8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 1/12
Schedule Q
Attachment llI
Sec 1.2
A7
Traceability - Instrumentation materials shall be traceable from the
manufacturer and supplier through delivery, storage, fabrication,
erection, installation, repair, modification and use.
Schedule "Q"
Attachment lV
Sec. 3.3
A8
Verify that the contractor or it's Saudi Aramco approved third party
inspector performed the quality activities at the supplier and sub-supplier
locations as required by the inspection level assigned for the materials
and equipment identified in SAER-1972 Inspection Requirements.
A6QC Before Installation - Instrumentation materials shall conform to allapplicable requirements, standards, and specifications prior to release to
be used as part of the work.
Schedule "Q" Attachment lV
Sec 7.1
A5
Free of Damage - Instrumentation materials shall be free of damage. All
Incoming material shall be visually inspected for damage and
conformance to all applicable inspection releases with Material Test
Report (MTR).
Schedule "Q"
Attachment lV
Sec 7.1
Schedule "G"
Sec. 4.1
A4
As Designed - Instrumentation materials shall be in accordance with the
Saudi Aramco-approved project-specific design drawings, diagrams,
schedules, lists, databases, and associated documents. See
Attachments 1, 2 and 3
Schedule "G"
Sec. 4.1
A3 New and Unused - Instrumentation materials shall be new and unused.
A2
Material identification Procedure reviewed and shall be implemented forall materials, parts and components, including partially fabricated
assemblies.( Based on project specs, which define the length of tube and
part number in the drawings)
Schedule "Q"
Attachment lV
Sec. 3.2
A1 Review Quality Documentation for Material Receiving.Schedule Q,
Att, IV, Sec. 3.1.
FAIL N/A RE-INSP DAITEM
No. ACCEPTANCE CRITERIA REFERENCE PASS
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
PLANT NO.EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
TRAVEL TIM
SAUDI ARAMCO USE ONLYSCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUI
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
A Document Rev iew and Certi ficati on
A9
Vendor to provide usual warranty from the packaged unit manufacturer.
The warranty to include all materials, workmanship and performance
characteristics in accordance with his standard terms and conditions.
Components supplied by the packaged unit vendor will include, but are
not limited to field instruments, controls, valves, safety systems, pre-wired field interfaces, plant control system interfaces and electrical
systems.
34-SAMSS-831
Sec. 1
A10
Inspection: The items manufactured to this specification (34-SAMSS-
831) are subject to verification by the Buyer's Inspection Representative
per Saudi Aramco Inspection Requirement Form 175-340200, attached
to the Purchase Order.
34-SAMSS-831,
Sec. 10.2
A11
The Contractor to produce certification that the equipment shall operate
continuously without any degradation and should comply with a minimum
-maximum range of 10°C(50°F) to 35°C(95°F) in indoor Air conditioned
or a range of 0°C (32°F) to 55°C (32°F) in outdoor sheltered and to a
range of 0°C (32°F) to 65°C (149°F) ( in outdoor unsheltered conditions)
34-SAMSS-831,
Sec. 5.1
Page 1 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 2/12
Schedule Q,
Att IV, Sec. 7.1.
General Requirements
ITEM
No. ACCEPTANCE CRITERIA REFERENCE
A16
Acceptance Cri ter ia: Vendor's records shall be available to verify that
all items have been subjected to the following tests prior to the final
acceptance test:
Functional Tests: Buyer will witness a complete functional test of the
control system to verify satisfactory operation of the instrumentation
during the performance test of the packaged unit.
All pneumatic instrumentation shall pass :
a) Leakage test of all piping and tubing
b) Functional test of all pneumatic instruments
c) Functional test of all pneumatic control loops
34-SAMSS-831,
Sec. 10.3.1
PASS FAIL N/A RE-INSP DA
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
B1
All materials shall be suitable for the specified service, and the Vendor
shall obtain a written approval from the Buyer for all selected materials in
severe process services. All wetted parts in sour service shall conform to
NACE MR0175 - 2002.
34-SAMSS-831
Sec. 9
B2
C3Cast iron shall not be used for hydrocarbon service, or for any flange-
mounted instrument.
34-SAMSS-831,
Sec. 9.1
A12
Vendor to provide certification that the equipment complies the following:Humidity Indoor humidity design basis shall be 20% to 80% relative
humidity. Outdoor design basis shall be 5% to 95% relative humidity (non
condensing).
34-SAMSS-831,
Sec. 5.2
A13
Contractor to provide certification that the equipment meets the severe
dust and contaminants requirements detailed below:
5.3.1 Onshore Environment Usual airborne dust concentration is 1
mg/m³. During sandstorms, dust concentrations may reach 500 mg/m³.
Particle size distribution is as follows: • 95% of all particles are less than
20 micrometers • 50% of all particles are less than 1.5 micrometers
Elements present in dust include compounds of calcium, silicon,
magnesium, aluminum, potassium, chlorides and sodium. When wetted
(high humidity conditions) these compounds function as electrolytes and
can result in severe corrosion. Other pollutants present in the
atmosphere under the most extreme conditions are:H2S 20 ppm (vol/vol)
Hydrocarbon 150 ppm (vol/vol)
SO2 10 ppm (vol/vol)
CO 100 ppm (vol/vol)
NOx 5 ppm (vol/vol)
O3 1 ppm (vol/vol)
34-SAMSS-831,
Sec. 5.3.1
A14 Storage, Handli ng, and Preservation
A15The manufacturer's storage, handling and preservation instructions to be
followed.
Schedule Q,
Att, IV, Sec 5.
B
C. Material Requirements for instruments, piping and tubing/ Fittings
The Vendor shall submit a list of all selected instrument manufacturers,
instrument model numbers and specification sheets for approval by theBuyer.
34-SAMSS-831
Sec. 9.1
C2
All process-connected instruments shall be cast or forged steel, stainless
steel or a suitable corrosion resistant alloy equal to or better than the
ASTM specifications.
34-SAMSS-831,
Sec. 9.1
C1
Purchase Order and Instrument specification sheet criteria shall be
confirmed and compared with instrument stainless steel tags / labels
and nameplates, and shipment checked for damage, prior to acceptance
of the shipment
Page 2 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 3/12
ITEM
No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DA
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
C8
Instrument Piping and Tubing Process connections up to and
including the first block valve (the root valve) shall comply with 01-
SAMSS-017, Table -1 (See Attachment -1).
34-SAMSS-831,
Sec. 9.1
SAES-J-902,
Sec. 7.3
C6
C5
Enclosures for instruments in outdoor plant areas shall be NEMA Type 4
in accordance with NEMA ICS 6 and NEMA 250 or IEC 60529 Type IP
65.
SAES-J-902,
Sec. 7.1
The field junction box, in a Class I, Zone 2 location and in non-
hazardous areas, shall be a single door NEMA Type 4X or IEC 60529
Type IP 66 box. The box construction shall meet the following
requirements: 7.2.1 Type 316 stainless steel body, door and hardware.
7.2.2 Continuously welded seams, finished smooth.
7.2.3 Continuous stainless steel hinge with removable pin.
7.2.4 Stainless steel captive clamps.
7.2.5 Data/Print pocket on inside of door.
7.2.6 External mounting brackets.7.2.7 Collar studs for mounting inside panel.
7.2.8 Ground stud for terminating A/C safety ground wire.
7.2.9 Painted steel panel (back-pan); in 'severe corrosive environments'
a stainless-steel panel shall be used.
SAES-J-902,
Sec. 7.2
C4 Instrument enclosures shall be steel or copper free aluminum, suitablefor the environmental conditions.
34-SAMSS-831,Sec. 9.1
C7
Instrument enclosures and junction boxes having an internal volume
exceeding 2,000 cm³ shall be provided with Type 300 Series stainless
steel breather and drain fittings, or a combination breather and drain
fitting.
C9
Piping and tubing materials downstream of the first block valve shall
comply with check list items ( C8 to C16) / paragraphs :
All threaded fittings shall be forged carbon steel or stainless steel per ASME B16.11, and be Class 3000 for systems rated up to and including
ANSI Class 900, and Class 6000 for systems rated ANSI Class 1500. All
threaded connections shall be tapered per ASME B1.20.1.
34-SAMSS-831,Sec. 9.1
C10
The minimum size of auxiliary piping and tubing for mechanical
equipment shall be 1/2-inch NPS with the exception of air compressor
packages which shall be 3/8-inch NPS.
01-SAMSS-017,
Sec. 5.1.3
C11
All piping, tubing and valves shall be adequately supported and fastened
in a manner which facilitates replacement, and prevents vibration. Refer
to Drawing AB-036521 for valve bracing.(Attachment-2)
01-SAMSS-017,
Sec. 5.1.4
C12
Unions are not permitted in pressurized lines carrying flammable or toxic
fluids unless they are required for removal or assembly of the equipment
and cannot otherwise be substituted by flanges..
01-SAMSS-017,
Sec. 5.1.8
C13
All piping systems shall be provided with vent valves at high points and
drain valves at low points. Horizontal runs in pressure piping shall slopegradually towards drain points. The minimum slope of drain lines shall be
1:50.
01-SAMSS-017,Sec. 5.1.9
C14
A block valve, 3/4-inch NPS minimum, shall be installed in each
instrument take-off connection and shall be located as close as feasible
to the line, vessel, or mechanical equipment. Thermocouples and
thermometers are excluded from the 3/4-inch NPS minimum
requirement.
01-SAMSS-017,
Sec. 5.1.10
Page 3 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 4/12
ITEM
No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DA
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
C17
Fittings:316 stainless steel compression fittings shall be either Crawford
Swagelok, Parker Hannifin A-Lok, Parker Hannifin Corp. CPI or Hoke
Gyrolock. Any proposal to use fittings other than those listed above shall
be reviewed by Supervisor, Instrumentation Unit, Process
Instrumentation Division, P&CSD.
34-SAMSS-831,
Sec. 9.2.2.2
C23
Manifolds: Manifolds for flow meter service shall have a rating Class
6000 at 95°C, or Class 4000 at 260°C. Manifolds shall have 316
stainless steel body, bonnet, stem and seat, and teflon packing.
Connections shall be ½ inch NPT female at oval flange surface.
34-SAMSS-831,
Sec. 9.3.3
C15
Pipe may be bent where necessary to achieve the desired configuration.Bending of the pipe shall conform to the following: Pipe bends shall have
surfaces free of cracks and buckles. Flattening of the cross section of
bends shall not exceed 8 percent of the nominal pipe diameter. Bending
procedures and required heat treatment shall be in accordance with
ASME B31.3.
01-SAMSS-017,
Sec. 5.1.11 and
Sec 6.2
C16
Tubing: Stainless steel tubing shall be seamless, annealed, minimum
wall thickness 1.24 mm, per ASTM A269, Grade TP-316L. Instrument air
tubing shall be ¼ inch, 3/8 inch, or ½ inch OD stainless steel. Wall
thickness shall be 0.75 mm or larger.
34-SAMSS-831,
Sec. 9.2.2.1
C18
Flexible hoses shall be stainless steel armored, with integral connectors.
The hose length shall not exceed 600 mm. The hose lining shall be
suitable for the process and operating conditions.
34-SAMSS-831,
Sec. 9.2.2.2
C19
Valves and Manifolds : Forged carbon steel valves shall conform to
ASTM A105, Grade 2. Forged stainless steel valves shall comply with
ASTM A182, Grade F316.
34-SAMSS-831,
Sec. 9.3
C20
Gate Valves (Excluding th e Root Valve): Gate valves shall be forged
steel, with ratings as required, but at least Class 800 at 454°C. Gate
valves shall have 316 stainless steel trim and stem, solid wedge,
reduced bore, renewable stellited seat, and a hand wheel. Furthermore,
they shall be suitable for repacking under pressure. Gate valves shall
have internal screw rising stems for services below 175°C. An outside
screw and yoke design is required for services at and above 175°C.
34-SAMSS-831,
Sec. 9.3.1
C21Needle Valves: Needle valves shall be bar stock steel, with ratings as
required, but at least Class 3000.
34-SAMSS-831,
Sec. 9.3.2
C22Needle valves shall have 316 stainless steel trim, integral seat, and
welded bonnet. Needle valves shall have internal screw rising stems.
34-SAMSS-831,
Sec. 9.3.1
D. Instrumentation Requirements
D1
General power wiring, for circuits up to 600 V to ground and a
maximum current rating of 15 A, shall be stranded copper; flame
retardant PVC, XLPE or XLPO insulated; size 14 AWG; have an
insulation minimum temperature rating of 90°C and shall comply with
NFPA 70 or IEC 60502-1.
34-SAMSS-831,
Sec. 7.1.1
D2
Instrumentation signal wiring shall be stranded copper; flame retardant
PVC, XLPE or XLPO insulated and shall have an insulation minimum
temperature rating of 90°C. The minimum wire size shall be:
• 16 AWG single twisted pair/triad from instruments to the nearest skid
mounted junction box. Cables carrying analog signals shall also be
shielded.
• 18 AWG for multi-twisted pair/triad cables from junction boxes to other
junction boxes or marshalling cabinets.
• 22 AWG for multi-conductor cable inter-cabinet wiring.
34-SAMSS-831,
Sec. 7.1.1
D3
Specialty cables (e.g., High Temperature, communication, network
cables) shall be certified by any of the agencies listed in Appendix
2.(Attachment 3)
34-SAMSS-831,
Sec. 7.1.1
Page 4 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 5/12
ITEM
No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DA
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
34-SAMSS-831,
Sec. 7.1.4
D12
An identification tag or nameplate of 316 stainless steel shall be
attached securely to the equipment with SS or Monel fasteners. The tag
shall be marked with raised alphanumeric or die stamped with the
following information: • Saudi Aramco Purchase Order number •
Manufacturer • Part/Model Number • Serial Number • Date of
Manufacture • Mark/Tag Number The tag or nameplate shall be located
so that the information can be read after installation of the equipment or
components.
34-SAMSS-831,
Sec. 7.2.4
D4 Pair/triads of multi-twisted pair/triad control cables shall be numbered. 34-SAMSS-831,Sec. 7.1.1
D5
Except for thermocouple wiring, black and white are the preferred colors
for pair conductors and black, white and red for triad conductors unless
otherwise specified in the purchase order. Blue color insulation or jacket
shall only be used for intrinsically safe installation.
34-SAMSS-831,
Sec. 7.1.1
D6Splices are not permitted in wiring. When wiring must be extended,
connections shall be made via terminal blocks.
34-SAMSS-831,
Sec. 7.1.1
D7
Terminals Wiring connections shall be made to channel (rail) mounted
terminal blocks. These terminal blocks shall have tubular box clamp
connector and compression bar or yoke for wire termination. More than
two connections per terminal point are not allowed. If open screw type
terminals are used, terminal lugs shall be ring tongue, compression type,
with insulated sleeves.
34-SAMSS-831,
Sec. 7.1.2
D8 Fused terminals shall be used for power distribution, alarm and shutdownsystems.
34-SAMSS-831,Sec. 7.1.2
D9 All packaged unit wiring, intended for interface with plant wiring, shall be
terminated in junction boxes.
34-SAMSS-831,
Sec. 7.1.3
D11
Provision for grounding the skid structure shall be made at diagonally
opposite corners. The skid structure shall be designed to accommodate
two-hole compression connector, for (2/0 AWG) copper conductor, at
each corner.
34-SAMSS-831,
Sec. 7.1.5
Wire Tagging Interconnecting wires between skid mounted components
and between skid mounted instruments and the skid termination panel
shall be tagged. Each tag shall identify the device to which the opposite
end of the wire is connected. Heat shrink or ferrule type wire tags with
permanently embossed identification markings shall be used.
D10
E. Local Control and Alarm Display Cabinet Requirements
E1Finish: The cabinet finish shall be per manufacturer's standard unless
stated otherwise. The color of the coating shall be as specified in the
34-SAMSS-831,
Sec. 7.2.1
34-SAMSS-913,
Sec. 10.3.2
E3
Drawings: Vendor shall provide wiring diagrams or wiring list showing
termination strips and all electronic interconnections, with names and
equipment/terminal identification. All spare terminals, terminal strips and
wires shall appear on the vendor wiring drawings or list.
34-SAMSS-831,Sec. 7.2.3
E2Design: Vortex coolers, heat pumps or air conditioners may be used to
reduce internal cabinet temperature with the prior approval of Supervisor,
34-SAMSS-831,
Sec. 7.2.2
E4
Indication Li ghts, Pushbuttons and Switches Indication lights,
pushbuttons and switches shall be of the oil tight, heavy duty type. Long-
life type dated lamps or LED cluster lamps shall be used. Indication
lights and pushbuttons shall have the following color: Red - abnormal,
trip, shutdown, off, closed, emergency Yellow - (pre-) alarm Green -
normal, on, open, permissive start
Page 5 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 6/12
ITEM
No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DA
SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
34-SAMSS-831,
Sec. 7.2.5E5
Controllers and Instrumentation: The vendor shall ensure that allequipment, including digital controllers and displays are suitable for
operation in the ambient conditions specified in Specification sheet.
Controllers and displays shall be installed in locations where vibration is
negligible. Digital displays shall be screened from direct sunlight.
Page 6 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 7/12
At tachment 1 Sheet 1 of 2 -- Material selection and Join ing Methods -01-SAMSS-017
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 7 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 8/12
SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
At tachment 1 - Sheet 2 of 2 - Mater ial select ion and Joining Methods -01-SAMSS-017
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
Page 8 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 9/12
Attachment 2 -- Valve bracings std DWG AB-036521 sht 1 rev 08
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 9 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 10/12
Attachment 5 -- Temperature sensors in thermowells , STD. Dwg. AB-036019 sht 1 rev 21
Skid for Non- Hazardous Locat ions -Mater ial Receiving SAIC-J-6020 1-Oct-05 INST
SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 10 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 11/12
SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
1-Oct-05 INST
At tach ment 4 -- Elect rical Equipment Temperatu re c lass NEC table 500.8(B)
Attachment 6 -- Liquid level guage glasses, instrument piping details l ib. Dwg DB950046
Skid for Non- Hazardous Locat ions -Material Receiving SAIC-J-6020
Page 11 of 12
8/12/2019 SAIC-J-6020-Rev 0
http://slidepdf.com/reader/full/saic-j-6020-rev-0 12/12
1-Oct-05 INST
Attachment 7 -- Straight pipe requirements for Orifice , Venturi and f low nozzles Std. Dwg A
Skid for Non- Hazardous Locat ions -Material Receiving SAIC-J-6020
SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)
SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER
Page 12 of 12