Drawing Index
Sheet # Sheet Name Issue Date
Project Directory
Client:Mandana Nabizadeh, DDS & Ali Behzadi, DMD
Design Architect:JoeArchitect, Inc.
1422 Delgany Street, Suite LL1Denver, CO. 80202720.946.3228720.946.3004 (fax)
Dental Equipment Provider:Patterson DentalMike Cothern
Building Code Summary
Scope of Work: 2,192 sq. ft. interior tenant finish on 1stfloor of existing 1 story, fully sprinkled,type V-B building
Applicable Codes: 2012 Florida Building Code2008 National Electrical Code2010 Mechanical Code2010 Fuel Gas Code2010 Florida Energy Code2010 Plumbing Code2010 florida Fire Preservation Code2009 NFPA 101 Life Safety Code w/ Florida Amendments2009 NFPA 1 Uniform Fire Code w/ Florida AmendmentsEngineering Standards ManualOrlando Urban Storm Water Management ManualFlorida StatutesFlorida AdministrativeOrlando City Code
Occupancy Classification: B
Construction Type: V-B
Tenant Finish Area: 2,192 sq. ft.
Gross Building Area: 2,374 sq. ft.
Building Height: 1 story
Occupant Load Factor: 1 occupant / 100 sq. ft.
Occupant Load: 22
Total Exit Width: (0.2"/occupant) * 22 occupants = 4.4"32" minimum clear width req'd.
Number of Exits Required: 1 exit required, ? exits provided
Max. Travel Distance to Exit: 200 ft allowed (non sprinkled)56 ft maximum travel distance
Fire Protection: Existing building non sprinklered
Architect of Record:WJ WEEKS Archtecture llc AA26002407
1200 East Hillcrest Street Suite 200Orlando, Florida 32803407.234.3695407.888.4930 (fax)
Civil Engineer:SK Consortium Inc. EB 7080
1053 North Orlando Avenue Suite 3Maitland, Florida 32751407.629.4288407.629.1656 (fax)
Landscape Architect:Daniel A. Rodgers
230 North Glenwood AvenueOrlando, Florida 32751407.353.0112
Structural Engineer:RDI Structural Engineering, Inc. CA 29982
1135 Pasadena Avenue South Suite 100South Pasadena, Florida 33707727.388.1344
MEP Engineers:RBE Consulting Services LLC #27269
2875 Split Oak CourtOviedo, Florida 32766407.796.3820407.796.3671fax)
Demolition Site PlanC001
C101 Site Development Plan
C201 Grading and Drainage Plan
C401 Detail Sheet
CIVIL
LANDSCAPE LA - 100 Existing Tree Plan
LA - 200 Landscape Plan & Plant Palette
LA - 201 Landscape Planting Details
ELECTRICAL Electrical Site Photometric PlanE0.2
Electrical Power & Systems PlansE1.1
Lighting Floor PlanE2.1
E3.1 Electrical Roof Plan
E4.1 Power Riser Diagram, Details and Schedules
3-24-14
6-3-15
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
x-xx-xx
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
LA - 300 Irrigation Plan Details & Notes
C0 CoverARCHITECTURE
Demolition Floor PlanA 1.0
New Floor PlanA 2
Roof PlanA 2.2
Existing Exterior ElevationsA 7.0
New Exterior ElevationsA 9.1
A 9.2 New Exterior Elevations
1Color Renderings
Existing Photos
A 10.1
A 10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
A 2.3
4
A 2.3
2
A 2.3
6
A 2.3
1
A 2.3
5
5
12'-8 3/4"
8'-0 1/2"
8'-2"
X3
Copy/fax
11'-0"
8'-6 1/4"
11'-0"
7'-11 1/4"+/-
11
3
8
4
8'-11"
10'-8"
8'-6"
6'-1" 3'-10 3/4"
2'-8"
3'-6"
2'-0"
Children's Practice
Waiting
104
Adult PracticeWaiting
101
Reception
102
Kids' Area
105
Restroom
106
Open Bay
108
Quiet Room 1
110
Quiet Room 2
111
Sterilization
113Mechanical
115
Med Gas
114
Treatment Hallway
116
Lab
112
Consult
107
Operatory 2
117
Operatory 1
118
Hygiene
119
IT Closet
120
Adult PracticeHallway
121A
Restroom
122Staff Room
123
Doctors' Office
124
Imaging Station
109
10
75'-0"
X1
X2
1
2
X4
4'-0 1/2"
W9
W9
W9
W9
W3
W9
W9
W9
9
9'-2"
3'-2"
Reception Hallway
103
6
11'-10 3/4"6'-4"
8'-0 1/2"
5'-0 1/4"
5'-7"
2'-8"
3'-6"
2'-0"
2'-8"
3'-6"
1'-10 1/2"
3'-5 3/4"
2'-0"
9'-0"
7'-8 1/2"
8'-11 1/4"
10'-0 1/2"
8'-0"
6'-6"
4'-5 1/2" 5'-0" 2'-6"
W3
See FloorPlan Note 9
W8W8W8
4'-2"5'-4"
18'-3 3/4"
11'-10 1/4"
See Floor Plan Note 10
1'-1"
4'-1 3/4" 1'-6"
2'-0"
3'-0"
Adult PracticeHallway
121B
LC
LC
12
13
FEC
FEC
1525
60 min
X > 8205
(a)
pull side
18 min445
1220
48 min
X > 8205
(c)
push side, door provided with
both closer and latch
12 min305
1220
48 min
X > 8205
(b)
push side
Figure 404.2.4.3
Maneuvering Clearances at Recessed Doors and Gates
0'-8"
W9
W9
W9
W9
W9
W9
W9
W9
W9
Partition (P-Types)Schedule# Wall Type Fire Rating Assembly Description
W1 4-7/8" Partition N/A 5/8" Type 'X' GWB applied to each side of 3-5/8" steel studs 24" OC. Height varies; refer to specifications and drawings. See RCP for location of insulation.
W3 4-1/4" Partition N/A 5/8" Type 'X' GWB on finish side of 3-5/8" steel studs 24" OC. Height varies; refer to specifications and drawings. See RCP for location of insulation.
W4 5/8" GWB N/A 5/8" Type 'X' GWB on finish side of existing framing. Height varies; refer to specifications and drawings. See RCP for location of insulation.
W8 6-1/8" Mechanical RoomPartition
N/A 5/8" Type 'X' GWB applied to each side of 3-5/8" steel studs 24" OC and 1-1/4" Kinetics IsoMax resilient channel. Full height assembly from finish floor to BO deck. Provide full 3-1/2" BATT insulation.
W9 1-1/2" Partition N/A 5/8" Type 'X' GWB on finish side of 7/8" steel hat channel 24" OC. Height varies; refer to specifications and drawings. See RCP for location of insulation.
All walls W1 UNO
Mandana Nabizadeh, D.D.S. Children Dentistry
A 9.2
5
A 9.2
5
A 9.2
5
A 9.2
5
NOTE; VERIFY FINAL FRAME SIZE, FABRIC AND ANCHORING TOBUILDING BY CANOPY MANUFACTURER TO MEET CODEREQUIREMENTS. SUBMIT FABRIC AND FRAME COLOR SAMPLESFOR OWNERS REVIEW. REF; SUNDANCE ARCH. PRODUCTS
LUMINAIRE SCHEDULE
Symbol Label Qty File Lumens LLF WattsCatalog Number Description Lamp
W1 8 WST_2_42TRT
_MD.ies
3200 1.00 93
S1 3 KAD_175M_R3
_(PULSE_STA
RT).ies
14400 1.00 208
WST 2/42TRT MD
ARCHITECTURAL
SCONCE WITH MEDIUM
THROW DISTRIBUTION
WITH CLEAR, FLAT
GLASS LENS. MEETS
THE 'NIGHTTIME
FRIENDLY' CRITERIA
TWO 42-WATT TRIPLE
TUBE COMPACT
FLUORESCENT,
HORIZONTAL POSITION.
KAD 175M R3
(PULSE START)
Area Luminaire, 175W
MH, R3 Reflector, Full
Cutoff MEETS THE
'NIGHTTIME FRIENDLY'
CRITERIA
ONE 175-WATT CLEAR
BT-28 METAL HALIDE,
HORIZONTAL POSITION.
STATISTICS
Description Symbol Avg Max Min Max/Min Avg/Min
Calc Zone #3 3.1 fc 21.5 fc 0.0 fc N / A N / A
Children's PracticeWaiting
104
Adult PracticeWaiting
101
Reception102
Kids' Area105
Patient Restroom106
Open Bay108
Quiet Room 1110
Quiet Room 2111
Sterilization113
Mechanical115
Med Gas114
Treatment Hallway116
Lab112
Consult107
Operatory 2117
Operatory 1118
Hygiene119
IT Closet120
Adult PracticeHallway
121
Restroom122
Staff Room123
Doctors' Office124
Imaging Station109
Reception Hallway103
Children's PracticeWaiting
104
Adult PracticeWaiting
101
Reception102
Kids' Area105
Patient Restroom106
Open Bay108
Quiet Room 1110
Quiet Room 2111
Sterilization113
Mechanical115
Med Gas114
Treatment Hallway116
Lab112
Consult107
Operatory 2117
Operatory 1118
Hygiene119
IT Closet120
Adult PracticeHallway
121
Restroom122
Staff Room123
Doctors' Office124
Imaging Station109
Reception Hallway103
METER
3-1/2" CONDUIT
3#500, 1#3G. IN
MAIN DS
400A
SEE GROUNDING DETAIL
2/E5.1. CONNECT PER N.E.C
NEW
3-1/2" CONDUIT
OVERHEAD OR UNDERGROUND SERVICE ENTRANCE
PER UTILITY AND SITE-SPECIFIC CONDITIONS WIRING
TO BE SIZED PER LOCAL CODE REQUIREMENT
(4)#500KCMIL, (1)#3G, (1)#3IG