26
POWER TRANSFORMER 1 Insulation Resistance Measurement Procedure a. For LT systems, use only 500V or 1000V Megger. b. For MV & HV systems, use 2500V or 5000V Megger. c. Remove Earth from Transformer neutral. d. Measure as per table below. Circuit Megger Use MV & HV 1U - E 5kV 2U - E 5kV 1U - 2U 5kV 2 Winding Resistance Measurement Circuit Tap No Resistance Ω 1U-1N All Taps 1V-1N 1W-1N 2U-2N 2V-2N 2W-2N 1U 1V 1W 1N 2U 2V 2W 2N 1U 1V 1W 1N 2U 2V 2W 2N WINDING RESISTANCE METER I I I I I1 P1 P2 I2

Power Transformer Testing Procedures

Embed Size (px)

Citation preview

Page 1: Power Transformer Testing Procedures

POWER TRANSFORMER

1 Insulation Resistance MeasurementProcedurea. For LT systems, use only 500V or 1000V Megger.b. For MV & HV systems, use 2500V or 5000V Megger.c. Remove Earth from Transformer neutral.d. Measure as per table below.

Circuit Megger UsedMV & HV

1U - E 5kV2U - E 5kV1U - 2U 5kV

2 Winding Resistance Measurement

Circuit Tap No Resistance Ω

1U-1N All Taps1V-1N1W-1N

2U-2N2V-2N2W-2N

1U

1V

1W

1N

2U

2V

2W

2N

1U

1V

1W 1N

2U

2V

2W

2N

WINDING RESISTANCE METERI I I I

I1 P1 P2 I2

Page 2: Power Transformer Testing Procedures

3 Magnetic Current Test

Applied Voltage Measured Current1U-1V 1U1V-1W 1V1W-1U 1W1U-1N, 1V-1N,1W-1N 1N

4 Magnetic Balance Test

Applied Voltage Measured Voltage1U1N 1V1N 1W1N 1U1N 1V1N 1W1N 2U2N 2V2N 2W2N

415 - - - - 415 - - - - 415 -

Applied Voltage Measured Voltage1U1V 1V1W 1W1U 1U1V 1V1W 1W1U 2U2V 2V2W 2W2U

415 - - - - 415 - - - - 415 -

2U

2V

2W

2N

1U

1V

1W

1N

2U

2V

2W

2N

mA

415

V A

C mA

mA

mA

1U

1V

1W

1N

2U

2V

2W

2N

415

V A

C

Mea

sure

d v

olta

ge

Page 3: Power Transformer Testing Procedures

5 Vector Group Confirmation.

Dyn1

Conditions:1 -1U and 2u should be shorted.2 -Apply 415V to 1U,1V&1W3 -Satisfy the following conditions.

1U1W = 1U2n + 1W2n1W2w = 1W2V1V2v < 1V2w

Dyn11

3 -Satisfy the following conditions.1U1V = 1U2n + 1V2n1V2w = 1V2v1W2w < 1W2v

1U

1V1W

2W

2U

2V

1U 2U

1V1W

2V

2W 2n

1U

1V1W

2W

2U

2V

2U1U

1V1W

2W

2V

2n

Page 4: Power Transformer Testing Procedures

5 Vector Group Confirmation.

Ynd1

3 -Satisfy the following conditions.1U1N = 1U2v + 2v1N1W2v = 1V2v1V2v < 1V2w

YNyn0

3 -Satisfy the following conditions.1W2w = 1V2v1W2n = 1V2n1U1N = 1U2n + 1N2n

6 Short Circuit Test and Differential Stability.7 REF Stability Test

1U

1V1W

2W

2V

2U

1N

1U

1V1W

2W

2V

2U

1U

1V1W

2W 2V

2U

1N2n

1U

1V1W

2W 2V

2U

2n

1N

Page 5: Power Transformer Testing Procedures

8 Cooler Circuits9 Temperature Indicators Calibration

10 Auxilliary Protection Circuits

Page 6: Power Transformer Testing Procedures

6 Short Circuit Test and Differential Stability.

Stable Condition.

Diff RelayP1 S1

300/1 AS2 S1

S2 S1

P2 S2

B-Ph

Y-Ph

R-Ph

P1 S1

500/1 AS1 S2

S1 S2

S2

P2

Apply 3-Ph AC Voltage

N R Y B

Temporary Short

Id

Id

Id

Page 7: Power Transformer Testing Procedures

Example:Short Circuit Current Calculation.

Rating : 100MVAHV LV

Voltage 220 kV 132kVCurrent 262.43 A 437.40 A% of Impedance (%Z) = 8.05%

HV MVA = LV MVA = 100MVA

√3 x 220000 x I1 = √3 x 123000 x I2 = 100,000,000√3 x 220000 x I1 = 100,000,000I1 = 100,000,000 / (√3 x 220000)I1 = 262.43A

√3 x 123000 x I2 = 100,000,000I2 = 100,000,000 / (√3 x 132000)I2 = 437.40A

%Zv = 8.05% = 220kV x % of impedance = 220000 x (8.05/100)

%Zv = 17,710 V

If We may apply 415 V to HV sideHV I primary = (415 x 262.43) / 17710HV I primary = 6.15 AHV sec = 6.15 / 300HV sec = 0.0205A

LV I primary = (415 x 437.4) / 17710LV I primary = 10.25 ALV sec = 10.25 / 500LV sec = 0.0205 A

Page 8: Power Transformer Testing Procedures

Unstable Condition

S1

S2 S1

S2 S1

S2

S1

S1 S2

S1 S2

S2

Id

Apply 3-Ph AC Voltage

Temporary Short

Id

Id

Page 9: Power Transformer Testing Procedures
Page 10: Power Transformer Testing Procedures

7 REF Stability Test

i) Stable Condition.

R Y B

P1 S1 S1 S1

P2 S2 S2 S2

S2 S1 N

P2 P1

P2 P1

nS2 S1

P1 S1 S1 S1

P2 S2 S2 S2

r y b

Apply 3-Ph AC

Fault

HV REF

LV REF

SHORT

Page 11: Power Transformer Testing Procedures

ii) Unstable Condition (Type 1)

S1 S1 S1

S2 S2 S2

S2 S1

S2 S1

S1 S1 S1

S2 S2 S2

Apply 3-Ph AC

SHORT

LV REF

HV REF

Page 12: Power Transformer Testing Procedures

iii) Unstable Condition (Type 2)

S1 S1 S1

S2 S2 S2

S2 S1

S2 S1

S1 S1 S1

S2 S2 S2

HV REF

LV REF

LOADING TRANSFORMER

LOADING TRANSFORMER

Page 13: Power Transformer Testing Procedures