  • For the owner and the heating engineer

    Operating and Installation Manual

    VRC 400

    Programmable weather compensator with separat HW time control

    GB

  • 2Contents

    Operating manual and installation manual for VRC 400 weather compensator

    Contents

    Notes on the documentation . . . . . 4Symbols used........................................... 4Storage of the documents.................... 4

    Safety . . . . . . . . . . . . . . . . . . . . . . . . 5

    Operating manual. . . . . . . . . . . . . . . 6

    1 Control overview. . . . . . . . . . . . 6

    2 Display overview. . . . . . . . . . . . 7

    3 Description of the control . . . . 8

    4 Operation. . . . . . . . . . . . . . . . . . 94.1 Setting the operating modes ...... 94.2 Setting the current day and

    time ................................................... 124.3 Setting timer programmes .......... 134.4 Setting the room temperature ... 164.5 Setting the hot water

    temperature .................................... 194.6 Activating special functions........ 204.7 Info level........................................... 22

    5 Vaillant warranty . . . . . . . . . . . 23

    6 Recycling and disposal. . . . . . . 24

  • 3Operating manual and installation manual for VRC 400 weather compensator

    Contents

    Installation manual . . . . . . . . . . . . . 25

    7 Information on installation and operation . . . . . . . . . . . . . . 25

    7.1 CE label............................................. 257.2 Intended use.................................... 25

    8 Safety instructions and regulations . . . . . . . . . . . . . . . . 26

    8.1 Safety instructions ........................ 278.2 Regulations...................................... 27

    9 Installation . . . . . . . . . . . . . . . . 289.1 Control installation ........................ 289.2 Wall mounting ................................. 289.3 Installing the VRC 693 outdoor

    sensor ............................................... 30

    10 Electrical installation. . . . . . . . 3310.1 Connecting the weather

    compensator ................................... 3410.2 Connecting the outside sensor... 34

    11 Start-up. . . . . . . . . . . . . . . . . . . 3511.1 Installer level................................... 3611.2 Service/diagnostic level................ 4011.3 Handing over to the owner.......... 42

    12 Technical data. . . . . . . . . . . . . . 43

    13 Vaillant customer service . . . . 43

  • 4 Operating manual and installation manual for VRC 400 weather compensator

    Notes on the documentation

    Notes on the documentation

    The following information is intended to help you throughout the entire docu-mentation. Further documents apply in combination with this installation and operation manual.We accept no liability for any damage caused by failure to observe these instructions.

    Symbols usedPlease observe the safety instructions in this manual for the installation of the control.

    DangerImmediate risk of serious injury or death

    Symbol for a necessary task

    Storage of the documentsPlease pass on this operating and installa-tion manual to the owner of the system so that he can keep it available whenev-er it is required.

  • 5Operating manual and installation manual for VRC 400 weather compensator

    Safety

    Safety

    The weather compensator must be installed by a qualified engineer, who is responsible for adhering to the existing standards and regulations.

    We accept no liability for any damage caused by failure to observe these instructions.

  • 6 Operating Manual for VRC 400 weather compensator

    1 Control overview

    Operating manual

    1 Control overview

    1

    2

    Fig. 1.1 Control overview

    Key

    1 Display

    2 Dial (turn and click)

    I Info button

    F Special functions button

    P Programming button/installer level

  • 7Operating Manual for VRC 400 weather compensator

    Display overview 2

    2 Display overview

    9

    110

    2

    3

    1112

    4

    7

    8

    6

    5

    Fig. 2.1 Overview of display

    Key

    1 Installer level and

    service/diagnosis level (see 11.1)

    2 Info level (see 4.7)

    3 Circulation pump symbol

    4 Time/temperature display

    5 Days of the week

    6 Actual temperature

    7 Operating modes (see 4.1)

    8 Special functions (see 4.6)

    9 Setting timer programmes (see 4.3)

    10 Boiler operation indicator

    11 Hot water symbol

    12 Heating circuit symbol

  • 8 Operating Manual for VRC 400 weather compensator

    3 Description of the control

    3 Description of the control

    The VRC 400 is a weather compensator with a weekly programme for heating, hot water and a circulation pump for connecting to Vaillant boilers with an eBus.The VRC 400 enables you to set heating programmes depending on the outside temperature. In addition, you can select special functions such as the party func-tion, and control the timed operation of hot water and a separate circulation pump.

  • 9Operating Manual for VRC 400 weather compensator

    Operation 4

    4 Operation

    The operating principle uses three but-tons and a dial (Vaillant Turn and Click operating concept).The display normally shows the current operating mode (e.g. ), or, if activat-ed, the special function and the cur-rent room temperature, the day of the week, the time and the symbol for heating, hot water and/or the circula-tion pump, depending on which is requested.

    4.1 Setting the operating modesTable 4.1 contains an overview of the operating modes you can select.The selected operating mode affects the timer programmes both for heating and for hot water and the circulation pump. When the weather compensator is in

    normal display mode, press the dial once the symbol for the selected mode flashes in the display.

    Turn the dial until the display shows the operating mode you want.

    The display switches back to normal mode after five seconds.

  • 10 Operating Manual for VRC 400 weather compensator

    4 Operation

    Symbol MeaningHeating

    MeaningHot water/circulation pump

    Automatic: According to the timer programmes set in the weather compensator, the heating circuit switches between heating mode and set-back mode . The heating circuit symbol is displayed if a heating requirement is detected.

    The hot water cylinder/circulation pump mode switches between heat-ing ON and OFF according to the timer programme set on the control-ler. The hot water symbol and the circulation pump symbol are shown when the time window is active. If there is a hot water request, the hot water symbol flashes.

    Heating:The heating circuit is operated according to the room temperature, regardless of the programme set on the controller. The heating circuit symbol is displayed if a heating requirement is detected.

    Set-back:The heating circuit is operated according to the set-back temperature ECO, regardless of the pro-gramme set on the controller. The heating circuit symbol is displayed if a heating requirement is detected.

  • 11Operating Manual for VRC 400 weather compensator

    Operation 4

    Symbol MeaningHeating

    MeaningHot water/circulation pump

    ECO:According to the setted timer programmes, the heating circuit switches between heating mode and OFF. The heating circuit is switched off in set-back mode, provided the anti-frost function (activat-ed when the outside temperature is below 3 C) is not active. The heating circuit symbol is displayed if a heating requirement is detected or the anti-frost function is active.

    See the table on the left

    Off:The heating circuit is off, provided that the frost protection function (if the outside temperature is below 3 C) is not activated. If the frost protection function is activated, the heating circuit symbol is displayed.

    The boiler is not heated up, regard-less of the set timer programme. The circulation pump is switched off.The hot water and circulation pump symbols are not displayed.

    Table 4.1 Operating modes

  • 12 Operating Manual for VRC 400 weather compensator

    4 Operation

    4.2 Setting the current day and time

    To set the current day and time with the display in normal mode, you must per-form the following steps: Press the dial until a day of the week

    starts flashing. Turn the dial until you see the current

    day of the week.MO = MondayTU = TuesdayWE = WednesdayTH = ThursdayFR = FridaySA = SaturdaySU = Sunday

    Press the dial. The hours start flashing. Turn the dial until you see the current

    hour. Press the dial. The minutes start flash-

    ing. Turn the dial until you see the current

    minute.

    The display switches back to normal mode after five seconds.If the calendar is activated on the install-er level (see 11.1), you can set the day, month and year in the same way. This allows automatic switching from win-ter to summer time.

  • 13Operating Manual for VRC 400 weather compensator

    Operation 4

    4.3 Setting timer programmesThe controller is equipped with a basic program (Table 4.2). Time window

    Day/Block of days

    Start time

    End time

    H1 MO-FR 6:00 22:00

    H2 - - -

    H3 - - -

    H1 SA 7:30 23:30

    H2 - - -

    H3 - - -H1 SU 7:30 22:00

    H2 - - -

    H3 - - -

    Table 4.2 Default heating, hot water and cir-

    culation programmes

    You can adapt the default programmes to suit your needs. There are six steps to setting the times you want:1. Press the programming button P2. Select the timer programme (heating,

    hot water or circulation pump)3. Select the time window4. Select the day or block of days5. Set the start time6. Set the end time

    You can define three time windows for each day.When you press the P button the display returns to basic mode.

  • 14 Operating Manual for VRC 400 weather compensator

    4 Operation

    The table below illustrates the individual steps again, using the example of the hot water timer programme. If you want to change the timer pro-gramme for heating or the circulation pump, after pressing the programming button P, select the corresponding sym-bol (heating circuit or circulation pump) and continue as shown in the example.

    Display Required stepsPress the programming button P. The cursor (black triangle) marks the value which can be changed ( ), which also flashes. Turn the dial until you see the hot water symbol.

    Press the dial. The cursor marks the adjustable value (H1), which also flashes.Select the time window by turning the dial. Settings: H1, H2, H3

  • 15Operating Manual for VRC 400 weather compensator

    Operation 4

    Display Required stepsPress the dial. The cursor marks the days of week dis-play, which also flashes.Select a block of days or a single day of the week by turning the dial.Settings:MO - SUMO - FRSA - SUMO = MondayTU = TuesdayWE = WednesdayTH = ThursdayFR = FridaySA = SaturdaySU = Sunday

    Display Required stepsPress the dial. The cursor marks the start time and the hour display flashes.Select the start time by turning the dial. Press the dial again to set the min-utes.

    Press the dial. The cursor marks the end time and the hour display flashes.Select the end time by turn-ing the dial. Click the dial again to set the minutes.

    Table 4.3 Setting time windows

  • 16 Operating Manual for VRC 400 weather compensator

    4 Operation

    If necessary, you can switch the weather compensator from the week programme to a daily programme. With the display in normal mode, press

    the F button for 10 seconds.When you programme time windows, days of the week will no longer be dis-played.

    4.4 Setting the room temperatureIf the controller is installed in the boiler, the basic display shows the set room temperature, from which the required flow temperature for the set heating curve is calculated.

    You can set the room temperature directly from the basic display. If the temperature level function is activated on the installer level (setting different temperatures for each time window, see 11.1), the display shows the currently set -room temperature (T-H1, T-H2, T-H3).

    If the controller is installed outside the boiler in a wall mounting box, the basic display shows the room temperature cur-rently measured.

  • 17Operating Manual for VRC 400 weather compensator

    Operation 4

    Fig. 4.1 Set room temperature diagram

    The diagram in fig. 4.1 shows you the relationship between the set room tem-perature and the heating curve. If you increase the set room temperature, you

    move the set heating curve parallel on a 45 axis and the flow temperature calcu-lated by the weather compensator.

    Setting the required room temperature directly Turn the dial (with the display in nor-

    mal mode).The current temperature display disap-pears, the sun symbol is displayed on the mode level and the required room temperature is shown (e. g. TEMP 20.0 C).

    By turning the dial you can set the required room temperature directly (after 1 second).

  • 18 Operating Manual for VRC 400 weather compensator

    4 Operation

    The display switches back to normal mode after five seconds.

    Setting the room temperature for time windows (Only possible if the temperature level function is set on the installer level, see 11.1). In this case you can set different room temperatures for each time window. Press the dial several times until T-H1

    appears in the display along with a set value. The set value flashes.

    Turn the dial until you see the room tem-perature you want for the time window H1. The new room temperature is assigned to all time windows with H1.

    Press the dial. T-H2 is displayed along with a set value.The set value flashes.

    Turn the dial until you see the room temperature you want for the time win-dow H2. The new room temperature is assigned to all time windows with H2.

    Press the dial. T-H3 is displayed along with a set value.The set value flashes.

    Turn the dial until you see the room temperature you want for the time win-dow H3. The new room temperature is assigned to all time windows with H3.

  • 19Operating Manual for VRC 400 weather compensator

    Operation 4

    The display switches back to normal mode after five seconds.

    Setting the set-back temperature ECO Press the dial several times until ECO

    appears in the display. The set-back temperature is displayed and starts flashing.

    Turn the dial until the required set-back temperature is displayed (e.g. ECO 15.0 C).

    The display switches back to normal mode after five seconds.

    4.5 Setting the hot water temperature

    You can set the hot water temperature from the basic display. Please note the set maximum hot water temperature on the boiler. Press the dial several times until DHW

    appears in the display. The set value flashes.

    Turn the dial until the required hot water temperature is displayed (e.g. DHW 60 C).

    The display switches back to normal mode after five seconds.

  • 20 Operating Manual for VRC 400 weather compensator

    4 Operation

    4.6 Activating special functionsPress the F button to access the special functions. You can activate the following functions:

    Display Required stepsQuick vetoThe quick veto function allows you to adjust the room temperature for a short time (until the next time window). Press the special function button F once. The quick veto symbol appears in the display along with the quick veto room temperature, which flashes. Turn the dial until the quick veto tem-perature you want is displayed. After 10 seconds, the display returns to normal mode and the function is activated. To deactivate the function early, just press the F button.

    Display Required stepsEnergy-Saving functionThe energy-saving function lets you lower the heating for an adjustable period regardless of the set heating programme. Press the special function button twice and the energy-saving symbol appears on the display. You will also see the time flashing. Now turn the dial to set the end time up to which the heating is oper-ated in set-back mode. The display switches back to basic mode after 10 seconds and the function is activated.To deactivate the function early, just press the F button.

  • 21Operating Manual for VRC 400 weather compensator

    Operation 4

    Display Required stepsParty functionWhen you activate the party function the heating phase is con-tinued beyond the next set-back phase. This also applies to the hot water and circulation pump programmes. Press the special function button F three times. The party symbol appears in the dis-play and the function is activated after ten seconds.The function is deactivated auto-matically on reaching the next heating phase. If you want to deactivate the function before, just press the F button.The function can be activated only in Auto mode or Eco

    mode.

    Display Required stepsOne-time recharging/Cylinder BoostThis function allows you to fill the cylinder, regardless of the set timer programme. Press the special function button four times. The once-only cylinder filling symbol appears in the display and the function is activated after ten seconds. If you want to deactivate the function early, just press the F button.

  • 22 Operating Manual for VRC 400 weather compensator

    4 Operation

    Display Required stepsHoliday functionThe holiday function deactivates the weather compensator, but not the frost protection function. The hot water and circulation pump are also deactivated. Press the special function button F five times - the holiday function symbol flashes in the display. The set value for the number of days holiday also flashes. Turn the dial until the required number of days holiday appears. After 10 seconds the function is activated and the mode is set to OFF for the selected period (see 4.1).If you want to deactivate the function before, just press the F button. If the anti-legionnaires disease function is activated, it is performed on the last day of the holiday.

    Table 4.4 Special functions

    4.7 Info levelPress the info button to access the info level. The info symbol appears in the dis-play as soon as you open the info level. Each time you press the info button, dif-ferent information is displayed:- The name of the weather compensator

    (VRC 400)- The quick veto room temperature (if

    active)- The set room temperature T-H1 (if acti-

    vated - e.g. T-H1 20.0 C)- The set room temperature T-H2 (if acti-

    vated - e.g. T-H2 23.0 C)- The set room temperature T-H3 (if acti-

    vated - e.g. T-H3 20.0 C)

  • 23Operating Manual for VRC 400 weather compensator

    Operation 4, Vaillant warranty 5

    - The set room temperature if the tem-perature level function is not activated (e.g.. TEMP 21.5 C)

    - The current set-back temperature (e.g. ECO 15.0 C)

    - The set hot water temperature (e.g. DHW 60 C)

    - The day/month/year (if the calendar is activated)

    - Timer programmes set for heating (eve-ry single time window per day)

    - Timer programmes set for hot water (every single time window per day)

    - Timer programmes set for the circula-tion pump (every single time window per day)

    5 Vaillant warranty

    We only grant a Vaillant manufacturers warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions.The system owner will be granted a war-ranty in accordance with the Vaillant terms and conditions. All requests for work during the guarantee period must be made to Vaillant service (0870 6060 777).

  • 24 Operating Manual for VRC 400 weather compensator

    6 Recycling and disposal

    6 Recycling and disposal

    Neither the weather compensator or any of its accessories belong in the household waste. Make sure the old con-trol and any accessories are disposed of properly.

  • 25Installation Manual for VRC 400 weather compensator

    Information on installation and operation 7

    Installation manual

    7 Information on installa-tion and operation

    The assembly, electrical connection, con-trol settings and commissioning may only be carried out by an approved com-pany specialising in heating engineering.

    7.1 CE labelThe CE label shows that the VRC 400 weather compensator, when connected to Vaillant boilers, meets the basic requirements of the Council of Europes directive 89/336/EEC on electromagnet-

    ic compatibility and the low voltage directive 73/23/EEC.

    7.2 Intended useThe VRC 400 weather compensator is a state-of-the-art control which has been constructed in accordance with recog-nised safety regulations. Nevertheless, there is a risk of death or serious injury to the user or others, and the control or other property may be damaged in the event of improper use or use for which it is not intended.

    The VRC 400 weather compensator is designed to control a heating system with a heating circuit with or without a

  • 26 Installation Manual for VRC 400 weather compensator

    7 Information on installation and operation, 8 Safety instructions and regulations

    hot water system or circulation pump according to weather conditions, time and location, in connection with a Vail-lant boiler with an eBUS.Any other use or extended use is consid-ered to be improper. The manufacturer or supplier is not liable for any resulting damage. The user alone bears any risk. Intended use includes the observance of the oper-ating and installation manual.

    8 Safety instructions and regulations

    The control must be installed by an approved company specialised in heating engineering, which is responsible for compliance with applicable standards and regulations. We accept no liability for any damage caused by failure to observe these instructions.

  • 27Installation Manual for VRC 400 weather compensator

    Safety instructions and regulations 8

    8.1 Safety instructions

    Danger!Risk of fatal electric shock from touching live connections.Before working on the control, switch off the power supply and prevent it from being switched on again.Only remove the controller from its wall mounting or base when it is not live.

    8.2 RegulationsAll wiring must be in accordance with Building Regulations Part P, current IEE regulations, and all other relevant regu-lations and guidelines, and must be car-ried out by a suitably qualified person.

    Use standard commercial cables for the wiring.- Minimum cross-section of wires:

    0.75 mm2

    Do not exceed following maximum wire lengths:- Bus wires: 300 mConnections with 230 V and bus wires must be laid separately if longer than 10 m.

  • 28 Installation Manual for VRC 400 weather compensator

    8 Safety instructions and regulations, 9 Installation

    The controller may only be installed in dry rooms.

    9 Installation

    The weather compensator can be alter-nately integrated in the boiler or e.g. can be installed on the wall in the living area with the wall socket provided with the control. It is connected to the boiler merely with a 2-core connection cable.

    9.1 Control installationTo install the weather compensator directly in the front screen of the boiler, you only need to remove the front

    screen and to push the controller into the supplied plug-in connection with a pin bar.

    9.2 Wall mountingThe VRC 400 weather compensator is designed so that it can be used as a remote-control control with or without room modulation. The controller must be installed to ensure that it can properly record the room temperature (away from heat traps, not mounted on cold walls etc.). The best place of installation is mostly in the main living room on an inside wall at approx. 1.5 m height. There, the control-ler will be able to record the circulating

  • 29Installation Manual for VRC 400 weather compensator

    Installation 9

    air, unhindered by furniture, curtains or other objects. In the room where the controller is installed, all radiator valves must be fully open when using room modulation.

    The connection to the boiler is a 2-core bus cable (eBus), see fig. 10.1. Pull the weather compensator (1) out

    of the mounting box (5). Drill two holes (3) of 6 mm diameter

    (as shown in fig. 9.1) and put in the sup-plied wall plugs.

    Thread the connection cable through the duct (4).

    Fix the mounting box to the wall with the two screws provided.

    i F P

    1

    35

    4

    2

    Fig 9.1 Mounting the controller

  • 30 Installation Manual for VRC 400 weather compensator

    9 Installation

    Connect the lead as described in sec-tion 10.

    Place the weather compensator (1) on the mounting box (5) so that the pins on the back of the upper section fit into the recesses (2).

    Push the weather compensator onto the mounting box until it catches.

    9.3 Installing the VRC 693 outdoor sensor

    This equipment may only be opened by a qualified specialist and installed as shown in the diagram. Current safety regulations must be followed as well as the installation instructions for the heat-

    ing equipment and for the heating con-troller.

    Installation locationThe outdoor sensor should be installed on the side of the house where the most frequented rooms are located. If this side cant be clearly identified, then install it on the north or north-west side of the house.To ideally measure the outdoor tempera-ture, for houses up to three storeys, the device should be fitted about two thirds of the way up the wall. For taller build-ings, installation is recommended between the 2nd and 3rd floors.

  • 31Installation Manual for VRC 400 weather compensator

    Installation 9

    The location should not be protected from the wind, nor particularly exposed and it should not be exposed to direct sunlight. The device must be at least 1 m away from any opening in the outer wall, from which warm air can either continu-ously or occasionally issue.It can be installed either in or on the wall, depending on the accessibility of the location.

    N

    SW

    O

    1/3

    2/3

    > 1 m

    N, NW (optional)

    Fig. 9.2 Installation location of the VRC 693

    outdoor sensor

  • 32 Installation Manual for VRC 400 weather compensator

    9 Installation

    Caution!There is a risk of the wall and control becoming wet.Lay the cables properly and carefully to ensure that the out-door sensor and the building are not damaged by water.The control must be fixed to the wall in the correct position, as shown in fig. 9.3. The cable entry (3, fig. 9.3) must point downwards.

    Fig. 9.3 Fitting and positioning the outdoor

    sensor

  • 33Installation Manual for VRC 400 weather compensator

    Installation 9, Electrical installation 10

    Remove the cover (1) of the housing and fix the housing to the wall using two screws through the fixing holes (8).

    Lay a connection cable (4) of at least 2 x 0.75 mm2 and pull it up through the cable entry (3).Lay the cable properly and carefully to ensure that the sensor and the wall are not damaged by water.

    Wire up the terminals as shown in the diagram in fig. 10.1.

    Make sure the housing seal is correctly fixed in the top section of the housing (1) and push the top section onto the housing.

    Fix the top of the housing (1) to the bottom (2) using the screws supplied.

    10 Electrical installation

    The electrical connection may only be carried out by a suitably qualified engi-neer.

    Danger!Risk of fatal electric shock from touching live connections. Before working on the control, turn off the power supply and secure against restart.

  • 34 Installation Manual for VRC 400 weather compensator

    10 Electrical installation

    10.1 Connecting the weather com-pensator

    If the weather compensator is integrated directly in the boiler, the electrical con-nection is directly through the pin bars that are introduced in the connecting plug in the boiler.For wall mounting, the communciation to the boiler is through the eBus. All eBus-connectors are designed to take at least 2 x 0.75 mm2 (recommended) per termi-nal. This means that the wires can be swapped without impairing communica-tion (fig. 10.1).

    Also follow the instructions for the boil-er. Do not remove the jumper between ter-minals 3 and 4 on the boiler.

    10.2 Connecting the outside sensorThe external probe is connected directly on the boiler. Please observe the boiler manual while connecting the control.

  • 35Installation Manual for VRC 400 weather compensator

    Electrical installation 10, Start-up 11

    Fig. 10.1 Electrical connection

    11 Start-up

    Certain system parameters have to be set in order for them to best suit the actual conditions. These system parame-ters are all together in the intaller level and should only be set by the heating engineer.The service/diagnostic level is also intended for the engineer and is designed to help during servicing.

  • 36 Installation Manual for VRC 400 weather compensator

    11 Start-up

    11.1 Installer levelPress the P button to access the installer level. Press the P button for 10 seconds.

    The spanner symbol and the first parameter appear in the display.

    Press the dial. You can select all the system parameters in turn.

    Turn the dial to set the values you want.

    When you press the P button the display returns to basic mode.

    You can select and change the following parameters:

    Display Setting by turning the dial

    Set-back temperatureDefault setting: 15 CAdjustment range: 5 ... 30 C

    Set hot water temperatureDefault setting: 60 CAdjustment range: 35 ... 70 C

    Correction of actual room temperatureAdjustment of the displayed value in the range of max. +/- 3 CFactory setting 0 C

  • 37Installation Manual for VRC 400 weather compensator

    Start-up 11

    Display Setting by turning the dial

    Anti-legionnaires disease system1=Activate the anti-legion-naires disease function. Every Wednesday, one hour before the first time window, a connected hot water cyclinder is heated to 70 C, the circulation pump is switched on and oper-ated at 70 C for at least 30 minutes.Default setting = 0 (off)

    Display Setting by turning the dial

    Heating curveThe heating curve repre-sents the ratio between out-side temperature and target flow temperature. Default setting: 1,2Room temperature modula-tion (wall installation only)1 = Room temperature modulation (including the room tem-perature in the flow tem-perature calculation)2 = Thermostat function (switching off the heating when the set room tempera-ture is reached)Default setting: 0 = No room modulation

  • 38 Installation Manual for VRC 400 weather compensator

    11 Start-up

    Display Setting by turning the dial

    Minimum temperature (foot point)Adjustment range 15 ... 90 CDefault setting: 15 C

    Frost protection delayTimed suppression of anti-frost function (activated at outside tem-peratures below 3 C)Adjustment range: 0 ... 12 hDefault setting: 0 h

    Display Setting by turning the dial

    Outside temperature shut-down thresholdShurtdown temperature for demand-based deactivation of heatingAdjustment range: 5 ... 50 CDefault setting: 22 C

    Outside temperature cor-rectionCorrects the temperature currently measured by the set value to compensate for outside influencesAdjustment range: -5 ... +5 CDefault setting: 0 C

  • 39Installation Manual for VRC 400 weather compensator

    Start-up 11

    Display Setting by turning the dial

    Hydraulic switch1 = Activation of sensor recording when the hydrau-lic switch is used, default setting 0 = Off

    Day settingFor activation of the calendar

    Month settingFor activation of the calendar

    Display Setting by turning the dial

    Year settingFor activation of the calendar

    Temperature levelActivate the setting for different temperatures for each time window. 0 = Temperaturel level off 1 = Temperature level on, default setting: 0

  • 40 Installation Manual for VRC 400 weather compensator

    11 Start-up

    Display Setting by turning the dial

    Temperature level time window H1

    (only when temperature levels are activated)

    Temperature level time window H2

    (only when temperature lev-els are activated)

    Temperature level time window H3

    (only when temperature lev-els are activated)

    Table 11.1 System parameters

    11.2 Service/diagnostic levelAccess the service/diagnostic level by pressing the P button and the dial. Press the P button and the dial simul-

    taneously for 3 seconds.First, a heating request for 50 C is trig-gered to test communication with the boiler.Then you can select all the test options by pressing the dial (see table 11.2). When you press the P button the display returns to basic mode.

    You can select the following tests:

  • 41Installation Manual for VRC 400 weather compensator

    Start-up 11

    Dial Test Test procedurePress and push P button for 3 seconds

    Heating request A heating request of 50 C is simulated. The burner on the boiler starts up and the pump starts (only up to the maxi-mum flow temperature of the boiler).

    Turn Hot water request A hot water request is activated, charging pump starts working, all other elements are switched off.

    Turn Circulation pump The circulation pump is activated (if connected). All other elements are switched off.

    Press Display test All display elements are displayed.

    Press Software version The software version is displayed.

    Table 11.2

  • 42 Installation Manual for VRC 400 weather compensator

    11 Start-up

    42

    Restore default settings To restore the controller to its default

    condition, press the P button for 15 sec-onds.As soon as the display lights up twice, the controller is completely rest to its default settings. This means that you will have to perform all individual set-tings again.

    11.3 Handing over to the ownerThe owner of the weather controller must be instructed about its functions and how to operate it. Hand over any instructions intended

    for the owner as well as the control documents.

    Go through the operating manual with the owner and answer any questions.

    Draw special attention to the safety instructions which the owner must fol-low.

    Tell the owner to keep the instruction manuals near the controller.

  • 43Installation Manual for VRC 400 weather compensator

    Technical data 12, Vaillant customer service 13

    12 Technical data

    Description Unit

    Operating voltage Umax V 24

    Maximum ambient tempera-ture

    C 50

    Current consumption mA < 17

    Minimum cross-section of wires

    mm2 0.75

    Level of protection IP 20

    Protection class III

    DimensionsHeight mm 97

    Width mm 146

    Depth mm 40

    Table 12.1 Technical data

    13 Vaillant customer service

    To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement.Please contact Vaillant service (0870 6060 777) for further details.

  • 44 Operating manual and installation manual for VRC 400 weather compensator

    EC declaration of conformity

  • 83

    85

    87

    _00

    GB

    0

    4 2