(Applicable to Firmware 2.2.1 (HART® 5) or 3.1.1 (HART® 7) )
SVi1000 Operator Controls - Standard
SVi1000 ModesNormal ModeIn this mode the valve follows the 4-20 mA input signal.
HART® Override mode
In HART® override mode, the local user interface buttons are disabled until any button is pushed, then local control is reestablished. At this time, the instrument interface functions as if in Manual and Setup mode when us-
ing the optional laptop-based software or other HART® interface tools. In
HART® Override Mode the following functiond are supported over HART® by ValVue* or DTM based interface: Set Charact erizat ion (Lin ear, Equal%(30, 50, Camflex*), Quick Open an d Cust om En able or Disable Bumpless Tran sfer Set Near Closed Value Allow Tun e t o Overrid e limit s Con figure Tight Shut off Set Low er an d Upper Posit ion Limit s Con figure Posit ion Fault Limit s (Posit ion Error Ban d an d Time 1) Con figure Sw it ch I/O Run Fin d St ops Run Aut oTun e (Provid ed t he opt ion is set at t he local user in t erface) Perform a Man ual Fin d St ops Set Open St op Ad just men t Set Valve Posit ion Comman d valve t o full open or closed Failsafe ModeWhen a fault results in Failsafe mode being activated, the output pressure of t he SVi1000 is set low an d t he red st at us LED illumin at es con t in uously. If the fault is considered self-clearing, then once corrected, the unit returns t o Normal mod e. If t he fault is n ot self-clearin g, t hen t he un it requires a reset after correcting the failsafe condition.Commissioning ServicesThese are temporary states activated when a local user interface issued comman d d ict at es t heir use. When t he posit ion er is in a Commission Processes a st at us light in d icat es t his act ivit y. Examples of Commission Processes are Aut o Fin d St ops an d Aut o Tun e. On ce a t ask complet es t he un it ret urn s t o Normal mod e.
The local user in t erface is w here you con figure t he un it an d perform system operations. These operations consists of:Configuration Selection Switch This switch provides control to the following functions: Act uat or Air Act ion Select aut ot un ed or preset t un in g paramet ersAuto Find StopsThis function automatically sets the lower and upper stops. Open Stop AdjustmentUse t he Open St op Ad just men t screw t o perform an upper st op ad just men t an d save it t o t he d evice. AutotuningThe autotune process determines optimum tuning parameters for the valve being commissioned. This function is only active when the Con figurat ion Select or Sw it ch is set t o Aut oTun e.
Visit us on lin e: w w w .geoilan d gas.com/valves
* Mason eilan , SVI, ValVue an d Camflex are regist ered t rad emark s of t he Gen eral Elect ric Compan y.Other company names and product names used in this document are t he regist ered t rad emark s or t rad emark s of t heir respect ive ow n ers.
© 2016 Gen eral Elect ric Compan y. All right s reserved .
GEA31458B 03/2016Part # 720036098-888-0000
GE Oil & Gas Con t rol Valves an d In st rumen t at ion
Push But t on Guid e for Masoneilan* SVi*1000 Digit al Valve Posit ion er
HART® DD - SVi1000 (Applicable to Firmware 2.2.1 (HART® 5) or 3.1.1 (HART® 7) and DD version 1)
Visit us on lin e: w w w .geoilan d gas.com/valves
GE Oil & Gas Con t rol Valves an d In st rumen t at ion
HART® Handheld Guide for Masoneilan* SVi*1000 Digital Valve Posit ion er