5
BUILDING SECTION SYMBOL WALL SECTION SYMBOL ELEVATION SYMBOLS REFERENCE KEYNOTE SYMBOL A101 1 SIM DETAIL SYMBOL A101 1 SIM SIMILAR, TYPICAL, OR MIRRORED REFERENCE SIMILAR, TYPICAL, OR MIRRORED REFERENCE SPOT DIMENSIONS HEIGHT INDICATION (ABOVE RESPECTIVE GROUND FLOOR LEVEL ELEVATION) 0' - 0" WINDOW/ DOOR TAG SYMBOLS WALL TAG SYMBOL PARTITION TYPE 1,234 SF 12 ROOM NUMBER AREA OCCUPANT LOAD ROOM TAG SYMBOL Room name 101 CH= 1'-0" CEILING TAG SYMBOL HEIGHT INDICATION (ABOVE RESPECTIVE FLOOR LEVEL ELEVATION) DETAIL SHEET NUMBER SHEET NUMBER BUILDING SECTION NUMBER SHEET NUMBER DETAIL SHEET NUMBER BUILDING SECTION NUMBER SHEET NUMBER ELEVATION NUMBER A1 A101 E3/A504 DETAIL / SHEET # E3/A504 A101 1 SIM A101 1 SIM A101 1 SIM 1 A101 1t 101 DOOR TAG 1t WINDOW TAG 1 KEYED NOTE - REFERS TO KEYNOTE LEGEND ON EACH SHEET PROJECT LOCATION STEWART ST. BR E L A ND DR . S. L OC US T ST . W I L LI A M S A V E . SW E E T A V E . ES P I N A S T. OFFICE 138 OFFICE 136 WORK ROOM 163 OFFICE 163B CONFERENCE ROOM 163L OFFICE 163C OFFICE 163D OFFICE 163E OFFICE 163F OFFICE 163K OFFICE 163A OFFICE 163G ASSIST. DEAN 163H ASSOC. DEAN 163I DEAN'S OFFICE 164 SECRETARIAL 163M HALL 100 HALL 102 OCCUPANCY CLASSIFICATION: B (BUSINESS) FUNCTION OF SPACE: BUSINESS AREA OCCUPANT LOAD FACTOR: 100 GROSS NUMBER OF OCCUPANTS: 43 OCCUPANCY CLASSIFICATION: B (BUSINESS) FUNCTION OF SPACE: ACCESSORY STORAGE AREAS OCCUPANT LOAD FACTOR: 300 GROSS NUMBER OF OCCUPANTS: 1 2 3 4 1 2 2 1 2 2 4 2 2 2 1 2 2 10 D A 3 5 16 21 B C 6 9 23 11 12 16 5 21 MAX TRAVEL DISTANCE: 88' MAX TRAVEL DISTANCE: 100' 3'-0" # # A TOTAL NUMBER OF OCCUPANTS IN ROOM COMBINED NUMBER OF OCCUPANTS ALONG COMMON PATH OF TRAVEL EXIT IDENTIFICATION PROJECT INFORMATION MODIFICATIONS TO EXISTING BUILDING LEVEL OF ALTERATIONS: LEVEL 1 Per IBC 2015 - 304.1 EXISTING OCCUPANCY CLASSIFICATION - GROUP B (UNCHANGED) EXISTING CONSTRUCTION TYPE - IIIB SPRINKLERED: NO TOTAL GSF OF SUITE: 4,691 GSF MEANS OF EGRESS - Per IBC 2015 CHAPTER 10 MINIMUM REQUIRED EGRESS STAIRS 0.3"/ OCCUPANT EXITS 0.2"/ OCCUPANT EGRESS DOORS: 32" MINIMUM CLEAR EXIT TRAVEL DISTANCE REQUIREMENTS - Per IBC 2015 1017.2 OCCUPANCY CLASSIFICATION B (NON- SPRINKLERED) - 200'-0" MAX DISTANCE OCCUPANT LOAD FACTOR - Per IBC 2015 1004.1.2 BUSINESS AREA (B) - 100 GSF/OCCUPANT OCCUPANT LOAD: 4,278 GSF/100 = 43 OCCUPANTS ACCESSORY STORAGE AREAS - 300 GSF/OCCUPANT OCCUPANT LOAD: 1 TOTAL OCCUPANT LOAD: 44 OCCUPANTS EXIT CORRDOR WIDTH REQUIREMENTS - Per IBC 2015 1020.2 OCCUPANCY: "AN OCCUPANT LOAD OF LESS THAN 50" REQUIRED: 36" CLEAR WIDTH EXISTING WIDTH: 53" MIN. CODE REVIEW PROJECT INFORMATION MAX DISTANCE= 99'-0" A. Additive Alternate #1 Renovations to room 163 G to include: a. Removal and replacement of existing carpet b. Removal and replacement of existing light fixtures and new LED fixtures to match the new light fixtures in the suite’s conference room c. Removal and replacement of the existing HVAC grilles and diffusers to match the new diffusers in the suite’s conference room d. Removal and replacement of the acoustical ceiling tiles to match the new ceiling tiles in the suite’s conference room. Existing ceiling grid to remain and to receive new paint. Modify ceiling grid as required for new lighting layout. e. Preparation of existing substrates for new paint throughout U.N.O. New paint to be provided throughout the suite U.N.O. B. Additive Alternate #2 Re - finishing of existing closet doors a. Removal of existing closet doors and door hardware as indicated on the drawings. b. Strip existing finish coat and stain. Sand surface with fine grit sandpaper. Re - stain and finish (clear coat) to match door on conference room 163L or as selected by NMSU Architect ALTERNATE SCHEDULE R E G I S T E R E D A R C H I T E C T S T A T E O F N E W M E X I C O RICHARD HAAS NO. 2530 This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto. DESERT PEAK ARCHITECTS P.C. 311 N MAIN STREET LAS CRUCES NEW MEXICO 88001 P. 575.528.0022 SHEET NO. SHEET TITLE ISSUE: D C B A 1 3 4 5 2 PROJECT NO. 206 - 101 G001 COVER SHEET 10/07/2019 DEAN'S SUITE RENOVATIONS NMSU, BRELAND HALL 1525 STEWART ST. LAS CRUCES, NM 88003 CONSTRUCTION DOCUMENTS 10/07/2019 DRAWING INDEX OWNER: NEW MEXICO STATE UNIVERSITY CONTACT: ROBERT ESTRADA - PROJECT MANAGER CONSULTANTS: ARCHITECT: DESERT PEAK ARCHITECTS, INC 311 NORTH MAIN STREET LAS CRUCES, NM 88005 P. (575) 528 - 0021 CONTACT: RICHARD HAAS VICINITY MAP DEAN'S SUITE RENOVATIONS COVER G-SHEETS G001 COVER SHEET NMSU - BRELAND HALL 1525 STEWART ST. ELECTRICAL E2.0 FIRST FLOOR LIGHTING PLAN ELECTRICAL ENGINEER PILLAR ENGINEERING, LLC. 280 EAST FOSTER STE B. LAS CRUCES, NM 88005 P: (575) 647-1927 CONTACT: MARTIN PILLAR, PE SYMBOL LEGEND 2015 INTERNATIONAL BUILDING CODE 2015 EXISTING BUILDING CODE 2015 NM COMMERCIAL CODES 2015 UNIFORM MECHANICAL CODE 2015 NM MECHANICAL CODE 2017 NATIONAL ELECTRICAL CODE 2017 NM ELECTRICAL CODE 2009 INTERNATIONAL ENERGY CONSERVATION CODE DESIGN CODES ARCHITECTURAL A101 FIRST FLOOR PLAN & REFLECTED CEILING PLAN A602 WALL PARTITION TYPES AND SCHEDULES D101 DEMOLITION PLAN DEMOLITION 1/8" = 1'-0" G001 A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT SCHEDULE A 34" .2 170 23 B 64" .2 320 23 C 64" .2 320 23 + ADDITIONAL BUILDING OCCUPANTS (OCCUPANCY COUNT REMAINS UNCHANGED IN NEW WORK) D 64" .2 320 21 MARK WIDTH OF OPENING FACTOR ALLOWABLE # OF OCCUPANTS SERVED ACTUAL # OF OCCUPANTS SERVED OPERABLE GATE - BY OTHERS NMSU PROJECT # 3568 STAGING & STORAGE WORK AREA STEWART ST. BRELAND DR. PROPOSED LOCATION FOR STAGING AND STORING. COORDINATE WITH NMSU BRELAND HALL M a r k D a t e D e s c r i p t i o n

OWNER: NMSU PROJECT # 3568 CONSULTANTS: DEAN'S ......D101 DEMOLITION PLAN DEMOLITION G001 1/8" = 1'-0" A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OWNER: NMSU PROJECT # 3568 CONSULTANTS: DEAN'S ......D101 DEMOLITION PLAN DEMOLITION G001 1/8" = 1'-0" A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT

BUILDING SECTION SYMBOL WALL SECTION SYMBOL

ELEVATION SYMBOLS REFERENCE KEYNOTE SYMBOL

A101

1SIM

DETAIL SYMBOL

A101

1SIM

SIMILAR, TYPICAL, OR MIRRORED REFERENCE

SIMILAR, TYPICAL, OR MIRRORED REFERENCE

SPOT DIMENSIONS

HEIGHT INDICATION (ABOVE RESPECTIVE GROUND FLOOR LEVEL ELEVATION)

0'-0"

WINDOW/ DOOR TAG SYMBOLS

WALL TAG SYMBOL

PARTITION TYPE

1,234 SF

12

ROOM NUMBER

AREA

OCCUPANT LOAD

ROOM TAG SYMBOL

Room name101

CH= 1'-0"

CEILING TAG SYMBOL

HEIGHT INDICATION (ABOVE RESPECTIVE FLOOR LEVEL ELEVATION)

DETAIL

SHEET NUMBER

SHEET NUMBER

BUILDING SECTIONNUMBER

SHEET NUMBER

DETAIL

SHEET NUMBER

BUILDING SECTION NUMBER

SHEET NUMBER

ELEVATION NUMBER

A1 A101

E3/A504

DETAIL / SHEET #E3/A

504

A101

1SIM

A101

1SIM

A101

1SIM

1

A101

1t

101 DOOR TAG

1tWINDOW TAG

1

KEYED NOTE - REFERS TO KEYNOTE LEGEND ON EACH SHEET

PROJECT LOCATION

STEWART ST.

BR

ELA

ND

DR

.

S. LO

CU

ST

ST

.

WIL

LIA

MS

AV

E.

SW

EE

T A

VE

.

ES

PIN

A S

T.

OFFICE

138

OFFICE

136

WORK ROOM

163

OFFICE

163B

CONFERENCE ROOM

163L

OFFICE

163C

OFFICE

163D

OFFICE

163E

OFFICE

163F

OFFICE

163K

OFFICE

163A

OFFICE

163G

ASSIST. DEAN

163H

ASSOC. DEAN

163I

DEAN'S OFFICE

164

SECRETARIAL

163M

HALL

100

HALL

102

OCCUPANCY CLASSIFICATION: B (BUSINESS)FUNCTION OF SPACE: BUSINESS AREAOCCUPANT LOAD FACTOR: 100 GROSSNUMBER OF OCCUPANTS: 43

OCCUPANCY CLASSIFICATION: B (BUSINESS)FUNCTION OF SPACE: ACCESSORY STORAGE AREASOCCUPANT LOAD FACTOR: 300 GROSSNUMBER OF OCCUPANTS: 1

2

3

4

1

2

2

1

2

2

4

2

2

2

1

22

10

D

A

3

5

16

21

B

C

6

9

2311

12

16

5

21

MAX TRAVEL DISTANCE: 88'

MAX TRAVEL DISTANCE: 100'

3'-0

"

#

#

A

TOTAL NUMBER OF OCCUPANTS IN ROOM

COMBINED NUMBER OF OCCUPANTS ALONG COMMON PATH OF TRAVEL

EXIT IDENTIFICATION

PROJECT INFORMATION

MODIFICATIONS TO EXISTING BUILDING LEVEL OF ALTERATIONS: LEVEL 1

Per IBC 2015 - 304.1EXISTING OCCUPANCY CLASSIFICATION - GROUP B (UNCHANGED)

EXISTING CONSTRUCTION TYPE - IIIBSPRINKLERED: NO

TOTAL GSF OF SUITE: 4,691 GSF

MEANS OF EGRESS - Per IBC 2015 CHAPTER 10

MINIMUM REQUIRED EGRESS STAIRS 0.3"/ OCCUPANTEXITS 0.2"/ OCCUPANTEGRESS DOORS: 32" MINIMUM CLEAR

EXIT TRAVEL DISTANCE REQUIREMENTS - Per IBC 2015 1017.2

OCCUPANCY CLASSIFICATION B (NON- SPRINKLERED) - 200'-0" MAX DISTANCE

OCCUPANT LOAD FACTOR - Per IBC 2015 1004.1.2

BUSINESS AREA (B) - 100 GSF/OCCUPANTOCCUPANT LOAD: 4,278 GSF/100 = 43 OCCUPANTS

ACCESSORY STORAGE AREAS - 300 GSF/OCCUPANTOCCUPANT LOAD: 1

TOTAL OCCUPANT LOAD: 44 OCCUPANTS

EXIT CORRDOR WIDTH REQUIREMENTS - Per IBC 2015 1020.2

OCCUPANCY: "AN OCCUPANT LOAD OF LESS THAN 50"

REQUIRED: 36" CLEAR WIDTH EXISTING WIDTH: 53" MIN.

CODE REVIEW

PROJECT INFORMATION

MAX DISTANCE= 99'-0"

A. Additive Alternate #1 – Renovations to room 163 G to include:a. Removal and replacement of existing carpetb. Removal and replacement of existing light fixtures and new LED

fixtures to match the new light fixtures in the suite’s conference room

c. Removal and replacement of the existing HVAC grilles and diffusers to match the new diffusers in the suite’s conference room

d. Removal and replacement of the acoustical ceiling tiles to match the new ceiling tiles in the suite’s conference room. Existing ceiling grid to remain and to receive new paint. Modify ceiling grid as required for new lighting layout.

e. Preparation of existing substrates for new paint throughout U.N.O. New paint to be provided throughout the suite U.N.O.

B. Additive Alternate #2 – Re-finishing of existing closet doorsa. Removal of existing closet doors and door hardware as indicated

on the drawings.b. Strip existing finish coat and stain. Sand surface with fine grit

sandpaper. Re-stain and finish (clear coat) to match door on conference room 163L or as selected by NMSU Architect

ALTERNATE SCHEDULE

RE

G

I ST ERED A RCH

I T

EC

T

ST

AT

E

OF NEWMEX

ICORICHARD HAAS

NO. 2530

This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.

DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022

SHEET NO.

SHEET TITLE

ISS

UE

:

D

C

B

A

1 3 4 52

PROJECT NO.206-101

G001

COVER SHEET

10/0

7/2

019

DE

AN

'S S

UIT

E R

EN

OV

AT

ION

S

NM

SU

, B

RE

LA

ND

HA

LL

15

25

ST

EW

AR

T S

T.

LA

S C

RU

CE

S, N

M 8

80

03

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

10/07/2019

DRAWING INDEXOWNER:NEW MEXICO STATE UNIVERSITY

CONTACT: ROBERT ESTRADA - PROJECT MANAGER

CONSULTANTS:

ARCHITECT:

DESERT PEAK ARCHITECTS, INC

311 NORTH MAIN STREET

LAS CRUCES, NM 88005

P. (575) 528 - 0021

CONTACT: RICHARD HAAS

VICINITY MAP

DEAN'S SUITE RENOVATIONSCOVER G-SHEETS

G001 COVER SHEET

NMSU - BRELAND HALL1525 STEWART ST.

ELECTRICAL

E2.0 FIRST FLOOR LIGHTING PLAN

ELECTRICAL ENGINEER

PILLAR ENGINEERING, LLC.280 EAST FOSTER STE B.LAS CRUCES, NM 88005P: (575) 647-1927

CONTACT: MARTIN PILLAR, PE

SYMBOL LEGEND

2015 INTERNATIONAL BUILDING CODE2015 EXISTING BUILDING CODE2015 NM COMMERCIAL CODES2015 UNIFORM MECHANICAL CODE2015 NM MECHANICAL CODE2017 NATIONAL ELECTRICAL CODE2017 NM ELECTRICAL CODE2009 INTERNATIONAL ENERGY CONSERVATION CODE

DESIGN CODES

ARCHITECTURAL

A101 FIRST FLOOR PLAN & REFLECTED CEILING PLAN

A602 WALL PARTITION TYPES AND SCHEDULES

D101 DEMOLITION PLAN

DEMOLITION

1/8" = 1'-0"G001A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM

PROJECT NORTH

LEGEND

EXIT SCHEDULE

A 34" .2 170 23

B 64" .2 320 23

C 64" .2 320 23 + ADDITIONAL BUILDING OCCUPANTS (OCCUPANCY COUNT REMAINS UNCHANGED IN NEW WORK)

D 64" .2 320 21

MARK WIDTH OF OPENING

FACTOR ALLOWABLE # OF OCCUPANTS SERVED

ACTUAL # OF OCCUPANTS SERVED

OPERABLE GATE - BY

OTHERS

NMSU PROJECT # 3568

STAGING & STORAGE

WORK AREA

STEWART ST.

BR

ELA

ND

DR

.

PROPOSED LOCATION FOR STAGING AND STORING. COORDINATE WITH NMSU

BRELAND HALL

Mark

Date

Description

Page 2: OWNER: NMSU PROJECT # 3568 CONSULTANTS: DEAN'S ......D101 DEMOLITION PLAN DEMOLITION G001 1/8" = 1'-0" A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT

DEAN'S OFFICE

164

OFFICE

163A

SECRETARIAL

163M

ASSOC. DEAN

163I

ASSIST. DEAN

163HOFFICE

163F

OFFICE

163E

OFFICE

163D

OFFICE

163C

OFFICE

163B

CONFERENCE ROOM

163L

OFFICE

163K

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

3

3

3

33

3

3

3

3

33

3

3

33

3

3

33

3

4

4

4444

4

4

4

4

4

44

NO WORK THIS AREA

NO WORK THIS AREA

3

3

4

4

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

ALTERNATE #1:RENOVATIONS TO ROOM 163G. REFER TO ALTERNATE SCHEDULE

OFFICE

163G

5

5

5

5

5

5 5

6

7

7

7

OFFICE

138

OFFICE

136

12

13

14

TYP

5

156"

16

5 5

5

3

3

3

3

20

NO WORK THIS AREA

NO WORK THIS AREA

1

TYP

1

TYP

2

2

2

2

2

2

2

2

2

2

2

22

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

ALTERNATE #1:RENOVATIONS TO ROOM 163G. REFER TO ALTERNATE SCHEDULE

11

8

8

OFFICE

138

OFFICE

136

OFFICE

163B

OFFICE

163C

OFFICE

163D

OFFICE

163E

OFFICE

163K

OFFICE

163F

OFFICE

163G ASSIST. DEAN

163H

ASSOC. DEAN

163I

SECRETARIAL

163M

OFFICE

163A

DEAN'S OFFICE

164

HALL

100

WORK ROOM

163

CONFERENCE ROOM

163L

1

TYP

1

2

TYP

9

9

9

1 TYP

1

TYP

1

TYP

10

101

TYP

1

TYP

1

TYP

11

11

11

11

11

11

11 11

1111

11

1111

11

9

9

17

17

17

18

19

19

A. DIMENSIONS ARE NOMINAL FROM FACE OF EXISTING.B. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS

AND SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES.C. CONTRACTOR SHALL PROVIDE TEMPORARY BARRIERS DURING CONSTRUCTION

TO PROVIDE DUST AND DEBRIS CONTROL. CONTRACTOR TO COORDINATE BARRIER LOCATIONS WITH OWNER/ARCHITECT.

D. CONTRACTOR SHALL PROTECT ALL EXISTING TO REMAIN ITEMS WITHIN THE WORK AREA TO PREVENT DAMAGE. THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE DONE TO EXISTING CONDITIONS TO REMAIN.

E. CONTRACTOR SHALL COORDINATE SITE ACCESS AND STAGING AREA WITH OWNER/ARCHITECT.

F. THE CONTRACTOR SHALL REPAIR AND REPLACE ANY ITEM OR SURFACE DAMAGED BY THE WORK, OR AS REQUIRED BY NEW INSTALLATION.

G. ALL DEMOLISHED MATERIALS TO BE REMOVED FROM SITE. U.N.O.H. CONTRACTOR SHALL KEEP ALL EXISTING EXIT WAYS CLEAR AND OPEN DURING

CONSTRUCTION.I. HAZRDOUS MATERIALS - IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS

WILL BE ENCOUNTERED DURING THE WORK. UPON DISCOVERY OF HAZARDOUS MATERIALS, CONTRACTOR SHALL STOP WORK AND INFORM THE OWNER/ARCHITECT

J. REMOVE ALL EXPOSED CONDUIT AND WIRE-MOLD THAT IS NOT TO BE RE-USED.REMOVE ALL POWER AND LOW VOLTAGE WIRES THAT ARE NOT RE-USED BACK TO THE NEAREST JUNCTION BOX.

N

RE

G

I ST ERED A RCH

I T

EC

T

ST

AT

E

OF NEWMEX

ICORICHARD HAAS

NO. 2530

This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.

DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022

SHEET NO.

SHEET TITLE

ISS

UE

:

D

C

B

A

1 3 4 52

WORK AREA

PROJECT NO.206-101

D101

DEMOLITION PLAN

10/0

7/2

019

DE

AN

'S S

UIT

E R

EN

OV

AT

ION

S

NM

SU

, B

RE

LA

ND

HA

LL

15

25

ST

EW

AR

T S

T.

LA

S C

RU

CE

S, N

M 8

80

03

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

10/07/2019

PROJECT NORTH

KEYNOTE LEGEND1 CAREFULLY REMOVE AND DISPOSE OF EXISTING LIGHT FIXTURES. LIGHT FIXTURES TO BE REPLACED WITH

NEW, LED LIGHT FIXTURES IN NEW WORK.

2 CAREFULLY REMOVE EXISTING CEILING TILES AND CEILING MOUNTED EQUIPMENT. CEILING GRID TO

REMAIN. CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE DONE TO THE EXISTING CEILING

GRID DURING CONSTRUCTION

3 REMOVE AND DISPOSE OF EXISTING COVE BASE. PATCH / REPAIR WALL AS REQUIRED FOR NEW FINISHES

4 REMOVE AND DISPOSE OF EXISTING BROADLOOM CARPET IN THIS AREA. PREP FLOORS FOR NEW CARPET

TILE

5 CAREFULLY REMOVE EXISTING DOOR AND DOOR HARDWARE FROM FRAME. KEEP IN CLEAN, SAFE AREA FOR

RE-USE. DOORS TO BE RE-FINISHED IN NEW WORK.

6 EXISTING DOOR TO REMAIN. NO WORK.

7 ALTERNATE #2 - CAREFULLY REMOVE EXISTING DOOR AND DOOR HARDWARE FROM FRAME FOR CLOSET

DOORS SHOWN. KEEP IN CLEAN, SAFE AREA FOR RE-USE. DOORS TO BE RE-STAINED IN NEW WORK.

8 EXISTING 12" x 12" ADHERED ACOUSTIC TILE CEILING TO REMAIN. PATCH/REPAIR AS REQUIRED - PAINT IN

NEW WORK. COLOR AS SELECTED BY NMSU ARCHITECT.

9 EXISTING LED LIGHT FIXTURES. REMOVE AND STORE IN CLEAN, SAFE AREA. LIGHT FIXTURES TO BE

RELOCATED IN NEW WORK.

10 EXISTING 2' X 2' LED LIGHT FIXTURE TO REMAIN. REMOVE AND REPLACE AS REQUIRED FOR NEW WORK.

11 CAREFULLY REMOVE AND DISPOSE OF EXISTING SUPPLY AND RETURN DIFFUSERS. DIFFUSERS TO BE

REPLACED IN NEW WORK.

12 REMOVE EXISTING UPPER CABINETS AS SHOWN. PATCH / REPAIR WALL AS REQUIRED FOR NEW FINISHES

13 REMOVE UPPER CABINETS, BASE CABINETS AND COUNTERTOP IN THIS AREA. PATCH / REPAIR WALL AS

REQUIRED FOR NEW FINISHES

14 REMOVE EXISTING ROOM SIGNAGE THROUGHOUT THE SUITE - PATCH/REPAIR WALL AS REQUIRED FOR NEW

FINISHES

15 CAREFULLY REMOVE EXISTING DOOR AND DOOR HARDWARE. KEEP IN CLEAN, SAFE AREA FOR RE-USE.

DOORS TO BE RE-FINISHED AND RE-LOCATED IN NEW WORK. REMOVE DOOR FRAME - PREP OPENING FOR

INFILL

16 DEMOLISH AND REMOVE PORTION OF EXISTING WALL AS REQUIRED FOR NEW 3'-0" X 7'-0" DOOR IN NEW

WORK.

17 DEMOLISH AND REMOVE 4X4 FLUORESCENT LIGHT FIXTURE. PREP FOR NEW LED LIGHT FIXTURE

18 REMOVE EXISTING EXIT SIGN. REPLACE IN NEW WORK

19 REMOVE EXISTING EMERGENCY LIGHTINING. REPLACE IN NEW WORK.

20 REMOVE EXISTING CARPET IN ENTRY HALL. PREP FLOOR FOR NEW CARPET.

1/8" = 1'-0"D101A3 DEMOLITION FLOOR PLAN

1/8" = 1'-0"D101A1 DEMOLITION CEILING PLAN

PROJECT NORTH

GENERAL NOTES

Mark

Date

Description

Page 3: OWNER: NMSU PROJECT # 3568 CONSULTANTS: DEAN'S ......D101 DEMOLITION PLAN DEMOLITION G001 1/8" = 1'-0" A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT

DEAN'S OFFICE

164

OFFICE

163A

SECRETARIAL

163M

ASSOC. DEAN

163I

ASSIST. DEAN

163H

OFFICE

163F

OFFICE

163E

OFFICE

163D

OFFICE

163C

OFFICE

163B

CONFERENCE ROOM

163L

OFFICE

163K

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

ALTERNATE #1:RENOVATIONS TO ROOM 163G. REFER TO ALTERNATE SCHEDULE

OFFICE

136

OFFICE

138

WORK ROOM

163

NO WORK THIS AREA

OFFICE

163G

HALL

100

NO WORK THIS AREA

11

11

11

11

11

11

11

11

11

11

11

11 11

1111

12

12

12

12

12

12

12

13

13

13

11

12

14

15

15

15

16

16

15

15

14

14

14 14

17

14 14

14

17

17

11

12

12 12

12 12

12

12

12 12

17

18

15

19

20

20

20

20

20

20

20

20

20

20 20

2020

20

20

20

20

19

19

22

TYP

1

6"

163A

24

15

17 17

25

25

19

163M

26

27

TYP

28

29

30

3132

11

12

A. REFER TO REFLECTED CEILING PLAN SHEETS FOR CEILING-MOUNTED FIXTURES AND EQUIPMENT. COORDINATE WITH ELECTRICAL.

B. ALL DIMENSIONS ARE TO FACE OF EXISTING WALL UNLESS OTHERWISE NOTED.C. ALL EXISTING CRIMSON ACCENT WALLS WITHIN THE WORK AREA ARE TO BE TOUCHED-UP IN NEW WORK. D. ALL EXISTING CEILING MOUNTED EQUIPMENT REMOVED DURING DEMOLITION IS TO BE RE-INSTALLED IN-PLACE DURING NEW

WORK.E. CONTRACTOR TO FIELD VERIFY THAT ALL EXISTING HM FRAMES HAVE MATCHING PAINT COLOR. CONTRACTOR TO PAINT

UNMATCHING PORTIONS OF HM FRAMES TO MATCH FRAME COLOR THROUGHOUT SUITE.F. CONTRACTOR TO COORDINATE ALL PAINT COLORS, ACCENT COLORS AND ACCENT LOCATIONS WITH NMSU PRIOR TO

COMMENCING THE WORK.

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

ALTERNATE #1:RENOVATIONS TO ROOM 163G. REFER TO ALTERNATE SCHEDULE

OFFICE

136

OFFICE

138

3' -

9"

6' -

0"

3' -

10

"

EQ EQ EQ EQ

4' -

10

"8

' -

0"

4' -

9"

1

1

1

2

3

2

4

TYP

4

OFFICE

163B

OFFICE

163C

5

5

A

B

6

7

8

B

A

6

B

B A

TYPB

A

B A

OFFICE

163D

OFFICE

163E

9

B

A

BA

OFFICE

163F

OFFICE

163G

A

B

7

7

7

7

7

7

7

7

77

8

8

8

8

8

6

6

8

ASSIST. DEAN

163H

10

TYP

B A

B

A

A B

A

ASSOC. DEAN

163I

TYP

10

TYP

B

A

B

A

B

10

TYP

B

B

A

AA

AA

A

B

SECRETARIAL

163M

8

88

A

B

B

DEAN'S OFFICE

164

A

A

A

B

10

TYP

A

CONFERENCE ROOM

163L

WORK ROOM

163

HALL

100

HALL

102

21

21

21

6

9

6

TYP

6

TYP

6

B

6

23

23

6

4

4

4

7

8

8

OFFICE

163A

TYP

TYP

ACOUSTICAL TILE CEILING - 24" x 48"NEW CEILING TILES -

EXISTING CEILING GRID TO REMAIN -PAINT

EXISTING CEILING TO REMAIN - NO WORK

EXISTING ADHERED ACOUSTICAL TILE CEILING - 12" X 12"-PAINT

HVAC RETURN AIR GRILLE - REF MECHANICAL SHEETS.

HVAC SUPPLY AIR DIFFUSER- REFFER TO SCHEDULE

EXIT LIGHTING - REF ELECTRICAL SHEETS.

2x2 LIGHT FIXTURE - REF ELECTRICAL SHEETS.

2x4 LIGHT FIXTURE - REF ELECTRICAL SHEETS.

RCP LEGENDA. Additive Alternate #1 – Renovations to room 163 G to include:

a. Removal and replacement of existing carpetb. Removal and replacement of existing light fixtures and new LED

fixtures to match the new light fixtures in the suite’s conference room

c. Removal and replacement of the existing HVAC grilles and diffusers to match the new diffusers in the suite’s conference room

d. Removal and replacement of the acoustical ceiling tiles to match the new ceiling tiles in the suite’s conference room. Existing ceiling grid to remain and to receive new paint. Modify ceiling grid as required for new lighting layout.

e. Preparation of existing substrates for new paint throughout U.N.O. New paint to be provided throughout the suite U.N.O.

B. Additive Alternate #2 – Re-finishing of existing closet doorsa. Removal of existing closet doors and door hardware as indicated

on the drawings.b. Strip existing finish coat and stain. Sand surface with fine grit

sandpaper. Re-stain and finish (clear coat) to match door on conference room 163L or as selected by NMSU Architect

ALTERNATE SCHEDULE

N

RE

G

I ST ERED A RCH

I T

EC

T

ST

AT

E

OF NEWMEX

ICORICHARD HAAS

NO. 2530

This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.

DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022

SHEET NO.

SHEET TITLE

ISS

UE

:

D

C

B

A

1 3 4 52

WORK AREA

PROJECT NO.206-101

A101

FIRST FLOOR PLAN &

REFLECTED CEILING

PLAN

10/0

7/2

019

DE

AN

'S S

UIT

E R

EN

OV

AT

ION

S

NM

SU

, B

RE

LA

ND

HA

LL

15

25

ST

EW

AR

T S

T.

LA

S C

RU

CE

S, N

M 8

80

03

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

10/07/2019

1/8" = 1'-0"A101A2 FIRST FLOOR PLAN

GENERAL NOTES KEYNOTE LEGEND1 SURFACE MOUNTED LIGHT FIXTURE - REFER TO ELECTRICAL

2 EXISTING 12" x 12" ADHERED ACOUSTIC TILE CEILING TO REMAIN. PATCH/REPAIR AS REQUIRED - PAINT IN NEW WORK. COLOR AS

SELECTED BY NMSU ARCHITECT.

3 NEW EXIT SIGN - REFER TO ELECTRICAL

4 NEW EXIT LIGHT - REFER TO ELECTRICAL

5 EXISTING 2' X 2' LED LIGHT FIXTURE TO REMAIN. REMOVE AND REPLACE AS REQUIRED FOR NEW WORK.

6 LIGHT FIXTURE; PROVIDE/REMOVE SEGMENTS OF CEILING GRID TEE AS REQUIRED FOR NEW LIGHTING LAYOUT; PAINT NEW SEGMENTS

TO MATCH EXISTING - REFER TO ELECTRICAL

7 EXISTING CEILING GRID TO REMAIN. PAINT. COLOR AS SELECTED BY NMSU ARCHITECT

8 NEW ACOUSTIC CEILING TILES TO MATCH CEILING TILES IN CONFERENCE ROOM 163L. EXISTING CEILING GRID TO REMAIN

9 RE-LOCATED EXISTING LED LIGHT FIXTURE; CONTRACTOR TO VERIFY COLOR TEMPERATURES OF RE-LOCATED LIGHT FIXTURES ARE THE

SAME AS NEW LED LIGHT FIXTURES; REPLACE EXISTING FIXTURES THAT VARY IN COLOR TEMPERATURE WITH NEW LED LIGHT FIXTURE.

10 LIGHT FIXTURE - REFER TO ELECTRICAL

11 NEW CARPET TILE IN THIS AREA - COLOR AS SELECTED BY NMSU ARCHITECT

12 NEW RUBBER BASE IN THIS AREA - COLOR AS SELECTED BY NMSU ARCHITECT

13 ALTERNATE #2 -STRIP FINISH COAT AND STAIN OFF EXISTING CLOSET DOOR. SAND SURFACE WITH FINE GRIT SANDPAPER. RE-STAIN TO

MATCH DOOR ON CONFERENCE ROOM 163L OR AS SELECTED BY NMSU ARCHITECT

14 STRIP FINISH COAT AND STAIN OFF EXISTING DOOR. SAND SURFACE WITH FINE GRIT SANDPAPER. RE-STAIN TO MATCH DOOR ON

CONFERENCE ROOM 163L OR AS SELECTED BY NMSU ARCHITECT. RE-INSTALL EXISTING DOOR AND DOOR HARDWARE

15 EXISTING CRIMSON ACCENT WALL TO REMAIN. TOUCH-UP PAINT IN NEW WORK.

16 RE-PAINT EXISTING DOOR. COLOR AS SELECTED BY NMSU ARCHITECT

17 EXISTING DOOR TO REMAIN. NO WORK.

18 PAINT WOOD PANELING ABOVE EXISTING DOOR - COLOR AS SELECTED BY NMSU ARCHITECT

19 PROVIDE ROLLER SHADES FOR ALL EAST FACING WINDOWS. FIELD VERIFY WINDOW SIZES.

20 NEW PAINT ON ALL WALLS U.N.O. - COLOR AS SELECTED BY NMSU ARCHITECT - EXISTING CRIMSON ACCENT COLORS TO REMAIN

21 NEW 4' X 4' LED LIGHT FIXTURE. REFER TO ELECTRICAL

22 REPLACE EXISTING ROOM IDENTIFICATION SIGNAGE WITH NEW SIGNAGE PER NMSU STANDARD. PROVIDE BRAILLE @ 60" A.F.F. AND

INTERNATIONAL SYMBOL OF ACCESSIBILITY WHERE REQUIRED

23 NEW EMERGENCY LIGHTING. REFER TO ELECTRICAL

24 INFILL EXISTING OPENING. REFER TO WALL PARTITION TYPES

25 PAINT PORTIONS OF UN-MATCHING EXISTING HOLLOW METAL FRAMES TO MATCH HOLLOW METAL FRAMES THROUGHOUT THE SUITE

26 CRIMSON PAINT ACCENT WALL - COLOR TO BE APPROVED BY NMSU ARCHITECT.

27 DASHED LINES INDICATE FURNITURE (BY OTHERS, N.I.C.)

28 GATE (BY OTHERS). CONTRACTOR TO PROVIDE AND INSTALL GATE HARDWARE. REFER TO SCHEDULE AND SPECIFICATIONS.

29 LOCATION OF EXISTING ADT FOCUS 200P ALARM PANEL. ELECTRIC STRIKE TO BE CONNECTED TO ALARM SYSTEM. REFER TO ELECTRICAL.

30 CONTRACTOR TO PROVIDE AND INSTALL RACEWAYS AND LOW VOLTAGE WIRING THROUGH FURNITURE (FURNITURE BY OTHERS) FOR

ELECTRIC STRIKE. RACEWAYS ARE TO BE INSTALLED ON CLIPS PROVIDED BY FURNITURE MANUFACTURER TO AVOID VOIDING THE

FURNITURE WARRANTY.

31 HOLD-UP BUTTON TO BE MOUNTED ON SIDE OF FURNITURE (HOLD-UP BUTTON AND INSTALLATION BY OTHERS; FURNITURE BY OTHERS)

32 PUSH RELEASE BUTTON FOR GATE ELECTRIC STRIKE TO BE MOUNTED ON UNDERSIDE OF FURNITURE (PUSH RELEASE BUTTON AND

INSTALLATION BY OTHERS; FURNITURE BY OTHERS).

PROJECT NORTH 1/8" = 1'-0"A101

C1 FIRST FLOOR REFLECTED CEILING PLANPROJECT NORTH

DIFFUSER AND GRILLE SCHEDULEType Mark Manufacturer Model Description

A TITUS OMNI SUPPLY DIFFUSER; STANDARD FINISH - #26 WHITE; STEEL CONSTRUCTION; 24" X 24" FACE; LAY-IN; CONTRACTOR TO

FIELD VERIFY REQUIRED NECK SIZE

B TITUS 50F RETURN GRILLE; STANDARD FINISH - #26 WHITE; STEEL CONSTRUCTION; 12" X 24" FACE; 1/2" BLADE SPACING; LAY-IN

ROOM FINISH SCHEDULEROOM ID FLOOR WALLS CEILING

COMMENTSROOM NO ROOM NAME FLOOR BASE NORTH SOUTH EAST WEST MATL

100 HALL CPT RB N/A N/A N/A N/A N/A REPLACE EXISTING CARPET TILE AND BASE BOARDS IN AREA SHOWN.

101 ENTRY HALL CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

102 WAITING AREA CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

102 HALL CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

136 OFFICE CPT RB P P P P ECP EXISTING ADHERED ACOUSTIC CEILING TO REMAIN - PAINT

138 OFFICE CPT RB P P P P ECP EXISTING ADHERED ACOUSTIC CEILING TO REMAIN - PAINT

163A OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163B OFFICE CPT RB P P P EP ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163C OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163D OFFICE CPT RB P P P EP ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163E OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163F OFFICE CPT RB P P P EP ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163G OFFICE CPT RB P P P EP ATC BASE BID: NO WORK THIS AREA. ALTERNATE #1: RENOVATIONS TO ROOM 163G AS INDICATED IN SCHEDULE

163H ASSIST. DEAN CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163I ASSOC. DEAN CPT RB P P EP P ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163K OFFICE CPT RB P P EP P ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163M SECRETARIAL CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

164 DEAN'S OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

Mark

Date

Description

Page 4: OWNER: NMSU PROJECT # 3568 CONSULTANTS: DEAN'S ......D101 DEMOLITION PLAN DEMOLITION G001 1/8" = 1'-0" A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT

A

7'-0

"

3'-0"

1

2"

7'-2

"

2"

3'-4"

FIRST FLOOR0' - 0"

FINISHED FLOOR

CEILING LINE

EXISTING DECK

EACH SIDE

3 5/8" METAL STUD W/ STANDARD GYP - EACH SIDE

TAPE AND TEXTURE TO MATCH EXISTING - PAINT

RESILIENT BASE

GYPSUM BOARD 5/8",STANDARD - TAPE ANDTEXTURE (SANTE FE TEXTURE,TYP) - PAINT

GYPSUM BOARD 5/8",STANDARD - TAPE ANDTEXTURE (SANTE FE TEXTURE,TYP) - PAINT

1

6"

GAP WITH CLIPS ALLOWING

MOVEMENT

3-5/8" METAL STUDS, 16" OCMINIMUM

RE

G

I ST ERED A RCH

I T

EC

T

ST

AT

E

OF NEWMEX

ICORICHARD HAAS

NO. 2530

This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.

DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022

SHEET NO.

SHEET TITLE

ISS

UE

:

D

C

B

A

1 3 4 52

PROJECT NO.206-101

A602

WALL PARTITION

TYPES AND

SCHEDULES

10/0

7/2

019

DE

AN

'S S

UIT

E R

EN

OV

AT

ION

S

NM

SU

, B

RE

LA

ND

HA

LL

15

25

ST

EW

AR

T S

T.

LA

S C

RU

CE

S, N

M 8

80

03

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

10/07/2019

FIRST FLOOR DOOR AND FRAME SCHEDULEDOOR FRAME MISC

MARK WIDTH HT THK ELEV MATL ELEV MATLHDWSET COMMENTS

163A 3' - 0" 7' - 0" 1 3/4" A SC WD 1 HM 1 RE-FINISH AND RE-LOCATE EXISTING DOOR. NEW FRAME AND NEW HARDWARE

163M 3' - 0" 3' - 6" N/A TBD N/A N/A 2 GATE N.I.C. - GATE HARDWARE PROVIDED AND INSTALLED BY CONTRACTOR.LOW-VOLTAGE WIRING BY OTHERS. CONTRACTOR TO COORDINATE THE WORK WITHOWNER

1/4" = 1'-0"1

DOOR TYPES 1/4" = 1'-0"

2HM FRAME TYPES

ABBREVIATION LEGEND

HM: HOLLOW METALSC WD: SOLID CORE WOOD DOOR (EXISTING)CPT: CARPET TILERB: RUBBER BASEP: PAINTEP: EXISTING CRIMSON ACCENT COLOR TO REMAIN. TOUCH UP PAINTATC: ACOUSTICAL TILE CEILINGECP: EXISTING ADHERED ACOUSTIC CEILING - PAINT

ROOM FINISH SCHEDULEROOM ID FLOOR WALLS CEILING

COMMENTSROOM NO ROOM NAME FLOOR BASE NORTH SOUTH EAST WEST MATL

100 HALL CPT RB N/A N/A N/A N/A N/A REPLACE EXISTING CARPET TILE AND BASE BOARDS IN AREA SHOWN.

101 ENTRY HALL CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

102 WAITING AREA CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

102 HALL CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

136 OFFICE CPT RB P P P P ECP EXISTING ADHERED ACOUSTIC CEILING TO REMAIN - PAINT

138 OFFICE CPT RB P P P P ECP EXISTING ADHERED ACOUSTIC CEILING TO REMAIN - PAINT

163A OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163B OFFICE CPT RB P P P EP ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163C OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163D OFFICE CPT RB P P P EP ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163E OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163F OFFICE CPT RB P P P EP ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163G OFFICE CPT RB P P P EP ATC BASE BID: NO WORK THIS AREA. ALTERNATE #1: RENOVATIONS TO ROOM 163G AS INDICATED IN SCHEDULE

163H ASSIST. DEAN CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

163I ASSOC. DEAN CPT RB P P EP P ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163K OFFICE CPT RB P P EP P ATC EXISTING CEILING GRID TO REMAIN - PAINT ; EXISTING CRIMSON ACCENT COLOR TO REMAIN

163M SECRETARIAL CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

164 DEAN'S OFFICE CPT RB P P P P ATC EXISTING CEILING GRID TO REMAIN - PAINT

1/2" = 1'-0"A602A5 WALL PARTITION TYPES

Mark

Date

Description

Page 5: OWNER: NMSU PROJECT # 3568 CONSULTANTS: DEAN'S ......D101 DEMOLITION PLAN DEMOLITION G001 1/8" = 1'-0" A1 FIRST FLOOR PLAN - OCCUPANCY/LIFE SAFETY DIAGRAM PROJECT NORTH LEGEND EXIT

J

J

J

J

J

J

J

J

ss

S2

ss

ssS2

ssS2

ssS2

ss

S2

s S2s

s

S2

s

s

S2s

ssS

2

ssS2

JJ

J

J

J

J

J

J

J

J

J

J

J

J

s

s

s

s

s

S2

s

ss

S2

J

J

J

s

S2

s

s

J

s

s

s

s

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

OFFICE

136

OFFICE

138

OFFICE

163B

OFFICE

163C

OFFICE

163D

OFFICE

163E

OFFICE

163F

OFFICE

163G

ASSIST. DEAN

163H

ASSOC. DEAN

163I

SECRETARIAL

163M

DEAN'S OFFICE

164

CONFERENCE ROOM

163L

WORK ROOM

163

HALL

100

HALL

102

B

BB

B

OFFICE

163K

B

B

B

B

B

B

A

A

A

A

A A

A A

A A

A1

A1

A1

A1

A

A

A1

A1

C

C

C

A2

A2

A2

A2

EMX

EMX

EM

EM

EM

OFFICE

163A

EM

EM

EM

X1

X1

X1

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

EM

Ea

c

E

E

OC1OC1

B

B B

B

C1

Eb

E

X

aa

a a

a

aa

b

b

b

b

b

b

b

c

c

c

c

c

c

c

c

c

c

c

c

E

EMX

3

X1

J

J

S2

SECRETARIAL

J

J

s

sJ

J

N

This document may not be

reproduced in whole or part by any

means, electronic or otherwise

without the explicit written

permission of Desert Peak

Architects P.C.. All reports, plans,

specifications, computer files, field

data and other documents and

instruments prepared by the

Architect as instruments of service

shall remain the property of the

Architect. The Architect shall retain

all common law, statutory, and

other reserved rights, including the

copyright thereto.

DESERT PEAK ARCHITECTS P.C.

1014 SOUTH MAIN STREET

LAS CRUCES

NEW MEXICO 88005

P. 575.528.0022

SHEET NO.

SHEET TITLE

IS

SU

E:

D

C

B

A

1 3 4 52

WORK AREA

PROJECT NO.

206-101

E1.0

FIRST FLOOR PLAN

LIGHTING PLAN

18-11-15

DE

AN

'S

S

UIT

E R

EN

OV

AT

IO

NS

NM

SU

, B

RE

LA

ND

H

ALL

1525 S

TE

WA

RT

S

T.

LA

S C

RU

CE

S, N

M 88003

1/8" = 1'-0"

E1.0

1 FIRST FLOOR REFLECTED CEILING PLAN

EXIT LIGHT FIXTURE, CONNECT TO UNSWITCHED HOT CONDUCTOR.

EMERGENCY LIGHTS FIXTURE, CONNECT TO UNSWITCHED HOT CONDUCTOR.

SINGLE POLE WALL SWITCH, 48" TO TOP OF BOX. UNLESS OTHERWISE NOTED.

THREE-WAY WALL SWITCH, 48" TO TOP OF BOX UNLESS OTHERWISE NOTED.

JUNCTION BOX

RECESSED FIXTURE, LETTER DENOTES TYPE

3

"X1"

"EM"

"G"

FLUORESCENT FIXTURE, LETTER DENOTES TYPE

"A"

ELECTRICAL SYMBOL LEGEND

JUNCTION BOX INSTALLED ABOVE THE CEILING WITH FLEXIBLE CONDUIT

CONNECTION TO LAY-IN FIXTURES. MAXIMUM 6'-0" LENGTH OF CONDUIT

WITH REQUIRED CONDUCTORS ALONG WITH GREEN WIRE GROUND.

ABOVE FINISHED FLOORAFF

BRANCH CIRCUIT IN WALLS OR CEILING.

SYMBOL DESCRIPTION

KEYED NOTE SYMBOL-ELECTRICAL2

COMBINATION EXIT/EMERGENCY LIGHT FIXTURE, CONNECT TO UNSWITCHED

"EMX"

HOT CONDUCTOR.

FLUORESCENT FIXTURE, UPPERCASE LETTER DENOTES FIXTURE TYPE, LOWERCASE

"A" "a"

LETTER DENOTES WHICH SWITCH IS CONTROLLING FIXTURE.

DESCRIPTION & MFR. CAT. No.TYPE LAMPS & WATTS MOUNTING

CREE CR24-40L-35K-10V

A2

A

LED 40 W RECESSED

FIXTURE SCHEDULE

CREE CR24-40L-35K-10V-SMK24

LED 40 W SURFACE MOUNTED

E2.0 LIGHTING PLAN KEYNOTE

1 EXISTING EMERGENCY LIGHT FIXTURE TO BE REPLACED BY

NEW LIGHT FIXTURE. CONNECT NEW FIXTURES TO EXISTING

WIRING.

2 CONTRACTOR TO REPLACE EXISTING SWITHCES AND INSTALL

WALL MOUNTED OCCUPANCY SENSOR DUAL TECHNOLOGY

WATTSTOPPER DSW-311, OR EQUAL. SENSOR TO BE SET FOR

AUTO-ON/AUTO-OFF FUNCTION. AUTO-ON FUNCTION TO BE

SET TO TURN ON ONLY 50% OF TOTAL LIGHTING LEVEL OF

EACH LIGHT FIXTURE. AUTO-OFF FUNCTION TO BE SET TO

TURN OFF LIGHTS AFTER 15 MIN. OF NO MOTION SENSING.

REFER TO DETAIL 1/E2.0 ON THIS SHEET.

3 EXISTING LIGHT FIXTURE TO BE RELOCATED AS SHOWN FROM

OFFICES 163F AND 163G. CONTRACTOR TO RELOCATE ONLY

THE FOUR (4) FIXTURES THAT ARE RATED AT 3500K. THE

OTHER FIXTURES IN ROOM 163F TO BE RETURNED TO OWNER.

4 EXISTING SWITCH TO REMAIN. CONTROL THE NEW THREE

LIGHT FIXTURES IN HALLWAY AS SHOWN. CONNECT TO

EXISTING CIRCUIT CURRENTLY SERVING CORRIDOR.

5 PROVIDE AND INSTALL CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR WATTSTOPPER DT-335 OR EQUAL.

SENSOR TO BE SET FOR AUTO-ON/AUTO-OFF AND TO BE

PROGRAMMED TO TURN OFF LIGHTS AFTER 15 MIN. OF NO

MOTION SENSING. MAKE CONNECTIONS BETWEEN CEILING

MOUNT SENSORS AND SWITCHES AS NECESSARY. REFER TO

DETAIL 2/E2.0 ON THIS SHEET.

6 CONNECT ALL EMERGENCY LIGHT FIXTURES TO NEW

UNSWITCHED HOT CONDUCTOR SERVING THIS AREA.

7 CONTRACTOR TO PROVIDE AND INSTALL NEW WALL MOUNTED

OCCUPANCY SENSOR DUAL TECHNOLOGY WATTSTOPPER

DSW-311, OR EQUAL. SENSOR TO BE SET FOR

AUTO-ON/AUTO-OFF FUNCTION. AUTO-ON FUNCTION TO BE

SET TO TURN ON ONLY 50% OF EACH LIGHT FIXTURE.

AUTO-OFF FUNCTION TO BE SET TO TURN OFF LIGHTS AFTER

15 MIN. OF NO MOTION SENSING. REFER TO DETAIL 1/E2.0 ON

THIS SHEET.

8 EXISTING SWITCH TO BE REMOVED. CONTRACTOR TO

PROVIDE A STEEL BLANK COVER AND RE-SWITCH NEW

FIXTURES AS SHOWN.

9 CONTRACTOR TO RE-WIRE NEW LIGHT FIXTURES TO EXISTING

CIRCUIT MAINTAINED DURING DEMOLITION.

10 EXISTING LIGHT SWITCH TO BE REMOVED. CONTRACTOR TO

RE-WIRE LIGHT TO NEW SWITCH AS SHOWN AND PROVIDE

BLANK COVER.

11 EXISTING LIGHT SWITCHES TO REMAIN IN SAME BOX AREA AS

SHOWN, BUT REWIRED AS SHOWN IN DETAILS 2/E2.0.

6

1

1

EMDUAL LITE EV4D-02WAL

INCLUDED WALL/CEILING

sOCCUPANCY SENSOR DW-311DIMMER SWITCH WIRING DIAGRAM

1

E1.0

NTS

S2

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

GENERAL NOTES:

L.

VIOLET

RED

LINE

GROUND

GREEN

GREY

BLACK

DRIVER

OR BALLAST

WHITE

NEUTRAL

YELLOW

(SINGLE-WAY WIRING)

ELECTRICAL INSTALLATION MUST FOLLOW ALL NATIONAL AND

LOCAL ELECTRICAL CODES. INSTALLATION MUST CONFORM TO

THE LOCAL POWER COMPANY'S SPECIFICATIONS.

ALL MATERIALS SHALL BE IN ACCORDANCE WITH THE NATIONAL

ELECTRICAL MANUFACTURERS ASSOCIATION AND SHALL BE

LISTED BY THE U.L.

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL PERMIT AND

INSPECTION FEES REQUIRED BY THE GOVERNING BODIES.

ELECTRICAL CONTRACTOR MUST COMPLY WITH THE LATEST

A.D.A. REQUIREMENTS.

MINIMUM SIZE CONDUCTORS SHALL BE #12 THW CU. UNLESS

NOTED OR SIZED BY CODE.

ALL WIRING MUST BE IN CONDUIT, INCLUDING ALL L.V. WIRING.

THIN WALL CONDUIT (EMT) CAN BE INSTALLED CONCEALED

ABOVE CEILING, IN FURRED WALLS, AND WALLS EXCEPT WHERE

THOSE WALLS ARE GROUTED SOLID. USE FLEX CONDUIT FOR

MOTORS AND LIGHTING FIXTURES. USE WATER TIGHT FLEX

CONDUIT FOR WATER HEATERS DISPOSALS, EXTERIOR

CONNECTIONS, ETC. BOND ACCORDING TO CODE.

VERIFY LOCATIONS OF ALL ELECTRICAL EQUIPMENT WITH OTHER

TRADES TO AVOID CONFLICTS AND INTERFERENCES.

CONTRACTOR MUST VISIT SITE TO BECOME FAMILIAR WITH

EXISTING CONDITIONS BEFORE BIDDING ON THIS PROJECT.

ELECTRICAL DEVICE INSTALLATION SHALL COMPLY WITH

ACCESSIBILITY CODES ADOPTED FOR NEW MEXICO.

FEEDER, BRANCH CIRCUIT DESIGN, AND INSTALLATION SHALL

COMPLY WITH THE 2019 NEW MEXICO ELECTRICAL CODE

14.10.4.10 (B) (6) AND (C) (2) FOR VOLTAGE DROP.

ABANDONED POWER WIRING WILL BE REMOVED BACK TO THE

SOURCE. THE ACCESSIBLE PORTIONS OF CONDUIT/TUBING AND

EQUIPMENT SHALL BE REMOVED. THE ACCESSIBLE PORTIONS OF

ABANDONED CABLES (VOICE, DATA, VIDEO, ALARM, ETC.) SHALL

BE REMOVED.

ALL ELECTRICAL EQUIPMENT IN FIRE RATED WALLS MUST BE

INSTALLED SO THAT FIRE RATING IS NOT COMPROMISED.

2

2

22

2

2

2

2

7

2

1

2

BCREE CR22-32L-35K-10V

LED 32 W RECESSED

A1CREE CR24-50L-35K-10V

LED 50 W RECESSED

3

3

3

3

*SENSOR TO BE SET TO TURN ON AT 50% OF TOTAL LIGHT LEVEL. THE OTHER SWITCH TO

CONTROL OTHER 50%. SENSOR TO BE SET SO THE LIGHTS TURN OFF AFTER 15 MIN. OF

NO MOTION SENSING.

4

8

4

5 5

CEILING MOUNTEDSENSOR WIRING DIAGRAM #1

OC12

E1.0

NTS

LIGHTING

LOAD

TYPICAL

FIXTURE

LIGHTING

SWITCH

NEUTRAL

HOT

LOAD

GROUND

WATTSTOPPER

DT-335

2

2

6

s

LIGHTING CONTROLS LEGEND

DW-311 OR EQUAL WATTSTOPPER DIMMING WALL SWITCH DUAL TECHNOLOGY, SELF POWERED, 48" TO TOP OF

BOX

DT-355 OR EQUAL WATTSTOPPER CEILING MOUNTED DUAL-TECHNOLOGY, 1000 SQ FT, LINE

VOLTAGE

S2

OC1

NOTES:

1. All sensor locations are approximate, refer to manufacturers installation instructions prior to installation.

2. Ultrasonic ceiling mount sensors should be located a minimum of six feet from HVAC supply/return vents.

3. Contractor is responsible for: proper sensitivity & time delay settings (for non-adaptive products), recommended placement, and field verification of circuits

with in respect to power placement.

4. Sensors mounted over the door must be placed one foot inside the threshold.

5. Contractor is responsible for ensuring that the sensor bill of materials complies with the sensor design and layout specifications.

6. Contractor is responsible for installing equipment in compliance with local code.

7. All sensors to be set to turn off lighting after 15 minutes of no motion sensing.

8. Wall mounted occupancy sensors must not be installed behind doors.

9. Contractor may connect low voltage system in daisy chain to minimize LV cable runs.

MODELDEVICEDESCRIPTION

9

9

4

10

9

9

Mark

Date

Description

NOTES: (1) CONTRACTOR TO VERIFY THE VOLTAGE OF THE EXISTING LIGHTING CIRCUITS (120V OR 277V)

BEFORE ORDERING ANY LIGHT FIXTURES

CFINELITE HTP RSE 4X4 S 835 96 277 SC FC 10 FA50 C1 96

LED 55 W RECESSED

C1FINELITE HTP RSE 2X2 S 835 96 277 SC FC 10 FA50 C1 96

LED 27 W RECESSED

11

9

6

4

9

6

6

6

6

6

6

6

6

2

6

EMXEXITRONIX CLED-U1-WH

INCLUDED WALL/CEILING

X1EXITRONIX 902E U WB RC BA

INCLUDED WALL/CEILING

6

13

12

12 PROVIDE AND INSTALL J-BOX ON WALL AT 18" A.F.F. WITH A 3/4"

CONDUIT WITH PULLSTRING AND BUSHINGS TO J-BOX FOR

SECURITY DOOR MAGNETIC LOCK. J-BOX TO HAVE A BLANK

COVER WITH A 1/2" SUPPLY HOLE ON COVER. REFER TO DETAILS

3/E1.0 AND 4/E1.0 ON THIS SHEET. VERIFY EXACT LOCATION AND

INTERCONNECTION REQUIREMENTS WITH OWNERS SECURITY

CONSULTANT BEFORE DOING ANY WORK.

13 PROVIDE AND INSTALL J-BOX ON LATCH SIDE OF DOOR FOR

FUTURE MAGNETIC LOCK. INSTALL A 3/4" CONDUIT WITH

PULLSTRING AND BUSHING TO J-BOX ON WALL FOR DOOR

CONTROL ACCESS, CONDUIT TO BE RUN BEHIND DESK. SEE

DETAIL 4/E1.0 AND 3/E1.0 ON THIS SHEET. VERIFY EXACT

LOCATION AND INTERCONNECTION REQUIREMENTS WITH

OWNERS SECURITY CONSULTANT BEFORE DOING ANY WORK.

13

12

MAGNETIC GATE DETAIL3

E1.0

NTSMAGNETIC LOCK CONDUT DETAIL4

E1.0

NTS

13

12

AutoCAD SHX Text
FINISHED FLOOR
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
3/4" CONDUIT WITH PULLSTRING AND BUSHINGS
AutoCAD SHX Text
200W, 120V, TRANSFORMER (BY OTHERS)
AutoCAD SHX Text
DESK/FURNITURE
AutoCAD SHX Text
18"
AutoCAD SHX Text
4" SQUARE J-BOX FOR TRANSFORMER
AutoCAD SHX Text
T
AutoCAD SHX Text
DESK/FURNITURE
AutoCAD SHX Text
WALL
AutoCAD SHX Text
4" SQUARE J-BOX .
AutoCAD SHX Text
LV
AutoCAD SHX Text
CONTRACTOR MUST CONNECT TRANSFORMER TO NEAREST AVAILABLE 120V CIRCUIT FOR TRANSFORMER RELAY
AutoCAD SHX Text
4" SQUARE J-BOX FOR MAGNETIC DOOR STRIKE
AutoCAD SHX Text
1/2" CONDUIT WITH PULLSTRING AND END BUSHING FOR DOOR STRIKE LOW VOLTAGE WIRING. LOW VOLTAGE WIRING BY OTHERS.
AutoCAD SHX Text
EL PASO, TEXAS 79902
AutoCAD SHX Text
FAX. (915) 838-9909
AutoCAD SHX Text
TEL. (915) 838-9900
AutoCAD SHX Text
1818 E. RIO GRANDE
AutoCAD SHX Text
ENGINEERING CONSULTANTS
AutoCAD SHX Text
REGISTRATION # F005236