23
1 OPERATION AND MAINTENANCE MANUAL 1. Introduction 1.1. General 1.2. Technical data 1.3. System description 2. Installation 2.1. General criteria and material required 2.2. Components mounting 2.3. Water intake 2.4. Hydraulic connections 2.5. Electric connections 3. Operating procedures 3.1. Remote panel commands 3.2. First start-up procedure 3.3. Normal operations 4. Maintenance 4.1. Shutdown procedure 4.2. Maintenance and recurrent inspections 4.3. Troubleshooting 5. Safety cautions 6. Warranty

OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

  • Upload
    ngoliem

  • View
    220

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

1

OPERATION AND MAINTENANCE MANUAL

1. Introduction

1.1. General

1.2. Technical data

1.3. System description

2. Installation

2.1. General criteria and material required

2.2. Components mounting

2.3. Water intake

2.4. Hydraulic connections

2.5. Electric connections

3. Operating procedures

3.1. Remote panel commands

3.2. First start-up procedure

3.3. Normal operations

4. Maintenance

4.1. Shutdown procedure

4.2. Maintenance and recurrent inspections

4.3. Troubleshooting

5. Safety cautions

6. Warranty

Page 2: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

2

1. Introduction

1.1 General

Thank you for choosing a Schenker Watermaker, and we are sure that the plant will contribute

to make your cruises more comfortable and more pleasant.

As all the equipment aboard, the knowledge of operating and maintenance procedures allows to

use the system in the best way, and to guarantee a perfect functioning throughout the years.

We invite you to read carefully this manual and to keep it aboard for a quick reference.

The Smart systems, as alternative to the high pressure pumps of traditional plants, utilizes the

ENERGY RECOVERY SYSTEM patented device, which amplifies the pressure of common low

pressure pumps, and recoup all the hydraulic energy back from the membranes, allowing an high

energy efficiency and the possibility to supply the watermaker directly from the batteries.

The ENERGY RECOVERY SYSTEM operating components are reduced to the minimum,

thanks to 2 international patented solutions that eliminate the necessity of pilot valves.

The lack of high-pressure pumps makes the system silent and vibrations free, and enormously

simplify the use because no adjustment is necessary for its operating.

Page 3: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

3

1. Introduction

1.2 Technical data

WATERMAKER GROUP

Dimensions

Length: 118 cm

Width: 24 cm

Height: 24 cm

Net weight: 21 Kgs.

Connections:

Seawater intake holder for hose int. diam. 16 mm.

Salt water outlet holder for hose int. diam. 16 mm.

Fresh water outlet compression fitting for hose int. diam. 6 mm. int. X 8 mm. external

PUMPS GROUP

Dimensions

Length: 34 cm

Width: 19 cm

Height: 35 cm

Net weight: 10 Kg.

Connections:

Seawater intake holder for hose int. diam. 16 mm.

Salt water outlet holder for hose int. diam. 16 mm.

Filter: 5 micron polyestere pleated type

Power supply: 12 Vdc +/- 20% (version 60M12)

24 Vdc +/- 20% (version 60M24)

Power consumption: average of 240 Watt

Production performance: 60 Lit/h +/- 20% @ seawater 25 °C - salinity 35.000 ppm

Seawater temperature range: 13°C - 35 °C @ salinity 35.000 ppm

Quality of water produced: average of 450 ppm TDS

CEE conformity: In compliance with directives 89/392 CEE sect.1 (general safety

machines requirements) , 89/336 CEE (electromagnetic compatibil-

ity).

Page 4: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

4

1. Introduction

1.3 System description

The Smart systems are based on 2 main units:

� PUMPS AND FILTER GROUP

1. In

2. Out

3. Pumps relays box

4. Electric connections

This unit picks-up the sea water up and sends it to the watermaker at pressure (about 7,4 –7,8

Bar). The filter housing contains a 5 micron filter cartridge, and its job is to filter impurities that

may damage the watermaker unit. A red push-button is positioned on the top of the housing to

help to purge air from the filter.

The pumps are fitted with a safety cut off switch, calibrated at

about 9 Bar. The pressure switch can be adjusted by an 2 mm.

allen key. To make the allen key adjustment to the pressure switch

pictured, the cover to the connector must be removed. This gives

access to make an adjustment by inserting the allen key without

removing the connector

itself.

Pressure switch detail

Turning the allen key clockwise increases the preset pressure, and turning anti clockwise de-

creases the preset pressure. The movement required is very small. (1/4 turn = 1 BAR).

This action will not be required in normal circumstances as the unit has been pre calibrated at the

factory. The grey box contains the power relays that activate the pumps electric motors.

Pump relay box

Page 5: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

5

� WATERMAKER GROUP.

The watermaker group is constituted of the following components:

Reverse osmosis membrane, installed inside blue color high-pressure vessel. Its job is to sepa-

rate the intake high-pressure seawater into two flows: one for the salt-water drain and one for the

fresh water production.

Energy Recovery System. It has the function to amplify the pressure supplied by the pump and

recover the hydraulic energy back from the membranes. The ERS device makes periodic cycling

by a hydraulically controlled automatic valve. The cycles are noticeable through a ”beat” issued

periodically by the watermaker unit. The unit is constituted of 2 cylinders, and a central body

containing the hydraulic valves necessary for the system functioning.

Manometer. It is located on the front of the ERS, and it measures the pump running pressure.

Depressurization valve. It is utilized only during the air bleeding phase, at the first plant start-

up. It is recognizable by a bleu lever and it is located on back side of the watermaker. Its func-

tion is to depressurize the system and the bleed the air. The valve must be closed during normal

working conditions and opened during the air bleeding operations. It is suggested to open the

lever only halfway (45°) during the air bleeding operations.

Pulsation dimmer It is installed on the left of the ERS . It is a black cylindrical unit and its

purpose is to dampen the pump's pressure oscillations during the watermaking. The accumulator

is factory pre charged with air to a pressure of about 3 BAR This can be recharged using the

valve on the unit and a tyre pump. It may be worthwhile checking this pressure when first start-

ing up of the watermaker after installationand has the function to dampen the pumps pressure

oscillations during the watermaker functioning.

Reset valve

Depressurization

valve

Positioner knob

Page 6: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

6

Positioner: It is a stainless steel threaded arm, with a black knob, located on the right side of

the unit. Its function is to reset the unit in case the system blocks during the restart.

Reset valve. It is installed on the left of the ERS and it is recognizable by the little blue plastic

lever. The valve must be closed during normal functioning (lever perpendicular to the valve).

Such valve has the function to allow the reset in case of a system block. It must be opened before

acting on the valve positioner.

Computer box . It is an external unit. It has to be installed relatively close to the watermaker, in a

position protected from water. It is connected to the remote panel and controls the functions of the

watermaker automatically.

The microswitches P1, P2, and EV allow the direct command of pump1, pump2 and the electro-

valve respectively. They can be used, as an emergency solution, for starting the watermaker in case

of total failure of the electronic computer. In normal condition they have to be switched off.

Signal pressure switch (probe). It is a little steel device, mounted on the left, top side of the ERS,

close the reset valve. It must be connected inside the computer box, throw the cables PS / PS . Its

function is check that the cycling of the machine is correct.

Remote panel cable

connector

Emergency mi-

croswitch emer-

Electric con-

nections

Signal pressure

switch

Page 7: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

7

2. Installation

2.1 General criteria It is important to plan carefully the activity prior to start the installation works, evaluating any

possible alternative solution. The fundamental choices to make are:

� Finding of seawater intakes and any necessary fittings.

� Positioning of main units .

� Pipes and electric cables laying.

A well-done installation is the maximum optimization between functionality, accessibility, in-

stallation saving and esthetic. All plant components have been designed to achieve this target. It

is suggested to draw a schematic electric and hydraulic connections layout once an installation

solution is chosen, and enclose it into the manual for further quick reference.

2. Installation

2.2 Components mounting � Pump group.

The pumps are self-priming type. Anyway it suggested to install the pumps group below the wa-

termaker, as low as possible respect the sea level, and as close as possible respect the sea

water intake.

Th pump group needs to be installed inside to adequately ventilated room, with the purpose to

facilitate the cooling of the pump and not subject to condenses or drippings.

Avoid the contact or the proximity with inflammable material or liquid, since the pump surfaces

can reach elevated temperatures. Avoid locating the pump wherever a possible loss of water can

involve damages or jeopardize its safety. It is necessary to foresee the necessary space to be able

to unscrew the filter container for replacing the cartridge. The pump group must be installed on a

base sufficiently horizontal, suitable to sustain the weight of the group. It could be necessary to

realize a suitable wooden or fiberglass structure if an horizontal support is not available. The

base of the pump group is equipped with vibration-damping devices, but however it is preferable

to not install the pumps on a plan particularly subject to vibrations. It is preferable to install the

pump in an acoustically isolated room since they constitute the principal source of noise, al-

though modest, of the plant.

Possible locations of the pump group are: engine compartment, sink closets, peak tank.

The unit is normally fixed on the support structure using the screw furnished with the equipment

or the passing bolts with die and washer, if the inferior part of the support structure is accessi-

ble.

� Watermaker group.

The watermaker unit is totally hydraulic, as electric devices are not present. Therefore, it is also

possible to install the unit inside spaces that can be exposed to humidity, to condense, or to the

presence of inflammable vapors. There are not height limits in comparison to the seawater level.

Avoid to install the system wherever any possible leak may cause damages to the boat or jeop-

ardize its safety, since possible leaks due to accidental causes (pipe bursting, hose clamp loosen-

ing, equipment failure, etc.) may cause water losses.

The hydraulic intake and outlet connections are positioned, in the standard version, on the left of

the unit. Therefore, it is necessary to foresee a minimum distance of 20 cm. to allow the pipes

laying. The watermaker unit must be installed on a base sufficiently horizontal, suitable to sus-

tain the weight of the group (approx. 25 Kg). It could be necessary to realize a suitable wooden

or fiberglass structure if an horizontal support is not available. The watermaker unit is equipped

with vibration-damping devices, but however it is preferable to not install the unit on a plan par-

ticularly subject to vibrations.

Possible locations of the watermaker group are: engine compartment, closets, and peak tank. It is

advisable to install the unit in such position to make the instrumentation easily visible, and make

the valves (located on the right of the unit) easily accessible.

Page 8: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

8

The unit is normally fixed on the support structure using the screw furnished with the equipment

or the passing bolts with die and washer, if the inferior part of the support structure is accessi-

ble.

� Non return valve.

The non return valve must be installed vertically, as close as possible to the water inlet.

2. Installation

2.3 Water intakes

The necessary hydraulic intakes are:

� Seawater intake

It is ideal a specific sea water intake, size ¾” min. in a central position, well under the water sur-

face even when the vessel is well heeled over.

The scoop is recommended. It must be oriented to the bow of the boat.

As alternative it is possible Tee into an water inlet as long as the following conditions are met:

- 3/4” minimum size,

- No air can be introduced into the system from other use ie: salt water tap in galley

-Must always be under the water surface even when the vessel is well heeled over.

Allow a minimum ½” on-off ball valve on the water intake. The hose connections, especially if

under the seawater level, must be secured with double hose clamps.

It is not advisable to Tee into the engine cooling water intake as it may impair the cooling of the

engine. An easily inspected mesh type filter will be required close to the water intake. The filter

has to be of 50 microns. It is possible to use filters from existing outlets

� Fresh water intake for washing.

It is necessary to use a offtake downstream the boat sanitary water pressurization system (fresh

water pump).

The following conditions must be respected during the operation:

the washing operations have to be always executed with the fresh water pump on,

the fresh water pump pressure doesn't have to exceed 2,5 BAR.

� Salt-water drain.

The salt-water drain shall be ½” minimum size and it has to be preferably above the seawater

level.

It is possible to use offtakes from existing apparatuses, provided that it is not the engine cooling

water drain or uses that drain with elevated heads.

Page 9: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

9

2. Installation

2.4 Hydraulic connections

OUT

IN

Connection to the fresh water tank (use the small 6X8 hose).

The connection has to be made, using the small hose furnished with the equipment, and relevant

endowed fittings.

Pressurized fresh water valve Pump

Elecrovalve Non return valve

5 micron filter Net filter

Swan neck upward - Disharge Water inlet

Watermaker Active carbon filter

Fresh water outlet

All the hydraulic connections (to exception of the fresh water production) have to be realized

with a 16 mm. int. diam. hose and a ½” holder. The hydraulic section that is continuously un-

der consistent pressure is the pump outlet – 5 m. filter – watermaker inlet connections . For this

section is necessary to use a good quality PN 15 min. reinforced hose. An inadequate hose

could burst, jeopardizing seriously the safety of the boat.

“Armovin” type hose int. dia. 16 mm.

Reinforced ho-se PN15 min int. dia. 16 mm.

Exhausted discharge

Plumb to pressure side of boat fresh water sys-

Page 10: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

10

The hydraulic connections are the followings:

Low pressure

max 3 bar

-connections sea water inlet- net filter -

backflow valve inlet.

-connection watermaker’s exhaust dis-

charge - drain outlet.

PN 5 stainless steel spring type

hose 16 mm int. diam

Medium pres-

sure – max

13 bar

-connections fresh water pressurized sys-

tem–carbon filter-backflow valve outlet–

pump inlet

-connections pump outlet-5 microns fil-

ter– watermaker inlet.

PN 15 reinforced hose 16 mm

int. diam.)

Low pressure -

max 3 bar

- Connection to the fresh water tank

Small 6X 8 blue pipe (furniched)

PUMP CONNECTIONS:

Connect the in/out hoses to the pump as follows:

WATERMAKER CONNECTIONS:

Connect the in/out hoses to the watermaker as follows:

OUT

IN

Connection to the fresh water tank (use the small 6X8 hose).

The connection has to be made, using the small hose furnished with the equipment, and relevant

endowed fittings.

The connection has to be made between the little grey fitting located on the right side of the sil-

ver vessel, and the upper side of the tank, on a ¼” outlet if available.

It is possible, in case of metal tanks, to make a ¼” threaded hole where to connect the endowed

male connector.

An ulterior possibility is to draw a “T” derivation on the tank air drain hose.

This is possible if the breather pipe section is enough larger (16 mm.) to avoid that the water

flow from the watermaker can block the leak, creating functional problems to the fresh water

pump.

Fresh

water

Page 11: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

11

There are no particular limits on the connection length. The bending radius of the hose doesn't

have to be less than 50 mm.

2.Installation

2.5 Electric connections

� Remote control panel mounting

The remote control panel has the following dimensions:

width 135 mm. height 116 mm.

It can be flush mounted on any surface, providing the area behind is free of moisture and conden-

sation and there is enough depth to house the rear part of the panel (approx. 8 cm.).

To cut on the mounting surface will have the following dimensions:

width 115 mm. height 97 mm.

� Wiring

Power Supply

The Power supply, coming from the service batteries, needs to be connected to the terminals +

and – of the Pump Box. An automatic circuit breaker (32A for 12VDC systems and 16A for

24VDC systems) must be installed on the power supply. The section of the cables must be ade-

quate. See the table below:

Voltage Automatic Cable lenght

switch up to 3 mts 3 - 7 mt. 7-10 mt.

Volt Ampere mm2 AVG mm2 AVG mm2 AVG

12 32 10 7 16 5 25 3

24 16 4 11 4 11 6 9

Connections between the pump box and the computer box

4 cables (section 2,5 mm2) will connect the pump box with the computer box.

The cables + / - will provide the power to the computer box.

The cables P1 and P2 will provide the commands to the two pumps of the systems.

Connections between the computer box and pressure switch and electrovalve

The pressure switch, positioned on the watermaker, has to be connected to the clamps PS/PS in

the computer box (section 2,5 mm2)

The electrovalve, positioned on the active carbon filter has to be connected to the clamps EV/EV

in the computer box (section 2,5 mm2)

Connection between the computer box and remote panel.

Connect the remote panel to the computer box using pre wired cable supplied (standard length 10

mts.)

Page 12: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

12

Wiring connection diagram

Pressure switch

Electrovalve

Page 13: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

13

3. Operation

3.1. Remote panel commands

KEYBOARD FEATURES

The panel keyboard has a total of four push button. The display light switches off after 15 min-

utes of not use. Pushing any button, the display will light again, without activate any other

command. The functions of the push buttons are:

START Used to start the system.

If it is pushed shortly the system starts and the unit will run indefinitely until will be pushed

STOP.

If it is pushed for at least 3 seconds the system starts, and will stop automatically after the work-

ing hours selected with the timer (see menu functions).

It can anyway be stopped before, pushing STOP.

It is used as well to scroll the different options in the single menu.

STOP Used to stop the system.

The system, once pushed STOP, usually doesn’t stop suddenly. It automatically await for the

correct positioning of the internal valve (2-3 seconds), and then stops automatically.

If the automatic washing is activated (washing light on), the system, once pushed STOP, will

perform the automatic washing (1 min) before stops.

The push button STOP is used as well to exit from the menu function.

WASHING Used to rinse the system automatically with fresh water.

If it is pushed shortly the system will get ready to perform an automatic washing (1 minute long)

once the system will be stopped.

If it is pushed for at least 3 seconds the system will just perform a 10 minutes rinsing, without

suck up sea water.

MENU Used to enter into the MENU mode and modify some parameters.

Pushing it repeatedly the different MENU options can be scrolled.

On his turn the START push button allows to scroll the different options of the single menu.

The system recognizes the current value without any further command.

The STOP push button allows to exit from the MENU function.

Page 14: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

14

Menu options:

• PUMPS.

4 options are available:

P1 the system works with pump1 only. In this case the production will be about 30 lit/h

and the electric consumption will be about 100 watt

P2 the system works with pump2 only. In this case the production will be about 30 lit/h

and the electric consumption will be about 100 watt

P1&P2 the system works with one pump only, alternating p1 and P2 every 20 minutes in

order to balance the wearing of the two pumps. Even in this case the production will be

about 30 lit/h and the electric consumption will be about 100 watt.

P1+P2 the system works with both pumps. In this case the production will be about 60

lit/h and the electric consumption will be about 240 watt

• WORKING TIME (timer)

It allows to select the working time of the watermaker (1-6 hours).

The timer is activated if the START button is pushed for more than 3 seconds only.

• BY-PASS

It allows to exclude the sensor (signal pressure switch) that detects the correct cycling of

the ERS. The operation with the by-pass is necessary only in case of malfunctioning of

the signal pressure switch (in example if the system gets blocks, with the message “

SYSTEM BLOCKED”, not as consequence of a real hydraulic problem, but just as con-

sequence of the malfunctioning of the probe.

The bypass is used also during special operation like the shut down procedure (washing

with chemicals). The bypass activation is automatically removed after one single produc-

tion cycle.

Don’t activate the by-pass if not necessary.

• AUTOMATIC START-UP. This function activate automatically the first start up proce-

dure. The procedure is necessary when a new machine is started for the first time, or

after the filter cartridge replacement, or a general service. The procedure allows

to purge completely the air from the system, and from the seawater and the washing

fresh water hoses. The depressurization valve must be opened before start the proce-

dure.

• PERIODIC WASHING This function allows a periodic automatic rinsing (every 6-10

days) with fresh water. It can be used before long inactivity periods. The single washing

operation will last about 1 minute. The consumed fresh water, for every washing, is

about 10 liters.

Therefore it is suggested to evaluate if the fresh water reservoir is enough for the pro-

grammed cycles. Selecting NO, the function will be disabled.

To activated the function select the days (6-10), exit from the menu, pushing STOP, and

then push WASHING for 3 seconds.

The display will indicate the remaining day before the first rinsing. The function is any-

way disabled pushing STOP, or after a normal production cycle.

Page 15: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

15

MESSAGES

SYSTEM STANDBY

It indicates that the system is ready to be set and started.

TOTAL HOURS

It indicates that the total, progressive working time of the watermakers.

SYSTEM WASHING

It indicates that the unit is in washing mode (pumps and electrovalve on).

SYSTEM BLOCKED

The message must be acknowledged pushing STOP.

This messages means that an hydraulic block of the machine occurred, and then the pumps has

been switched off as safety procedure. In this case is suggested to perform a reset procedure and

investigate on the possible hydraulic origins of the problem.

If the origin of the problem is just a malfunctioning of the signal pressure switch, it is possible to

start again the unit, activating the bypass.

BYPASS WARNING

This message advice or remember that the unit is working in bypass mode (then some safety

functions are disabled).

CHANGE PUMP FILTERS

This is a blinking messages that must be acknowledged pressing the key STOP

This messages suggest to replace the filter of the pump group.

3. Operation

3.2. First start-up procedure

The first start-up procedure is necessary to start the first time a new system, just installed.

The purpose of the procedure is basically purge out the air from the system.

It can be used as well after a filter replacement, or after other maintenance operations.

Preliminary checks:

� Verify that all components are connected correctly.

� Verify that the filters cartridges are installed.

� Verify that the seawater valve, and the possible drain valve, are opened.

� Verify that the reset valve is closed (lever orthogonal to the body valve) and the positioner

completely unscrewed.

� Verify that the small gray valve on the active carbon filter is opened and the fresh water

pump of the boat is on.

� Verify that the fresh water tanks are full enough (at least 50 liters) to perform the first wash-

ing operations.

Start-up procedure:

1. Open halfway the depressurization valve (45°).

2. Activate the start up procedure throw the function of the MENU (select the specific function

in the menu mode, exit from menu mode pushing STOP, and start the procedure pushing

START).

3. Close the depressurization valve when the display shows the specific message.

The procedure lasts about 3 minutes. It can anyway stopped anytime pushing STOP.

After the procedure the system is ready to start normally.

Page 16: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

16

3. Operation

3.3. Normal operation procedure

• It is always strictly recommended to select the automatic washing, pushing WASH-

ING.

Production without timer.

-Select the pump mode (P1, P2, P2&P2, or P1+P2) throw the specific pump menu (the system

anyway will hold the previous setting, even if the electric power is switched off).

-Push the button START.

The control will open the depressurization valve, helping the inlet pump hose to get filled with

water. Then the pump(S) will start after 5 seconds.

The display will show the increasing production time.

-Push STOP to stop the unit.

If the washing has been selected, the system will start the washing procedure, and then will stop

automatically after 1 minute.

Production with timer.

-Select the pump mode (P1, P2, P2&P2, or P1+P2) throw the specific pump menu (the system

anyway will hold the previous setting, even if the electric power is switched off).

-Select the timing (1-6 hours) throw the specific timer menu (the system will hold as well the

previous setting.)

-Push the button START for more than 3 seconds.

The display will show the decreasing production time.

The system will stop after the selected hours, performing before, if selected, the automatic wash-

ing.

Anyway the system can be stopped at any time pushing STOP.

Single washing operation (10 min. last)

-Select the pump mode P1+P2

-Push washing for more than 3 seconds.

The display will indicate the remaining time. It is possible anyway to stop the operation at any-

time pushing STOP.

Periodic washing

-Select the days (6-10) in the washing menu

- Exit from the menu pushing STOP

- Push WASHING for 3 seconds.

The display will indicate the remaining day before the first rinsing.

The function is anyway disabled pushing STOP, or after a normal production cycle.

Page 17: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

17

ATTENTION If the watermaker get air, (or if some other problem occurs) the automatic hydraulic valve may

stop in a central position. This means that pressure on both sides of the valve are the same and

the unit is effectively stalled and has to be manually restarted.

In this case the working pressure goes up suddenly (up to 8-9 Bar) and the pumps are switched

off from the pumps pressure switch. The pumps then have the tendency to try to restart when the

pressure decreases, and then to jam again, resulting in a typical start-stop noise. After approx. 20

sec. the computer recognize the problem , and turn off the pumps, and the message “WARNING

SYSTEM BLOCKED” is displayed.

This event, besides being very unusual, does not damage the system, but it is necessary to reset

the valve with the following simple procedure:

RESET PROCEDURE

1. Turn the system off.

2. Open the reset valve (lever in horizontal position).

3. Screw the positioner knob clockwise until it can be moved no further.

10 turns at least are necessary.

4. Unscrew the positioner knob up to the original position, until when it is blocked

back.

5. Close the reset valve (lever in vertical position).

6. Restart the system

Page 18: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

18

4. Maintenance

4.1 Shutdown procedure It is necessary to perform the shutdown procedure before effecting standstills longer than 3

months, for instance before laying up for winter.

The purpose of the shutdown is to clean the unit of possible deposits of limestone, and to inhibit

the growth of microorganisms that may reduce the reverse osmosis membrane's efficiency.

The following equipment is necessary in order to perform the shutdown operation:

� 1 ea. recipient 20 liters minimum capacity (a bucket of such capacity could also be suitable).

� Two 16 mm. linen hoses of a length that allow them to be fed into the same container

� A prepared shutdown solution SCHENKER CLEANING 1.

� Tools for de-assembling hoses (screwdrivers, pliers, etc.)

Hydraulic connections diagram to perform the shutdown

The shutdown procedure is:

1. Collect approx. 15 liters of unchlorinated fresh water into the bucket. The water produced by

the watermaker itself could be fine.

2. Empty the entire content of the SCHENKER CLEANING 1 solution into the picked water,

and mix carefully following the indications on the pack. Wear a protection mask in order to

avoid inhaling product dusts. The water temperature doesn't have to be lower than 25°C

preferably.

3. Close the grey valve on the active carbon filter.

4. Disconnect watermaker unit drain hose and the pumps suction hose.

5. Connect two hose pieces to the drain and to the pump suction.

6. Insert the end side of the hoses into the bucket, verifying that the hoses have been properly

dipped in the solution and that they don't inhale air.

7. Open the depressurization valve at 45°.

8. Start the watermaker (with both pumps, and bypass activated ) and leave the system on for

approx. 30 min., checking that the hoses are properly positioned in the container, so as to

avoid drawing air or spilling the liquid into the boat.

9. Turn the watermaker off, disconnect hose pieces, and connect the pump suction, drain and

water production original hoses.

Chemical Cleaning Kits:

Schenker No 1 is an acid based organic cleaner.

This is used for 'pickling' the watermaker when not in use and as part of the general cleaning

process. See 4.1 Shutdown procedure

Schenker No 2 is an alkaline base organic cleaner. If the watermaker has been left standing

without pickling or has a 'bag egg” smell, cleaning with Schenker No2 will remove this.

Page 19: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

19

4. Maintenance

4.2 Verifications and periodic maintenance The following periodic procedures are to be followed to maintain trouble free operation:

OPERATION EVERY PROCEDURE

Strainer check and cleaning

Every 5 days

Check and clean

5 micron cartridge replacement

Every 15-20 days in average conditions (4 hours/day usage). Anyway replace it when the message CHANGE PUMP FILTERS

appears.

Unscrew anticlockwise the filter holder.

Active carbon filter replacement

Every 6 months Close the grey valve before open the filter

Purge periodically the air from the sys-tem, opening at 45° for a couple of min-utes the depressuri-zation valve

Every 15 days

� Check the working pressure

Check the pressure on the manometer located on the front of the unit.

The working pressure depends on many factors such as water temperature, salinity level of sea-

water, battery voltage, cleanliness of membranes and type of installation.

The pressure, under mid range working conditions is approx. 5,6 BAR with one pump on, and

approx. 7,6 BAR with two pumps on. There is a small pressure loss , in the range of 0,2 Bars,

during the cycle.

� Membrane replacement

The reverse osmosis membranes have an average working life of 7 years. After 5 years they may

start to degrade. If in doubt as to their condition contact a Schenker service point and replace as a

matter of course after 7 years.

Page 20: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

20

4. MAINTENANCE

4.3 SYSTEM TROUBLESHOOTING

PROBLEM PROBABLE CAUSE SOLUTION

Pumps do not start

Pressure switch burned or dis-

connected

Electronic failure

Restore

Activate the pumps with

the miscoswitches

Pumps start but stop at

high pressure

System is blocked

Dirty filter

Dirty membranes

Trouble in the cycling system

Perform Reset

Replace cartridge

Perform cleaning cycle

Contact a Schenker service

point

While functioning the

pumps momentarily shuts

down

Pump pressure switch not cali-

brated

Dirty filter or membranes

Cold sea water

Calibrate pressure switch

Clean or replace

Calibrate pressure switch

Low production / normal or

low pressure

Exhausted batteries

Air in the plant

Seal system leak

Check battery charge

Perform bleeding

Contact a Schenker service

point

Low production / high

pressure (> 8 Bar)

Cold sea water

Dirty membranes

Normal condition

Perform cleaning cycle

Leaking in the plant

Loose connectors

ERS loss

Tighten connectors

Contact a service point

Page 21: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

21

ELECTRONIC TROUBLESHOOTING

Probe (system pressure switch ) troubleshooting:

If the system goes frequently in blocked position (generating the message SYSTEM BLOCKED)

without hydraulic problems, this could possible that the origin of fault is a malfunctioning of the

probe (pressure switch)

The pressure switch can be tested with following procedure:

1. De-connect the pressure switch cables.

2. Activate the by-pass and start the system.

3. Check with a meter in ohm position, between the cables PS/PS, the functioning of the pres-

sure switch. If working, the pressure switch closes and open the circuit alternatively each 3-4

seconds.

4. If the pressure switch is always close or open during the functioning of the watermaker, it is

out of service and must be replaced.

Page 22: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

22

5. SAFETY WARNINGS

� Ensure the watermaker is correctly installed by contacting a Schenker service point.

� The water produced by a Schenker Modular 60 watermaker using clean sea water will have

an average quality of 400 ppm TDS. Unless the correct cleaning procedures are carried out in

accordance with this manual, there may be bacteria present in the produced water.

� Avoid using the watermaker where seawater is polluted (ports, or close to built-up areas, etc.)

� Do not locate near the pumps unit in areas that can reach elevated temperature. Ie: Engine

compartments or where inflammable substances are stored. This will adversely affect the

working of the pumps and may present a fire risk.

� Do not touch the pumps and pump fans when the unit is working.

� Children and those unfamiliar with the watermaker shall not touch or operate the unit.

� Check periodically for leaks.

� Do not operate the watermaker when the vessel is left unattended.

� Avoid installing the watermaker where a leak may go unnoticed and jeopardize the safety of

the boat.

� Unqualified and non-Schenker personnel shall not perform any maintenance work on the wa-

termaker

Page 23: OPERATION AND MAINTENANCE MANUAL - … · OPERATION AND MAINTENANCE MANUAL 1 ... installed inside blue color high-pressure vessel. ... and it measures the pump running pressure. Depressurization

23

6. WARRANTY

The equipment and the relevant accessories are guaranteed 12 months from delivery. The guaran-

tee does not include consumable items (filters, carbon filters, membranes, etc.). The “ERS” pres-

sure amplification device is guaranteed 36 months, provided that the annual maintenance is per-

formed at a Schenker service point.

The guarantee covers faults, defect of materials and parts. It is limited to the replacement or re-

pair of faulty parts. The expense for the disconnecting and reinstalling on the vessel and transport

of the equipment from or to our Service Point, or our factory will be at the customers own ex-

pense.

The under guarantee delivered parts transport, will be at customer’s own risk.

In case of repairs under guarantee performed by our technicians on the customer vessel, the

faulty parts replacement cost will be at Schenker's expense, while manpower and travel expenses

will be charged to the customer. The guarantee does not include faults caused by negligence in

operating, maintenance and installation of the device (if not carried out by an authorised Schen-

ker Service point).

Dismantling by non-authorized personnel will render void all guarantees. Schenker Italia can not

be held liable for any direct or indirect damage caused by the malfunctioning equipment, limiting

its responsibility to the repair and replacement of faulty parts.