A - Wire terminal identi ficat ion A-4
General-Instrument Racks and Panel Fabrication SAIC-J-6028 1-Oct-05 INST
Attachment -5 ISA RP 60.6 Appendix C - Character Heights
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 17 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 18/19
1-Oct-05 INST
Attachment 6 Appendix A- Name plates( usable area) A-2
General-Instrument Racks and Panel Fabrication SAIC-J-6028
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 18 of 19
8/12/2019 SAIC-J-6028 - Rev 0
http://slidepdf.com/reader/full/saic-j-6028-rev-0 19/19
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
1-Oct-05 INST
Attachment-7 Air -borne dust concentration and contaminant levels 34-SAMSS-821 Sec 4.3
General-Instrument Racks and Panel Fabrication SAIC-J-6028
Page 19 of 19