On-load tap-changer VACUTAP® VRC and VRETechnical Data TD 246/03
www.reinhausen.com
3TD 246/03246/03/01/0
Table of Contents
1 General / Technical data .......................................................................................................................................................... 4
1.1 On-load tap-changer designations ........................................................................................................................... 4
1.2 Summary of the technical data ................................................................................................................................... 5
1.2.1 Step capacity diagram .................................................................................................................................... 6
1.2.2 Step capacity diagram EAF/LF operation .................................................................................................. 6
1.3 Rated insulation level .................................................................................................................................................... 7
1.4 Rated withstand voltages ............................................................................................................................................. 8
1.4.1 Rated withstand voltages of the internal insulation ............................................................................. 8
1.4.2 VR-rated withstand voltages - multiple coarse change-over selector ............................................. 10
2 Special designs ............................................................................................................................................................................. 11
2.1 Parallel jumpers for parallel connections ............................................................................................................... 11
2.2 On-load tap-changer combination VACUTAP® VRC I/VRC II for delta connection ..................................... 11
2.3 On-load tap-changer VACUTAP® VRC III 700 Y und VRC I 701/1001/1301 withmultiple coarse change-over selector (up to max. of 5 coarse taps) .............................................................. 11
3 Appendix ........................................................................................................................................................................................ 12
3.1 Dimension drawings / connection diagrams .......................................................................................................... 12
3.2 Installation drawings ..................................................................................................................................................... 13
Table of Contents
NOTE
These technical data are intended for the calculator and designer of the transformer. These type-specific data areonly valid in connection with the information contained in the general section (TD 61) since this section containsimportant information on such subjects as potential connection of the tap winding, leakage inductance, currentdivision, and so on.
Changes may have been made to a product after going to press with this documentation.
We expressly reserve the right to make changes to a product’s technical data and design as well as changesto the scope of delivery.
In all cases, the information submitted and agreements concluded during processing of the quotation and orderin question shall be binding.
Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformermanufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirementsof the transformer are met.
4 TD 246/03 246/03/01/0
Exsample VRC III 700 Y - 72,5 / C - 10 19 1W R
- / -
VRCVRE
IIIIII
400VRC 550VRC,VRE 700VRC,VRE 1000VRC,VRE 1300
1230
Applications Y72.5123170245300BCDDE101214161810121416181923273135
013
WG
tie-in resistor Rpotential switch S
P
1923
35
Change-over selector
reversing change-over selectorcoarse change-over selector
Number of max. operating positions without change-over selector
Mid-positions
2731
Number of max. operating positions with change-over selector
1012141618
Contacts 1012141618
Tap selector size VRC;VRE
VRC;VRE
VRC;VREVRC;VRE
For neutral connection onlyUm (in kV) VRC,VRE
VRC,VREVRC,VREVRC,VREVRC,VRE
1 sector2 sectors
3 sectors (Y)3 sectors
Type VACUTAP ® VRCVACUTAP ® VRE
Basic connectiondiagram
Tie-in measures
Number of phases 1 phase2 phases3 phases
Ium (in A) VRC
Number of configured sectors
potential switch with tie-in resistor
0 mid-positions (without change-overselector)1 mid-position3 mid-positions
1 General / Technical Data
1 General / Technical Data
1.1 On-load tap-changer designationsExample
5TD 246/03246/03/01/0
1 General / Technical Data
1.2 Summary of the technical data
On-load tap-changer
No. of phases and application 31) 31) 31) 2 2 2 1 1 1 1 1 31) 1 1 1
Max. rated through-current 400 550 700 400 550 700 400 550 700 1000 1300 700 700 1000 1300
Ium(in A)
Rated short-time withstand 6 8 10 6 8 10 6 8 10 12 15 10 10 12 15current (in kA)
Rated short-circuit duration 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3(in s)
Rated peak withstand current 15 20 25 15 20 25 15 20 25 30 37.5 25 25 30 37.5(in kA)
Max. rated step voltage 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300 4000 4000 4000 4000Uim (in V)2)
Step capacity (PStN) 1320 1500 1500 1320 1500 1500 1320 1500 1500 1500 1500 2800 2800 3000 3000(in kVA)
Rated frequency (in Hz) 50 ... 60
Operating positions Without change-over selector: max. of 183) With change-over selector: max. of 353)
VRC
III 4
00 Y
VRC
III 5
50 Y
VRC
III 7
00 Y
VRC
II 40
2
VRC
II 55
2
VRC
II 70
2
VRC
I 401
VRC
I 551
VRC
I 701
VRC
I 100
1
VRC
I 130
1
VRE
III 7
00 Y
VRE
I 701
VRE
I 100
1
VRE
I 130
1
Note: 1) Neutral point
2) The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if thestep capacity is limited to its rated value.
3) For more operating positions, see section 2 Special designs.
Oil compartment: Pressure-tight up to 0.3 bar permanent differential pressure (test pressure 0.6 bar), head and cover ofthe diverter switch oil compartment are vacuum-proof.
Temperature The on-load tap-changer VACUTAP® VR can be operated in the rated load range at temperatures of therange: surrounding oil between -25° and + 105 °C and with overload up to 115 °C according to IEC 60214-1.
Dimensions: Weight, displacement volume, oil content of the diverter switch oil compartment are shown in therelevant dimension drawings.
6 TD 246/03 246/03/01/0
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 200 400 600 800 1000 1200 1400
VR
E III 7
00Y
VR
E I 7
01
VR
E I 1
001
3000 kVA
1500 kVA
VR
C III 5
50Y
VR
C II 552''''
VR
C I 5
51'''
VR
C I 1
001
VR
C I 1
301
VR
C III 4
00Y
VR
C II 402''''
VR
C I 4
01'''
VR
C III 7
00Y
VR
C II 702''''
VR
C I 7
01'''
VR
E I 1
301
1 General / Technical Data
Fig. 1Step capacities (rated step voltage Ui, rated through-current Iu).
Note: 1) When used for electrical arc furnace (EAF) and ladle furnace transformers (LF),refer to step capacity diagram chapter 1.2.2.
Rate
d st
ep v
olta
ge U
i (V)
1.2.1 Step capacity diagram1)
1.2.2 Step capacity diagram EAF/LF operation2)
Rate
d st
ep v
olta
ge U
i (V)
Rated through-current Iu (A)
Rated through-current Iu (A)
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 200 400 600 800 1000 1200 1400
1500 kVA
1750 kVA
2400 kVA
1360 kVA
VR
C III 4
00Y
VR
C II 402''''
VR
C I 4
01'''
VR
C III 5
50Y
VR
C II 552''''
VR
C I 5
51'''
VR
C III 7
00Y
VR
C II 702''''
VR
C I 7
01'''
VR
E I 7
01
VRE III 700Y
VRE I 1001
VR
C I 1
001
VR
C I 1
301
VRE I 1301
Fig. 2Step capacities electrical arc furnace and ladle furnace operation (EAF/LF), rated step voltage Ui, rated through-current Iu.
Note: 2) Please contact MR.
7TD 246/03246/03/01/0
1 General / Technical Data
1.3 Rated insulation level
Rated insulation level On-load tap-changer
72.5 to 300 kV VRC I 401/551/701; VRC I 1001; VRC I 1301; VRC II 402/552/702;
VRE I 701; VRE I 1001; VRE I 1301
72.5 to 245 kV VRC III 400/550/700 Y; VRE III 700 Y
Highest voltage for 72.5 123 170 245 300equipment Um (in kV)1)
Rated lightning impulse with- 350 550 750 1050 1050stand voltage (in kV, 1.2/50 μs)
Rated switching impulse 850 850withstand voltage (in kV)
Rated short-duration power 140 230 325 460 460frequency withstand voltage(in kV, 50 Hz, 1 min.)
Note: 1) According to IEC 60214-1, chapter 3.57: highest r.m.s. phase-to-phase voltage in a three-phase system for which aon-load tap-changer is designed with respect to its insulation.
8 TD 246/03 246/03/01/0
1 General / Technical Data
1.4 Rated withstand voltages
1.4.1 Rated withstand voltages of the internal insulation
Fig. 2 shows diagrams of the voltage stress present on the tap winding of the three primary basic connections of three-poleon-load tap-changers and single-pole on-load tap-changers.When selecting the on-load tap-changer, a check must be made to determine whether the highest stress on the tap selectordoes not exceed the related rated withstand voltages.
a0 = Between selected and preselected tapping on the diverter switch and tap selector
a1 = Between tap selector contacts of the winding of one tap position (connected or not connected)
a = Between beginning and end of a tapped winding and also with coarse winding, between beginning and end of a coarse winding.Note for coarse tapping arrangement in (-) - position of the change-over selector:When stressed with impulse voltage, the permissible withstand voltage „a“ must be adhered to between the end of a coarse tap windingconnected with the K tap selector contact and the tap selector contact at the end of the tapped winding of the same phase
b = Between the tap selector contacts of different phases and between change-over selector contacts of different phases, which are connectedwith the beginning/end of a tapped winding or with a tap selector contact
f = Between diverter switch terminal and ground
Additional for coarse tapping arrangement in (+) - position of the change-over selector:c1 = From one (-) - change-over selector contact to terminal of the same phasec2 = Between (-) - change-over selector contacts of different phases
CAUTIONAdhere to maximum ratedlightning impulse withstandvoltage stress on a0in mid-position.
8997560E
Fig. 2 Rated withstand voltages
With coarse change-over selector in (+) – position With coarse change-over selector in (–) – position
With reversing change-over selectorWithout change-over selector
9TD 246/03246/03/01/0
1 General / Technical Data
On-load tap-changer VRC III 400 Y ... VRE I 1301, rated withstand voltages of the interal on-load tap-changer insulation
Note: 1)Insulation distance omitted for single-pole on-load tap-changers
The admissible maximum operating voltage on the individual tap selector distances complies to half the value of the abovementioned rated short-duration power frequency withstand voltages.
Without change-over selector With reversing change-over selector With coarse change-over selector
Connection Tap selector size Connection Tap selector size Connection Tap selector size
10050 B/C/D/DE 10071W B/C/D/DE 10071G B/C/D/DE10060 B/C/D/DE 10081W B/C/D/DE 10081G B/C/D/DE10070 B/C/D/DE 10091W B/C/D/DE 10091G B/C/D/DE10080 B/C/D/DE 12101W B/C/D/DE 12101G B/C/D/DE10090 B/C/D/DE 12111W B/C 12111G B/C10100 B/C/D/DE 14111W D/DE 14111G D/DE12110 B/C/D/DE 14121W B/C 14121G B/C12120 B/C/D/DE 14131W B/C 14131G B/C14130 B/C/D/DE 16121W D/DE 16121G D/DE14140 B/C/D/DE 16131W D/DE 16131G D/DE16150 B/C/D/DE 16141W B/C/D/DE 16141G B/C/D/DE16160 B/C/D/DE 16151W B/C 16151G B/C18170 B/C/D/DE 18151W D/DE 18151G D/DE18180 B/C/D/DE 18161W B/C 18161G B/C22190 B/C/D/DE 18171W B/C 18171G B/C22200 B/C/D/DE 10191W B/C/D/DE 10191G B/C/D/DE22210 B/C 12231W B/C/D/DE 12231G B/C/D/DE22220 B/C 14271W B/C/D/DE 14271G B/C/D/DE
16311W B/C/D/DE 16311G B/C/D/DE18351W B/C/D/DE 18351G B/C/D/DE
Available connections (also available as 3 W, 3 G)
Insulation Tap selector size B Tap selector size C Tap selector size D Tap selector size DEdistances
kV kV kV kV kV kV kV kV1.2/50 μs 50 Hz 1.2/50 μs 50 Hz 1.2/50 μs 50 Hz 1.2/50 μs 50 Hz
1 min. 1 min. 1 min. 1 min.
a0
a1 150 30 150 30 150 30 150 30
a 265 50 350 82 490 105 550 120
b1) 265 50 350 82 490 146 550 160
c1 485 143 545 178 590 208 660 230
c21) 495 150 550 182 590 225 660 250
Power frequency withstand voltage test (50 Hz/60 s): 20 kV 50 Hz 1 min; Response voltage at 1mA-leakage current: 44 kV 1.2/50 μs;3 kA-residual voltage (= lightning impulse protection level): 70 kV 1.2/50 μs with ZnO
10 TD 246/03 246/03/01/0
1.4.2 VR-rated withstand voltages - multiple coarse change-over selector
Insulation Tap selector size B Tap selector size Cdistances
kV kV kV kV1.2/50 μs 50 Hz 1.2/50 μs 50 Hz
1 min. 1 min.
a0
a1 150 30 150 30
a 265 50 350 82
b1) 265 50 350 82
c1 455 127 525 165
c21) 455 127 525 165
d1 265 50 350 82
d2 350 82 450 105
d3 350 82 450 105
On-load tap-changer VACUTAP® VRC with multiple coarse change-over selector,rated withstand voltages of the internal on-load tap-changer insulation
7278970E
Note: 1) Insulation distance omitted for single-pole on-load tap-changers
The admissible maximum operating voltage on the individual tap selector distances complies to half the value of the abovementioned rated short-duration power frequency withstand voltages.
1 General / Technical Data
a0 = Between selected and preselected tapping on the diverterswitch and tap selector
a1 = Between tap selector contacts of the winding of a tapposition (connected or not connected)
a = Between beginning and end of a tapped winding and alsobetween the connected K contact and any points of thetapped winding of the same phase
b = Between the tap selector contacts of different phases andbetween the connected K contact of one phase and anypoints of the tapped winding of another phase
c1 = Between any coarse tappings of one phase to the diverterswitch terminal of the same phase
c2 = Between identically-named, unconnected coarse tappings ofdifferent phases
d1 = Between connected and adjacent coarse tap contacts in onephase.
d2 = Between unconnected, adjacent coarse tap contacts in onephase
d3 = Between beginning and end of all coarse taps of one phasef = Between diverter switch terminal and ground
Power frequency withstand voltage test (50 Hz/60 s): 20 kV 50 Hz 1 min;Response voltage at 1 mA-leakage current: 44 kV 1.2/50 μs;
3 kA-residual voltage (= lightning impulse protection level): 70 kV 1.2/50 μs with ZnO
11TD 246/03246/03/01/0
2 Special designs
2 Special designs
KHW 352-3
Fig. 3On-load tap-changer combination VRC I 401 / VRC II 402(a – VRC I 401, b – VRC II 402) for delta connection.
2.2 On-load tap-changer combination VACUTAP® VRC I/VRC IIfor delta connection
The VRC II 402 on-load tap-changer can also be used with thesingle-phase on-load tap-changer VRC I 401 as a two-columnon-load tap-changer combination VRC I 401/VRC II 402 foradjusting the voltage of transformer windings in a delta connection(similar to VRC I 551 / VRC II 552 and VRC I 701 / VRC II 702).The tap windings should correspond to those in fig. 3.
2.3 On-load tap-changer VACUTAP® VRC III 700 Y and VRC I 701/1001/1301 with multiple coarse change-overselector (up to max. of 5 coarse taps)
Extremely fine voltage adjustment requires a great number of operating positions which sometimes may only be implementedwith a multiple coarse tapping arrangement.
For instance, 107 operating positions can be obtained by using a coarse 5-tap winding and a tapped winding with 18 tappings.The multiple coarse change-over selector is attached to both sides of the tap selector.
The on-load tap-changers are available (on request) for Um = 72.5 up to max. 300 kV and for 2 to 5 coarse taps (tap selector sizesB and C) or 2 and 3 coarse taps (tap selector size D).
2.1 Parallel jumpers for parallel connections
Current division on the connection terminals of 2 tap selector planes only for on-load tap-changers VACUTAP® VR I 1001and of 3 tap selector planes only for on-load tap-changers VACUTAP® VR I 1301,see appenidix, drawing 727025.
Parallel jumpers on the tap selector terminals are then mandatory when the tap winding was wound in two or more branchesand each of these branch taps is connected to the terminals of the tap selector.
This measure reliably prevents the following.
a) Introduction of circulating currents into the current paths of tap selector and diverter switchb) Arcing on movable tap selector contact bridges due to commutationc) Overvoltage between adjacent tap selector terminals connected in parallel
12 TD 246/03 246/03/01/0
3.1 Dimension drawings / connection diagrams
On-load tap-changer VACUTAP® VRC, VRE, survey of types ........................................................................... 727017_1-4 Page 14-17
On-load tap-changer VACUTAP® VR, basic connection diagrams, designation oftap selector terminal contacts according to MR standard .............................................................................. 719037_1/2 Page 18/19
On-load tap-changer VACUTAP® VRC III 400/550/700 Y, connection diagram 10191W ..................... 1599595 Page 20
On-load tap-changer VACUTAP® VRE III 700 Y, connection diagram 10193W ........................................ 1599601 Page 21
On-load tap-changer VACUTAP® VRC III 400/550/700 Y - 0/W/G, dimension drawing ......................... 899981 Page 22
On-load tap-changer VACUTAP® VRE III 700 Y - 0/W/G, dimension drawing ........................................... 899982 Page 23
On-load tap-changer VACUTAP® VRC II 402/552/702 - 0/W/G, dimension drawing ............................. 899989 Page 24
On-load tap-changer VACUTAP® VRC I 401/551/701 - 0/W/G, dimension drawing ............................... 899990 Page 25
On-load tap-changer VACUTAP® VRE I 701 - 0/W/G, dimension drawing ................................................. 899991 Page 26
On-load tap-changer VACUTAP® VRC I 1001 - 0/W/G, dimension drawing .............................................. 718306 Page 27
On-load tap-changer VACUTAP® VRE I 1001 - 0/W/G, dimension drawing ............................................... 718307 Page 28
On-load tap-changer VACUTAP® VRC I 1301 – 0/W/G, dimension drawing .............................................. 718308 Page 29
On-load tap-changer VACUTAP® VRE I 1301 – 0/W/G, dimension drawing .............................................. 727040 Page 30
On-load tap-changer VACUTAP® VRC/VRE connecting leads 3W, 1G, 3G,dimension drawing ..................................................................................................................................................... 727875 Page 31
On-load tap-changer VACUTAP® VRC III 700 Y, with multiple coarse change-over selector,dimension drawing ..................................................................................................................................................... 718314 Page 32
On-load tap-changer VACUTAP® VRC I 701, with multiple coarse change-over selector,dimension drawing ..................................................................................................................................................... 718316 Page 33
On-load tap-changer VACUTAP® VRC I 1001, with multiple coarse change-over selector,dimension drawing ..................................................................................................................................................... 718318 Page 34
On-load tap-changer VACUTAP® VRC I 1301, with multiple coarse change-over selector,dimension drawing ..................................................................................................................................................... 718321 Page 35
3 Appendix
3 Appendix
13TD 246/03246/03/01/0
3 Appendix
3.2 Installation drawings
On-load tap-changer VACUTAP® VRC und VRE, installation drawing .......................................................... 899992_1/2 Page 36/37
On-load tap-changer VACUTAP® VR, on-load tap-changer head ................................................................. 899944 Page 38
On-load tap-changer VACUTAP® VR,on-load tap-changer head with flange for pressure-relief device ................................................................ 899946 Page 39
On-load tap-changer VACUTAP® VR, special design for bell-type tank ...................................................... 720781 Page 40
On-load tap-changer VACUTAP® VRC und VRE, contact arrangement on the tap selector,no. of contacts per plane 10 ... 22 ......................................................................................................................... 899993 Seite 41
On-load tap-changer VACUTAP® VRC I 1001/1301, VRE I 1001/1301,jumpers for the parallel connection of tap selector terminals ....................................................................... 727025 Page 42
On-load tap-changer VACUTAP® VR, installation position of tap selector terminals ............................... 727042 Page 43
On-load tap-changer VACUTAP® VRC III 400/550/700 Y, VRE III 700 Y,arrangement of tap selector terminals .................................................................................................................. 899994 Seite 44
On-load tap-changer VACUTAP® VRC I 401/551/701, VRE I 701,arrangement of tap selector terminals .................................................................................................................. 899995 Page 45
On-load tap-changer VACUTAP® VRC I 1001, VRE I 1001,arrangement of tap selector terminals .................................................................................................................. 899996 Page 46
On-load tap-changer VACUTAP® VRC I 1301, VRE I 1301,arrangement of tap selector terminals .................................................................................................................. 727043 Seite 47
On-load tap-changer VACUTAP® VR, versions of the on-load tap-changer head,swivelling range and drive direction of the gear unit ....................................................................................... 721216 Page 48
On-load tap-changer VACUTAP® VR, versions of the on-load tap-changer head,swivelling range and drive direction of the gear unit ....................................................................................... 728474 Seite 49
On-load tap-changer VACUTAP® VR, horizontal drive shaft ........................................................................... 899958 Seite 50
On-load tap-changer VACUTAP® VRC and VRE, design: VRC III, VRE III,tie-in resistors with or without potential switch ................................................................................................ 899972 Seite 51
On-load tap-changer VACUTAP® VRC, design: VRC II,tie-in resistors with or without potential switch ................................................................................................ 899986 Page 52
On-load tap-changer VACUTAP® VRC and VRE, design: VRC I, VRE I,tie-in resistors with or without potential switch ................................................................................................ 718447 Page 53
On-load tap-changer VACUTAP® VRC and VRE,tie-in resistor cylinder with potential switch without tie-in resistors ........................................................... 899973 Page 54
14 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC, VRESurvey of types
7270172E_1
15TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC, VRESurvey of types
7270172E_2
16 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC, VRESurvey of types
7270172E_3
17TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC, VRESurvey of types
7270172E_4
18 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRBasic connection diagramsDesignation of tap selector terminal contacts according to MR standard
7190370E_1
19TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRBasic connection diagramsDesignation of tap selector terminal contacts according to MR standard
7190370E_2
20 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC III 400/550/700 Y-10191WConnection diagram
1599595
21TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRE III 700 Y-10193WConnection diagram
1599601
22 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC III 400/550/700 Y – 0/W/GDimension drawing
8999814E
23TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRE III 700 Y – 0/W/GDimension drawing
8999826E
24 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC II 402/552/702 – 0/W/GDimension drawing
8999894E
25TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 401/551/701 – 0/W/GDimension drawing
8999904E
26 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRE I 701 – 0/W/GDimension drawing
8999914E
27TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 1001 – 0/W/GDimension drawing
7183064E
28 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRE I 1001 – 0/W/GDimension drawing
7183075E
29TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 1301 – 0/W/GDimension drawing
7183084E
30 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRE I 1301 – 0/W/GDimension drawing
7270405E
31TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC/VREConnecting leads 3W, 1G, 3GDimension drawing
7278750E
32 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC III 700 Ywith multiple coarse change-over selectorDimension drawing
7183144E
33TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 701with multiple coarse change-over selectorDimension drawing
7183164E
34 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC I 1001with multiple coarse change-over selectorDimension drawing
7183184E
35TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 1301with multiple coarse change-over selectorDimension drawing
7183214E
36 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC and VREInstallation drawing
8999923E_1
37TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC and VREInstallation drawing
8999923E_2
38 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VROn-load tap-changer head
8999444E
39TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VROn-load tap-changer head with flange for pressure-relief device
8999462E
40 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRSpecial design for bell-type tank
7207810E
41TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC and VREContact arrangement on the tap selectorNo. of contacts per plane 10 ... 22
8999932E
42 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC I 1001/1301VRE I 1001/1301
Jumpers for the parallel connection of tap selector terminals
7270251E
43TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRInstallation position of tap selector terminals
7270420E
44 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC III 400/550/700 YVRE III 700 Y
Arrangement of tap selector terminals
8999940E
45TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 401/551/701VRE I 701
Arrangement of tap selector terminals
8999950E
46 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRC I 1001VRE I 1001
Arrangement of tap selector terminals
8999960E
47TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC I 1301VRE I 1301
Arrangement of tap selector terminals
7270430E
48 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRVersions of the on-load tap-changer headSwivelling range and drive direction of the gear unit
7212164E
49TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRVersions of the on-load tap-changer headSwivelling range and drive direction of the gear unit
7284740E
50 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRHorizontal drive shaft
8999583E
51TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC and VREDesign: VRC III, VRE IIITie-in resistors with or without potential switch
8999722E
52 TD 246/03 246/03/01/0
On-load tap-changer VACUTAP® VRCDesign: VRC IITie-in resistors with or without potential switch
8999862E
53TD 246/03246/03/01/0
On-load tap-changer VACUTAP® VRC and VREDesign: VRC I, VRE ITie-in resistors with or without potential switch
7184473E
54 TD 246/03 246/03/01/0