Upload
dangphuc
View
217
Download
0
Embed Size (px)
Citation preview
Planning and installation Basic Line Ai1 Air
Air to water heat pump
WATERKOTTE GmbH, Gewerkenstraße 15, D-44628 Herne
Tel.: 0049/(0)2323/9376-0, Fax: 0049/(0)2323/9376-99, E-Mail: [email protected]
Internet: http://www.waterkotte.de
21.10.2015 / Z21437
Basic Line Ai1 Air – Indoor unit
Basic Line BS7010 – Hydraulikstation
- Indoor unit
Basic Line Ai1 Air /Basic Line BS 7010
- Outdoor unit
Basic Line Ai1 Air /Basic Line BS 7006 - Outdoor unit
21.10.2015 2 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
Copyright 2014 by
WATERKOTTE GmbH
Gewerkenstraße 15, 44628 Herne, Germany
All rights reserved. Reproduction, duplication as well as translation of this
publication, or excerpts therefrom, require prior written approval by
WATERKOTTE GmbH.
Illustrations and diagrams serve as explanatory description and shall not be
used as drawings for construction, offers or installation.
All specifications comply with the state of technology at time of printing; we
reserve the right to make changes that serve technical progress.
This publication has been prepared with all reasonable care.
WATERKOTTE GmbH does not assume any liability for remaining errors or
omissions, or for possible damages.
Note: This symbol applies only to countries within the European Union (EU).
This symbol is in compliance with Directive 2002/96/EC, Article 10. The
product has been designed and manufactured with high-quality materials
and components which are suitable for recycling.
This symbol means that electrical and electronic equipment, at the end of
its useful life, shall be disposed of separately from household waste. Please
dispose of this equipment at your designated collection point or local recy-
cling centre.
In the European Union, different collection systems are available for used
electrical and electronic equipment. Please help us conserve the environ-
ment we live in!
Never vent R410A into the atmosphere:
R410A is a fluorinated greenhouse gas according to Kyoto Protocol and
has a global warming potential (GWP) of 1975.
21.10.2015 3 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
Content 1 Safety ..................................................................................................................................... 5
1.1 Intended use ...................................................................................................................... 5
1.2 Basic safety precautions .................................................................................................... 5 1.2.1 Keep information available .................................................................................... 5 1.2.2 Before initial use .................................................................................................... 5 1.2.3 Environmental protection ...................................................................................... 6 1.2.4 Modifications and repairs on the heat pump ......................................................... 6
1.3 Hazards ............................................................................................................................. 6
1.4 Operator's duty of care ...................................................................................................... 8
1.5 Other applicable documents .............................................................................................. 8
2 Product description and scope of delivery ................................................................................ 9
2.1 Overview............................................................................................................................ 9 2.1.1 Basic Line Ai1 Air /BS 7010 (outdoor module) .................................................... 10 2.1.2 Basic Line Ai1 Air (indoor module) ....................................................................... 10 2.1.3 Basic Line BS Hyd 5010 hydraulic station ........................................................... 10
3 Components and installation .................................................................................................. 11
3.1 Heating system Basic Line Ai1 Air BS 7010 / BS 7006 .................................................... 11
3.2 Structure and control ....................................................................................................... 11 3.2.1 Electronic heat pump control .............................................................................. 11
4 Transport to installation site ................................................................................................... 12
4.1 Environmental conditions for installation (indoor module) ................................................. 12
4.2 Residual head circulation pump (heating) ......................................................................... 12
5 Installation and connection .................................................................................................... 13
5.1 Installation and connection of indoor unit ......................................................................... 13
5.2 Environmental conditions for installation .......................................................................... 13
5.3 Dimensions and connections outdoor module BS 7010 (5010.5) .................................... 14
5.4 Dimensions and connections outdoor module BS 7006 (5006.5) .................................... 15
5.5 Dimensions and connections (indoor module) Basic Line Ai1 Air ..................................... 16
5.6 Dimensions and connections (indoor module) BS Hyd 5010 hydraulic station ................. 17
5.7 Installation of cover and cladding panels .......................................................................... 18
5.8 Disassembly of cladding panels ....................................................................................... 18
5.9 Disassembly of cover and cladding panels (outdoor module) ........................................... 18
6 Installation and connection of the outdoor module .................................................................. 19
6.1 Selecting a location for outdoor module .......................................................................... 19
6.2 Clearance for ventilation and operation ............................................................................ 20
6.3 Installation in base plate or on the wall ............................................................................. 20
6.4 Installation and space requirement .................................................................................. 21
7 Connection lines ................................................................................................................... 22
7.1 Refrigerant charge and additional charge ........................................................................ 22
7.2 Oil traps ........................................................................................................................... 23
7.3 Insulation ......................................................................................................................... 23 7.3.1 Tube airtight testing method (recommended procedure), test equipment nitrogen24
7.4 Connection outdoor module / indoor module (refrigerant lines) Basic Line Ai1 Air ............ 25
7.5 Connections (refrigerant and heating) indoor module hydraulic station ............................. 26
21.10.2015 4 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7.6 Connections outdoor module (refrigerant line) .................................................................. 27
8 Refrigerant ............................................................................................................................ 28
8.1 Requirements on handling of R410A refrigerant ............................................................... 28
8.2 Safety guidelines for the handling of refrigerants .............................................................. 28
8.3 Charging refrigerant circuit ............................................................................................... 29
8.4 Mounting (heating /domestic water side) ......................................................................... 30
9 Electrical work ....................................................................................................................... 31
9.1 Electrical connection outdoor module .............................................................................. 32 9.1.1 Cable cross sections/types ................................................................................. 32
9.2 Electrical connection (indoor module) (hydraulic station / control module) ........................ 32 9.2.1 Installing external wall sensor .............................................................................. 32 9.2.2 Power supply- Heating element.......................................................................... 32 9.2.3 Heating element - thermostat setting .................................................................. 32
9.3 Electrical and BUS connection (outdoor module BS 7010.5) ........................................... 33
9.4 Electrical and BUS connection (outdoor module, BS 7006.5) .......................................... 34
9.5 Electrical connection Basic Line Ai1 Air (5010.5) (indoor module)..................................... 35
9.6 Electrical and BUS connection Basic Line BS Hyd 5010 hydraulic station ....................... 35 9.6.1 DIP-Switch (outdoor module) .............................................................................. 35
9.7 Electrical wiring diagram Basic Line Ai1 Air / BS 7010 (outdoor module) ......................... 36
9.8 Electrical wiring diagram - Basic Line Ai1 Air (indoor module) .......................................... 37
9.9 Electrical wiring diagram - Basic Line BS Hyd 5010 hydraulic station (indoor module) ..... 38
9.10 WWPR2 Controler - connections ..................................................................................... 39
9.11 Electrical connections ...................................................................................................... 40
10 Commissioning ..................................................................................................................... 41
10.1 Pre-startup checks .......................................................................................................... 41
10.2 Initial start of heat pump .................................................................................................. 43
10.3 Control of entire operation ............................................................................................... 44
10.4 Turning heat pump off ..................................................................................................... 44
10.5 Taking heat pump out of operation for extended period .................................................. 44
11 Technical data ...................................................................................................................... 45
12 Connection diagram .............................................................................................................. 46
12.1 Basic Line Ai1 Air with underfloor heating, without single room control ............................ 46
12.2 Basic Line Ai1 Air with underfloor heating, with single room control ................................ 47
12.3 Basic Line Ai1 Air with radiators / fan convectors ........................................................... 48
12.4 Basic Line Ai1 Air with hydraulic compensator ................................................................ 49
12.5 Basic Line Ai1 Air hydraulic compensator and additional heater ...................................... 50
12.6 Basic Line BS 7010 with underfloor heating, without single room control ........................ 51
12.7 Basic Line BS 7010 with underfloor heating, without single room control, decentral domestic hot water preparation ................................................................................................................. 52
12.8 Legend (hydraulic schemes) ............................................................................................ 53
13 Refrigeration circuit Basic Line Ai1 Air / BS 7010 .................................................................... 55
14 Maintenance and inspection .................................................................................................. 57
Safety
21.10.2015 5 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
1 Safety
1.1 Intended use
Your WATERKOTTE heat pump of the Basic Line series is used for space
heating and cooling, and heating of domestic water.
An outdoor module, which is coupled to a heat source (air) that is available
year-round, serves as heat generator.
Project planning of the heat source system must be performed in compli-
ance with the technical information provided by WATERKOTTE for layout of
heat source systems. Heat pump shall only be turned on after the refriger-
ant connections are completely charged, and the other hydraulic circuits
are completely charged and vented, and all electrical connections are
properly completed.
Commissioning may only be carried out by trained professionals. Damages
caused by non-compliance with above mentioned items are not covered by
the warranty (see enclosed Exclusion of Warranty).
1.2 Basic safety precautions
1.2.1 Keep information available
In addition to the operating manual, also furnish operating instructions in
terms of Labour Protection Law and Work Equipment ordinance. Keep all
safety and operating signs on the heat pump in fully legible condition at all
times. Replace damaged or illegible signs immediately.
1.2.2 Before initial use
Before initial use of your WATERKOTTE heat pump, familiarise yourself with:
Operating and control elements of your WATERKOTTE heat pump
Equipment of heat pump
Operation of heat pump
Immediate surroundings of heat pump
Safety devices of heat pump
Before initial start, perform the following steps:
Ensure that all safety devices are installed and function as intended.
Check heat pump for visible damage. Eliminate any detected defects
immediately. Heat pump may only be operated in perfect condition!
Ensure that only authorised personnel is in the work area of the heat
pump and that no other persons are endangered when heat pump is
started.
Remove all objects and other materials that are not required for opera-
tion of the heat pump from the work area of the heat pump.
Activate the electrical connection; the module must be in standby mode
(oil sump heater active).
Check heating circuit temperature: Temperature heating circuit below
16 °C.
Safety
21.10.2015 6 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
1.2.3 Environmental protection
Observe the regulations regarding waste avoidance and proper waste
recycling or disposal when performing any kind of work on and with the
heat pump.
Ensure that particularly during installation and maintenance work, as well
as when placing out of operation, groundwater pollutants such as
grease, oils, refrigerants, solvent-containing cleaning fluids, etc. do not
contaminate the ground or enter into the sewer system!
These substances must be collected, stored, transported, and disposed
of in suitable containers.
1.2.4 Modifications and repairs on the heat pump
For safety reasons, no unauthorised modifications shall be performed on
the heat pump.
Thus, all intended modifications are subject to written approval by
WATERKOTTE.
Use only original WATERKOTTE spare parts.
Original parts are specifically designed for your heat pump. Externally pro-
cured parts provide no guarantee that they are designed and manufactured
in compliance with relevant usage and safety requirements.
Parts and special equipment not delivered by WATERKOTTE are not ap-
proved for use on the heat pump.
1.3 Hazards
Observe the following points to avoid life-threatening injuries and damages
to the heat pump during operation:
Risk of death by electric shock!
Do not use water or other liquids to clean the system!
Keep all electrical supply modules locked at all times!
Any work on the electrical equipment of the heat pump shall only be per-
formed by professional electricians!
Safety
21.10.2015 7 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
Leaking refrigerant can result in severe personal injuries (suffocation or hy-
pothermia)!
Avoid direct contact with refrigerant!
When selecting the installation site, observe the minimum volume under
consideration of the refrigerant applied (as per EN 378-1).
Risk of burns!
During operation, surface temperatures (compressor and pressure line) can
climb above 100 °C or drop below 0 °C.
Do not remove housing cover during operation!
Allow heat pump to cool down before removing cover.
Risk of injury!
Risk of chemical burns when skin comes in direct contact with lubricant
leak.
Wear suitable clothing when performing maintenance work on the heat
pump!
Do not put your fingers or others into the fan, or evaporator.
The inside parts of the heat pump may run at high speed or high tempera-
ture, they could cause serious injury. Do not remove the grills on the fan
outlet and top cover.
The hot water probable need to mix with cold water for terminal usage, too
hot water (over 50 °C in the heating module may cause injury.
The installation height of power supply should be over 1.8m, if any water
may spatter, the module can be safe from water.
Electrostatic charge!
Electronic components can be damaged by electrostatic processes.
Ground yourself before touching electronic components.
Risk of total loss!
Repeated restart of the heat pump can result in total loss! In case of heat
pump failure, an inspection by qualified and authorised personnel must be
performed before restart.
Safety
21.10.2015 8 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
1.4 Operator's duty of care
Your WATERKOTTE heat pump has been designed and built on the basis
of a risk analysis and after careful selection of standards to be observed.
Thus, your heat pump is state-of-the-art and provides for maximum safety.
In practice, however, this safety can only be ensured by taking all necessary
measures. As operator of the heat pump it is your responsibility to plan
these measures and oversee their implementation.
You must ensure that:
The heat pump is only used as intended (see also chapter 1.1, "Intended use").
The heat pump is only operated in perfect, fully functional condition and safety devices are checked regularly to ensure that they are working properly.
The operating manual is available in perfect condition at the heat pump at all times.
The heat pump is operated, maintained and repaired only by adequately qualified and authorised personnel.
None of the safety and warning notices on the heat pump are removed or damaged.
1.5 Other applicable documents
Operating manual: WATERKOTTE heat pump controller.
WATERKOTTE technical information
Product description and scope of delivery
21.10.2015 9 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
2 Product description and scope of delivery
2.1 Overview
1 Basic Line Ai1 Air /BS 7010 - (outdoor module)
2 Basic Line Ai1 Air /BS 7006 - (outdoor module)
3 Basic Line Ai1 Air - (indoor module)
4 Basic Line BS Hyd 5010 hydraulic station – (indoor module)
4
3
1
2
Product description and scope of delivery
21.10.2015 10 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
2.1.1 Basic Line Ai1 Air /BS 7010 (outdoor module)
The device contains:
Compressor, inverter controlled
Evaporator
Fans
Inverter board, EVD
2.1.2 Basic Line Ai1 Air (indoor module)
The indoor module contains:
Integrated hot water tank 170 l Monochrome, semi-graphic, 8-line display Central power switch 6 convenient buttons and 3 indicator LEDs Intuitive control software BasicPro Speed-controlled circulation pump, efficiency class A Integrated electrical heating element 6 kW Combination fitting with safety valve Air vent 3-way motor ball valve membrane expansion tank
2.1.3 Basic Line BS Hyd 5010 hydraulic station
The hydraulik station contains:
Monochrome, semi-graphic, 8-line display Central power switch Outdoor temperature sensor 6 convenient buttons and 3 indicator LEDs Intuitive control software BasicPro Speed-controlled circulation pump, efficiency class A Integrated electrical heating element 6 kW Combination fitting with safety valve Metal housing (W x H x D) 743 x 750 x 303 mm Docking features for 1 additional module: e.g. domestic hot water tank,
living area ventilation
Series options
Hydraulic station incl. control (only heating)
- Art. Nr.: BS701059CH
Hydraulic station incl. control (heating and domestic hot water)
- Art. Nr.: BS701059CHW
Components and installation
21.10.2015 11 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
3 Components and installation
3.1 Heating system Basic Line Ai1 Air BS 7010 / BS 7006
The newly developed heating system was designed as a compact air
source heat pump for outdoor installation. It is suitable for heating and
cooling low-energy buildings.
Thanks to the inverter-controlled compressor, the Basic Line Ai1 Air and BS
7010 operate extremely energy-efficiently. Due to the infinitely variable
adjustment of the power it impresses with high performance. Even at
outdoor temperatures of -15 °C, flow temperatures of 55° C are possible
The outdoor module contains all the heat pump technology (nicht der not
the condenser). The control moduel with the tank (Ai1 Air) or the hydraulic
module BS Hyd 5010 are installed in the building.
3.2 Structure and control
Complete hot water heating system with integrated central hot water supply
(option), consisting of: heat generator (heat pump), regulation and electrical
control, complete electrics and control system, semi-graphic display.
3.2.1 Electronic heat pump control
The heat pump control is included in the delivery scope of the
WATERKOTTE heat pump. Use in other than
WATERKOTTE heat pumps will void any warranty claim.
Info: Technical details, operation and warning messages (see Operating
manual for heat pump control).
The control is used to control and monitor heating systems that are operat-
ed with WATERKOTTE compact heat pumps according to technical guide-
lines of WATERKOTTE Wärmepumpen GmbH. All tasks to do with control
are fulfilled (depending on the external temperature, control, monitoring,
self-diagnosis, saving of data in case of breakdown, etc.
WATERKOTTE explicitly states that function warranty will become void if
used on systems not approved by WATERKOTTE. Any liability for conse-
quential damages due to incorrect function within these systems shall be
explicitly excluded.
Transport to installation site
21.10.2015 12 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
4 Transport to installation site
Modules of the Basic Line 7010 series are delivered ready-to-connect with
metal cladding. The Basic Line Ai1 Air / Basic Line 7010 are delivered ready
for connection.
Since the heat pump module weighs 120 kg or more, for instance, at least
two people are required for transport.
The devices are mounted on top of each other only at the installation site.
During transport it must be ensured that appropriate means of transport are
used (lift truck, transport rollers, handcart).
It is crucial that the heat pump is transported upright!
Transport in tilted position (45°) is permitted only temporarily during inser-
tion. Horizontal transport results in oil displacement in compressor and can
cause damage to the heat pump during start-up.
After carton is removed or opened it is not permitted to tilt the module by
applying pressure to the pipelines or housing enclosure; this could result in
bent housing parts and pipelines.
4.1 Environmental conditions for installation (indoor module)
The room must be dry. Room temperature should be between +5 °C and
+25 °C.
4.2 Residual head circulation pump (heating)
Residual head circulation pump (heating) - Hydraulic station BS Hyd 5010 - Indoor module Basic Line Ai1 Air
10 kW ∆t=5K 6 m
Installation and connection
21.10.2015 13 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
5 Installation and connection
5.1 Installation and connection of indoor unit
To make hydraulic connections, you must use the supplied material (con-
necting lines and gaskets).
During assembly of connecting lines, use an according tool as brace to
prevent damage to the heat distribution station.
Installation of the indoor unit must be performed on a flat and horizontal
surface.
Wall clearance (free space) in front: at least 1000 mm.
Due to the connections on the rear of the unit, the mounting distance to
the wall (rear, right side, left side) must be selected in such a way that
access is ensured in case of repairs.
Recommendation for good service accessibility: Wall clearance (free
space), left, right 400 mm. Wall clearance rear at least
300 mm.
Figure 1: Recommendation - wall clearance for installation
5.2 Environmental conditions for installation
When selecting the installation site, observe the minimum volume under
consideration of the refrigerant applied (as per EN 378-1).
The room must be dry. Room temperature should be between +5 °C and
+25 °C. To facilitate maintenance, the use of a base plate is recommended.
To compensate for minor unevenness, we recommend use of an approx.
10 mm thick rubber mat.
Installation and connection
21.10.2015 14 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
5.3 Dimensions and connections outdoor module BS 7010 (5010.5)
Figure 2: Dimensions outdoor module BS 7010 (all dimensions mm)
A Cable entries, electrical connection
B Cover: connection refrigerant line
A
B
Installation and connection
21.10.2015 15 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
5.4 Dimensions and connections outdoor module BS 7006 (5006.5)
Figure 3: Dimensions outdoor module BS 7006 (all dimensions mm)
A Cable entries, electrical connection
B Cover: connection refrigerant line
Installation and connection
21.10.2015 16 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
5.5 Dimensions and connections (indoor module) Basic Line Ai1 Air
Figure 4: Dimensions indoor module Basic Line Ai1 Air (all dimensions mm
Installation and connection
21.10.2015 17 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
5.6 Dimensions and connections (indoor module) BS Hyd 5010 hydraulic station
Figure 5: Dimensions indoor module (buttom)
Installation and connection
21.10.2015 18 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
5.7 Installation of cover and cladding panels
To prevent transport damage, the cover, front and side panels of the heat
pump are enclosed separately.
After establishing all connections, mount them to the required positions (in-
sert and press).
5.8 Disassembly of cladding panels
The heat pump is provided with a disassembly tool. Use this tool to remove
the cladding panels to prevent damage.
Procedure:
Keep enough distance with the disassembly tool to the upper/lower
panel edge so as not to damage the retaining bolt (see figure).
The disassembly tool is manually driven into the gap between the front
and side panel with moderate force.
5.9 Disassembly of cover and cladding panels (outdoor module)
Cover and cladding panels are fixed with screws. In the case of a disas-
sembly the screws must be removed with an appropriate screwdriver.
Installation and connection of the outdoor module
21.10.2015 19 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
6 Installation and connection of the outdoor module
6.1 Selecting a location for outdoor module
Select a location permitting easy wiring and pipe access to the power
source and indoor module.
Avoid locations exposed to direct sunlight / other heat sources.
Select a location from which noise emitted by the module will not incon-
venience neighbours.
Avoid locations where combustible gases may leak, be produced, flow /
accumulate.
Please note that water may drain from module during operation. Ensure
unobstructed condensation drain.
Select a level location that can handle the weight and vibration of the
module.
Avoid locations where the module could be covered by snow. To pre-
vent snow from blocking / blowing against the air intake in regions sub-
ject to heavy snowfall, special precautions are required (selecting a
higher installation location / installing a protective cover in front of the air
intake). This can reduce airflow and cause malfunctions.
Avoid locations exposed to oil, steam, or sulphuric gas.
To ensure stability, we recommend the use of two concrete brackets in
combination with a gravel bed for condensed water drainage.
Select an installation site where the module is largely protected from for-
eign objects (leaves, etc.). In this connection observe the recommenda-
tions in chapter Maintenance and inspection.
Select an installation site where no foreign material (leaves, etc.) get into
the module.
Do not exceed permissible line length between indoor and outdoor
module.
Risk of injury!
When carrying the module at the bottom there is a risk of crushing the
hands / fingers.
Installation and connection of the outdoor module
21.10.2015 20 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
6.2 Clearance for ventilation and operation
When installing outdoor module on a rooftop / other location unprotected
from the wind, align air outlet opening in such a way that it is not directly
exposed to strong winds. Strong wind blowing directly into the air outlet
opening may impede normal airflow and thus cause malfunctions.
Precautions against strong winds can be seen in the following examples:
Align air outlet to nearest wall with a distance of about 50 cm.
Air guide: Position the module in such a way that the air discharged
from the air outlet is guided perpendicular to the direction from which
seasonal strong winds usually blow.
6.3 Installation in base plate or on the wall
Secure the base of the module firmly with four M10 screws to a proper
base plate (screws and nuts are not included in delivery). Please note:
Connection directions: The connection (piping and wiring) is performed
from below.
Ensure that water can drain off during defrosting. This can be accom-
plished by excavating the ground.
The installation height depends on the climate conditions at the site. In-
stall the module at a height that takes possible flooding or heavy snow
into account, but at least about 40 cm to 60 cm above the ground to al-
low unobstructed drainage of condensation. This ensures trouble-free
operation even in case of snow.
Note: Ice formation can occur particularly during the cold season. In ex-
treme cases, this can block the fans. Remedial action: Ensure unob-
structed drainage of melted water and remove excessive ice build up
below the module manually if necessary.
Figure 6: Securing in base plate
WATERKOTTE GmbH offers a wall mounting set.
Ensure that the melted water can drain off. Ensure that the entire drain is
frost-free to prevent freezing in the winter. For this purpose, a trace
heating could be applied.
Base plate
Installation and connection of the outdoor module
21.10.2015 21 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
6.4 Installation and space requirement
Check the figures to determine space requirement:
1. In front of wall, air outlet clear in front, flow obstacle in rear
2. In front of wall with roof, air outlet clear in front, flow obstacles in
rear and top
3. In recess: Flow obstacle in rear and on both sides
4. In front of wall, air outlet toward wall; flow obstacle in front.
5. Between two walls, air outlet toward wall, sides clear: Flow obsta-
cle in front and rear.
6. In recess with roof, air outlet clear in front, flow obstacle at rear, on
both sides and above.
Figure 7: Space requirement and minimum distances for installation
Connection lines
21.10.2015 22 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7 Connection lines
Using a hydraulic station you have to create a pipeline connection between
outdoor module and hydraulic station. It is equipped with a water fill anti-
freeze mixture, the concentration depends on the geographical location.
During assembly of connecting lines, use an according tool as brace to
prevent damage.
7.1 Refrigerant charge and additional charge
The outdoor modules come fully charged with refrigerant R410A from the
factory, allowing tube lengths (one way) up to 5 m without requiring addi-
tional charging. If tube lengths are less than 5 m, the charge in the outdoor
module is sufficient. In new modules, excess refrigerant must not be
drained. However, to optimise the module we recommend individual ad-
justment of refrigerant quantity to total volume (refer to table).
The outdoor module shall not exceed 3 m higher or 7 m deep stand
out as the indoor module.
If line length exceeds 5 m, charge module with additional R410A re-
frigerant.
Series
Factory pre-
charge
[kg
0-5 m 5 m – 20 m
5010.5 3,0 kg
Additional
charge
0
Additional
charge
40 g/m*
5006.5 1,9
Additional
charge
0
Additional
charge
40 g/m*
*Inefficiencies possible, pipeline cross sections have to be adjusted.
Please note:
The line length of 15 m (one way) may only be exceeded if the hot
water temperature is limited to 47.5 ° C! This shall be applied to the
basic settings of the controller.
The heating water temperature in heating mode has to be limited to
50 ° C!
Please note:
Do not exceed permissible line length LMAX (20 m)!
If the maximum difference in height is achieved of 3 m, an oil trap at 1.5 m
has to be provided.
Connection lines
21.10.2015 23 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7.2 Oil traps
To ensure the permanent oil flow in the 16 mm line, it is necessary, in criti-
cal installation conditions, to provide oil traps in the suction line.
A vertical line running 16 mm requires:
at a cable length of 1.5 m, a centrally integrated oil trap
at a cable length of more than 1.5 m - Oil traps have to be installed cen-
trally every 1.5 m
If the 16 mm line running in the direction of flow with constant slope and a
length of more than 6 m, oil traps have to be installed every 6 m.
7.3 Insulation
For refrigerant line we recommend the use of pre-insulated original
WATERKOTTE double-copper tube rings 10 / 16 x 1.0 mm (Z16956) and
matching screw clamps (Z16957).
Recommendation:
Note: To prevent heat loss it is recommended to insulate the refrigerant
pipes separately. Note the national technical regulations (Germany: EnEV or
VDI 2055).
Connection lines
21.10.2015 24 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7.3.1 Tube airtight testing method (recommended procedure), test equipment nitrogen
Make sure that stop valves A and B are closed, and do not open them.
Connect the testing tools (stop valve A).
Add pressure to the refrigerant lines through the service port C of the liquid
stop valve A.
Do not increase pressure to the specified value at once, but rather
gradually:
1. Pressurise to 0.5 MPa (5 bar), wait five minutes, and make sure
that pressure does not drop.
2. Pressurise to 1.5 MPa (15 bar), wait five minutes, and make sure
that pressure does not drop.
3. Pressurise to 4,2 MPa (42 bar) (max. working pressure) and meas-
ure ambient temperature and refrigerant pressure.
4. If specified pressure is maintained for one day and does not drop,
the tubes have passed the test and there are no leaks.
5. If the ambient temperature changes by 1 °C, the pressure will
change by about 0.01 MPa (0.1 bar). Make the necessary correc-
tions.
6. If the pressure drops during steps (2) or (3), a gas leak exists. Look
for the source of the gas leak.
A Stop valve, liquid side B Stop valve, gas side C Service port D Open/close section
Connection lines
21.10.2015 25 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7.4 Connection outdoor module / indoor module (refrigerant lines) Basic Line Ai1 Air
The connections are located on the rear of the indoor module.
Because all connections are on the rear panel, choose a installation dis-
tance from the wall (rear, right side, left side), which is also ensures access
in case of repair.
Pos. Description Thread
A Cable entries
1 Domestic Hot water OUT G¾“int.
2 Cold water IN G¾“int.
3 Refrigerant line IN (heat pump IN
copper pipe 16 mm
4 Refrigerant line OUT (heat pump OUT
copper pipe 10 mm
5 Heating flow G1¼“, flat sealing
6 Heating Return G1¼“, flat sealing
7 Gauge pressure flow; boiler safety group (heating)
G¾“int.
Connection lines
21.10.2015 26 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7.5 Connections (refrigerant and heating) indoor module hydraulic station
All connections are located on the bottom of the indoor module.
Depending on the device type the connections can vary, see table. Select a
the mounting space that ensures the appropriate clearence in any case of
repair.
Figure 8: Connections indoor module (buttom)
Heating
BS7010CH (Pos.)
Heating Hot water
BS7010CHW (Pos.)
Electrical connections X X
Sensor connections (calorimeter)
6 6
Drain (safety valve) 7 7
Heating flow 3,
G1¼“a, flachdichtend
3,
G1¼“a, flat sealing
Heating Return 4,
G1¼“a, flachdichtend
4,
G1¼“a, flat sealing
Refrigerant
(gas side)
2,
16 mm
2,
16 mm
Refrigerant
(liquid side)
1,
10 mm
1,
10 mm
Cold water
(from tank) --
5
G1¼“, flat sealing
Elektrische Anschlüsse Raccords électriques
Electrical connections
Connection lines
21.10.2015 27 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
7.6 Connections outdoor module (refrigerant line)
The refrigerant line connections (flare connection) are located on the right
side of the module. To connect the refrigerant lines, the cover must be re-
moved (4 screws).
Figure 9: Cover refrigerant lines connections (outdoor module)
Figure 10: refrigerant lines connections (flare connection) outdoor module
1 10 mm, liquide side
2 16 mm, gas side
Note:
If metric tubes are used as refrigerant line, you can use the adapter from
the indoor modules.
Refrigerant
21.10.2015 28 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
8 Refrigerant
8.1 Requirements on handling of R410A refrigerant
Ensure that work on air conditioning equipment is only performed by quali-
fied persons. Qualified persons are those who can show that they have
completed technical / vocational training in connection with an approved
advanced training course according to the Ozone Layer Regulation. Com-
pleted training of air conditioning systems or air conditioning technology is
also considered proof of qualification. Ensure that inspections on refrigera-
tion equipment, which require contact with the refrigeration circuit, are only
performed by trained operating personnel. Instructions must be provided by
qualified persons (these regulations can vary within the EC, hence follow the
laws and regulations of the respective country).
8.2 Safety guidelines for the handling of refrigerants
The following safety guidelines must be observed:
Always wear protective goggles and protective gloves!
At normal atmospheric pressure and ambient temperatures, liquid re-
frigerant evaporates so rapidly that it may cause tissue freezing (risk of
going blind) in case of skin /eye contact.
Should the refrigerant contact the skin, flush the affected area repeated-
ly with plenty of cold water. Do not rub the eyes! Visit a doctor immedia-
tely!
Ensure proper ventilation of workplace when working on refrigerant cir-
cuit. Inhaling high concentrations of gaseous refrigerants may cause diz-
ziness and suffocation sensations.
Never perform work on refrigerant circuits in work pits. The gaseous re-
frigerant is heavier than air. Thus, a high concentration could accumulate
in the pit.
Do not smoke! Burning cigarettes can cause the refrigerant to decom-
pose into toxic substances.
Keep refrigerant away from open flames / hot metal. Poisonous gases
could be released.
Never vent refrigerants into the atmosphere. As soon as you open the
refrigerant container / the air conditioning system, the content escapes
at high pressure. Pressure level depends on temperature. The higher the
temperature, the higher the pressure.
Avoid exposure of system components to heat. Otherwise, drain module
first.
When removing the service hoses, do not point connections toward
yourself. Residual refrigerant could escape.
Never change factory setting of adjustment screw on expansion valve.
Refrigerant
21.10.2015 29 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
8.3 Charging refrigerant circuit
Requirements:
Refrigerant line connections between outdoor and indoor module have
been established.
Tube airtight test has been performed (pressure test).
The outdoor module is fully charged with (R410A) refrigerant (in factory).
Procedure:
1. Connect vacuum pump to indoor module (Schrader valve, opens
automatically).
2. Start vacuum pump
3. When using a high-performance vacuum pump, the required vacuum
is generated after 70 minutes (-101 kPa / 5 torr).
4. Close the valve of the connection tube of the vacuum pump.
5. Open the two valves (1 a. 2) on the indoor module. The refrigerant flows
into the entire system.
6. Disconnect the tube of the vacuum pump.
Refrigerant
21.10.2015 30 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
How to open valves:
- Remove both protective caps.
- Open the valve completely by using an allen wrench.
Note: The ball shut-off valves are permanently opened only at time of
commissioning.
7. After both valves are fully open, attach protective caps again and tighten
(20 - 25 Nm).
Note: Refrigerant could escape if protective caps are left off.
Also make sure that the corresponding washers are screwed into the pro-
tective caps again.
8.4 Mounting (heating /domestic water side)
The installation of the heating system (flow/return)) and hot / cold water is to
be performed on the basis of the connection diagrams.
The specifications of current drinking water regulations must be observed.
Antifreeze has to be ensured for all pipes and fittings.
Ball shut-off valve
Ball shut-off valve
Electrical work
21.10.2015 31 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9 Electrical work
Before carrying out electrical work:
Risk of death by electric shock!
Any work on the electrical equipment of the heat pump shall only be per-
formed by professional electricians!
Risk of death by electric shock!
Install circuit breakers for personal protection.
For the power lines, use standard cables of sufficient capacity. Other-
wise there is a risk of short circuits, overheating / fire.
When installing power lines, do not apply tension to the cables. Loosen-
ing connections pose a risk of cables slipping from terminals / breaking;
this can result in overheating / fire.
Master switch on module (beside touch screen): If master switch is acti-
vated (switch is lit), the indoor and outdoor module are ready for opera-
tion.
The exterior temperature sensor is connected to terminals 5o / 5u.
The external disconnection is optionally connected to terminals 49/50.
The electrical disconnection of the outdoor module can take place from
the indoor module (service purposes).
Attention: However, voltage supply of the 3 feed lines- heating element,
compressor, control voltage, is applied to the main terminals/ relays of the
device!
Should it be necessary, disconnect all feed lines from the house fuse
box.
Electrical work
21.10.2015 32 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.1 Electrical connection outdoor module
To connect the outdoor module, the cover of the right side of the module
has to be removed.
Refer to the connection diagramms!
Neutral conductor must be connected too.
Failure to observe: results in destruction of circuit board on outdoor mod-
ule.
9.1.1 Cable cross sections/types
All cable cross sections/types must be specified on site by a professional
electrician, in compliance with applicable DIN standards. Use a shielded
cable for the BUS.
9.2 Electrical connection (indoor module) (hydraulic station / control module)
The electrical connection is performed on the terminal of the indoor module.
Follow the wiring diagram.
9.2.1 Installing external wall sensor
Install external sensor (included in delivery) always vertically (even if tempo-
rary), with cable entry pointing downward. Next, screw connection must be
tightened enough to allow sealing insertion of cable and to prevent water
from entering the housing.
When performing temporary installation, sensor might have to be mounted
on board, which is fastened to wall using a steel nail.
To prevent transport damages, front and side panels of heat distribution
station are separately enclosed.
After all connections are completed, install plates at specified positions (in-
sert and press)
9.2.2 Power supply- Heating element
The power supply (230 V or 400 V) is selectable. The power supply is de-
fined by linking the terminals on the control board.
9.2.3 Heating element - thermostat setting
The thermostat of the heating element is permanently set on 75 °C. Con-
nection and disconnection takes place via the heat pump controller. The
electric resistance heater has a safety temperature limiter. In case of trigger-
ing, it must be reset manually. To reset use the button on the bottom of the
safety temperature limiter (under the cap).
A G S 5 4
Electrical work
21.10.2015 33 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.3 Electrical and BUS connection (outdoor module BS 7010.5)
Pos. Description
1
BUS connection (use screened line) Terminals: A = + B = - GND = GND
2 Electrical connection (230 V)
Electrical work
21.10.2015 34 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.4 Electrical and BUS connection (outdoor module, BS 7006.5)
Pos. Description
1
BUS connection (use screened line) Terminals : GND = GND B = - A = + 12 V = not connected - = Fan + = Fan
2 Electrical connection (230 V)
Electrical work
21.10.2015 35 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.5 Electrical connection Basic Line Ai1 Air (5010.5) (indoor module)
9.6 Electrical and BUS connection Basic Line BS Hyd 5010 hydraulic station
9.6.1 DIP-Switch (outdoor module)
In case of replacing or repairing: Check the position of the DIP switches on
the main board (outdoor module). The correct switch position is shown on
the wiring diagram (outdoor module).
Electrical work
21.10.2015 36 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.7 Electrical wiring diagram Basic Line Ai1 Air / BS 7010 (outdoor module)
Electrical work
21.10.2015 37 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.8 Electrical wiring diagram - Basic Line Ai1 Air (indoor module)
Electrical work
21.10.2015 38 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.9 Electrical wiring diagram - Basic Line BS Hyd 5010 hydraulic station (indoor module)
Electrical work
21.10.2015 39 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.10 WWPR2 Controler - connections
Deutsch English Français
B1 - Temperatur Raum B1 – Temp. room B1 – Temp. pièce
B2 - Temperatur Außen B2 – Temp. outdoor B2 - Temp. extérieur
B3 - Temperatur Warmwasser B3 – Temp. hot water B3 – Temp. ECS
B4 - Temperatur Vorlauf B4 – Temp. flow B4 – Temp. depart chauffage
B5 - Temperatur Rücklauf B5 – Temp. return B5 – Temp. retour chauffage
B6 - Temperatur Speicher B6 - Temperatur buffer B6 – Temp. ballon tampon
B7 - B7 - B7 -
DI1 - EVU Abschaltung/ SG Ready A DI1 - EVU / SG Ready A DI1 – Coupure ext. / SG Ready A
DI2 - Sollwertbeeinflussung/ SG
Ready B DI2 - Setpoint/ SG Ready B DI2 – Valeur cons./ SG Ready B
DI3 - Störmeldung Heizungsseitig DI3 – Alert heating side
DI3 – Message panne côte chauf-
fage
DI4 - Frei DI4 – Free DI4 – Libre
DI5 - Frei DI5 – Free DI5 – Libre
DI6 - Frei DI6 – Free DI6 – Libre
Di7 - Frei Di7 – Free Di7 – Libre
Y1 – Y1 – Y1 –
Y2 - Y2 - Y2 -
Y3 - Pumpe Heizung PWM Y3 - Pump heating PWM Y3 - Pompe chauffage PWM
J6 – BMS Card J6 – BMS Card J6 – BMS Card
J7 – Displayport J7 – Displayport J7 – Displayport
J8 – Erweiterungsbus J8 – Bus extensions J8 – Bus d’extension
J9 – tLan J9 – tLan J9 – tLan
J10 – AEH-Bus J10 – Bus outside unit J10 – Bus unité extérieur
J11 – EVD 1 J11 – EVD 1 J11 – EVD 1
NO1 – Pumpe Trenntauscher NO1 – Pump exchanger NO1 – Pompe échangeur sép.
NO2 – Stetiges Kühlsignal NO2 – Cont. cooling signal NO2 – Signal rafraîchissement
constant
NO3 – Freig. Außeneinheit NO3 – Release outside unit NO3 – Autorisation unité extérieur
NO4 – Alarm NO4 – Alarm NO4 – Alarme
NO5 – Speicherentladepumpe NO5 – Buffer unloading pump NO5 – Pompe décharge ballon
NO6 – Ext. Wärmeerzeuger NO6 – Ext. heat generator NO6 – Producteur de chaleur ext.
NO7 – MKV WW / Pumpe WW NO7 – MBV HW / Pump HW NO7 – Vanne ECS / pompe ECS
NC7 - NC7 - NC7 -
Electrical work
21.10.2015 40 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
9.11 Electrical connections
Commissioning
21.10.2015 41 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
10 Commissioning
During commissioning of machine, anticipate the following specific risks.
Risk of total loss!
Faulty connections can cause unexpected startup of machine / uncon-
trolled machine operation.
Mix up of connections causes motor to run in wrong direction; this could
damage the machine.
Incorrectly wired connections can destroy electrical / electronic compo-
nents.
Electrostatic processes / power failure can pose a risk for electronic com-
ponents and also result in software errors.
To avoid damage to machine / injuries during commissioning of machine,
the following points must be observed:
Commissioning of machine shall only be performed by qualified persons, in
compliance with safety instructions.
Activate all safety devices and emergency-stop switches prior to commis-
sioning.
Check motor for correct direction of rotation prior to commissioning.
Also read chapter 1.2.
10.1 Pre-startup checks
Before starting machine, check first the requirements according to the fol-
lowing checklist.
All electrical feed lines in the corresponding cross-sections are wired to
the terminals, as per connection plan. The BUS cable is shielded.
The main switch is in "OFF" position.
The fuses in the fuse box are in compliance with the specifications in
the wiring diagram (circuit breaker, switch, type C for compressor feed
line!).
The hydraulic connections for heat source, space heating and domes-
tic water are connected.
The ball shut-off valves on the refrigerant lines are open.
The following positions must also be checked.
The gas stop valve as well as the liquid stop valve are fully open.
Before operation, check if all plates, fuses and other protective devices
are properly installed. Components that are rotating, hot / under high
voltage can cause injuries.
Do not touch switch with wet hands. This poses a risk of electric shock.
The module must be grounded. Do not connect the ground wire to gas /
water lines, lightning rods / telephone grounding lines. Improperly
grounded module poses a risk of electric shock.
Use circuit breakers (ground fault interrupter, isolating switch (+B fuse),
and moulded case circuit breaker) with the specified capacity. Failure of
Commissioning
21.10.2015 42 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
module / fire may result from circuit breaker when capacity exceeds
specifications
Do not touch refrigerant tubes with bare hands during operation. The re-
frigerant tubes are hot / cold, depending on condition of flowing refriger-
ant. Contact with tubes poses a risk of burns / frostbite.
Turn on main power switch 12 hours before starting operation.
This allows the oil sump heater to bring lubricant to operating temperature.
Starting operation directly after turning on power switch can cause severe
damage to internal parts. Keep main power switch on during period of ope-
ration.
After finishing operation, wait at least five minutes before turning main
power switch off. Otherwise, there is a risk of water leak / module failure.
Risk of total loss!
Repeated restart of the heat pump can result in total loss!
In case of heat pump failure, an inspection by qualified and authorised
personnel must be performed before restart.
Info: Controller settings must initially only be performed during the first
start of the machine.
During restart this is not necessary since the settings are stored (the set-
tings remain stored even in case of power failure).
Info: During initial commissioning, the specified values are often outside
the limits in the beginning, thus numerous warnings can appear.
For this reason, service personnel can suppress the warning messages
for this period; see Operating instructions for heat pump controller.
After completing installation and wiring and tubing of indoor and outdoor
modules, check for refrigerant leaks, loose power supply or control wir-
ing, wrong polarity, and ensure that no single phase in the power supply
is disconnected.
Check also the solidification point of the water-glycol mixture. It must be
below the expected minimum temperature of the medium.
Risk of total loss!
Do not start module if insulation resistance is below 1.0 MΩ.
Commissioning
21.10.2015 43 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
Insulation resistance
After installation or after module has been cut off from power supply for an
extended period, the insulation resistance will drop below 1 MΩ due to re-
frigerant accumulating in the compressor. This is not a malfunction. Pro-
ceed as follows:
1. Remove wires from compressor and measure insulation resistance
of compressor.
2. If insulation resistance is below 1 MΩ, the compressor is faulty or
the resistance dropped due to refrigerant accumulation in com-
pressor.
3. After wires are connected and power is switched on, compressor
starts to warm up. Remeasure insulation resistance based on acti-
vation times indicated below.
The insulation resistance drops due to refrigerant accumulation in
the compressor. Resistance will rise above 1 MΩ after compressor
has warmed up for 4 hours.
(The required compressor warm-up time varies according to at-
mospheric conditions and refrigerant accumulation.)
To operate the compressor with refrigerant accumulation, it must
be warmed up at least 12 hours to prevent failure.
4. If insulation resistance rises above 1 MΩ, the compressor is not
faulty.
10.2 Initial start of heat pump
The initial start of the heat pump is performed by a qualified
WATERKOTTE system partner.
Figure 11:ON / OFF switch (arrow)
Switch is lit => power supply switched on (regular operation)
Starting operation directly after turning on power switch can cause severe
damage to internal parts! Keep main power switch on during period of op-
eration.After all checks have been conducted (Kap. 10), proceed as follows:
1. Turn on main power switch (on heat pump)
2. The compressor does not start immediately, because the oil dump
Commissioning
21.10.2015 44 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
heater has to heat the oil up to operating temperature. This takes
up to 30 min in cool ambient temperature.
3. Once the operating temperature is reached, the compressor starts.
10.3 Control of entire operation
This heat pump is equipped with an efficient electronic control system. All
necessary settings and options are described in the controller manual.
Tip: The correct use of the controller saves money. Particularly the correct
settings of flow temperature, hot water temperature, heating curve and
heating times can result in substantial cost savings.
10.4 Turning heat pump off
After finishing operation, wait at least five minutes before turning main pow-
er switch off. Otherwise, there is a risk of water leak / module failure.
Procedure:
Switch off main switch of heat pump.
Switching off circuit breaker: Compressor, control voltage and electrical
heating element.
10.5 Taking heat pump out of operation for extended period
- see 10.4-
Total loss (freezing)
At low outdoor temperatures the device and the pipes must be protected
from freezing.
Technical data
21.10.2015 45 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
11 Technical data Basic Line Ai1 Air / Basic Line BS 7010 5006.5 5010.5
Heating capacity (A-7/W35) kW* 6.6 7.1
Power consumption 2.8 2.8
COP (A-7/W35) EN14511 2.4 2.6
Heating capacity (A2/W35) kW* 7.5 10.8
Power consumption 2.3 2.8
COP (A2/W35) controlled (EN14511) 3.54
(controlled at 4.5 kW)
3.55 (controlled at 6.7 kW)
Heating capacity (A7/W35) kW* 8.6 12.3
Power consumption 2.3 2.9
COP (A7/W35) controlled (EN14511) 4.61
(controlled at 5.5 kW)
4.49 (controlled at 8.0 kW)
Cooling capacity (A35/W7) kW* - 7.8
Power consumption - 3.0
COP (A35/W7) EN14511 - 2.5
Cooling capacity (A35/W18) kW* - 10.6
Power consumption - 3.2
COP (A35/W18) EN14511 - 3.3
Heating water flow rate (∆t=5K ) at 8.0 kW m³/h 1.0 (at 6.0 kW) 1.4 (at 8.0 kW)
Air volume flow (max) m³/h 2800 7000
Application limit A-15/W45; A-7/W50; A0/W55
Compressor rolling piston
Refrigerant R410A
Noise level at 5 m distance (outdoor module) free field dB(A) 33 47
Sound level power dB(A) 58 69 Electrical data Electrical power supply 220-240V, 1~, 50 Hz 220-240V, 1~, 50 Hz
Electrical power supply - Electrical resistance heating (Power supply selectable
220-240V, 1~, 50 Hz
380-415 V, 3~, 50 Hz 220-240V, 1~, 50 Hz
380-415 V, 3~, 50 Hz
Max. operating current A 18.5 18.5 Customer-supplied main fuse C 25 A C 25 A Customer-supplied control fuse A 10 10
Current consumpt. max., electr. resistance heating (230 V) A 26.1 26.1
Current consumpt. max., electr. resistance heating (400 V) A 8.7 8.7
Electrical resistance heating kW 6 6
Customer-supplied main fuse: Electrical resistance heating (220-240 V)
A B 32 A B 32 A
Customer-supplied main fuse: Electrical resistance heating (380-415 V
A B 16 A B 16 A
Dimensions, weight, connections Refrigerant volume kg 1.9 3.
Weight outdoor module kg 100 120
Weight indoor module (Basic Line Ai1 Air) kg 145 145
Weight hydraulic station (Basic Line BS Hyd 5010) kg 39-40 39-40
Volume tank (Basic Line Ai1 Air)) l 170 170
Refrigerant lines (outdoor module) 16 / 10 mm 16 / 10 mm
Heating connections (hydraulic station) 1¼“a 1¼“a
Dimensions (outdoor module) W x H x D mm 1235x855x510 1055x1194x460
Dimensions (indoor module) W x H x D (Basic Line Ai1 Air) mm 600x1850X650 600x1850X650
Dimensions hydraulic station W x H x D (Basic Line BS Hyd 5010)
mm 743x750x303 743x750x303
1) Tolerances as per EN 12900 apply to the performance data listed
Connection diagram
21.10.2015 46 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12 Connection diagram
12.1 Basic Line Ai1 Air with underfloor heating, without single room control
Connection diagram
21.10.2015 47 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.2 Basic Line Ai1 Air with underfloor heating, with single room control
Connection diagram
21.10.2015 48 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.3 Basic Line Ai1 Air with radiators / fan convectors
Connection diagram
21.10.2015 49 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.4 Basic Line Ai1 Air with hydraulic compensator
Connection diagram
21.10.2015 50 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.5 Basic Line Ai1 Air hydraulic compensator and additional heater
Connection diagram
21.10.2015 51 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.6 Basic Line BS 7010 with underfloor heating, without single room control
Connection diagram
21.10.2015 52 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.7 Basic Line BS 7010 with underfloor heating, without single room control, decen-tral domestic hot water preparation
Connection diagram
21.10.2015 53 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
12.8 Legend (hydraulic schemes)
No. Description
1 Underfloor heating
2 Heat pump
3 Indoor module
4 Outdoor module
5 Flexible connections
6 Fitting group for flushing and venting
7 Dirt trap integrated in ball valve
8 Flow rate monitoring
9 Groundwater pump
10 Plate heat exchanger
11 Motor-operated changeover ball valve (interruption-free)
12 Optimised thermal tank (compact condensing boiler)
13 Optimised thermal tank (return series storage)
14 Temperature sensor
15 Radiators or convectors
16 Bronze pump
17 Pressure regulator
18 Backflow preventer
19 Safety valve
20 Valve, control deviation 1 to 2 Kelvin
21 Diaphragm expansion tank for domestic water systems
22 Diaphragm expansion tank with isolation fitting
23 Domestic cold water
24 Domestic hot water
25 Circulation
26 Domestic water heater
27 250 l domestic hot water tank
28 Air separator with air diverter
29 Differential pressure overflow valve
30 Pressure controlled circulation pump
31 Charging and draining valve
32 Circulating pump
33 Air separator with vent, gauge and safety valve
34 Safety group
35 Safety valve with vent and gauge
36 Tacosetter for hydraulic compensation
37 Supply compact condensing boiler 250 l
38 Pool
39 Motor-driven mixer
40 Solar diaphragm expansion tank with isolation fitting
41 Heat source module
42 Heat source module natural cooling
43 Motor-driven changeover ball valve, interruption-free (heating and cooling)
44 2nd heat generator
45 Check valve
46 Balancing valve for hydraulic compensation
47 Dirt trap
48 Motor-driven changeover valve
49 Motor-driven valve
50 Connections integrated coil tube heat exchanger
51 Pool heat exchanger
52 Ball valve
53 Optimised thermal tank with integrated smooth pipe heat exchanger
54 Geothermal energy probes
55 Compact condensing boiler 1000 l to 2500 l
56 Thermostat valve
57 Temperature controller
Connection diagram
21.10.2015 54 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
No. Description
58 Gravity brake
59 Tichelmann hydraulic expansion set
60 Tichelmann hydraulic basic set
61 Solar connection set
62 Collector temperature sensor
63 Vacuum tube
64 Electrical resistance heating
65 Compact condensing boiler 400 Litre with domestic water heater (SET 454)
66 Control valve
67 Exterior temperature sensor
68 Pilot room sensor
69 Motor-driven ball valve
70 Safety group with safety valve, pressure regulator, backflow preventer and diaphragm expansion tank with flow fitting for domestic water systems.
71 215 l plastic tank
72 Funnel
73 Copper immersion tube with suction strainer, non-return valve and pump connection
74 Self-priming pump WJ 301 EM with 2m connecting cable (230V), rated input 1100 W, connections suc-tion side and pressure side Rp1"
75 1500 mm flow-line hose with 1 1/4“ union nut with 2 gaskets and reducing nipple 1 1/4“a x 1“a
76 1500 mm return flow hose with 1 1/4“ union nut with 2 gaskets
77 Air separator, safety group with gauge, air diverter, safety valve, diaphragm expansion tank with isolation fitting.
78 Motor-operated changeover ball valve (domestic hot water preparation)
79 Motor-driven changeover ball valve (pool)
80 Multilayer filter for pool water cleaning
81 Pool water - disinfection system
82 PH value control and correction system
83 Pool water drain
84 Pool water circulation pump
Refrigeration circuit Basic Line Ai1 Air / BS 7010
21.10.2015 55 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
13 Refrigeration circuit Basic Line Ai1 Air / BS 7010
Figure 12: Refrigeration circuit Basic Line Ai1 Air
Figure 13: Refrigeration circuit Basic Line Ai1 Air with hot water tank
lgb
Refrigeration circuit Basic Line Ai1 Air / BS 7010
21.10.2015 56 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
MSR-Nr Instrumentation Component
PIC/1 Measurement of pressure readout in the controller display and control in the electrical switchboard
Pressure transmitter LP
TIC/2 Measurement of temperature, readout in the controller display and control in the electrical switchboard
NTC 10K, gauge: suction gas over-heating
TIC/3 Measurement of temperature, readout in the controller display and control in the electrical switchboard
NTC 10K, gauge: condenser IN
TIC/4 Measurement of temperature, readout in the controller display and control in the electrical switchboard
NTC 10K, gauge: condenser OUT
PIC/5 Measurement of pressure readout in the controller display and control in the electrical switchboard
Pressure transmitter HP
PZ+/6 Safety pressure relief valve (high pressure) Safety pressure switch HP
PZ-/7 Safety pressure relief valve (low pressure)
TIC/8 Measurement of temperature, readout in the controller display and control in the electrical switchboard
NTC 10K, gauge: pressure gas
TIC/9 Measurement of temperature, readout in the controller display and control in the electrical switchboard
Temperature sensor Gauge: heating flow (indoor module)
TIC/10 Measurement of temperature, readout in the controller display and control in the electrical switchboard
Temperature sensor: heating return (indoor module)
TIC11 Measurement of temperature, readout in the controller display and control in the electrical switchboard
Temperature sensor: hot water tem-perature
Nr. Instrumentation Type
A For hydraulic station / heat utilization
1 Compressor Rolling piston
2 Condenser corrugated plates, copper soldered
3 Check valve
4 4- way motor ball valve
5 Expansion valve Electronic
6 Evaporator Heat exchanger (lamellae)
7 Flüssigkeitsabscheider
8 Refrigerant receiver
9 Valve (hot water)
10 Electrical heating element
11 Circulation pump
12 Hot water tank
13 Security group
A Heating side
B Hot water side
Maintenance and inspection
21.10.2015 57 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
14 Maintenance and inspection
Have your WATERKOTTE heat pump maintained annually. This will ensure
the operational safety and efficiency of your heat pump. Additional infor-
mation is available from your WATERKOTTE service partner.
During maintenance, the technical condition of the heat pump system is
checked as well (target / actual comparison). In this process, a diagnostic
measurement of the thermodynamic part ensures that the efficiency is
maintained at an optimum level.
Note:
In the event of severe contamination it is recommended to clean the mod-
ule between maintenance cycles. At the same time, also remove residues
such as leaves and the like from the defrosting tray and check the conden-
sation drain (blockages) of the outdoor module.
Additional inspection points are:
Check heating circuit: System pressure, function of expansion tank, venting, rotation direction of pump and volume setting.
Check cooling circuit: Screw connections, tightness, charge level, refrig-erant control, diagnosis measurement log.
Check setting of control. Tightness check: The legally required test intervals are dependent on re-
frigerant charge weight. Refer to heat pump log book for more detailed information.
Maintenance and inspection
21.10.2015 58 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
Maintenance and inspection
21.10.2015 59 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
Maintenance and inspection
21.10.2015 60 / 60
Copyright 2014 by: WATERKOTTE GmbH. Subject to changes.
WATERKOTTE GmbH, Gewerkenstraße 15, D-44628 Herne
Tel.: 0049/(0)2323/9376-0, Fax: 0049/(0)2323/9376-99, Service: 0049/(0)2323/9376-350
E-Mail: [email protected]
Internet: http://www.waterkotte.de