ARCHITECT OWNER 11057 EVENT DR. SALADO, TEXAS 76571 VICINITY MAP PROJECT LOCATION MRB GROUP CONTACT: TANYA REED 303 WEST CALHOUN AVE TEMPLE, TX 76501 P. 254.771.2054 [email protected] BELL COUNTY CONTACT: PHIL GOODWILL SALADO ANNEX RENOVATION 11057 EVENT DR. SALADO, TX 76571 P. 254.933.6701 [email protected] Copyright © 2021 MRB Group All Rights Reserved PROJECT 0229.20001 SEPTEMBER 1, 2021 CONTRACT DOCUMENTS FOR THE MEP MD ENGINEERING CONTACT: MICHAEL SMITH PO BOX 1931 BELTON, TX 76513 P. 469.467.0200 MSMITH@MD - ENG.COM 8834 N. Capital of Texas Hwy, Suite 147, Austin, TX 78759 Phone: 512-436-8571 303 W. Calhoun Ave. Temple, TX 76501 Phone: 254-771-2054 www.mrbgroup.com MRB Group, P.C. 100% FOR SUBMITTAL DRAWING INDEX G000 COVER SHEET G001 NOTES, SYMBOLS & ABBREVIATIONS LS101 LIFE SAFETY PLAN D101 DEMOLITION PLAN D102 SIGN DEMO C101 PROPOSED SITE PLAN A101 SCHEMATIC FLOOR PLAN A102 RCP/ROOF PLAN A103 PARTITION TYPE AND FINISHES A201 ELEVATIONS A202 ELEVATIONS A203 ROAD SIGNAGE A301 BUILDING SECTIONS A302 WALL SECTIONS A401 INTERIOR ELEVATIONS A402 ENLARGED PLANS AND ACCESSORIES A501 DETAILS A601 DOOR/WINDOW SCHEDULES S101 STRUCTURAL PLAN MP000 LEGEND AND GENERAL NOTES - MECHANICAL/PLUMBING M001 MECHANICAL SCHEDULES M002 MECHANICAL SCHEDULES M201 FLOOR PLAN - MECHANICAL M202 ROOF PLAN - MECHANICAL M401 DETAILS - MECHANICAL M501 SECTION VIEWS ED201 ELECTRICAL DEMOLITION PLAN E000 LEGEND AND GENERAL NOTES - ELECTRICAL E001 ONE LINE / SCHEDULES / PANELBOARDS E002 SCHEDULES E201 LIGHTING PLAN E301 POWER PLAN E401 POWER TO MECHANICAL PLAN E402 POWER TO MECHANICAL ROOF PLAN E501 DETAILS - ELECTRICAL P001 PLUMBING SCHEDULES P201 SANITARY / VENT PLAN P301 PRESSURE PIPE PLAN P401 DETAILS - PLUMBING FP201 FIRE PROTECTION PLAN

D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

ARCHITECTOWNER

11057 EVENT DR.SALADO, TEXAS 76571

VICINITY MAP

PROJECTLOCATION

MRB GROUPCONTACT: TANYA REED303 WEST CALHOUN AVE

TEMPLE, TX 76501P. 254.771.2054

[email protected]

BELL COUNTYCONTACT: PHIL GOODWILL

SALADO ANNEX RENOVATION

11057 EVENT DR.SALADO, TX 76571

P. [email protected]

Copyright © 2021 MRB Group All Rights Reserved

PROJECT 0229.20001SEPTEMBER 1, 2021

CONTRACT DOCUMENTSFOR THE

MEPMD ENGINEERING

CONTACT: MICHAEL SMITHPO BOX 1931

BELTON, TX 76513P. 469.467.0200

[email protected] N. Capital of Texas Hwy, Suite 147, Austin, TX 78759

Phone: 512-436-8571303 W. Calhoun Ave. Temple, TX 76501

Phone: 254-771-2054www.mrbgroup.com

MRB Group, P.C.

100% FOR SUBMITTAL

DRAWING INDEX

G000 COVER SHEET

G001 NOTES, SYMBOLS & ABBREVIATIONS

LS101 LIFE SAFETY PLAN

D101 DEMOLITION PLAN

D102 SIGN DEMO

C101 PROPOSED SITE PLAN

A101 SCHEMATIC FLOOR PLAN

A102 RCP/ROOF PLAN

A103 PARTITION TYPE AND FINISHES

A201 ELEVATIONS

A202 ELEVATIONS

A203 ROAD SIGNAGE

A301 BUILDING SECTIONS

A302 WALL SECTIONS

A401 INTERIOR ELEVATIONS

A402 ENLARGED PLANS AND ACCESSORIES

A501 DETAILS

A601 DOOR/WINDOW SCHEDULES

S101 STRUCTURAL PLAN

MP000 LEGEND AND GENERAL NOTES - MECHANICAL/PLUMBING

M001 MECHANICAL SCHEDULES

M002 MECHANICAL SCHEDULES

M201 FLOOR PLAN - MECHANICAL

M202 ROOF PLAN - MECHANICAL

M401 DETAILS - MECHANICAL

M501 SECTION VIEWS

ED201 ELECTRICAL DEMOLITION PLAN

E000 LEGEND AND GENERAL NOTES - ELECTRICAL

E001 ONE LINE / SCHEDULES / PANELBOARDS

E002 SCHEDULES

E201 LIGHTING PLAN

E301 POWER PLAN

E401 POWER TO MECHANICAL PLAN

E402 POWER TO MECHANICAL ROOF PLAN

E501 DETAILS - ELECTRICAL

P001 PLUMBING SCHEDULES

P201 SANITARY / VENT PLAN

P301 PRESSURE PIPE PLAN

P401 DETAILS - PLUMBING

FP201 FIRE PROTECTION PLAN

Page 2: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

ROOM

1

ELEVATION #

SHEET #

ELEVATION #

SHEET #

DETAIL #

SHEET #

ROOM

PARTITION TYPE

WINDOW TYPE

EXTERIOR ELEVATION MARK

SECTION MARK

DETAIL CALLOUT

LEVEL

SPOT ELEVATION

EQUIPMENT TYPE

REVISION #

BREAK LINE

CENTERLINE SYMBOL

CENTERLINE

ITEM ABOVE

FIRE EXTINGUISHER CABINET

KEYNOTE

A

101

1

101

1

101

1

101

12

12

F.E.

12

NORTH

EXISTING DOOR TO REMAIN

DOOR SYMBOL

WALL TO REMOVE

NEW WALL

EXISTING WALL

COLUMN GRID

SYMBOLS - ARCHITECTURAL

DOOR/WALL TO BE REMOVED

NAME

HEIGHT A.F.F.

1

HEIGHT A.F.F.

#101

NORTH

ABACTADJAFFALUMALTANODAPPROXARCHASPHAVG

ANCHOR BOLTACCOUSTICAL CEILING TILEADJACENTABOVE FINISHED FLOORALUMINUMALTERNATEANODIZEDAPPROXIMATE(LY)ARCHITECHTURALASPHALTAVERAGE

J, JSTJT

JOISTJOINT

LLINLLHLLVLONGLOUVLT

LENGTH, LONGLINEARLONG LEG HORIZONTALLONG LEG VERTICALLONGITUDINALLOUVERLIGHT

BD, BRDBET, BTWBITBLDGBLKBLKGBMBOT, BBRKBSMTBUR

BOARDBETWEENBITUMINOUSBUILDINGBLOCKBLOCKINGBEAM (BENCHMARK)BOTTOMBRICKBASEMENTBUILT-UP-ROOF

MASMATLMAXMECHMEDMEMMEMBMANUFMFGMHMINMISCMOMTL

MASONRYMATERIALMAXIMUMMECHANICALMEDIUMMEMBERMEMBRANEMANUFACTURE(D)MANUFACTURERMANHOLEMINIMUMMISCELLANEOUSMASONRY OPENINGMETAL

CBCEMCFCICJCLGCLRCMUCOCOLCONCCONNCONSTCONTCONTRCORRCTRCY

CATCH BASINCEMENTCUBIC FOOT (FEET)CAST IRONCONTROL JOINTCEILINGCLEARCONCRETE MASONRY UNITCLEAN OUT, COMPANYCOLUMNCONCRETECONNECTIONCONSTRUCTIONCONTINUOUSCONTRACTORCORRIDOR, CORRUGATEDCENTERCUBIC YARD(S)

NNFNICNONOMNORMN.T.S.

NORTHNEAR FACENOT IN CONTRACTNUMBERNOMINALNORMALNOT TO SCALE

OCODOFFOHOHGOPNGOPP

ON CENTER(S)OUTSIDE DIMENSIONOFFICEOVERHEADOVERHANGOPENINGOPPOSITE

DET, DTLDFDIADIAGDIMDNDSDWGDWL

DETAILDRINKING FOUNTAINDIAMETERDIAGONALDIMENSIONDOWNDOWN SPOUTDRAWINGDOWEL

PARTPAVMTPCCPERFPERMPLPLBGPLYWDPSFPSIPVC

PARTITIONPAVEMENTPRE CAST CONCRETEPERFORATEDPERMANENTPLATEPLUMBINGPLYWOODPOUNDS PER SQUARE FOOTPOUNDS PER SQUARE INCHPOLYVINYL CHLORIDE

EEAECEFEJELELECELEVEQEQUIPESTETREWEXISTEXPEXT

EASTEACHEPOXY COATEDEACH FACEEXPANSION JOINTELEVATIONELECTRICALELEVATOREQUALEQUIPMENTESTIMATEDEXISTING TO REMAINEACH WAYEXISTINGEXPANSION, EXPANDEXTERIOR

RADRDREFREINFREQREVRMROROW

RADIUSROOF DRAINREFERENCEREINFORCE(D)REQUIREDREVISION(S), REVISEDROOMROUGH OPENINGRIGHT-OF-WAY

FDNFFFINFLFLASHFLEXFLR, FLFOCFOMFOSFOWFPFTFTGFUT

FOUNDATIONFINISHED FLOORFINISHEDFLANGEFLASHINGFLEXIBLEFLOOR(ING)FACE OF CONCRETEFACE OF MASONRYFACE OF STUDFACE OF WALLFIRE PROTECTIONFOOT, FEETFOOTINGFUTURE

SSSSANSCHSECSFSHTSIMSPECSQSTSTNDSTDSTGSTLSTRSYSYSSYM

SOUTHSTAINLESS STEELSANITARYSCHEDULESECTIONSQUARE FOOT (FEET)SHEETSIMILARSPECIFICATION(S)SQUARESTREETSTAINEDSTANDARDSTORAGESTEELSTRUCTURE, STRUCTURALSQUARE YARD(S)SYSTEMSYMMETRY, SYMMETRICAL

GAGALVGCGENGWBGYP

GAGEGALVANIZEDGENERAL CONTRACTORGENERALGYPSUM WALL BOARDGYPSUM

TT&GTEMPTHKT.O.TRANSTYP

TREADTONGUE AND GROOVETEMPORARYTHICK, THICKNESSTOP OFTRANSVERSETYPICAL

HBHCHDCP, HCHDRHGTHMHORIZHVAC

HOSE BIBHOLLOW COREHANDICAP(PED)HEADERHEIGHTHOLLOW METALHORIZONTALHEATING/VENTILATING/AIR CONDITIONING

UNEXU.N.O.

UNEXCAVATEDUNLESS NOTED OTHERWISE

IDININSULINTINV

INSIDE DIAMETERINCH, INCHESINSULATE(D), INSULATIONINTERIORINVERT

VARVERT

VARIES, VARIABLEVERTICAL

WW/W/OWDWPWTWWF

WESTWITHWITHOUTWOODWATERPROOF(ED)(ING)WEIGHTWELDED WIRE FABRIC

ABBREVIATIONSGENERAL CONSTRUCTION NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

ALL WORK OF THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INTERNATIONAL CODE COUNCIL BUILDING CODE, FIRE CODE, ENERGY CONSERVATION CODE, PLUMBING CODE, TAS, AND ALL OTHER APPLICABLE STATE AND FEDERAL CODES AND REGULATIONS.

THE CONTRACTOR SHALL PERFORM THE WORK IN SUCH A MANNER THAT THE SAFETY OF THE WORKERS IS REASONABLY ASSURED. THIS SHALL INCLUDE PROVISIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA).

THE CONTRACTOR SHALL COMPLY WITH ALL CONTRACTUAL REQUIREMENTS; BE RESPONSIBLE FOR CONTROL OF CONSTRUCTION LOCATIONS, ELEVATIONS, DIMENSIONS, AND QUANTITIES.

PRIOR TO COMMENCEMENT OF THE WORK, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, DATUMS AND LEVELS TO IDENTIFY ANY ERRORS AND OMISSIONS; ASCERTAIN ANY DISCREPANCIES BETWEEN THIS DRAWING AND THE FULL CONTRACT DOCUMENTS; AND BRING THESE ITEMS TO THE ATTENTION OF THE ARCHITECT FOR CLARIFICATION PRIOR TO THE SUBMITTAL OF BIDS. FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR FROM PROVIDING ALL WORK AS REQUIRED TO COMPLETE PROJECT REQUIREMENTS. DRAWINGS ARE NOT TO BE SCALED.

PRIOR TO COMPLETION OF ALL WORK, CLEAN PREMISES FOR OCCUPANCY. WORK AREA SHALL BE MAINTAINED IN ORGANIZED & BROOM CLEAN CONDITION AT ALL TIMES.

THE CONTRACTOR IS RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, AND FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE CONSTRUCTION WORK; CONTRACTOR WILL BE RESPONSIBLE TO CARRY OUT THE CONSTRUCTION WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

WHEN DEMOLITION IS REQUIRED: ANY AND ALL SUSPECTED ASBESTOS AND/OR LEAD PAINT DISCOVERED DURING DEMOLITION OR CONSTRUCTION, MUST BE REPORTED TO THE OWNER IMMEDIATELY. DO NOT DISTURB OR AFFECT SUSPECTED MATERIALS UNTIL DIRECTED IN WRITING BY THE OWNER. ALL SALVAGEABLE ITEMS SHALL BE DELIVERED TO THE FACILITIES AREA, EXCEPT AS OTHERWISE DIRECTED BY OWNER. ITEMS NOT NOTED ON THE DRAWINGS FOR REUSE, SHALL BE PROTECTED, HANDLED, STORED, AND REINSTALLED IN LOCATIONS INDICATED, AND OPERATE CONSISTENT WITH THAT, PRIOR TO WORK.

REPRODUCTION OF ANY PORTION OF THESE DRAWINGS FOR RESUBMITTAL AS SHOP DRAWINGS IS PROHIBITED. SUCH SHOP DRAWINGS WILL BE REJECTED.

COORDINATE ARCHITECTURAL DRAWINGS WITH STRUCTURAL DRAWINGS. ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE WHERE DRAWINGS CONFLICT. FAILURE TO INCORPORATE OR BUILD TO ARCHITECTURAL DETAILS EVEN IF NOT INDICATED ON STRUCTURAL DRAWINGS DOES NOT OBVIATE CONTRACTORS RESPONSIBILITY.

EXISTING STRUCTURES, EQUIPMENT, AND PIPING ADJACENT TO PROPOSED CONSTRUCTION OR IMPROVEMENTS SHALL BE ADEQUATELY SUPPORTED AND PROTECTED DURING CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OR REPLACEMENT OF ANY NEW OR EXISTING STRUCTURES, PIPING, EQUIPMENT, ETC. THAT IS DAMAGED DURING CONSTRUCTION.

THE GENERAL CONTRACTOR TO PROVIDE TEMPORARY HEAT, VENTILATION, POWER, AND LIGHTING THROUGHOUT THE COURSE OF THE JOB WHERE REQUIRED.

THE CONTRACTOR SHALL NOT DISTURB ANY AREAS BEYOND THOSE SHOWN ON THE DRAWINGS AND SHALL LIMIT THE EXTENT OF DISTURBANCE FOR EACH AREA OF CONSTRUCTION AS MUCH AS POSSIBLE. THE CONTRACTOR SHALL UTILIZE EVERY EFFORT TO MINIMIZE DISTURBANCE TO THE SURROUNDING AREA.

SPRINKLER & FIRE DETECTION MODIFICATIONS SHALL BE PERFORMED STRICTLY ACCORDING TO CODE. CONTRACTOR SHALL PROVIDE ANY/ALL NECESSARY DESIGN INFORMATION, CALCULATIONS & DRAWINGS AS NECESSARY FOR MUNICIPAL APPROVAL & CODE COMPLIANT INSTALLATION. THESE CONTRACTOR PROVIDED DRAWINGS SHALL BY STAMPED BY LICENSED ENGINEER AS REQUIRED BY MUNICIPALITY.

ALL REFERENCES TO "THE CONTRACTOR" IN THESE CONTRACT DOCUMENTS REFER TO THE GENERAL CONTRACTOR (GC) UNLESS NOTED OTHERWISE.

MATERIALS, DETAILS, AND WORK PRACTICES INDICATED ON ONE PORTION OF CONTRACT DOCUMENTS SHALL BE OF THE SAME NATURE AT SAME OR SIMILAR SITUATIONS SHOWN ON THE DRAWINGS, EXCEPT AS OTHERWISE NOTED.

WHEN EXISTING CONSTRUCTION IS REMOVED, DISTURBED, DAMAGED, REPLACED OR RENOVATED IN ANY WAY, CONTRACTOR SHALL PROVIDE PATCHING, PAINTING AND MATERIALS OF SAME TYPE AND QUALITY AS TO MATCH EXISTING ADJACENT SURFACES. REFINISH SURFACES AS NECESSARY TO PROVIDE AN EVEN CONTIGUOUS FINISH.

DURING CUTTING, PATCHING AND REMOVAL OF WORK, CLEAN AND PROTECT WORK IN PROGRESS, ADJOINING WORK, AND EXISTING CONSTRUCTION ON A BASIS OF CONTINUOUS MAINTENANCE.

REMOVE AND DISPOSE OF ALL DEBRIS, RUBBISH AND OTHER WASTE MATERIALS RESULTING FROM WORK OF THIS PROJECT.

ALL NEW WORK SHALL BE PLUMB, LEVEL, AND SQUARE. SCRIBE AND MAKE FIT ALL NEW WORK TO EXISTING.

ALL BUILDING SIGNAGE SHALL BE ADA/TAS COMPLIANT.

DRAWINGS AND DIMENSIONS

GENERAL BIDDING NOTES

1. ATTENTION ALL USERS OF THESE DRAWINGS, GENERAL CONTRACTORS, SUB-CONTRACTORS, MANUFACTURERS, SUPPLIERS: CAREFULLY AND THOROUGHLY REVIEW THESE GENERAL NOTES. IT IS YOUR RESPONSIBILITY TO KNOW AND ADHERE TO THESE REQUIREMENTS.

2. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR THE CONVENIENCE OF THE ARCHITECT AND THE CONTRACTOR. THE SEPARATIONS USED HEREIN ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE, AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS, OR OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS THAT THE WORK IS NOT TO BE CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED WHOLE.

3. EVERY EFFORT HAS BEEN MADE TO MAKE THESE DOCUMENTS CONCISE AND COORDINATED, TO DEFINE WORK IN THE MOST LOGICAL PLACE AND TO ELIMINATE REDUNDANCY. DO NOT PRESUME THAT YOUR SCOPE OF WORK IS SINGULARLY DEFINED. YOUR SCOPE OF WORK IS DEFINED THROUGHOUT THE ENTIRE SET OF DRAWINGS AND SPECIFICATIONS AND IS NOT CONTAINED IN JUST ONE SERIES OF DRAWINGS OR DIVISION OF SPECIFICATIONS. YOU MUST REVIEW THE ENTIRE SET OF CONTRACT DOCUMENTS TO DETERMINE YOUR SCOPE OF WORK.

4. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES (SUCH AS CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, ETC.) ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE ARCHITECT PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR SHALL PROVIDE THE BETTER QUALITY OR GREATER QUANTITY OF WORK.

5. MECHANICAL AND ELECTRICAL DRAWINGS MAY SHOW INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL M.E. EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL AND STRUCTURAL DETAILING OF SHAFTS, CHASES, ETC...

6. THE CONTRACTOR AND ALL SUB-CONTRACTORS SHALL VISIT THE SITE AND BECOME FAMILIAR WITH SITE CONDITIONS AS THEY MAY AFFECT CARRYING OUT THE WORK AS DESCRIBED IN THESE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL INVESTIGATE, VERIFY, AND BE RESPONSIBLE FOR ALL CONDITIONS OF THE PROJECT, AND NOTIFY THE ARCHITECT OF ANY CONDITIONS THAT REQUIRE MODIFICATION BEFORE PROCEEDING WITH THE WORK.

7. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE OWNER.

8. ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.

1. DO NOT SCALE THE DRAWINGS.

2. ALL DIMENSIONS ON PLANS ARE FINISH TO FINISH UNLESS NOTED OTHERWISE.

3. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE ARCHITECT IMMEDIATELY SHOULD ANY DISCREPANCIES BE FOUND IN THE DRAWINGS AND SPECIFICATIONS.

4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND ACTUAL FIELD CONDITIONS NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.

5. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY THE CONTRACTOR AND APPROVED BY THE OWNER BEFORE ACTUAL CONSTRUCTION WORK BEGINS. ANY INDICATION OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR THE CONVENIENCE OF THE CONTRACTOR, AND ARE NOT TO BE TAKEN LITERALLY.

6. SEE NOTES ON INDIVIDUAL DRAWINGS FOR INFORMATION RELATED TO PLANS AND DETAILS ON THOSE SHEETS.

7. THE TERM "ALIGN" REFERS TO LOCATING DIFFERENT COMPONENTS OF CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.

8. CONTRACTORS AND ALL SUB-CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION AND/OR ORDERING OF MATERIALS.

9. USE OF THE WORD "VERIFY" POINTS OUT A SITUATION WHICH MUST BE CONFIRMED PRIOR TO PROCEEDING WITH THE WORK, FABRICATION OF EQUIPMENT, OR ORDERING MATERIAL. NOTIFY THE ARCHITECT OF ANY DISCREPANCY.

80

" M

IN.

27

" M

IN.

4" MAX.

COUNTER DEPTH

10"-24"

34"

MA

X.

46"

MA

X.

15"

MIN

.

48"

MA

X.

20" MAX.

48"

MA

X.

FORWARD APPROACHSIDE APPROACHFORWARD APPROACHSIDE APPROACHMAX.

10"

15"

MIN

.

48"

MA

X.

FRONT APPROACH- PUSH SIDE *IF CLOSER AND LATCH

PROVIDED

HINGE APPROACH- PULL SIDE X=36" MIN IF Y=60"X=42" MIN IF Y=54"

HINGE APPROACH- PUSH SIDE * 48" MIN IF BOTH CLOSER AND LATCH ARE

PROVIDED

LATCH APPROACH- PULL SIDE * 54" MIN WHERE CLOSER IS

PROVIDED

LATCH APPROACH- PUSH SIDE * 48" MIN WHERE CLOSER IS

PROVIDED

SIDE APPROACH FRONT APPROACH

MIN

18"

* 12"

X MIN.

24"

24"

48

"

42

"

* 4

2"

MIN

.

PUSH SIDE

PULL SIDE

* 4

8"

MIN

.

MIN.

22"

* 4

2"

PUSH SIDE

PULL SIDE

Y M

IN.

PUSH SIDE

48

" M

IN.

PULL SIDE

60

" M

IN.

FRONT APPROACH-PULL SIDE

ACCESSIBLE CLEARANCES AND REACH RANGES

DOOR CLEARANCES

> 20" -25" MAX.

44"

MA

X.

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:2

2 A

MG001

NOTE

S, S

YMBO

LS &

ABB

REVI

ATIO

NS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:2

2 A

MG001

NOTE

S, S

YMBO

LS &

ABB

REVI

ATIO

NS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

1 14

No.

Revisions and Descriptions

By

Date

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:2

2 A

MG001

NOTE

S, S

YMBO

LS &

ABB

REVI

ATIO

NS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

1 18

No.

Revisions and Descriptions

By

Date

Page 3: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

WH

WH

UP

DN

99' - 1" LF

64' - 8" LF

64' -0" L

F

54' - 5" LF

EFE

EFE

FE

FE

FE

FE

KNOX BOX AS REQ.

EFE - EXISTING FIRE EXTINGUISHER

FE - NEW FIRE EXTINGUISHER

LEGEND

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:2

3 A

MLS101

LIFE

SAF

ETY

PLAN

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1/8" = 1'-0"1

LIFE SAFETY BUILDING EXTERIOR MATERIALS NO LONGER ALLOWEDBUILDING DESIGN

STANDARDS PREFERENCE

OUTDOOR STORAGE TBD TBD

OUTDOOR RETAIL DISPLAY TBD TBD

REFUSE CONTAINER AREA REQ. 5.1

OFF STREET LOADING AREA NONE 5.1

PARKING SPACE DIM. TCSS MANUAL 5.1

OFF-STREET PARKING REQ. OFFICE = 1/200 SF=38, 122

EXISTING5.1

LANDSCAPE IRRIGATION 5.2 5.2

MIN. LANDSCAPE REQ. 5.2 5.2

MIN. LANDSCAPE AREA 5.2 5.2

LANDSCAPE 10% STREET YARD 5.2

SIDEWALKS TBD TBD

ONE-WAY ACCESS TBD TBD

TWO-WAY CURB CUTS WIDTH TBD TBD

MIN. CORNER CLEARANCE TBD TBD

MIN. ISLAND WIDTH TBD TBD

CURB RETURN RADII TBD TBD

MAX. DRIVE APPROACHES EXISTING TBD TBD

OFFICE USE PERMITTED 4.1

MAX. BUILDING AREA 50,000 3.8.D

MAX. HEIGHT (STORIES) 40' 3.8.D

MAX. BUILDING COVERAGE % 60% 3.8.D

MIN. REAR YARD 25' 3.8.D

MIN. SIDE YARD CORNER TBD ILLUSTRATION #8 APPENDIX

MIN. SIDE YARD 15', 25' ADJACENT PUBLIC ST. 3.8.D

MIN. FRONT YARD 25' 3.8.D

MIN. LOT DEPTH 150' 3.8.D

MIN. LOT WIDTH 80' 3.8.D

MIN. LOT AREA 8,000 SF 3.8.D

ZONING ETJ SALADO SECTION 21

DESCRIPTION REQUIRED AND METETJ SALADO ZONING

ORDINANCE

2 18

REMOVE AND REPLACE ALL FIRE EXTINGUISHERS. RELOCATE WHERE SHOWN

Page 4: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

WH

WH

DN2

2

2

2

2

2

2

1

1

1

1

11

1

1

1

1

1

1

3

3

3

4

4

5

5

6

6

4

4

4

4

6

78

9

9

9

10

10

2

1111

11

11

11

8' - 0"26' - 8"3' - 4"7' - 2"

4"

3' -

4"

8' - 0"7' - 5"6' - 4"7' - 5"8' - 0"41' - 7"10

10

10

99

2

25' - 11"

DEMO - REMOVE ALL EXTERIOR STONE, DOORS, WALLS, CEILINGS, FLOORS, LIGHTING, ELECTRICAL, AND PLUMBING FIXTURES IN AREAS SHOWN DASHED

TO REMAIN

GENERAL DEMOLITION NOTES:

A. THESE NOTES ARE GENERAL IN NATURE AND APPLY TO THE ENTIRE BUILDING WHETHER OR NOT SPECIFICALLY NOTED OR REFERENCED ON EACH SHEET. THE DRAWINGS INDICATE ONLY THE GENERAL EXTENT OF DEMOLITION AND MAY NOT INCLUDE ALL DEMOLITION WHICH WILL BE REQUIRED FOR NEW CONSTRUCTION, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTING THE WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR THE INCLUSION OF ALL REQUIRED DEMOLITION AREAS UNDERGOING MODIFICATION WHETHER SUCH WORK IS OR IS NOT INDICATED ON THE CONTRACT DOCUMENTS. TO DETERMINE THE FULL EXTENT OF ITEMS TO BE DEMOLISHED OR REMOVED AND SALVAGED FOR RE-USE, DEMOLITION SHALL GENERALLY BE ARRANGED TO AGREE WITH THE ACCOMPLISHMENT OF WORK UNDER THE VARIOUS PHASES AND IN COORDINATION WITH THE WORK OF ALL TRADES. CONTRACTOR SHALL EXAMINE THE CONTRACT DOCUMENTS FOR ADDITIONAL REQUIREMENTS.

B. ALL WORK MUST BE IN STRICT COMPLIANCE WITH ALL CODES, REGULATIONS, AND ORDINANCES OF THE AGENCIES HAVING JURISDICTION OVER ANY PORTION OF THE WORK, INCLUDING ALL LICENSES AND PERMITS.

C. THE CONTRACTOR SHALL BEAR THE RESPOSIBILITY OF VERIFYING EXISTING UTILITY LOCATIONS AND ENSURE THAT UTILITIES IN AREAS OF DEMOLITION AND CONSTRUCTION ARE NOT DAMAGED. DAMAGED UTILITIES SHALL BE REPAIRED AT THE CONTRACTOR'S OWN EXPENSE AND SHALL NOT IMPACT PROJECT SCHEDULE.

D. DIMENSIONS NOTED AS VIF (VERIFY IN FIELD) ARE APPROXIMATE BUT SHALL BE MAINTAINED AS MUCH AS GOOD CONSTRUCTION PRACTICES ALLOW. NOTIFY ARCHITECT OF ANY DISCREPANCY MORE THAN ONE INCH. SPECIFIC DIMENSIONS SHALL BE MAINTAINED.

E. CONTRACTOR SHALL NOTIFY ARCHITECT IMMEDIATELY IF ANY UNFORSEEN CONDITIONS ARE DISCOVERED THAT POTENTIALLY EFFECT THE STRUCTURAL INTEGRITY OF THE WORK TO REMAIN.

F. ELEMENTS TO BE REMOVED THAT ARE INDICATED BY BROKEN LINES SHOW THE GENERAL EXTENT OF DEMOLITION ONLY. UNLESS NOTED OTHERWISE ACTUAL DIMENSIONS MAY NEED TO BE DETERMINED BY FIELD MEASURING.

G. COORDINATE ALL SHUTOFF SERVICES WITH THE OWNER 72 HOURS IN ADVANCE MINIMUM.

H. IF AREAS IMMEDIATELY ADJACENT TO THE WORK WILL BE OCCUPIED, MINIMIZE INTERFERENCE WITH THE DAILY ACTIVITIES OF THE OWNER'S STAFF AND OPERATIONS.

I. ITEMS TO BE SALVAGED FOR RE-USE SHALL BE STORED IN A SAFE AND SECURE LOCATION AS DIRECTED BY THE OWNER UNTIL REINSTALLATION.

J. DURING ALL PHASES OF WORK CLEANING AND DISPOSAL SHALL BE PERFORMED DAILY IN SUCH A MANNER AS TO INSURE THAT THE PREMISES, ADJACENT PUBLIC PROPERTY AND ADJACENT PRIVATE PROPERTIES ARE MAINTAINED FREE FROM ACCUMULATION OF DEBRIS, WASTE MATERIAL AND RUBBISH. UNLESS NOTED OTHERWISE ALL EQUIPMENT, WRECKED AND DEMOLISHED MATERIALS, DEBRIS AND RUBBISH SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES AS QUICKLY AS IT ACCUMULATES. DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF SITE. COMPLY WITH ALL LOCAL HAULING & DISPOSAL REQUIREMENTS.

K. AT ALL LOCATIONS WHERE DEBRIS IS TO BE TRANSFERED VERTICALLY FOR A DISTANCE OF 10 FEET OR MORE THE CONTRACTOR SHALL PROVIDE AN ENCLOSED CHUTE FOR THIS PURPOSE. DEBRIS SHALL NOT SPILL FROM THE BOTTOM OF THE CHUTE DIRECTLY ONTO THE GROUND. THE FINAL DROP OF DEBRIS SHALL BE INTO EITHER AN APPROVED COLLECTION HOPPER OR TRUCK.

L. THE GENERAL CONTRACTOR SHALL VERIFY THAT ALL ITEMS TO BE REMOVED/DEMOLISHED ARE NON-LOAD BEARING PRIOR TO START OF ANY DEMOLITION. REMOVE PORTION OF EXISTING WALL SYSTEM(S) IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO FRAMING, WALLBOARD, BASES, TRIM AND BRACING.

M. COORDINATE ARCHITECTURAL DEMOLITION DRAWINGS WITH ALL OTHER DEMOLITION DRAWINGS INCLUDING BUT NOT LIMITED TO STRUCTURAL, MECHANICAL, ELECTRICAL PLUMBING.

N. ANY ERRORS, OMISSIONS, OR DISCREPANCIES IN THE DRAWINGS, RELATED TO THE EXISTING CONDITIONS AND DEMOLITION IN GENERAL, SHALL BE REPORTED TO THE ARCHITECT/OWNER PRIOR TO START OF ANY DEMOLITION.

O. THERE IS NO KNOWN EXISTANCE OF ASBESTOS CONTAINING MATERIALS (ACMs) OR LEAD BASED PAINT IN THIS PROJECT. THE ARCHITECT HAS NO KNOWLEDGE OF AND SHALL NOT BE HELD LIABLE FOR ANY ASBESTOS OR OTHER HAZARDOUS MATERIALS ON THE JOB SITE. ANY SUSPECTED ACMs AND/OR LEAD PAINT DISCOVERED DURING DEMOLITION OR CONSTRUCTION MUST BE REPORTED TO THE OWNER IMMEDIATELY. DO NOT DISTURB OR AFFECT SUSPECTED MATERIALS UNTIL DIRECTED IN WRITING BY OWNER.

P. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL MEANS AND METHODS OF DEMOLITION AND CONSTRUCTION EMPLOYED ON THIS PROJECT INCLUDING ALL TEMPORARY BRACING, SUPPORT AND PROTECTION OF THE EXISTING STRUCTURE. THIS INCLUDES BUT IS NOT LIMITED TO PERFORMING A STRUCTURAL ANALYSIS OF THE AREAS TO BE EFFECTED BY THE WORK AND DETERMINING LOADS ON TEMPORARY SHORING, BRACING AND SUPPORT SYSTEMS. WHEN REQUIRED, CONTRACTOR SHALL RETAIN THE SERVICES OF A REGISTERED PROFESSIONAL STRUCTURAL ENGINEER AT HIS/HER OWN EXPENSE TO MAINTAIN SAFE AND STABLE CONDITIONS ON THE PROJECT INCLUDING PROVISIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA). ANY SEQUENCES OF WORK OR METHODS INDICATED OR IMPLIED IN THE CONTRACT DOCUMENTS ARE PRESENT ONLY AS ASSUMPTIONS TO BE CONSIDERED AS A SUGGESTED OPTION FOR REVIEW BY THE CONTRACTOR.

EV

EN

T D

R.

13

15

14

12

16

10' - 7"

3' - 0"

28' - 2"26' - 1"28' - 3"3' - 0"

82' - 6"

10

' -

6"

12

1313

14

1510

10

4 19

DEMOLITION KEYED NOTES:

1

2

3

4

5

6

7

8

9

10

REMOVE EXISTING DOOR AND DOOR FRAME - PREP FOR NEW DOOR WHERE WALLS REMAIN

REMOVE EXISTING INTERIOR WALL. FIELD VERIFY STRUCTURAL SUPPORT PRIOR TO REMOVAL

REMOVE EXISTING WOOD STAIRS, LANDINGS & SIDEWALLS -PROTECT EXISTING WALL.

REMOVE WINDOWS - PREP FOR INFILL ON ALL EXTERIOR WINDOWS.

REMOVE CASED OPENING IN THEIR ENTIRETY

REMOVE ALL CABINETRY AND COUNTERTOPS

REMOVE ALL FLOORING - PREP FOR NEW FLOORING (ALL ROOMS)

REMOVE ALL CEILING IN THEIR ENTIRETY TO STRUCTURE (ALL ROOMS WHERE APPLICABLE)

SELECT DEMO WALL FOR NEW DOOR/ WINDOW AS SCHEDULED RE: ELEV.

REMOVE STONE AND PREP FOR NEW PRE MANUFACTURED STONE REPLACEMENT

REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED CABINETRY/ TOILET PARTITONS

REMOVE PARAPET AND SIGNAGE - PREP FOR CLOSURE TO MATCH THE REST OF THE BUILDING.

REMOVE CHAIN LINK FENCE AND GATE ON SOUTH SIDE OF BUILDING - PREP ASPHALT TO BE FLUSH WITH EXISTING SITE

REMOVE RAILING TO REATTACH TO EXTENSION

REMOVE PIPE FENCE AND GAZEBO - PREP FOR NEW MONUMENT WALL AS SHOWN ON PLANS

REMOVE CONC FLATWORK AND ASPHALT WHERE SHOWN - PREP FOR NEW FOUNDATION BEAMS AND NEW CONCRETE (APPROX 308 SF ASPHALT, AND 248 SF CONC

REMOVE SIGNAGE - PREP FOR NEW SIGN

11

12

13

14

15

16

SITE DEMO

17

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:2

1 A

MD101

DEM

OLIT

ION

PLAN

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

dM TMR

1/8" = 1'-0"1

DEMO PLAN

No.

Revisions and Descriptions

By

Date

1" = 40'-0"3

EXISTING SITE - DEMO1/8" = 1'-0"

2WEST - DEMO 3 16

Page 5: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

6' - 0"

11' - 7"

7' - 8"

2' -

8"

2' -

2"

2' -

3"

1' - 6"1' - 2"6' - 0"1' - 6"1' - 5"

1' - 11"7' - 8"2' - 0"

2

A203

GENERAL DEMOLITION NOTES:

A. THESE NOTES ARE GENERAL IN NATURE AND APPLY TO THE ENTIRE BUILDING WHETHER OR NOT SPECIFICALLY NOTED OR REFERENCED ON EACH SHEET. THE DRAWINGS INDICATE ONLY THE GENERAL EXTENT OF DEMOLITION AND MAY NOT INCLUDE ALL DEMOLITION WHICH WILL BE REQUIRED FOR NEW CONSTRUCTION, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTING THE WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR THE INCLUSION OF ALL REQUIRED DEMOLITION AREAS UNDERGOING MODIFICATION WHETHER SUCH WORK IS OR IS NOT INDICATED ON THE CONTRACT DOCUMENTS. TO DETERMINE THE FULL EXTENT OF ITEMS TO BE DEMOLISHED OR REMOVED AND SALVAGED FOR RE-USE, DEMOLITION SHALL GENERALLY BE ARRANGED TO AGREE WITH THE ACCOMPLISHMENT OF WORK UNDER THE VARIOUS PHASES AND IN COORDINATION WITH THE WORK OF ALL TRADES. CONTRACTOR SHALL EXAMINE THE CONTRACT DOCUMENTS FOR ADDITIONAL REQUIREMENTS.

B. ALL WORK MUST BE IN STRICT COMPLIANCE WITH ALL CODES, REGULATIONS, AND ORDINANCES OF THE AGENCIES HAVING JURISDICTION OVER ANY PORTION OF THE WORK, INCLUDING ALL LICENSES AND PERMITS.

C. THE CONTRACTOR SHALL BEAR THE RESPOSIBILITY OF VERIFYING EXISTING UTILITY LOCATIONS AND ENSURE THAT UTILITIES IN AREAS OF DEMOLITION AND CONSTRUCTION ARE NOT DAMAGED. DAMAGED UTILITIES SHALL BE REPAIRED AT THE CONTRACTOR'S OWN EXPENSE AND SHALL NOT IMPACT PROJECT SCHEDULE.

D. DIMENSIONS NOTED AS VIF (VERIFY IN FIELD) ARE APPROXIMATE BUT SHALL BE MAINTAINED AS MUCH AS GOOD CONSTRUCTION PRACTICES ALLOW. NOTIFY ARCHITECT OF ANY DISCREPANCY MORE THAN ONE INCH. SPECIFIC DIMENSIONS SHALL BE MAINTAINED.

E. CONTRACTOR SHALL NOTIFY ARCHITECT IMMEDIATELY IF ANY UNFORSEEN CONDITIONS ARE DISCOVERED THAT POTENTIALLY EFFECT THE STRUCTURAL INTEGRITY OF THE WORK TO REMAIN.

F. ELEMENTS TO BE REMOVED THAT ARE INDICATED BY BROKEN LINES SHOW THE GENERAL EXTENT OF DEMOLITION ONLY. UNLESS NOTED OTHERWISE ACTUAL DIMENSIONS MAY NEED TO BE DETERMINED BY FIELD MEASURING.

G. COORDINATE ALL SHUTOFF SERVICES WITH THE OWNER 72 HOURS IN ADVANCE MINIMUM.

H. IF AREAS IMMEDIATELY ADJACENT TO THE WORK WILL BE OCCUPIED, MINIMIZE INTERFERENCE WITH THE DAILY ACTIVITIES OF THE OWNER'S STAFF AND OPERATIONS.

I. ITEMS TO BE SALVAGED FOR RE-USE SHALL BE STORED IN A SAFE AND SECURE LOCATION AS DIRECTED BY THE OWNER UNTIL REINSTALLATION.

J. DURING ALL PHASES OF WORK CLEANING AND DISPOSAL SHALL BE PERFORMED DAILY IN SUCH A MANNER AS TO INSURE THAT THE PREMISES, ADJACENT PUBLIC PROPERTY AND ADJACENT PRIVATE PROPERTIES ARE MAINTAINED FREE FROM ACCUMULATION OF DEBRIS, WASTE MATERIAL AND RUBBISH. UNLESS NOTED OTHERWISE ALL EQUIPMENT, WRECKED AND DEMOLISHED MATERIALS, DEBRIS AND RUBBISH SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES AS QUICKLY AS IT ACCUMULATES. DISPOSE OF ALL DEMOLISHED OR REMOVED MATERIALS LEGALLY OFF SITE. COMPLY WITH ALL LOCAL HAULING & DISPOSAL REQUIREMENTS.

K. AT ALL LOCATIONS WHERE DEBRIS IS TO BE TRANSFERED VERTICALLY FOR A DISTANCE OF 10 FEET OR MORE THE CONTRACTOR SHALL PROVIDE AN ENCLOSED CHUTE FOR THIS PURPOSE. DEBRIS SHALL NOT SPILL FROM THE BOTTOM OF THE CHUTE DIRECTLY ONTO THE GROUND. THE FINAL DROP OF DEBRIS SHALL BE INTO EITHER AN APPROVED COLLECTION HOPPER OR TRUCK.

L. THE GENERAL CONTRACTOR SHALL VERIFY THAT ALL ITEMS TO BE REMOVED/DEMOLISHED ARE NON-LOAD BEARING PRIOR TO START OF ANY DEMOLITION. REMOVE PORTION OF EXISTING WALL SYSTEM(S) IN THEIR ENTIRETY INCLUDING BUT NOT LIMITED TO FRAMING, WALLBOARD, BASES, TRIM AND BRACING.

M. COORDINATE ARCHITECTURAL DEMOLITION DRAWINGS WITH ALL OTHER DEMOLITION DRAWINGS INCLUDING BUT NOT LIMITED TO STRUCTURAL, MECHANICAL, ELECTRICAL PLUMBING.

N. ANY ERRORS, OMISSIONS, OR DISCREPANCIES IN THE DRAWINGS, RELATED TO THE EXISTING CONDITIONS AND DEMOLITION IN GENERAL, SHALL BE REPORTED TO THE ARCHITECT/OWNER PRIOR TO START OF ANY DEMOLITION.

O. THERE IS NO KNOWN EXISTANCE OF ASBESTOS CONTAINING MATERIALS (ACMs) OR LEAD BASED PAINT IN THIS PROJECT. THE ARCHITECT HAS NO KNOWLEDGE OF AND SHALL NOT BE HELD LIABLE FOR ANY ASBESTOS OR OTHER HAZARDOUS MATERIALS ON THE JOB SITE. ANY SUSPECTED ACMs AND/OR LEAD PAINT DISCOVERED DURING DEMOLITION OR CONSTRUCTION MUST BE REPORTED TO THE OWNER IMMEDIATELY. DO NOT DISTURB OR AFFECT SUSPECTED MATERIALS UNTIL DIRECTED IN WRITING BY OWNER.

P. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL MEANS AND METHODS OF DEMOLITION AND CONSTRUCTION EMPLOYED ON THIS PROJECT INCLUDING ALL TEMPORARY BRACING, SUPPORT AND PROTECTION OF THE EXISTING STRUCTURE. THIS INCLUDES BUT IS NOT LIMITED TO PERFORMING A STRUCTURAL ANALYSIS OF THE AREAS TO BE EFFECTED BY THE WORK AND DETERMINING LOADS ON TEMPORARY SHORING, BRACING AND SUPPORT SYSTEMS. WHEN REQUIRED, CONTRACTOR SHALL RETAIN THE SERVICES OF A REGISTERED PROFESSIONAL STRUCTURAL ENGINEER AT HIS/HER OWN EXPENSE TO MAINTAIN SAFE AND STABLE CONDITIONS ON THE PROJECT INCLUDING PROVISIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA). ANY SEQUENCES OF WORK OR METHODS INDICATED OR IMPLIED IN THE CONTRACT DOCUMENTS ARE PRESENT ONLY AS ASSUMPTIONS TO BE CONSIDERED AS A SUGGESTED OPTION FOR REVIEW BY THE CONTRACTOR.

DEMOLITION KEYED NOTES:

1

2

3

4

5

6

7

8

9

10

REMOVE EXISTING DOOR AND DOOR FRAME - PREP FOR NEW DOOR WHERE WALLS REMAIN

REMOVE EXISTING INTERIOR WALL. FIELD VERIFY STRUCTURAL SUPPORT PRIOR TO REMOVAL

REMOVE EXISTING WOOD STAIRS, LANDINGS & SIDEWALLS -PROTECT EXISTING WALL.

REMOVE WINDOWS - PREP FOR INFILL ON ALL EXTERIOR WINDOWS.

REMOVE CASED OPENING IN THEIR ENTIRETY

REMOVE ALL CABINETRY AND COUNTERTOPS

REMOVE ALL FLOORING - PREP FOR NEW FLOORING (ALL ROOMS)

REMOVE ALL CEILING IN THEIR ENTIRETY TO STRUCTURE (ALL ROOMS WHERE APPLICABLE)

SELECT DEMO WALL FOR NEW DOOR/ WINDOW AS SCHEDULED RE: ELEV.

REMOVE STONE AND PREP FOR NEW PRE MANUFACTURED STONE REPLACEMENT

REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED CABINETRY/ TOILET PARTITONS

REMOVE PARAPET AND SIGNAGE - PREP FOR CLOSURE TO MATCH THE REST OF THE BUILDING.

REMOVE CHAIN LINK FENCE AND GATE ON SOUTH SIDE OF BUILDING - PREP ASPHALT TO BE FLUSH WITH EXISTING SITE

REMOVE RAILING TO REATTACH TO EXTENSION

REMOVE PIPE FENCE AND GAZEBO - PREP FOR NEW MONUMENT WALL AS SHOWN ON PLANS

REMOVE CONC FLATWORK AND ASPHALT WHERE SHOWN - PREP FOR NEW FOUNDATION BEAMS AND NEW CONCRETE (APPROX 308 SF ASPHALT, AND 248 SF CONC

REMOVE SIGNAGE - PREP FOR NEW SIGN

11

12

13

14

15

16

SITE DEMO

17

DEMO - REMOVE ALL EXTERIOR STONE, DOORS, WALLS, CEILINGS, FLOORS, LIGHTING, ELECTRICAL, AND PLUMBING FIXTURES IN AREAS SHOWN DASHED

TO REMAIN

Scal

e:

Project No.

Dat

e:

Dra

wn

By:

Che

cked

By:

Sheet No.

Proj

ect T

itle:

Dra

win

g Ti

tle:

Cop

yrig

ht C

202

1M

RB

Gro

upAl

l Rig

hts

Res

erve

d

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:5

5:5

2 A

MD102

SIGN

DEM

O

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1/2" = 1'-0"1

ROAD SIGNAGE DEMO

17

4 18

Page 6: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

33

24

7

21

10

EV

EN

T D

R.

A0861BC Y WILLIAMS2.40 ACRES

FM 2484

7

AC ENCLOSURE

AC ENCLOSURE

SEPTIC ENCLOSURE

130 (9X18 TYP) PARKING SPACES - FIELD VERIFY

5

18' - 0"

24' - 0"

PERMANENTLY CLOSED GATE

EXPANDED ROAD. BY

PREVIOUS CIVIL PROJECT

27' - 9"36' - 0"25' - 0"

23

SITE EXISTING EXCEPT @ ENTRY - RESTRIPE ASPHALT PARKING LOT AS SHOWN W/ 4" WHITE STRIPING AND RED FIRE LANE STRIPING PER CODE

C101

2FIRE LANE

FIRE LANE

FIRE LANEC101

3

13

' -

1"

9' -

9"

ROOF LINE ABOVE6" CONCRETE FILLED BOLLARD (TYP OF 4) -SPACED EVENLY - SEE 5/C101

FOYER

NEW SLOPED CONCRETE SLAB

NEW SLOPED CONCRETE

EXISTING ASPHALT

SLO

PE

AS

RE

Q'D

20

' -

1"NEW WHEEL STOPS WHERE

RESTRIPING OCCURS (TYP)

SLOPE

2% MAXSLOPE

2% MAX

MATCH EXISTING ELEV.

NEW SLOPED CONCRETE

MATCH EXISTING ELEV

MATCH EXISTING ELEV

MATCH F.F.0' - 0"

3' - 0"31' - 8"19' - 1"31' - 9"3' - 0"

EXISTNEW

16' - 0"19' - 1"16' - 0"

FOLLOW EXIST GRADE

EXIST NEW

SLOPE TO EXISTING WALK 1:12 MAX

SLOPE TO EXISTING WALK 1:12 MAX

FOLLOW EXIST GRADE

ROUNDED CONC. TOP TO DRAIN

6" DIA. CONCRETE FILLED STEEL BOLLARD, TYP. - PAINT

18" DIA. CONCRETE PIER

4' -

3"

3' -

0"

4' -

0"

1' - 6"

DIM

TO

SIG

NA

GE

1' -

0"

4

C101

DIM TO OUTSIDE WALL

10' - 0"

14

' -

9"

14' - 4"

DIM

TO

OU

TS

IDE

WA

LL

10

' -

0"

10 1/8"

FINISHED FLOOR0' - 0"

8" FILLED CMU W/ #4 VERTICAL REBAR @ 16" O.C.

1 1/4" GEN STONE MANUFACTURED STONE PANELS OR APPROVED EQUAL

12" PRECAST STONE CAP

7' -

10

"2

"

3' - 8"

1' - 4 15/16" 10 1/8" 1' - 4 15/16"

1' -

0"

0' -

10

"

#4 DOWEL @ 16" O.C.

REVERSE DIRECTION OF HOOK ON EVERY OTHER REBAR

#4 HORIZONTAL @ 32" MAX O.C. (USE BOND BEAM BLOCK)

2' -

0"

#4 @ 16" O.C.

1 OF 4 - #4 CONT.

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:1

9 A

MC101

PROP

OSED

SIT

E PL

AN

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

dM TMR

1" = 40'-0"1

SITE

No.

Revisions and Descriptions

By

Date

3/16" = 1'-0"2

ENLARGED SITE

1/2" = 1'-0"5

BOLLARD DETAIL, TYP

1/4" = 1'-0"3

STONE WALL3/4" = 1'-0"

4STONE WALL STRUCTURE

5 18

Page 7: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

WH

WH

666

666

UP

DN

CLERKS

121

OPEN/FUTURE VOTING

130

JUDGES CHAMBER

120

COURTROOM

115

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

MOP

107

ELEC

111

60

' -

3"

IT

122

JURY/TRAINING

116

18

' -

10

"1

2' -

5"

10

' -

0"

18

' -

0"

5' -

10

"4

' -

11

"4

' -

0"

3' -

3"

13' - 9"4' - 10"7' - 9"10' - 4"46' - 0"18' - 1"17' - 0"7' - 6"

12

' -

5"

6' -

5"

4' - 4"

6' - 6"

6' -

0"

10

' -

0"

10

' -

10

"1

1' -

11

"8

' -

0"

6' -

3"

6' -

3"

15' - 0"17' - 9"29' - 4"

46' - 0"21' - 7"5' - 3"14' - 9"

20

' -

10

"

6' -

0"

6' -

7"

10

' -

3"

4' -

0"

32

' -

5"

12

' -

7"

12

' -

0"

4' -

8 1

/2"

4' -

8 1

/2"

11

' -

0"

6' -

1"

5' -

8"

15

' -

1"

2' - 11"3' - 1"

9' - 11"4' - 6"2' - 7"

4' -

8"

4' -

0"

3' -

9"

6' -

10

"

2' - 11 1/2"1' - 11"4' - 0"1' - 11"4' - 0"1' - 11"4' - 0"15' - 5"

4' -

0"

9' -

5"

5' -

3"

9' -

5"

4' -

0"

10' - 4"

3' - 3"4' - 3"

EVIDENCE

104

STORAGE

109

CONFERENCE

112

CONFERENCE

113

ADA RR

129

CONSTABLE

103

29' - 6"7' - 6"45' - 9"

CORRIDOR

125

CONSTABLE

105

STORAGE

118

2' -

7"STORAGE

124

AV

117

5' - 6"8' - 5"4' - 2"

16

' -

0"

16

' -

0"

COURT

114

7' -

0"

6' -

0"

3' -

0"

3' -

0"

6' -

0"

7' -

0"

4' -

0"

11

' -

7"

45' - 0"19' - 1"61' - 2"

10

' -

0"

FOYER

101

1

A301

2

A301

CLOSET

119

COORIDOR

123

20' - 1 1/2"3' - 4"6' - 4 1/2"2' - 10"14' - 8"3' - 10"3' - 0"3' - 10"25' - 9"3' - 4"26' - 8"3' - 4"1' - 3"3' - 4"3' - 7"

13' - 8"4' - 4"70' - 10"10' - 6"15' - 5"

20' - 1 1/2"3' - 4"6' - 4 1/2"2' - 10"3' - 4"

8' - 0"

7' - 5"6' - 4"7' - 5"8' - 0"42' - 7"

4' -

6"

34

' -

10

"1

1' -

6"

8' -

5"

50

' -

8"

9' -

7"

3' - 6"4' - 6 1/2"10' - 0"4' - 6 1/2"3' - 6"

1

A302

A40113

A401 6

A4017

A401

1

3

11

12

10

2

17' - 10"

125' - 3"

10' - 2"5' - 3"

1' -

7"

4' -

1"

1' -

7"

4' -

6"

9' - 11"5' - 6"

9' -

5"

5' -

0"

3' - 9"2' - 6"

3' -

6"

26' - 1" ALL SEATING TO BE PROVIDED BY OWNER

DOORS AND WINDOW SCHEDULE - SHEET A601

17

A501

7' - 8"12' - 4"

0' - 0"

1' -

8"

3

A302

14

A401

4

C101

A402

2

A402

3

A402

1

9' - 9"

19

' -

6"

4' -

4"

36

' -

5"

1' -

10

"6

' -

4"

1' -

10

"

6' -

1"

3' -

4"

0' -

2"

1' -

4"

3' -

4"

22

' -

3"

2' -

10

"2

0' -

11

"

2'-10" x 2'-10" WINDOW INFILL

36" x 84" WALL INFILL

36" x 84" WALL INFILL

56" x 84" WALL INFILL 36" x 84" WALL INFILL

36" x 84" WALL INFILL

3'-10" x 2'-10" WINDOW INFILL3" X 3'-10" WINDOW INFILL

8' -

7"

20' - 7"MEZZANINE ABOVE - RE: A102

36" x 84" WALL INFILL

5' - 11"11' - 6"

4' -

5"

A102

5

A401

9

2' -

0"

A401 4

5

6' - 9"6' - 9"3' - 8"

11

' -

10

"

2' -

11

"6

' -

0"

3' -

1"

10' - 2"

12

' -

1"

10' - 1"

6' -

2"

8' - 0"3' - 0"3' - 0"

6' -

11

"

3' - 0"3' - 0"3' - 6"

SAFES BY OWNER

10 1/8" - CMU WITH PREMANUFACTURED GENSTONE ON BOTH SIDES

12" - EXISITNG WALL

12" - NEW WALL INFILL

8 5/8" - PRE MANUFACTURED GENSTONE ON EXTERIOR SHEATHING ON 6" METAL STUD ON GYP BD ON INTERIOR

5" - EXISTING WALL

4 7/8" - NEW METAL STUD WALL

5" - NEW WOOD STUD PONY WALL W/ PLYWOOD FACES

4 7/8" - NEW METAL STUD PONY WALL W/ GYP FACES

4 3/4" - NEW WOOD STUD PONY WALL W/ GYP BOTH SIDES @ DESKS

1 1/4" PRE MANUFACTURED GENSTONE

WALL LEGEND

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:0

7 A

MA101

SCHE

MAT

IC F

LOOR

PLA

N

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

3/16" = 1'-0"1

FLOOR PLAN SCHEMATIC 7,646 SF

No.

Revisions and Descriptions

By

Date

6 18

Page 8: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

UP

EXISTING METAL ROOF

2:1

22

:12

41' - 9"26' - 1"57' - 8"

3:1

2

3:12

3:1

2

3:12

HVAC

HV

AC

EX

IST

ING

RA

MP

EXISTING METAL ROOF

EXISTING METAL ROOF EXISTING METAL ROOF

EXISTING METAL ROOF

EXISTING METAL ROOFEXISTING METAL ROOF

NEW METAL ROOF - MATCH EXIST

4:124:12

3:1

24:12

4

A102

2' -

0"

20' - 7"

HVAC MECH EXTENSION

NEW FASCIA PANEL AND

TRIM TO MATCH EXIST @

PARAPET DEMO

3:1

2

12' - 0"

9' - 0"

9' - 0"9' - 0"

9' - 0"9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

*

*

****

**

**

24 X 36 ALUM ATTIC ACCESS PULL DOWN - RATED 250 LB MIN

GYP. BD.

CEILING LEGEND

2X2 ACT

FINISHED FLOOR0' - 0"

REATTACH RAILING @ FRONT OF MEZZANINE

EXISTING WOODEN FENCE

2'-0" EXTENSION

4' - 9"

2' - 0" 6' - 7"

EXIST EXPANDED METAL RAILING

INFILL EXPANDED METAL RAILING TO

MATCH EXISTING

EXIST STEEL MECH MEZZANINE. EXTEND C-CHANNEL 2'-0" NORTH - BRACING TO MATCH SIZE & SPACING OF EXISTING. NEW EXPANDED METAL FLOORING TO MATCH EXISTING. FULLY WELD AND GRIND ALL CONNECTIONS, TYP. (PAINT ALL EXPOXY BLACK)

EXISTING BUILDING

0' - 5"

1

A301

2

A301

A40113

A401

8

1' - 0"

0' - 6"

0' - 6" 0' - 0"0' - 0"

6' - 0"7' - 5"

6' -

0"

6' -

0"

1' -

0"

5' -

8"

11"

1' - 0"1' - 0"

22'-0" RADIUS

3' -

0"

7' -

1"

9' -

2"

4"

7' -

1"

4"

1' -

0"

6' -

0"

1' -

0"

1' - 3"2' - 9"

2' -

0"

3' -

9"

3' -

0"

3' - 0"

1' - 0"6' - 0"1' - 0"3' - 0"

1' - 8"

1 1/2" TUBE STEEL RAILING -WELD AND GRIND ALL JOINTS

10

A501

11

A501

12

A501

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:0

9 A

MA102

RCP/

ROOF

PLA

N

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1" = 10'-0"1

ROOF PLAN

1" = 10'-0"2

RCP PLAN

3/8" = 1'-0"4

HVAC PLATFORM

***

BLOW - IN CELLULOSE INSULATION OVER GYP - 0'-6" MIN @ THESE ROOMS (COVER ENTIRE CEILING)

BLOW - IN CELLULOSE INSULATION OVER GYP - 6'-0" MIN FROM WALL

3/8" = 1'-0"5

ENLARGED PLAN @ DAIS

7 18

Page 9: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

WH

WH

UP

DN

WH

WH

UP

DN

1

7

7

2

11

1

1

1

1

1

1

1

1

7

7

1

4

1

1

1

3

7

7

1

3

5

5

5

5

5

5

55 5

5

5

1

5

5

5

5

53

A103

5

1

6 6

6

6

3

3

7

TYPE 1. STANDARD WALL - 3 5/8" METAL STUD AT 16" O.C. WITH 5/8" GYP ON BOTH SIDES - SUBSITUTE WITH GREEN BOARD AT WET AREAS

TYPE 2. PONY WALL - TYPE 1 WALL - 4'-0" HIGH WITH 3X3 STL COLUMN @ UNSUPPORTED END (TYP)

TYPE 3. PONY WALL - 2X4 WOOD STUD @ 16" O.C. WITH 3/4" OAK VENEER, STAINED PLYWOOD ON BOTH SIDES. SEE INTERIOR ELEV. FOR WALL HEIGHTS

TYPE 4. EXTERIOR - 2" PRE MANUFACTURED STONE WITH ON WATERPROOF BARRIER ON EXTERIOR SHEATHING ON 6" METAL STUD 18 ga WITH 5/8" GYP BD ON INTERIOR. 6" BATT INSULATION IN ALL CAVITIES

TYPE 5. EXISTING WALLS - SHALL NOT BE MODIFIED.

TYPE 6. EXTERIOR - 2" PRE MANUFACTURED STONE - SEE ELEVATIONS FOR HEIGHTS

TYPE 7. SOUND WALL - TYPE 1 W/ 4" UNFACED BATT INSULATION

WALL TYPES

OAK STAINED PLYWOOD CAP WITH 1 1/4" STAINED BULLNOSE EDGES

SE

E E

LE

V.

3X3 STEEL COLUMN ON 4X3 PLATE BOLTED TO FLOOR @ UNSUPPORTED ENDS (TYP)

FINISH SPECIFICATIONS

GYP BD - INTERIOR CEILINGS TO BE 5/8" TYPE 'X' GYPSUM BOARD, TEXTURED WITH A MEDIUM LEVEL ORANGE PEEL AND PAINTED WITH ONE COAT PREP RITE 200 LATEX WALL PRIMER B28W200 (1.1 MILS) AND TWO COATS REGAL INTERIOR PAINT.

ACT - 2X2 ACOUSTIC TILE, ARMSTRONG OPTIMA LAY-IN SQUARE. THROUGHOUT EXCEPT WHERE OTHERWISE NOTED - INSTALL PER MANUF RECOMMENDATIONS

METAL FRAMES TO BE PAINTED WITH SATIN WATER BASE ACRYLIC LATEX EQUIVALENT TO ONE COAT OF DTM ACRYLIC PRIMER/FINISH (2.5 MILS) AND TWO FINISH COATS DTM ACRYLIC S-6 (3.0 MILS EA.). PAINT TO MATCH ADJACENT WALLS

ALL WINDOW TRIM, PRIME & PAINT, INTERIOR SIDE

RUBBER BASE, TYP. THROUGHOUT. TILE BASE IN BATHROOMS

ALL INTERIOR DOORS TO BE STAIN GRADE

ALL INTERIOR FRAMES TO BE PAINTED

WALLS

CEILINGS

TRIM

DOORS

FLOORS

ALL PAINTS TO BE SHERWIN WILLIAMS UNLESS OTHERWISE NOTED OR APPROVED EQUIVALENT

ALL INTERIOR GYP. BD. WALLS TO BE 5/8" TYPE 'X' GYPSUM BOARD, TEXTURED WITH A MEDIUM LEVEL ORANGE PEEL AND PAINTED WITH ONE COAT ULTRA SPEC 500 WALL PRIMER 534 (1.1 MILS) AND TWO COATS INTERIOR PAINT SATIN A100 (1.6 MILS)

SEALED CONCRETE

CARPET TILE FLOORING BY PATCRAFT AS NOTED ON PLANS

LUXURY VINYL TILE BY PATCRAFT AS NOTED ON PLANS

PORCELAIN TILE IN WET AREAS (RESTROOMS AND MOP ROOM)

ALL INTERIOR SIGNAGE TO BE ADA COMPLIANT. STANDARD SIGNAGE AT EACH ENTRANCE, AND INTERIOR ROOM.

EXTERIOR SIGNAGE TO BE FROM TEXAS CUSTOM SIGNS OR APPROVED EQUAL

SIGNAGE

PRIME AND PAINT ALL EXPOSED METAL, CONDUIT, PLYWOOD PANELS (TYP)MISC

CONSTABLE

103

EVIDENCE

104

LOBBY

102

FOYER

101

MEN

106

MOP

107

WAIT/SECURITY

108

WOMEN

110

STORAGE

109

CONFERENCE

112

CONFERENCE

113

ELEC

111

COURT

114

COURTROOM

115

CLERKS

121

IT

122

COORIDOR

123

STORAGE

124

OPEN/FUTURE VOTING

130

JUDGES CHAMBER

120

STORAGE

118CLOSET

119

AV

117

JURY/TRAINING

116BREAKROOM

126

RISER

127

ADA RR

129

RR

128

CORRIDOR

125

CONSTABLE

105

SEALED CONCRETE (SC-1)

CARPET TILE (CT-1)

LUXURY VINYL TILE (LVT-1)

PORCELAIN TILE (PT-1)

ROOM FINISH LEGEND

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:1

1 A

MA103

PART

ITIO

N TY

PE A

ND F

INIS

HES

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1" = 10'-0"1

PARTITION PLAN

1 1/2" = 1'-0"3

PONY WALL DETAIL (TYP)

FINISH MATERIALS

Code Material Manufacturer Size Style/Color Comments

PT-1 PORCELAIN TILE TBD 12x12 TBD

PTD-1 PAINT SHERWIN WILLIAMS - TBD

PTD-2 PAINT SHERWIN WILLIAMS - TBD TRIM

SC-1 SEALED CONCRETE TBD - TBD

TB-1 TILE BASE TBD 4x12 TBD

RB-1 RUBBER BASE ROPPE 1x4 TBD

LVT-1 LUXURY VINYL TILE PATCRAFT TBD TBD

CT-1 CARPET TILE PATCRAFT TBD TBD

1" = 10'-0"2

FLOOR FINISH PLAN

Room Schedule

Number NameFloorFinish

BaseFinish

WallFinish Ceiling Finish

CeilingHeight Comments

101 FOYER LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

102 LOBBY LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

103 CONSTABLE CT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

104 EVIDENCE SC-1 RB-1 PTD-1 2X2 ACT 9' - 0"

105 CONSTABLE CT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

106 MEN PT-1 TB-1 PTD-1 GYP BD 9' - 0"

107 MOP SC-1 TB-1 PTD-1 2X2 ACT 9' - 0"

108 WAIT/SECURITY LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

109 STORAGE SC-1 RB-1 PTD-1 2X2 ACT 9' - 0"

110 WOMEN PT-1 TB-1 PTD-1 GYP BD 9' - 0"

111 ELEC LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

112 CONFERENCE CT-1 RB-1 PTD-1 GYP BD 9' - 0"

113 CONFERENCE CT-1 RB-1 PTD-1 GYP BD 9' - 0"

114 COURT LVT-1 RB-1 PTD-1 GYP BD 12' - 0"

115 COURTROOM LVT-1 RB-1 PTD-1 GYP BD 12' - 0"

116 JURY/TRAINING LVT-1 RB-1 PTD-1 GYP BD 9' - 0"

117 AV LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

118 STORAGE LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

119 CLOSET LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

120 JUDGES CHAMBER CT-1 RB-1 PTD-1 GYP BD 9' - 0"

121 CLERKS CT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

122 IT LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

123 COORIDOR LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

124 STORAGE LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

125 CORRIDOR LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

126 BREAKROOM LVT-1 RB-1 PTD-1 2X2 ACT 9' - 0"

127 RISER SC-1 RB-1 PTD-1 OPEN TO DECK 9' - 0"

128 RR PT-1 TB-1 PTD-1 GYP BD 9' - 0"

129 ADA RR PT-1 TB-1 PTD-1 GYP BD 9' - 0"

130 OPEN/FUTURE VOTING LVT-1 RB-1 PTD-1 GYP BD 9' - 0" 8 18

GENERAL NOTE:

ALL NEW FULL HEIGHT WALLS TO BE SUPPORTED TO STR @ 4'-0" O.C. IF PERPENDICULAR WALL NOT PRESENT. RE: 20/A501

Page 10: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

FINISHED FLOOR0' - 0"

EXISTING EAVEHEIGHT

15' - 0"

1

A301

42' - 7" 8' - 0" 1' - 1" 4' - 6 1/2" 3' - 3" 3' - 6" 3' - 3" 4' - 6 1/2" 1' - 0" 8' - 0" 3' - 4" 2' - 10" 6' - 6 1/2" 3' - 0" 20' - 3 1/2"

2' -

0"

6' -

0"

AWNING EAVEHEIGHT

9' - 0"

3' -

6"

3:12

4:12 4:12

EXISTING AWNING

4' -

0"

4' -

0"

GEN STONE MANUFACTURED STONE NEW METAL ROOF - MATCH EXISTING

2" GEN STONE MANUFACTURED LEDGER - FOLLOW MANUF RECOMMENDATIONS FOR

INSTALLATION

14' - 4"

NEW GENSTONE PRE MANUFACTURED STONE TO REPLACE DEMOED STONE

6" BOLLARD (4 TOTAL)

EXISTING WALL PANELS

FINISHED FLOOR0' - 0"

EXISTING EAVEHEIGHT

15' - 0"

1

A301

EXISTING METAL ROOFEXISTING METAL PANEL WALLS

AWNING EAVEHEIGHT

9' - 0"

3:12

2' -

4"

EXISTING WOOD PONY WALLNEW GEN STONE WAINSCOT WALL GENSTONE PRE MANUFACTURED STONE WRAPPED WALL (BEYOND)

8' -

5"

4' - 10" 15' - 9"

EXISTING STAIRS, RAMP AND RAILING TO REMAIN

EXISTING AWNINGRELOCATED EXPANDED METAL GUARD

EXISTING AWNING

EXISTING AWNING

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

3/16" = 1'-0"

9/2

/202

1 1

0:3

8:1

2 A

MA201

ELEV

ATIO

NS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

3/16" = 1'-0"1

South

3/16" = 1'-0"2

North

9 18

Page 11: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

FINISHED FLOOR0' - 0"

EXISTING EAVEHEIGHT

15' - 0"

2

A301

3:12

2:12 2:12

3:12

EXISTING RAMP

EXISTING HVAC MEZZANINE (NO WORK)

EXISTING HVAC MEZZANINE

8' -

5"

8' -

8"

10' - 0"

6' - 7" 2' - 0"

2'-0" EXTENSION

NEW METAL ROOF - MATCH EXISTING

NEW RAILING AROUND MEZZANINE

EXISTING WOOD FENCE ENCLOSURE

7' - 5"

NEW 6" BOLLARD (1 OF 4)

EXISTING FENCE AND GATE

FINISHED FLOOR0' - 0"

EXISTING EAVEHEIGHT

15' - 0"

2

A301

AWNING EAVEHEIGHT

9' - 0"

2:122:12

3:12

45' - 8" 3' - 0" 1' - 10" 3' - 0"1' - 9 1/4" 14' - 9"

3:12

2' - 0" 6' - 7"

2'-0" EXTENSION WITH NEW RAILING

REPLACE STONE WITH GEN STONE WALL TO MATCH GEN STONE WAINSCOT

NEW PRIVACY WALL WRAP WITH GEN STONE MANUFACTURED STONE PANELS

8' -

0"

SIGNAGE BY TEXAS CUSTOM SIGNS OR APPROVED EQUAL

6" BOLLARD

EXISTING GATE AND FENCE

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

3/16" = 1'-0"

9/7

/20

21

1:5

5:2

8 P

MA202

ELEV

ATIO

NS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

3/16" = 1'-0"1

East

3/16" = 1'-0"2

West

10 18

Page 12: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

Bell CountySalado Annex

2

A203

0' - 4" 8' - 0" 0' - 4"

1' -

6"

4' -

0"

1' -

7"

1/4" STEEL PLATE W/ 4 BOLTS - 2" STANDOFF FROM BACK PLATE - FINISH TO BE SEALED GLOSSY BLACK ON ALL SIDES

1/2" X 6" HILTI SNCHORS SET INTO STONE

0' -

6"

2' -

10

"0

' -

4"

2' -

10

"0

' -

7"

1' -

0"

1' - 0"

11057 Event Dr

1' - 0"3' - 10"0' - 4"3' - 10"1' - 0"

PLASMA CUT LETTERING - FONT TO BE DETERMINED BY OWNER

0' -

4"

0' - 4"

1' -

7"

4' -

0"

1' -

6"

0' - 2"

1/2" X 6" HILTI ANCHORS SET INTO STONE (TYP OF 8)

0' - 2"

1/2" X 8" HILTI ANCHORS SET INTO STONE (TYP OF 4)

0' - 4"

0' -

4"

0' -

4"

0' - 4"

2' -

10

"0

' -

4"

2' -

10

"

4' - 10" 0' - 4" 4' - 10"

10' - 0"

6' -

0"

1' - 2" 7' - 8" 1' - 2"

1' -

2"

3' -

8"

1' -

2"

0' -

3 1/

8"

1/4" STEEL PLATES - 3 BOLTS EACH W/ 2" STANDOFF FROM SMOOTH FACE OF STONE.

0' - 4"

0' -

4"

0' - 4"

0' -

4"

0' - 4"

ALIGN INSIDE HOLE FOR BOLTS WITH TOP STEEL PLATE

0' -

3 1/

8"

Scal

e:

Project No.

Dat

e:

Dra

wn

By:

Che

cked

By:

Sheet No.

Proj

ect T

itle:

Dra

win

g Ti

tle:

Cop

yrig

ht C

202

1M

RB

Gro

upAl

l Rig

hts

Res

erve

d

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:5

5:5

2 A

MA203

ROAD

SIG

NAGE

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1/2" = 1'-0"1

ROAD SIGNAGE 1/2" = 1'-0"2

ROAD SIGNAGE SECTION

1" = 1'-0"3

BACK PANELS

11 18

Page 13: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

FINISHED FLOOR0' - 0"

2

A301

COURTROOM

115

CLERKS

121

LOBBY

102

2:122:12

NEW METAL ROOF - MATCH EXISTING

GEN STONE MANUF STONE PANELS

INFILL AT ALL DOOR/WINDOW HOLES

8' -

5"

FINISHED FLOOR0' - 0"

1

A301

EXISTING METAL ROOF

OPEN/FUTURE VOTING

130

JUDGES CHAMBER

120

COURTROOM

115

COURT

114 WAIT/SECURITY

108

A302

2MOUNT TO FLOOR USING L-BRACKETS

9' - 9"

4' -

0"

PONY WALL

4

A102

1 1/2" TUBE STEEL -WELD AND GRIND ALL JOINTS. MOUNT 32" MIN ABOVE RAMP FLOOR

4"

ALL WALLS TO EXTEND 4" ABOVE CEILING HEIGHT - BRACE

UNSUPPORTED WALLS - RE: 19/A501

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

3/16" = 1'-0"

9/2

/202

1 1

0:3

8:1

4 A

MA301

BUIL

DING

SEC

TION

S

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

3/16" = 1'-0"1

Section 1

3/16" = 1'-0"2

Section 2

12 18

Page 14: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

METAL ROOF TO MATCH EXISTING MATERIAL ON ROOF SHEATHING ON 6" Z PURLINS SPACED @ 24" O.C. WITH 3/4" HARDI PANEL SOFFIT WHERE EXPOSED

GEN STONE PRE MANUFACTURED STONE ON EXTERIOR SHEATHING ON 6" STRUCTURAL METAL STUD SPACED 16" O.C. WITH 5/8" GYPSUM BOARD ON INTERIOR

BASE AS SCHEDULED

CEILING AS SCHEDULED

R-15 BATT INSULATION

R-38 SPRAY FOAM INSULATION

0' -

5"

3' - 6"

SEE STRUCTURAL FOR FOOTING DETAILS

METAL FASCIA CONNECTED TO END CHANNEL - INSTALL PER MANUF RECOMMENDATIONS

ANCHOR BOLT

HARDI SOFFIT

EXISTING EXTERIOR WALL

1 1/4" GEN STONE MANUFACTURE STONE PANELS OR APPROVED EQUAL

METAL FLASHING AS REQ'D

2" GEN STONE MANUFACTURED LEDGER -FOLLOW MANUF RECOMMENDATIONS FOR INSTALLATION

3' -

9"

0' -

3 1

/2"

A501

13

CONT. METAL FLASHING TO MATCH WALL PANEL PROFILE - CAULK ALL JOINTS

STANDING SEAM METAL ROOF TO MATCH EXISTING MATERIAL ON ROOF SHEATHING ON 5 1/2" Z PURLINS SPACED @ 48" O.C. WITH 3/4" HARDI BOARD SOFFIT

EXISTING EXTERIOR WALL - REPAIR IF DAMAGED DURING CONST. (TYP)

EXISTING ROOF

6" C-CHANNEL - INSTALL BLOCKING BEHIND AND BOLT THROUGH @ 24" O.C.

R-38 SPRAY FOAM INSULATION

EXISTING GUTTER AND DOWNSPOUT -NO WORK

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:1

5 A

MA302

WAL

L SE

CTIO

NS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1 1/2" = 1'-0"1

FOYER WALL SECTION1 1/2" = 1'-0"

2STONE WAINSCOT WALL

1" = 1'-0"3

ROOF CONNECTION TO BUILDING

13 18

Page 15: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

LOBBY

102

1' - 8"17' - 10"1' - 8"

9

A501

2' -

10

"

2' - 0"4' - 9"2' - 0"4' - 9"2' - 0"2' - 3"

2' -

10

"4

' -

2"

1' - 0"4' - 2"4' - 1"4' - 1"4' - 2"2' - 0"

18

A501

LOBBY

102

1' - 0"

1' - 8" 3' - 10" 1' - 1"

9

A501

1' - 8" 2' - 0" 2' - 11"

18

A501

2' -

10

"4

' -

2"

LOBBY

102

1' - 8" 4' - 1" 4' - 2" 1' - 8"

9' - 11" 1' - 8"

2' - 1" 2' - 0" 4' - 0" 2' - 0" 1' - 6"

9

A501

18

A501

2' -

10

"4

' -

2"

BREAKROOM

126

3

A501

4

A501

1

A501

4' - 2 1/16" 3' - 0" 2' - 9" 3' - 0" 1' - 9"

7

A501

8

A501

2' -

10

"

JURY/TRAINING

116

2' - 6" 2' - 9" 1' - 3"

1

A501

4

A501

3

A501

2' -

10

"

COURTROOM

115

3/4" WOOD MOULDING -SPACED EVENLY ON 1/2" WOOD PANEL

MOUNT TABLES USING L BRACKETS ALL SEATING BY OWNER

COURTROOM

115

32' - 0 1/8"

12' - 7 1/2" 0' - 10"0' - 10" 12' - 7 1/2"

0' -

6"

2' -

0"

0' -

6"

3' -

0"

2' - 1 1/2"2' - 0"

1/2" WOOD PANEL W/ 2' - 0" X 2' - 0" MOULDING SPACED EVENLY

USE L BRACKETS TO MOUNT TABLES TO FLOOR -

COURTROOM

115

MOUNT TABLES USING L BRACKETSALL SEATING BY OWNER

BAILIFF DESK

11"

COURTROOM

115

2' -

0 1

/2"

2' - 0"2' - 1 1/2" 1' - 1 1/2" 2' - 9" 1' - 1 1/2" 2' - 1 1/2"

2' -

0"

0' -

9"

4" 7' - 1" 4"

7' - 9"

RAMP (ADA)

6" AFF

1/2" WOOD PANEL WITH WOOD MOULDING SPACED EVENLY

3' -

6"

3' -

0"

1' - 6"

AV

117

CLOSET

119

7' - 0 1/8" 1' - 0"

2X4 FRAMING WITH 1/2" PLYWOOD

FIXED CLOSET SHELF AND CLOTHES RACK

1' - 6"

6' -

0"

0' -

4"

BASE AS SCHEDULED - BEYOND

6

A501

1' - 3"2' - 9"

5

A501

2' -

10

"

3' - 0"3' - 0"3' - 0"3' - 0"

2' -

10

"1

' -

8"

2' -

6"

4

A501

7

A501

18" DEEP - 3/4" PLYWOOD SHELVING; FLOOR TO

CEILING @ 24" O.C.

HEAVY DUTY STEEL BRACKETS TO BE SPACED EVENLY

18" DEEP - 3/4" PLYWOOD SHELVING; FLOOR TO CEILING @ 24" O.C.

HEAVY DUTY STEEL BRACKETS TO BE SPACED EVENLY

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:1

6 A

MA401

INTE

RIOR

ELE

VATI

ONS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1/4" = 1'-0"1

LOBBY - NORTH1/4" = 1'-0"

2LOBBY - EAST

1/4" = 1'-0"3

LOBBY - WEST

1/4" = 1'-0"6

BREAKROOM - EAST1/4" = 1'-0"

7JURY/TRAINING - WEST

1/4" = 1'-0"10

COURTROOM - NORTH

1/4" = 1'-0"11

COURTROOM - EAST1/4" = 1'-0"

12COURTROOM - SOUTH

1/4" = 1'-0"13

COURTROOM - WEST

3/8" = 1'-0"14

RAISED FLOOR SECTION

1/4" = 1'-0"8

BAILIFF DESK - NORTH

14 18

1/4" = 1'-0"9

CLERKS - NORTH

3/8" = 1'-0"4

EVIDENCE ROOM - EAST 3/8" = 1'-0"5

EVIDENCE ROOM - SOUTH

Page 16: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

WH

A402 6

A402

8

5

A8

A7

A4

A2

A9 A10

A5

A3

A1

A6

A6

A3

A1A9

A2

A4

A5

4

7 9

A11

1' -

0"

2' -

0"

4' -

0"

1' -

0"

3' - 6"

4' -

0"

1' -

0"

2' -

0"

1' -

10

"

1' - 6"

3' -

6"

1' -

9"

1' -

6"

A40210 12

11

A1 A2

A1

A2

A2

A2

A2

A3

A3 A4

A4

A4

A4

A4

A5

A6A

A7

A8

A9

A9

A9

A9

A9

A11

2' - 0"1' - 0"

1' -

0"

4' - 0"

3' -

6"

1' -

6"

2' - 0"1' - 0"

2' - 0"1' - 0"

2' - 0"1' - 0"

2' - 0"1' - 0"

2' - 0"1' - 0"

2' -

6"

1' -

0"

5' -

0"

3' -

1"

3' -

1"

3' -

1"

3' -

3"

5' - 6"

A402 1513

14

16

A1

A2

A2

A3

A3

A5

A6A

A7

A8

A9

A9

A10

A10

A10A11

4' - 0"

3' -

6"

1' -

6"

3' - 0"

3' - 0"

1' -

6"

1' -

6"

2' - 0"1' - 0"

0' -

9"

3' - 4"

5' -

2"

3' -

1"

4' -

4"

2' -

6"

2' -

9"

5' - 6"

A1

A2

A3

A4

A5

A6

A6A

A7

A8

A9

A10

A11

ACCESSORIES LEGEND

INSTALL AT EACH RESTROOM LAVATORY AS SHOWN ON PLANS 1. MODEL NUMBER: GEORGIA PACIFIC COMMERCIAL MODEL 59462

EACH RESTROOM TOILET1. MODEL NUMBER: BOBRICK B-2890

INSTALL AT EACH LAVATORY AS SHOWN ON PLANS1. MODEL NUMBER: BOBRICK B-2111 OR EQUAL

EACH UNI-SEX RESTROOM1. MODEL NUMBER: BOBRICK B-270

PORCELAIN WALL-MOUNT (ADA)1. INSULATE HOT WATER SUPPLY AND DRAIN

RE: MEP

INSTALLED 24" X 36" BEVELED FRAME OVER WALL MOUNTED LAVATORY1. MODEL NUMBER: BOBRICK B-290 OR APPROVED EQUAL - CONFIRM WITH

OWNER PRIOR TO INSTALLATION2. DESCRIPTION: BEVELED FRAME EDGE GALVANIZED STEEL BACK WITH

SLOTS FOR MOUNTING SCREWS AND INTEGRAL SCREW-HEAD LOCK. BACK PROTECTED BY SHOCK-ABSORBING WATER-RESISTANT PADDING

3. INSTALL MIRROR AT 3'-4" AFF TO REFLECTIVE SURFACE

INSTALLED 72" X 48" BEVELED EDGE MIRROR - ADHERE TO WALL WHERE SHOWN1. MODEL NUMBER: BOBRICK B-290 OR APPROVED EQUAL2. INSTALL MIRROR AT 3'-4" AFF TO REFLECTIVE SURFACE

INSTALLED IN EACH ACCESSIBLE TOILET AS SHOWN ON PLANS1. MODEL NUMBER: BOBRICK B-68062. DESCRIPTION: 1-1/2" OUTSIDE DIA. X PLAN LENGTH, HORIZONTAL,

1-1/2" WALL CLEARANCE. TYPE 304 MINIMUM 18 GA. STAINLESS STEEL. CONCEALED SCREW ATTACHED MOUNTING AND ANCHORAGE. NO.4 SATIN FINISH. MINIMM 900 POUND SUPPORTING CAPACITY

EACH UNI-SEX, MOUNT TO DOOR (ADA)1. MODEL NUMBER BOBRICK B-6722. MOUNT @ 48" AFF MAX.

INSTALLED IN EACH UNISEX AND PARTITIONED RESTROOM - CENTERLINE 16" FROM WALL AT ALL ADA RESTROOMS1. MODEL NUMBER: RE: MEP

1. MODEL NUMBER: RE: MEP

INSTALL IN EACH ACCESSIBLE RESTROOM AS SHOWN ON PLANS1. MODEL NUMBER: BOBRICK KB110-SSWM

PAPER TOWEL DISPENSERTOUCHLESS

TOILET TISSUE DISPENSER

SOAP DISPENSER

SANITARY NAPKIN DISPOSAL

SINK

SMALL MIRROR

LARGE MIRROR

42" GRAB BAR

36" GRAB BAR

ADA COMPLIANT FLOOR MOUNTED TOILET

ADA COMPLIANT WALL MOUNTED URINAL

BABY CHANGING STATION WALL MOUNTED

A8A9

A7

A4

A2A11

2

A501

2' - 0"

3' -

0"

3' - 0"

A6A1A3

A10

A5

2' -

10

" A2

A4

3' -

0"

2' - 0"

A9

A5

A6

A1

2

A5014' -

0"

6' - 0"

7' - 0"

A1 A3

A6A

A5

A11

2' -

10

"

A1

A3

A9

2

A501

6' - 0"

4' -

0"

7' - 0"

A3 A6A

A5

A11

2' -

10

"

A3

A1

A10

A9

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:1

7 A

MA402

ENLA

RGED

PLA

NS A

ND A

CCES

SORI

ES

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

3/8" = 1'-0"1

ENLARGED SINGLE RESTROOMS3/8" = 1'-0"

2ENLARGED WOMEN'S RR

3/8" = 1'-0"3

ENLARGED MEN'S RR

1/4" = 1'-0"5

ADA RR - NORTH

1/4" = 1'-0"4

ADA RR - WEST1/4" = 1'-0"

6ADA RR - EAST

1/4" = 1'-0"7

RR - WEST1/4" = 1'-0"

8RR - NORTH

1/4" = 1'-0"9

RR - EAST

1/4" = 1'-0"10

WOMENS RR - WEST1/4" = 1'-0"

11WOMENS RR - NORTH

1/4" = 1'-0"12

WOMENS RR - EAST1/4" = 1'-0"

13MENS RR - WEST

1/4" = 1'-0"14

MENS RR - NORTH

1/4" = 1'-0"15

MENS RR - EAST1/4" = 1'-0"

16MENS RR - SOUTH

15 18

PARTITION NOTE:

ALL PARTITIONS TO BE P-LAM W/ CEILING AND FLOOR MOUNTS AS SHOWN

Page 17: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

KNEE SPACE CLEAR AREA

TILE WALL WHERE EXPOSED

BASE AS SCHEDULED

1/2" SOLID SURFACE COUNTERTOP ON 3/4" WATER RESISTANT PARTICLE BOARD OR MDF, EASED EDGES, TYP

0' -

9"

0' -

1 1

/2"

0' - 8"

1' -

6"

0' - 11"

0' -

2 1

/2"

0' - 3"

PULL AS SPECIFIED

P-LAM ON 3/4" MDF DOOR

FULLY CONCEALED 170° OPENING HINGES

P-LAM BASE - ATTACH TOE KICK TO DOOR

INSULATE ALL EXPOSED PIPES

UNDERMOUNT SINK, RE: MEP

EXTEND FLOORING AS SCHEDULED UNDER SINK AREA

2' -

10

"

2' - 0"

2' - 0"

DOUBLE BEVELED EDGE

0' -

10

"

2' -

3"

0' -

2"

P-LAM CABINETRY

TILE

BASE AS SCHEDULED

REQ'D CLEAR AREA

SOLID SURFACE COUNTERTOP

2' -

10

"

4"

1'-1

1"

5"

BASE AS SCHEDULED

SOLID SURFACE COUNTERTOP

DOUBLE BEVELED EDGE

P-LAM FACE

P-LAM CABINETRY

1/2" ADJ. SHELF

2' -

10

"

2' - 0"

1/2" MELAMINE ADJ. SHELF

P-LAM DOORS

2' -

6"

RE

FE

R T

O E

LE

V.

1' - 2"

2 SCREW HANDLE (TYP @ CASEWORK)

LAMINATE DOORS1

' -

0"

RE

FE

R T

O E

LE

V.

1' - 2"

CONT. SEALANT,BOTH SIDES.

METAL STUD WALL FRAMING W/ BATT INSULATION

5/8” GYP. BD.

HOL. MTL. FRAME, PAINT

DOOR AS SCHED.

EXISTING METAL BUILDING

0' - 1"

GENSTONE LEDGER CAP

MTL FLASHING, CAULK ALL JOINTS

EXISTING METAL BUILDING

3 1

/2"

2"

STOREFRONT WINDOW AS SCHEDULED -FLASH & CAULK WINDOW PER MANUF. RECOMMENDATIONS

CONTINUOUS CAULK AT ALL JOINTS

5/8" GYP. BD. (TYP.)

1x WOOD TRIM SILL, TYP. ALL WINDOWS, PRIME & PAINT

R-15 BATT INSULATION, TYP. AT WALLS

EXISTING METAL BUILDING

5/8" GYP. BD. WALL FINISH AS SCHED.

3 5/8" METAL STUD

CONT. SEALANT, BOTH SIDES

HM. FRAME, PAINT

DOOR AS SCHED.

BASE AS SCHEDULED

TEMPERED GLASS

VERTICAL SUPPORT

BRACKET

5/8' GYP. BD ON3 5/8" MTL STUD, ACHOR TO CONC. 48" OC.

2' -

10

"2

"

1' - 8"

LOBBY CONSTABLE

3/4" PLYWOOD CASED OPENING FOR WINDOW

3"

10

"

10

" 2' - 0"

(3) GROMMETS (MIN) @ EACH DESK, CONTRACTOR TO COORDINATE LOCATION WITH OWNER

DRAWER BEYOND

P-LAM FACE

SOLID SURFACE COUNTERTOP

1' - 8"

2' -

10

"

DOUBLE BEVELED EDGE

0' - 2 1/2"

0' - 3" 1' - 2 1/2"

0' -

3"

1 1/2" TUBE STEEL LEGS WITH END CAPS AND 1X1

BRACE - FULLY WELD AND GRIND ALL JOINTS

1/2" SOLID SURFACE COUNTERTOP ON

3/4" PLYWOOD.

SOLID SURFACE COUNTERTOP

1/2" ADJ. SHELF

P-LAM DOORS

BASE AS SCHEDULED

0' -

4"

1' -

11

"0

' -

7"

2' - 0"

2' -

10

"

4"

45.0

BOX HEADER

CEILING AS SCHEDULED (ACT GRID DOES NOT QUALIFY AS BRACING)

(2) SCREWS

STRUCTURE ABOVE

ANGLE BRACE AT ALTERNATE SIDES @ 48" MAX

12:1

2 SLO

PE

BEND STUD AND CONNECT TO ROOF JOIST W/ (2) #10 SCREWS SPACED 1" APART MIN

SOLID SURFACE COUNTERTOP

DOUBLE BEVELED EDGE

1 1/2" BULLNOSE TO WRAP AROUND WOOD PONY WALLS (TYP)

0' - 11"

2' -

10

"

GRANITE COUNTERTOP

2X STUD @ 16" O.C. MAX WITH 1/2" STAIN GRADE OAK PLYWOOD ON EACH SIDE WITH 3/4" MOULDING

2X FRAMING @ 16" O.C.E.W. MAX WITH 3/4" T&G (GLUE AND SCREW) PLYWOOD AND FLOORING AS SCHEDULED. (TYP @ RAISED DECK)

1' -

0"

3' -

9"

1 1/2" TUBE STEEL LEGS WITH END CAPS AND 1X1 BRACE @ 24" O.C. - FULLY WELD AND GRIND ALL JOINTS

10" 1 1/2"

1' - 2"

2' -

3"

1' -

2 1

/4"

10

"1

1/2

"

2"

2' - 0"

1' - 0"

SOLID SURFACE COUNTERTOP

DOUBLE BEVELED EDGE

1 1/2" BULLNOSE TO WRAP AROUND WOOD PONY WALLS (TYP)

1' - 8"

2' -

3"

3"

BASE AS SCHEDULED

TEMPERED GLASS

VERTICAL SUPPORT

BRACKET

5/8' GYP. BD ON 3 5/8" MTL STUD, ACHOR TO CONC. 48" OC.

2' -

10

"2

"

1' - 8"

LOBBY CLERKS

3/4" PLYWOOD CASED OPENING FOR WINDOW

3"

10

"

10

" 0' - 1"

2' -

10

"

SOLID SURFACE COUNTERTOP

DOUBLE BEVELED EDGE

P-LAM FACE0' -

5 1

/2"

2' -

3"

0' - 5" 1' - 7"

2' - 0"

SOLID SURFACE COUNTERTOP

1/2" ADJ. SHELF

P-LAM DOORS

BASE AS SCHEDULED

0' -

4"

1' -

11

"0

' -

7"

2' -

10

"

1' - 7"

2' - 0"

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:1

7 A

MA501

DETA

ILS

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

3/4" = 1'-0"1

CABINET DETAIL @ SINK (ADA -OPERABLE DOORS)

3/4" = 1'-0"2

CABINET DETAIL @ BATHROOM SINK(ADA)

3/4" = 1'-0"4

CABINET DETAIL ADA HEIGHT(TYP.)

3/4" = 1'-0"7

CABINET UPPERS (TYP.)3/4" = 1'-0"

8CABINET UPPERS - @ MICRO

1 1/2" = 1'-0"14

EXTERIOR DOOR HEADER (TYP)1 1/2" = 1'-0"

13EXTERIOR FLASHING DETAIL

1 1/2" = 1'-0"16

WINDOW HEADER & SILL DETAIL (TYP)

1 1/2" = 1'-0"15

INTERIOR DOOR HEADER (TYP)

3/4" = 1'-0"18

LOBBY PASS-THRU @ CONSTABLE

1" = 1'-0"9

SERVICE COUNTER ADA

3/4" = 1'-0"3

CABINET DETAIL - DRAWERS ADA @WALL

3/4" = 1'-0"19

UNSUPPORTED WALL BRACING (TYP)

3/4" = 1'-0"10

WITNESS STAND1" = 1'-0"

11DAIS

3/4" = 1'-0"12

COURTROOM CLERK

16 183/4" = 1'-0"

17LOBBY PASS-THRU @ CLERKS

3/4" = 1'-0"6

DESK W/ PONY WALL ADA3/4" = 1'-0"

5

CABINET DETAIL - DRAWERS ADA W/PONY WALL

Page 18: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

WH

WH

UP

DN

107

126

121

123

124

115

114

111

129

130

132

140

127

135

136

137

134

103

101102

E

EEE

E

E

BB

D

C

133

139

138

110

117

A

122

125

119

104

106

C

113

116

112

C

108

120

128109

105

CONSTABLE

103

EVIDENCE

104

LOBBY

102

FOYER

101

MEN

106

MOP

107

WAIT/SECURITY

108

WOMEN

110

STORAGE

109

CONFERENCE

112

CONFERENCE

113

ELEC

111

COURT

114

COURTROOM

115

CLERKS

121

IT

122

COORIDOR

123

STORAGE

124

OPEN/FUTURE VOTING

130

JUDGES CHAMBER

120

STORAGE

118CLOSET

119

AV

117

JURY/TRAINING

116BREAKROOM

126

RISER

127

ADA RR

129

RR

128

CORRIDOR

125

CONSTABLE

105

118

141

F.F.

6' -

8"

6' - 0"3' - 0"

6' -

8"

3' - 0" 6' - 0"

6' -

8"

2' - 6"

6' -

8"

1 2 3 4 5 6 7 8

3' - 0"

3' -

0"

4' - 0"

7' -

0"

9

6' -

8"

6' - 0"

STAINED PLYWOOD DOOR AND TRIM TO MATCH ADJ. WALLS

DOOR TYPES

6' -

8"

6' -

8"

3' - 0"

F.F.2' -

0"

6' -

0"

10' - 0" 4' -

0"

4' -

0"

8' - 0" 5' - 0" 2' - 0"

5' -

0"

3' -

0"

4' -

2"

2' -

10

"

A B C D

WINDOW TYPES3' - 3" 3' - 6" 3' - 3"

E

4' -

0"

4' -

0"

3' - 0"

0' -

10

"0

' -

10

"

Type Count Width Height Manufacturer Head Height Comments

A

B

C

D

1

2

3

6

10' - 0"

8' - 0"

5' - 0"

ALL UNMARKED WINDOWS ARE EXISTING

Window Schedule

PELLA

PELLA

6' - 0"

4' - 0"

5' - 0"

8'- 0"

8'- 0"

8'- 0"PELLA

FIXED

FIXED

FIXED W/ ONE WAY GLASS

SERVICE COUNTERE

2

3' - 0" 4' - 0"

8'- 0"PELLA FIXED W/ ONE WAY GLASS

2' - 0" 4' - 2" 7'- 0"

CARD READ DOORS

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/7

/20

21

1:5

5:2

9 P

MA601

DOOR

/WIN

DOW

SCH

EDUL

ES

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1/8" = 1'-0"1

DOOR/WINDOW PLAN

17 18

Page 19: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

EXISTING BUILDING. NO NEW SLAB NEEDED

NEW FOYER

1' -

0"

8' -

0"

8' - 0 1/2"1' - 0"8' - 0 1/2"

2

S101

3

S101

4

S101

1' - 0"

0' -

5"

(2) #6 REBAR - BOTTOM CONTINUOUS

TYP. 8 MIL. POLY

6" COMPACTED SAND OR CRUSHER FINES

STIRRUPS #3 - 48" O.C.

(2) #5 REBAR - TOP CONTINUOUS

#3 @ 12" O.C. EACH WAY IN SLAB

0' -

3"

CONTINUOUS VAPOR BARRIER

2:12 SLOPE MAX

4" CONCRETE FLAT WORK W/ 6X6 W2.9 X W2.9 W.W.F.

6" COMPACTED SAND OR CRUSHER FINES

1' - 0"

MIN

2' -

6"

0' -

5"

#3 REBAR STIRRUP@ 48" O.C.

TYP. 8 MIL. POLY

0' -

3"

(2) #6 REBAR

(2) #5 REBAR - TOP CONTINUOUS#3 REBAR @ 12" O.C.E.W.CENTER OF SLAB

(START 5" FROM EDGE)FINISH SLAB

CONTINUOUS VAPOR BARRIER

GENERAL NOTES:

1. REMOVE UPPER 3' OF EXPANSIVE CLAY OR TO TOP OF LIMESTONE

2. BEAM DEPTH CAN BE REDUCED UP TO 24" MIN. WHEN UNIFORMLY BEARING ON LIMESTONE BEDROCK, ANGLE/CUT STIRRUPS TO FIT

6" COMPACTED SAND OR CRUSHER FINES

1' - 0"

MIN

2' -

6"

0' -

5"

#3 REBAR STIRRUP@ 48" O.C.

TYP. 8 MIL. POLY (2) #6 REBAR

(2) #5 REBAR - TOP CONTINUOUS

#3 REBAR @ 12" O.C.E.W.CENTER OF SLAB(START 5" FROM EDGE)

FINISH SLAB

CONTINUOUS VAPOR BARRIER

1' - 3"

#3 DOWELS x 1'-3" LONG DRILL 3" INTO EXIST

CONCRETE AND ANCHOR WITH HILTI HY-200 ADHESIVE

ELEMENT

FOOTINGS, CAISSONS (DRILLED SHAFT)

INTERIOR SLAB ON GRADE

EXTERIOR SLABS

FILL CONCRETE

28 DAY STRENGTH

4000 PSI

4000 PSI

4000 PSI

2000 PSI

AIR CONTENT

1-3%

1-3%

6-8%

-

COURSE AGGREGATE

ATSM #56

ATSM #56

ATSM #56

ATSM #67

MAX SLUMP

3"

3"

3"

4"

NOTES

A, B, C, D, E, F

A, C, F, G

NOTES:

A. USE TYPE II CEMENT.B. A VIBRATORY SCREED SHALL BE USED FOR ALL THESE SLABS. THIS REQUIREMENT

MAY BE RELAXED (AS APPROVED BY STRUCTURAL ENGINEER), IF A HRWR IS USED.C. MIXING WATER FOR THIS CONCRETE SHALL BE LIMITED TO 250 LBS. PER CUBIC

YARD. WORKABILITY SHALL BE OBTAINED BY METHODS OTHER THAN THE ADDITION OF WATER.

D. A GRADATION ANALYSIS OF THE COARSE AGGREGATE SHALL BE SUBMITTED WITH THE MIX DESIGN. A MINIMUM OF 5% SHALL BE RETAINED ON A 1" SIEVE.

E. A GRADATION ANALYSIS OF THE COARSE AGGREGATE SHALL BE SUBMITTED WITH THE MIX DESIGN. A MINIMUM OF 5% SHALL BE RETAINED ON A 3/4" SIEVE.

F. SLUMP LIMIT MAY BE RELAXED WITH USE OF A HIGH RANGE WATER REDUCING ADD MIXTURE, IF APPROVED BY THE ENGINEER.

G. AIR CONTENT ON EXT. SLABS CAN BE REDUCED TO 4-5% IF BROOM FINISH IS NOT DESIRED.

STRUCTURAL NOTES

DESIGN LOADS1. GRAVITY LOADS

A. DESIGN UNIFORM SUPERIMPOSED DEAD LOADS ARE IN ADDITION TO THE WEIGHT OF THE BUILDING STRUCTURE.

B. DESIGN UNIFORM LIVE LOADS ARE AS LISTED BELOW. LIVE LOAD REDUCTIONS ARE CALCULATED IN ACCORDANCE WITH THE BUILDING CODE.

C. DESIGN CONCENTRATED LIVE LOADS ARE NOT COMBINED WITH UNIFORM LIVE LOADS.D. MECHANICAL AREAS ARE DESIGNED TO SUPPORT THE EQUIPMENT SHOWN ON THE

MECHANICAL DRAWINGS AND SPECIFICATIONS. ANY MODIFICATIONS TO THE SIZE, WEIGHT, OR LOCATION OF EQUIPMENT SHOULD BE SUBMITTED FOR REVIEW OF LOADING PRIOR TO INSTALLATION OF EQUIPMENT.a. DEAD LOADS

• ROOF: 3 PSF CEILING & MECH + 7 PSF ROOFINGb. LIVE LOADS

• OFFICE SPACE: 50 PSF• ROOF: 12 PSF MIN. TO 20 PSF (REDUCED BASED ON AREA AND PITCH)

FOUNDATION

REINFORCED CONCRETE AND FLOOR SLAB NOTES1. ALL CONCRETE WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST RELEVANT

AMERICAN CONCRETE INSTITUTE (ACI) CODES.

2. PROVIDE MIX DESIGN FOR REVIEW/APPROVAL BY ENGINEER OF RECORD BEFORE BEGINNING CONSTRUCTION. SUBMITTAL SHALL INCLUDE GRADATION ANALYSIS OF COARSE AND FINE AGGREGATE, AS WELL AS A STATISTICAL ANALYSIS OF AVERAGE COMPRESSIVE STRENGTH OF BATCH PLANT'S PREVIOUS FIELD RESULTS FOR SIMILAR TYPE OF CONCRETE.

3. ALL SLABS-ON-GRADE SHALL BE PLACED OVER A MINIMUM OF 8" COMPACTED NO. 1/2 CRUSHED STONE, UNLESS OTHERWISE NOTED. COMPACTION SHALL BE 95% OF MAX. DRY DENSITY IN ACCORDANCE WITH MODIFIED PROCTOR TEST.

4. DEPRESSED AND/OR SLOPING SLABS TO MAINTAIN FULL THICKNESS.

5. CONTRACTOR TO VERIFY THE LOCATION OF ALL FLOOR DEPRESSIONS, SLEEVES, AND FLOOR DRAINS WITH DRAWINGS PRIOR TO POURING FLOOR SLAB. VERIFY WITH E.C. THAT ALL ELECTRICAL CONDUITS ARE IN PLACE PRIOR TO POURING FLOOR SLABS.

6. G.C. TO COORDINATE WITH OTHER CONTRACTORS FOR LOCATION, SIZE, TYPE AND INVERT OF PENETRATIONS AND SLEEVES. SLEEVES FURNISHED BY OTHER CONTRACTORS SHALL BE INSTALLED BY G.C. FOR PENETRATIONS IN BEAMS LESS THAN 6" DIA., ADD (1) STIRRUP ON EA. SIDE OF PENETRATION. CONSULT ENGINEER FOR LARGER PENETRATIONS OR REBAR CONFLICT.

7. ALL CONSTRUCTION JOINTS ADDED FOR CONSTRUCTABILITY SHALL BE VERIFIED WITH THE STRUCTURAL ENGINEER IF NOT SPECIFICALLY SHOWN ON THE DRAWINGS.

8. REINFORCING STEEL SHALL CONFORM TO ASTM A-615, GRADE 60, U.N.O

9. REINFORCING STEEL, SPECIFICALLY NOTED TO BE SHOP OR FIELD WELDED SHALL CONFORM TO ASTM A-706, GRADE 60. WELDING OF OTHER REINFORCING STEEL IS NOT PERMITTED.

10. ALL REINFORCING SHALL HAVE MINIMUM LAP LENGTH AS FOLLOWS: #4 BAR-16", #5 BAR-24", #6 BAR-36" UNLESS OTHERWISE NOTED. HOOK CONTINUOUS BARS AT DISCONTINUOUS ENDS. TOP REINF. SHALL BE CONTINUOUS AT SUPPORTS AND LAP SPLICED AT MIDSPAN TYP.

11. LAP ALL REINFORCEMENT AT FOOTING/GRADE BEAM CORNERS/ENDS WITH #5 BENT CORNER BARS WITH 2'X2' LEGS U.N.O.

12. DETAILING OF CONCRETE REINFORCING AND ACCESSORIES SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ACI 315. SUBMIT REBAR SHOP DRAWINGS FOR REVIEW/APPROVAL BY ENGINEER OF RECORD PRIOR TO ORDERING REBAR.

13. UNLESS NOTED OTHERWISE, CONCRETE COVER FOR REINFORCING SHALL BE AS FOLLOWS:BEAMS AND WALLS ON EARTH = 2" SIDES AND TOP, 3" BOTTOMSLABS ON GROUND = CENTER IN SLAB, 2" MIN. ON EA. SIDE

14. NO HORIZONTAL JOINTS WILL BE PERMITTED IN CONCRETE, EXCEPT WHERE THEY NORMALLY OCCUR OR WHERE NOTED. VERTICAL JOINTS SHALL OCCUR AT OR NEAR CENTER OF SPANS.

15. NOTIFY THE CITY BUILDING OFFICIAL, THE SPECIAL INSPECTOR AND MRB GROUP AT LEAST 48 HOURS IN ADVANCE TO REVIEW THE FOUNDATION CONSTRUCTION BEFORE CONCRETE PLACEMENT.

16. NOTIFY CERTIFIED TECHNICIANS ACCORDING TO ACI 301 TO MONITOR AND TEST CONCRETE ACCORDING TO ACI 311.5R. TEST ACCORDING TO SPECIFICATIONS AND ACI REQUIREMENTS. REJECT OR ACCEPT CONCRETE BASED ON THE RESULTS OF TESTS. REPORT ALL TESTING PROMPTLY.

17. PLACE AND CURE CONCRETE ACCORDING TO ACI 302. IR. DO NOT USE CONCRETE THAT HAS NOT BEEN PLACED IN THE FORMS 1.5 HOURS AFTER THE INITIAL MIXING WATER WAS ADDED.

18. ALL EXPOSED INTERIOR CONCRETE AND EXTERIOR CONCRETE PADS AND SUPPORTS NOT TO BE PAINTED SHALL BE SEALED BY AN APPROVED PRODUCT, CONTRACTOR TO SUBMIT PRODUCT DATA TO ENGINEER FOR APPROVAL.

19. DESIGN MIXES TO PROVIDE NORMAL WEIGHT CONCRETE WITH THE FOLLOWING PROPERTIES:

GENERAL CONSTRUCTION NOTES1. SEE MECHANICAL DRAWINGS FOR EXACT LOCATION AND SIZES OF SMALL MECHANICAL

OPENINGS, SLEEVES, ETC. NOT SHOWN ON THE STRUCTURAL DRAWINGS.

2. REFER TO ARCHITECTURAL DRAWINGS FOR ALL FINISHES, DIMENSIONS OF SLAB DROPS, CHAMFERS, ETC.

3. THE USE OF REPRODUCTIONS OF THE DESIGN STRUCTURAL DRAWINGS FOR SHOP DRAWING PURPOSES IS NOT ACCEPTABLE.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING TEXAS 811 PRIOR TO ANY EXCAVATION OR SITE WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SUPPORT AND PROTECTION OF ALL UTILITIES EXPOSED AND SUPPORT SYSTEMS SHALL BE UTILIZED AS RECOMMENDED BY THE RESPECTIVE UTILITY OWNERS.

5. THE CONTRACTOR SHALL VERIFY, PRIOR TO CONSTRUCTION, THAT THE NEW STUCTURE WILL NOT CONFLICT WITH ANY EXISTING UTILITIES. IF CONFLICTS ARISE, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND SHALL STOP THE WORK UNTIL AN APPROPRIATE SOLUTION TO THE CONFLICTS ARE FOUND, AND THE CONTRACTOR IS GIVEN WRITTEN AUTHORIZATION TO PROCEED WITH THE WORK.

6. GC SHALL BE RESPONSIBLE FOR ANY TESTING SERVICES.

7. ALL AREAS OF SITE DISTURBED DURING CONSTRUCTION SHALL BE GRADED, TOPSOILED, PREPARED AND PERMANENTLY SEEDED AT THE END OF CONSTRUCTION, BY THE G.C., UNLESS OTHERWISE NOTED.

8. GC IS RESPONSIBLE FOR, THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, AND FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE CONSTRUCTION WORK; GC WILL BE RESPONSIBLE TO CARRY OUT THE CONSTRUCTION WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

9. SUBMIT PRODUCT INFO AND WARRANTIES.

10. INSTALL ALL PRODUCTS PER MANUFACTURERS RECOMMENDATIONS.

1. THE FOLLOWING CODES AND STANDARDS, INCLUDING ALL SPECIFICATION REFERENCED WITHIN, SHALL APPLY TO THE DESIGN, CONSTRUCTION, QUALITY CONTROL AND SAFETY OF ALL WORK PERFORMED ON THE PROJECT.

A. INTERNATIONAL BUILDING CODE 2018 (IBC 2018)

B. "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", AMERICAN SOCIETY OF CIVIL ENGINEERS, ASCE 7-16.

C. ADDITIONAL CODES FOR MATERIALS SHALL BE FOUND IN THE APPROPRIATE SECTIONS THAT FOLLOW. SEE THOSE SECTIONS FOR THE APPLICABLE CODES.

BUILDING CODES AND STANDARDS

4. SNOW LOADSA. GROUND SNOW LOAD = 5 PSF

SPECIAL INSPECTIONS (ATTENTION OWNER AND CONTRACTOR):

2. WIND LOADSA. IN ACCORDANCE WITH ASCE 7, RISK CATEGORY II, BASED ON A WIND SPEED OF 106 MPH

AND EXPOSURE CLASS B.B. INTERNAL PRESSURE COEFFICIENT = +/-0.18 (ENCLOSED BUILDING)

3. SEISMIC LOADSA. IN ACCORDANCE WITH ASCE 7, RISK CATEGORY II, SITE CLASS CB. SEISMIC DESIGN CATEGORY A, SS = 0.06 S1 = 0.039

1. THESE NOTES APPLY TO ALL FOUNDATIONS AND SLABS ON GRADE DETAILED ON THE STRUCTURAL DRAWINGS, UNLESS NOTED OTHERWISE.

2. ALL EXCAVATION, CONSTRUCTION, AND BACK FILL FOR CONCRETE FOOTINGS, FOUNDATIONS AND WALLS SHALL BE PERFORMED UNDER DRY CONDITIONS. CONTRACTOR TO PERFORM SHORING AND DEWATERING AS REQUIRED.

3. NO LOOSE, SOFT, WET, FROZEN OR OTHERWISE UNSUITABLE MATERIAL SHOULD BE LEFT IN PLACE BELOW FOUNDATIONS.

4. SUBGRADE PREPARATION UNDER BUILDING SLAB ON GROUND:A. REMOVE THE TOPSOIL, TREE ROOTS, VEGETATION, AND ANY WET, SOFT OR LOOSE

SOILS.B. EXCAVATE A MIN. OF 3'-0" (OR T/O LIMESTONE) FOR PLACEMENT OF SELECT FILL.

EXCAVATION SHALL EXTEND A MINIMUM OF 3' BEYOND THE BUILDING PERIMETER.C. PLACE A MINIMUM OF 3'-0" OF SELECT FILL OVER 1' MOISTURE-CONDITIONED SOIL PAD

UNDER AND AROUND EACH BUILDING PAD. THE SELECT FILL SHALL BE LAYER COMPACTED IN 8 INCH MAXIMUM LOOSE THICKNESS TO A DRY DENSITY OF NOT LESS THAN 95% OF STANDARD PROCTOR (ASTM D-698) MAXIMUM DRY DENSITY. THE SOIL MOISTURE AT TIME OF COMPACTION SHALL BE WITHIN 2% OF THE MATERIAL'S OPTIMUM MOISTURE CONTENT. PLACE SELECT FILL AS SOON AS POSSIBLE OVER SUBGRADE TO LIMIT MOISTURE LOSS WITHIN THE UNDERLYING SOILS.

D. SELECT FILL SHALL BE SM, SC, GM OR GC AS PER USCS AND SHOULD MEET THE CRITERIA DEFINED IN THE GEOTECH REPORT.

5. UNLESS SPECIFIED OTHERWISE, VAPOR BARRIER SHALL CONSIST OF 8 MIL POLYETHYLENE SHEET. TURN DOWN AT GRADE BEAMS AND PIERS. LAP AND SEAL AT ALL JOINTS AND AROUND ALL COLUMNS AND STUB-OUTS. PATCH ALL TEARS PRIOR TO PLACING CONCRETE.

1. PURSUANT TO SECTION 1704 OF THE INTERNATIONAL BUILDING CODE, WHERE APPLICATION IS MADE FOR CONSTRUCTION AS DESCRIBED IN THAT SECTION, THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS TO PROVIDE INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED UNDER SECTION 1704. THESE MAY INCLUDE, BUT NOT BE LIMITED TO:A. SOILS AND FOUNDATIONSB. CAST-IN-PLACE CONCRETEC. MASONRYD. WOOD CONSTRUCTION

2. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON AS PER SECTION 1704 OF THE INTERNATIONAL BUILDING CODE WHO SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE CODE ENFORCEMENT OFFICIAL, FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION.

3. THE OWNER SHALL REFER TO THE SCHEDULE OF STRUCTURAL SPECIAL INSPECTIONS AND SPECIFICATIONS INCLUDED IN THE PROJECT CONTRACT DOCUMENTS OR CONTACT MRB GROUP FOR THIS INFORMATION IF NOT PROVIDED.

4. ALL PREFABRICATED ITEMS SHALL BE MANUFACTURED BY APPROVED AND CERTIFIED SHOPS, AND INSPECTED AS REQUIRED PER SECTION 17 OF THE INTERNATIONAL BUILDING CODE.

5. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER'S TESTING AND SPECIAL INSPECTION REPRESENTATIVES.

MASONRY1. MASONRY WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST BUILDING CODE

REQUIREMENTS FOR MASONRY STRUCTURES (ACI-530)

2. UNLESS OTHERWISE NOTED, ALL MASONRY UNITS SHALL CONFORM TO ASTM C90, GRADE N, TYPE 1. ALL UNITS SHALL BE TWO CORE, NORMAL WEIGHT BLOCK, F'M=2000 PSI.

3. ALL MORTAR SHALL CONFORM TO ASTM C270, TYPE S, WITH A MINIMUM COMPRESSIVE STRENGTH OF 1,800 PSI @ 28 DAYS

4. GROUT FOR FILLING BLOCK CORES SHALL CONFORM TO ASTM C476, WITH A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI @ 28 DAYS, GROUT SHALL BE PLACED IN LIFTS NOT EXCEEDING 4 FEET IN HEIGHT, UNLESS OTHERWISE APPROVED BY THE ENGINEER.

5. UNLESS OTHERWISE NOTED, ALL MASONRY SHALL BE REINFORCED WITH A 9 GAUGE HORIZONTAL LADDER TYPE WIRE REINFORCING AT 16" O.C. HORIZONTAL REINFORCING SHALL BE GALVANIZED AS REQUIRED BY ACI 530. PROVIDE ADDITIONAL REINFORCING WITHING 8" OF OPENINGS AND DISCONTINUITIES. VERTICAL REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60. MINIMUM LAP LENGTHS: #4 BAR-24", #5 BAR-30"

6. A MINIMUM OF TWO BLOCKS (16" WIDE X 16" HIGH) SHALL BE FILLED SOLID WITH 3,000 PSI GROUT AT ALL LINTEL, BEAM AND COLUMN BEARING POINTS, UNLES SOTHERWISE NOTED ON PLANS.

7. WHERE INTERIOR MASONRY WALLS MEET OTHER INTERIOR OR EXTERIOR WALLS, PROVIDE A CONTROL JOINT WITH METAL STRAP ANCHORS BETWEEN WALLS.

8. PROVIDE VERTICAL REINFORCEMENT AT CORNERS OF ALL CMU WALLS, WITHIN 16" OF EACH SIDE OF OPENINGS AND WITHIN 8" OF CONTROL JOINTS.

9. PROVIDE CONTROL JOINTS AT 24" O.C. MAX.

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834

N. C

apita

l of T

exas

Hw

y, Su

ite 1

47, A

ustin

, TX

787

59Ph

one:

512-

436-

8571

303

W. C

alhou

n A

ve. T

empl

e, TX

765

01Ph

one:

254-

771-

2054

ww

w.m

rbgr

oup.

com

MR

B G

roup

, P.C

.

As indicated

9/2

/202

1 1

0:3

8:2

3 A

MS101

STRU

CTUR

AL P

LAN

0229.20001

SALA

DO A

NNEX

REN

OVAT

ION

1105

7 EV

ENT

DR.

SALA

DO, T

X.

9/1/

2021

AM

TMR

No.

Revisions and Descriptions

By

Date

1/4" = 1'-0"1

FOUNDATION PLAN

1/2" = 1'-0"2

PERIMETER GRADE BEAM W/ ADA RAMP1/2" = 1'-0"

3INTERIOR GRADE BEAM

1/2" = 1'-0"4

INTERIOR GRADE BEAM @ EXISTINGSLAB 16 16

Page 20: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

ASHRAE CO

700 PPM ---- 15 CFM/PERSON

500 PPM ---- 20 CFM/PERSON

350 PPM ---- 30 CFM/PERSON

C

C 1

2C

2DIFFERENTIAL

1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY ALL NATIONAL, STATE, AND LOCAL CODES

2. CONTRACT DRAWINGS FOR MECHANICAL WORK (HVAC, PLUMBING, AND FIRE PROTECTION) ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. IT IS THE CONTRACTORS RESPONSIBILITY FOR INSTALLING ALL MATERIALS PER SMACNA STANDARDS AND THE MANUFACTURER'S STANDARDS.

3.

4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON THE OTHER CONTRACT DRAWINGS.

5. WHEN TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURE SHALL BE USED.

6. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE LATEST EDITION NATIONAL ELECTRIC CODE AND DIVISION 16 (23) OF THE SPECIFICATION.

7. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

8. MECHANICAL EQUIPMENT, DUCTWORK, AND PIPING SHALL NOT BE SUPPORTED FROM METAL DECK.

9. LOCATION AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES.

10. PROVIDE REMOTE BALANCING DAMPERS SIMILAR TO 'YOUNG CONCEALED REGULATORS' FOR ALL TAPS MADE ABOVE INACCESSIBLE CEILINGS OR WALLS. FINISH CONCEALMENT COVERS PER ARCHITECTS RECOMMENDATIONS.

11. ALL AHU AND FCU FANS SHALL OPERATE CONTINUOUSLY DURING THE OCCUPIED MODE OF OPERATION WITH ASSOCIATED OUTSIDE AIR MOTORIZED DAMPERS IN THE FULL OPEN POSITION (UNLESS NOTED OTHERWISE OR DCV SYSTEM). DAMPER SHALL BE CLOSED WITH THE FANS OPERATIONAL IN THE MORNING WARM UP OR COOL DOWN MODES.

12. CONTRACTOR SHALL MAINTAIN A MINIMUM CLEARANCE OF 10"-0" BETWEEN OUTSIDE AIR INTAKE PINTS AND ANY EXHAUST AIR, CONTAMINATED RELIEF AIR, OR PLUMBING VENT TERMINATION POINTS.

13. CONDENSATE PIPING DOWN TO A PLUMBING FIXTURE SHALL BE FULLY INSULATED WITHING WALL. PROVIDE ESCTUTCHEON PLATE AT WALL. PIPING SHALL NOT BE ROUTED TO EXPOSED VIEW.

14. PRESSURIZED LIQUID, GAS, AIR SYSTEM PIPE AND ELECTRICAL CONDUIT SHALL NOT BE ROUTED BENEATH ANY SUSPENDED EQUIPMENT. FIRE PROTECTION, ELECTRICAL, AND MECHANICAL CONTRACTORS SHALL COORDINATE TRADES.

15. ALL REMOTE MOUNTED DISCONNECT SWITCHES FOR MECHANICAL EQUIPMENT SHALL HAVE I.D. NAME PLATES.

16.

GENERAL PLUMBING NOTESGENERAL PROJECT NOTES:GENERAL HVAC NOTES:1. PLUMBING CONTRACTOR IS TO PROVIDE FIRE STOPS AT ALL

PIPING FLOOR ANS RATED WALL PENETRATIONS PER SPECIFICATIONS

2. COORDINATE ROUTING OF ALL PIPING WITH NEW STRUCTURE, DUCTWORK, EQUIPMENT, ETC. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

3. SLOPE ALL DRAIN PIPING 2-1/2" AND SMALLER @ 1/4"/FT. AND ALL DRAIN PIPING 3" ABD LARGER @ 1/8"/FT

4. PROVIDE CLEAN OUTS IN SANITARY AND STORM DRAINAGE SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTION, NEAR THE BASE OF STACKS, EVERY 75 FEET IN HORIZONTAL RUNS, AND ELSEWHERE AS INDICATED.

5. UNLESS OTHERWISE NOTED ALL PIPING SHALL BE NO LESS THAN 3/4".

6. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF ROOF DECKING, WITH SPACE FOR INSULATION REQUIRED.

7. INSTALL PIPING SO THAT VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE

8. WHEN DOMESTIC COLD AND HOT WATER PIPING DROPS INTO A PIPE CHASE, THE SIZE SHOWN FOR THE PIPE DROPS SHALL BE USED TO THE LAST FIXTURE.

9. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.

10. PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING SYSTEM BRANCHES IN WHICH BRANCH PIPING SERVES TWO OR MORE FIXTURES.

11. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS (100 FEET OR MORE) TO PERMIT DISASSEMBLY FOR ALTERNATION AND REPAIRS

12. PROVIDE ALL PLUMBING FIXTURES WITH ACCESSIBLE QUARTER TURN BALL VALVES.

13. TRAP PRIMERS SHALL BE PROVIDED FOR ALL FLOOR DRAINS AND FLOOR SINKS UNLESS NOTED OTHERWISE ON DRAWINGS. REFER TO SPECIFICATIONS FOR TRAP PRIMER REQUIREMENTS.

14. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL PIPING AND PIPE SIZES NOT SHOWN ON FLOOR PLANS.

15. TERMINATE GAS VENTS A MINIMUM OF 2'0" ABOVE ROOF WITH RAIN CAP.

16. FIRE PROTECTION PER NFPA 13 AND ALL OTHER APPLICABLE SECTIONS. FP PIPE SHALL NOT BE ROUTED BENEATH SUSPENDED MECHANICAL EQUIPMENT.

17. EXISTING FIRE PROTECTION SPRINKLER HEADS LOCATED IN NON-CEILING AREA SHALL BE UPRIGHT HEADS. MODIFY EXISTING SECONDARY F.P, PIPING AND SWING ARMS AS REQ'D. TO PROVIDE FULL COVERAGE FOR NEW FLOOR PLAN LAYOUT.

18. CONTRACTOR SHALL COORDINATE INSTALLATION OF GAS SERVICE AND METER WITH GAS COMPANY. CONTRACTOR SHALL PAY ALL FEES, PERMITS, AND CHARGES ASSOCIATED WITH THE INSTALLATION OF BOTH THE GAS METER AND SERVICE.

19. GAS PIPING ON ROOF - CONTRACTOR SHALL PROVIDE ROOF PIPE SUPPORTS ON 10'-0" CENTERS, EACH CHANGE IN DIRECTION, EACH ROOFTOP UNIT, AND EACH PIPE PENETRATION THROUGH ROOF. REFER TO MECHANICAL SPECIFICATIONS FOR REQUIRED OFFSET OR LOOPS FOR PIPE EXPANSION.

20. GAS PIPING INSIDE BUILDING - ALL GAS PIPING INSIDE BUILDING SHALL BE SLEEVED. CONTRACTOR SHALL EXTEND BOTH ENDS OF SLEEVE OUTSIDE BUILDING. WHERE GAS SLEEVES TERMINATE INTO WALL BOXES, CONTRACTOR SHALL INSTALL A 2" VENT FROM EACH WALL BOX AND EXTEND VENT UP THROUGH ROOF. CONTRACTOR SHALL PROVIDE GOOSENECK VENTS AT EACH ROOF PENETRATION.

21. ALL PIPING (DOM./FP/DRAIN/PRODUCTION) MATERIAL SHALL NOT BE CONSTRUCTED FROM PVC IN THE AREA ABOVE THE SCHEDULED CEILING, WHICH IS UTILIZED AS A RETURN AIR PLENUM. ALL WIRE THAT IS NOT IN CONDUIT SHALL BE PLENUM RATED WITHIN THIS AREA.

22. MOUNTING HEIGHT ELEVATION OF ALL WALL HUNG OR COUNTER MOUNTED FIXTURES SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO INSTALLATION OF ROUGH-IN WORK.

23. INSULATE ALL EXPOSED WATER AND DRAIN LINES ADA/TAS ACCESSIBLE LAVATORIES AND SINKS WITH MCGUIRE PRO WRAP OR EQUAL. PROVIDE OFFSET DRAIN FITTINGS WHERE REQUIRED TO PROVIDE MINIMUM CLEARANCES.

24. FLOOR DRAINS SHALL BE INSTALLED AT LOW POINTS OF UNIFORMLY SLOPED FLOOR. CONTACTOR SHALL FIELD COORDINATE WITH STRUCTURAL TO ENSURE FLOORS ARE UNIFORMLY SLOPED ACROSS THE ENTIRE TOILET ROOMS OR OVER AS WIDE AN AREA AS PRACTICAL FOR OPEN AREA FLOOR DRAINS. CONVEX FLOOR SLOPE IN THE IMMEDIATE VICINITY OF THE FLOOR DRAIN IS NOT ACCEPTABLE.

1. WITHOUT PRIOR APPROVAL FROM ENGINEER AND OWNER, ALL MECHANINCAL EQUIPMENT SHALL NOT BE OPERATED DURING CONSTRUCTION OF THE BUILDING PER MANUFACTURER RECOMMENDATIONS. MECHANICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE TEMPORARY HEATING OR COOLING AS NEEDED TO CLIMATIZE THE BUILDING.

2.ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED WITHIN FURRED CHASES OR ABOVE SUSPENDED CEILINGS.

3. ALL DUCTWORK SIZES ARE PROVIDED IN CLEAR INSIDE AIRSTREAM DIMENSIONS. INCREASE DUCT SIZES TO ACCOMMODATE ANY INTERNAL INSULATION REQUIREMENTS (AS SPECIFIED). PROVIDE A MINIMUM OF 15 LINEAR FT. OF INTERNAL ACOUSTIC LINER ON SUPPLY AND RETURN AIR DUCTWORK FROM ANY FCU, AHU, AC, OR RTU (UNO). PROVIDE 8LF INTERNAL LINER FOR MIXING OR VAV BOXES.

4. PROVIDE FLEXIBLE CONNECTIONS ON AT THE INTAKE AND DISCHARGE OF ALL MOTOR DRIVEN EQUIPMENT.

5. PROVIDE VIBRATION ISOLATORS FOR MOTOR-DRIVEN MECHANICAL EQUIPMENT

6. ALL FLEXIBLE DUCTWORK SHALL HAVE A MAXIMUM DEVELOPED LENGTH OF (5) FIVE FT.

7.CONTRACTOR SHALL REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR THE EXACT LOCATION OF ALL CEILING MOUNTED M/E/P DEVICES INCLUDING BUT NOT LIMITED TO LIGHTS, DIFFUSERS, GRILLES ETC..

8. AIR DEVICE DUCT SIZES SHALL BE THE SAME SIZE AS SHOWN ON THE DRAWINGS UNLESS NOTED AS OTHHERWISE. REFER TO THE SCHEDULES FOR THE CFM RANGES. PROVIDE A TRANSITION FROM THE NECK SIZE TO THE REQUIRED DUCT SIZE SHOWN.

9. CONTRACTOR SHALL VERIFY THE EQUIPMENT CLEARANCE REQUIREMENTS WITH THE MANUFACTURER'S RECOMMENDATIONS. EXACT LOCATION OF SELECTED EQUIPMENT SHALL BE COORDINATED WITH THE STRUCTURE TO PROVIDE RECOMMENDED CLEARANCES FOR MAINTENANCE.

10.

PROVIDE FIRE DAMPERS, FIRE/SMOKE DAMPERS AND FIRE STOP AS REQUIRED BY CODE AUTHORITIES FOR DUCT PENETRATIONS THROUGH FIRE OR SMOKE RATED WALL AND CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR WALL TYPES.

11.LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED MAINTENANCE ACCESS FOR ALL UNIT ACCESS PANELS, CONTROLS, AND VALVING.

12. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM CONTRACTOR AND WIRED BY THE ELECTRICAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MOUNTING THE SMOKE DETECTOR IN THE DUCTWORK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS. DETECTORS SHALL BE PROVIDED IN THE SUPPLY AND THE RETURN DUCTWORK (PRIOR TO MIXING WITH OUTSIDE AIR) FOR ANY AIR HANDLING UNIT SYSTEM 2000 CFM SUPPLY SUPPLY AIR AND ABOVE. THE DETECTOR SHALL BE HARDWIRED TO THE UNITS STARTER TO SHUT DOWN THE FAN UPON DETECTION OF PRODUCTS OF COMBUSTION AS WELL AS SEND A SUPERVISORY ALARM SIGNAL TO THE FIRE ALARM PANEL (IF PROVIDED - IF NOT, PROVIDE VISUAL/ AUDIBLE ALARM IN A SUPERVISORY/ APPROVED LOCATION). FOR VAV SYSTEMS THE BMS SHALL DISABLE ASSOCIATED MIXING BOX FANS UPON DETECTION OF SMOKE AT EITHER OF THE AHU'S SMOKE DETECTORS. ENABLE MIXING BOX FANS UPON SMOKE SIGNAL CLEAR.

13. FINISH ALL EXPOSED TO VIEW DUCTWORK AND WALL LOUVERS PER ARCHITECTS RECOMMENDATIONS. ALL EXPOSED ROUND DUCT SHALL BE INTERNALLY SEALED AND MANUFACTURED FROM SPIRAL WOUND PAINT GRIP STEEL.

14. ALL FLOOR BRANCHES OF PIPE RISERS SHALL BE PROVIDED WITH SHUT OFF VALVES AND DRAIN CONNECTION.

15. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND SENSORS 4'-0" (CENTERLINE) ABOVE FINISHED FLOOR. NOTIFY THE ARCHITECT/ ENGINEER OF ANY ROOMS WHERE THE ABOVE LOCATION CAN NOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON PROPER LOCATION.

16. DUCTWORK AND ITS CONSTRUCTION WILL BE GALVANIZED SHEET METAL AND CONSTRUCTED ACCORDING TO THE LATEST SMACNA STANDARDS.

17. ALL DUCTWORK IS SHOWN IN SCHEMATIC FORM. DUCT RISES AND DROPS ARE NOT SHOWN. PROVIDE OFFSETS AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO AVOID INTERFERENCE WITH OTHER TRADES. EACH TRADE SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES.

18. PIPING IS SHOWN IN SCHEMATIC FORM. ROUTE PIPING AS REQUIRED FOR CLEARANCE WITH STRUCTURAL CONDITIONS. COORDINATE WITH OTHER TRADES AS REQUIRED. PIPING SHALL BE INSTALLED WITH ADEQUATE SLOPE AS REQUIRED FOR EACH PARTICULAR SYSTEM.

19. DOUBLE NUT LOCK DOWN FOR MULTI-VANE DAMPERS INSTALLED IN HIGH VELOCITY DUCTWORK/SMOKE REMOVAL DUCTWORK.

20. ALL RADIUS TURNS SHALL BE SMOOTH WALL WITH A RADIUS OF R = 1.5D.

FLOOR CONTROL VALVE

TEE

TEE, UP

TEE, DOWN

SINGLE SWEEP TEE

CROSS

LATERAL

45 DEGREE ELBOW

90 DEGREE ELBOW

90 DEGREE ELBOW UP

CAP

HVAC & PLUMBING, VALVE

& FITINGS SYMBOLS

VENT THRU ROOF

BUTTERFLY VALVE

SOLENOID VALVE

EXPANSION JOINT

FLOAT AND THERM. TRAP

BUCKET STEAM TRAP

FLOOR CLEAN OUT

FIRE HOSE CABINET

PRESSURE RELIEF VALVE

CONTROL, 2 WAY VALVE

CONTROL, 3 WAY VALVE

STRAINER & BLOW OFF VALVE

PRESSURE GAUGE & COCK

UNION OR COMPANION FLANGES

PRESSURE & TEMPERATURE TAP (PETES PLUG)

MANUAL AIR VENT

TEMPERATURE SENSOR

PRESSURE SENSOR

THERMOMETER & WELL

HOSE END DRAIN

AUTOMATIC AIR VENT

FLOW METER

TSF FLOW SWITCH

ANCHOR (PIPE)

HOSE BIBB

B

B

T

H

F

~

F.H.C.

D.S.

CO

CO

OR

R.D.

V.T.R.

HUMIDISTAT

CLEAN OUT

GATE VALVE

FLOOR DRAIN

HUB DRAIN

DOWN SPOUT

ROOF DRAIN

CHECK VALVE

GLOBE VALVE

BALL VALVE

PLUG VALVE

THERMOMETER

THERMOSTAT

OS & Y VALVE

ALL SYMBOLS ON THIS LIST ARE NOT NECESSARILY USED ON THIS JOB.

BALANCING VALVE (WITH PETE'S PLUG EITHER SIDE)

SINGLE W.F. LATERAL STUB

DOUBLE W.F. LATERAL STUB

DOUBLE W.F. LAT & TRAP

FLOOR DRAIN RISER W/TRAP

SINGLE W.F. LAT. & TRAP

O.D. OVERFLOW ROOF DRAIN

PIPE GUIDE

COMPRESSED AIR TAP

MOTORIZED ISOLATION VALVE (2-POSITION-24v)

MANUALLY CALIBRATED BALANCING VALVE

AUTOMATIC FLOW CONTROL VALVE

PIPE SIZE REDUCER (CONCENTRIC)

90 DEGREE ELBOW DOWN

ANGLE GATE VALVE

ANGLE GLOBE VALVE

PIPE SIZE REDUCER (ECCENTRIC)

MOTORIZED CONTROL VALVE (MODULATING-24v)

DESCRIPTIONSYMBOL

DIRECTION OF FLOW

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

TEMPERED CHILLED WATER SUPPLY

TEMPERED CHILLED WATER RETURN

(ALL DESIGNATIONS MAY NOT APPEAR ON DRAWINGS.)

PIPING DESIGNATIONS

SYMBOL DESCRIPTION

SD

OD

140

F

MG

G

RL

RS

CD

PC

D

PR

X X X

CWS

CWR

CHS

CHR

CS

CR

D

FLOW SWITCH

POST INDICATOR VALVES (PIV)

OPEN SCREW AND YOKE VALVE (OS&Y)

FIRE DEPARTMENT CONNECTION

UP AND DOWN SPRINKLER AT SAME LOCATION

UP SPRINKLER

SYSTEM RISER

HOSE VALVE (ANGLE VALVE)

RISE UP ON PIPING

DROP IN PIPING

TAMPER SWITCH FOR VALVES

PENDANT SPRINKLER

UPRIGHT SPRINKLER OR RISE (SPRIG)

PENDANT SPRINKLER ON DROP

SIDEWALL SPRINKLER

A

FIRE PROTECTION SYMBOLS(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)

STATIC PRESSURE SENSOR

R/A GRILLE OR REGISTER

S/A GRILLE/REGISTER W/ SQUARE NECK. 4-WAY THROW (U.N.O)

MOTORIZED DAMPER (WITH END SW.)

THERMOSTAT OR TEMP SENSOR)/ HUMIDISTAT/CARBON DIOXIDE SENSOR

FIRE/SMOKE DAMPER (WITH SM. DET.)

VOLUME DAMPER

FIRE DAMPER

S/A GRILLE/REGISTER W/ ROUND NECK & FLEX CONNECTION. 4-WAY THROW (U.N.O)

90 DEGREE S/A ELBOW DOWN

90 DEGREE S/A ELBOW UP

90 DEGREE R/A ELBOW UP

90 DEGREE R/A ELBOW DOWN

SIDEWALL SUPPLY GRILLE OR REGISTER WITH AIR EXTRACTOR

SPIN-IN TAP WITH DAMPER

SQUARE ELBOW WITH DOUBLE WALL TURNING VANES

TEE WITH SQUARE ELBOWS, TURNING VANES & SPLITTER DAMPER

BRANCH TAKE-OFF

RADIUS ELBOW (R=1.5 MIN.)

ACCESS DOOR AD

SHEET METAL DUCT 16"x12"

DIRECTION OF FLOW

TURNING VANES (RECTANGULAR),SMOOTH RADIUS

SUPPLY DUCT SECTION UP

WYE JUNCTION

BRANCH TAKE-OFF

FLEXIBLE DUCT CONN. WITH DAMPER

SIZE OR SHAPE TRANSITION

45 DEGREE ELBOW (R=1.5 MIN.)

RADIUS ELBOW (R=1.5 MIN.)

ROUND ELBOW UP (R/A SIMILAR)

ROUND ELBOW DOWN (R/A SIMILAR)

HIDDEN SHEET METAL DUCT

INTERNALLY INSULATED SHEET METALDUCT

SUPPLY DUCT SECTION DOWN

RETURN DUCT SECTION UP

RETURN DUCT SECTION DOWN

EXHAUST DUCT SECTION UP

EXHAUST DUCT SECTION DOWN

16"x12"

M

SP

AFAIRFLOW MEASURE STATION

SMOKE DAMPER (WITH SM. DET.)

DUCTWORK LEGEND

ALL SYMBOLS ON THIS LIST ARE NOT NECESSARILY USED ON THIS PROJECT.

16"x12"

DUCT MOUNTED SMOKE DETECTOR (TUBE SENSING TYPE)

P

COUNTER WEIGHTED BACKDRAFT DAMPER BD

ABOVEALTERNATING CURRENTAIR CONDITIONER

ABOVE FINISHED FLOOR

ABOVE GRADE AND GFI

AIR HANDLING UNITALTERNATE

AMPEREAPPROXIMATELYARCHITECTURALAVERAGEBOILER

BAROMETRIC RELIEF DAMPERBRITISH THERMAL UNIT

CUBIC FEET PER MINUTE

CONSTRUCTION DOCUMENTS

CHILLERCHEMICALCHILLED WATER PUMP

CEILINGCOMPRESSORCOOLING TOWERCONDENSER WATER PUMP

DRY BULB

DETAIL

DIAMETER

DIMENSION

DESIGN DEVELOPMENT

ENTERING DRY BULB

ELECTRICALELEVATION

ENTERING WET BULBENTERING WATER TEMPERATUREEXHAUSTEXISTING

DEGREES FAHRENHEIT

GROUND FAULT INTERRUPTERGALLONS PER MINUTE

FEET PER MINUTEFEET PER SECONDFOOT OR FEET

HEAD

HEAT PUMP UNITHOUR(S)HEIGHT

HEATERHEAT,VENT AND AIR CONDITIONINGHOT WATER PUMPHEAT EXCHANGERFREQUENCY (HERTZ)INSIDE DIAMETER OR DIMENSIONINCHESKILOWATTKILOWATT HOUR

MAXIMUMLEAVING WATER TEMPERATURE

1000 BTU PER HOURMECHANICALMANUFACTURERMINIMUM

NUMBER

NOT APPLICABLENOISE CRITERIA

NECK DIMENSION

OPPOSED BLADE DAMPEROUTSIDE DIAMETER

OUTSIDE AIR

ORIGINAL

PHASEPOWERED MIXING BOXPLUMBING

PRESSUREPANEL

REFERENCE

RETURN AIRRETURN AIR GRILLE

ROOF TOP UNIT

STAND ALONE DIGITAL CONTROLLER

SENSIBLE

SQUARE

SUPPLY AIR

STATIC PRESSURE

SINGLE SPEED MOTORSTART/STOP/STATUS

TEMPERATURE

VOLTVARIABLE AIR VALVEVELOCITYWATTWITH

WEATHERPROOFWATER PRESSURE DROPWEATHERPROOF GFITRANSFORMER

ABV.ACA/C

AFF

AG

AHUALT.

AMP.APPROX.ARCH.AVG.B

BRDBTU

CFM

CD

CH.CHEM.CHP

CLG.CMPR.CTCWP

DB

DET.

DIA.

DIM.

DD

EDB

ELEC.ELEV.

EWBEWTEXH.EXIST.

DEG. F

GFIGPM

FPMFPSFT.

HD.

HPUHR.HT.

HTR.HVACHWPHXHZ.IDIN.KWKWH

MAX.LWT

MBHMECH.MFR.MIN.

NO.

N/ANC

NK

OBDOD

OA

ORIG.

PH.PMBPLBG.

PRESS.PNL.

RE.

RARAG

RTU

SDC

SENS.

SQ.

SA

SP

S/SS/S/S

TEMP.

VVAVVEL.WW/

WP.WPDWPGXFMR.

AFG ABOVE FINISHED GRADE

CKT. CIRCUIT

DEFL. DEFLECTION

MVD MANUAL VOLUME DAMPER

WB WET BULB

MEP ABBREVIATIONS

WITHOUTW/O

UNO UNLESS NOTED OTHERWISEUH UNIT HEATER

SAG SUPPLY AIR GRILLE

LAT LEAVING AIR TEMPERATURE

HP HORSE POWER

FLR. FLOOR

FAN COIL UNITFCU

EF EXHAUST FAN

CONDENSING UNITCU

RD. RADIUS

HOA HANDS/OFF/AUTO. MOTOR STARTER

HTG. HEATING

EA EXHAUST AIR

F/A FREE AREA OPENING (SQ. FT.)

ABOVE FINISHED CEILINGAFC

NOT IN CONSTRUCTIONNIC

W.G. WATER GUAGE

TOTAL STATIC PRESSURE (IN. W.G.)T.S.P.

MOTOR STARTERSTR.

SEER SEASON ENERGY EFFICIENCY RATIO

AMB. AMBIENT TEMPERATURE (F. DEGREE)

BUILDING MANAGEMENT SYSTEMBMS

CUBIC FEET PER HOURCFH

DISC. DISCONNECT SWITCH

ENERGY MGMT. CONTROL SYSTEMEXTERNAL STATIC PRESS. (IN. W.G.)E.S.P.

EMCS.

P.D. PRESSURE DROP (FT)

RPM REVOLUTIONS PER MINUTE

FRACTIONAL HORSE POWERFHP

COIL FINS PER INCH.FPI

MCAMOCP

MINIMUM CURRENT AMPS.MAX. OVER CURRENT PROTECTION

BELOW GRADEB.G.

AHAP AS HIGH AS POSSIBLE

OWNERS AUTHORIZED REPRESENTATIVEOAR

OWNER FURNISHED CONTRACTOR INSTALLEDOFCI

RS/L

RS/L/H

AIAIRFLOW IONIZER STATION

SECTION

DETAIL SYMBOL

(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS)

DRAWING SYMBOLS

NOTE BY SYMBOL

AIR DISTRIBUTION DEVICE

SUBTITLE

X12

XX

XX

XX

XX

XXXX

-

-

NUMBER

DESCRIPTION

SCALE

DETAIL #

DRAWING NO. TO REFER TO

AIR QUANTITY

ARROWS INDICATETHROW PATTERN

G-R-DDESIGNATION

DRAWING NUMBER WHERESECTION IS LOCATED

SECTION NUMBER

GAS PRESSURE REDUCING VALVE

WATER PRESSURE REDUCING VALVE

HOT WATER FOR HEATING SUPPLY

HOT WATER FOR HEATING RETURN

HWS

HWR

SANITARY SEWER

SUBSOIL DRAIN PIPING

STORM DRAIN

OVERFLOW DRAIN

PLUMBING VENT

DOMESTIC COLD WATER

DOMESTIC HOT WATER (120 F)

DOMESTIC HOT WATER RECIRC.

DOMESTIC HOT WATER (140 F)

FIRE LINE

BRANCH FIRE LINE WITH SPRINKLER HEADS

MEDIUM PRESSURE NATURAL GAS LINE

LOW PRESSURE NATURAL GAS LINE

REFRIGERANT LIQUID LINE

REFRIGERATED SUCTION LINE

CONDENSATE DRAIN LINE (HVAC)

PUMPED CONDENSATE

REFRIGERANT SUCTION & LIQUID LINES

REFRIG. SUCTION, LIQUID, HOT GAS LINES

DISCHARGE DRAIN

T H C/ /

ELEVATION/ RISER DIAGRAM SYMBOL

XX

XX

DRAWING NUMBER

POINTS TO ELEVATION/ RISER AREA

ELEVATION/ RISER #

FSD

FD

SD

ALL EXISTING SYSTEM INFORMATION AND/OR LOCATIONS ARE PROVIDED BY THE OWNER OR BY A 3RD PARTY. IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY ALL MEP SERVICES ARE LOCATED AS DESIGNED BEFORE BIDDING THE PROJECT. IN OCCURENCES WHERE EXISTING DOES NOT MATCH DESIGNED, IT IS THE CONTRACTORS RESPONSIBILITY TO NOTIFY THE OWNER, ARCHITECT, & ENGINEER BEFORE PROCEEDING. IF ANY DISCREPANCIES ARE NOT IDENTIFIED AT BIDDING, THE COST SHALL BE ABSORBED BY THE CONTRACTOR AND NOT PASSED ONTO THE OWNER OR ENGINEER OF RECORD.

ALL DEMOLITION ACTIVITIES SHALL BE PERFORMED SO AS TO PROVIDE MINIMAL DISRUPTION TO THE NEIGHBORING TENANTS

17. ALL SAW CUTTING SHALL BE PERFORMED AFTER HOURS SO THAT OPERATION DOES NOT DISTURB NEIGHBORING TENANTS. THERE SHALL BE NO GAS POWERED EQUIPMENT IN TENANT AREAS.

EQUIP. OR FIXTURE DRAIN LINE

PRESSURE RELIEF DISCHARGE

EXISTING PIPING

EXISTING PIPING TO BE REMOVED

UNDERFLOOR

CONNECT TO NEW OR EXISTING

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

1/8" = 1'-0"

9/1

/20

21 6

:06

:15

PMMP000

LE

GE

ND

AN

D G

EN

ER

AL

NO

TE

S -

ME

CH

AN

ICA

L/P

LU

MB

ING

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

03/11/20

TG TG

No.

Revisions and Descr iptions

By

Date

Page 21: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

9/1

/20

21 7

:41

:34

PMM001

ME

CH

AN

ICA

L S

CH

ED

UL

ES

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

TG

TG

4. INSTALL FLEXIBLE CONNECTION AT OUTLET.

3. REFER TO MFG. DATA FOR REFRIGERANT LINE SIZING.

2. PROVIDE 2" PLEATED, MERV 13 RATED FILTERS. PROVIDE SPARE SET.

1. EXTERNAL STATIC PRESSURE (E.S.P.) IS DUCTWORK AND GRILLES ONLY. BHP SHOULD INCLUDE TWICE THE INITIAL FILTER STATIC PRESSURE.

NOTES: 5. EXPOSED LINE SET MUST BE INSTALLED IN WALL ESCUTCHEON.

EX. FCU-04 LOBBY / SUPPORT 3,335 410 900 0.75 3 104.0 79.1 78.3 / 63.7 2 EXISTING 35 89.8 62.7 208 / 3 LENNOX TAA120S4D-1Y EXISTING 1-5

EX. FCU-03 CONSTABLE / CLERKS 1,200 180 900 0.75 1/3 32.2 26.8 78.4 / 64 2 EXISTING 15 38.5 61.9 208 / 3 LENNOX CBX32M-036-230-6-05 EXISTING 1-5

EX. FCU-02 COURT 1,750 345 900 0.75 1/2 52.6 38.9 78.4 / 65.8 2 EXISTING 20 62.7 60.4 208 / 3 LENNOX CBX32M-060-230-6-05 EXISTING 1-5

EX. FCU-01 JUDGES CHAM. / BREAKROOM 1,050 125 900 0.75 1/2 31.0 23.4 76.9 / 63.7 2 EXISTING 15 38.0 63.6 208 / 3 LENNOX CBX32M-036-230-6-05 EXISTING 1-5

RPM IN.W.G. HP TOTAL MBH SENS. MBH EAT DB/WB(F) STAGES MCA MCCP KW CAP MBH EAT (F) V /PH NUMBER (>200 LBS.)DESIG. SERVES CFM MIN O/A

MAX FAN E.S.P. MOTOR DATA COOLING COIL DATA HEATING COIL DATA (ELEC)MFG.

MODEL OP. WEIGHTREMARKS

EXISTING FAN COIL UNIT SCHEDULE

2. PROVIDE MANUFACTURERS RECOMMENDED SERVICE AND OPERATIONAL CLEARANCES - NOT LESS THAN 24" CLEAR.

1. SIZE AND INSTALL REFRIGERANT LINES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

NOTES:

EX. CU-FCU-04 EX. FCU-04 10 120.0 - 105 / 32 EXISTING LENNOX TSA120S4DN1Y 5611E02455 41 50 208 / 1 EXISTING 13.5 EXISTING 1,2

EX. CU-FCU-03 EX. FCU-03 3.0 36.0 - 105 / 32 EXISTING LENNOX TSA036S4N43Y 5811K12080 14.2 20 208 / 1 EXISTING 14.5 EXISTING 1,2

EX. CU-FCU-02 EX. FCU-02 5.0 60.0 - 105 / 32 EXISTING LENNOX TSA060S4N44Y 5811H09128 21.3 35 208 / 1 EXISTING 13.5 EXISTING 1,2

EX. CU-FCU-01 EX. FCU-01 3.0 36.0 - 105 / 32 EXISTING LENNOX TSA036S4N43Y 5811K12081 14.2 20 208 / 1 EXISTING 14.5 EXISTING 1,2

TONS (MBH) HTG. (MBH) SUM / WINT MBH @ 47F AMB. NUMBER NUMBER MCA MOCP V / PH (>200 LBS.)DESIG. SERVES

NOM. CAPACITY CAPACITY COND. AMB.(F) HEATING CAPACITYMANUF.

MODEL SERIAL ELECTRICAL DATAMIN SEER/EER

@AHRI

SEER OP. WEIGHTREMARKS

EXISTING SPLIT SYSTEM HEAT PUMP SCHEDULE

4. PROVIDE COUNTERED WEIGHTED BACKDRAFT DAMPER WITH FELTED BLADE STRIKES.

3. PROVIDE MANUFACTURERS ROOF CURB - 12" HIGH ABOVE FINISHED ROOF. NO CURB SLOPE- MOUNT PARALLEL TO ROOF ANGLE.

2. OUTSIDE AIR APPLICATIONS SHALL HAVE 2 POSITION ACTUATORS (120V/1PH - N.C.) BY HOOD MANUFACTURER. END SW. BY CONTROLS CONTRACTOR.

1. PROVIDE BIRD SCREEN

NOTES:

VH-D RELIEF 200 -- 0.05 0.37 8" GREENHECK GRSR -- 1-2, 4

VH-C INTAKE 450 -- 0.05 0.82 12" GREENHECK GRSI -- 1-3

VH-B INTAKE 315 -- 0.05 0.58 10" GREENHECK GRSI -- 1-3

VH-A INTAKE 450 -- 0.05 0.82 12" GREENHECK GRSI -- 1-3

(>200 LBS.)

MARK SERVICES MAXIMUM CFMMIN. PERIMETER

INTAKE AREA (SQ.FT)

MAX P.D. (W.G.)

MIN.THROAT

AREA (SQ.FT)

DUCT SIZE MANUFACTURER MODEL NO.

OP. WEIGHT

REMARKS

ROOF VENTILATOR SCHEDULE

7. DISCONNECT SWITCH.

6. NEMA 3R EXTERNALLY MOUNTED WEATHERPROOF DISCONNECT SWITCH

5. GRAVITY BACKDRAFT DAMPER.

4. GALV. ROOF CURB 12" HIGH ABOVE FINISHED ROOF NOT DECK, SLOPED TO MATCH ROOF PITCH.

3. BIRD SCREEN

2. UNIT MOUNTED SPEED CONTROL RHEOSTAT (SCR) SWITCH.

IT IS CONTRACTORS RESPONSIBILITY TO VERIFY AN ISOLATION SYSTEM IS INSTALLED INTEGRAL OR FIELD INSTALLED. B. RUN FAN DURING OCCUPIED HOURS.

1. SUPPORT WITH VIBRATION ISOLATORS. IF ISOLATORS ARE INTEGRAL TO EQUIPMENT, ADDITIONAL ISOLATORS SHALL BE EXCLUDED. A. INTERLOCK WITH LIGHT SWITCH.

OPTIONS & ACCESSORIES CONTROL / INTERLOCK

EF-04 ADA RR CEILING 75 DIRECT 0.2 850 27 W 115 1 2 GREENHECK SP-L80 1,5,7, A -

EF-03 ADA RR CEILING 150 DIRECT 0.2 1,000 83 W 115 1 3.5 GREENHECK SP-A250 1,5,7, A -

EF-02 IT DOWNBLAST 300 DIRECT 0.50 1,300 1/12 115 1 6.7 GREENHECK G-095-G 1-6, B -

EF-01 EVIDENCE DOWNBLAST 300 DIRECT 0.50 1,300 1/12 115 1 6.7 GREENHECK G-095-G 1-6, A -

(IN W.G.) RPM HP VOLTS PHASE SONES NUMBER WEIGHT (>200 LBS.)DESIG. SERVES TYPE CFM DRIVE

E.S.P. MAX. FAN MOTOR MAX.MANUFACTURER

MODELREMARKS

OPERATING

FAN SCHEDULE

No.

Revisions and Descr iptions

By

Date

Page 22: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

9/1

/20

21 7

:41

:34

PMM002

ME

CH

AN

ICA

L S

CH

ED

UL

ES

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

21

TG

TG

4. PROVIDE MANUFACTURERS REMOTE WALL MOUNTED T'SENSOR.

3. COORDINATE COLOR WITH ARCHITECT.

2. REFER TO HVAC DRAWINGS FOR ANY NECK SIZES OTHER THAN THOSE SHOWN ABOVE.

1. MATCH FRAME OR AIR DEVICE WITH CEILING. REFERENCE ARCHITECTURAL REFLECTIVE CEILING PLANS AND ROOM FINISH SCHEDULE.

NOTES:

DIFFUSER FOR LAY-IN CEILING. 325 - 23 10"

VOLUME ROUND NECK CEILING SUPPLY 245 - 20 8"

J TITUS 24"X24" ARCHITECTURAL FACE, VARIABLE 150 - 20 6" ALUM. N T3SQ-2 1,2,3,4

MOUNTED APPLICATIONS

FOR SURFACE

E TITUS 12"x12" EXHAUST GRILLE, 35° DEFL. 530 600 - 10"x10" ALUM. N 350 FL 1,2,3

LAY-IN CEILING MOUNTED APPLICATIONS.

D TITUS 24"X12" PERFORATED RETURN GRILLE FOR 900 600 15 22"x10" ALUM. N PAR-AA 1,2,3

1350 400 20 22"x22"

900 400 18 18"x18"

530 500 21 14"

390 500 17 12"

325 600 20 10"

LAY-IN CEILING MOUNTED APPLICATIONS. 210 600 17 8"

C TITUS 24"X24" PERFORATED RETURN GRILLE FOR 115 600 13 6" ALUM. N PAR-AA 1,2,3

MOUNTED APPLICATIONS

CEILING SUPPLY DIFFUSER FOR SURFACE 210 600 - 8"

B TITUS 12"x12" ARCHITECTURAL FACE, ROUND NECK 120 600 - 6" ALUM. N OMNI-AA 1,2,3

855 800 20 14"

630 800 20 12"

LAY-IN CEILING. 440 800 - 10"

NECK CEILING SUPPLY DIFFUSER FOR 280 800 - 8"

A TITUS 24"X24" ARCHITECTURAL FACE, ROUND 150 800 - 6" ALUM. N OMNI-AA 1,2,3

CFM VEL (FPM) NC INCHES NUMBERDESIG. MFG. DESCRIPTION

MAX MAX NECK MAX NECK SIZEMATERIAL OBD

MODELNOTES

AIR DEVICE SCHEDULE

5. PROVIDE CONTROL PANEL LABEL LISTING THE SHORT CIRCUIT RATING (SCR IN KAIC) REFER TO ELEC. POWER TO MECH. SCHEDULE FOR RATING REQMTS.

4. PROVIDE MANUFACTURERS MOUNTING BRACKET.

3. PROVIDE ALL SAFETIES.

2. PROVIDE INTEGRAL CONTROL VOLTAGE TRANSFORMER, RELAYS AND CONTROLS FOR A SINGLE POINT ELECTRICAL CONNECTION.

1. PROVIDE MANUFACTURERS SINGLE STAGE THERMOSTAT UNIT MOUNTED (REMOTE MOUNTED).

NOTES:

UH-01 350 10.2 3 208 1 1/100 1600 208 1 QMARK MUH-03 1-7

(MBH) KW VOLTS PHASE HP RPM VOLTS PHASE (>200 LBS.)MARK CFM

CAPACITY ELEC. HEATING COIL DATA FAN DATAMANUFACTURER MODEL NO.

OP. WEIGHTREMARKS

UNIT HEATER SCHEDULE

No.

Revisions and Descr iptions

By

Date

Page 23: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

NOTES BY SYMBOL " ":

CLERKS

121

CONSTABLE

103

OPEN/FUTURE

VOTING

130

CONFERENCE

112

CONFERENCE

113

JUDGES

CHAMBER

120

COURTROOM

115

IT

122

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

ELEC

111

JURY/TRAINING

116

EVIDENCE

104

STORAGE

109

ADA RR

129

CORRIDOR

125

CONSTABLE

105

STORAGE

118

STORAGE

124

AV

117

COURT

114

FOYER

101

CLOSET

119

COORIDOR

123

A - 6"ø

150 CFM

A - 6"ø

150 CFM

A - 10"ø

290 CFM

A - 10"ø

290 CFM

A - 10"ø

290 CFM

A - 10"ø

295 CFM

A - 10"ø

295 CFM

A - 10"ø

290 CFM

A - 6"ø

120 CFM

EX.FCU-02

18"x16"18"x12"12"ø

EX.FCU-04

A - 6"ø

100 CFM

A - 6"ø

100 CFM

A - 6"ø

100 CFMA - 6"ø

50 CFM

A - 8"ø

200 CFM

A - 8"ø

200 CFM

A - 6"ø

50 CFM

A - 6"ø

125 CFM

A - 6"ø

125 CFM

A - 10"ø

300 CFM

A - 10"ø

300 CFM

A - 10"ø

300 CFM

A - 10"ø

300 CFM

A - 8"ø

210 CFM

A - 8"ø

210 CFM

A - 8"ø

210 CFM

A - 8"ø

210 CFM

A - 8"ø

210 CFM

14"x14" 24"x18"24"x14"

B - 8"ø

200 CFM

B - 8"ø

200 CFM

B - 6"ø

100 CFM

B - 6"ø

40 CFM

B - 6"ø

75 CFM

A - 6"ø

100 CFM

12"ø

18

"x16"

C

C

18"x16"

16"x12"

24"x18"

10"ø

J - 6"ø

100 CFM

J - 6"ø

100 CFM

A - 6"ø

75 CFM

B - 6"ø

50 CFM

B - 6"ø

50 CFM

D

A - 6"ø

150 CFM

A - 6"ø

150 CFM

10"ø

18

"x14"

T'J'

A - 6"ø

120 CFM

10

6"ø

16"x12"C - 14"ø

C - 14"ø

02

M501

01

M501

20

"x18"

12"ø

8"ø

C

TFCU-03

TFCU-04

TFCU-02

TFCU-02

MOP

107

E - 10"ø

(300 CFM )

E - 10"ø

300 CFM

EX.FCU-03

EX.FCU-01

12"ø

8"ø

14"ø

C

C

D

14"x14"

20"x20"14"ø10"ø

8"ø

10"ø

14"x14"

8"ø

6"ø

D

10"ø12"ø

8"ø20"x20"

8"ø

EF-03 EF-04

10"ø

C - 10"ø

20"x20"

03

M501

14"ø

10"ø

46"x20"

C - 10"ø

C - 10"ø

C

14

"x14"

14

06

M501

04

M501

1

1

1

23

3

4

4

4

4

5

6

UH-01

6"ø

6"ø

8"ø

10"ø8"ø

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 7

:41

:38

PMM201

FL

OO

R P

LA

N -

ME

CH

AN

ICA

L

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

TG

TG

TRUE NORTH

1 ROUTE FULLY INSULATED CONDENSATE LINEDOWN TO SINK TAILPIECE.

2 12"Ø OUTSIDE AIR DUCT UP TO VENTILATOR,VH-A. REFER TO M2.2 FOR TERMINATION.TRANSITION AS NECESSARY IN THE VERTICAL.PROVIDE MOTORIZED DAMPER TO SHUT WHENUNIT IS OFF.

3 8"Ø OUTSIDE AIR DUCT UP TO VENTILATOR,VH-B. REFER TO M2.2 FOR TERMINATION.TRANSITION AS NECESSARY IN THE VERTICAL.PROVIDE MOTORIZED DAMPER TO SHUT WHENUNIT IS OFF.

4 RELOCATE UNIT'S REFRIGERANT LINES ASNECESSARY WITH NEW PLACEMENT.

5 8"Ø EXHAUST DUCT UP TO VENTILATOR, VH-D.REFER TO M2.2 FOR TERMINATION. TRANSITIONAS NECESSARY IN THE VERTICAL.

6 12"Ø OUTSIDE AIR DUCT UP TO VENTILATOR,VH-C. REFER TO M2.2 FOR TERMINATION.TRANSITION AS NECESSARY IN THE VERTICAL.PROVIDE MOTORIZED DAMPER TO SHUT WHENUNITS ARE OFF.

0 3' 6' 12'

GRAPHIC SCALE3/16" = 1'-0"

1.5'

GENERAL NOTES:

1 COORDINATE WITH ALL TRADES BEFOREINSTALLING ANY EQUIPMENT, CONDENSATEDRAINS, REFRIGERANT LINES, OR DUCTWORK.

2 INSTALL CONDENSING UNITS AND SIZEREFRIGERANT LINES PER MANUFACTURER'SGUIDELINES AND REQUIREMENTS.

3 PROVIDE MANUFACTURER RECOMMENDEDCLEARANCE FOR SERVICE OF INDOOR AHUUNITS.

4 ROOF CURB SHALL MATCH SLOPE OF THE ROOF.

5 INTAKES AND FLUES/EXHAUST SHALL BELOCATED A MINIMUM OF 10'-0" FROM EACHOTHER.

3/16" = 1'-0"01

FLOOR PLAN - MECHANICAL

No.

Revisions and Descr iptions

By

Date

Page 24: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

NOTES BY SYMBOL " ":

VH-A

VH-C

1

1

02

M501

01

M501

EF-01

EF-02

VH-B

EX.

CU-FCU-01EX.

CU-FCU-03

EX.

CU-FCU-02

EX.

CU-FCU-04

VH-D

03

M501

06

M501

04

M501

22

22

3

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 7

:41

:40

PMM202

RO

OF

PL

AN

-M

EC

HA

NIC

AL

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

TG

TG

3/16" = 1'-0"01

ROOF PLAN - MECHANICAL

1 CONTRACTOR TO VERIFY VENTILATOR IS AT MINIMUM

10 FT FROM THE EXISTING EXHAUST FANS.

2 CONTRACTOR TO INSTALL NEW REFRIGERATION

LINES. REUSE EXISTING WALL PENETRATIONS AND

RESEAL.

3 MAINTAIN 10 FT CLEARANCE FROM ANY AIR INTAKES.

GENERAL NOTES:

1 COORDINATE WITH ALL TRADES BEFORE

INSTALLING ANY EQUIPMENT, CONDENSATE

DRAINS, REFRIGERANT LINES, OR DUCTWORK.

2 INSTALL CONDENSING UNITS AND SIZE

REFRIGERANT LINES PER MANUFACTURER'S

GUIDELINES AND REQUIREMENTS.

3 PROVIDE MANUFACTURER RECOMMENDED

CLEARANCE FOR SERVICE OF INDOOR AHU

UNITS.

4 ROOF CURB SHALL MATCH SLOPE OF THE ROOF.

5 INTAKES AND FLUES/EXHAUST SHALL BE

LOCATED A MINIMUM OF 10'-0" FROM EACH

OTHER.

TRUE NORTH0 3' 6' 12'

GRAPHIC SCALE

3/16" = 1'-0"

1.5'

No.

Revisions and Descr iptions

By

Date

Page 25: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

SCALE:

SCALE:

SCALE:

SCALE:

SCALE:

SCALE:

SCALE:

AIR DUCT/ROOF PENETRATION0507 FAN COIL SUPPORT NTS

1.5WR

W

R

W

R

R

W

2/3W

R

1/3W

W

1/6W

1/3W

1/2W

W

GREATER THAN W.

R SHALL EQUAL OR BE

GREATER THAN 1/3W.

R SHALL EQUAL OR BE

GREATER THAN 1/6W.

R SHALL EQUAL OR BE

NOTES:

ALL STANDARD RADIUS ELBOWS SHOWN ON PLANS MAY BE MADE SHORT RADIUS ELBOWS.ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTION,SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

2.

1.

NTS

NTSNTS

MAJOR RECTANGULAR DUCT WYE03 NTS

01 VANED DUCT ELBOW DETAIL

MAJOR RECTANGULAR DUCT TEE02

1-1/8"

"D"

"C"

"A"

"H"

"F"

"B"

"E"

AIR FLOW

"G"

DIMENSIONAL RELATIONSHIPS

ANGLES A&B EACH TO BE 15 DEGREES OR LESS

SEE DUCT PLANS FOR VALUES OF C,D, AND E.

F = C+DH = 1.5XC

G = H+3" MINIMUM

HEIGHT OF FITTING EQUAL TO THAT OF HIGHEST OF 3DUCTS

CHANGE IN HEIGHTS OF DOWNSTREAM DUCTS TOOCCUR AFTER THE TURN

1.

2.

3.

4.

5.

6.

7.

SPLITTER DAMPER ANDREGULATOR

DIMENSION

NO CHANGE INVERTICAL DUCT

1-9/16"

2" R

90 DEG.

1" R

4" R

2" R

SMALL DOUBLE VANE

90 DEG.

4-1/2"

8-1/4"2-1/4"

SMALL DOUBLE VANE

LARGE DOUBLE VANELARGE DOUBLE VANE RUNNER

SQUARE ELBOW.LARGE DOUBLE VANE

SQUARE ELBOWSMALL DOUBLE VANE

15" OR MORE

"G"

DIMENSION

NO CHANGE INVERTICAL DUCT

AIR FLOW

"E"

"B"

"F"

"H""A"

DIMENSIONAL RELATIONSHIPS

"C"

"D"

ANGLES A&B EACH TO BE 15DEGREES OR LESSSEE DUCT PLANS FOR VALUES OF C,D,AND E.F = C+DH = 1.5XCG = H+3" MINIMUM

HEIGHT OF FITTING EQUAL TO THATOF HIGHEST OF 3 DUCTSCHANGE IN HEIGHTS OFDOWNSTREAM DUCTS TO OCCURAFTER THE TURN

1.

2.

3.4.5.6.

7.

SPLITTER DAMPERAND REGULATOR

04 TYPICAL CEILING SUPPLY DIFFUSER06 MED. PRES. DUCT RADIUS ELBOW

LAY - IN CEILING

STRAIGHT FLEX12" MIN. OF

CONICAL TAP

TAP CAN BE THE IN SIDE OR BOTTOM

ROUND RIGID W/ INSULATION(R-8) LIMIT FLEX TO 5'-0"

LOCKING QUADRANT DAMPER WITHINSULATION STAND-OFF.

CEILING TYPE DIFFUSER

METAL MECHANICAL TYPEBAND AT CONN. OF FLEX

SUPPORT WIRE

1" MIN. BAND CLAMP ATDIFFUSER TURN DOWN

INSULATED FLEX DUCT(RE. TO SPECS)

SUPPLY TRUNK DUCT

MASTICALLY SEAL ALLFITTING JOINTS (TYP.)

CUT OUT SIZE FOR

CONNECTION PIPE

MASTIC SEAL ALLFLEX INTERNALCONNECTIONS

23.63

3.7 3

INSULATE BACK OFDIFFUSERS (R-6)

NOTES:

1. APPLICATION FOR SUPPLY AND

RETURN DIFFUSERS.

2. INSULATION SHALL FIT TIGHT

AGAINST DIFFUSER.

3. SEAL ALL (4) SIDES OF THE

INSULATION TO THE GRILLE.

4. R-6 INSULATION.

SEAL WATERTIGHT

FLASHING SKIRT BYMECH. CONTRACTOR

8" CURB COUNTERFLASHING

1"

ROOF

8" CURB

AIR DUCT

STRUCTURE

FILTER ACCESS

LINED RETURNAIR PLENUM

FLEX CONNECTION (TYP)

LINED SUPPLYAIR PLENUM

ALL-THREAD RODSECURE TOSTRUCTURE.

22GA SECONDARY CONTINUOUSLY WELDED CONDENSATEPAN WITH UNISTRUT SUPPORT ACROSS FAN COIL INSIDEPAN. PAN LENGTH & WIDTH LARGER THAN VALVEASSEMBLIES.

UNISTRUT SUPPORT TORUN LENGTH OF FANCOIL (2) REQUIRED (1)PER SIDE.

SPOT-WELD OR SHEET METALSCREW PAN SUPPORT TO PANBOTTOM (TYP. 4)

2"

NOTE: SECONDARY DRAIN PAN SHALL HAVE FLOAT SENSOR TO DEACTIVATE FAN.1.

VIBRATION ISOLATION. IF UNIT ISINTERNALLY ISOLATED, PROVIDERUBBER ISOLATION, OTHERWISEPROVIDE SPRING ISOLATION.

M.C. SHALL HARDWIRE TO MOTOR STARTER. DRAIN PAN SHALL EXTEND UNDER CONTROL VALVES.

BALL VALVE WITH THREADED ENDCAP

NTS

NTS

SCALE:

SCALE:

SINK TAIL-PIECE

CONDENSATEDRAIN PIPE

WALL

SINK TAIL-PIECE

ESCUTCHEON

INSULATE CONDENSATE DRAIN PIPING ANDFITTINGS WITH 1" THICK 'ARMAFLEX' FOAMPLASTIC INSULATION. SEAL JOINTS W/ ADHESIVE.

SAN. TEE FITTING SIMILARTO 'McGUIRE' NO. 520

RIGID PIPING(NO FLEX HOSES)

ADA INSUL. (TYP.)

NTSCONDENSATE TERMINATION08

BRANCH DUCT DETAIL09 NTS

NOTES:

AIR FLOW

"D"

"A"

BRANCH DUCT

EQUALIZING GRID REQUIRED IFFIRST TAKEOFF IS LESS THAN 5'-0"FROM BRANCH OF MAIN DUCT.

BALL JOINT CONNECTION

SPLITTER DAMPER 18 GAUGEMINIMUM

45°

"B"

"C"

MAXIMUM MAIN DUCT VELOCITY1200 FPM

B=A X 1.5 + 3C= A/2 + 3

D=A/2

4.

1.2.

3.

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

1/8" = 1'-0"

9/1

/20

21 6

:06

:09

PMM401

DE

TA

ILS

-M

EC

HA

NIC

AL

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

TG TG

No.

Revisions and Descr iptions

By

Date

Page 26: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

FINISHED FLOOR0' - 0"

Roof24' - 1"

EX.FCU-02

10"ø

10"ø

VH-A

FINISHED FLOOR0' - 0"

Roof24' - 1"

10"ø

VH-C

EX.FCU-04

10"ø18"x24"

FINISHED FLOOR0' - 0"

FINISHED FLOOR0' - 0"

EX.10

TON

EX.10

TON

EX.5

TON

WICCU

FINISHED FLOOR0' - 0"

Roof24' - 1"

FINISHED FLOOR0' - 0"

EX.FCU-03

EX.FCU-01

VH-B

FINISHED FLOOR0' - 0"

FINISHED FLOOR0' - 0"

EX.CU-FCU-03

EX.CU-FCU-01

FINISHED FLOOR0' - 0"

FINISHED FLOOR0' - 0"

EXISTING EAVEHEIGHT

15' - 0"

AWNING EAVEHEIGHT

9' - 0"

EX.5

TONEX.3

TON

EX.3

TON

EX.5

TONFINISHED FLOOR

0' - 0"FINISHED FLOOR

0' - 0"

AWNING EAVEHEIGHT

9' - 0"

EX.CU-FCU-02

EX.CU-FCU-04

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

1/4" = 1'-0"

9/1

/20

21 7

:41

:43

PMM501

SE

CT

ION

VIE

WS

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

Author

TG

1/4" = 1'-0"01

FCU-02

1/4" = 1'-0"02

FCU-04

1/4" = 1'-0"05

MEZZANINE (NORTH) - DEMO

1/4" = 1'-0"03

EX. FCU-01 & EX. FCU-03

1/4" = 1'-0"06

MEZZANINE (NORTH) - NEW

1/4" = 1'-0"07

MEZZANINE (EAST) - DEMO

1/4" = 1'-0"04

MEZZANINE (EAST) - NEW

No.

Revisions and Descr iptions

By

Date

Page 27: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

05

M501

EX.

10

TON

EX.

10

TON

EX.

5

TON

EX.

5

TON

EX.

3

TON

EX.

3

TON

EX.

5

TON

07

M501

WIC

CU

1

1

1

2

2

2 3

2

NOTES BY SYMBOL " ":

GENERAL DEMO NOTES:1. REFER TO MP0.0 FOR GENERAL PLUMBING

NOTES, ABBREVIATIONS, AND SYMBOLS.

2. PRIOR TO THE DEMOLITION OF WORK BY ANY

TRADE PROVIDE A QUALIFIED MECHANICAL

CONTRACTOR TO DISCONNECT ALL MECHANICAL

EQUIPMENT WITHIN THE AREA OF DEMOLITION.

THIS CONTRACTOR SHALL REMAIN ON SITE

DURING DEMOLITION, TO DISCONNECT AND TEST

ALL MECHANICAL SYSTEMS THAT BECOMES

ACCESSIBLE DURING THE COURSE OF

DEMOLITION.

3. TOUR THE PROJECT SITE WITH THE OWNER'

REPRESENTATIVE TO IDENTIFY AND MARK THOSE

ITEMS SCHEDULED FOR DEMOLITION, THAT THE

OWNER WISHES TO RETAIN. DELIVER THOSE

ITEMS SO MARKED, TO THE OWNER'S STORAGE,

WITHIN THE PROJECT SITE AS DIRECTED.

4. ALL REMAINING DEMOLITION ITEMS SHALL

BECOME THE CONTRACTORS PROPERTY AND

SHALL BE REMOVED FROM THE SITE. HAZARDOUS

MATERIALS SHALL BE DISPOSED OF IN

ACCORDANCE WITH FEDERAL REGULATIONS AND

THE CONTRACT DOCUMENTS.

5. WHERE CEILINGS OR WALLS ARE SCHEDULED

FOR DEMOLITION ON THE ARCHITECTURAL

DRAWINGS, DISCONNECT AND REMOVE ALL

MECHANICAL EQUIPMENT AND APPURTINANCE

ASSOCIATED WITH THOSE WALLS.

6. IDENTIFY DUCTWORK AND PIPING PASSING

THOUGH THE AREA OF DEMOLITION AND

SERVING EQUIPMENT OR AIR DEVICES OUTSIDE

THE AREA THAT WILL REMAIN. MARK AND

PROTECT THESE DUCTS AND PIPES DURING

DEMOLITION.

7. THE MECHANICAL SERVICE TO AREAS NOT

WITHIN THE DEMOLITION SCOPE OF WORK SHALL

NOT LOSE FUNCTION UNLESS SCHEDULED AND

AGREED TO BY THE OWNER.

8. REFER TO ARCHITECTURAL DRAWINGS FOR

AREAS OF DEMOLITION.

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 7

:41

:46

PMMD202

RO

OF

DE

MO

LIT

ION

PL

AN

-M

EC

HA

NIC

AL

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

TG

TG

3/16" = 1'-0"01

ROOF DEMO PLAN - MECHANICAL

1 REFER TO M2.2 FOR NEW LOCATION OF EXISTING

UNIT. CONTRACTOR TO INSTALL NEW

REFRIGERATION LINES AND ADJUST EXISTING

ELECTRICAL ITEMS AS NECESSARY.

2 REMOVE AND SALVAGE HEAT PUMP,

REFRIGERANT LINES, ELECTRICAL LINES, AND

ASSOCIATED FAN COIL AND RETURN TO OWNER

OR OWNER'S REP.

3 REMOVE AND SALVAGE EXISTING WALK-IN

COOLER'S CONDENSING UNIT AND ALL

ASSOCIATED EQUIPMENT. RETURN TO OWNER

OR OWNER'S REP.

TRUE NORTH0 3' 6' 12'

GRAPHIC SCALE

3/16" = 1'-0"

1.5'

No.

Revisions and Descr iptions

By

Date

Page 28: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

DN

1

1

1

2

1

1

1

1

1

1

1

1

1

1

1

3

EX. 4 2

1

1

11

1

1

1

2

A. REFER TO DRAWING E000 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND GENERAL NOTES.

B. THE ELECTRICAL CONTRACTOR SHALL VERIFY WITH THE CONSTRUCTION MANAGER THAT A SURVEY HAS BEEN CONDUCTED AND ALL UNDERGROUND UTILITIES HAVE BEEN IDENTIFIED AND MARKED. CALL DIG TESS.

C. UTILITIES SHOWN ON THESE DRAWINGS ARE FOR REFERENCE ONLY. THE ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL EXISTING UTILITIES AND ROUTING OF ALL NEW UNDERGROUND UTILITIES WITH RESPECT TO TRADES (GENERAL, PLUMBING, CIVIL, ETC.) PRIOR TO DIGGING. MINIMIZE DIGGING BY SHARING TRENCHES WHENEVER POSSIBLE.

D. COORDINATE ANY DEMOLITION, TEMPORARY, AND PERMANENT (ELECTRICAL AND TELEPHONE) SERVICES TO THE SITE WITH THE RESPECTIVE LOCAL UTILITY COMPANY REPRESENTATIVES, IN THE FIELD, PRIOR TO COMMENCEMENT OF WORK. ALL ASSOCIATED COST/FEES BY THE UTILITY COMPANY SHALL BE INCLUDED IN THE BID PRICE.

E. COORDINATE SERVICE SHUTDOWNS WITH ALL TRADES INVOLVED ON SITE AND OBTAIN WRITTEN AUTHORIZATION FROM THE OWNER 72 HOURS PRIOR TO ANY ELECTRICAL AND/OR TELEPHONE SHUTDOWN.

F. CONTRACTOR SHALL REMOVE ALL UNUSED OR ABANDONED CONDUIT AND WIRING UNLESS NOTED OTHERWISE ON THE DRAWINGS.

G. ALL EQUIPMENT AND DEVICES REMOVED DURING CONSTRUCTION SHALL BE RETURNED TO THE BUILDING OWNER UNLESS OTHERWISE INSTRUCTED BY THE BUILDING OWNER.

H. IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY EXISTING JOB SITE CONDITIONS DURING THE BIDDING PERIOD TO OBTAIN THE SCOPE OF ELECTRICAL WORK INVOLVED. THE SCOPE OF WORK SHALL INCLUDE OUTLETS, BOXES, CONDUIT, WIRING, FIXTURE DEVICES AND MATERIALS, WHICH MUST BE RE-ROUTED, RELOCATED OR REMOVED WITHER TEMPORARILY. PERMANENTLY, OR WHICH MUST BE PROVIDED SO THAT THE INDICATED REMODELING MAY BE ACCOMPLISHED. RE-ESTABLISH SERVICE TO ALL OUTLETS, PANELBOARDS, LIGHT FIXTURES, OR OTHER ELECTRICAL DEVICE THAT MAYBE INTERRUPTED BECAUSE OF THE REMODELING WORK.

I. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS FROM AUTHORITIES HAVING JURISDICTION AND PAY ALL ASSOCIATED FEES.

GENERAL NOTES:

NOTES BY SYMBOL " ":

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 6

:09

:18

PMED201

EL

EC

TR

ICA

L D

EM

OL

ITIO

N P

LA

N

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

3/16" = 1'-0"1

ELECTRICAL DEMOLITION PLAN

TRUE NORTH0 3' 6' 12'

GRAPHIC SCALE3/16" = 1'-0"

1.5'

1 REMOVE ELECTRICAL DEVICES AND LIGHT FIXTURES IN AREA.RETAIN WIRE AND CONDUIT FOR FUTURE REUSE.

2 REMOVE ELECTRICAL DEVICES ON WALL. RETAIN WIRE ANDCONDUIT FOR FUTURE REUSE.

3 REMOVE EXISTING PANEL. RETAIN FEEDER AND BRANCHCIRCUITS FOR FUTURE REUSE. REFER TO ONELINE DIAGRAMON DRAWINGS E001 FOR ADDITIONAL INFORMATION.

4 REMOVE AND RELOCATE EXISTING PANEL. REFER TO DRAWINGE301 FOR NEW LOCATION.

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 29: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

S

S

S

S

S

S

S

S

S

S

SS

EXIT

SECTION

DETAIL SYMBOL

SUBTITILE

RISER DIAGRAMSYMBOL

ELECTRICAL ABBREVIATIONS

WIRING METHOD NOTES:

ELECTRICAL CONVENTIONS

DRAWING SYMBOLS

GENERAL NOTES

LIGHTING SYMBOLS

ELECTRICAL SYMBOLS DATA SYMBOLS

XX

XX-X

XX-X

XP

FACP

ADA AMERICANS WITH DISABILITIES ACTABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFGAIR HANDLING UNITAHU

AIC

ABOVE FINISHED CEILINGAFC

APPROXIMATE OR APPROXIMATELYALTERNATEALT

APPROX

AMERICAN WIRE GAGE

ARCHITECTAUTOMATIC TRANSFER SWITCHAUXILIARY

ARCHATSAUXAWG

BELOW FINISHED CEILINGBFCBELOW FINISHED GRADEBFGBUILDINGBLDGCONDUIT OR TUBINGCCABLE TELEVISIONCATVCIRCUIT BREAKERCBCLOSED-CIRCUIT TELEVISIONCCTVCIRCUITCKTCEILINGCLGCOMMUNICATIONSCOMM

DIRECT CURRENTDCCURRENT TRANSFORMER(S)CT(S)

DISCONNECTDISCDOUBLE-POLE, DOUBLE THROWDPDTDOUBLE POLE, SINGLE THROWDPSTDRAWING(S)DWG(S)EMPTY CONDUIT OR TUBINGEC

EGS ENGINE-GENERATOR SETEHH ELECTRICAL HANDHOLEELEV ELEVATIONEMERG EMERGENCYEMH ELECTRICAL MANHOLEEMT ELECTRICAL METALLIC TUBING

EXISTINGELECTRICAL WATER COOLER

EXEWC

FUSE(S)FFIRE ALARM ANNUNCIATOR PANELFAAPFIRE ALARM CONTROL PANELFACPFURNISHED BY OWNERFBOFLOORFLFULL LOAD AMPERE(S)FLAFLEXIBLEFLEX

FS

FULL VOLTAGE, NON-REVERSINGFVNRFULL VOLTAGE, REVERSINGFVRGROUNDGGROUND FAULT CIRCUIT INTERRUPTGFCI

HIGH INTENSITY DISCHARGEHIDHAND-OFF-AUTOMATICHOAHORSEPOWERHPHIGH PRESSURE SODIUMHPS

HVAC

HERTZIESHZ

ISOLATED GROUNDIGINTERMEDIATE METALLIC CONDUITIMC

JBOX JUNCTION BOXKILOAMPERE(S)KA

KW KILOWATTS(S)KWH KILOWATT-HOUR(S)KV KILOVOLT(S)KVA KILOVOLT-AMPERE(S)KVAR KILOVOLT-AMPERE(S) REACTIVE

LPS LOW PRESSURE SODIUMLIGHTINGLTGMETER(S)mMAXIMUMMAX

MAIN CIRCUIT BREAKERMCBMOTOR CONTROL CENTERMCCMOTOR CIRCUIT PROTECTORMCPMETAL HALIDEMHMICROPHONEMICMINIMUMMINMAIN LUGS ONLYMLOMILLIMETER(S)mmMANUAL MOTOR STARTERMMS

MANUAL TRANSFER SWITCHMTSMEGAVOLT-AMPERE(S)MVAMEGAVOLT-AMPERE(S) REACTIVEMVAR

MW MEGAWATT(S)NC NORMALLY CLOSED

NATIONAL ELECTRICAL CODENECNEMA

NATIONAL FIRE PROTECTION ASSOCIATIONNFPANON-FUSIBLE SAFETY SWITCHNF

NOT IN CONTRACTNIC

NORMALLY OPENNONOT TO SCALENTSOVERHEADOH

P POLE(S)PA PUBLIC ADDRESS SYSTEMPF POWER FACTORPL PILOT LIGHTPNL PANELBOARDPVC POLYVINYL CHLORIDERC REMOTE CONTROLRCP REFLECTED CEILING PLANRCPT RECEPTACLES(S)RGS RIGID GALVANIZED STEELRVSS REDUCED VOLTAGE, SOLID STATESF SQUARE FOOT OR FEETSPDT SINGLE-POLE, DOUBLE-THROWSPST SINGLE-POLE, SINGLE-THROWSS START-STOPSW SWITCHSWBD SWITCHBOARDTA TRIP AMPERE(S)

TAS TEXAS ACCESSIBILITY STANDARDSTELEPHONETELTEMPORARYTEMPTEXAS UTILITIES ELECTRICTUTELEVISIONTVTYPICALTYP

UG UNDERGROUNDUL UNDERWRITERS LABORATORIES, INC.UPS UNINTERRUPTIBLE POWER SUPPLY

VARIABLE FREQUENCY DRIVE

VOLT-AMPERE(S)

VFD

VAV VOLTAGE OR VOLT(S)

W/OW/

WITHOUTWITH

WPW

WEATHERPROOFWATT(S)

XFMRXP

TRANSFORMEREXPLOSION-PROOF

#

DELTA

NUMBER

WIRE SIZES ARE INDICATED BY AMERICAN WIRE GAGE OR CIRCULAR MILS.

NOTES BY SYMBOL APPLY TO DRAWING ON WHICH AND WHERE SYMBOL APPEARS.

2

3

4

K

P

T

WP

ALL DIMENSIONS GIVEN SHALL BE INTERPRETED AS DIMENSIONTO THE TOP OF THE ELECTRICAL BOX IN ACCORDANCE WITH ADA.

S

1. DO NOT COMBINE NEUTRALS AND GROUNDS OF SEPARATE

BRANCH CIRCUITS.

2. WIRE SHALL BE COPPER THWN - SOLID FOR SIZES 12, 10, 8;

STRANDED FOR SIZES 6 AND LARGER.

D

NIGHT LIGHTNL

INDICATES FIXTURE TYPE - SEE LIGHT FIXTURE SCHEDULE

INDICATES PANEL CIRCUIT

LIGHTING FIXTURE

2-SPEED, CONSEQUENT POLE2SCP2SSW 2-SPEED, SEPARATE WINDING

AMPERE(S)ALTERNATING CURRENTAIR-COOLED CONDENSING UNITACCU

ACA

AMPERE INTERRUPTINGCAPACITY(ROOT MEAN SQUARESYMMETRICAL)

ILLUMINATING ENGINEERINGSOCIETY OF NORTH AMERICA

NATIONAL ELECTRICALMANUFACTURER'S ASSOCIATION

FUSIBLE SAFETY SWITCHOR FUSIBLE SWITCH

(ALL ABBREVIATIONS MAY NOT APPEAR ON DRAWINGS.)

SINGLE-POLE SWITCH WITH WEATHERPROOF COVERPLATEAT 48" ABOVE FINISHED GRADE OR FLOOR UNO

TIME SWITCH AT 48" ABOVE FINISHEDFLOOR UNO.

SINGLE-POLE SWITCH AND PILOT LIGHT AT48" ABOVE FINISHED FLOOR UNO.

KEY-OPERATED SWITCH AT 48" ABOVEFINISHED FLOOR UNO.

FOUR-WAY SWITCH AT 48" ABOVE FINISHEDFLOOR UNO.

THREE-WAY SWITCH AT 48" ABOVE FINISHEDFLOOR UNO.

TWO-POLE SWITCH AT 48" ABOVE FINISHEDFLOOR UNO.

SINGLE-POLE DIMMING SWITCH AT 48" ABOVEFINISHED FLOOR UNO.

SINGLE-POLE SWITCH AT 48" ABOVE FINISHEDFLOOR UNO.

SINGLE POLE SWITCH AT 48" ABOVE FINISHEDFLOOR WITH SECURITY DETENTION PLATE.

(ALL CONVENTIONS MAY NOT APPEAR ON DRAWINGS.)

GENERAL NOTES APPLY TO ELECTRICAL DRAWING SET.

DRAWING NOTES APPLY TO DRAWING ON WHICH NOTE APPEARS.

TYPICAL LIGHTING NOTATIONS SHOWN ON LIGHTING PLAN:

CENTER LINE

NUMBER OF POLES

RATING OF SWITCH

RATING OF FUSES OR NON-FUSIBLE

NEMA ENCLOSURE TYPE.

3P/60A/NF/3R

DISCONNECT SWITCH

MAXIMUM CURRENT AMPACITYMCA

MAXIMUM OVER-CURRENT PROTECTIONMOCP

HEATING AND AIR CONDITIONING RATINGHACR

HEATING, VENTILATION ANDAIR CONDITIONING

TYPICAL POWER NOTATIONS SHOWN ON POWER PLAN:

UNO UNLESS NOTED OTHERWISE

E/R EXISTING TO BE REMOVED ANDREINSTALLED AFTER MODIFICATION

INDICATES SWITCH ASSOCIATED WITH FIXTURE

FIRE ALARM REQUIREMENTS

TBPE POLICY ADVISORY: PER THE POLICY ADVISORY OPINION 04-04-FA

PLANNING OF FIRE ALARM SYSTEMS ISSUED BY THE TEXAS BOARD OF

PROFESSIONAL ENGINEERS AND LAND SURVEYORS (TBPELS), THE

FOLLOWING STATEMENT IS MADE: THE LICENSED ENGINEER OF RECORD FOR

THIS PROJECT WILL NOT PREPARE FIRE ALARM SYSTEM DRAWINGS NOR SHOW

FIRE ALARM SYSTEM DEVICES ON THE ELECTRICAL DRAWINGS. PROVIDE A

COMPLETE AND AUTOMATIC BUILDING FIRE ALARM SYSTEM. THE FIRE ALARM

PLANNER SHALL BE LICENSED BY THE STATE FIRE MARSHALL'S OFFICE. THE

PLANNING OF THE FIRE ALARM SYSTEM SHALL MEET ALL CRITERIA STATED IN

THE TBPE POLICY ADVISORY OPINION. SUGGESTED LOCATION OF FIRE ALARM

AND ALARM ANNUNCIATOR PANEL ARE SHOWN ON THESE PLANS BASED ON

OWNER PREFERENCE. CONTRACTOR SHALL CONFIRM EXACT LOCATION AND

QUANTITIES WITH THE FIRE MARSHALL. REFER TO SPECIFICATION 283111 FOR

REQUIREMENTS.

LB-3,5 PANELBOARD, SWITCHBOARD OR MOTOR CONTROLCENTER CIRCUIT DESIGNATION

A. THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS

FROM AUTHORITY HAVING JURISDICTION AND PAY ALL ASSOCIATED FEES.

B. LOCATE JUNCTION AND PULL BOXES AS REQUIRED TO ALLOW ACCESS

AFTER EQUIPMENT AND APPURTENANCES ARE INSTALLED. COORDINATE

LOCATIONS AND ELEVATIONS OF ELECTRICAL DEVICES WITH DRAWINGS

AND OTHER TRADES PRIOR TO INSTALLATION.

C. PROTECT PERMANENT BUILDING FIXTURES FROM DAMAGE DURING

CONSTRUCTION PERIOD. PROVIDE PLYWOOD OR SIMILAR MATERIAL

UNDER EQUIPMENT OR MATERIALS STORED ON FLOORS AND IN AREAS

WHERE CONSTRUCTION MAY DAMAGE FINISHES. SURFACES OR FINISHES

DAMAGED DURING CONSTRUCTION SHALL BE REPLACED AT THE COST

OF THE CONTRACTOR.

D. CONTRACTOR SHALL COORDINATE LOCATIONS OF FIXTURES AND

ELECTRICAL DEVICES INSTALLED IN OR ON THE CEILING WITH

ARCHITECTURAL REFLECTED CEILING PLAN. CEILING MOUNTED

ELECTRICAL DEVICES SHALL BE MOUNTED IN THE CENTER OF THE TILES,

UNLESS OTHERWISE NOTED.

E. PROPERLY SUPPORT LOW VOLTAGE WIRING CABLING NOT IN CONDUIT

PER CODE. IN AREAS SUCH AS CORRIDORS DESIGNATED FOR NEW

CEILINGS AND FINISHES, SUPPORT EXISTING ELECTRICAL DEVICES AND

EQUIPMENT IN AND ABOVE THE CEILING, INCLUDING CONDUIT AND

CABLING. PROVIDE PROPER PERMANENT SUPPORT AS NEEDED TO

COMPLY WITH CODE AND TAKE WEIGHT OFF CEILING SUPPORTS.

REMOVE AND REINSTALL ELECTRICAL DEVICES AND EQUIPMENT AS

NEEDED FOR PAINTING, WALL COVERINGS, CEILINGS, AND FINISH WORK.

REFER TO ARCHITECTURAL DRAWINGS.

F. BRANCH CIRCUITS OVER 75 FEET (25 METERS) IN LENGTH (TOTAL ONE

WAY) FROM THE PANEL, THE ELECTRICAL CONTRACTOR SHALL

CALCULATE THE VOLTAGE DROP AND PROVIDE AN APPROPRIATE

CONDUCTOR SIZE TO ACHIEVE NO MORE THAN 3% MAXIMUM ALLOWABLE

VOLTAGE DROP.

G. DO NOT SCALE THE DRAWINGS. BECAUSE OF THE SCALE OF THE

DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS OR

OTHER SIMILAR ITEMS WHICH MAY BE REQUIRED TO MAKE A COMPLETE

OPERATING SYSTEM. CAREFULLY INVESTIGATE CONDITION AFFECTING

WORK AND INSTALL WORK IN SUCH A MANNER THAT INTERFERENCES

BETWEEN PIPES, CONDUIT, DUCT, EQUIPMENT, ARCHITECTURAL AND

STRUCTURAL FEATURES SHALL BE AVOIDED.

H. ALL EXITS LIGHTS SHALL HAVE THEIR NORMAL BRANCH CIRCUIT WIRING

TIED INTO THE LOCAL LIGHTING CIRCUIT IN THE AREA FOR WHICH THEY

SERVE, AHEAD OF ALL SWITCHING.

I. WHERE ELECTRICAL DEVICES ARE MOUNTED IN A GRID CEILING, THEY

SHALL BE MOUNTED IN THE CENTER OF THE CEILING TILE UNLESS

OTHERWISE NOTED.

J. ALL LAY-IN TYPE FIXTURES SHALL BE PROVIDED WITH A RED SAFETY

CABLE SUPPORTED FROM THE STRUCTURE OF BUILDING.

K. ALL DEVICES, EQUIPMENT, FIXTURES AND THE LIKE MUST BE GROUNDED

BY USE OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL

AND ELECTRICAL BONDS OF METALLIC RACEWAY SYSTEMS SHALL BE

MAINTAINED.

L. PROVIDE CIRCUIT, CONDUIT, WIRE, DISCONNECT SWITCH,

OVERCURRENT AND SHORT CIRCUIT PROTECTION FOR ALL EQUIPMENT,

WHETHER SHOWN ON THE DRAWINGS OR NOT, INCLUDING, MOTORIZED

DAMPERS, SMOKE DAMPERS, ELECTRIC HEAT TRACE, POWER FOR

ENERGY MANAGEMENT SYSTEM, WATER SOFTENING EQUIPMENT, WATER

TREATMENT SYSTEMS, AIR DRYERS, ELECTRIC FLUSH VALVES, ELECTRIC

TRAP PRIMERS, ELECTRIC SOLENOIDS, SHOWER VALVES, AND OTHER

MISCELLANEOUS EQUIPMENT. WITH NO ADDITIONAL COST TO THE

OWNER.

M. REFER TO MECHANICAL PLANS FOR EXACT LOCATION OF MECHANICAL

EQUIPMENT AND LOCATE DISCONNECT SWITCHES IN ACCORDANCE WITH

THE N.E.C.

N. REFER TO MECHANICAL SPECIFICATIONS, HVAC PLANS AND PLUMBING

PLANS FOR ADDITIONAL ELECTRICAL WORK AND REQUIREMENTS.

O. REFER TO CONTROL SCHEMATICS ON THE MECHANICAL DRAWINGS FOR

ADDITIONAL CONTROL WIRING AND CONTROL CONNECTIONS.

P. UNLESS OTHERWISE NOTED, ALL DEVICE ELEVATIONS REFER TO THE

CENTERLINE OF BACK BOX. THE CONTRACTOR SHALL COORDINATE ALL

BOX LOCATIONS WITH OTHER TRADES.

Q. PROVIDE 'SEAL-OFFS' WHEN CONDUIT PASSES THROUGH AREAS OF

DIFFERENT AMBIENT TEMPERATURES AND/OR HAZARDOUS AREAS.

R. IF MORE THAN THREE CURRENT-CARRYING CONDUCTORS ARE ROUTED

IN THE SAME CONDUIT, DERATING SHALL BE TAKEN INTO ACCOUNT.

INCREASING THE CONDUCTOR AMPACITY (BY INCREASING WIRE SIZE) TO

COMPENSATE AS FOLLOWS:

NO. OF CONDUCTORS AMPACITY INCREASE4 THRU 6 125%7 THRU 9 145%

10 THRU 20 (MAX) 200%

THE CONDUIT SIZE (CAPACITY) SHALL ALSO BE INCREASED TO CONFORM

TO N.E.C., CHAPTER 9.

S. ALL FIRE ALARM DEVICES SHALL BE MOUNTED AT HEIGHTS AS SPECIFIED

BY THE NFPA 70 AND ADA.

T. PROVIDE PHASE-LOSS RELAYS ON ALL NEW THREE PHASE MECHANICAL

EQUIPMENT 1 HP AND LARGER TO PREVENT SINGLE PHASING.

COORDINATE WITH MECHANICAL EQUIPMENT CONTRACTOR.

U. ALL BREAKERS USED TO FEED MECHANICAL EQUIPMENT SHALL BE 'HACR'

TYPE.

V. ALL EQUIPMENT TO BE CONSIDERED 'AS-EQUAL' MUST BE SUBMITTED TO

THE ENGINEER FOR APPROVAL NO LATE THAN ONE (1) WEEK PRIOR TO

BID DATE.

W. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITH ALL

TRADES FOR SUBSTITUTED EQUIPMENT FROM THIS DESIGN.

UNCOORDINATED CHANGES THAT OCCUR FROM A SUBSTITUTION WILL BE

THE CONTRACTORS RESPONSIBILITY TO ABSORB THE COST AND NOT

PASS ONTO THE OWNER.

X. PROVIDE PROTECTION IN FIRE RATED WALL MEMBRANE PENETRATIONS.

PROTECTION SHALL WRAP THE OUTSIDE OF THE BOX OR ENCLOSURE TO

MAINTAIN WALL FIRE RATING. DO NOT USE PENETRATION PROTECTION

ON THE INTERIOR OF BOX/ENCLOSURE OR COVER PLATE TYPE

PROTECTION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

Y. ALL LOW VOLTAGE CABLING (FIRE ALARM, DATA, TEMPERATURE

CONTROLS, ETC.) LOCATED IN EXPOSED STRUCTURAL AREAS SHALL BE

INSTALLED IN CONDUIT AND ROUTED TIGHT TO DECK. INSTALLATIONS

NOT IN COMPLIANCE WITH THIS REQUIREMENT SHALL BE REMOVED AND

REINSTALLED AT THE CONTRACTORS EXPENSE.

Z. CONTRACTOR SHALL COMPLY WITH APPLICABLE ENERGY CODE.

AA. ALL MECHANICAL EQUIPMENT AND MOTOR CONTROLLERS SHALL BE

PROVIDED WITH AN APPROPRIATE SHORT CIRCUIT CURRENT RATING

(SCCR) FACTORY INSTALLED LABEL. THE LABEL SHALL INDICATE THE

AVAILABLE SHORT CIRCUIT CURRENT AT THAT PIECE OF EQUIPMENT AS

REQUIRED BY N.E.C. 440.10 AND N.E.C. 430.8.

AB. PER DIVISION 26 SPECIFICATIONS, THE CONTRACTOR SHALL PERFORM A

SHORT CIRCUIT STUDY AND PROVIDE A SUMMARY OF THE CALCULATIONS

TO THE MECHANICAL CONTRACTOR. THIS INFORMATION SHALL BE

INCLUDED WITH THE MECHANICAL EQUIPMENT SUBMITTALS. SUBMITTALS

WILL NOT BE ACCEPTED WITHOUT SCCR INFORMATION AND EQUIPMENT

ORDERED PRIOR TO REVIEW OF THE SCCR DATA IS DONE SO AT THE

CONTRACTORS RISK. CONTRACTOR SHALL COORDINATE BETWEEN

TRADES AS REQUIRED.

(ALL CONVENTIONS MAY NOT APPEAR ON DRAWINGS.)

CEILING-MOUNTED SURFACE OR SUSPENDEDSINGLE-FACE EXIT SIGN WITH DIRECTIONALARROW AS INDICATED; SHADED QUADRANTINDICATES FACE OF SIGN.

CEILING-MOUNTED SURFACE OR SUSPENDEDDOUBLE-FACE EXIT SIGN WITH DIRECTIONALARROWS AS INDICATED; SHADED QUADRANTINDICATES FACES OF SIGN.

WALL-MOUNTED EXIT SIGN WITH DIRECTIONALARROW(S) AS INDICATED; SHADEDQUADRANT(S) INDICATE FACE(S) OF SIGN.

EMERGENCY LIGHT FIXTURE

(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)

WP

GFI

IG

n

S

SINGLE RECEPTACLE; NEMA 5-20R AT 18"ABOVE FINISHED FLOOR UNO.

DUPLEX RECEPTACLE; NEMA 5-20R AT 18"ABOVE FINISHED FLOOR UNO.

QUADRAPLEX RECEPTACLE; NEMA 5-20R AT 18"ABOVE FINISHED FLOOR UNO.

RECEPTACLE W/WEATHERPROOF COVERPLATE;DUPLEX NEMA 5-20R 18" ABOVE FINISHEDGRADE OR FLOOR UNO.

DUPLEX RECEPTACLE WITH DETENTION PLATE

GROUND-FAULT CIRCUIT INTERRUPTERRECEPTACLE; DUPLEX NEMA 5-20R 18" ABOVEFINISHED GRADE OR FLOOR UNO.

ISOLATED GROUND RECEPTACLE; DUPLEX NEMA5-20R AT 18" ABOVE FINISHED FLOOR UNO

RECEPTACLE MOUNTED n INCHES ABOVEFINISHED FLOOR OR GRADE; NEMA 5-20R UNO

SPECIAL-PURPOSE RECEPTACLE; SEE SPECIAL-PURPOSE RECEPTACLE, CONNECTION ANDFLOOR BOX SCHEDULE ON DRAWING.

HARDWIRE CONNECTION OR PROVISION FORCONNECTION; SEE SPECIAL-PURPOSERECEPTACLE, CONNECTION AND FLOOR BOXSCHEDULE ON DRAWING.

MULTIOUTLET ASSEMBLY

B

B

FLOOR-MOUNTED DUPLEX RECEPTACLEAND DATA CONNECTION.

RECEPTACLE 208 VOLT.

(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.) (ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)

DUCT SMOKE DETECTORD

NON FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

LOW VOLTAGE PANEL

HIGH VOLTAGE PANEL

PUSHBUTTON

D ELECTRIC DOOR OPENER

2

JUNCTION BOX

TRANSFORMER

CIRCUIT BREAKER

COMBINATION DISCONNECT SWITCH/MOTORSTARTER.

MOTOR SYMBOL; THE NUMBER INSIDEINDICATES HP.

SECURITY CAMERA

TV

TELEVISION DATA OUTLET; SINGLE GANG 2.5"DEEP BOX AT 72" AFF, UNLESS NOTEDOTHERWISE, (WITH 1" CONDUIT TO ABOVENEAREST CEILING) AND ADJACENT NEMA 5-20RDUPLEX RECEPTACLE.

F0

WP

SP

DATA SYSTEM JACK; SINGLE GANG BOX AT 18"AFF WITH 1" CONDUIT TO ABOVE NEARESTACCESSIBLE CEILING; SUBSCRIPTED # INDICATES AMOUNT OF NETWORK DROPS

TELEPHONE SYSTEM VOICE JACK; SINGLE GANGBOX AT 18" AFF WITH 1" CONDUIT TO ABOVENEAREST ACCESSIBLE CEILING; SUBSCRIPTED # INDICATES AMOUNT OF NETWORK DROPS

COMBINATION VOICE AND DATA JACK; 1-GANGBOX AT 18" AFF WITH 1" CONDUIT TO ABOVENEAREST ACCESSIBLE CEILING; SUBSCRIPTED # INDICATES AMOUNT OF NETWORK DROPS

DATA SYSTEM FIBER OPTIC JACK; SINGLE GANGBOX AT 18" AFF WITH 1" CONDUIT TO ABOVENEAREST ACCESSIBLE CEILING; SUBSCRIPTED# INDICATES AMOUNT OF NETWORK DROPS

WALL PHONE. VOICE AND DATA JACK; 1-GANGBOX AT 48" AFF WITH 1" CONDUIT TO ABOVENEAREST ACCESSIBLE CEILING; SUBSCRIPTED# INDICATES AMOUNT OF NETWORK DROPS

OCCUPANCY SENSOR "SWITCH PACK" OR"POWER PACK" REFER TO DETAIL 8 ON SHEET E3

REMOTE DOOR UNLOCK PUSH BUTTON

CONTROLLED DOOR

OVERHEAD DOOR CONTROLLER

SOUND SYSTEM SPEAKER; CEILING-MOUNTED2-GANG, 4" DEEP BOX WITH 1" CONDUIT TOABOVE NEAREST ACCESSIBLE CEILING

SOUND SYSTEM DEVISE; SEE SOUNDSYSTEM DEVICE SCHEDULE ON DRAWINGS.

CLOCK SYSTEM SINGLE RECEPTACLE; NEMA5-15R AT 80" ABOVE FINISHED FLOOR UNO.

WIRELESS ACCESS POINT

FIRE ALARM CONTROL PANEL

2' x 4' LUMINARE

CARD READERCR

6"

FINISHED FLOOR

ADA MINIMUM HEIGHT

COUNTER HEIGHT

TOP OF BACKSPLASH

PANELBOARDOR CABINET

ADA MAXIMUM OBSTRUCTED

ADA MAXIMUM UN OBSTRUCTED

FOR THE ITEMS BELOWFINISHED CEILING

REFER TO ARCHITECT

18"

43"

84" 84" 84" 84"

12" MIN

B S

F FAA

LA-1

(ALL SYMBOLS MAY NOT APPEAR ON DRAWINGS.)

RISER NUMBER

POINTS TO RISER AREA

NUMBER

DESCRIPTION

SCALE

DETAIL #

DRAWING NO. TO REFER TO

SECTION NUMBER

DRAWING NUMBER WHERESECTION IS LOCATED

X

Ax

J

S

#

#

#

#

#

WAP

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

NTS

9/1

/20

21 6

:09

:13

PME000

LE

GE

ND

AN

D G

EN

ER

AL

NO

TE

S -

EL

EC

TR

ICA

L

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 30: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

EXISTINGPANEL

LA2(225A)

M

TO EXISTING UTILITYTRANSFORMER

225AT225AF

225AT225AF

225AT225AF

100AT100AF

EXISTING METER208Y/120V, 3P, 4W

EXISTINGPANEL

UNDERGROUND CONDUITS

EXISTINGPANEL

LA1(225A)

1

NOTES BY SYMBOL:

1. PROVIDE NEW PANEL. RECONNECT ALL BRANCH

CIRCUITS NOT REMOVED DURING DEMOLITION.

2. RELOCATED EXISTING PANEL AS SHOWN ON E301.

EXTEND CONDUIT AND WIRE AS REQUIRED TO

MATCH EXISTING.

3. SEAL ANY MISSING KNOCKOUTS ON PANEL.

EXISTINGPANEL

LA3

2

3 3 3 3EXISTING

PANELLA2

(225A)

M

EXISTING METER208Y/120V, 3P, 4W

225AT225AF

225AT225AF

225AT225AF

100AT100AF

TO EXISTING UTILITYTRANSFORMER

EXISTINGPANEL

UNDERGROUND CONDUITS

EXISTINGPANEL

LA1(225A)

1

NOTES BY SYMBOL:

1. REMOVE EXISTING PANEL. RETAIN AND

RECONNECT ALL BRANCH CIRCUITS NOT REMOVED

DURING DEMOLITION TO NEW PANEL.

2. RETAIN EXISTING WIRE AND CONDUIT FOR REUSE.

3. RELOCATE EXISTING PANEL. REFER TO 2/E001 AND

E301 FOR ADDITIONAL INFORMATION.

4. VERIFY WHICH DISCONNECT IS CONNECTED TO

EXISTING PANELS.

2

EXISTINGPANEL

LA3

3

4 4 4 4

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

NTS

9/1

/20

21 6

:09

:14

PME001

ON

E L

INE

/ S

CH

ED

UL

ES

/ P

AN

EL

BO

AR

DS

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

NTS2 ONELINE DIAGRAM

TOTAL + SPARE 33.4

SPARE 1 AT 0.5 EA = 0.5

TOTAL 14.58 10.69 7.34 32.61 32.92

MISCELLANEOUS 0.50 0.00 0.50 1.00 1.00 1.00

KITCHEN 0.00 0.00 0.00 0.00 0.65 0.00

HEAT 0.00 0.00 0.00 0.00 1.00 0.00

VOLT/PHASE: 208/3 KVA 16.64 9.00

LARGEST MOTOR HP: 15 FLC 46.20 8.00

MOTOR 0.40 0.00 0.00 0.40 NEC 4.56

RECEPTACLE 9.00 7.45 5.76 22.21 NEC 16.11

LIGHTING 4.68 3.24 1.08 9.00 1.25 11.26

LOAD A B C KVA MULT KVA

LOAD... CONN. DESN TOTAL DESIGN AMPS: 92.8

REMARKS: *PROVIDE RED SAFETY BREAKER

TOTALS 5.68 8.82 0.00 0.00 0.00 0.50 0.50 0.00 0.00 0.00 10.43 3.33 TOTALS

83 SPACE - 83 C 84 - SPARE 84

81 SPACE - 81 B 82 - SPARE 82

79 SPACE - 79 A 80 - SPARE 80

77 SPACE - 77 C 78 - SPARE 78

75 SPACE - 75 B 76 - SPARE 76

73 SPACE - 73 A 74 - SPARE 74

71 SPACE - 71 C 72 - SPARE 72

69 SPACE - 69 B 70 - SPARE 70

67 SPACE - 67 A 68 - SPARE 68

65 SPACE - 65 C 66 - SPARE 66

63 SPACE - 63 B 64 - SPARE 64

61 SPACE - 61 A 62 - SPARE 62

59 SPACE - 59 C 60 - SPARE 60

57 SPACE - 57 B 58 - SPARE 58

55 SPACE - 55 A 56 - SPARE 56

53 SPACE - 53 C 54 - SPARE 54

51 SPACE - 51 B 52 - SPARE 52

49 SPARE 20/1 49 A 50 20/1 SPARE 50

47 SPARE 20/1 47 C 48 20/1 SPARE 48

45 RCPT ROOF 20/1 0.40 45 B 46 0.40 20/1 AIR DEVICE J 46

43 IT RACK 30/1 2.16 43 A 44 0.40 20/1 EF-1, EF-2 44

41 SPARE W ATTIC 20/1 41 C 42 0.54 20/1 RCPT 105 42

39 CONTACTER 20/1 1.08 39 B 40 0.54 20/1 RCPT 105 40

37 RCPT 118 20/1 0.72 37 A 38 0.72 20/1 RCPT 120 38

35 RCPT 117 20/1 0.72 35 C 36 1.08 20/1 S WALL PACK & E... 36

33 RCPT 117 20/1 0.72 33 B 34 0.36 20/1 FLOOR BOX 116 34

31 RCPT 115 20/1 0.72 31 A 32 1.08 20/1 SEPTIC SYSTEM 32

29 PROJECTOR 20/1 0.36 29 C 30 20/1 SPARE 30

27 E & S LIGHTS 20/1 1.08 27 B 28 0.54 20/1 RCPT 116 28

25 FLOOR BOX 115 20/1 0.36 25 A 26 0.72 20/1 RCPT 116 26

23 SPARE BY ATTIC... 20/1 23 C 24 0.54 20/1 RCPT 115 24

21 FLOOR BOX 115 20/1 0.36 21 B 22 0.72 20/1 RCPT 115 22

19 TRANL TRAIN 20/1 1.08 19 A 20 1.08 20/1 FRONT CANOPY... 20

17 *FIRE ALARM 20/1 0.50 17 C 18 0.54 20/1 RCPT 115 18

15 RCPT 114 20/1 0.54 15 B 16 0.54 20/1 RCPT 114 16

13 RCPT 113 20/1 0.54 13 A 14 0.50 20/1 TIME CLOCK 14

11 RCPT 108-110 20/1 0.54 11 C 12 0.54 20/1 RCPT 112 12

9 WEST SIGN 20/1 1.08 9 B 10 0.50 20/1 EWC 10

7 UTILITY LIGHT... 20/1 1.08 7 A 8 0.90 20/1 RCPT 108 8

5 RCPT 106-108 20/1 1.08 5 C 6 0.90 20/1 RCPT 102, 108 6

3 RETAIL SCONCE 20/1 1.08 3 B 4 0.75 20/1 RCPT 102 4

1 LTG101-102,106-15 20/1 1.36 1 A 2 1.17 20/1 LTG 103-105,116-130 2

POLE LTG RCPT MTR HEAT KITC MISC MISC KITC HEAT MTR RCPT LTG POLECKT DESCRIPTION

AMP/ LOA... LOA... AMP/DESCRIPTION CKT

MOUNTING: SURFACE VOLTAGE: 208 /120V 3PH, 4W

MAIN SIZE: 225 A MAIN TYPE: MLO SECTION 1 PANEL NAME: LA1

NEW PANELBOARD SCHEDULE

TOTAL + SPARE 59.9

SPARE 0 AT 0.5 EA = 0.0

TOTAL 22.47 21.07 18.63 62.17 59.88

MISCELLANEOUS 0.00 0.00 0.00 0.00 1.00 0.00

KITCHEN 0.00 0.00 0.00 0.00 0.65 0.00

HEAT 0.00 0.00 0.00 0.00 1.00 0.00

VOLT/PHASE: 120/1 KVA 1.66 3.00

LARGEST MOTOR HP: 1 FLC 13.80 2.00

MOTOR 16.71 15.67 15.21 47.59 NEC 47.59

RECEPTACLE 5.76 5.40 3.42 14.58 NEC 12.29

LIGHTING 0.00 0.00 0.00 0.00 1.25 0.00

LOAD A B C KVA MULT KVA

LOAD... CONN. DESN TOTAL DESIGN AMPS: 166.2

REMARKS:

TOTALS 0.00 4.68 34.70 0.00 0.00 0.00 0.00 0.00 0.00 12.89 9.90 0.00 TOTALS

41 SPACE - 41 C 42 - SPACE 42

39 1.50 39 B 40 0.18 20/1 RP-1 40

37UH-01 20/2

1.50 37 A 38 1.04 38

35 3.00 35 C 36 1.0415/2 CU-AC-1

36

33 3.00 33 B 34 1.08 20/1 TMV 34

31

WH-1 30/3

3.00 31 A 32 0.36 20/1 VH-A, VH-B, VH-C 32

29 RCPT 130 20/1 0.54 29 C 30 0.36 20/1 UNDER FRIDGE 30

27 RCPT 130 20/1 0.54 27 B 28 0.36 20/1 FRIDGE 28

25 RCPT 126,128,129 20/1 0.72 25 A 26 1.08 20/1 DSFAND PLUGS 26

23 RCPT 126 20/1 0.72 23 C 24 0.72 20/1 RCPT 121, 123, 125 24

21 RCPT 122 20/1 1.08 21 B 22 0.72 20/1 RCPT 121 DESK 22

19 RCPT 122 20/1 1.08 19 A 20 1.08 20/1 RCPT 121 DESK 20

17 2.52 17 C 18 0.36 20/1 FLOOR BOX 121 18

15 2.52 15 B 16 0.72 20/1 RCPT 121 16

13

5 TON 35/3

2.52 13 A 14 0.72 20/1 RCPT 104 14

11 2.52 11 C 12 0.72 20/1 RCPT 103 12

9 2.52 9 B 10 0.72 20/1 RCPT 103 10

7

3 TON 35/3

2.52 7 A 8 0.72 20/1 RCPT 103 8

5 2.52 5 C 6 3.60 6

3 2.52 3 B 4 3.60 4

1

3 TON 35/3

2.52 1 A 2 3.60

50/3 10 TON

2

POLE LTG RCPT MTR HEAT KITC MISC MISC KITC HEAT MTR RCPT LTG POLECKT DESCRIPTION

AMP/ LOA... LOA... AMP/DESCRIPTION CKT

MOUNTING: SURFACE VOLTAGE: 208 /120V 3PH, 4W

MAIN SIZE: 225 A MAIN TYPE: MLO SECTION 1 PANEL NAME: LA2

EXISTING PANELBOARD SCHEDULE

NTS1 ONELINE DEMOLITION DIAGRAM

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 31: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

9/1

/20

21 6

:09

:14

PME002

SC

HE

DU

LE

S

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION VOLTS LAMPS WATTS

A1 RECESSED 2 X 2 ACRYLIC BASKET TROFFER, APPROX. 2400 LUMENS, 3500K COLOR

TEMPERATURE, 0-10V DIMMING

METALUX 22CZ-LD4-24-UNV-L835-CD1-U

LITHONIA 2BLT2 33L ADP EZ1 LP840

COLUMBIA LCAT22-40MLG-EDU

120 LED 19

A2 RECESSED 2 X 2 ACRYLIC BASKET TROFFER, APPROX. 3900 LUMENS, 3500K COLOR

TEMPERATURE, 0-10V DIMMING

METALUX 22CZ-LD4-39-UNV-L835-CD1-U

LITHONIA 2BLT2 33L ADP EZ1 LP840

COLUMBIA LCAT22-40MLG-EDU

120 LED 29

A3 RECESSED 2 X 2 ACRYLIC BASKET TROFFER, APPROX. 4400 LUMENS, 3500K COLOR

TEMPERATURE, 0-10V DIMMING

METALUX 22CZ-LD4-44-UNV-L835-CD1-U

LITHONIA 2BLT2 33L ADP EZ1 LP840

COLUMBIA LCAT22-40MLG-EDU

120 LED 34

B1 RECESSED 2 X 4 ACRYLIC BASKET TROFFER, APPROX. 4000 LUMENS, 3500K COLOR

TEMPERATURE, 0-10V DIMMING

METALUX 24CZ-LD5-40-UNV-L840-CD-1-U

LITHONIA 2BLT4 40L ADP EZ1 LP835

COLUMBIA LCAT-24-40-FK24-VW-G-ED-U

120 LED 32

B2 RECESSED 2 X 4 ACRYLIC BASKET TROFFER, APPROX. 4600 LUMENS, 3500K COLOR

TEMPERATURE, 0-10V DIMMING

METALUX 24CZ-LD5-46-UNV-L840-CD-1-U

LITHONIA 2BLT4 40L ADP EZ1 LP835

COLUMBIA LCAT-24-40-FK24-VW-G-ED-U

120 LED 35

R1 RECESSED 6" LED CAN, APPROX. 1500 LUMENS, 4000K COLOR TEMPERATURE,

WHITE REFLECTOR TRIM, 0-10VDIMMING DRIVER

ELITE HH6-LED-1500L-DIM10-120-ND-40K-HH6-6501-CL-WH

HALO COMM HC6-15-D010-HM6-12-840-61-ND-C

LITHONIA LDN6 40/20 6AR LSS 120 EZ10 TRW

120 LED 18

V1 3' VANITY LIGHTING, 3500K COLOR TEMPERATURE

STUDIO M SPEC SM562006SN

LITHONIA FMVCSL 36IN MVOLT 30K 90CRI BN

120 LED 30

X1 SINGLE/DUAL FACE EDGE LIT EXIT SIGN WITH GREEN LED LAMPS, UNIVERSAL

ARROWS, UNIVERSAL MOUNTING, ALUMINUM HOUSING, NI CAD BATTERY, SELF

DIAGNOSTICS

LITHONIA EDG G EL SD

DUALLITE LES G NEI

SURELITES EUX7-G-SD

120 LED 4

X2 EXTERIOR EGRESS EMERGENCY LIGHT, MOUNT 6" ABOVE DOOR FRAME, BRONZE

FINISH, SELF POWEREDBATTERY BACKUP

LITHONIA AFF UVOLT LTP SDRT WT

DUALLITE PCZ

EVENLITE MOE BB 7 B

120 LED 4

NOTES:

1 ALL LIGHT FIXTURES SHALL BE CONTROLLED BY A DIGITAL CONTROL SYSTEM TO MEET

CODE.

2 EXIT SIGNS SHALL BE UNIVERSAL MOUNT WITH UNIVERSAL ARROWS.

3 ALL REQUESTS FOR SUBSITUTIONS/ALTERNATES MUST BE SUBMITTED 10 WORKING DAYS

PRIOR TO BID DATE.

4 ALL SUBMISSIONS SHALL INCLUDE DETAILED CUT SHEETS AND PERFORMANCE DATA FOR

CONSIDERATION.

5 ALL STATED WATTAGE IN FIXTURE SCHEDULE SHALL BE PLACED ON FIXTURES AT AND BY

THE FACTORY.

6 ALL LED DRIVERS ARE SPECIFICATION GRADE, ELECTRONIC <10%THD, DIMMING 100-10%

UNLESS OTHERWISE NOTED.

7 ALL LED COLORS ARE 3500K OR AS STATED.

8 HEIGHTS GIVEN ARE TO BOTTOM OF LIGHT FIXTURE UNLESS OTHERWISE NOTED. SEE

ARCHITECTURAL ELEVATIONS BEFORE INSTALLATION.

9 FINAL LIGHT FIXTURE COLOR FINISH SELECTION SHALL BE BY THE ARCHITECT DURING

SUBMITTAL PHASE.

10 REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND DIGITAL CONTROL

REQUIREMENTS.

RP-1 RECIRC PUMP 120/1 1/6 HP 15/3 3 #12, 1 #12G, 3/4" C 3P/30A/NF/1R

WH-1 ELECTRIC WATER HEATER 208/3 9 KW 30/3 3 #10, 1 #10G, 3/4" C 3P/30A/NF/1R

ITEM DESCRIPTION V/PH KW/HP C/B WIRE & CONDUIT DISCONNECT

PLUMBING EQUIPMENT SCHEDULE

UH-01 RISER 208/1 3 0.5 20/1 2 #12, 1 #12G, 3/4" C -

V/PH KW AMPSITEM SERVES

ELECTRICALC/B WIRE & CONDUIT DISCONNECT

UNIT HEATER SCHEDULE

J JUDGE CHAMBER 120/1 2 20/1 2 #12, 1 #12G, 3/4" C -

V/PH AMPSITEM SERVES

ELECTRICALC/B WIRE & CONDUIT DISCONNECT

AIR DEVICE UNIT SCHEDULE

EF-04 ADA RR 120/1 27 W 0.2 15/1 2 #12, 1 #12G, 3/4" C MANUAL MOTOR STARTER

EF-03 ADA RR 120/1 83 W 0.7 15/1 2 #12, 1 #12G, 3/4" C MANUAL MOTOR STARTER

EF-02 IT 120/1 1/12 HP 0.5 15/1 2 #12, 1 #12G, 3/4" C MANUAL MOTOR STARTER

EF-01 EVIDENCE 120/1 1/12 HP 0.5 15/1 2 #12, 1 #12G, 3/4" C MANUAL MOTOR STARTER

V/PH HP/W AMPSITEM SERVES

ELECTRICALC/B WIRE & CONDUIT DISCONNECT

FAN SCHEDULE

VH-D RELIEF NO POWER REQUIRED

VH-C INTAKE 120/1 2 15/1 2 #12, 1 #12G, 3/4" C -

VH-B INTAKE 120/1 2 15/1 2 #12, 1 #12G, 3/4" C -

VH-A INTAKE 120/1 2 15/1 2 #12, 1 #12G, 3/4" C -

V/PH AMPSITEM SERVES

ELECTRICALC/B WIRE & CONDUIT DISCONNECT

ROOF VENTILATOR SCHEDULE

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 32: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

3

3

3

3 3a

4D

3D

Db

3c

3

4

3

3a

3cDd

4a

3D

b

4a

3a

3D

bNOTES BY SYMBOL " ":

CLERKS

121

CONSTABLE

103

OPEN/FUTURE

VOTING

130

CONFERENCE

112

CONFERENCE

113

JUDGES

CHAMBER

120

COURTROOM

115

IT

122

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

MOP

107

ELEC

111JURY/TRAINING

116

EVIDENCE

104

STORAGE

109

ADA RR

129

CORRIDOR

125

CONSTABLE

105

STORAGE

118

STORAGE

124

AV

117

COURT

114

FOYER

101

CLOSET

119

COORIDOR

123

B1B1

A2

A2

A1 A1

A1

A1

A2B1 B1B1

B1B1B1 B1

B1

B1

B1

B1

B1

B1

B1

B1 B1

A2

B1a

B1a

B1a

B1a

B1a

B1a

B1aB1a

B1a

A2a

A2

A2

B1

B1

B2B2

A2

B2 B2 B2

B1aB1aB1aB1aB1a

B1aB1aB1aB1aB1a

B1aB1aB1aB1aB1a

B1c

B1c B1c

B1c

B1c

A2

A3

A3

R1

R1

R1

R1

R1

R1

R1

R1

R1

R1

R1

R1

R1

R1

B1B1

B1B1

B1B1

R1

V1

V1

V1

V1

V1

V1

V1

V1

A2

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

1

1

1

1

1

1

1

1

2

2

2

1

2

2

2

2

2

2

1

1

1

1 1

B1

LA1-2

LA1-2

LA1-2

LA1-1 LA1-1

LA1-1 LA1-1 LA1-1

LA1-1 LA1-1 LA1-1

LA1-1

LA1-2 LA1-2

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1 LA1-1

LA1-1 LA1-1

LA1-1

LA1-1

LA1-1 LA1-1 LA1-1

LA1-1

LA1-1 LA1-1 LA1-1

LA1-1 LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1 LA1-1

LA1-1 LA1-1

LA1-1 LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-1

LA1-2LA1-2LA1-2

LA1-2

LA1-2LA1-2

LA1-2LA1-2

LA1-2LA1-2

LA1-2LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2 LA1-2

LA1-2

LA1-2

LA1-2

LA1-1

X2

X2 X2 X2

X2

X2

X2X2

A2

LA1-2

R1b

R1b

R1b

LA1-1

LA1-1

LA1-1

A2

A2

LA1-2

LA1-2

R1b

R1b

R1b

R1d

R1d

LA1-2

LA1-2

LA1-2

LA1-2

LA1-2

3D

3a

NL

NL

NL

NL

X2

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 6

:41

:29

PME201

LIG

HT

ING

PL

AN

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

TRUE NORTH

3/16" = 1'-0"1

LIGHTING PLAN

0 6' 12' 24'

GRAPHIC SCALE

3/32" = 1'-0"

3'

1 PROVIDE A CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR.

2 PROVIDE A SWITCH MOUNTED DUAL TECHNOLOGY VACANCY

SENSOR.

GENERAL NOTES:

A REFER TO DRAWING E000 FOR ELECTRICAL LEGEND,

ABBREVIATIONS AND GENERAL NOTES – ELECTRICAL.

B REFER TO DRAWING E001 FOR LIGHTING FIXTURE SCHEDULE.

C THE CONTRACTOR SHALL SUBMIT A FULL SET OF OCCUPANCY

CONTROL LOCATION DRAWINGS SUBMITTALS TO THE A/E PRIOR TO

PURCHASING OR INSTALLATION. OCCUPANCY CONTROL

LOCATIONS AND QUANTITIES SHALL BE BASED ON THE

MANUFACTURE’S RECOMMENDATIONS. THE LIGHTING PLANS SHOW

DESIGN INTENT ONLY AND DO NOT REFLECT EVERY

MANUFACTURER PERMUTATIONS.

D OCCUPANCY CONTROLS SHALL BE WIRED SUCH THAT ALL

GENERAL ROOM LIGHTING IS CONTROLLED.

E ALL EXITS LIGHTS AND SIGNS SHALL HAVE THEIR NORMAL OR

EMERGENCY BRANCH CIRCUIT WIRING TIED INTO THE LOCAL

LIGHTING CIRCUIT IN THE AREA FOR WHICH THEY SERVE, AHEAD OF

ALL SWITCHING.

F PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH

CIRCUIT.

G COORDINATE ALL DEVICE MOUNTING LOCATIONS, HEIGHTS AND

SPACING WITH ARCHITECTURAL FLOOR PLANS AND ELEVATIONS.

BIDDERS SHALL EXAMINE ARCHITECTURAL DRAWINGS TO INCLUDE

ANY NECESSARY COORDINATION COST.

H IN GENERAL, WALL MOUNTED DEVICES AT LOWER HEIGHTS SHALL

BE STACKED DIRECTLY BELOW DEVICES AT HIGHER ELEVATIONS.

PROVIDE CONDUIT OFFSET AS REQUIRED.

I LIMIT CONDUIT ROUTING IN AREAS WITH OPEN CEILINGS TO LOADS

IN THAT AREA. ROUTE CONDUIT IN CONCEALED BULKHEADS WHERE

POSSIBLE. WHERE NOT POSSIBLE, CONDUIT SHALL BE RAN

PARRALLEL AND TIGHT TO STRUCTURE.

J REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LOCATIONS OF LIGHT FIXTURES. CONTRACTORS SHALL

COORDINATE LOCATIONS OF LIGHTS, SPEAKERS, AIR DIFFUSERS,

GRILLES, AND THE LIKE, WITH THE REFLECTED CEILING PLAN.

K REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND/OR

ROOM FINISH SCHEDULE AND VERIFY LIGHT FIXTURE TYPE FOR

CEILING CONSTRUCTION PRIOR TO ORDERING THE FIXTURES.

PROVIDE FIXTURES THAT ARE COMPATIBLE WITH THE CEILING

SYSTEM.

L ALL LAY-IN TYPE FIXTURES SHALL BE PROVIDED WITH A RED

SAFETY CABLE SUPPORTED FROM THE STRUCTURE OF BUILDING.

M CONTRACTOR SHALL CLEAN ALL LIGHT FIXTURES, INSIDE AND OUT,

PRIOR TO FINAL ACCEPTANCE BY OWNER.

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 33: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

UP

DN

WAP

WAP

WAP

WAPWAP

WAP

NOTES BY SYMBOL " ":CLERKS

121

CONSTABLE

103

OPEN/FUTURE

VOTING

130

CONFERENCE

112

CONFERENCE

113

JUDGES

CHAMBER

120

COURTROOM

115

IT

122

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

MOP

107

ELEC

111

JURY/TRAINING

116

EVIDENCE

104

STORAGE

109

ADA RR

129

CORRIDOR

125

CONSTABLE

105

STORAGE

118

STORAGE

124

AV

117

COURT

114

FOYER

101

CLOSET

119

COORIDOR

123

GFCILA1-5

GFCILA1-11

GFCILA1-5

GFCILA2-25

GFCILA2-25

GFCILA2-23

GFCILA2-23

LA2

1

1

1

1

1

1

2

+40"

LA1-4LA1-4

LA1-4

LA1-4 LA1-6 LA1-6 LA1-6

LA1-6

LA1-6

LA1-5 LA1-5

LA1-5

LA1-5

LA1-8

LA1-11

LA1-8

LA1-8

LA1-8

LA1-10

LA1-12

LA1-13

LA1-12

LA1-13

LA1-15

LA1-15LA1-15

LA1-16

LA1-16LA1-16

LA1-18LA1-18

LA1-18

LA1-31 LA1-31

LA1-31

LA1-31

LA1-24

LA1-24

LA1-22

LA1-22

LA1-22

LA1-22

LA1-24

LA1-25

LA1-21

LA1-38

LA1-38

LA1-38

LA1-38

LA1-28

LA1-26LA1-26GFCILA1-26

GFCILA1-26

LA1-28 LA1-28

LA1-34

LA1-37

LA1-37

LA1-37

LA1-37

LA2-14

LA2-14

LA2-14

LA2-14

LA1-40LA1-40

LA1-40

LA1-42

LA1-42

LA1-42

LA2-10

LA2-10 LA2-10 LA2-8 LA2-8

LA2-8

LA2-8

LA2-12LA2-12LA2-12

LA2-12

LA2-16LA2-16LA2-16LA2-16

LA2-20 LA2-20 LA2-20

LA2-22

LA2-22

LA2-18

LA2-24

LA2-24

LA2-24

LA2-24

LA2-25

LA2-25

GFCILA2-23

GFCILA2-23

1

1

LA2-30

LA2-28

LA2-27

LA2-27

LA2-27

LA2-29

LA2-29

LA2-29

LA2-21LA2-21

LA2-21

LA2-19 LA2-19 LA2-19

LA1-29

LA1-11

LA1-35

LA1-35LA1-33

LA1-33

LA1

3

3

33

3

3 3

3

31

1

3333

3

3

3

3 3 3

3

+40"+40" +40" +40" +40"3

2

3

3

3

3

3

3

3

3

3

3

2

2

2

2

4

2

2

2

4

2

2

1

1

1

1

2

2

2

3

3

4

WAP

LA1-43 5

LA1-8

LA3

6

7

8

LA1-6

9

LA2-25

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 6

:09

:16

PME301

PO

WE

R P

LA

N

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

3/16" = 1'-0"1

POWER PLAN

1 MOUNT GFCI RECEPTACLE +44” A.F.F.

2 PROVIDE GFCI BREAKER FOR CIRCUIT INDICATED.

3 PROVIDE FLOOR BOX WITH 2 NETWORK DROPS.

4 PROVIDE FLOOR BOX WITH 4 NETWORK DROPS.

5 PROVIDE CEILING MOUNTED 5-30R RECEPTACLE FOR IT RACK.COORDINATE EXACT LOCATION WITH IT.

6 RELOCATED PANEL. EXTEND WIRE AND CONDUIT TO MATCHEXISTING. VERIFY EQUIPMENT CONNECTED TO PANEL AND FILLOUT PANEL SCHEDULE.

7 PROVIDE 1"C FOR FIBER CABLE.

8 PROVIDE 1"C FOR MICROPHONE WIRING.

9 EXISTING ELECTRICAL METER.

TRUE NORTH0 3' 6' 12'

GRAPHIC SCALE3/16" = 1'-0"

1.5'

GENERAL NOTES:

A REFER TO DRAWING E000 FOR ELECTRICAL LEGEND,ABBREVIATIONS AND GENERAL NOTES – ELECTRICAL.

B REFER TO DRAWING E001 FOR ELECTRICAL RISER DIAGRAMAND E5 SERIES SHEETS FOR SUPPLEMENTAL DETAILS.

C THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATED THEGENERAL EXTENT OF THE WORK. THE CONTRACTOR SHALLPROVIDE ALL PULL BOXES, JUNCTION BOXES ANDINCIDENTAL MATERIALS AND LABOR FOR A COMPLETE ANDFULLY FUNCTIONAL SYSTEM.

D VERIFY REQUIREMENTS OF ALL MECHANICAL EQUIPMENTWITH SHOP DRAWING SUBMITTALS. NOTIFY THE ENGINEEROF ANY CONFLICTS BETWEEN MECHANICAL EQUIPMENTSUBMITTALS AND ELECTRICAL DRAWINGS.

E EACH CIRCUIT SHALL HAVE A DEDICATED NEUTRALCONDUCTOR CONNECTED BACK TO THE PANEL.

F PROVIDE FIRE STOPPING FOR ALL CONDUIT SLEEVES.

G PROVIDE FIRE ALARM POWER SUPPLY PANELS (NAC’S) ASREQUIRED BY THE MANUFACTURER.

H COORDINATE ALL DEVICE MOUNTING LOCATIONS, HEIGHTSAND SPACING WITH ARCHITECTURAL FLOOR PLANS ANDELEVATIONS. BIDDERS SHALL EXAMINE ARCHITECTURALDRAWINGS TO INCLUDE ANY NECESSARY COSTS WITH BID.

I IN GENERAL, DEVICES AT LOWER HEIGHTS SHALL BESTACKED DIRECTLY BELOW DEVICES AT HIGHERELEVATIONS. PROVIDE CONDUIT OFFSET AS REQUIRED.

J ALL FIRE ALARM POWER PANELS (NACS) SHALL BECONNECTED TO A NEW DEDICATED 20A/1P CIRCUITBREAKER IN THE NEAREST 208Y/120V BRANCH PANELBOARDWITH 2#12, #12G, 3/4"C. CONTRACTOR SHALL VERIFY EXACTLOCATION AND QUANTITIES WITH FIRE ALARMCONTRACTOR. CONTRACTOR SHALL UPSIZE WIRE FORVOLTAGE DROP AS REQUIRED.

K ALL FIRE/SMOKE DAMPERS SHALL BE CONNECTED TO A NEWDEDICATED 20a/1p CIRCUIT BREAKER IN NEAREST 208Y/120VBRANCH PANELBOARD WITH 2#12, #12G, 3/4"C. CONTRACTORSHALL UPSIZE WIRE FOR VOLTAGE DROP AS REQUIRED. NOMORE THAN (20) TWENTY FIRE/SMOKE DAMPERS TO ASINGLE CIRCUIT. FIRE/SMOKE DAMPERS SHALL BECONNECTED TI FIRE ALARM SYSTEM BY FIRE ALARMCONTRACTOR.

L LIMIT CONDUIT ROUTING IN AREAS WITH OPEN CEILINGS TOLOADS IN THAT AREA. ROUTE CONDUIT IN CONCEALEDBULKHEADS WHERE POSSIBLE. WHERE NOT POSSIBLE,CONDUIT SHALL BE RAN PARRALLEL AND TIGHT TOSTRUCTURE.

M ALL 125-VOLT, SINGLE PHASE 15 AMP AND 20 AMPRECEPTACLES INSTALLED IN RESTROOMS, KITCHENS,ROOFTOPS, OUTDOORS OR WITHIN 6 FEET OF A SINK OROTHER WATER SOURCE, SHALL BE GFCI TYPE ORPROTECTED BY A GFCI CIRCUIT BREAKER, PER NEC 210.8(B).

N CONTRACTOR SHALL PROVIDE NEATLY TYPED PANELSCHEDUL INSIDE PANEL DOOR.

O ALL CONDUIT AND/OR WIRING SHALL BE INSTALLEDBETWEEN THE BOTTOM AND TOP OF CORD OF JOIST. DONOT INSTALL CONDUIT WITHIN 3'-0" OF ANY A/C UNITSUNLESS THE CONDUIT AND/OR WIRING SERVICES THE A/CUNIT.

P ALL ELECTRICAL DEVICES TO BE STUDDED TO THE CEILING.

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 34: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

UP

DN

NOTES BY SYMBOL " ":

CLERKS

121

CONSTABLE

103

OPEN/FUTURE

VOTING

130

CONFERENCE

112

CONFERENCE

113

JUDGES

CHAMBER

120

COURTROOM

115

IT

122

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

MOP

107

ELEC

111JURY/TRAINING

116

EVIDENCE

104

STORAGE

109

ADA RR

129

CORRIDOR

125

CONSTABLE

105

STORAGE

118

STORAGE

124

AV

117

COURT

114

FOYER

101

CLOSET

119

COORIDOR

123

LA2

EX.

FCU-04

EX.

FCU-02

1

2

2

LA2-31,33,35

EF-03 EF-04

WH-1

UH-01

EX.

FCU-03

EX.

FCU-01

LA1

LA3

2

2

3

3

RP-1

TMV-1LA2-34

LA2-40

1

1

J J

LA2-34,36

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 6

:09

:17

PME401

PO

WE

R T

O M

EC

HA

NIC

AL

PL

AN

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

3/16" = 1'-0"1

POWER TO MECHANICAL PLAN

1 REFER TO POWER TO MECHANICAL SCHEDULE ONDRAWING E002 FOR ADDITIONAL INFORMATION.

2 EXISTING EQUIPMENT.

3 CONNECT EHAUST FAN TO SAME CICRCUIT ANDSENSOR AS LIGHTS IN ROOM.

TRUE NORTH0 3' 6' 12'

GRAPHIC SCALE3/16" = 1'-0"

1.5'

GENERAL NOTES:

A VERIFY REQUIREMENTS OF ALL MECHANICALEQUIPMENT WITH SHOP DRAWING SUBMITTALS.NOTIFY THE ENGINEER OF ANY CONFLICTS BETWEENMECHANICAL EQUIPMENT SUBMITTALS ANDELECTRICAL DRAWINGS PRIOR TO INSTALLATION.PROVIDE A CIRCUIT TO ALL MECHANICAL EQUIPMENT.

B CONTRACTOR SHALL REFER TO MECHANICAL ANDPLUMBING SHEETS, AND DIVISION 22 AND 23SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS,SCOPE, AND RESPONSIBILITY BY DIVISION 26CONTRACTOR.

C REFER TO MECHANICAL PLANS FOR EXACT LOCATIONOF MECHANICAL EQUIPMENT AND LOCATEDISCONNECT SWITCHES IN ACCORDANCE WITH THEN.E.C.

D CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHFOR ALL EQUIPMENT THAT IS NOT PROVIDED WITH AFACTORY DISCONNECT.

E REFER TO CONTROL SCHEMATICS ON THEMECHANICAL DRAWINGS FOR ADDITIONAL CONTROLWIRING AND CONTROL CONNECTIONS FOR DIVISION26 CONTRACTOR.

F PROVIDE PHASE-LOSS RELAYS ON ALL NEW THREEPHASE MECHANICAL EQUIPMENT 1 HP AND LARGERTO PREVENT SINGLE PHASING. COORDINATE WITHMECHANICAL EQUIPMENT CONTRACTOR.

G SOME EXHAUST FANS MAY BE CONTROLLED VIA THEENERGY MANAGEMENT SYSTEM, REFER TO THEMECHANICAL EQUIPMENT SCHEDULE FORADDITIONAL INFORMATION.

H ALL BREAKERS USED TO FEED MECHANICALEQUIPMENT SHALL BE ‘HACR’ TYPE.

I MAINTAIN EQUIPMENT ACCESS FREE OF ALLCONDUIT, WIRING, HANGERS, SUPPORTS, ETC.

J ALL MECHANICAL EQUIPMENT AND MOTORCONTROLLERS SHALL BE PROVIDED WITH ANAPPROPRIATE SHORT CIRCUIT CURRENT RATING(SCCR) FACTORY INSTALLED LABEL. THE LABELSHALL INDICATE THE AVAILABLE SHORT CIRCUITCURRENT AT THAT PIECE OF EQUIPMENT ASREQUIRED BY N.E.C. 440.10 AND N.E.C. 430.8.

No.

Revisions and Descr iptions

By

Date

LA1-46 LA1-46

06.14.18

09/01/2021

Page 35: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

VH-A

VH-C

LA2-32

LA2-32

EF-02

EF-01

VH-B

WPLA1-45

1

EX.

CU-FCU-03

EX.

CU-FCU-01

VH-D

LA2-32

EX.

CU-FCU-04

EX.

CU-FCU-02

WPLA1-45

11

1

1

LA1-44

LA1-44

2 2

2

2

3

3

1

NOTES BY SYMBOL " ":

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 6

:09

:17

PME402

PO

WE

R T

O M

EC

HA

NIC

AL

RO

OF

PL

AN

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

TRUE NORTH0 3' 6' 12'

GRAPHIC SCALE3/16" = 1'-0"

1.5'

GENERAL NOTES:

A VERIFY REQUIREMENTS OF ALL MECHANICALEQUIPMENT WITH SHOP DRAWING SUBMITTALS.NOTIFY THE ENGINEER OF ANY CONFLICTS BETWEENMECHANICAL EQUIPMENT SUBMITTALS ANDELECTRICAL DRAWINGS PRIOR TO INSTALLATION.PROVIDE A CIRCUIT TO ALL MECHANICAL EQUIPMENT.

B CONTRACTOR SHALL REFER TO MECHANICAL ANDPLUMBING SHEETS, AND DIVISION 22 AND 23SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS,SCOPE, AND RESPONSIBILITY BY DIVISION 26CONTRACTOR.

C REFER TO MECHANICAL PLANS FOR EXACT LOCATIONOF MECHANICAL EQUIPMENT AND LOCATEDISCONNECT SWITCHES IN ACCORDANCE WITH THEN.E.C.

D CONTRACTOR SHALL PROVIDE DISCONNECT SWITCHFOR ALL EQUIPMENT THAT IS NOT PROVIDED WITH AFACTORY DISCONNECT.

E REFER TO CONTROL SCHEMATICS ON THEMECHANICAL DRAWINGS FOR ADDITIONAL CONTROLWIRING AND CONTROL CONNECTIONS FOR DIVISION26 CONTRACTOR.

F PROVIDE PHASE-LOSS RELAYS ON ALL NEW THREEPHASE MECHANICAL EQUIPMENT 1 HP AND LARGERTO PREVENT SINGLE PHASING. COORDINATE WITHMECHANICAL EQUIPMENT CONTRACTOR.

G SOME EXHAUST FANS MAY BE CONTROLLED VIA THEENERGY MANAGEMENT SYSTEM, REFER TO THEMECHANICAL EQUIPMENT SCHEDULE FORADDITIONAL INFORMATION.

H ALL BREAKERS USED TO FEED MECHANICALEQUIPMENT SHALL BE ‘HACR’ TYPE.

I MAINTAIN EQUIPMENT ACCESS FREE OF ALLCONDUIT, WIRING, HANGERS, SUPPORTS, ETC.

J ALL MECHANICAL EQUIPMENT AND MOTORCONTROLLERS SHALL BE PROVIDED WITH ANAPPROPRIATE SHORT CIRCUIT CURRENT RATING(SCCR) FACTORY INSTALLED LABEL. THE LABELSHALL INDICATE THE AVAILABLE SHORT CIRCUITCURRENT AT THAT PIECE OF EQUIPMENT ASREQUIRED BY N.E.C. 440.10 AND N.E.C. 430.8.

3/16" = 1'-0"1

POWER TO MECHANICAL ROOF PLAN

1 REFER TO POWER TO MECHANICAL SCHEDULE ONDRAWING E002 FOR ADDITIONAL INFORMATION.

2 EXISTING EQUIPMENT.

3 PROVIDE CONVENIENCE RECEPTACLE IF THERE ISN'TALREADY AN EXISTING ONE IN AREA.

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 36: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

SCALE:SCALE:SCALE:

SCALE:

NTS01 DETAIL OF LIGHT FIXTURE INSTALLATION (LAY-IN CEILING)

TO FIXTURE

FLEX CONDUITWHIPS-MAX. 6'-0"

4S J-BOX

SAFETY CABLESUPPORTED FROMSTRUCTURE(TYPICAL)

FIRE BOX BY GENERALCONTRACTOR (TO COVERFIXTURES) WHEREREQUIRED BY CODE

LAY-IN GRIDFIXTURE ASSCHEDULED

MAXIMUM OF FOUR FIXTURESAND FOUR 6'-0" FLEXCONDUITS WIRED TO EACHJ-BOX. SUSPEND ORATTACH TO STRUCTUREAS REQUIRED.

NTS

+

+++++

+++++

++ +

++++ +++++ +++++ +++++ +

+

03 COMMUNICATIONS DEVICE BOXES

18"FINISHED FLOOR

TYPICAL COMMUNICATIONSDEVICE OUTLET BACKBOX

TYPICAL COMMUNICATIONSHAND OPERATED DEVICEBACKBOX

TYPICAL COMMUNICATIONSHAND OPERATED DEVICEBACKBOX

FINISHEDCEILING LINE

12" MIN.

LONG SWEEPRADIUS BENDS

BUNDLED COMMUNICATIONSWIRE SUPPORTED FROMSTRUCTURE AS REQUIRED

44"

NTS04 TELEPHONE/DATA BAR DETAIL

SERIES COPPER C

ABLE LUG

THOMAS AND BETTS #31000

SEE GROUNDIN

G RISER D

IAGRAM

GROUND CONDUCTOR

WITH 3/8" H

OLES @ 3" O

.C.

1/4"x 1"x 4' COPPER B

AR

CONDUIT WITH G

ROUNDING

BUSHING EACH END

7200 VOLT IN

SULATORS

BOLT INTO W

ALL

STANDOFF STRAPS,

2" Wx 1/4" G

ALVANIZED STEEL

WITH 277V LIGHTS02

WIRING DETAIL FOR 120V

EXHAUST SERVING TWO TOILET ROOMS

CH

M

2-POLE WALLSWITCH INTOILET DIM(TYP.)

277V.LIGHTS

GROUND LEADS NOT SHOWNFOR CLARITY.

WOMEN

SQUARE D OR EQUAL FANRELAY TYPE C CLASS8501C06-V04/9991-UEIMOUNTED ABOVE CLG.

MANUAL MOTOR SWITCHWITH OVERLOAD HEATER

TOILET EXH. FANCOMMON TO BOTHTOILET ROOMS

120V. AT PNL.

N

MEN

277V.LIGHTS

120V. AT PNL.

N

NTS

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

NTS

9/1

/20

21 6

:41

:30

PME501

DE

TA

ILS

-E

LE

CT

RIC

AL

211359

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11

057

EV

EN

T D

R.

SA

LA

DO

, T

X.

09/01/

21

MT

RJ

No.

Revisions and Descr iptions

By

Date

06.14.18

09/01/2021

Page 37: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

9/1

/20

21 8

:49

:18

PMP001

PL

UM

BIN

G S

CH

ED

UL

ES

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

Author

TG

No.

Revisions and Descr iptions

By

Date

TMV-1THERMOSTATIC MIXING

VALVEWATTSLFMMV

- - - 1/2" 1/2"THERMOSTATIC MIXING VALVE: WATTS LFMMV, WITHINTEGRAL FILTER WASHERS AND CHECK VALVES, 1/2" NPT INLET AND OUTLET. VALVE SHALLBE ASSE 1070 CERTIFIED.

W.C.O. WALL CLEAN-OUTJR SMITH4532S-U

- - - - - - -WALL CLEAN-OUT: JR SMITH 4532S-U, CAST IRON CLEANOUT TEE WITH COUNTERSUNK TAPER THREAD-BRONZE PLUG, STAINLESS STEEL ROUNDCOVER AND VANDAL PROOF SCREW.

G.C.O./D.C.O.

EXTERIORFLOOR CLEAN-OUT

JR SMITH4103S-F-C-U

- - - - - - -EXTERIOR FLOOR CLEAN-OUT: JR SMITH 4103S-F-C-U, CAST IRON CLEANOUT WITH ROUND ADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP(HEAVY DUTY), TAPER THREAD WITH BRONZE PLUG, FLANGE WITH FLASHING CLAMP AND VANDAL PROOF TOP.

F.C.O.INTERIOR

FLOOR CLEAN-OUTJR SMITH

4023S-F-C-U- - - - - - -

INTERIOR FLOOR CLEAN-OUT: JR SMITH 4023S-F-C-U, CAST IRON CLEANOUT WITH ROUND ADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP,TAPER THREAD WITH BRONZE PLUG, FLANGE WITH FLASHING CLAMP AND VANDAL PROOF TOP.

FD-2FLOOR DRAIN

(MECHANICAL ROOMS)JR SMITH

2350-P050-U- 3" 3" 2" 1/2" - -

FLOOR DRAIN: JR SMITH 2350-P050-U, 8" ROUND CAST IRON FLOOR DRAIN WITH SEDIMENT BUCKET, BOTTOM OUTLET, REVERSIBLE FLASHINGCOLLAR, SEEPAGE OPENINGS AND ADJUSTABLE CAST IRON BAR-TYPE GRATE. PROVIDE VANDAL PROOF SCREWS AND 1/2" TRAP PRIMERCONNECTION. PROVIDE AUTOMATIC TRAP PRIMER AS SPECIFIED AND MAKE FINAL CONNECTION.

FD-1FLOOR DRAIN

(RESTROOMS/SHOWERS)JR SMITH

2005-P050-U- 3" 3" 2" 1/2" - -

FLOOR DRAIN: JR SMITH 2005-P050-U, CAST IRON FLOOR DRAIN WITH BOTTOM OUTLET, REVERSIBLE FLASHING COLLAR, SEEPAGE OPENINGS ANDADJUSTABLE NICKEL BRONZE STRAINER HEAD. PROVIDE VANDAL PROOF SCREWS AND 1/2" TRAP PRIMER CONNECTION. PROVIDE AUTOMATICTRAP PRIMER AS SPECIFIED AND MAKE FINAL CONNECTION. VERIFY ROUND OR SQUARE HEAD BASED UPON FLOOR COVERING.

MS-1 MOP SINKSTERN WILLIAMS

HL-1800STERN WILLIAMS

T-15-VB3" 3" 2" 3/4" 3/4" -

MOP SINK: STERN WILLIAMS HL-1800, 24"x24"x12" SERVICE BASIN COMPOSED OF PEARL GRAY MARBLE CHIPS AND WHITE PORTLAND CEMENTGROUND SMOOTH, GROUTED, AND SEALED. BASIN SHALL HAVE 6" DROP AT THRESHOLD AND STAINLESS STEEL CAP OF ONE PIECE 20 GA. 302STAINLESS STEEL CAST INTEGRAL ON THRESHOLD. PROVIDE FAUCET WITH VACUUM BREAKER, ADJUSTABLE TOP BRACE, 3/4" HOSE THREAD ONSPOUT WITH BUCKET HOOK, INLETS ON 8" CENTERS AND POLISHED CHROME FINISH. PROVIDE 36" HOSE AND WALL HOOK (T-35) AND 24" LONGSTAINLESS STEEL MOP HANGER WITH 3 RUBBER SPRING LOADED GRIPS (T-40).FAUCET: STERN WILLIAMS T-15-VB,

HB-1NON FREEZEHOSE BIBB

-WOODFORD

B65-WH- - - 3/4" - -

NON FREEZE HOSE BIBB: WOODFORD B65-WH, BOX MOUNTED, AUTOMATIC DRAINING, BACKFLOW PROTECTED, FREEZELESS WALL HYDRANT WITHMETAL WHEEL HANDLE AND "WATER" STAMPED ON THE DOOR. EXTERIOR FINISH SHALL BE SELECTED BY ARCHITECT.

S-1H

COUNTER MOUNTEDSINGLE COMPARTMENTSTAINLESS STEEL SINK

(ADA)

JUSTSL-ADA-2125-16-GR

JUSTJWF-200-W4 (faucet)

1-1/2" 2" 1-1/2" 1/2" 1/2" NO

SINK: JUST SL-ADA-2125-16-GR, SINGLE COMPARTMENT, 16 GAUGE, TYPE 304, 18-8 STAINLESS STEEL, SELF RIMMING SINK WITH FAUCET HOLES ON8" CENTERS (21"x25"x5.5"D). UNDERSIDE OF SINK IS FULLY UNDERCOATED WITH DRAIN PUNCH IN CENTER OF SINK.FAUCET: JUST JWF-200-W4, SHALL HAVE BRASS VALVE BODIES, POLISHED CHROME PLATED FINISH, HIGH RISE SPOUT WITH 10" CLEARANCE, WRISTBLADE HANDLES AND VANDAL RESISTANT AERATOR (1.5 GPM).STRAINER AND TAILPIECE: PROVIDE STAINLESS STEEL CUP STRAINER WITH REMOVABLE STAINLESS STEEL BASKET (J-35). SINK SHALL BE PUNCHEDFOR BUBBLER.P-TRAP: JT-125 CAST BRASS.STOPS AND RISERS:THERMOSTATIC MIXING VALVE:

TP TRAP PRIMERPRECISION PLUMBING

PRODUCTS, INC.MODEL # PT

- 1/2" X

TRAP PRIMER: PRECISION PLUMBING PRODUCTS, INC MODEL #PT, SHALL SUPPLY 2 OZ. POTABLE WATER AT 20PSIG AT A MIN. 10 SECONDS EVERY24 HOURS. ASSEMBLY SHALL BE A STEEL CABINET FLUSH WALL MOUNTED ABOVE FINISHED FLOOR. CABINET FIRE RATED 16" GAUGE DEPTH AT 6".3/4"NPT FEMALE- ANSI/ASME BI.20.1. OUTLET 1/2" COMPRESSION FITTING. MANIFOLD 3/4" TYPE "L" COPPER TUBING. ASTM B88. ELECTRICALCOMPONETS WITH CIRCUIT BREAKER, TEST SWITCH, TIMER, SOLENOID VALVE MARKED AS UL LISTED. ELECTRONIC ASSEMBY TESTED ANDCERIFIED PER UL #73. BACKFLOW PREVENTION ANTI-SIPHON ATMOSPHERIC VACUUM BREAKER WITH ACCESS DOOR FIRE RATED.

EWC-1HWALL MOUNTED

ELECTRIC WATER COOLERHALSEY TAYLORHACG8BLPV-WF

- 1-1/2" 2" 1-1/2" 1/2" - X

ELECTRIC WATER COOLER: HALSEY TAYLOR HAC8FS-QADA, SELF CONTAINED, WATER COOLER THAT SHALL DELIVER A MINIMUM OF 8.0 GPH OFWATER AT 50°F COOLED FROM 80°F INLET WATER AND 90°F AMBIENT. UNIT SHALL BE ACTIVATED FROM BOTH FRONT AND SIDE PUSH BARS USINGLESS THAN 5 POUNDS OF FORCE. BUBBLERS SHALL BE ONE-PICE, CHROME PLATED, TWO-STREAM WITH AN INTEGRALLY DESIGNED NON-SQUIRTFEATURE. TOPS SHALL BE CONSTRUCTED FROM 300 SERIES STAINLESS STEEL AND HAVE AN INTEGRAL DRAIN. CABINETS SHALL BE STAINLESSSTEEL. EVAPORATOR SHALL BE AN INSULATED, TUBE ON TANK. COOLING SYSTEM SHALL USE R-134a AND AN ADJUSTABLE THERMOSTAT WITH ANOFF POSITION. PROVIDE UNIT WITH CONCEALED SUPPORT CARRIER.

L-1HWALL HUNG LAVATORY

(ADA)KOHLER

K-2035-08

KOHLER TRITONK-7307-KE (Faucet)K-16012-5 (Handles)

1-1/2" 1-1/2" 1-1/4" 1/2" 1/2" -

LAVATORY: K-2035-08 22"X18" WALL HUNG, VITREOUS CHINA, GLAZED , AND OVERFLOW. ADA LEVER HANDLES AND 1.5 GPM AERATOR. INSTALL INACCORDANCE WITH ADA AND TAS.FAUCET: KOHLER K-7437-2ASTRAINER AND TAILPIECE: MCGUIRE 155 LAT WC OFFSET PLUG DRAIN.P-TRAP: MCGUIRE 8872 GRID DRAIN.STOPS AND RISERS:MIXING VALVE: PROVIDE THERMOSTATIC MIXING VALVE TLT10. INSTALL IN ACCORDANCE WITH ADA AND TAS.

L-1COUNTERTOP

LAVATORYKOHLER

PENNINGTON K-2196-8

KOHLER TRITONK-7307-KE (Faucet)K-16012-5 (Handles)

1-1/4" 2" 1-1/2" 1/2" 1/2" -

LAVATORY: KOHLER PENNINGTON K-2196-8 SELF RIMMING, VITREOUS CHINA (20" x 17") WITH OVERFLOW.FAUCET: KOHLER K-7307-KE BRASS VALVE BODIES, POLISHED CHROME PLATED FINISH. QUARTER-TURN WASHERLESS CERAMIC DISC VALVES, 5"SPOUT, LEVER BLADE HANDLES AND VANDAL RESISTANT AERATOR (0.5 GPM).STRAINER AND TAILPIECE:P-TRAP: MCGUIRE 8872 GRID DRAIN.STOPS AND RISERS:MIXING VALVE: PROVIDE THERMOSTATIC MIXING VALVE TLT10. INSTALL IN ACCORDANCE WITH ADA AND TAS.

U-1H

WALL HUNGURINAL

W/ FLUSH VALVE(ADA)

KOHLERBARDON K-4904-ET

KOHLERK-76317-CP

INT 2" 2" 3/4" - -

URINAL: KOHLER BARDON K-4904-ET WALL HUNG, .125 GPF WASHOUT FLUSH, 3/4" TOP SPUD, 2" OUTLET SPUD, VITREOUS CHINA URINAL WITH WALLHANGERS.FLUSH VALVE: KOHLER K-76317-CP EXPOSED FLUSH VALVE AND CAST IRON, FLOOR MOUNTED CLOSET CARRIER WITH INTEGRAL ADJUSTABLECLOSET FITTINGS. INSTALL IN ACCORDANCE WITH ADA.

WC-1/1H

FLOOR MOUNTEDTANK TYPE

WATER CLOSET(ADA)

KOHLERK-3519 HIGHLINE

- INT 4" 2" 3/4" - -

WATER CLOSET: KOHLER K-3519 HIGHLINE FLOOR MOUNTED, TANK TYPE VITREOUS CHINA ELONGATED BOWL, SLOAN FLUSHMATE SYSTEM, 1.1 GPFWITH 2" GLAZED TRAPWAY AND POLISHED CHROME TRIP LEVER. PROVIDE WITH K-4731-GC ELONGATED OPEN FRONT SEAT WITH SLOW CLOSINGRING. INSTALL IN ACCORDANCE WITH ADA AND TAS.SEAT: CHURCH MODEL 1295CT, ELONGATED OPEN FRONT SEAT WITH SLOW CLOSING RING. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTIN...

TAG FIXTURE TYPE MANUFACTURER VALVE / FAUCET TRAP WASTE VENT CW HW ELEC DESCRIPTION, TRIM AND NOTES

PLUMBING FIXTURE SCHEDULE

T&P AND OVERFLOW DRAINS SHALL DISCHARGE AS SPECIFIED ON PLANS.

3. CONTRACTOR SHALL PROVIDE T&P RELIEF VALVE, DRAIN VALVE AND EMERGENCY OVERFLOW DRAIN PAN FOR WATER HEATER.

2. WATER HEATER SHALL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS AND IN ACCORDANCE WITH ALL APPLICABLE CODES.

1. PROVIDE STAINLESS STEEL BRAIDED FLEXIBLE CONNECTORS

NOTES:

WH-1 208V / 3PH 9 20 120 30 A.O. SMITH DSE 30-9 1-3

SERVICE KW GPH @ 60F RISE WATER TEMP CAPACITY (GAL)

MARK ELECTRICAL DATA RECOVERY RATE LEAVING STORAGEMANUFACTURER AND MODEL REMARKS

WATER HEATER SCHEDULE

2. PROVIDE 7-DAY PROGRAMMABLE TIMECLOCK FOR OWNER SET ON / OFF PERIODS.

1. PROVIDE WITH AQUASTAT SET AT 120F TO ENERGIZE/DENERGIZE PUMP

NOTES;

RP-1 RECIRC PUMP DOMESTIC HOT WATER 5.5 12 1/8 / 84 110/1 - GRUNDFOS UPS 15-55 SFC NOTES 1,2

FT HP / W V/PH RPM NUMBER

DESIG. TYPE SERVES GPM HEAD MOTOR DATA MFG MODEL NOTES

PUMP SCHEDULE

Page 38: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

UP

DN

NOTES BY SYMBOL " ":

CLERKS

121

CONSTABLE

103

OPEN/FUTURE

VOTING

130

CONFERENCE

112

CONFERENCE

113

JUDGES

CHAMBER

120

COURTROOM

115

IT

122

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

MOP

107

ELEC

111

JURY/TRAINING

116

EVIDENCE

104

STORAGE

109

ADA RR

129

CORRIDOR

125

CONSTABLE

105

STORAGE

118

STORAGE

124

AV

117

COURT

114

FOYER

101

CLOSET

119

COORIDOR

123

2"ø V

2"ø

V2"ø

SS

2"ø

SS

2"ø SS

1

1

1

2

34

5

666

66

666

666

FD-1

2"ø SS

WC-1H

WC-1

L-1

U-1H

U-1H

U-1HMS-1

L-1

WC-1H

WC-1

WC-1

WC-1

WC-1

EWC-1H

S-1H

S-1H

WC-1HWC-1

U-1H

L-1

L-1

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 8

:49

:19

PMP201

SA

NIT

AR

Y / V

EN

T P

LA

N

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

Author

TG

3/16" = 1'-0"1

UNDERFLOOR SANITARY / VENT PLAN

1 PRIOR TO INSTALLING NEW SANITARY LINE, ROUTE 3" SS

TO EXISTING SS LINE IN THIS AREA. CONNECT NO

SMALLER THAN 3".

2 2" SS UP TO SERVICE SINK.

3 2" VENT UP TO SERVE SERVE MOP SINK.

4 3" SS UP TO SERVICE MOP SINK.

5 NEW 2" VENT LINE TO BE CONNECTED TO NEAREST 2"

MINIMUM VENT IN THIS AREA.

6 CONTRACTOR TO DEMO EXISTING PLUMBING FIXTURES

FOR DISPOSAL.

TRUE NORTH0 2' 4' 8' 16'

GRAPHIC SCALE

1/8"=1'-0"

GENERAL NOTES:

1 REFER TO MP0.0 FOR GENERAL PLUBMING NOTES,

ABBREVIATIONS, AND SYMBOLS. REFER TO

SPECIFICATIONS FOR ADDITIONAL PROJECT

REQUIREMENTS.

2 COORDINATE ALL PIPING AND FIXTURES WITH ALL

TRADES BEFORE WORK BEGIN.

3 ALL PLUMBING ELECTRICAL DEVICES REQUIRING

POWER SHALL BE COORDINATED BY THE CONTRACTOR.

4 ALL SANITARY PIPING 3" AND GREATER SHALL BE

SLOPED AT 1/8" PER FOOT WITH SANITARY PIPE 2-1/2"

AND SMALLER SLOPED AT 1/4" PER FOOT.

5 PATCH FLOORS, WALLS, CEILINGS, ETC. TO MATCH

EXISTING CONDITIONS WHERE CUTTING IS REQUIRED.

No.

Revisions and Descr iptions

By

Date

Page 39: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

UP

DN

NOTES BY SYMBOL " ":

CLERKS

121

CONSTABLE

103

OPEN/FUTURE

VOTING

130

CONFERENCE

112

CONFERENCE

113

JUDGES

CHAMBER

120

COURTROOM

115

IT

122

LOBBY

102

BREAKROOM

126

RR

128

RISER

127

WAIT/SECURITY

108

WOMEN

110

MEN

106

MOP

107

ELEC

111

JURY/TRAINING

116

EVIDENCE

104

STORAGE

109

ADA RR

129

CORRIDOR

125

CONSTABLE

105

STORAGE

118

STORAGE

124

AV

117

COURT

114

FOYER

101

CLOSET

119

COORIDOR

123

3/4

3/4"ø HW

1

1111

1

11

1

2

11

1

WC-1H

WC-1

U-1H

U-1H

U-1H

L-1

MS-1

WC-1

WC-1

WC-1

WC-1

L-1

EWC-1H

S-1H

S-1H

L-1

U-1H WC-1

3

RP-1

WH-1TMV-1

3/4"ø CW

3

3/4"ø HW

3/4"ø HW

1"ø HW

1"ø HW

3/4"ø HW

3/4"ø HW

1"ø HW

1"ø HW

1"ø HW

R

R

WC-1H

L-1

WC-1H

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 8

:49

:22

PMP301

PR

ES

SU

RE

PIP

E P

LA

N

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

TG

TG

1 CONTRACTOR TO DEMO EXISTING PLUMBING

FIXTURES FOR DISPOSAL.

2 RELOCATED FIXTURE. CONTRACTOR TO RELOCATE

EXISTING HOT AND COLD WATER LINES.

3 CONNECT TO NEAREST COLD WATER LINE.

3/16" = 1'-0"1

PRESSURE PIPE PLAN

TRUE NORTH

GENERAL NOTES:

1 REFER TO MP0.0 FOR GENERAL PLUMBING NOTES,

ABBREVIATIONS, AND SYMBOLS.

2 COORDINATE ALL PIPING AND FIXTURES WITH ALL

OTHER TRADES BEFORE WORK IS TO BEGIN.

3 NO EXPOSED PIPING UNLESS APPROVED BY ARCHITECT.

4 ALL SANITARY PIPING TO BE AT A 1/8" SLOPE, UNLESS

NOTED OTHERWISE.

5 ALL PLUMBING ELECTRICAL DEVICES REQUIRING POWER

SHALL BE COORDINATED BY THE CONTRACTOR.

6 THERE SHALL BE NO PIPING ROUTED OVER

ELECTRICAL/IT ROOMS.

7 TRAP PRIMERS/TRAP GUARDS SHALL BE PROVIDED FOR

ALL FLOOR DRAINS AND FLOOR SINKS EXCEPT FOR

SHOWER DRAINS AND FLOOR SINK AT ICE MAKER.

0 3' 6' 12'

GRAPHIC SCALE

3/16" = 1'-0"

1.5'

No.

Revisions and Descr iptions

By

Date

Page 40: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

SCALE:

SCALE:

SCALE:

SCALE:

SCALE:

D

WALL CLEANOUT DETAIL02 NTS

NTS

NTS

NTS

NTS

FLOOR

TEMP. AND PRESSURERELIEF VALVE

DRAIN VALVE

4" HOUSEKEEPING PAD

DRAIN PAN

DRAIN - INDIRECT DISCHARGETO EXISTING FLOOR DRAIN

STAINLESS STEEL

NOTE: CONNECT TO EXISTING WATER LINES

ADJUSTABLE

STRAINER

THREADED, CAULKED

OR NO-HUB

CONNECTION

WATERPROOF

MEMBRANE

CLAMP WATERPROOF

MEMBRANE INSIDE OF

DRAIN BODY

LOOSE

GRAVEL AT

WEEP HOLES

3mm TO

6mm GRAVEL

SIZEFLASHING

CLAMP WITH

WEEP HOLES

STRUCTURAL

SLAB

MOP HANGER

MOP

(BY OTHERS)

SINK

MOP

BRACKET

HOSE

30" HOSE

BREAKER

WITH VACUUM

SERVICE FAUCET

PROVIDE SILICONE SEALANT

AROUND TOP OF SINK AT

ALL WALLS

FIN. FLR.

18"

36"

48"

TEMPERED FIXTURES

T

HOT WATERSOURCE

BALANCINGVALVE

CHECKVALVE

CHECKVALVE

ISOLATION VALVE

TEMPEREDWATERRECIRCULATIONPUMP

AQUASTAT

TEMPEREDRETURN LINE

HEAT TRAP

COLD WATER SUPPLY

NOTE: THE MIXING VALVE SHALL BE INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONS.. MOUNT ON WALL NEXT TO

WATER HEATER.

TO PLUMBING FIXTURES

120° F

CHECKVALVE

DIGITALMIXING VALVE

DIELECTRIC UNION

DIELECTRIC UNION

DIELECTRIC UNION

MOP SINK DETAIL01

FLOOR DRAIN DETAIL03

04 MIXING VALVE PIPING DIAGRAM

WATER HEATER DETAIL05

ELEC./CIRCULATING

ACCESS COVER CLEANOUT FITTING

SECURING SCREW

FINISHED WALL

CLEANOUT PLUG

WH-1

HW

BALL VALVE

CHECK VALVE

CW

EXPANSION TANK EQUAL TO AMTROL

MODEL NO. ST-5

HWRRP-1

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

1/8" = 1'-0"

9/1

/20

21 8

:49

:23

PMP401

DE

TA

ILS

-P

LU

MB

ING

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

21

Author

TG

No.

Revisions and Descr iptions

By

Date

Page 41: D101 DEMOLITION PLAN SALADO ANNEX RENOVATION D102 …

666

666

UP

DN

WH

WH

WH

LEGEND:REVISED FIRE PROTECTION

AREA - RELOCATE / REPLACE

SPRINKLER HEADS AS REQUIRED

EXISTING

FIRE

RISER

ROOM

REVISED FIRE PROTECTION

AREA - PROVIDE DRY PIPE SYSTEM

Scale:

Project No.

Date:

Drawn By:

Checked By:

Sheet No.

Project Title:

Drawing Title:

Copyright C 2021MRB Group

All Rights Reserved

of

8834 N

. C

apit

al o

f T

exas

Hw

y, S

uit

e 147, A

ust

in, T

X 7

8759

Ph

on

e: 5

12-4

36-8

571

303 W

. C

alh

oun

Ave.

Tem

ple

, T

X 7

6501

Ph

on

e: 2

54-7

71-2

054

ww

w.m

rbg

rou

p.c

om

MR

B G

rou

p,

P.C

.

As indicated

9/1

/20

21 8

:49

:18

PMFP201

FIR

E P

RO

TE

CT

ION

PL

AN

0229.20001

SA

LA

DO

AN

NE

X R

EN

OV

AT

ION

11057 E

VE

NT

DR

.

SA

LA

DO

, T

X.

09/01/

2021

NL

TG

TRUE NORTH3/16" = 1'-0"

01FIRE PROTECTION PLAN 0 3' 6' 12'

GRAPHIC SCALE

3/16" = 1'-0"

1.5'

GENERAL NOTES:

1 FIRE PROTECTION CONTRACTOR SHALL PROVIDE WET

PIPE SPRINKLER AND STAND PIPE SYSTEM FOR THE AREA

OF WORK IN ACCORDANCE WITH NFPA 13, NFPA 14 AND

SALADO FIRE REQUIREMENTS. FIRE SPRINKLER SYSTEM IS

TO BE PERMITTED BY COUNTY FIRE MARSHAL.

CONTRACTOR SHALL COORDIN

2 PROVIDE WET PIPE SPRINKLER PROTECTION WITH 0.10

GPM PER SQUARE FOOT DENSITY OVER MOST LIGHT 1500

SQUARE FOOT OR THE ENCLOSED AREA PER NFPA 13.

LIGHT HAZARD SPRINKLER SPACING, 165°F TEMPERATURE

RATING, FOR ALL AREAS EXCEPT MECHANICAL ROOM.

3 THE FIRE SPRINKLER PIPING SHOWN IS INTENDED TO

INDICATE THE LOCATION OF MAIN SUPPLY PIPING AND

STANDPIPIES, AS WELL AS THE AREAS INTENDED FOR FIRE

SPRINKLERS. THE INCLUDSION OF THIS AREA INTENDED

FOR FIRE SPRINKLERS. THE INCLUSION OF THIS

INFORMATION SHALL IN NO WAY DIMINISH THE

RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE A

FULLY DESIGNED, SIZED AND INSTALLED FIRE SPRINKLER

SYSTEM, AS REQUIRED BY THE PROJECT SPECIFICATIONS

AND THE LAWS OF THE STATE OF TEXAS.

4 FIRE SPRINKLER SHOP DRAWINGS SHALL BE

COORDINATED WITH ALL TRADES AND EXISTING

CONDITIONS PRIOR TO SUBMISSION TO FIRE MARSHALL.

5 THE OWNER AND FIRE DEPARTMENT SHALL BE NOTIFIED

48 HOURS PRIOR TO ANY CONNECTIONS TO THE EXISTING

FIRE SYSTEM.

6 FIRE PROTECTION DESIGN AND NOMENCLATURE SHALL

MATCH EXISTING SALADO FACILITY STANDARDS.

7 CONTRACTOR SHALL PROVIDE SPRINKLER COVERAGE

ABOVE CEILINGS IN AREAS OF COMBUSTIBLE

CONTSTRUCTION.

No.

Revisions and Descr iptions

By

Date