Operating ParametersSUNNY BOY/SUNNY MINI CENTRAL/WINDY BOYTechnical Description

Page 2: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250
Page 3: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Table of Contents

Technical Description SB_SMC_WB_Par-TEN104250 3

Table of Contents1 Notes on this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.1 Area of Validity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.2 Target Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.3 Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.4 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Explanation of the Operating Parameters. . . . . . . . . . . . . 84 Setting the Country Standard . . . . . . . . . . . . . . . . . . . . . . 155 Value Ranges and Factory Settings . . . . . . . . . . . . . . . . . 175.1 Sunny Boy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175.1.1 Sunny Boy 1200/1700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175.1.2 Sunny Boy 2100TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185.1.3 Sunny Boy 2500/3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195.1.4 Sunny Boy 3300/3800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205.1.5 Sunny Boy 3300TL HC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215.2 Sunny Mini Central . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225.2.1 Sunny Mini Central 4600A/5000A/6000A. . . . . . . . . . . . . . . . . . . . . . . . 225.2.2 Sunny Mini Central 7000HV/7000HV-11 . . . . . . . . . . . . . . . . . . . . . . . . . 245.2.3 Sunny Mini Central 6000TL/7000TL/8000TL . . . . . . . . . . . . . . . . . . . . . . . 265.2.4 Sunny Mini Central 9000TL/10000TL/11000TL . . . . . . . . . . . . . . . . . . . . 285.2.5 Sunny Mini Central 9000TL/10000TL/11000TL

with Reactive Power Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305.3 Windy Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325.3.1 Windy Boy 1100LV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325.3.2 Windy Boy 1200/1700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335.3.3 Windy Boy 2500/3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345.3.4 Windy Boy 3300/3800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355.3.5 Windy Boy 5000A/6000A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Page 4: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Table of Contents SMA Solar Technology AG

4 SB_SMC_WB_Par-TEN104250 Technical Description

Page 5: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Notes on this Manual

Technical Description SB_SMC_WB_Par-TEN104250 5

1 Notes on this Manual1.1 Area of ValidityThis document describes the operating parameters including value ranges and factory settings for the following SMA inverters:

1.2 Target GroupThis document is intended for installers and operators of the inverter. Some tasks described in this document may only be carried out by electrically qualified persons.

1.3 Additional InformationFor information on assembly, installation, commissioning, and maintenance of the inverter as well as device-specific technical data refer to the installation guide of the respective inverter. You will find information on operating the inverter in the user manual of the respective inverter.

Sunny Boy Windy Boy Sunny Mini CentralSB 1200 WB 1200 SMC 4600ASB 1700 WB 1700 SMC 5000ASB 2100TL WB 2500 SMC 6000ASB 2500 WB 3000 SMC 7000HVSB 3000 WB 3300 SMC 7000HV-11SB 3300TL HC WB 3800 SMC 6000TLSB 3300 WB 5000A SMC 7000TLSB 3800 WB 6000A SMC 8000TL

SMC 9000TL-10SMC 10000TL-10SMC 11000TL-10SMC 9000TLRP-10SMC 10000TLRP-10SMC 11000TLRP-10

Page 6: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Notes on this Manual SMA Solar Technology AG

6 SB_SMC_WB_Par-TEN104250 Technical Description

1.4 Symbols UsedThe following types of safety instructions and general information are used in this manual:

G

DANGER!

"DANGER" indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING!

"WARNING" indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION!

"CAUTION" indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE!

"NOTICE" indicates a situation that can result in property damage, if not avoided.InformationInformation provides tips that are valuable for the optimal installation and operation of your product.

Page 7: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Safety Instructions

Technical Description SB_SMC_WB_Par-TEN104250 7

2 Safety InstructionsThe various operating parameters control the functionality of the inverter. They can only be viewed and changed using a communication device or communication software.Some parameters can only be viewed by an installer (grayed-out parameters). The so-called ”installer password” is required for this.Parameters designated with * are safety-related grid monitoring parameters (SMA Grid Guard parameters). In order to change SMA Grid Guard parameters, you will need to enter the SMA Grid Guard Code. The application form is located in the download area at www.SMA.de/en, in the "Certificate" category for each inverter.

DANGER!Danger to life through changing the inverter's internal safety specifications.

Unauthorized changes to the SMA Grid Guard parameters void the operating license.• Only change SMA Grid Guard parameters with express permission of the utility

operator.Parameter Factory SettingsYou can see the standard to which the inverter was set upon delivery from the type plate and the supplementary document with the factory settings.

Page 8: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Explanation of the Operating Parameters SMA Solar Technology AG

8 SB_SMC_WB_Par-TEN104250 Technical Description

3 Explanation of the Operating ParametersName DescriptionACVtgRPro* Voltage surge protection (only relevant for Germany).

In Germany, Sunny Boy and Sunny Mini Central inverters can feed into the public grid with up to 260 V AC. However, the DIN VDE 0126-1-1 standard stipulates that the 10-minute AC voltage average may not exceed 253 V. If the 10-minute average exceeds the threshold value of 253 V, the inverter will disconnect from the grid. As soon as the 10-minute average returns to a value of less than 253 V, the inverter will continue to feed power into the grid. If voltage surge protection is not required in the relevant grid area (outside Germany), it can be deactivated by presetting the LDVtgC parameter. In this case, only the quick disconnection will be active, which can be configured through the Vac-Max parameter.

AID-Esk-Alpha* Gain factor of the escalating anti-island processAntiIsland-Ampl* Amplification of the anti-island process (alternative anti-islanding process,

which is deactivated for Germany).AntiIsland-Freq* Repetition rate of the AntiIsland process (alternative anti-islanding process,

which is deactivated for Germany).AntiIsland-Lim* Maximum frequency, above and below the grid frequency of 50 or 60 Hz,

before the grid monitoring system disconnects the device from the grid.Control Configuration of the current control. If the operating parameter "Control" is

set to "Auto", the inverter automatically chooses the optimal type of current regulation. If the operating parameter "Control" is set to "Grid", the inverter regulates on the grid side. If set to "Bridge", the inverter regulates on the bridge side. This setting can help in the event of difficult grid conditions. Discuss the alteration of this parameter with the SMA Serviceline.

DC-Offset_Max* Threshold value for the maximum direct current component in the AC current.

Default* Defines the country standard for adjusting country-specific information. You will find the procedure for changing country settings in section 4 ”Setting the Country Standard” (page 15).

dFac-Max* Maximum change of grid frequency before the grid monitoring system disconnects the device from the grid.

DGS-HystVolNom* Hysteresis in percent.When the AC voltage exceeds the value set, the inverter starts feeding again.(only for SMC 9000TLRP-10, SMC 10000TLRP-10 and SMC 11000TLRP-10, SMC 7000HV-11)

Page 9: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Explanation of the Operating Parameters

Technical Description SB_SMC_WB_Par-TEN104250 9

DGS-PWMVolNom* Switch-off voltage in percent relative to VRef + VRefOfs.When the AC voltage drops below the value set here, the inverter will stop feeding.(only for SMC 9000TLRP-10, SMC 10000TLRP-10 and SMC 11000TLRP-10, SMC 7000HV-11)

dV V-Const Device-internal parameter.dV-Mpp Track Device-internal parameter.dVref-Mpp Device-internal parameter.dZac-Max Maximum change of grid impedance before the grid monitoring system

disconnects the device from the grid.E_total Total energy yield of the inverter.

Changing this parameter may be necessary if you replace your inverter and want to use data from the old device.

Fac-delta-*Fac-delta+*Fac-delta-Fast*Fac-delta+Fast*

Maximum permissible frequency deviation (frequency increase protection and frequency drop protection), above (Fac-delta+, Fac-delta+Fast) and below (Fac-delta-, Fac-delta-Fast) a grid frequency of 50 or 60 Hz, before the grid monitoring system disconnects the device from the grid.

Fac-Limit deltaFac-Start delta

For setting the frequency-dependent output derating in the "Off Grid" operating mode. More information on this subject can be found in the Sunny Island operation manual.

Fac-Min-Fast-Tm*Fac-Max-Fast-Tm*Fac-Min-Tm*Fac-Max-Tm*

Disconnection time for frequency increase protection (Fac-delta+, Fac-delta+Fast) and frequency drop protection (Fac-delta-, Fac-delta-Fast).

Fac-Pderating Active power limitation depending on frequency.Fac-Tavg Averaging time of grid frequency measurement.Fan-Test By setting the "Fan-Test" parameter to "1", the functionality of the fan can

be tested (only for inverters with fan).Firmware-BFR Firmware version of the operation control unit (BFR)Firmware-SRR Firmware version of the current control unit (SRR)GndFltRea Controls the behavior of the inverter in the event of a ground fault.

• GndFltWrn: If there is a ground fault, the inverter continues to feed into the grid.

• GndFltDscon: If there is a ground fault, the inverter disconnects from the grid.

Name Description

Page 10: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Explanation of the Operating Parameters SMA Solar Technology AG

10 SB_SMC_WB_Par-TEN104250 Technical Description

h_Total Total operating hours of the inverter. Changing this parameter may be necessary if you replace your inverter and want to use data from the old device.

Hardware-BFS Hardware version of the operation control unit (BFS).I SearchNewMPP Device-internal parameter.impedance test Activation and deactivation of the islanding detection via impedance

monitoring (0 = off / 1 = on).This parameter can only be changed when the inverter is deactivated (disconnection on the AC side), or if it is in "Stop" mode.

Inst.-Code SMA Grid Guard parameters can only be changed after the SMA Grid Guard password has been entered.

KI-Wind-Reg This value defines the integral factor of the power control. It determines the factor of the time-related response to the control deviation (control deviation = nominal power − actual power).ki * Time integral of control deviation = corrective power valueExcessively high values lead to vibrations and instability in the system.

KP-Wind-Reg This value defines the proportional factor of the power control. It sets the factor of the direct response to the control deviation.kp * Control deviation = corrective power valueExcessively high values lead to vibrations and instability in the system.

LdVtgC* Compensation for the voltage drop in the cabling.This parameter takes into account the voltage drop between the inverter and the power supply line point. The 10-minute average voltage at the inverter connection must not exceed the sum of ACVtgRPro plus LDVtgC. The LDVtgC parameter is preset to 0 V for Germany. In grid regions where an additional voltage increase protection (see ACVtgRPro parameter) is not required, the LDVtgC parameter is preset to 50 V. The voltage increase protection is therefore deactivated for these grid regions (253 V + 50 V = 303 V) and only the fast disconnection intervenes via the Vac-Max parameter.

Memory Function Default Param.: Resets all country-independent parameters to the factory settings.reset op.data: resets all operating data.Reset errors: resets a permanent fault.

Netzanschluss (Grid connection)

With this operating parameter, it is possible to store information in the inverter, regarding which phase the inverter is connected to. This means that in the plant overview it is easy to manage which inverter is installed at which phase.

Name Description

Page 11: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Explanation of the Operating Parameters

Technical Description SB_SMC_WB_Par-TEN104250 11

Operating Mode Operating mode of the inverter:Mpp-Operation: Maximum Power PointV-Const: Constant voltage mode (the setpoint is defined in "Vconst-Setpoint")Stop: disconnection from grid, no operationTurbine: operating mode for small wind turbine systems (this operating mode may only be set in wind energy inverters). The use of this mode is expressly prohibited for inverters of other energy forms, such as Sunny Boys or Sunny Mini Centrals. Otherwise the operation permission and all warranty claims become void.)

P-HzStop* Switch-back frequency for full active power.More information on this parameter can be found in the installation guide of the respective inverter.

P-HzStr* Start frequency for active power limitation. More information on this parameter can be found in the installation guide of the respective inverter.

P-W* Maximum active power of the inverter for an active power process with a firmly specified active power limitation.

P-WCtlHzMod* Activation of the characteristic curve for the active power limitation, in relation to the set frequency thresholds P(f).More information on this parameter can be found in the installation guide of the respective inverter.

P-WGra* Gradient of the active power limitation.More information on this parameter can be found in the installation guide of the respective inverter.

P-Wind-Ramp This parameter lets you configure the controlled startup of the small wind turbine system. Only once the inverter is connected to the grid, will the small wind turbine system not be charged rapidly, but rather with a configurable ramp. After the connection process, this parameter will no longer be active.

P-WMod* Activation of the process for active power limitation.More information on this parameter can be found in the installation guide of the respective inverter.

PF-PF* Specification of the displacement power factor cos φ.PF-PFExt* Setting of the excitation (lagging, leading).Phase* Setting the phase to which the inverter feeds.

More information on this parameter can be found in the installation guide of the respective inverter.

Plimit Display of the active power limitation of the inverter.

Name Description

Page 12: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Explanation of the Operating Parameters SMA Solar Technology AG

12 SB_SMC_WB_Par-TEN104250 Technical Description

Pmax Active power limitation of the inverter.PowerBalancer Operating mode of the SMA Power Balancer for prevention of asymmetric

loads in 3-phase systems with Sunny Mini Central. The SMA Power Balancer has four operating modes:Off: the SMA Power Balancer is deactivated. In the event of a device fault or grid voltage disturbance at an inverter, only this inverter is disconnected from the grid and the other two devices continue to run at an undiminished power level.PowerGuard: operating mode in which no distinction is made between a device fault and a grid voltage disturbance. The relevant device disconnects itself from the grid, while the other two inverters limit their output to 5 kVA over a 10-minute average.PhaseGuard: operating mode in which a distinction is made between a device fault and a grid voltage disturbance. In the event of a device fault at the first Sunny Mini Central, the other two inverters continue to operate without reducing their output. In case of a grid voltage disturbance, all devices will immediately disconnect from the grid.FaultGuard: operating mode in which a distinction is made between a device fault and a grid voltage disturbance. In the event of a device fault, the fault message will be sent to the other two devices with a time delay of 5 minutes. After the 5 minutes have passed, the other two devices will disconnect from the grid as well. In case of a grid voltage disturbance, all devices will immediately disconnect from the grid.

PTot-Min The DC power required before the inverter begins feeding power into the grid.

Q-VArMod* Selection of the reactive power procedure.More information on this parameter can be found in the installation guide of the respective inverter.

Ripple-Ctl-FrqRipple-Ctl-LevRipple-Ctl-Rcvr

The "Ripple-Ctl-Frq", "Ripple-Ctl-Lev", and "Ripple-Ctl-Rcvr" parameters are intended for handling ripple control signals from the SMA inverters. These parameters are not available for all inverters. These parameters may only be changed after prior consultation with SMA Solar Technology AG.

Riso-Min This parameter is used to change the threshold value for the insulation monitoring. The parameter cannot be permanently saved.

Slimit Apparent power limitation of the inverterSMA-Grid-Guard SMA Grid Guard versionSMA-SN Serial number of inverterSmax Apparent power limitation of the inverter

Name Description

Page 13: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Explanation of the Operating Parameters

Technical Description SB_SMC_WB_Par-TEN104250 13

Speicher (Memory)

Permanent: modified parameters are stored in the EEPROM and can be used even when the inverter has been restarted.Volatil: prevents the parameters being saved in the EEPROM. The parameters are only saved until the next start.

T-Max-FanT-Max-Fan-InT-Max-Fan-Mod

Temperature for maximum fan rotation speed.

T-Start-FanT-Start-Fan-InT-Start-Fan-Mod

As of this temperature, the fan will start to run at minimum speed.

T-Start* Grid monitoring time: time during which the inverter monitors the grid before it connects to the grid.

T-Stop The period the inverter waits before disconnecting from the grid when Udc drops below Vpv-Start.

T-Stop-FanT-Stop-Fan-InT-Stop-Fan-Mod

If, after a temperature increase, the inverter cools down to below this threshold value, the fan will switch off again.

testcurrent Zac Setting for the impulse for impedance monitoring (0 = off).This parameter can only be changed when the inverter is deactivated (disconnection on the AC side), or if it is in "Stop" mode.

UdcWindStart This parameter defines the starting point of the output characteristic curve.When the DC input voltage reaches this value after grid synchronization, the inverter uses the output characteristic curve to start the load of the small wind turbine system and feeds into the grid.

UdcWindStop This parameter is only relevant for the Windy Boy 1100LV. If the value falls below UDCWindStop, the inverter decreases its internal (DC) consumption by deactivating the power semiconductor.

Uac-Min-Tm*Uac-Max-Tm*Uac-Min-Fast-Tm*Uac-Max-Fast-Tm*

Switch-off time for voltage increase protection (Uac-Max-Tm, Uac-Max-Fast-Tm) and voltage decrease protection (Uac-Min-Tm, Uac-Min-Fast-Tm).

Vac-Min*Vac-Max*Uac-Min-Fast*Uac-Max-Fast*

Additional monitoring of AC voltage (deactivated for Germany). Lower (Vac-Min) and upper (Vac-Max) limits of the allowable AC voltage, before the grid monitoring system disconnects the device from the grid.

Vac-Tavg Averaging time for measuring grid frequency.

Name Description

Page 14: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Explanation of the Operating Parameters SMA Solar Technology AG

14 SB_SMC_WB_Par-TEN104250 Technical Description

Vconst-Setpoint Target PV voltage for constant operational voltage. This parameter is only important when the "Operating Mode" parameter is set to "V-Const".

Vpv-Start The DC voltage required before the inverter begins feeding power into the grid.This value is above the minimum MPP voltage which is required in order to always guarantee safe connection to the grid, and to minimize grid relay wear.If, after disconnection from the grid, and in the absence of any further disturbances, the inverter does not automatically reconnect to the grid, this parameter can be decreased in small steps.It should be noted that if the value is set too low, this leads to an increased number of connections to the grid, and thus to increased wear of components.

VRef* Phase voltage at the output side of the transformer.VRefOfs* Adjustable voltage offset (e.g. through cable losses).WGraReconEna* Activation of the gradient of the active power limitation upon reactivation

after a system incident.Wind_a0Wind_a1Wind_a2Wind_a3

The following formula gives the factors for the voltage-dependent power calculation:P(u) = a0 + a1 * U + a2 * U² + a3 * U³

Zac-Max Maximum grid impedance before the grid monitoring system disconnects the device from the grid.

Name Description

Page 15: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Setting the Country Standard

Technical Description SB_SMC_WB_Par-TEN104250 15

4 Setting the Country StandardUsing the "Default" parameter you can set the installation country and/or the grid connection standard valid for your country via a communication device or a PC with appropriate software. This is necessary if the inverter was originally ordered for another country and was preset accordingly by SMA Solar Technology AG. If your country or the standard valid in your country is not listed in the following overview, please contact the SMA Serviceline.Parameter Setting DescriptionDefault* GER/MSD Country-specific parameter settings for Germany in

accordance with the DIN VDE 0126 (4.99)GER/VDE0126-1-1 Country-specific parameter settings for Germany and

France in accordance with the DIN VDE 0126-1-1VDE0126-1-1/UTE Country-specific parameter settings for France in

accordance with the UTE C15-712-1SP/RD1663SP/RD1663-ASP/RD1663/661SP/RD1663/661-A

Country-specific parameter settings for Spain

AUS/AS4777 Country-specific parameter settings for AustraliaIT/DK5940 Ed.2 Country-specific parameter settings for ItalyGBGB/G83GB/G83/1-1

Country-specific parameter settings for Great Britain

KOR/KEPCO Guide Country-specific parameter settings for KoreaEN 50438 Country-specific parameter settings for various

European countriesEN 50438-CZCZ/PPDS

Country-specific parameter settings for the Czech Republic

GR/PPC Country-specific parameter settings for GreeceTH/PEATH/MEATH/IEC61727/PEATH/IEC61727/MEA

Country-specific parameter settings for Thailand (City)

BE/C10/11 Country-specific parameter settings for BelgiumCN/CGC/GF001 Country-specific parameter settings for China

Page 16: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Setting the Country Standard SMA Solar Technology AG

16 SB_SMC_WB_Par-TEN104250 Technical Description

Default* MVtgDirective Extension to the disconnection thresholds of the inverter for voltage and frequency to the extreme values (prerequisite: external three-phase decoupling protection)(only for SMC with Reactive Power Control, SMC 5000A, SMC 6000A, and SMC 7000HV-11)

Other Parameter settings for countries for which no pre-defined settings exist can be configured here.

trimmed If country-specific parameters have been changed, "trimmed" is shown in the display.

OFF_Grid Setting for inverters which are operated in a stand-alone grid. More information can be found in the Sunny Island installation guide.

Parameter Setting Description

Page 17: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 17

5 Value Ranges and Factory Settings5.1 Sunny Boy

5.1.1 Sunny Boy 1200/1700Name Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAntiIsland-Ampl* 0 deg … 10 deg Depending on country standardAntiIsland-Freq* 1 mHz … 2 000 mHz 500 mHzdFac-Max* 0.1 Hz/s … 4.0 Hz/s 4.0 Hz/sE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 4.5 Hz Depending on country standardFac-delta+* 0.1 Hz … 4.5 Hz Depending on country standardGndFltRea* (firmware version 3.06 and higher)

GndFltWrn Depending on country standardGndFltDscon

h_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Pmax* (SB 1200) 0 W … 1 250 1 200 WPmax* (SB 1700) 0 W … 1 750 1 700 WT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sVac-Max* 230 V … 300 V Depending on country standardVac-Min* 160 V … 300 V Depending on country standardVconst-Setpoint 150 V … 430 V 410 VVpv-Start (SB 1200) 110 V … 400 V 120 VVpv-Start (SB 1700) 150 V … 400 V 180 V

Page 18: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

18 SB_SMC_WB_Par-TEN104250 Technical Description

5.1.2 Sunny Boy 2100TLName Value/Range Default ValuedFac-Max* 0.005 Hz/s … 4.0 Hz/s 4.0 Hz/sdV V-Const 0.5 V/s … 20 V/s 2 V/sdV-Mpp Track 0.55 V/TaMpp …

10 V/TaMpp1.4 V/TaMpp

dVref-Mpp 5 V … 380 V 100 VdZac-Max* 0 m Ω … 2 000 m Ω Depending on country standardE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0 Hz … 4.5 Hz Depending on country standardFac-delta+* 0 Hz … 4.5 Hz Depending on country standardh_Total 0 h … 200 000 h 0 hI SearchNewMPP 0 mA … 9 000 mA 164 mAOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Riso-Min 0 k Ω … 10 000 k Ω 1 200 k ΩT-Start* 5 s … 300 s 10 sT-Stop 1 s … 300 s 10 sVac-Max* 180 V … 300 V Depending on country standardVac-Min* 180 V … 300 V Depending on country standardVconst-Setpoint 125 V … 600 V 600 VVpv-Start 125 V … 600 V 150 V

Page 19: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 19

5.1.3 Sunny Boy 2500/3000Name Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAntiIsland-Ampl* 0 deg … 10 deg Depending on country standardAntiIsland-Freq* 0 mHz … 2 000 mHz 500 mHzdFac-Max* 0.1 Hz/s … 4.0 Hz/s 4.0 Hz/sE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 4.5 Hz Depending on country standardFac-delta+* 0.1 Hz … 4.5 Hz Depending on country standardh_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Pmax (SB 2500) 0 W … 2 550 W 2 500 WPmax (SB 3000) 0 W … 3 050 W 3 000 WT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sVac-Max* 230 V … 300 V Depending on country standardVac-Min* 160 V … 230 V Depending on country standardVconst-Setpoint 250 V … 600 V 600 VVpv-Start (SB 2500) 250 V … 600 V 300 VVpv-Start (SB 3000) 290 V … 600 V 330 V

Page 20: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

20 SB_SMC_WB_Par-TEN104250 Technical Description

5.1.4 Sunny Boy 3300/3800Name Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAntiIsland-Ampl* 0 deg … 10 deg 0 degAntiIsland-Freq* 0 mHz … 2 000 mHz 500 mHzdFac-Max* 0.1 Hz/s … 4.0 Hz/s 4.0 Hz/sdZac-Max 350 m Ω … 20 000 m Ω 700 m ΩE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 4.5 Hz Depending on country standardFac-delta+* 0.1 Hz … 4.5 Hz Depending on country standardGndFltRea GndFltWrn GndFltWrn

GndFltDsconh_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Pmax (SB 3300) 0 … 3 600 W 3 600 WPmax (SB 3800) 0 … 3 800 W 3 800 WRipple-Ctl-Frq 105 Hz … 1 605 Hz 1 605 HzRipple-Ctl-Lev 0.5 % … 8.00 % 1.70 %Ripple-Ctl-Rcvr enable auto

disableauto

Riso-Min 0 k Ω … 10 000 k Ω 1 000 k ΩT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 stestcurrent Zac 0 mA … 16 000 mA 10 000 mAVac-Max* 230 V … 300 V Depending on country standardVac-Min* 160 V … 230 V Depending on country standardVconst-Setpoint 200 V … 500 V 500 VVpv-Start 200 V … 500 V 250 V

Page 21: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 21

5.1.5 Sunny Boy 3300TL HCName Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAntiIsland-Ampl* 0 deg … 10 deg 0 degAntiIsland-Freq* 0 mHz … 2 000 mHz 500 mHzdFac-Max* 0.1 Hz/s … 4.0 Hz/s 4.0 Hz/sdZac-Max* 350 m Ω … 20 000 m Ω Depending on country standardE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 4.5 Hz 2.45 HZFac-delta+* 0.1 Hz … 4.5 Hz 0.19 HZh_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Ripple-Ctl-Frq 105 Hz … 1 605 Hz 1 605 HzRipple-Ctl-Lev 0.5 % … 8.00 % 8.00 %Ripple-Ctl-Rcvr enable disable

disableauto

PTot-Min 0 W … 500 W 35 WRiso-Min 1 500 k Ω … 30 000 k Ω 1 500 k ΩT-Start* 2 s … 300 s 2 stestcurrent Zac 0 mA/1 mA 1 mAVac-Max* 230 V … 300 V 260 VVac-Min* 160 V … 300 V 198 VVconst-Setpoint 0 V … 750 V 290 V

Page 22: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

22 SB_SMC_WB_Par-TEN104250 Technical Description

5.2 Sunny Mini Central

5.2.1 Sunny Mini Central 4600A/5000A/6000AName Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAntiIsland-Ampl* 0 deg … 10 deg 0 degAntiIsland-Freq* 0.1 mHz … 2 000 mHz 500 mHzdFac-Max* 0.1 Hz/s … 6.0 Hz/s Depending on country standarddZac-Max (SMC 4600A) 0.35 m Ω … 20 000 m Ω 685 m ΩdZac-Max (SMC 5000A) 0.35 m Ω … 20 000 m Ω 685 m ΩdZac-Max (SMC 6000A) 0.35 m Ω … 20 000 m Ω 670 m ΩE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 6 Hz Depending on country standardFac-delta+* 0.1 Hz … 5 Hz Depending on country standardFac-Limit delta 0 Hz … 5 Hz 2 HZFac-Start delta 0 Hz … 5 Hz 1 HZFan-Test 0 … 1 0GndFltRea GndFltWrn GndFltWrn

GndFltDsconh_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

P-HzStop* 0 Hz … 5 Hz 0.05 HZP-HzStr* 0 Hz … 5 Hz 0.20 HZP-WCtlHzMod* Off Off

OnP-WGra* 10 %/Hz … 100 %/Hz 40 %/HzPmax* (SMC 4600A) 0 W … 5 050 W 5 000 WPmax* (SMC 5000A) 0 W … 5 550 W 5 500 WPmax* (SMC 6000A) 0 W … 6 050 W 6 000 WPowerBalancer Off Off

PowerGuardPhaseGuardFaultGuard

Ripple-Ctl-Frq 105 Hz … 1 605 Hz 1 605 Hz

Page 23: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 23

Ripple-Ctl-Lev 0.5 % … 8.0 % 8.0 %Ripple-Ctl-Rcvr enable disable

disableauto

Riso-Min 0 k Ω … 10 000 k Ω 1 000 k ΩT-Max-Fan 0 °C … 100 °C 90 °CT-Start-Fan 0 °C … 100 °C 70 °CT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sT-Stop-Fan 0 °C … 100 °C 50 °Ctestcurrent Zac 0 mA … 25 000 mA 16 000 mAVac-Max* 230 V … 300 V Depending on country standardVac-Min* 70 V … 230 V Depending on country standardVconst-Setpoint 250 V … 600 V 600 VVpv-Start 250 V … 600 V 300 V

Name Value/Range Default Value

Page 24: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

24 SB_SMC_WB_Par-TEN104250 Technical Description

5.2.2 Sunny Mini Central 7000HV/7000HV-11Name Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAntiIsland-Ampl* 0 deg … 10 deg Depending on country standardAntiIsland-Freq* 0.1 mHz … 2 000 mHz 500 mHzdFac-Max 0.1 Hz/s … 4.0 Hz/s 4.0 Hz/s DGS-HystVolNom*(SMC 7000HV-11)

0 % … 60 % 5 %

DGS-PWMVolNom* (SMC 7000HV-11)

40 % … 100 % 70 %

dZac-Max (SMC 7000HV) 0.35 m Ω … 20 000 m Ω 650 m ΩE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 6 Hz Depending on country standardFac-delta+* 0.1 Hz … 5 Hz Depending on country standardFac-Limit delta 0 Hz … 5 Hz 2 HZFac-Start delta 0 Hz … 5 Hz 1 HZFan-Test 0 … 1 0GndFltRea (SMC 7000HV-11) GndFltWrn GndFltWrn

GndFltDsconh_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V 0 VOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

P-HzStop* 0 Hz … 5 Hz 0.05 HZP-HzStr* 0 Hz … 5 Hz 0.20 HZP-W* (SMC 7000HV-11) 0 W … 7 000 W 7 000 WP-WCtlHzMod*(SMC 7000HV-11)

Off OffOn

P-WGra* (SMC 7000HV-11) 10 %/Hz … 100 %/Hz 40 %/HzP-WMod* (SMC 7000HV-11) Off WCtlCom

WCnstWCtlCom

PF-PF* (SMC 7000HV-11) 0.8 … 1.0 1PF-PFExt* (SMC 7000HV-11) Overexcited Underexcited

UnderexcitedPmax 0 W … 7 000 W 7 000 W

Page 25: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 25

PowerBalancer Off OffPowerGuardPhaseGuardFaultGuard

Q-VArMod*(SMC 7000HV-11)

Off PFCnstPFCnst

PFCtlComRipple-Ctl-Frq 105 Hz … 1 605 Hz 1 605 HzRipple-Ctl-Lev 0.5 % … 8.0 % 8.0 %Ripple-Ctl-Rcvr enable disable

disableauto

Riso-Min 0 k Ω … 10 000 k Ω 1 000 k ΩSmax (SMC 7000HV-11) 0 VA ... 7 000 VA 7 000 VAT-Max-Fan 0 °C … 100 °C 90 °CT-Start-Fan 0 °C … 100 °C 70 °CT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sT-Stop-Fan 0 °C … 100 °C 50 °Ctestcurrent Zac 0 mA … 25 000 mA 16 000 mAVac-Max* 230 V … 300 V Depending on country standardVac-Min* 70 V … 230 V Depending on country standardVconst-Setpoint 335 V … 800 V 800 VVpv-Start 370 V … 800 V 400 VVRef* (SMC 7000HV-11) 215 V … 245 V 230 VVRefOfs* (SMC 7000HV-11) − 20 V … 20 V 0 VWGraReconEna*(SMC 7000HV-11)

0 … 1 0

Name Value/Range Default Value

Page 26: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

26 SB_SMC_WB_Par-TEN104250 Technical Description

5.2.3 Sunny Mini Central 6000TL/7000TL/8000TLName Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAID-Esk-Alpha* 0 deg/% … 40 deg/% Depending on country standardAntiIsland-Ampl* 0 deg … 10 deg Depending on country standardAntiIsland-Freq* 0.1 mHz … 2 000 mHz Depending on country standardDC-Offset_Max* 100 mA … 5 000 mA Depending on country standarddFac-Max* 0.1 Hz/s … 6.0 Hz/s Depending on country standardE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 6.0 Hz Depending on country standardFac-delta+* 0.1 Hz … 5.0 Hz Depending on country standardFac-Limit delta 0 Hz … 5 Hz 2 HZFac-Start delta 0 Hz … 5 Hz 1 HZFan-Test 0 … 1 0h_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Pmax* (SMC 6000TL) 0 W … 6 000 W 6 000 WPmax* (SMC 7000TL) 0 W … 7 000 W 7 000 WPmax* (SMC 8000TL) 0 W … 8 000 W 8 000 WPowerBalancer Off Off

PowerGuardPhaseGuardFaultGuard

Riso-Min 1 500 k Ω … 10 000 k Ω 1 500 k ΩT-Max-Fan 0 °C … 110 °C 90 °CT-Start-Fan 0 °C … 110 °C 70 °CT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sT-Stop-Fan 0 °C … 110 °C 50 °CUac-Max-Fast* 230 V … 300 V Depending on country standardUac-Min-Fast* 115 V … 220 V Depending on country standardVac-Max* 230 V … 300 V Depending on country standardVac-Min* 160 V … 300 V Depending on country standardVconst-Setpoint 250 V … 700 V 600 V

Page 27: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 27

Vpv-Start 335 V … 700 V 400 VName Value/Range Default Value

Page 28: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

28 SB_SMC_WB_Par-TEN104250 Technical Description

5.2.4 Sunny Mini Central 9000TL/10000TL/11000TLName Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAID-Esk-Alpha* 0 deg/% … 40 deg/% Depending on country standardAntiIsland-Ampl* 0 deg … 10 deg Depending on country standardAntiIsland-Freq* 0.1 mHz … 2 000 mHz 500 mHzAntiIsland-Lim* 0.1 Hz … 6.0 Hz Depending on country standardDC-Offset_Max* 100 mA … 5 000 mA 800 mAdFac-Max* 0.1 Hz/s … 6.0 Hz/s Depending on country standardE_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 6.0 Hz Depending on country standardFac-delta+* 0.1 Hz … 5.0 Hz Depending on country standardFac-Limit delta 0 Hz … 5 Hz 2 HZFac-Start delta 0 Hz … 5 Hz 1 HZFan-Test 0 … 1 0h_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

Pmax* (SMC 9000TL-10) 0 W … 9 090 W 9 000 WPmax* (SMC 10000TL-10) 0 W … 10 100 W 10 000 WPmax* (SMC 11000TL-10) 0 W … 11 110 W 11 000 WPowerBalancer Off Off

PowerGuardPhaseGuardFaultGuard

Riso-Min 280 k Ω … 10 000 k Ω 280 k ΩT-Max-Fan-In 0 °C … 80 °C 75 °CT-Max-Fan-Mod 0 °C … 120 °C 110 °CT-Start-Fan-In 0 °C … 80 °C 65 °CT-Start-Fan-Mod 0 °C … 120 °C 80 °CT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sT-Stop-Fan-In 0 °C … 80 °C 60 °CT-Stop-Fan-Mod 0 °C … 120 °C 70 °CUac-Max-Fast* 220 V … 300 V 300 V

Page 29: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 29

Uac-Min-Fast* 115 V … 220 V 120 VVac-Max* 230 V … 300 V Depending on country standardVac-Min* 160 V … 230 V Depending on country standardVconst-Setpoint 250 V … 700 V 500 VVpv-Start 335 V … 700 V 400 V

Name Value/Range Default Value

Page 30: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

30 SB_SMC_WB_Par-TEN104250 Technical Description

5.2.5 Sunny Mini Central 9000TL/10000TL/11000TL with Reactive Power ControlName Value/Range Default ValueACVtgRPro* 230 V … 300 V 253 VAID-Esk-Alpha* 0 deg/% … 40 deg/% Depending on country standardDC-Offset_Max* 100 mA … 5 000 mA Depending on country standardDGS-PWMVolNom* 40 % … 100 % 70 %DGS-HystVolNom* 0 % … 60 % 5 %E_total 0 kWh … 200 000 kWh 0 kWhFac-delta‒* 0.1 Hz … 6 Hz Depending on country standardFac-delta+* 0.1 Hz … 5 Hz Depending on country standardFac-Limit delta 0 Hz … 5 Hz 2 HZFac-Start delta 0 Hz … 5 Hz 1 HZFan-Test 0 … 1 0h_Total 0 h … 200 000 h 0 hLDVtgC* 0 V … 50 V Depending on country standardOperating Mode Mpp-Operation Mpp-Operation

V-ConstStop

P-HzStop* 0 Hz … 5 Hz 0.05 HZP-HzStr* 0 Hz … 5 Hz 0.20 HZP-W* 0 W … 11 110 W 11 000 WP-WCtlHzMod* Off Off

OnP-WGra* 10 %/Hz … 100 %/Hz 40 %/HzP-WMod* Off WCtlCom

WCnstWCtlCom

PF-PF* 0.8 … 1.0 1PF-PFExt* Overexcited Underexcited

UnderexcitedPmax (SMC 9000TLRP-10) 0 W … 9 090 W 9 000 WPmax (SMC 10000TLRP-10) 0 W … 10 100 W 10 000 WPmax (SMC 11000TLRP-10) 0 W … 11 110 W 11 000 W

Page 31: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 31

PowerBalancer Off OffPowerGuardPhaseGuardFaultGuard

Q-VArMod* Off PFCnstPFCnst

PFCtlComRiso-Min 900 k Ω … 10 000 k Ω 900 k ΩSmax (SMC 10000TLRP-10) 0 VA ... 10 100 VA 10 000 VASmax (SMC 11000TLRP-10) 0 VA ... 11 100 VA 11 000 VASmax (SMC 9000TLRP-10) 0 VA ... 9 090 VA 9 000 VAT-Start* 5 s … 1 600 s Depending on country standardT-Stop 1 s … 3 600 s 2 sUac-Max-Fast* 230 V … 300 V Depending on country standardUac-Min-Fast* 70 V … 220 V Depending on country standardVac-Max* 230 V … 300 V Depending on country standardVac-Min* 70 V … 230 V Depending on country standardVconst-Setpoint 250 V … 700 V 500 VVpv-Start 335 V … 700 V 400 VVRef* 215 V … 245 V 230 VVRefOfs* − 20 V … 20 V 0 VWGraReconEna* 0 … 1 0

Name Value/Range Default Value

Page 32: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

32 SB_SMC_WB_Par-TEN104250 Technical Description

5.3 Windy Boy

5.3.1 Windy Boy 1100LVName Value/Range Default ValueKI-Wind-Reg 0 … 0.25 0.005KP-Wind-Reg 0 … 0.25 0.117Operating Mode Mpp-Operation Turbine

V-ConstStop

TurbineP-Wind-Ramp 10 W/s … 600 W/s 400 W/sPmax 0 W … 1 150 W 1 100 WT-Stop 1 s … 3 600 s 2 sUdcWindStart 1 V … 60 V 25 VUdcWindStop 1 V … 60 V 24.9 VVpv-Start 20 V … 60 V 25 VWind_a0 − 1 000 000 000 …

1 000 000 000− 1 897.57

Wind_a1 − 1 000 000 000 … 1 000 000 000

182.87

Wind_a2 − 1 000 000 000 … 1 000 000 000

− 5 933.95

Wind_a3 − 1 000 000 000 … 1 000 000 000

66 410

Page 33: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 33

5.3.2 Windy Boy 1200/1700Name Value/Range Default ValueKI-Wind-Reg 0 V … 0.25 V 0.005KP-Wind-Reg 0 V … 0.25 V 0.117Operating Mode Mpp-Operation Turbine

V-ConstStop

TurbineP-Wind-Ramp 10 W/s … 2 000 W/s 330 W/sPmax (WB 1200) 0 W … 1 250 W 1 200 WPmax (WB 1700) 0 W … 1 750 W 1 700 WT-Stop 1 s … 3 600 s 2 sUdcWindStart 1 V … 500 V 150 VVpv-Start (WB 1200) 110 V … 400 V 120 VVpv-Start (WB 1700) 150 V … 400 V 180 VWind_a0 (WB 1200) − 1 000 000 000 …

1 000 000 000− 83

Wind_a0 (WB 1700) − 1 000 000 000 … 1 000 000 000

− 341

Wind_a1 (WB 1200) − 1 000 000 000 … 1 000 000 000

2.92

Wind_a1 (WB 1700) − 1 000 000 000 … 1 000 000 000

8.76

Wind_a2 (WB 1200) − 1 000 000 000 … 1 000 000 000

− 30.62

Wind_a2 (WB 1700) − 1 000 000 000 … 1 000 000 000

− 73

Wind_a3 (WB 1200) − 1 000 000 000 … 1 000 000 000

99.22

Wind_a3 (WB 1700) − 1 000 000 000 … 1 000 000 000

197.84

Page 34: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

34 SB_SMC_WB_Par-TEN104250 Technical Description

5.3.3 Windy Boy 2500/3000Name Value/Range Default ValueKI-Wind-Reg 0 … 0.25 0.005KP-Wind-Reg 0 … 0.25 0.02Operating Mode Mpp-Operation Turbine

V-ConstStop

TurbineP-Wind-Ramp 10 W/s … 2 000 W/s 500 W/sPmax (WB 2500) 0 W … 2 550 W 2 500 WPmax (WB 3000) 0 W … 3 050 W 3 000 WT-Stop 1 s … 3 600 s 2 sUdcWindStart (WB 2500) 150 V … 600 V 250 VUdcWindStart (WB 3000) 150 V … 600 V 270 VVpv-Start (WB 2500) 250 V … 600 V 300 VVpv-Start (WB 3000) 290 V … 600 V 330 VWind_a0 (WB 2500) − 1 000 000 000 …

1 000 000 000− 1538

Wind_a0 (WB 3000) − 1 000 000 000 … 1 000 000 000

− 3923

Wind_a1 (WB 2500) − 1 000 000 000 … 1 000 000 000

17.07

Wind_a1 (WB 3000) − 1 000 000 000 … 1 000 000 000

38.36

Wind_a2 (WB 2500) − 1 000 000 000 … 1 000 000 000

− 64.43

Wind_a2 (WB 3000) − 1 000 000 000 … 1 000 000 000

− 128

Wind_a3 (WB 2500) − 1 000 000 000 … 1 000 000 000

85.06

Wind_a3 (WB 3000) − 1 000 000 000 … 1 000 000 000

147.8

Page 35: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Value Ranges and Factory Settings

Technical Description SB_SMC_WB_Par-TEN104250 35

5.3.4 Windy Boy 3300/3800Name Value/Range Default ValueOperating Mode Mpp-Operation Turbine

V-ConstStop

TurbineGndFltRea GndFltWrn GndFltWrn

GndFltDsconKI-Wind-Reg 0 … 0.25 0.005KP-Wind-Reg 0 … 0.25 0.117P-Wind-Ramp (WB 3300) 10 W/s … 2 000 W/s 600 W/sP-Wind-Ramp (WB 3800) 10 W/s … 2 000 W/s 650 W/sPmax (WB 3300) 0 W … 3 600 W 3 600 WPmax (WB 3800) 0 W … 3 800 W 3 800 WT-Stop 1 s … 3 600 s 2 sVpv-Start 200 V … 500 V 250 VUdcWindStart (WB 3300) 150 V … 500 V 200 VUdcWindStart (WB 3800) 150 V … 500 V 180 VWind_a0 (WB 3300) − 1 000 000 000 …

1 000 000 000− 290

Wind_a0 (WB 3800) − 1 000 000 000 … 1 000 000 000

− 610.56

Wind_a1 (WB 3300) − 1 000 000 000 … 1 000 000 000

7.086

Wind_a1 (WB 3800) − 1 000 000 000 … 1 000 000 000

0.83

Wind_a2 (WB 3300) − 1 000 000 000 … 1 000 000 000

− 52

Wind_a2 (WB 3800) − 1 000 000 000 … 1 000 000 000

9.51

Wind_a3 (WB 3300) − 1 000 000 000 … 1 000 000 000

120

Wind_a3 (WB 3800) − 1 000 000 000 … 1 000 000 000

26.37

Page 36: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

Value Ranges and Factory Settings SMA Solar Technology AG

36 SB_SMC_WB_Par-TEN104250 Technical Description

5.3.5 Windy Boy 5000A/6000AName Value/Range Default ValueGndFltRea GndFltWrn GndFltWrn

GndFltDsconKI-Wind-Reg 0 … 0.25 0.005KP-Wind-Reg 0 … 0.25 0.2Operating Mode Mpp-Operation Turbine

V-ConstStop

TurbineP-Wind-Ramp (WB 5000A) 10 W/s … 2 000 W/s 830 W/sP-Wind-Ramp (WB 6000A) 10 W/s … 2 000 W/s 1 000 W/sPmax (WB 5000A) 0 W … 5 550 W 5 500 WPmax (WB 6000A) 0 W … 6 050 W 6 000 WT-Stop 1 s … 3 600 s 2 sUdcWindStart (WB 5000A) 1 V … 500 V 150 VUdcWindStart (WB 6000A) 1 V … 800 V 150 VVpv-Start 250 V … 600 V 300 VWind_a0 (WB 5000A) − 1 000 000 000 …

1 000 000 000− 1993

Wind_a0 (WB 6000A) − 1 000 000 000 … 1 000 000 000

− 8197

Wind_a1 (WB 5000A) − 1 000 000 000 … 1 000 000 000

22.687

Wind_a1 (WB 6000A) − 1 000 000 000 … 1 000 000 000

77.08

Wind_a2 (WB 5000A) − 1 000 000 000 … 1 000 000 000

− 92.3

Wind_a2 (WB 6000A) − 1 000 000 000 … 1 000 000 000

− 247.8

Wind_a3 (WB 5000A) − 1 000 000 000 … 1 000 000 000

135.3

Wind_a3 (WB 6000A) − 1 000 000 000 … 1 000 000 000

281.2

Page 37: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Contact

Technical Description SB_SMC_WB_Par-TEN104250 37

6 ContactIf you have technical problems concerning our products, contact the SMA Serviceline. We need the following information in order to provide you with the necessary assistance:

• Inverter type• Serial number of inverter• Type and number of connected PV modules or small wind turbine systems• Blink code or display message of the inverter• Optional equipment, e.g. communication devices

SMA Solar Technology AGSonnenallee 134266 Niestetal, Germanywww.SMA.de

SMA Serviceline Inverters: +49 561 9522 1499Communication: +49 561 9522 2499Fax: +49 561 9522 4699E-Mail: [email protected]

Page 38: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250
Page 39: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250

SMA Solar Technology AG Legal Restrictions

Technical Description SB_SMC_WB_Par-TEN104250 39

The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either partially or in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the document for the purposes of evaluating the product or its correct implementation is allowed and does not require permission.

Exclusion of liabilityThe general terms and conditions of delivery of SMA Solar Technology AG shall apply.The content of these documents is continually checked and amended, where necessary. However, discrepancies cannot be excluded. No guarantee is made for the completeness of these documents. The latest version is available online at www.SMA.de or from the usual sales channels.Guarantee or liability claims for damages of any kind are excluded if they are caused by one or more of the following: • Damages during transportation• Improper or inappropriate use of the product• Operating the product in an unintended environment• Operating the product whilst ignoring relevant, statutory safety regulations in the deployment location• Ignoring safety warnings and instructions contained in all documents relevant to the product• Operating the product under incorrect safety or protection conditions• Altering the product or supplied software without authority• The product malfunctions due to operating attached or neighboring devices beyond statutory limit values• In case of unforeseen calamity or force majeureThe use of supplied software produced by SMA Solar Technology AG is subject to the following conditions:• SMA Solar Technology AG rejects any liability for direct or indirect damages arising from the use of software developed by

SMA Solar Technology AG. This also applies to the provision or non-provision of support activities.• Supplied software not developed by SMA Solar Technology AG is subject to the respective licensing and liability agreements

of the manufacturer.

SMA Factory WarrantyThe current guarantee conditions come enclosed with your device. These are also available online at www.SMA.de and can be downloaded or are available on paper from the usual sales channels if required.

TrademarksAll trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand is not a registered trademark.The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by SMA Solar Technology AG is under license.SMA Solar Technology AGSonnenallee 134266 NiestetalGermanyTel. +49 561 9522-0Fax +49 561 9522-100www.SMA.deE-Mail: [email protected]© 2004 to 2010 SMA Solar Technology AG. All rights reserved

Page 40: Operating Parameters SUNNY BOY/SUNNY MINI …files.sma.de/dl/1348/SB_SMC_WB_Par-TEN104250.pdf · SMA Solar Technology AG Notes on this Manual Technical Description SB_SMC_WB_Par-TEN104250