12
RPS Station Solutions for the North American Solar Market 2015/2016

RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

RPS StationSolutions for theNorth American Solar Market

2015/2016

Page 2: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

Power, controland green solutions

Page 3: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

3

RPS Station

Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that is designed to minimize field installation time and maximize system uptime over a longer lifetime. The RPS Station is equipped with Bonfiglioli’s modular RPS TL-UL inverter series, optimized for the needs of the North American PV market.

FlexibilityThe RPS Station is available in a wide range of configurations, electrical power ratings and design options to meet even the most demanding requirements. Two different designs – concrete and metal full shelters – ensure to always have the best solution in place for each specific application. Optional design features include cold-weather package, air-conditioning, motor tracker power supply and project-specific communication devices, all in compliance with NEC 2014.

Reliability and PerformanceAll RPS Station solutions from Bonfiglioli are factory- assembled as a completely weatherproof NEMA 3R-rated structure, safely protecting the equipment from the elements. The standard system includes a temperature-controlled cooling system and air filters.The oil-filled transformer is an ANSI standard pad-mount style and is supplied completely filled with environmentally friendly FR3 oil.

A wide range of features are available including:• Standard power ratings from 1.0 to 3.15 MWac• Primary voltages from 12.47 kV to 34.5 kV• MV-transformer with Wye or delta configuration• Self-powered load center with possibility to

connect customer loads• Communication and fiber optic enclosure for

connection to plant SCADA• Direct mounting to pre-poured concrete slab base

or pier mounted• PE certified design and construction

Proven Technology and LongevityWith over 25 years of engineering excellence in power conversion technology and a strong presence in global PV markets, Bonfiglioli has the required footprint, experience and infrastructure to develop and deliver complete, cost-effective PV station solutions.

In addition, the overall business composition of Bonfiglioli ensures financial stability to support installations long-term, and to provide and support an uptime guarantee and wide range of extended warranty options.

Contact us or visit BonfiglioliUSA.com/PV for more information.

Page 4: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that
Page 5: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

5

RPS Station (concrete and metal shelter solutions)

Design Features • Fully integrated enclosed ‘walk in’ solution

available in both concrete and metal for effective protection of equipment and service personnel from the elements

• Bottom cable entry glands for DC connections• Insulation to prevent excessive heat build-up from

solar radiation• Utility power distribution equipment, lighting

receptacles, cooling fans and optional customer loads or external tracker motors

• Pad-mount oil filled step-up transformer• Power cables from inverters to power transformer

fully pre-installed• Inverter cooling duct system, air inlet louver and

outlet louver• Temperature-controlled cooling fans

Design Standards• NEC & OSHA compliant working clearance

including 2 personnel access doors with panic hardware

• Designed according to the UBC code for wind, seismic, snow and floor loading

• Design to guarantee best performances in every climatic conditions

• Direct mounting to pre-poured concrete slab base or pier mounted

• PE certified design and construction, including local state building approval (where required)

Design Options• Wide range of power sizes to accommodate every

project requirement• Several MV connection voltages and winding

configuration available• Transformer internal gauges: liquid level,

thermometer, pressure (optional external mounting)

• Optional customer loads powered by inverter output

• Communication enclosure for the connection to plant SCADA equipment, meteo stations and plant controller

Additional customized features and options are available. Please contact us today to learn more.

Equipment layout 2.0 MW RPS Station (typical)

Page 6: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that
Page 7: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

7

The flexibility of the Bonfiglioli RPS Station allows utility-scale solar power plants to be easily designed while providing a very cost effective solution for a wide range of applications.

Built to perform and last even in the harshest of conditions, from high elevation mountains to hot, sandy deserts, the RPS Station is field tested and industry proven.

Whether it is 1 MW or 100 MW+ plant sizes, the RPS Station can be tailored to project specific requirements while delivering the same world renowned quality and bankability.

With the recent installation of more than 200 MW in the USA, the RPS station is proving to be a go-to solution for turn-key utility scale solutions in North America.

RPS Station

UtilityNetwork

MV Cables in “Loop-feed”configuration

MV Substation/POI

A typical arrangement of the Bonfiglioli RPS Station for a utility scale solar plant.

Page 8: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that
Page 9: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

9

RPS Station North America (selected versions) 2000 2500 2700 3150(metal version only)

Inverter(s) -2 x RPS TL-UL 1125

Multi-MPPT2 x RPS TL-UL 1350

Multi-MPPT2 x RPS TL-UL 1350

Multi-MPPT2 x RPS TL-UL 1575

Multi-MPPT

Input Ratings (DC)

Maximum input current A 3500 4200 4200 4900

Maximum input voltage V 1000

MPPT range V 610…850

Number of MPP trackers - 10 12 12 14

Number of DC inputs - 20 24 24 28

Output Ratings (AC)

Inverter maximum active power (factory setting) kW 2000 2500 2700 3150

Inverter maximum apparent power kVA 2390 2868 2868 3346

Power factor range - controllable 0.8i…0.8c (nominal >0.99)

AC voltage kV 6.6…34.5

Nominal frequency Hz 60

Max output current (at 34.5 kV) A 40 48 48 56

Current harmonic distortion % < 3

Transformer type - Pad-mount oil filled transformer (KNAN)

Connection phases - 3

Auxiliary power

Aux voltage - 120/240 V internal

Standby power consumption (typ) W < 600 < 600 < 600 < 600

Operating power consumption (typ) W < 5000 < 5500 < 5500 < 6000

Efficiency

Inverter maximum efficiency % 98.6 (prelim)

Inverter European Weighted efficiency % 98.4 (prelim)

Inverter CEC Weighted Efficiency % 98.0 (prelim)

Transformer no-load losses (typ) kW 24,1 19,8 19,8 25,7

Transformer load losses (typ) kW 2,6 3,7 3,7 3,9

Mechanical details

Dimensions (WxHxD)metal (m) / concrete (c)

m8.4 x 3.4 x 3.25 (m)

10.5 x 3.55 x 3.65 (c)9 x 3.4 x 3.25 (m)

10.5 x 3.55 x 3.65 (c)9 x 3.4 x 3.25 (m)

10.5 x 3.55 x 3.65 (c)9.6 x 3.4 x 3.25 (m)

ft27' x 11' x 10'6" (m)

34' x 11'5" x 11'10" (c)29' x 11' x 10'6" (m)

34' x 11'5" x 11'10" (c)29' x 11' x 10'6" (m)

34' x 11'5" x 11'10" (c) 31' x 11' x 10'6" (m)

Weight (approx.)metal (m) / concrete (c)

kg21500 (m) 44000 (c)

23000 (m) 46000 (c)

23000 (m) 46000 (c)

24500 (m)

lb48000 (m) 97000 (c)

51000 (m) 102000 (c)

51000 (m) 102000 (c)

54000 (m)

Environmental data

Ambient operating temperature range °C -4°F … 122°F ('-20°C ... +50°C)

Rel. humidity % up to 95 (not condensing)

Max. altitude ft 13123 ft (derating above 3280 ft)

Fresh air consumption (inverter)m3/h 15000 18000 18000 21000

cfm 8830 10596 10596 12362

Protection and monitoring

Input-side disconnection - DC circuit breaker on each inverter module

Output-side disconnection - Load-break switch & PRCLF

Array Grounding Config. - Floating

Array Ground Fault Protection - Impedance Monitoring

Grid Protection - Anti-Islanding / Adjustable voltage and frequency settings according to IEEE1547

Surge Protection - UL1449, Class II on DC Input and AC Inverter Output

Features

DC connection - 5/8" bolts on copper bar

AC connection - Integral deadfront loop feed 600 A bushings

Communication protocol - Modbus TCP over Ethernet

Standards & certifications

Standards - UL1741 / CSA107.1 / IEEE1547 (inverters), NEC2014

Protection Class - Nema 3R

Supported Power Management Functions - LVRT, Power Factor Control, Grid Fault Support, Power / Frequency Control and Ramp Rate

Estimated data, final values may change without notice based on final design of system and selection of optional features.Other sizes and options available upon request.

Page 10: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

HeadquartersITALY • Lippo di Calderara, Bologna

BranchesAUSTRALIA • SydneyBRAZIL • São PauloCANADA • TorontoCHINA • ShanghaiFRANCE • ParisGERMANY • NeussGERMANY • KrefeldINDIA • Chennai, Tamil NaduINDIA • Mannur, Tamil NaduINDIA • Bangalore, KarnatakaITALY • MilanoITALY • RoveretoNEW ZEALAND • AucklandSOUTH AFRICA • JohannesburgSINGAPORE • SingaporeSPAIN • BarcelonaTURKEY • IzmirUNITED KINGDOM • RedditchUNITED KINGDOM • WarringtonUSA • Hebron, KentuckyVIETNAM • Ho Chi Minh

ResellersAFRICA • Algeria, Egypt, Kenya, Morocco, South Africa, Tunisia

ASIA • Bahrain, China, Emirates, Japan, Jordan, Hong Kong, India, Indonesia, Iran, Israel, Kuwait, Malaysia, Oman, Pakistan, Philippine, Qatar, Saudi Arabia, Singapore, South Korea, Syria, Thailand, Taiwan, Vietnam

EUROPE • Albania, Austria, Belgium, Bielorussia, Bulgaria, Cyprus, Croatia, Czech Republic, Denmark, Estonia, Finland, France, Holland, Hungary, Germany, Great Britain, Greece, Ireland, Italy, Lettonia, Lituania, Luxemburg, Malta, Montenegro, Norway, Poland, Portugal, Romania, Russia, Slovakian Republic, Serbia, Slovenia, Spain, Sweden, Switzerland, Turkey, Ucraina

LATIN AMERICA • Argentine, Bolivia, Brasil, Chile, Colombia, Costa Rica, Ecuador, Guatemala, Honduras, Mexico, Peru, Uruguay, Venezuela

NORTH AMERICA • Canada, United States

OCEANIA • Australia, New Zealand

Production facilitiesITALY • Calderara di Reno, BolognaCasting and gearcutting plantAssembly HDP, HDO, 300 seriesITALY • Vignola, ModenaGearmotor assembly plant Precision gearbox manufacturing and assembly plantITALY • ForlìPlanetary gearboxes manufacturing and assembly plantITALY • Rovereto, TrentoBrushless motor and precision gearboxes productionGERMANY • KrefeldInverter plantSLOVAKIA • Považská BystricaLarge gearboxes manufacturing plantINDIA • Chennai, Tamil NaduPlanetary gearbox manufacturing and assembly plantINDIA • Mannur, Tamil NaduGearmotors manufacturing and assembly plantINDIA • Bangalore, KarnatakaPhotovoltaic Inverter assemblyVIETNAM • Ho Chi MinhElectric motor plantCHINA • ShanghaiPhotovoltaic Inverter assemblyBRAZIL • São PauloPlanetary gearboxes manufacturing and assembly plantUSA • Hebron, KentuckyPlanetary gearboxes manufacturing and assembly plant

Bonfiglioli Worldwide

USA

Canada

IndiaSpain

United Kingdom

Vietnam

Italy

Brazil

France

Singapore

Slovakia

South Africa

Germany

Australia

Turkey

New Zealand

China

Page 11: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

wind

photovoltaicmobile

industrial

As one of the world’s leading providers of clean energy solutions, with utility-scale PV installations currently in place around the world, Bonfiglioli has the innovative know-how and technical capacity to bring commercial and utility-scale PV power plants to life.For the PV sector, Bonfiglioli designs and manufactures highly efficient and innovative electronic control systems for photovoltaic fields and has the expertise to manage every aspect of photovoltaic energy generation from MPPT tracking to utility interconnection.

Bonfiglioli also designs and manufactures a complete range of gearmotors, drive systems and planetary gearboxes for industrial processes, automation, mobile machinery and wind energy applications.

Over 50 years of engineering excellence makes Bonfiglioli a preferred supplier and partner for market leaders around the world.For more information, visit Bonfiglioliusa.com

Bonfiglioli Solutions

Page 12: RPS Station - Bonfigliolifairvisitingreport.bonfiglioli.com/media/filer... · RPS Station Bonfiglioli’s RPS Station is a fully integrated photovoltaic power conversion system that

VE_CAT_RSTA_USA_ENG_R03_0

Bonfiglioli has been designing and developing innovative and reliable power transmission and control solutionsfor industry, mobile machinery and renewable energyapplications since 1956.

Bonfiglioli USA3541 Hargrave Drive, Hebron, Kentucky 41048tel. (+1) 859 334 3333 - fax (+1) 859 334 8888www.bonfiglioliusa.com© Bonfiglioli Vectron GmbH, 2015. All rights reserved.