Product Data Sheet 00813-0100-4004, Rev HA April 2010 www.rosemount.com Rosemount 8800D HART ® AND FOUNDATION FIELDBUS PROTOCOLS Available with optional MultiVariable output and temperature compensated mass flow for saturated steam. Available in wafer, flanged, dual, reducer and high pressure designs. Available in Reducer Vortex which extends the measurable flow range, reduces installation costs, and minimizes project risk. All-welded, non-clog design eliminates ports and gaskets. Adaptive Digital Signal Processing (ADSP) provides vibration immunity and the ability to optimize the measurable flow range. With the unique isolated sensor design, the CriticalProcess Vortex allows for replacement without breaking the process seal. Simplified troubleshooting through device diagnostics and meter verification. Contents Specifications........................................................................................................... page 6 Typical Flow Ranges................................................................................................ page 11 Product Certifications............................................................................................... page 22 Dimensional Drawings.............................................................................................. page 28 Ordering Information................................................................................................ page 44 Rosemount 8800D Series Vortex Flowmeter

Rosemount 8800D Series Vortex Flowmeter 8800D V… · Rosemount 8800D ROSEMOUNT 8800D VORTEX FLOWMETER WITH FOUNDATION FIELDBUS The software for the 8800D Flowmeter with FOUNDATION

  • Author
    others

  • View
    11

  • Download
    0

Embed Size (px)

Text of Rosemount 8800D Series Vortex Flowmeter 8800D V… · Rosemount 8800D ROSEMOUNT 8800D VORTEX...

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Rosemount 8800D Series Vortex Flowmeter

    HART® AND FOUNDATION™ FIELDBUS PROTOCOLS

    • Available with optional MultiVariable output and temperature compensated mass flow for saturated steam.

    • Available in wafer, flanged, dual, reducer and high pressure designs.

    • Available in Reducer™ Vortex which extends the measurable flow range, reduces installation costs, and minimizes project risk.

    • All-welded, non-clog design eliminates ports and gaskets.

    • Adaptive Digital Signal Processing (ADSP) provides vibration immunity and the ability to optimize the measurable flow range.

    • With the unique isolated sensor design, the CriticalProcess™ Vortex allows for replacement without breaking the process seal.

    • Simplified troubleshooting through device diagnostics and meter verification.

    www.ros

    ContentsSpecifications........................................................................................................... page 6

    Typical Flow Ranges................................................................................................ page 11

    Product Certifications............................................................................................... page 22

    Dimensional Drawings.............................................................................................. page 28

    Ordering Information................................................................................................ page 44

    emount.com

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    2

    THE ROSEMOUNT 8800D DELIVERS RELIABILITY

    • Rosemount Reliability -The 8800D Vortex eliminates impulse lines, ports, and gaskets to improve reliability.

    • Non-clog Design - Unique gasket-free construction which has no ports that can clog.

    • Vibration Immunity - Mass Balancing of the sensor system, and Adaptive Digital Signal Processing (ADSP) provide Vibration immunity.

    • Replaceable Sensor - The sensor is isolated from the process and can be replaced without breaking the process seals. All line sizes use the same sensor design allowing a single spare to serve every meter. The CriticalProcess Vortex enhances the ability to replace the sensor without shutting down the process.

    • Simplified Troubleshooting - Device Diagnostics enable field verification of Meter Electronics and Sensor with no process shutdown.

    THE ROSEMOUNT 8800D OFFERING

    • The 8800D is available in wafer style meter bodies for 1/2 through 8-in. line sizes, and ASME B16.5 (ANSI), DIN, or JIS flanged style meter bodies for 1/2 through 12-in. line sizes.

    • Alignment rings, provided with each wafer-style flowmeter, ensure that the meter body is properly centered with the adjacent piping.

    • The wafer, flanged, and weld end style meter bodies are available in 316 stainless steel and nickel alloy materials of construction.

    • Available up to ASME class 1500 for 1 through 8-in. (25 mm through 200 mm) and ASME class 900 for 1/2-in. (15 mm) through 8-in. (200 mm).

    • Available with FOUNDATION fieldbus functionality which includes Device Diagnostics and PlantWeb Alerts.

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    3

    THE ROSEMOUNT 8800DR REDUCER VORTEX EXTENDS THE MEASURABLE FLOW RANGE AT A REDUCED COST

    • Rosemount Reliability - Designed with same electronics, sensor, and meter body as the 8800D.

    • Reduced Cost - Eliminates field assembly and welding of separate reducers and piping reducing installed cost by as much as 50%.

    • Extended Measurable Flow - Low-end flow range is doubled with the Rosemount 8800DR Reducer Vortex.

    • Reduced Project Risk - Reducer Vortex and the Standard Vortex have the same face-to-face dimension. As a result either meter can be used without affecting pipe layout.

    • Available as flanged meter for 1 through 12-in. stainless steel and nickel alloy materials of construction.

    • Available with FOUNDATION fieldbus functionality.

    THE DUAL-SENSOR VORTEX FLOWMETER

    • Safety Integrated Systems (SIS) - Ideal solution where redundant flow signals are required.

    • Rosemount Reliability - Designed with same electronics, sensor, and meter body as the 8800D.

    • Redundant Flow Measurement - Dual Vortex meter is constructed of two complete vortex meters: sensor, electronics, and shedder bar(1). The meters are welded together and flow calibrated to provide an accurate single flowmeter with two independent flow measurements.

    • Available as flanged meter for 1/2 through 12-in. stainless steel and nickel alloy materials of construction.

    (1) All 6-in. (150 mm) through 12-in. (300 mm) dual style vortex meters have a single shedder bar.

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    4

    8800D MULTIVARIABLE VORTEX REDUCES INSTALLATION COSTS, SIMPLIFIES INSTALLATION, AND IMPROVES PERFORMANCE IN SATURATED STEAM

    • MultiVariable Vortex DesignIncorporates temperature sensor into the vortex meter using the shedder bar as a thermowell, which keeps the vortex and temperature sensors isolated from process for easy verification and replacement.

    • Temperature Compensated Capability for Saturated SteamCalculates density from measured process temperature and uses the calculated density to provide a temperature compensated mass flow.

    • Increased performance in Saturated SteamPerformance in saturated steam is improved due to the fact that the electronics will be compensating for changes in the process temperature.

    • Reduces Installed CostsMultiVariable Vortex eliminates the need for an external thermowell and temperature sensor.

    • Output OptionsCan map independent variables to analog output, pulse output, or HART burst variables.

    • Available with Flow Computer for additional functionalityIntegrate the MultiVariable Vortex with a pressure transmitter for full pressure and temperature compensation of superheated steam and various gases.

    • Remote Mount ElectronicsAlso available with remote mounted electronics up to 75 ft. (23 m).

    When you integrate the MultiVariable Vortex with a Rosemount Flow Computer, you get:• Remote Communications• Heat Calculations• Remote Totalization• Peak Demand Calculation• Datalogging Capabilities

    Please see Product Data Sheet 00813-0100-4005 for more information on the Rosemount Flow Computer.

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    ROSEMOUNT 8800D VORTEX FLOWMETER WITH FOUNDATION FIELDBUSThe software for the 8800D Flowmeter with FOUNDATION fieldbus permits remote testing and configuration using any FOUNDATION fieldbus-compliant host, such as the DeltaV system from Emerson Process Management.

    Transducer BlockThe transducer block calculates flow from sensor frequency. The calculation includes information about damping, shedding frequency, K-factor, process fluid, pipe ID, and diagnostics.

    Resource BlockThe resource block contains physical transmitter information, including available memory, manufacturer identification, device type, software tag, and unique identification.

    Backup Link Active Scheduler (LAS)The transmitter is classified as a device link master. A device link master can function as a Link Active Scheduler (LAS) if the current link master device fails or is removed from the segment.

    The host or other configuration tool is used to download the schedule for the application to the link master device. In the absence of a primary link master, the transmitter will claim the LAS and provide permanent control for the H1 segment.

    DiagnosticsThe transmitter automatically performs continuous self-diagnostics. The user can perform on-line testing of the transmitter digital signal. Advanced simulation diagnostics are available. This enables remote verification of the electronics via a flow signal generator built into the electronics. The sensor strength value can be used to view the process flow signal and provide information regarding filter settings.

    FOUNDATION Fieldbus Function BlocksAnalog Input

    The AI function block processes the measurement and makes it available to other function blocks. The AI function block also allows filtering, alarming, and engineering unit changes.

    The 8800D Flowmeter with FOUNDATION fieldbus comes standard with three AI function blocks (1 block for flow, 1 block for signal strength, and one block for future use with the MTA option).

    Proportional/Integral/Derivative

    The optional PID function block provides a sophisticated implementation of the universal PID algorithm. The PID function block features input for feed forward control, alarms on the process variable, and control deviation. The PID type (series or Instrument Society of America [ISA]) is user-selectable on the derivative filter.

    IntegratorThe standard integrator block is available for totalization of flow.

    SetupBasic setup requires connecting the transmitter to a fieldbus network or Field Communicator. The FOUNDATION fieldbus-compliant host will automatically establish communication with the device.

    The Rosemount 8800D Flowmeter can be easily configured using the DeltaV system. User-configurable parameters include: tag, scaling and units, process fluid type, damping, fixed process density, pipe inside diameter (ID)(1), and fixed process temperature(1).

    Tagging information can be entered into the transmitter to allow identification and a physical description. 32-character tags are provided for identification of the transmitter and each function block.

    (1) Process temperature and pipe ID have known effects on the K-factor. The 8800D software automatically accounts for these effects by compensating the K-factor.

    5

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Specifications

    The following specifications are for the Rosemount 8800D, Rosemount 8800DR, and Rosemount 8800DD, except where noted.

    FUNCTIONAL SPECIFICATIONSProcess Fluids

    Liquid, gas, and steam applications. Fluids must be homogeneous and single-phase.

    Line Sizes

    Wafer1/2, 1, 11/2, 2, 3, 4, 6, and 8 inches(DN 15, 25, 40, 50, 80, 100, 150, and 200)

    Flanged and Dual-Sensor Style1/2, 1, 11/2, 2, 3, 4, 6, 8, 10, and 12 inches(DN 15, 25, 40, 50, 80, 100, 150, 200, 250, and 300)

    Reducer1, 11/2, 2, 3, 4, 6, 8, 10, and 12 inches(DN 25, 40, 50, 80, 100, 150, 200, 250, and 300)

    Pipe Schedules

    Process piping Schedules 10, 40, 80, and 160.

    NOTEThe appropriate bore diameter of the process piping must be entered using the Field Communicator or AMS Device Manager. Meters will be shipped from the factory at the Schedule 40 default value unless otherwise specified.

    Measurable Flow Rates

    Capable of processing signals from flow applications which meet the sizing requirements below.

    To determine the appropriate flowmeter size for an application, process conditions must be within the Reynolds number and velocity limitations for the desired line size provided in Table 1, Table 2, and Table 3.

    NOTEConsult your local sales representative to obtain a computer sizing program that describes in greater detail how to specify the correct flowmeter size for an application.

    The Reynolds number equation shown below combines the effects of density (�), viscosity (�cp), pipe inside diameter (D), and flow velocity (V).

    Table 1. Minimum Measurable Meter Reynolds NumbersMeter Sizes

    (Inches / DN) Reynolds Number Limitations1/2 through 4/15 through 100

    5000 minimum6 through 12/150 through 300

    Table 2. Minimum Measurable Meter Velocities(1)

    (1) Velocities are referenced to schedule 40 pipe.

    Feet per Second Meters per Second

    Liquids(2)

    (2) This minimum measurable meter velocity is based on default filter settings.

    Gases(2)

    The is the process fluid density at flowing conditions in lb/ft3 for ft/s and kg/m3 for m/s

    Table 3. Maximum Measurable Meter Velocities(1)(Use the smaller of the two values)

    (1) Velocities are referenced to schedule 40 pipe.

    Feet per Second Meters per SecondLiquids

    Gases(2)

    (2) Accuracy limitations for gas and steam for Dual-style meters (1/2-in. to 4-in.): max velocity of 100 ft/s (30.5 m/s).

    The is the process fluid density at flowing conditions in lb/ft3 for ft/s and kg/m3 for m/s

    RDVDcp------------=

    36/ 54/

    36/ 54/

    90,000/ or 25 134,000/ or 7.690,000/ or 250 134,000/ or 76

    6

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    7

    Process Temperature Limits

    Standard–40 to 450 °F (–40 to 232 °C)

    Extended–330 to 800 °F (–200 to 427 °C)

    MultiVariable (MTA option)

    –40 to 800 °F (–40 to 427 °C)• Use above 450 °F (232 °C) requires Extended

    Sensor

    Output Signals

    4–20 mA Digital HART Signal Superimposed on 4–20 mA signal

    Optional Scalable Pulse Output0 to 10000 Hz; transistor switch closure with adjustable scaling via HART communications; capable of switching up to 30 Vdc, 120 mA maximum

    Digital FOUNDATION fieldbus signal Completely digital output with FOUNDATION fieldbus communication (ITK 5.1 compliant).

    Analog Output Adjustment

    Engineering units and lower and upper range values are user-selected. Output is automatically scaled to provide 4 mA at the selected lower range value, 20 mA at the selected upper range value. No frequency input is required to adjust the range values.

    Scalable Frequency Adjustment

    The scalable pulse output can be set to a specific velocity, volume, or mass (i.e. 1 pulse = 1 lb). The scalable pulse output can also be scaled to a specific rate of volume, mass, or velocity (i.e. 100 Hz = 500 lb/hr).

    Ambient Temperature Limits

    Operating–58 to 185 °F (–50 to 85 °C)–4 to 185 °F (–20 to 85 °C) for flowmeters with local indicator

    Storage –58 to 250 °F (–50 to 121 °C)–50 to 185 °F (–46 to 85 °C) for flowmeters with local indicator

    Pressure Limits

    Flange Style Meter Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, DIN PN 10, 16, 25, 40, 64, 100, and 160, and JIS 10K, 20K, and 40K

    Reducer Style Meter Rated for ASME B16.5 (ANSI) Class 150, 300, 600, and 900, DIN PN 10, 16, 25, 40, 64, 100, and 160.

    Dual Sensor Style MeterRated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, DIN PN 10, 16, 25, 40, 64, 100, and 160, and JIS 10K, 20K, and 40K

    Wafer Style Meter Rated for ASME B16.5 (ANSI) Class 150, 300, and 600, DIN PN 10, 16, 25, 40, 64, and 100, and JIS 10K, 20K, and 40K

    NOTE: All Wafer Style Meters are pressure rated and labeled at 1500 PSI / 10.34 MPa at 100 °F / 38 °C regardless of Alignment Ring Size code ordered.

    Weld-End Style MeterW1 Welds to Schedule 10 mating pipe Max Working Pressure 720 psig (4.96 MPa-g)

    W4 Welds to Schedule 40 mating pipe Max Working Pressure 1440 psig (9.93 MPa-g)

    W8 Welds to Schedule 80 mating pipe Max Working Pressure 2160 psig (14.9 MPa-g)

    W9 Welds to Schedule 160 mating pipe Max Working Pressure 3600 psig (24.8 Mpa-g)

    NOTE:1-in. (25 mm), and 1.5-in. (40 mm) weld to Schedule 80 mating pipe

    Power Supply

    HART AnalogExternal power supply required. Flowmeter operates on 10.8 to 42 Vdc terminal voltage (with 250-ohm minimum load required for HART communications, 16.8 Vdc power supply is required)

    FOUNDATION fieldbusExternal power supply required. Flowmeter operates on 9 to 32 Vdc, 18 mA maximum.

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Power Consumption

    One watt maximum

    Load Limitations (HART Analog)

    Maximum loop resistance is determined by the voltage level of the external power supply, as described by:

    NOTEHART Communication requires a minimum loop resistance of 250 ohms.

    Optional LCD Indicator

    The optional LCD indicator is capable of displaying:• Primary Variable• Velocity Flow• Volumetric Flow• Mass Flow• Percent of Range• Analog Output (if applicable)• Totalizer (Output Code “D” and “P” Only)• Shedding Frequency• Pulse Output Frequency (if applicable)• Electronics Temperature (Output Code “D”

    and “P” Only)• Process Temperature (MTA Option Only)• Calculated Process Density (MTA Option

    Only)

    If more than one item is selected, the display will scroll through all items selected.

    Enclosure Rating

    FM Type 4X; CSA Type 4X; IP66

    Permanent Pressure Loss

    The approximate permanent pressure loss (PPL) from the Rosemount 8800D flowmeter is calculated for each application in the Vortex sizing software available from your local Rosemount representative. The PPL is determined using the equation:

    where:

    Minimum Upstream Pressure (Liquids)

    Flow metering conditions that would allow cavitation, the release of vapor from a liquid, should be avoided. This flow condition can be avoided by remaining within the proper flow range of the meter and by following appropriate system design.

    For some liquid applications, incorporation of a back pressure valve should be considered. To prevent cavitation, the minimum upstream pressure should be:

    Rmax = 41.7(Vps – 10.8)Vps = Power Supply Voltage (Volts)Rmax = Maximum Loop Resistance (Ohms)

    Power Supply (Volts)

    Load

    (Ohm

    s)

    OperatingRegion

    1250

    1000

    500

    010.8 42

    PPL = Permanent Pressure loss (psi or kPa)Where:

    �f = Density at operating conditions (lb/ft3 or kg/m3)

    Q = Actual volumetric flow rate (Gas = ft3/min or m3/hr; Liquid = gal/min or l/min)

    D = Flowmeter bore diameter (in. or mm)A = Constant depending on meter style, fluid type

    and flow units. Determined per following table:

    Table 4. Determining the PPL

    Meter Style

    English Units SI Units

    ALiquid AGas ALiquid AGas8800DF/W 3.4 � 10-5 1.9 � 10-3 0.425 118

    8800DR 3.91 � 10-5 2.19 � 10-3 0.489 1368800DD(1)

    (1) For all 6-in. thru 12-in. line sizes A is the same for 8800DD and 8800DF

    6.12 � 10-5 3.42 � 10-3 0.765 212

    P = 2.9P + 1.3pv or P = 2.9P + pv + 0.5 psia (3.45 kPa) (use the smaller of the two results)

    P = Line pressure five pipe diameters downstream of the meter (psia or kPa abs)

    P = Pressure loss across the meter (psi or kPa)pv = Liquid vapor pressure at operating conditions

    (psia or kPa abs)

    PPLA f Q

    2

    D4------------------------------=

    8

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Failure Mode Alarm

    HART AnalogIf self-diagnostics detect a gross flowmeter failure, the analog signal will be driven to the values below:

    High or low alarm signal is user-selectable through the fail mode alarm jumper on the electronics. NAMUR-compliant alarm limits are available through the C4 or CN Option. Alarm type is field configurable also.

    FOUNDATION fieldbusThe AI block allows the user to configure the alarm to HI-HI, HI, LO, or LO-LO with a variety of priority levels.

    Saturation Output Values

    When the operating flow is outside the range points, the analog output continues to track the operating flow until reaching the saturation value listed below; the output does not exceed the listed saturation value regardless of the operating flow. The NAMUR-Compliant Saturation Values are available through the C4 or CN option. Saturation type is field configurable.

    Damping

    Flow Damping adjustable between 0.2 and 255 seconds.

    Process Temperature Damping adjustable between 0.4 and 32.0 seconds (MTA Option Only).

    Response Time

    Three vortex shedding cycles or 300 ms, whichever is greater, maximum required to reach 63.2% of actual input with the minimum damping (0.2 seconds).

    Turn-on Time

    HART AnalogLess than four (4) seconds plus the response time to rated accuracy from power up (less than 7 seconds with the MTA Option).

    FOUNDATION fieldbusPerformance within specifications no greater than 10.0 seconds after power is applied.

    Transient Protection

    The optional transient terminal block prevents damage to the flowmeter from transients induced by lightning, welding, heavy electrical equipment, or switch gears. The transient protection electronics are located in the terminal block.

    The transient terminal block meets the following specifications:ASME B16.5 (ANSI)/IEEE C62.41 - 1980 (IEEE 587) Categories A, B 3 kA crest (8 � 20 s)6 kV crest (1.2 � 50 s)6 kV/0.5 kA (0.5 s, 100 kHz, ring wave)

    Security Lockout

    When the security lockout jumper is enabled, the electronics will not allow you to modify parameters that affect flowmeter output.

    Output Testing

    Current SourceFlowmeter may be commanded to set the current to a specified value between 4 and 20 mA.

    Frequency SourceFlowmeter may be commanded to set the frequency to a specified value between 0 and 10000 Hz.

    Low Flow Cutoff

    Adjustable over entire flow range. Below selected value, output is driven to 4 mA and zero pulse output frequency.

    Humidity Limits

    Operates in 0–95% relative humidity under noncondensing conditions (tested to IEC 60770, Section 6.2.11).

    Overrange Capability

    HART AnalogAnalog signal output continues to 105 percent of span, then remains constant with increasing flow. The digital and pulse outputs will continue to indicate flow up to the upper sensor limit of the flowmeter and a maximum pulse output frequency of 10400 Hz.

    Low 3.75High 22.6NAMUR Low 3.60NAMUR High 22.6

    Low 3.9High 20.8NAMUR Low 3.8NAMUR High 20.5

    9

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    FOUNDATION fieldbusFor liquid process fluid type, the transducer block digital output will continue to a nominal value of 25 ft/s. After that, the status associated with the transducer block output will go to UNCERTAIN. Above a nominal value of 30 ft/s, the status will go to BAD.

    For gas/steam service, the transducer block digital output will continue to a nominal value of 220 ft/s for 0.5 and 1.0-in. line sizes and a nominal value of 250 ft/s for 1.5–12-in. line sizes. After that, the status associated with the transducer block output will go to UNCERTAIN. Above a nominal value of 300 ft/s for all line sizes, the status will go to BAD.

    Flow Calibration

    Meter bodies are flow-calibrated and assigned a unique calibration factor (K-factor) at the factory. The calibration factor is entered into the electronics, enabling interchangeability of electronics and/or sensors without calculations or compromise in accuracy of the calibrated meter body.

    Status (FOUNDATION fieldbus only)

    If self-diagnostics detect a transmitter failure, the status of the measurement will inform the control system. Status may also set the PID output to a safe value.

    Schedule Entries (FOUNDATION fieldbus only)

    Six (6)

    Links (FOUNDATION fieldbus only)

    Twelve (12)

    Virtual Communications Relationships (VCRs) (FOUNDATION fieldbus only)

    Two (2) predefined (F6, F7)Four (4) configured (see Table 5) Table 5. Block Information

    Block Base IndexExecution Time (Milliseconds)

    Resource (RB) 300 —Transducer (TB) 400 —Analog Input (AI) 1,000 20

    Proportional/Integral/Derivative (PID)

    10,000 30

    Integrator (INT) 12,000 20

    10

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Typical Flow Ranges

    Table 6 - Table 12 show typical flow ranges for some common process fluids with default filter settings. Consult your local sales representative to obtain a computer sizing program that describes in greater detail the flow range for an application.

    Table 6. Typical pipe velocity ranges for 8800D and 8800DR(1)

    (1) Table 6 is a reference of pipe velocities that can be measured for the standard Rosemount 8800D and the reducer Rosemount 8800DR Vortex Meters. It does not consider density limitations, as described in tables 2 and 3. Velocities are referenced in schedule 40 pipe.

    Process Line Size Liquid Velocity Ranges Gas Velocity Ranges

    (Inches/ DN) Vortex Meter (2)

    (2) Velocity range of the Rosemount 8800DW is the same as Rosemount 8800DF.

    (ft/s) (m/s) (ft/s) (m/s)0.5/ 15 8800DF005 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.21/ 25 8800DF010 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR010 0.25 to 8.8 0.08 to 2.7 2.29 to 87.9 0.70 to 26.81.5/ 40 8800DF015 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR015 0.30 to 10.6 0.09 to 3.2 2.76 to 106.1 0.84 to 32.32/ 50 8800DF020 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR020 0.42 to 15.2 0.13 to 4.6 3.94 to 151.7 1.20 to 46.23/ 80 8800DF030 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR030 0.32 to 11.3 0.10 to 3.5 2.95 to 113.5 0.90 to 34.64/ 100 8800DF040 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR040 0.41 to 14.5 0.12 to 4.4 3.77 to 145.2 1.15 to 44.36/ 150 8800DF060 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR060 0.31 to 11.0 0.09 to 3.4 2.86 to 110.2 0.87 to 33.68/ 200 8800DF080 0.70 to 25.0 0.21 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR080 0.40 to 14.4 0.12 to 4.4 3.75 to 144.4 1.14 to 44.010/ 250 8800DF100 0.90 to 25.0 0.27 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR100 0.44 to 15.9 0.13 to 4.8 4.12 to 158.6 1.26 to 48.312/ 300 8800DF120 1.10 to 25.0 0.34 to 7.6 6.50 to 250.0 1.98 to 76.2

    8800DR120 0.63 to 17.6 0.19 to 5.4 4.58 to 176.1 1.40 to 53.7

    11

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Table 7. Water Flow Rate Limits for the Rosemount 8800D and 8800DR(1)

    Process Line Size

    Vortex Meter (2)Minimum and Maximum Measurable Water Flow Rates*

    (Inches/ DN) Gallons/Minute Cubic Meters/Hour0.5/ 15 8800DF005 1.76 to 23.7 0.40 to 5.41/ 25 8800DF010 2.96 to 67.3 0.67 to 15.3

    8800DR010 1.76 to 23.7 0.40 to 5.41.5/ 40 8800DF015 4.83 to 158 1.10 to 35.9

    8800DR015 2.96 to 67.3 0.67 to 15.32/ 50 8800DF020 7.96 to 261 1.81 to 59.4

    8800DR020 4.83 to 158.0 1.10 to 35.93/ 80 8800DF030 17.5 to 576 4.00 to 130

    8800DR030 7.96 to 261.0 1.81 to 59.34/ 100 8800DF040 30.2 to 992 6.86 to 225

    8800DR040 17.5 to 576 4.00 to 1306/ 150 8800DF060 68.5 to 2251 15.6 to 511

    8800DR060 30.2 to 992 6.86 to 2258/ 200 8800DF080 119 to 3898 27.0 to 885

    8800DR080 68.5 to 2251 15.6 to 51110/ 250 8800DF100 231 to 6144 52.2 to 1395

    8800DR100 119 to 3898 27.0 to 88512/ 300 8800DF120 391 to 8813 88.8 to 2002

    8800DR120 231 to 6144 52.2 to 1395*Conditions: 77 °F (25 °C) and 14.7 psia (1.01 bar absolute)

    (1) Table 7 is a reference of flow rates that can be measured for the standard Rosemount 8800D and the reducer 8800DR Vortex Meters. It does not consider density limitations, as described in tables 2 and 3.

    (2) Velocity range of the 8800DW is the same as 8800DF.

    Table 8. Air Flow Rate Limits at 59 °F (15 °C)

    Process Pressure

    Flow Rate

    Limits

    Minimum and Maximum Air Flow Ratesfor line sizes 1/2-in./DN 15 through 1-in./DN 25

    1/2-in./DN 15 1-in./DN 25

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    ACFM ACMH ACFM ACMH ACFM ACMH ACFM ACMH0 psig

    (0 bar G)maxmin

    27.93.86

    47.36.56

    Not Available

    Not Available

    79.27.81

    13413.3

    27.93.86

    47.36.56

    50 psig(3,45 bar G)

    maxmin

    27.91.31

    47.32.22

    Not Available

    Not Available

    79.23.72

    1346.32

    27.91.31

    47.32.22

    100 psig(6,89 bar G)

    maxmin

    27.90.98

    47.31.66

    Not Available

    Not Available

    79.22.80

    1344.75

    27.90.98

    47.31.66

    150 psig(10,3 bar G)

    maxmin

    27.90.82

    47.31.41

    Not Available

    Not Available

    79.22.34

    1343.98

    27.90.82

    47.31.41

    200 psig(13,8 bar G)

    maxmin

    27.90.82

    47.31.41

    Not Available

    Not Available

    79.22.34

    1343.98

    27.90.82

    47.31.41

    300 psig(20,7 bar G)

    maxmin

    27.90.82

    47.31.41

    Not Available

    Not Available

    79.22.34

    1343.98

    27.90.82

    47.31.41

    400 psig(27,6 bar G)

    maxmin

    25.70.82

    43.91.41

    Not Available

    Not Available

    73.02.34

    1243.98

    25.70.82

    43.91.41

    500 psig(34,5 bar G)

    maxmin

    23.00.82

    39.41.41

    Not Available

    Not Available

    66.02.34

    1123.98

    23.00.82

    39.41.41

    12

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Table 9. Air Flow Rate Limits at 59 °F (15 °C)

    Process Pressure

    Flow Rate

    Limits

    Minimum and Maximum Air Flow Ratesfor line sizes 11/2-in./DN 40 through 2-in./DN 50

    1½-in./DN 40 2-in./DN 50

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    ACFM ACMH ACFM ACMH ACFM ACMH ACFM ACMH0 psig

    (0 bar G)maxmin

    21218.4

    36031.2

    79.27.81

    13413.3

    34930.3

    59351.5

    21218.4

    36031.2

    50 psig(3,45 bar G)

    maxmin

    2128.76

    36014.9

    79.23.72

    1346.32

    34914.5

    59324.6

    2128.76

    36014.9

    100 psig(6,89 bar G)

    maxmin

    2126.58

    36011.2

    79.22.80

    1344.75

    34910.8

    59318.3

    2126.58

    36011.2

    150 psig(10,3 bar G)

    maxmin

    2125.51

    3609.36

    79.22.34

    1343.98

    3499.09

    59315.4

    2125.51

    3609.36

    200 psig(13,8 bar G)

    maxmin

    2125.51

    3609.36

    79.22.34

    1343.98

    3499.09

    59315.4

    2125.51

    3609.36

    300 psig(20,7 bar G)

    maxmin

    1985.51

    3379.36

    79.22.34

    1343.98

    3269.09

    55415.4

    1985.51

    3379.36

    400 psig(27,6 bar G)

    maxmin

    1725.51

    2939.36

    73.02.34

    1243.98

    2849.09

    48315.4

    1725.51

    2939.36

    500 psig(34,5 bar G)

    maxmin

    1545.51

    2629.36

    66.02.34

    1123.98

    2549.09

    43215.4

    1545.51

    2629.36

    Table 10. Air Flow Rate Limits at 59 °F (15 °C)

    Process Pressure

    Flow Rate

    Limits

    Minimum and Maximum Air Flow Ratesfor line sizes 3-in./DN 80 through 4-in./DN 100

    3-in./DN 80 4-in./DN 100

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    ACFM ACMH ACFM ACMH ACFM ACMH ACFM ACMH0 psig

    (0 bar G)maxmin

    77066.8

    1308114

    34930.3

    59351.5

    1326115

    2253195

    77066.8

    1308114

    50 psig(3,45 bar G)

    maxmin

    77031.8

    130854.1

    34914.5

    59324.6

    132654.8

    225393.2

    77031.8

    130854.1

    100 psig(6,89 bar G)

    maxmin

    77023.9

    130840.6

    34910.8

    59318.3

    132641.1

    225369.8

    77023.9

    130840.6

    150 psig(10,3 bar G)

    maxmin

    77020.0

    130834.0

    3499.09

    59315.4

    132634.5

    225358.6

    77020.0

    130834.0

    200 psig(13,8 bar G)

    maxmin

    77020.0

    130834.0

    3499.09

    59315.4

    132634.5

    225358.6

    77020.0

    130834.0

    300 psig(20,7 bar G)

    maxmin

    71820.0

    122034.0

    3269.09

    55415.4

    123734.5

    210258.6

    71820.0

    122034.0

    400 psig(27,6 bar G)

    maxmin

    62520.0

    106234.0

    2849.09

    48315.4

    107634.5

    182858.6

    62520.0

    106234.0

    500 psig(34,5 bar G)

    maxmin

    56020.0

    95134.0

    2549.09

    43215.4

    96434.5

    163858.6

    56020.0

    95134.0

    13

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    14

    NOTESThe Rosemount 8800D measures the volumetric flow under operating conditions (i.e. the actual volume at the operating pressure and temperature–acfm or acmh), as shown above. However, gas volumes are strongly dependent on pressure and temperature. Therefore, gas quantities are typically stated in standard or normal conditions (e.g. SCFM or NCMH). (Standard conditions are typically 59 °F and 14.7 psia. Normal conditions are typically 0 °C and 1 bar abs.) The flow rate limits in standard conditions are found using the equations below: Standard Flow Rate = Actual Flow Rate X Density Ratio Density Ratio = Density at Actual (Operating) Conditions / Density at Standard Conditions

    Table 11. Air Flow Rate Limits at 59 °F (15 °C)

    Process Pressure

    Flow Rate

    Limits

    Minimum and Maximum Air Flow Ratesfor line sizes 6-in./DN 150 through 8-in./DN 200

    6-in./DN 150 8-in./DN 200

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    ACFM ACMH ACFM ACMH ACFM ACMH ACFM ACMH0 psig

    (0 bar G)maxmin

    3009261

    5112443

    1326115

    2253195

    5211452

    8853768

    3009261

    5112443

    50 psig(3,45 bar G)

    maxmin

    3009124

    5112211

    132654.8

    225393.2

    5211215

    8853365

    3009124

    5112211

    100 psig(6,89 bar G)

    maxmin

    300993.3

    5112159

    132641.1

    225369.8

    5211162

    8853276

    300993.3

    5112159

    150 psig(10,3 bar G)

    maxmin

    300978.2

    5112133

    132634.5

    225358.6

    5211135

    8853229

    300978.2

    5112133

    200 psig(13,8 bar G)

    maxmin

    300978.2

    5112133

    132634.5

    225358.6

    5211135

    8853229

    300978.2

    5112133

    300 psig(20,7 bar G)

    maxmin

    280778.2

    4769133

    123734.5

    210258.6

    4862135

    8260229

    280778.2

    4769133

    400 psig(27,6 bar G)

    maxmin

    244278.2

    4149133

    107634.5

    182858.6

    4228136

    7183229

    244278.2

    4149133

    500 psig(34,5 bar G)

    maxmin

    218878.2

    3717133

    96434.5

    163858.6

    3789136

    6437229

    218878.2

    3717133

    Table 12. Air Flow Rate Limits at 59 °F (15 °C)

    Process Pressure

    Flow Rate

    Limits

    Minimum and Maximum Air Flow Ratesfor line sizes 10-in./DN 250 through 12-in./DN 300

    10-in./DN 250 12-in./DN 300

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    ACFM ACMH ACFM ACMH ACFM ACMH ACFM ACMH0 psig

    (0 bar G)maxmin

    8214712.9

    139561211

    5211452

    8853768

    117811022

    200161736

    8214712.9

    139561211

    50 psig(3,45 bar G)

    maxmin

    8214339.5

    13956577

    5211215

    8853365

    11781486.9

    20016827

    8214339.5

    13956577

    100 psig(6,89 bar G)

    maxmin

    8214254.7

    13956433

    5211162

    8853276

    11781365.4

    20016621

    8214254.7

    13956433

    150 psig(10,3 bar G)

    maxmin

    8214213.6

    13956363

    5211135

    8853229

    11781306.3

    20016520

    8214213.6

    13956363

    200 psig(13,8 bar G)

    maxmin

    8214213.6

    13956363

    5211135

    8853229

    11781306.3

    20016520

    8214213.6

    13956363

    300 psig(20,7 bar G)

    maxmin

    7664213.6

    13021363

    4862135

    8260229

    10992306.3

    18675520

    7664213.6

    13021363

    400 psig(27,6 bar G)

    maxmin

    6664213.6

    11322363

    4228136

    7183229

    9559306.3

    16241520

    6664213.6

    11322363

    500 psig(34,5 bar G)

    maxmin

    5972213.6

    10146363

    3789136

    6437229

    8565306.3

    14552520

    5972213.6

    10146363

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Table 13. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%)

    Process Pressure

    Flow Rate Limits

    Minimum and Maximum Saturated Steam Flow Rates for line sizes 1/2-in./DN 15 through 1-in./DN 25

    ½-in./DN 15 1-in./DN 25

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr15 psig

    (1,03 bar G)maxmin

    12012.8

    54.65.81

    Not Available

    Not Available

    34234.8

    15515.8

    12012.8

    54.65.81

    25 psig(1,72 bar G)

    maxmin

    15814.0

    71.76.35

    Not Available

    Not Available

    44939.9

    20318.1

    15814.0

    71.76.35

    50 psig(3,45 bar G)

    maxmin

    25017.6

    1138.00

    Not Available

    Not Available

    71150.1

    32222.7

    25017.6

    1138.00

    100 psig(6,89 bar G)

    maxmin

    42923.1

    19410.5

    Not Available

    Not Available

    122165.7

    55429.8

    42923.1

    19410.5

    150 psig(10,3 bar G)

    maxmin

    60627.4

    27512.5

    Not Available

    Not Available

    172478.1

    78235.4

    60627.4

    27512.5

    200 psig(13,8 bar G)

    maxmin

    78231.2

    35414.1

    Not Available

    Not Available

    222588.7

    100940.2

    78231.2

    35414.1

    300 psig(20,7 bar G)

    maxmin

    113537.6

    51517.0

    Not Available

    Not Available

    3229107

    146448.5

    113537.6

    51517.0

    400 psig(27,6 bar G)

    maxmin

    149244.1

    67620.0

    Not Available

    Not Available

    4244125

    192556.7

    149244.1

    67620.0

    500 psig(34,5 bar G)

    maxmin

    185554.8

    84124.9

    Not Available

    Not Available

    5277156

    239370.7

    185554.8

    84124.9

    Table 14. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%)

    Process Pressure

    Flow Rate Limits

    Minimum and Maximum Saturated Steam Flow Rates for line sizes 11/2-in./DN 40 through 2-in./DN 50

    1½-in./DN 40 2-in./DN 50

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr15 psig

    (1,03 bar G)maxmin

    91782.0

    41637.2

    34234.8

    15515.8

    1511135

    68561.2

    91782.0

    41637.2

    25 psig(1,72 bar G)

    maxmin

    120493.9

    54642.6

    44939.9

    20318.1

    1983155

    89970.2

    120493.9

    54642.6

    50 psig(3,45 bar G)

    maxmin

    1904118

    86453.4

    71150.1

    32222.7

    3138195

    142388.3

    1904118

    86453.4

    100 psig(6,89 bar G)

    maxmin

    3270155

    148370.1

    122165.7

    55429.8

    5389255

    2444116

    3270155

    148370.1

    150 psig(10,3 bar G)

    maxmin

    4616184

    209483.2

    172478.1

    78235.4

    7609303

    3451137

    4616184

    209483.2

    200 psig(13,8 bar G)

    maxmin

    5956209

    270294.5

    222588.7

    100940.2

    9818344

    4453156

    5956209

    270294.5

    300 psig(20,7 bar G)

    maxmin

    8644252

    3921114

    3229107

    146448.5

    14248415

    6463189

    8644252

    3921114

    400 psig(27,6 bar G)

    maxmin

    11362295

    5154134

    4244125

    192556.7

    18727487

    8494221

    11362295

    5154134

    500 psig(34,5 bar G)

    maxmin

    14126367

    6407167

    5277156

    239370.7

    23284605

    10561274

    14126367

    6407167

    15

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Table 15. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%)

    Process Pressure

    Flow Rate Limits

    Minimum and Maximum Saturated Steam Flow Rates for line sizes 3-in./DN 80 through 4-in./DN 100

    3-in./DN 80 4-in./DN 100

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr15 psig

    (1,03 bar G)maxmin

    3330298

    1510135

    1511135

    68561.2

    5734513

    2601233

    3330298

    1510135

    25 psig(1,72 bar G)

    maxmin

    4370341

    1982155

    1983155

    89970.2

    7526587

    3414267

    4370341

    1982155

    50 psig(3,45 bar G)

    maxmin

    6914429

    3136195

    3138195

    142388.3

    11905739

    5400335

    6914429

    3136195

    100 psig(6,89 bar G)

    maxmin

    11874562

    5386255

    5389255

    2444116

    20448968

    9275439

    11874562

    5386255

    150 psig(10,3 bar G)

    maxmin

    16763668

    7603303

    7609303

    3451137

    288661150

    13093522

    16763668

    7603303

    200 psig(13,8 bar G)

    maxmin

    21630759

    9811344

    9818344

    4453156

    372471307

    16895593

    21630759

    9811344

    300 psig(20,7 bar G)

    maxmin

    31389914

    14237415

    14248415

    6463189

    540521574

    24517714

    31389914

    14237415

    400 psig(27,6 bar G)

    maxmin

    412581073

    18714487

    18727487

    8494221

    710471847

    32226838

    412581073

    18714487

    500 psig(34,5 bar G)

    maxmin

    512971334

    23267605

    23284605

    10561274

    883342297

    400681042

    512971334

    23267605

    Table 16. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%)

    Process Pressure

    Flow Rate Limits

    Minimum and Maximum Saturated Steam Flow Rates for line sizes 6-in./DN 150 through 8-in./DN 200

    6-in./DN 150 8-in./DN 200

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr15 psig

    (1,03 bar G)maxmin

    130131163

    5903528

    5734513

    2601233

    225342015

    10221914

    130131163

    5903528

    25 psig(1,72 bar G)

    maxmin

    170801333

    7747605

    7526587

    3414267

    295752308

    134151047

    170801333

    7747605

    50 psig(3,45 bar G)

    maxmin

    270191676

    12255760

    11905739

    5400335

    467872903

    212221317

    270191676

    12255760

    100 psig(6,89 bar G)

    maxmin

    464052197

    21049996

    20448968

    9275439

    803563804

    364491725

    464052197

    21049996

    150 psig(10,3 bar G)

    maxmin

    656112610

    297611184

    288661150

    13093522

    1134404520

    514552050

    656112610

    297611184

    200 psig(13,8 bar G)

    maxmin

    845302965

    383421345

    372471307

    16895593

    1463755134

    663952329

    845302965

    383421345

    300 psig(20,7 bar G)

    maxmin

    1226663572

    556401620

    540521574

    24517714

    2124116185

    963482805

    1226663572

    556401620

    400 psig(27,6 bar G)

    maxmin

    1612364192

    731351901

    710471847

    32226838

    2792007259

    1266433293

    1612364192

    731351901

    500 psig(34,5 bar G)

    maxmin

    2004685212

    909312364

    883342297

    400681042

    3471349025

    1574574094

    2004685212

    909312364

    16

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Table 17. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%)

    Process Pressure

    Flow Rate Limits

    Minimum and Maximum Saturated Steam Flow Rates for line sizes 10-in./DN 250 through 12-in./DN 300

    10-in./DN 250 12-in./DN 300

    Rosemount 8800D Rosemount 8800DR Rosemount 8800D Rosemount 8800DR

    lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr lb/hr kg/hr15 psig

    (1,03 bar G)maxmin

    355193175

    161111440

    225342015

    10221914

    509944554

    231302066

    355193175

    161111440

    25 psig(1,72 bar G)

    maxmin

    466184570

    211462073

    295752308

    134151047

    668625218

    303282367

    466184570

    211462073

    50 psig(3,45 bar G)

    maxmin

    737484575

    334522075

    467872903

    212221317

    1057746562

    479782976

    737484575

    334522075

    100 psig(6,89 bar G)

    maxmin

    1266605996

    574522720

    803563804

    364491725

    1816638600

    824013901

    1266605996

    574522720

    150 psig(10,3 bar G)

    maxmin

    1788087125

    811063232

    1134404520

    514552050

    25645710218

    1163274635

    1788087125

    811063232

    200 psig(13,8 bar G)

    maxmin

    2307228092

    1046543670

    1463755134

    663952329

    33091511607

    1501015265

    2307228092

    1046543670

    300 psig(20,7 bar G)

    maxmin

    3348109749

    1518674422

    2124116185

    963482805

    48020313983

    2178166343

    3348109749

    1518674422

    400 psig(27,6 bar G)

    maxmin

    44008511442

    1996195190

    2792007259

    1266433293

    63119516411

    2863057444

    44008511442

    1996195190

    500 psig(34,5 bar G)

    maxmin

    54716514226

    2481906453

    3471349025

    1574574094

    78477520404

    3559689255

    54716514226

    2481906453

    17

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    18

    PERFORMANCE SPECIFICATIONSThe following performance specifications are for all Rosemount models except where noted. Digital performance specifications applicable to both Digital HART and FOUNDATION fieldbus output.

    Flow AccuracyIncludes linearity, hysteresis, and repeatability.

    Liquids - for Reynolds Numbers over 20000

    Digital and Pulse Output±0.65% of rate

    Note: The accuracy for the 8800DR, line sizes 6 to 12-in. (150 to 300mm), is ±1.0% of rate.

    Analog OutputSame as pulse output plus an additional 0.025% of span

    Gas and Steam - for Reynolds Numbers over 15,000

    Digital and Pulse Output±1.0% of rate

    Note: The accuracy for the 8800DR, line sizes 6 to 12-in. (150 to 300mm), is ±1.35% of rate.

    Analog OutputSame as pulse output plus an additional 0.025% of span

    Accuracy limitations for gas and steam:

    For 1/2 and 1-in. (DN 15 and DN 25): max velocity of 220 ft/s (67.06 m/s)

    For 1/2 to 4-in. (DN 15 to DN 200) Dual-style meters: max velocity of 100 ft/s (30.5 m/s)

    NOTEAs the meter Reynolds Numbers decreases below the stated limit to 10,000 the accuracy error band will increase linearly to +/-2.0%. For Reynolds Numbers down to 5,000 the accuracy error band will increase linearly from +/-2.0% to +/-6.0%.

    Process Temperature Accuracy

    2.2 °F (1.2 °C) or 0.4% of reading (in °C), whichever is greater.

    NOTEFor remote mount installations, add ±0.018 °F/ft. (±0.03 °C/m) of uncertainty to the temperature measurement.

    Mass Flow Accuracy for Temperature Compensated Mass Flow

    Digital and Pulse Output± 2.0% of rate (Nominal)

    Nominal conditions include temperature variation in saturation and superheat at 150 psig (10 bar-g) and above.

    For pressure below 150 psig (10 bar-g), add 0.08% of uncertainty for every 15 psi (1 bar) below 150 psig (10 bar-g).

    Analog OutputSame as pulse output plus an additional 0.025% of span

    Repeatability

    ± 0.1% of actual flow rate

    Stability

    ± 0.1% of rate over one year

    Process Temperature Effect

    Automatic K-factor correction with user-entered process temperature.

    Table 18 indicates the percent change in K-factor per 100 °F (55.5 °C) in process temperature from reference temperature of 77 °F (25 °C).

    Ambient Temperature Effect

    Digital and Pulse OutputsNo effect

    Analog Output±0.1% of span from –58 to 185 °F (–50 to 85 °C)

    Table 18. Process Temperature Effect

    MaterialPercent Change in

    K-Factor per 100 °F (55.5 °C)

    316L @ < 77 °F (25 °C) + 0.23316L @ > 77 °F (25 °C) - 0.27

    Nickel Alloy C < 77 °F (25 °C) + 0.22Nickel Alloy C > 77 °F (25 °C) - 0.22

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Vibration Effect

    An output with no process flow may be detected if sufficiently high vibration is present.

    The meter design will minimize this effect, and the factory settings for signal processing are selected to eliminate these errors for most applications.

    If an output error at zero flow is still detected, it can be eliminated by adjusting the low flow cutoff, trigger level, or low-pass filter.

    As the process begins to flow through the meter, most vibration effects are quickly overcome by the flow signal.

    Vibration Specifications

    Integral Aluminum Housings, Remote Aluminum Housings, and Remote SST HousingsAt or near the minimum liquid flow rate in a normal pipe mounted installation, the maximum vibration should be 0.087-in. (2,21 mm) double amplitude displacement or 1 g acceleration, whichever is smaller. At or near the minimum gas flow rate in a normal pipe mounted installation, the maximum vibration should be 0.043-in. (1,09 mm) double amplitude displacement or 1/2 g acceleration, whichever is smaller.

    Integral SST HousingAt or near the minimum liquid flow rate in a normal pipe mounted installation, the maximum vibration should be 0.044-in. (1,11 mm) double amplitude displacement or 1/3 g acceleration, whichever is smaller. At or near the minimum gas flow rate in a normal pipe mounted installation, the maximum vibration should be 0.022-in. (0,55 mm) double amplitude displacement or 1/6 g acceleration, whichever is smaller.

    Mounting Position Effect

    Meter will meet accuracy specifications when mounted in horizontal, vertical, or inclined pipelines. Best practice for mounting in a horizontal pipe is to orient the shedder bar in the horizontal plane. This will prevent solids in liquid applications and liquid in gas/steam applications from disrupting the shedding frequency.

    EMI/RFI Effect

    Meets EMC requirements to EU Directive 2004/108/EC.

    HART AnalogOutput error less than ±0.025% of span with twisted pair from 80-1000 MHz for radiated field strength of 10 V/m. Tested per EN61326.

    FOUNDATION fieldbus and Digital HARTNo affect on the values that are being given if using HART digital signal or FOUNDATION fieldbus. Tested per EN61326.

    Magnetic-Field Interference

    HART AnalogOutput error less than ±0.025% of span at 30 A/m (rms).

    FOUNDATION fieldbusNo effect on digital output accuracy at 30 A/m (rms). Tested per EN 61326.

    Series Mode Noise Rejection

    HART AnalogOutput error less than ±0.025% of span at 1 V rms, 60 Hz.

    FOUNDATION fieldbusNo effect on digital output accuracy at 1 V rms, 60 Hz.

    Common Mode Noise Rejection

    HART AnalogOutput error less than ±0.025% of span at 30 V rms, 60 Hz.

    FOUNDATION fieldbusNo effect on digital output accuracy at 250 V rms, 60 Hz.

    Power Supply Effect

    HART AnalogLess than 0.005% of span per volt

    FOUNDATION fieldbusNo effect on accuracy.

    19

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    PHYSICAL SPECIFICATIONSNACE Compliance

    Materials of Construction meet NACE material recommendations per MR0175/ISO15156 for use in H2S containing environments in oil field production. Materials of construction also meet NACE recommendations per MR0103-2003 for corrosive petroleum refining environments. MR0103 compliance requires Q25 option in model code.

    NOTE:Certificate of compliance for MR0175/ISO15156 requires Q15 as a separate line item.

    Electrical Connections1/2 –14 NPT, PG 13.5, or M20 � 1.5 conduit threads; screw terminals provided for 4–20 mA and pulse output connections; communicator connections permanently fixed to terminal block.

    Non-Wetted Materials

    HousingLow-copper aluminum (FM Type 4X, CSA Type 4X, IP66)Optional SST housing

    PaintPolyurethane

    Cover O-ringsBuna-N

    Flanges316/316L lap joint

    Temperature Sensor (MTA Option)Type-N Thermocouple

    Process-Wetted Materials

    Meter Body316L wrought stainless and CF-3M cast stainless or N06022 wrought Nickel Alloy and CW2M cast Nickel Alloy. Other material grades available. Consult factory for other materials of construction.

    Flanges 316/316L stainless steelNickel Alloy N06022 Weld Neck

    CollarsNickel Alloy N06022316/316L Stainless Steel

    Process Connections

    Mounts between the following flange configurations:

    ASME B16.5 (ANSI): Class 150, 300, 600, 900, 1500

    DIN: PN 10, 16, 25, 40, 64, 100, 160

    JIS: 10K, 20K, and 40K

    Weld-end: Schedule 10, Schedule 40, Schedule 80, Schedule 160

    Mounting

    Integral (Standard)Electronics are mounted on meter body.

    Remote (Optional)Electronics may be mounted remote from the meter body. Interconnecting coaxial cable available in nonadjustable 10, 20, and 30 ft (3,0, 6,1, and 9,1 m) lengths. Consult factory for non-standard lengths up to 75 ft (22,9 m). Remote mounting hardware includes a pipe mount bracket with one u-bolt.

    Surface Finish of Flanges and CollarsStandard: To the requirements of the applicable flange standard.Smooth: 63 to 125 inches(1.6 to 3.1 meters) Ra roughness

    20

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    21

    Temperature Limitations for Integral MountingThe maximum process temperature for integral mount electronics is dependent on the ambient temperature where the meter is installed. The electronics must not exceed 185°F (85°C). The following is for reference, please note that the pipe was insulated with 3 inches of ceramic fiber insulator.

    Pipe Length Requirements

    The vortex meter may be installed with a minimum of ten diameters (D) of straight pipe length upstream and five diameters (D) of straight pipe length downstream.

    Rated Accuracy is based on the number of pipe diameter from an upstream disturbance. No K-factor correction is required if the meter is installed with 35 D upstream and 10 D downstream. The value of the K-factor may shift up to 0.5% when the upstream straight pipe length is between 10D and 35D. Please see Technical Data Sheet (00816-0100-3250) on Installation Effects for optional K-factor corrections. This effect can be corrected in the electronics. Tagging

    The flowmeter will be tagged at no charge, according to customer requirements. All tags are stainless steel. The standard tag is permanently attached to the flowmeter. Character height is 1/16-in. (1,6 mm). A wired-on tag is available on request. Wire on tags can contain five lines with up to 28 characters per line.

    Flow Calibration Information

    Flowmeter calibration and configuration information is provided with every flowmeter. For a certified copy of flow calibration data, Option Q4 must be ordered in the model number.

    Figure 1. Rosemount 8800 Vortex Flowmeter Ambient/process temperature limits

    Shows combinations of ambient and process temperatures needed to remain at or below 185°F (85°C) housing

    temperature

    200 (93)180 (82)

    160 (71)140 (60)

    120 (49)

    100 (38)

    80 (27)60 (16)

    0

    200

    (93)

    300

    (149

    )40

    0 (2

    04)

    500

    (260

    )60

    0 (3

    16)

    700

    (371

    )80

    0 (4

    27)

    900

    (482

    )

    1000

    (538

    )

    100

    (38)

    Am

    bien

    t Tem

    pera

    ture

    °F (°

    C)

    Process Temperature °F (°C)

    185°F Housing Temperature Limit

    Meter and pipe insulated with 3 inches of ceramic fiber insulation. Horizontal Pipe and Vertical meter position.

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    22

    Product Certifications

    Approved Manufacturing LocationsRosemount Inc. — Eden Prairie, Minnesota, USAEmerson Process Management BV - Ede, The NetherlandsEmerson Process Management Flow Technologies Company, Ltd - Nanjing, Jiangsu Province, P.R. China

    EUROPEAN DIRECTIVE INFORMATIONThe CE Declaration of Conformity for all applicable European directives for this product can be found on our website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.

    ATEX DirectiveRosemount Inc. complies with the ATEX Directive.

    Flameproof enclosure EEx d protection type in accordance with EN50018

    • Transmitters with Flameproof enclosure type protection shall only be opened when power is removed.

    • Closing of entries in the device must be carried out using the appropriate EEx d metal cable gland or metal blanking plug.

    • Do not exceed the energy level, which is stated on the approval label.

    Type n protection type in accordance with EN60079-15Closing of entries in the device must be carried out using the appropriate EExe or EExn metal cable gland and metal blanking plug or any appropriate ATEX approved cable gland and blanking plug with IP66 rating certified by an EU approved certification body.

    EUROPEAN PRESSURE EQUIPMENT DIRECTIVE (PED)

    Rosemount 8800 Vortex Flowmeter Line Size 40 mm to 300 mmCertificate Number PED-H-100

    0575Module H Conformity AssessmentMandatory CE-marking for flowmeters in accordance with Article 15 of the PED can be found on the flowtube body. Flowmeter categories I – IV, use module H for conformity assessment procedures.

    Rosemount 8800 Vortex Flowmeter Line Size 15 mm and 25 mm

    Sound Engineering PracticeFlowmeters that are SEP are outside the scope of PED and cannot be marked for compliance with PED.

    HAZARDOUS LOCATION CERTIFICATIONS

    Rosemount 8800D with HART Protocol

    North American Certifications

    Factory Mutual (FM)E5 Explosion-proof for Class I, Division 1, Groups B, C, and D;

    Dust Ignition-proof for Class II/III, Division 1, Groups E, F, and G; Temp Code T6 (-50°C Ta 70°C)Factory SealedEnclosure Type 4X.

    I5 Intrinsically safe for use in Class I, II, III Division 1, Groups A, B, C, D, E, F, G; Class I, Zone 0, AEx ia IIC T4Non-incendive for Class I, Division 2, Groups A, B, C, and D. NIFW (Non-incendive Field Wiring) when installed per Rosemount Drawing 08800-0112T4 (-50°C to 70°C)Enclosure Type 4X.

    K5 E5 and I5 Combination

    Canadian Standards Association (CSA)E6 Dust Ignition-proof for Class II and Class III, Division 1,

    Groups E, F, and G;Class I, Zone 1, Ex d[ia] IIC CSA 06.1674267T6 (-50°C to 70°C)Factory SealedSingle Seal.Enclosure Type 4X.

    I6 Intrinsically safe for use in Class I, II, III Division 1, Groups A, B, C, D, E, F, G;Non-incendive for Class I, Division 2, Groups A, B, C and DT4 (-50°C to 70°C)Single Seal.Enclosure Type 4X.

    K6 E6 and I6 Combination

    Combination CertificationsKB E5, I5, E6, and I6 Combination

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    European Certifications

    ATEX Intrinsic Safety I1 Certification No. Baseefa05ATEX0084X

    ATEX Marking II 1 GEEx ia IIC T5 (-60°C Ta 40°C)EEx ia IIC T4 (-60°C Ta 70°C)

    Input Parameters:Ui = 30 VdcIi(1) = 185 mAPi(1) = 1.0 WCi = 0 FLi = 0.97 mH

    0575

    SPECIAL CONDITIONSWhen fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    ATEX Type N CertificationN1 Certification No. Baseefa05ATEX0085X

    ATEX Marking II 3 GEEx nAnL II T5 (-40°C Ta 70°C)Input Parameters:

    Ui = 42 V dc MaxCi = 0 FLi = 0.97 mH

    SPECIAL CONDITIONSWhen fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    ATEX Flameproof CertificationE1 Certification No. KEMA99ATEX3852X

    ATEX Marking Remote Mount:Transmitter: II 2(1) G

    EEx d [ia] IIC T6 (-50°C Ta 70°C)Meter Body: II 1 G

    EEx ia IIC T6 (-50°C Ta 70°C)ATEX Marking Integral Mount: II 1/2 G

    EEx d [ia] IIC T6 (-50°C Ta 70°C) 0575

    V = 42 Vdc MaxUm = 250V

    SPECIAL CONDITIONSWhen the equipment is installed, precautions must be taken to ensure, taking into account the effect of the fluid temperature, that the ambient temperature of the electrical parts of the equipment is comprised between -50°C and 70°C. The remote mounted sensor may only be connected to the transmitter with the associated cable, supplied by the manufacturer.

    ATEX Dust Certification ND Certification No. Baseefa05ATEX0086

    ATEX Marking Ex tD A20 IP66 T90°C (-20°C Ta 70°C)Ui = 42 Vdc

    0575K1 E1, I1, N1 and ND Combination

    (1) Total for transmitter

    23

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    International IECEx Certifications

    Intrinsic SafetyI7 Certification No. IECEx BAS05.0028X

    Ex ia IIC T5 (-60°C Ta 40°C)Ex ia IIC T4 (-60°C Ta 70°C)

    Input Parameters:Ui = 30 VdcIi = 185 mAPi = 1.0 WCi = 0 FLi = 0.97 mH

    SPECIAL CONDITIONSWhen fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    Type N CertificationN7 Certification No. IECEx BAS05.0029X

    Ex nC IIC T5 (-40°C Ta 70°C) Ui = 42 V dc

    SPECIAL CONDITIONSWhen fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    Flameproof CertificationE7 Certification No. IECEx KEM05.0017X

    Marking Remote Mount:Transmitter: Ex d [ia] IIC T6 (-50°C Ta 70°C)Meter Body: Ex ia IIC T6 (-50°C Ta 70°C)

    Marking Integral Mount: Ex d [ia] IIC T6(-50°C Ta 70°C)

    V = 42 Vdc MaxUm = 250V

    SPECIAL CONDITIONSWhen the equipment is installed, particular precautions must be taken to ensure, taking into account the effect of the process fluid temperature, that the ambient temperature of the electrical parts of the equipment is comprised between -50°C and 70°C.The remote mounted sensor shall only be connected to the transmitter with the associated cable, supplied by the manufacturer.

    K7 E7, I7, and N7 Combination

    Chinese Certifications (NEPSI)

    Flameproof CertificationE3 Certification No. GYJ071327X

    Ex d [ia] IIC T6 (-50°C to 70°C)

    Intrinsic SafetyI3 Certification No. GYJ071171X

    Ex ia IIC T4/T5T4: (-60°C to 70°C)T5: (-60°C to 40°C)Input Parameters:

    Ui = 30 VdcIi = 185 mA Pi = 1.0 WCi = 0 FLi = 0.97 mH

    Type N CertificationN3 Certification No. GYJ071193X

    Ex nAnL IIC T5 (-40°C to70°C)42 Vdc Max

    K3 E3, I3, and N3 Combination

    Japanese Certifications (TIIS)

    Flameproof CertificationE4 Transmitter - Ex d [ia] T6

    Remote Sensor - Ex ia IIC T6

    Certificate DescriptionTC17816 8800D with display, without MTA optionTC17817 8800D without display, without MTA optionTC17905 8800D with display, with MTA optionTC17906 8800D without display, with MTA option

    24

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Rosemount 8800D With FOUNDATION™ Fieldbus Protocol

    North American Certifications

    Factory Mutual (FM) Approvals E5 Explosion-proof for Class I, Division 1, Groups B, C, and D.

    Dust Ignition-proof for Class II/III, Division 1, Groups E, F, and G.Temperature Code T6 (-50°C Ta 70°C)Factory SealedEnclosure Type 4X

    I5 Intrinsically safe for use in Class I, II, III Division 1, Groups A, B, C, D, E, F, G; Class I, Zone 0, AEx ia IIC T4Non-incendive for Class I, Division 2, Groups A, B, C, and D. NIFW (Non-incendive Field Wiring) when installed per Rosemount Drawing 08800-0112T4 (-50°C to 60°C)Enclosure Type 4X.

    IE FISCO/FNICO for Class I, Division 1, Groups A, B, C, and D. Class II/III, Division 1,Groups E, F, and G. T4 (-50°C to 60°C)when installed per Rosemount control drawing 08800-0116.

    K5 E5 and I5 combination

    Canadian Standards Association (CSA) ApprovalsSingle SealE6 Dust Ignition-proof for Class II and Class III, Division 1,

    Groups E, F, and G;Class I, Zone 1, Ex d[ia] IIC CSA 06.1674267T6 (-50°C to 70°C)Factory SealedSingle Seal.Enclosure Type 4X.

    I6 Intrinsically safe for use in Class I, II, III Division 1, Groups A, B, C, D, E, F, G;Non-incendive for Class I, Division 2, Groups A, B, C and DT4 (-50°C to 60°C)Single Seal.Enclosure Type 4X.

    IF FISCO/FNICO for Class I, Division 1, Groups A, B, C, and D;T4 (-50°C to 60°C)When installed per Rosemount drawing 08800-0112Enclosure Type 4X

    K6 E6 and I6 combination.

    Combination CertificationsKB E5, I5, E6, and I6 Combination

    European Certifications

    ATEX Intrinsic Safety CertificationI1 Certification No. Baseefa05ATEX0084X

    ATEX Marking II 1 GEEx ia IIC T4 (-60°C Ta 60°C)

    0575Input Parameters:Ui = 30 VdcIi = 300 mAPi = 1.3 WCi = 0 FLi = 20 H

    SPECIAL CONDITIONS FOR SAFE USE (X)When fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    ATEX FISCO/FNICOIA Certification No. Baseefa05ATEX0084X

    ATEX Marking II 1 G EEx ia IIC T4 (-60°C Ta 60°C)

    0575Input Parameters:Ui = 17.5 VdcIi = 380 mAPi = 5.32 WCi = 0 FLi < 10 H

    SPECIAL CONDITIONS FOR SAFE USE (X)When fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    ATEX Type N CertificationN1 Certification No. Baseefa05ATEX0085X

    ATEX Marking II 3 GEEx nAnL IIC T5 (-40°C Ta 70°C)Input Parameters:Ui = 32 Vdc MAXCi = 0 FLi = 20 H

    SPECIAL CONDITIONS FOR SAFE USE (X)When fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    25

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    ATEX Flameproof CertificationsE1 Certification No. KEMA 99ATEX3852X

    ATEX Marking Remote Mount:Transmitter: II 2(1) G

    EEx d [ia]IIC T6 (-50°C Ta 70°C)Meter Body: II 1 G

    EEx ia IIC T6 (-50°C Ta 70°C)ATEX Marking Integral Mount: II 1/2 GEEx d [ia] IIC T6 (-50°C Ta 70°C)

    0575V = 42 Vdc MaxUm = 250V

    SPECIAL CONDITIONSWhen the equipment is installed, particular precautions must be taken to ensure, taking into account the effect of the process fluid temperature, that the ambient temperature of the electrical parts of the equipment is comprised between -50°C and 70°C.The remote mounted sensor shall only be connected to the transmitter with the associated cable, supplied by the manufacturer.

    ATEX Dust CertificationND Certification No. Baseefa05ATEX0086

    ATEX Marking II 1 D T90°C (-20°C Ta 70°C) Ui = 42 Vdc

    0575K1 E1, I1, N1 and ND Combination

    International IECEx Certifications

    Intrinsic SafetyI7 Certification No. IECEx BAS 05.0028X

    Ex ia IIC T4 (-60°C Ta 60°C)Input Parameters:

    Ui = 30 VdcIi = 300 mAPi = 1.3 WCi = 0 FLi = 20 H

    SPECIAL CONDITIONSWhen fitted with 90V transient suppressors (T1 Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account upon installation.

    FISCO/FNICOIG Certification No. IECEx BAS 05.0028X

    Ex ia IIC T4 (-60°C Ta 60°C)Input Parameters:

    Ui = 17.5 VdcIi = 380 mAPi = 5.32 WCi = 0 FLi 10H

    Type N CertificationN7 Certification No. IECEx BAS 05.0029X

    Ex nC IIC T5 (-40°C Ta 70°C)Ui = 32 Vdc Max

    Flameproof CertificationE7 Certification No. IECEx KEM 05.0017X

    Marking Remote Mount:Transmitter: Ex d [ia] IIC T6 (-50°C Ta 70°C)Meter Body: Ex ia IIC T6 (-50°C Ta 70°C)

    Marking Integral Mount: Ex d [ia] IIC T6(-50°C Ta 70°C)

    V = 32 Vdc MaxUm = 250V

    SPECIAL CONDITIONSWhen the equipment is installed, particular precautions must be taken to ensure, taking into account the effect of the process fluid temperature, that the ambient temperature of the electrical parts of the equipment is comprised between -50°C and 70°C.The remote mounted sensor shall only be connected to the transmitter with the associated cable, supplied by the manufacturer.

    K7 E7, I7, and N7 Combination

    26

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Chinese Certifications (NEPSI)

    Flameproof CertificationE3 Certification No. GYJ071327X

    Ex d [ia] IIC T6 (-50°C to 70°C)

    Intrinsic SafetyI3 Certification No. GYJ071171X

    Ex ia IIC T6 (-60°C to 60°C)Input Parameters:

    Ui = 30 VdcIi = 300 mAPi = 1.3 WCi = 0 FLi = 20H

    FISCO/FNICOIH For FISCO:

    Certification No. GYJ071171XEx ia IIC T4 (-60°C to 60°C)

    Input Parameters:Ui = 17.5 VdcIi = 380 mAPi = 5.32 WCi = 0 FLi 10H

    For FNICO:Certification No. GYJ071193X

    Ex nAnL IIC T5 (-40°C to 70°C)17.5 Vdc Max

    Type N CertificationN3 Certification No. GYJ071193X

    Ex nAnL IIC T5 (-40°C to70°C)32 Vdc Max

    K3 E3, I3, and N3 Combination

    Japanese Certifications (TIIS)

    Flameproof Certification

    E4 TIIS FlameproofTransmitter - Ex d [ia] T6Remote Sensor - Ex ia IIC T6Certificate DescriptionTC17816 8800D with display, without MTA optionTC17817 8800D without display, without MTA optionTC17905 8800D with display, with MTA optionTC17906 8800D without display, with MTA option

    27

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Dimensional Drawings

    Figure 2. Flanged-Style Flowmeter Dimensional Drawings (1/2-through 12-in./15 through 300 mm Line Sizes)

    Terminal Cover

    Display Option

    Diameter3.06 (78)

    Diameter B

    3.20 (81)2.56 (65)

    2.85 (72)

    1.10(28)

    1.00 (25.4)

    C

    A

    2.00 (51)

    NOTEDimensions are in inches (millimeters)

    2.00 (51)

    A

    C

    D

    Diagram illustrated without MTA Option Diagram illustrated with MTA Option

    28

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Table 19. Flanged-Style Flowmeter (1/2-through 2-in./15 through 50 mm Line Sizes)Nominal Size

    in. (mm)Flange Rating

    Face-to-face A in. (mm)

    A-ANSI RTJ in. (mm)

    Diameter B in. (mm)

    C in. (mm)

    Din. (mm)

    Weight(1) lb (kg)

    ½ (15) Class 150Class 300Class 600Class 900

    6.8 (173)7.2 (183)7.7 (196)8.3 (211)

    –7.6 (193)7.6 (193)8.3 (211)

    0.54 (13,7)0.54 (13,7)0.54 (13,7)0.54 (13,7)

    7.6 (193)7.6 (193)7.6 (193)7.6 (193)

    ––––

    9.1 (4,1)10.4 (4,7)10.8 (4,9)15.6 (7,1)

    PN 16/40PN 100PN 160

    6.1 (155)6.6 (168)6.6 (168)

    –––

    0.54 (13,7)0.54 (13,7)0.54 (13,7)

    7.6 (193)7.6 (193)7.6 (193)

    –––

    10.4 (4,7)12.4 (5,6)12.4 (5,6)

    JIS 10K/20KJIS 40K

    6.3 (160)7.3 (185)

    ––

    0.54 (13,7)0.54 (13,7)

    7.6 (193)7.6 (193)

    ––

    10.2 (4,6)13.7 (6,2)

    1 (25) Class 150Class 300Class 600Class 900Class 1500

    7.5 (191)8.0 (203)8.5 (216)9.4 (239)9.4 (239)

    8.0 (203)8.5 (216)8.5 (216)9.4 (239)9.4 (239)

    0.95 (24,1)0.95 (24,1)0.95 (24,1)0.95 (24,1)0.95 (24,1)

    7.7 (196)7.7 (196)7.7 (196)7.7 (196)7.7 (196)

    –––––

    12.3 (5,6)15.0 (6,8)15.8 (7,2)24.4 (11,1)24.4 (11,1)

    PN 16/40PN 100PN 160PN 250

    6.2 (157)7.7 (195)7.7 (195)7.8 (198)

    ––––

    0.95 (24,1)0.95 (24,1)0.95 (24,1)0.95 (24,1)

    7.7 (196)7.7 (196)7.7 (196)7.7 (196)

    ––––

    13.6 (6,2)19.6 (8,9)19.6 (8,9)

    23.7 (10,7)JIS 10K/20K

    JIS 40K6.5 (165)7.8 (198)

    ––

    0.95 (24,1)0.95 (24,1)

    7.7 (196)7.7 (196)

    ––

    14.0 (6,3)17.7 (7,9)

    1 ½ (40) Class 150Class 300Class 600Class 900Class 1500

    8.2 (208)8.7 (221)9.3 (236)

    10.3 (262)10.3 (262)

    8.7 (221)9.2 (234)9.3 (236)

    10.3 (262)10.3 (262)

    1.49 (37,8)1.49 (37,8)1.49 (37,8)1.49 (37,8)1.49 (37,8)

    8.1 (206)8.1 (206)8.1 (206)8.1 (206)8.1 (206)

    –––––

    17.6 (8,0)23.0 (10,5)25.5 (11,6)36.6 (16,6)36.6 (16,6)

    PN 16/40PN 100PN 160PN 250

    6.9 (175)8.2 (208)8.4 (213)9.6 (244)

    ––––

    1.49 (37,8)1.49 (37,8)1.49 (37,8)1.49 (37,8)

    8.1 (206)8.1 (206)8.1 (206)8.1 (206)

    ––––

    19,4 (8,8)28.0 (12,7)29.5 (13,4)39.2 (17,8)

    JIS 10K/20KJIS 40K

    7.3 (185)8.4 (213)

    ––

    1.49 (37,8)1.49 (37,8)

    8.1 (206)8.1 (206)

    ––

    18.6 (8,4)25.5 (11,6)

    2 (50) Class 150Class 300Class 600Class 900Class 1500

    9.2 (234)9.7 (246)

    10.5 (267)12.7 (323)12.7 (323)

    9.7 (246)10.4 (264)10.7 (271)12.9 (328)12.9 (328)

    1.92 (48,8)1.92 (48,8)1.92 (48,8)1.92 (48,8)1.67 (42,4)

    8.5 (216)8.5 (216)8.5 (216)8.5 (216)8.5 (216)

    4.7 (119)4.7 (119)4.7 (119)4.7 (119)4.7 (119)

    22.0 (10,1)26.1 (11,8)29.8 (13,5)59.5 (27,0)61.9 (28,1)

    PN 16/40PN 64PN 100PN 160PN 250

    8.0 (203)9.1 (231)9.6 (244)

    10.2 (259)10.9 (277)

    –––––

    1.92 (48,8)1.92 (48,8)1.92 (48,8)1.92 (48,8)1.67 (42,4)

    8.5 (216)8.5 (216)8.5 (216)8.5 (216)8.5 (216)

    4.7 (119)4.7 (119)4.7 (119)4.7 (119)4.7 (119)

    23.2 (10,5)30.8 (13,9)36.5 (16,6)38.8 (17,6)47.4 (21,5)

    JIS 10KJIS 20KJIS 40K

    7.7 (195)8.2 (208)9.8 (249)

    –––

    1.92 (48,8)1.92 (48,8)1.92 (48,8)

    8.5 (216)8.5 (216)8.5 (216)

    4.7 (119)4.7 (119)4.7 (119)

    19.5 (8,8)20.4 (9,3)

    28.5 (12,9)

    (1) Add 0.2 lb (0,1 kg) for display option.

    29

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Table 20. Flanged-Style Flowmeter (3-through 6-in./80 through 150 mm Line Sizes) (Refer to previous drawing)Nominal Size

    in. (mm) Flange RatingFace-to-face A in.

    (mm)A ANSI RTJ

    in. (mm)Diameter B in.

    (mm) C in. (mm)D

    in. (mm) Weight(1) lb (kg)3 (80) Class 150

    Class 300Class 600Class 900Class 1500

    9.9 (251)10.6 (269)11.4 (290)12.9 (328)14.1 (358)

    10.4 (264)11.2 (284)11.5 (292)13.0 (330)14.2 (361)

    2.87 (72,9)2.87 (72,9)2.87 (72,9)2.87 (72,9)2.66 (67,6)

    9.1 (231)9.1 (231)9.1 (231)9.1 (231)9.1 (231)

    5.3 (135)5.3 (135)5.3 (135)5.3 (135)5.3 (135)

    37.2 (16,9)46.5 (21,1)52.6 (23,8)76.1 (34,5)

    108.9 (49,4)PN 16/40

    PN 64PN 100PN 160PN 250

    8.9 (226)10.0 (254)10.5 (267)11.1 (282)12.4 (315)

    –––––

    2.87 (72,9)2.87 (72,9)2.87 (72,9)2.87 (72,9)2.60 (66.0)

    9.1 (231)9.1 (231)9.1 (231)9.1 (231)9.1 (231)

    5.3 (135)5.3 (135)5.3 (135)5.3 (135)5.3 (135)

    36.6 (16,6)45.3 (20,6)54.7 (24,8)59.6 (27,0)90.1 (40,9)

    JIS 10KJIS 20KJIS 40K

    7.9 (200)9.3 (235)11.0 (280)

    –––

    2.87 (72,9)2.87 (72,9)2.87 (72,9)

    9.1 (231)9.1 (231)9.1 (231)

    5.3 (135)5.3 (135)5.3 (135)

    28.0 (12,7)35.4 (16,1)50.3 (22,8)

    4 (100) Class 150Class 300Class 600Class 900Class 1500

    10.3 (262)11.0 (279)12.8 (325)13.8 (351)14.5 (368)

    10.8 (274)11.6 (295)12.9 (328)13.9 (353)14.6 (371)

    3.79 (96,3)3.79 (96,3)3.79 (96,3)3.79 (96,3)3.40 (86,4)

    9.6 (244)9.6 (244)9.6 (244)9.6 (244)9.6 (244)

    5.9 (150)5.9 (150)5.9 (150)5.9 (150)5.9 (150)

    51.3 (23,3)71.5 (32,4)97.5 (44,2)

    120.8 (54,8)162.6 (73,8)

    PN 16PN 40PN 64

    PN 100PN 160PN 250

    8.4 (213)9.4 (239)

    10.4 (264)11.3 (287)12.1 (307)13.7 (348)

    ––––––

    3.79 (96,3)3.79 (96,3)3.79 (96,3)3.79 (96,3)3.79 (96,3)3.40 (86,4)

    9.6 (244)9.6 (244)9.6 (244)9.6 (244)9.6 (244)9.6 (244)

    5.9 (150)5.9 (150)5.9 (150)5.9 (150)5.9 (150)5.9 (150)

    40.4 (18,2)49.5 (22,4)62.5 (28,3)78.9 (35,8)86.2 (39,1)

    143.4 (65,0)JIS 10KJIS 20KJIS 40K

    8.7 (220)8.7 (220)11.8 (300)

    –––

    3.79 (96,3)3.79 (96,3)3.79 (96,3)

    9.6 (244)9.6 (244)9.6 (244)

    5.9 (150)5.9 (150)5.9 (150)

    37.5 (17,0)45.4 (20,6)75.8 (34,4)

    6 (150) Class 150Class 300Class 600Class 900Class 1500

    11.6 (295)12.3 (315)14.3 (363)16.1 (409)18.6 (472)

    12.1 (307)13.0 (330)14.5 (368)16.2 (411)18.8 (478)

    5.7 (144,8)5.7 (144,8)5.7 (144,8)

    5.14 (130,6)5.14 (130,6)

    10.8 (274)10.8 (274)10.8 (274)10.8 (274)10.8 (274)

    7.4 (188)7.4 (188)7.4 (188)7.4 (188)7.4 (188)

    81 (37)120 (55)187 (85)

    277.9 (126,0)375.8 (170,4)

    PN 16PN 40PN 64

    PN 100PN 160PN 250

    8.9 (226)10.5 (267)12.1 (307)13.6 (345)14.7 (373)17.2 (437)

    ––––––

    5.7 (144,8)5.7 (144,8)5.7 (144,8)5.7 (144,8)

    5.14 (130,6)5.14 (130,6)

    10.8 (274)10.8 (274)10.8 (274)10.8 (274)10.8 (274)10.8 (274)

    7.4 (188)7.4 (188)7.4 (188)7.4 (188)7.4 (188)7.4 (188)

    66 (30)86 (39)

    130 (59)160 (73)

    202.2 (91.7)312 (141,6)

    JIS 10KJIS 20KJIS 40K

    10.6 (270)10.6 (270)14.2 (360)

    –––

    5.7 (144,8)5.7 (144,8)5.7 (144,8)

    10.8 (274)10.8 (274)10.8 (274)

    7.4 (188)7.4 (188)7.4 (188)

    70 (32)88 (40)

    166 (75)

    (1) Add 0.2 lb (0,1 kg) for display option.

    30

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    Table 21. Flanged-Style Flowmeter (8-through 12-in./200 through 300 mm Line Sizes) (Refer to previous drawing)Nominal Size

    in. (mm)Flange Rating

    Face-to-face A in. (mm)

    A ANSI RTJ in. (mm)

    Diameter B in. (mm) C in. (mm)

    Din. (mm) Weight(1) lb (kg)

    8 (200) Class 150Class 300Class 600Class 900Class 1500

    13.5 (343)14.3 (363)16.5 (419)18.8 (478)22.8 (579)

    14.0 (356)14.9 (378)16.7 (424)18.9 (480)23.2 (589)

    7.55 (191,8)7.55 (191,8)7.55 (191,8)6.62 (168,1)6.62 (168,1)

    11.7 (297)11.7 (297)11.7 (297)11.7 (297)11.7 (297)

    8.3 (211)8.3 (211)8.3 (211)8.3 (211)8.3 (211)

    141.6 (64,2)198.7 (90,1)

    298.6 (135,2)479.2 (217,4)652.4 (259,9)

    PN 10PN 16PN 25PN 40PN 64PN 100PN 160PN250

    10.4 (264)10.4 (264)11.8 (300)12.5 (318)14.2 (361)15.8 (401)16.6 (422)20.5 (521)

    ––––––––

    7.55 (191,8)7.55 (191,8)7.55 (191,8)7.55 (191,8)7.55 (191,8)7.55 (191,8)6.62 (168,1)6.62 (168,1)

    11.7 (297)11.7 (297)11.7 (297)11.7 (297)11.7 (297)11.7 (297)11.7 (297)11.7 (297)

    8.3 (211)8.3 (211)8.3 (211)8.3 (211)8.3 (211)8.3 (211)8.3 (211)8.3 (211)

    110.5 (50,1)109.4 (49,6)137.7 (62,5)156.5 (71,0)217.1 (98,5)

    282.7 (128,2)346.6 (157,2)570.5 (258,8)

    JIS 10KJIS 20KJIS 40K

    12.2 (310)12.2 (310)16.5 (419)

    –––

    7.55 (191,8)7.55 (191,8)7.55 (191,8)

    11.7 (297)11.7 (297)11.7 (297)

    8.3 (211)8.3 (211)8.3 (211)

    110.1 (49,9)134.5 (61,0)255.7 (116,0)

    10 (250) Class 150Class 300Class 600

    14.5 (368)15.8 (401)19.0 (483)

    15.0 (381)16.4 (417)19.2 (488)

    9.56 (242,8)9.56 (242,8)9.56 (242,8)

    12.8 (325)12.8 (325)12.8 (325)

    9.3 (236)9.3 (236)9.3 (236)

    197.7 (89,7)286.2 (129,8)477.9 (216,9)

    PN 10PN 16PN 25PN 40PN 64PN 100

    11.9 (302)12.0 (307)13.5 (343)14.8 (376)16.4 (417)18.9 (480)

    ––––––

    9.56 (242,8)9.56 (242,8)9.56 (242,8)9.56 (242,8)9.56 (242,8)9.56 (242,8)

    12.8 (325)12.8 (325)12.8 (325)12.8 (325)12.8 (325)12.8 (325)

    9.3 (236)9.3 (236)9.3 (236)9.3 (236)9.3 (236)9.3 (236)

    157.1 (71,3)161.9 (73,5)198.6 (90,1)246.8 (111,9)308.2 (139,8)445.2 (201,9)

    JIS 10KJIS 20KJIS 40K

    14.5 (368)14.5 (368)18.1 (460)

    –––

    9.56 (242,8)9.56 (242,8)9.56 (242,8)

    12.8 (325)12.8 (325)12.8 (325)

    9.3 (236)9.3 (236)9.3 (236)

    174.5 (79,1)221.8 (100,6)378.5 (171,7)

    12 (300) Class 150Class 300Class 600

    16.8 (427)18.0 (457)20.5 (521)

    17.3 (439)18.6 (472)20.6 (523)

    11.38 (289,0)11.38 (289,0)11.38 (289,0)

    13.7 (348)13.7 (348)13.7 (348)

    10.1 (256)10.1 (256)10.1 (256)

    297.5 (134,9)415.7 (188,6)595.4 (270,1)

    PN 10PN 16PN 25PN 40PN 64PN 100

    13.1 (333)13.9 (353)15.0 (381)16.8 (427)18.8 (478)21.2 (538)

    ––––––

    11.38 (289,0)11.38 (289,0)11.38 (289,0)11.38 (289,0)11.38 (289,0)11.38 (289,0)

    13.7 (348)13.7 (348)13.7 (348)13.7 (348)13.7 (348)13.7 (348)

    10.1 (256)10.1 (256)10.1 (256)10.1 (256)10.1 (256)10.1 (256)

    204.1 (92,6)224.6 (101,9)269.4 (122,2)347.9 (157,8)431.2 (195,6)644.1 (292,2)

    JIS 10KJIS 20KJIS 40K

    15.7 (399)15.7 (399)19.6 (498)

    –––

    11.38 (289,0)11.38 (289,0)11.38 (289,0)

    13.7 (348)13.7 (348)13.7 (348)

    10.1 (256)10.1 (256)10.1 (256)

    222.9 (101,1)284.2 (128,9)493.8 (224,0)

    (1) Add 0.2 lb (0,1 kg) for display option.

    31

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    Figure 3. Rosemount 8800DR Reducer Flowmeter Dimensional Drawings (1-through 12-in./25 through 300 mm Line Sizes)

    Diameter B

    DisplayOption

    1.00 (25)

    3.20 (81) 2.85

    (72)2.56 (65)

    1.10(28)

    Diameter3.06 (78)

    Terminal Cover

    NOTEDimensions are in inches (millimeters)

    2.00 (51)

    A

    C C

    A

    2.00 (51)

    D

    Diagram illustrated without MTA Option Diagram illustrated with MTA Option

    32

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    TABLE 22. Reducer Flowmeter (1-through 3-in./25 through 80 mm Line Sizes)Nominal Size

    in. (mm)Flange Rating

    Face-to-face A in. (mm)

    A-ANSI RTJ in. (mm)

    Diameter B in. (mm)

    C in. (mm) D in. (mm)

    Weight(1) lb (kg)

    1 (25) Class 150 7.5 (191) 8.0 (203) 0.54 (13,7) 7.6 (193) – 11.6 (5,2)Class 300 8.0 (203) 8.5 (216) 0.54 (13,7) 7.6 (193) – 14.2 (6,4)Class 600 8.5 (216) 8.5 (216) 0.54 (13,7) 7.6 (193) – 15.1 (6,9)Class 900 9.4 (239) 9.4 (239) 0.54 (13,7) 7.6 (193) – 20.7 (9.4)PN 16/40 6.2 (157) – 0.54 (13,7) 7.6 (193) – 12.6 (5,7)PN 100 7.7 (195) – 0.54 (13,7) 7.6 (193) – 18.4 (8,4)

    1 ½ (40) Class 150 8.2 (208) 8.7 (221) 0.95 (24,1) 7.7 (196) – 15.8 (7,20)Class 300 8.7 (221) 9.2 (234) 0.95 (24,1) 7.7 (196) – 21.2 (9,6)Class 600 9.3 (236) 9.3 (236) 0.95 (24,1) 7.7 (196) – 23.8 (10,8)Class 900 10.3 (262) 10.3 (262) 0.95 (24,1) 7.7 (196) – 35.0 (15,9)PN 16/40 6.9 (175) – 0.95 (24,1) 7.7 (196) – 17.5 (7,9)PN 100 8.2 (208) – 0.95 (24,1) 7.7 (196) – 26.2 (11,9)PN 160 8.4 (213) – 0.95 (24,1) 7.7 (196) – 27.7 (12,6)

    2 (50) Class 150 9.2 (236) 9.7 (249) 1.49 (37,8) 8.1 (206) 4.7 (119) 22.6 (10,3)Class 300 9.7 (249) 10.4 (264) 1.49 (37,8) 8.1 (206) 4.7 (119) 26.8 (12,1)Class 600 10.5 (267) 10.6 (269) 1.49 (37,8) 8.1 (206) 4.7 (119) 30.6 (13,9)Class 900 12.7 (323) 12.9 (328) 1.49 (37,8) 8.1 (206) 4.7 (119) 60.8 (27,6)PN 16/40 8.0 (203) – 1.49 (37,8) 8.1 (206) 4.7 (119) 23.5 (10,7)

    PN 64 9.1 (231) – 1.49 (37,8) 8.1 (206) 4.7 (119) 31.3 (14,2)PN 100 9.6 (244) – 1.49 (37,8) 8.1 (206) 4.7 (119) 37.2 (16,9)PN 160 10.2 (259) – 1.49 (37,8) 8.1 (206) 4.7 (119) 39.6 (18,0)

    3 (80) Class 150 9.9 (251) 10.4 (264) 1.92 (48,8) 8.5 (216) 5.3 (134) 33.2 (15,0)Class 300 10.6 (269) 11.2 (284) 1.92 (48,8) 8.5 (216) 5.3 (134) 42.7 (19,4)Class 600 11.4 (290) 11.5 (292) 1.92 (48,8) 8.5 (216) 5.3 (134) 49.5 (22,4)Class 900 12.9 (328) 13.0 (330) 1.92 (48,8) 8.5 (216) 5.3 (134) 73.3 (33,2)PN 16/40 8.9 (226) – 1.92 (48,8) 8.5 (216) 5.3 (134) 33.3 (15,1)

    PN 64 10.0 (254) – 1.92 (48,8) 8.5 (216) 5.3 (134) 42.4 (19,3)PN 100 10.5 (267) – 1.92 (48,8) 8.5 (216) 5.3 (134) 52.2 (23,7)PN 160 11.1 (282) – 1.92 (48,8) 8.5 (216) 5.3 (134) 57.9 (26,3)

    (1) Add 0.2 lb (0,1 kg) for display option.

    33

  • Product Data Sheet00813-0100-4004, Rev HA

    April 2010Rosemount 8800D

    TABLE 23. Reducer Flowmeter (4-through 12-in./100 through 300mm Line Sizes) (Refer to previous drawing)Nominal Size

    in. (mm)Flange Rating

    Face-to-face A in. (mm)

    A ANSI RTJ in. (mm)

    Diameter B in. (mm) C in. (mm) D in. (mm) Weight(1) lb (kg)

    4 (100) Class 150 10.3 (262) 10.8 (274) 2.87 (72,9) 9.1 (231) 5.9 (149) 46.3 (21,0)Class 300 11.0 (279) 11.6 (295) 2.87 (72,9) 9.1 (231) 5.9 (149) 67.0 (30,4)Class 600 12.8 (325) 12.9 (328) 2.87 (72,9) 9.1 (231) 5.9 (149) 94.3 (42,8)Class 900 13.8 (351) 13.9 (353) 2.87 (72,9) 9.1 (231) 5.9 (149) 118.0 (53,5)

    PN 16 8.4 (213) – 2.87 (72,9) 9.1 (231) 5.9 (149) 36.4 (16,5)PN 40 9.4 (239) – 2.87 (72,9) 9.1 (231) 5.9 (149) 45.9 (20,8)PN 64 10.4 (264) – 2.87 (72,9) 9.1 (231) 5.9 (149) 59.7 (27,1)

    PN 100 11.3 (287) – 2.87 (72,9) 9.1 (231) 5.9 (149) 76.7 (34,8)PN 160 12.1 (307) – 2.87 (72,9) 9.1 (231) – 84.7 (38,4)

    6 (150) Class 150 11.6 (295) 12.1 (307) 3.79 (96,3) 9.6 (244) 7.4 (187) 70.3 (31,9)Class 300 12.3 (312) 13.0 (330) 3.79 (96,3) 9.6 (244) 7.4 (187) 113.1 (51,3)Class 600 14.3 (363) 14.4 (366) 3.79 (96,3) 9.6 (244) 7.4 (187) 185.1 (84,0)Class 900 16.1 (409) 16.2 (411) 3.79 (96,3) 9.6 (244) 7.4 (187) 246.3 (111,7)

    PN 16 8.9 (226) – 3.79 (96,3) 9.6 (244) 7.4 (187) 59.2 (26,9)PN 40 10.5 (267) – 3.79 (96,3) 9.6 (244) 7.4 (187) 81.9 (37,2)PN 64 12.1 (307) – 3.79 (96,3) 9.6 (244) 7.4 (187) 125.4 (56,9)

    PN 100 13.6 (345) – 3.79 (96,3) 9.6 (244) 7.4 (187) 162.3 (73,6)PN 160 14.7 (373) – 3.79 (96,3) 9.6 (244) 7.4 (187) 187.9 (85,2)

    8 (200) Class 150 13.5 (343) 14.0 (356) 5.70 (144,8) 10.8 (274) 8.3 (210) 124 (56)Class 300 14.3 (363) 14.9 (378) 5.70 (144,8) 10.8 (274) 8.3 (210) 186 (84)Class 600 16.5 (419) 16.7 (424) 5.70 (144,8) 10.8 (274) 8.3 (210) 295 (134)

    PN 10 10.4 (264) – 5.70 (144,8) 10.8 (274) 8.3 (210) 91 (41)PN 16 10.4 (264) – 5.70 (144,8) 10.8 (274) 8.3 (210) 91 (41)PN 25 11.8 (300) – 5.70 (144,8) 10.8 (274) 8.3 (210) 124 (56)PN 40 12.5 (318) – 5.70 (144,8) 10.8 (274) 8.3 (210) 145 (66)PN 64 14.2 (361) – 5.70 (144,8) 10.8 (274) 8.3 (210) 211 (96)

    PN 100 15.8 (401) – 5.70 (144,8) 10.8 (274) 8.3 (210) 283 (128)10 (250) Class 150 14.5 (368) 15.0 (381) 7.55 (191,8) 11.7 (297) 9.3 (236) 182.4 (82,8)

    Class 300 15.8 (401) 16.4 (417) 7.55 (191,8) 11.7 (297) 9.3 (236) 281.7 (127,8)Class 600 19.0 (483) 19.2 (488) 7.55 (191,8) 11.7 (297) 9.3 (236) 489.9 (222,2)

    PN 10 11.9 (302) – 7.55 (191,8) 11.7 (297) 9.3 (236) 138.6 (62,9)PN 16 12.0 (305) – 7.55 (191,8) 11.7 (297) 9.3 (236) 148.6 (67,4)PN 25 13.5 (343) – 7.55 (191,8) 11.7 (297) 9.3 (236) 191.0 (86,6)PN 40 14.8 (376) – 7.55 (191,8) 11.7 (297) 9.3 (236) 245.8 (111,5)PN 64 16.4 (417) – 7.55 (191,8) 11.7 (297) 9.3 (236) 314.1 (142,5)

    PN 100 18.9 (480) – 7.55 (191,8) 11.7 (297) 9.3 (236) 463.5 (210,2)12 (300) Class 150 16.8 (427) 17.3 (439) 9.56 (242,8) 12.8 (325) 10.1 (256) 282.0 (127,9)

    Class 300 18.0 (457) 18.6 (472) 9.56 (242,8) 12.8 (325) 10.1 (256) 412.2 (187,0)Class 600 20.5 (521) 20.6 (523) 9.56 (242,8) 12.8 (325) 10.1 (256) 609.9 (276,6)

    PN 10 13.1 (333) – 9.56 (242,8) 12.8 (325) 10.1 (256) 188.3 (85,4)PN 16 13.9 (353) – 9.56 (242,8) 12.8 (325) 10.1 (256) 211.8 (96,1)PN 25 15.0 (381) – 9.56 (242,8) 12.8 (325) 10.1 (256) 262.4 (119,1)PN 40 16.8 (427) – 9.56 (242,8) 12.8 (325) 10.1 (256) 349.9 (158,7)PN 64 18.8 (478) – 9.56 (242,8) 12.8 (325) 10.1 (256) 444.2 (201,5)

    PN 100 21.2 (538) – 9.56 (242,8) 12.8 (325) 10.1 (256) 672.1 (304,8)

    (1) Add 0.2 lb (0,1 kg) for display option.

    34

  • Product Data Sheet00813-0100-4004, Rev HAApril 2010 Rosemount 8800D

    35

    Figure 4. Wafer-Style Dimensional Drawings (1/2-through 8-in./15 through 200 mm Line Sizes)

    2.00 (51)

    E

    A

    Diameter D

    NOTEDimensions are in inches (millimeters)Electronics housing may be rotated in 90 degree increments

    2.00 (51)

    Terminal Cover

    Diameter B

    DisplayOption

    1.00 (25)

    3.20 (81)

    2.85 (72)

    2.56 (65)

    1.10 (28)

    C

    Diameter3.06 (78)

    Table 24. Rosemount 8800D Wafer-Style MeterNominal Size

    in. (mm)Face-to-face A

    in. (mm)Diameter B

    in. (mm)C

    in. (mm)Diameter D

    in. (mm)E

    in. (mm)Weight

    lb (kg)(1)

    ½ (15) 2.56 (65) 0.52