MasterHP
100-600 kVA3:3
ONLINE
VFITYPE
E-MEDICALDATACENTER INDUSTRY TRANSPORT
SmartGridready
Service1st start
EMERGENCY
Flywheelcompatible
SupercapsUPS
6
HIGHLIGHTS
• High eciency (up to 98.5%)
• IGBT-based rectifertechnology
• Compact and reliable
• Galvanic isolation• High overload capacity
• LCD Display
The Master HP series from 100 to 600 kVA
is the Riello UPS solution for installations
requiring high energ ecienc and
maximum power availability.
Master HP Series provides maximum
protection and power qualit for data
centres and industrial loads. The UPS has
an IGBT-based rectier, DSP (Digital Signal
Processors) technolog and provides true
On-line, double conversion powerprotection, (VFI SS 11 - Voltage and
Frequenc Independent in accordance with
IEC EN 62040-3).
Maximised cost savingsThe build specications oered b the
Master HP range and the exceptional level
of ecienc help to absorb the TCO, from
the installation stage to dail operation,
reducing power costs for the UPS and air
conditioning sstem and installation area
costs thanks to it s reduced size and weight.
Thanks to the ability to monitor the
mains input qualit and to select the bestoperating mode based on the interference
present (Smart Active mode) or circular
redundanc (Parallel Energ Saving mode,
which allows the UPS to regulate available
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 2/8
8 5 0
1
9 0 0
8 0 0 8 5 010 0 0 15 0 0
210 0 1 0
0 0 1 0 0 0
1 9
0 0
1 9 0 0
1
9 0 0
MHT 100MHT 120
MHT 300MHT 400
MHT 500MHT 600
MHT 160 - MHT 200MHT 250
DIMENSIONS
capacit based on the immediate demands
of the load, automaticall switching to
standb in the event of excess capacit), the
Master HP oers high levels of ecienc
also for partial loads, resulting in reduced
operating costs.
Power continuityFor ears, Riello UPS has developed and
supplied solutions for dealing with the
dierent requirements and problems that
inevitabl arise in critical applications.
Riello UPS oers exible, high-availabilit
solutions that are able to adapt to dierent
sstem structures and critical levels. Riello
UPS creates UPS sstems that can tolerate a
number of component or subsstem failures,
while continuing to operate normall,
providing power without interruption. This
is achieved b careful design, installing
redundant elements, eliminating commonfailure points, scheduling maintenance
activities and controlling and supervising
the sstem operating parameters and
environment. The TEC service team is read
to provide guidance and advice on projects.
Complete galvanic isolationMaster HP UPS feature an output isolation
transformer (on the inverter), inside the
UPS cabinet, providing galvanic isolation of
the load towards the batter and improved
versatilit in sstem conguration, allowing:• Complete galvanic isolation for medical
applications and critical infrastructures
• two trul separate network inputs (main
and emergenc), coming from two
dierent power sources (with dierent
neutrals); this is particularl well suited
to parallel sstems in order to ensure
selectivit between the t wo sources, thus
improving the reliability of the entire
installation;
• Installation in networks without neutral.
Housing the transformer inside the cabinet
allows for a signicant reduction in the
footprint, providing space savings.
Zero impact sourceThe Master HP series features the added
advantages of the Zero Impact Source
formula oered b an IGBT-based rectier
assembly. This eliminates problems
connected with installation in networks
with limited power capacit, where the UPS
is supplied b a generator set or anwhere
there are compatibilit problems with loads
that generate current harmonics. Master HPseries UPS have zero impact on the power
suppl source, whether it is a mains grid or
generator set:
• input current distortion < 3%
• input power factor 0.99
• power walk-in function that ensures
progressive rectier start up
• start-up dela function, to restart the
rectiers when mains power is restored if
there are several UPS in the system.
This provides savings in installation costs
via:
• a smaller electrical infrastructure.
• smaller circuit protection devices
• less wiring.
Master HP also performs the role of a lter
and power factor corrector, protecting the
upstream power suppl from an harmonics
and reactive power generated b the
consumers.
FlexibilityMaster HP is suitable for a wide range of
applications including IT and the most
demanding industrial environmentsand processes. With several operational
congurations including On-Line, Eco,
Smart Active, Stand B, Frequenc
Converter and Voltage Stabiliser. A broad
range of accessories and options, complex
congurations and sstem architectures can
be achieved to guarantee maximum power
availabilit and the option to add new UPS
without interruption to existing users.
Using the Riello UPS Group Snchroniser
(UGS) and Parallel Sstems Joiner (PSJ),
sophisticated inter group parallel andredundant sstems can be achieved to
provide the highest possible levels of
resilience and availabilit.
Specic solutionsThe UPS can be adapted to meet our
requirements. Contact our TEC team to
discuss specic solutions and options not
listed in this catalogue.
Battery care system: maximumbattery care
The Master HP range uses the sophisticated
Batter Care Sstem, also available on the
Master MPS models, which optimises batter
performance in order to extend the batter
life for as long as possible.
Main features• High ecienc (up to 98.5%)
• Compact size: e.g.: onl 0.85 m2 for the
Master HP 250 kVA
• Reduced weight
• Double load protection, both electronic
and galvanic, towards the batter.
The entire Master HP range is suitable for
use in a wide range of applications. Thanks
to the exibilit of conguration, available
options and accessories, it is suitable for
suppling an tpe of load, e.g. capacitive
loads such as blade servers etc.
Power suppl reliabilit and availabilit
are ensured for critical applications
b distributed or centralised parallel
congurations of up to 8 units, for redundant(N+1) or power parallel congurations and
all the dierent congurations oered b
the Master MPS range.
Smart Grid ReadyBeing smart grid read, Master HP allows for
the implementation of power accumulation
solutions, and at the same time ensures
extremel high levels of ecienc. It is
also able to independentl select the
most ecient operating method based on
the status of the grid. Master HP UPS arealso able to electronicall interface with
the energ manager using the smart gr id
communication network.
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 3/8
1 9 0 0
8 6 0 8 0 0
BB 1 9 0 0
4 0 0 8 5 0
1 9 0 0
4 0 0 1 0 0 0
TCE TCE
1
9 0 0
6 4 0 8 0 0
1
9 0 0
8 0 0 8 0 0
1 9 0 0
1 2 0 0 1 0
0 0
OPTIONS DETAILS
NOTE : The layout of controls and connectors may vary based on the size of the UPS
SWOUT
SWMBCOMMUNICATIONS
INTERFACE SLOT
PARALLELINTERFACE
UGS INTERFACE
MULTI I/OMODEM INTERFACE
REMOTEALARM
RS232REPOCONNECTORS
DRy CONTACTS
SWIN
FAN FUSES
SWByP
MHT (detail of front)
BATTERY BOX
MODELS BB 1900 480V6 / BB 1900 480V7
BB 1900 480V8 / BB 1900 480V9
UPS MODELS MHT 100-600
Dimen-sions(mm)
CABINETS WITH TOP ACCESS FOR CABLES
MODELS TCE MHT 100-250 TCE MHT 300-600
UPS MODELS MHT 100-250 MHT 300-600
Dimensions(mm)
THREE-PHASE ISOLATION TRANSFORMERS
MODELS TBX 100 T TBX 160 T TBX 200 T TBX 250 T TBX 300 T TBX 600 T
UPS MODELS MPT 100-160 / MHT 100-160 MPT 200 / MHT 200-250 MHT 300-600
Dimensions
(mm)
SOFTWARE
PowerShield3
PowerNetGuard
ACCESSORIES
NETMAN 101 PLUS
NETMAN 102 PLUSNETMAN 202 PLUS
MULTICOM 301
MULTICOM 302
MULTICOM 351
MULTICOM 352
MULTICOM 401
MULTI I/O
Interface kit AS400
MULTIPANEL
RTG 100
56K Modem
GSM Modem
PRODUCT ACCESSORIES
Isolation transformer
Snchronisation device (UGS):see Master MPS on page 84
Hot connection device (PSJ): see MasterMPS on page 84
Generator interface
Parallel conguration kit (Closed Loop)
Batter cabinets empt or forextended runtimes
Top Cable Entr cabinets
IP rating IP31/IP42
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 4/8
D A T M H T F 3 Y 1 3 G R E N
MODELS MHT 100 MHT 120 MHT 160 MHT 200 MHT 250 MHT 300 MHT 400 MHT 500 MHT 600
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Frequenc 45 - 65 Hz
Power factor > 0,99
Harmonic current distortion <3% THDi
Soft start 0 - 100% in 120’’ (selectable)Frequenc tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bpass line
BYPASS
Nominal voltage 360-400-420 Vac three-phase + N
Nominal frequenc 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 100 120 160 200 250 300 400 500 600
Active power (kW) 90 108 144 180 225 270 360 450 540
Number of phases 3 + N
Nominal voltage 380 - 400 - 415 Vac three-phase + N (selectable)
Static stabilit ± 1%
Dnamic stabilit ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequenc stabilit on battery 0.05%
Frequenc 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flwheels
Ripple current Zero
Recharge voltagecompensation
-0.5 Vx°C
INFO FOR INSTALLATION
Weight (kg) 656 700 800 910 1000 1400 1700 2100 2400
Dimensions (WxDxH) (mm) 800 x 850 x 1900 1000 x 850 x 1900 1500 x 1000 x 1900 2100 x 1000 x 1900
Remote signals dr contacts (congurable)
Remote controls ESD and bpass (congurable)
Communications Double RS232 + dr contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidit <95% non-condensing
Colour Dark gre RAL 7016
Noise level at 1 m 63 - 68 dBA 70 - 72 dBA
IP rating IP20 (others on request)
Smart Active ecienc up to 98.5%
Standards Safet: EN 62040-1-1 (Directive 2006/95/EC); EMC: EN 62040-2 (Directive 2004/108/EC)
Classication in accordancewith IEC 62040-3
(Voltage Frequenc Independent) VFI - SS - 111
Moving the UPS transpallet
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 5/8
INPUT
Rated power 400000 VA
Voltage 400 Vac three-phase Vac
Voltage tolerance + 20% - 25%
Frequency 50/60 Hz with autorangeFrequency tolerance 45/65 Hz
Power factor 0,99
Input current 564 A
Current distorsion <3%
Soft start 0-100% in 10
BY PASS
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance ± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency 50/60 Hz (autorange)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Rated current 564 A
Number phases 3
Back-feed protection yes
Overload capacity Inx10ms 14
OUTPUT and INVERTER OUTPUT
Rated power 400000 VA
Active power 360000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Dynamic stability ± 5% in 5 msFrequency same as the input (autorange)
Voltage distortion with distorcingload
<3%
Voltage distortion with linear load <1%
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mainssupply present
Inver ter efficiency at rated load 95 %
Overload 125% 150% 200% of the rated current for 10' / 1' / 7
RECTIFIER OUTPUT
Ripple <1%
BATTERIES
Type Maintenance-free sealed lead-acid
Maximum recharge current 0.2xC10
ENVIRONMENTAL
Altitude max 1000 m
Color Dark grey RAL 7035
Remote controls EPO and bypass
Safety compliance EN 62040-1
EMC conformance EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
Protection rating 3
Line-Interactive/Smart Activeefficiency
up to 98,5%
Master HP
MHT 400
© RPS Spa - Member of the Riello Elettronica Group - P.Iva IT02647040233
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 6/8
Noise 70÷72 dBA at 1 m
Remote signals voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm,output 12Vdc 80mA)
Operating temperature 0 ÷ 40 °C
Relative humidity 95% no condensing
DATA
Weight 1700 Kg
Dimensions (h w d) 1900x1500x1000 mm
Master HP
MHT 400
© RPS Spa - Member of the Riello Elettronica Group - P.Iva IT02647040233
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 7/8
INPUT
Rated power 500000 VA
Voltage 400 Vac three-phase Vac
Voltage tolerance + 20% - 25%
Frequency 50/60 Hz with autorangeFrequency tolerance 45/65 Hz
Power factor 0,99
Input current 702 A
Current distorsion <3%
Soft start 0-100% in 10
BY PASS
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance ± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency 50/60 Hz (autorange)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Rated current 702 A
Number phases 3
Back-feed protection yes
Overload capacity Inx10ms 14
OUTPUT and INVERTER OUTPUT
Rated power 500000 VA
Active power 450000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Dynamic stability ± 5% in 5 msFrequency same as the input (autorange)
Voltage distortion with distorcingload
<3%
Voltage distortion with linear load <1%
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mainssupply present
Inver ter efficiency at rated load 95 %
Overload 125% 150% 200% of the rated current for 10' / 1' / 7
RECTIFIER OUTPUT
Ripple <1%
BATTERIES
Type Maintenance-free sealed lead-acid
Maximum recharge current 0.2xC10
ENVIRONMENTAL
Altitude max 1000 m
Color Dark grey RAL 7035
Remote controls EPO and bypass
Safety compliance EN 62040-1
EMC conformance EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
Protection rating 3
Line-Interactive/Smart Activeefficiency
up to 98,5%
Master HP
MHT 500
© RPS Spa - Member of the Riello Elettronica Group - P.Iva IT02647040233
7/23/2019 Riello Master HP
http://slidepdf.com/reader/full/riello-master-hp 8/8
Noise 70 dBA at 1 m
Remote signals voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm,output 12Vdc 80mA)
Operating temperature 0 ÷ 40 °C
Relative humidity 95% no condensing
DATA
Weight 2100 Kg
Dimensions (h w d) 1900x2100x1000 mm
Master HP
MHT 500