NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL COVER INSTRUCTIONS FOR INSTALLING WALL SHEETING LAST REVISION BY: AES CHK: EGB DETAIL NAME IF APPLICABLE Part Number H9430 PAGE 1 FOR FIELD USE PLEASE DISTRIBUTE TO THE ERECTION CREW DUE TO THE PROCESS OF CONTINUOUS IMPROVEMENT, THE PRODUCTS AND PROCEDURES IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE ERECTION MANUAL REVISION INFORMATION ACTIVITY ADDENDUM RELEASE # PAGES REVISED RELEASE DATE Most Recent #10 7,9,14 & 15 7/27/2017 #9 14-15 10/07/2016 #8 3,10 4/12/2016 #7 22,23 5/1/2014 Previous Revisions #6 10,16-18 8/29/2012 WATERLOO, IN 305 Industrial Parkway Waterloo, IN 46793 Phone: 260-837-7891 Fax: 260-837-7384 SWANSEA, SC 200 Whetstone Road Swansea, SC 29160 Phone: 803-568-2100 Fax: 803-568-2121 TERRELL, TX 600 Apache Trail Terrell, TX 75160 Phone: 972-524-5407 Fax: 972-524-5417 LANCASTER, PA 255 Butler Avenue Suite 200 Lancaster, PA 17601 Phone: 717-735-7766 Fax: 717-735-7769 BRIGHAM CITY, UT 1050 North Watery Lane Brigham City, UT 84302 Phone: 435-919-3100 Fax: 435-919-3101

Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

COVER INSTRUCTIONS FOR INSTALLING WALL SHEETING

LAST REVISIONBY: AES CHK: EGB

DETAIL NAME IF APPLICABLEPart Number H9430 PAGE 1

FOR FIELD USE

PLEASE DISTRIBUTE TO THE ERECTION CREW

DUE TO THE PROCESS OF CONTINUOUS IMPROVEMENT, THE PRODUCTS AND PROCEDURES IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE

ERECTION MANUAL REVISION INFORMATIONACTIVITY ADDENDUM RELEASE # PAGES REVISED RELEASE DATE

Most Recent #10 7,9,14 & 15 7/27/2017#9 14-15 10/07/2016#8 3,10 4/12/2016#7 22,23 5/1/2014

Previous Revisions

#6 10,16-18 8/29/2012

WATERLOO, IN305 Industrial Parkway

Waterloo, IN 46793Phone: 260-837-7891

Fax: 260-837-7384

SWANSEA, SC200 Whetstone RoadSwansea, SC 29160Phone: 803-568-2100

Fax: 803-568-2121

TERRELL, TX600 Apache TrailTerrell, TX 75160

Phone: 972-524-5407Fax: 972-524-5417

LANCASTER, PA255 Butler Avenue

Suite 200Lancaster, PA 17601Phone: 717-735-7766

Fax: 717-735-7769

BRIGHAM CITY, UT1050 North Watery LaneBrigham City, UT 84302

Phone: 435-919-3100Fax: 435-919-3101

Page 2: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

1.0 TABLE OF CONTENTS

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEPAGE 2

1.0 TABLE OF CONTENTS

1.0 TABLE OF CONTENTS ........................................................................................21.0 RECEIVING, HANDLING AND STORING MATERIALS......................................3

1.1 Receiving Materials & Filing Claims.................................................................................31.2 Handling Materials ...........................................................................................................41.3 Storing Materials ..............................................................................................................5

2.0 PANEL PROFILES................................................................................................63.0 STANDARD PARTS..............................................................................................74.0 PROPER FASTENER INSTALLATION................................................................95.0 PANEL PREPARATION......................................................................................11

5.1 Pre-Drilling Panels .........................................................................................................115.2 Important Information About Wall Panel Orientation......................................................125.3 Wall Panel Erection Notes .............................................................................................13

6.0 BASE TRIM INSTALLATION..............................................................................146.1 Standard Base Angle Trim .............................................................................................146.2 Optional Base Trim ........................................................................................................15

7.0 FASTENER REQUIREMENTS FOR EACH PANEL TYPE ................................167.1 Fastener requirements for “CLASSIC” Wall Panel.........................................................167.2 Fastener Requirements for “ACCENT” Wall Panel ........................................................177.3 Fastener Requirements for “REVERSE CLASSIC” Wall Panel .....................................187.4 Proper Fastener Sequence Detail ..................................................................................19

8.0 CORNER TRIM INSTALLATION ........................................................................208.1 “CLASSIC” Panel ...........................................................................................................208.2 “ACCENT” Panel ............................................................................................................218.3 “REVERSE CLASSIC” Panel .........................................................................................22

9.0 GENERAL NOTES..............................................................................................239.1 Translucent Panel ..........................................................................................................239.2 Framed Opening Trim Installation..................................................................................23

Page 3: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

1.0 RECEIVING, HANDLING & STORING MATERIALS

LAST REVISIONDATE: 04-11-2016BY: KMC CHK: EGB

DETAIL NAME IF APPLICABLEPAGE 3

1.0 RECEIVING, HANDLING AND STORING MATERIALS

1.1 RECEIVING MATERIALS & FILING CLAIMS

Check shipment against delivery tickets during unloading.

Note any damage or discrepancies on the delivery tickets before signing as receiver.

Nucor Building Systems is not responsible for carrier damage or discrepancies not noted on the delivery tickets.

The customer assumes full responsibility for the condition of this material after deliver by the trucking company.

Nucor Building Systems is not responsible for items accepted in questionable condition.

Upon acceptance of shipment(s), the contractor is responsible for the proper storage and handling of materials as described in this manual.

Nucor Building Systems is not responsible for injury, damage, or loss as a result of improper storage and/or handling.

All claims must be filed with Nucor’s Quality Services Representative prior to any field modifications or purchases that may result in a charge to Nucor

Building Systems. Contact our Service Representative at:

This building is designed, manufactured, and delivered in accordance with most recent addition of the M.B.M.A. METAL BUILDING SYSTEMS MANUAL. CONSULT THE INFORMATION IN THE “COMMON INDUSTRY PRACTICES” SECTION.

WATERLOO, IN305 Industrial Parkway

Waterloo, IN 46793Phone: 260-837-7891

Fax: 260-837-7384

SWANSEA, SC200 Whetstone RoadSwansea, SC 29160Phone: 803-568-2100

Fax: 803-568-2121

TERRELL, TX600 Apache TrailTerrell, TX 75160

Phone: 972-524-5407Fax: 972-524-5417

LANCASTER, PA255 Butler Avenue

Suite 200Lancaster, PA 17601Phone: 717-735-7766

Fax: 717-735-7769

BRIGHAM CITY, UT1050 North Watery LaneBrigham City, UT 84302

Phone: 435-919-3100Fax: 435-919-3101

Page 4: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

1.0 RECEIVING, HANDLING & STORING MATERIALS

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEPAGE 4

1.2 HANDLING MATERIALS

Nucor wall panels are rolled and banded, with a cover panel placed top and bottom.

Panel bundle weight can be found on i.d. tag at low end of each bundle. Maximum weight is 4300 pounds.

Bundles up to 25 feet can be handled using a forklift. Forks must be spaced a minimum of five feet apart.

Bundles over 25 feet should be handled with a crane using a spreader bar and nylon slings. Lifting should occur at center of gravity.

Locate slings at 1/4 of the length of the panel from each end of the bundle.

Trim crates/boxes are to be handled the same as panel bundles.

STEEL CHOKERS/SLINGS, CABLES OR CHAINS SHALL NOT BE USED.

Page 5: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

1.0 RECEIVING, HANDLING & STORING MATERIALS

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEWSEM0010.DWG PAGE 5

1.3 STORING MATERIALS

Panel and trim bundles / crates should be blocked 12 inches above grade.

Elevate one end to allow moisture to drain.

Loosely cover with waterproof tarp to allow proper air circulation.

Inspect daily and dry if necessary.

Accessories must be kept dry and free of contamination. Store indoors if possible.

If the panels are wet, the bundles should be opened and then the panels should be dried and re-stacked to prevent damage.

IMPORTANT NOTE: The finish on these panels may not perform as intended if not erected within 90 days from receipt at the job site. The finish is also subject to severe damage if moisture, debris, or dust is allowed to get between the panels; therefore, panels MUST BE STORED UNDER COVER with one end elevated to allow for drainage and protection against moisture, dust, or debris until erected. The manufacturer will not accept claims for non-performing panels if not properly stored at the jobsite. The customer assumes full responsibility for the condition of this material after deliver by the trucking company.

12" MIN

PANEL BUNDLES

12" MIN

TRIM CRATE

WaterproofTarp

Page 6: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

2.0 PANEL PROFILES

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEWSEM0020.DWG PAGE 6

2.0 PANEL PROFILES

36" COVERAGE

12" 12" 12"

CLASSIC WALL PANEL

ACCENT WALL PANEL

REVERSE CLASSIC WALL PANEL

6"12"

36" COVERAGE

12" 12"

12"

36" COVERAGE

12" 12"

6"

PART NUMBERING CONVENTIONS Example: CW 6 - 12250

PANEL TYPECW = CLASSIC PanelAW = ACCENT PanelRC = REVERSE CLASSIC Panel

PANEL GUAGE2 = 22 guage4 = 24 guage6 = 26 guage

PANEL LENGTH (In Inches)The last (2) digits are for fractions of an inch.

Page 7: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

3.0 STANDARD PARTS

LAST REVISIONDATE: 07-27-2017BY: EGB CHK: KMC

DETAIL NAME IF APPLICABLEWSEM0030.dwg PAGE 7

3.0 STANDARD PARTS

Page 8: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

3.0 STANDARD PARTS

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEWSEM0040.dwg PAGE 8

Page 9: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

4.0 PROPER FASTENER INSTALLATION

LAST REVISIONDATE: 06-09-2017BY: AES CHK: EGB

DETAIL NAME IF APPLICABLEPAGE 9

4.0 PROPER FASTENER INSTALLATION

SEE THE FASTENER SCHEDULE BELOW

RECOMMENDED TOOL TYPES:2000 - 2500 rpm screw gun with torque adjustable clutch

Manual or electric rivet tool

6-7 amp or higher rated tools (DO NOT USE CORDLESS SCREW GUNS)DO NOT USE IMPACTING TOOLSTo assure proper voltage to the tool, extension cords should be checked for proper wire size/chord length.

16 gage wire, maximum chord length = 100’14 gage wire, maximum chord length = 200’12 gage wire, maximum chord length = 300’DRIVING TIPS:Drive fasteners perpendicular to panel surface

Compress the insulation at fastener location with one hand while driving the fastener with the

other. This will help keep the panel flat and prevent the fastener from “walking”.

Excessive pressure can cause drill point failure. Let the fastener do the work.

FIELD CUTTING OF PANELS:When field cutting or mitering wall panels, non-abrasive cutting tools such as nibblers or tin-snips shall be used. Abrasive cutting tools such as mechanical grinders or power saws can damage the material finish and create excess metal shavings that can corrode the panels. The use of non-approved cutting devices may void the factory warranty.IMPORTANT NOTE: NOSE CONES SHOULD BE USED ON SCREW GUNS TO PREVENT DISTORTING THE PANEL AND TO HELP AVOID OVER-DRILLING THE FASTENERS.FASTENER SEQUENCEFASTENERS SHOULD BE INSTALLED FROM THE BASE TO THE EAVE. This will help prevent the panels from oil-canning. See section 7.4 for detail.

IMPORTANT NOTE: After a panel has been installed, be sure to brush off all metal filings. Leaving these filings from the self-drilling fasteners may stick to the panel finish and cause rust staining to take place. Failure to remove these filings may void panel finish warranty.

Page 10: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

4.0 PROPER FASTENER INSTALLATION

LAST REVISIONDATE: 02-22-2016BY: SDF CHK: EGB

DETAIL NAME IF APPLICABLEWSEM0050.dwg PAGE 10

FASTENER SPECIFICATIONS USAGE

-2000 RPM; Torque Adjustable Clutch-DO NOT use Impacting Tools

Recommended Tool Types:

SELF-DRILLING SCREW Used to attach light gauge walltrim end laps and trim to wallpanels.

-2000 RPM; Torque Adjustable Clutch-DO NOT use Impacting Tools

Recommended Tool Types:

SELF-DRILLING SCREW Used to attach light gauge walltrim end laps and trim to wallpanels.

POP RIVET

-DO NOT use Impacting Tools

Recommended Tool Types:-Manual or Electric Rivet Tool

Used at trim laps, corner capsand attaching light gaugematerial to siding wherescrews can't be used.

H1040

H1041 SELF-DRILLING SCREW

SELF-DRILLING SCREW

H1045 SELF-DRILLING SCREW

H1047 SELF-DRILLING SCREW

-2000 RPM; Torque Adjustable Clutch-DO NOT use Impacting Tools

Recommended Tool Types:

-2000 RPM; Torque Adjustable Clutch-DO NOT use Impacting Tools

Recommended Tool Types:

-2000 RPM; Torque Adjustable Clutch-DO NOT use Impacting Tools

Recommended Tool Types:

-2000 RPM; Torque Adjustable Clutch-DO NOT use Impacting Tools

Recommended Tool Types:

Used to attach wall panel, wallflashing and light gauge parts.Use at insulation thicknessof =/> 6"

Used to attach wall panel, wallflashing and light gauge parts.Use at insulation thicknessof =/> 6"

Used to attach wall panel, wallflashing and light gauge parts.Maximum insulation thicknessis < 6"

Used to attach wall panel, wallflashing and light gauge parts.Maximum insulation thicknessis < 6"

Page 11: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

5.0 PANEL PREPARATION

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEWSEM0060.DWG PAGE 11

5.0 PANEL PREPARATION5.1 PRE-DRILLING PANELS

NUCOR RECOMMENDS PRE-DRILLING OF SIDELAP JOINTS, WHICH IN MANY CASES, WILL SPEED ERECTION AND MAKE A TIGHT JOINT.

STEP 1: Stack panels with ends flush on a level place on the ground in piles not exceeding 10 panels. Then place small wooden blocks under side lapping edge of stack of panels to hold them at correct height and position while drilling screw holes. Hold panels tightly together at each end with “Vise Grip Pliers”. Carefully mark positions for sidelap fasteners on top of high rib. Fasteners should be located “ON CENTER” of high rib AS SHOWN BELOW.

STEP 2: Drill holes for “Stitch” screws (Use #1,-7/32”-15/64” drill-bit) on top sheet of sidelap. Be sure panels are well nested before drilling.

WHEN USING OTHER TYPE FASTENERS, SIZE OF DRILL-BIT MAY CHANGE!

Page 12: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

5.0 PANEL PREPARATION

LAST REVISIONDATE: 04-13-2007BY: EGB CHK: RJF

DETAIL NAME IF APPLICABLEWSEM0070.dwg PAGE 12

5.2 IMPORTANT INFORMATION ABOUT WALL PANEL ORIENTATION

Nucor “ACCENT” and “REVERSE CLASSIC” wall panels are “HANDED” panels. The

“UPTURNED” leg of the panel ALWAYS goes on the bottom. See the details below.

"NUCOR RC PANEL"

"NUCOR ACCENT PANEL"

"NUCOR CLASSIC WALL" PANEL Steel Line

Steel Line

Steel Line

TUCK PANEL TIGHTTO THIS CORNER

TUCK PANEL TIGHTTO THIS CORNER

DIMENSION MAY VARY

DIMENSION MAY VARY

PANEL ERECTION

Page 13: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

5.0 PANEL PREPARATION

LAST REVISIONDATE: 08-15-2011BY: JV CHK: KMC

DETAIL NAME IF APPLICABLEPAGE 13

5.3 WALL PANEL ERECTION NOTES

Block girts to “level” position before starting panel erection. Keep this blocking (blocking is not provided by NBS) in place until the wall panel to girt fasteners are installed.

Make sure that the first wall panel is aligned and plumb.

To prevent “Oil-Canning”, all panel fasteners should start from the base and then be fastened to each girt location working toward the eave

Make sure that the foundation is square, level, and correct to the out-to-out steel line dimensions.

The erection crew is responsible for cleaning all wall panels before leaving the job site.

Prevailing wind, main traffic area, etc. should be taken into consideration when sheeting the wall.

Panels must be stored properly to prevent moisture damage. Reference section 1.3 for additional information.

At flush girt conditions, pre-drill columns (& stubs if req’d) for ease of panel attachment at these areas.

Page 14: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

6.0 BASE TRIM INSTALLATION

LAST REVISIONDATE: 07-27-2017BY: EGB CHK: KMC

DETAIL NAME IF APPLICABLEWSEM0080.dwg PAGE 14

6.0 BASE TRIM INSTALLATION6.1 STANDARD BASE ANGLE TRIM

At Standard Base Angle Trim laps, apply a bead of polyurethane tube caulk (H3152) to all adjoining surfaces and lap 1”.

If job has optional foam panel closures, attach to inside of wall panel at base and fasten through panel and closure, into base trim. (as shown) Fastening pattern will vary per wall panel type.

Refer to this manual; sections 7.1-7.4 and/or the const drawing set for more fastening info.

Field mitre base angle at corners.

INSULATION HINT: At the base, fold the insulation backer over the fiber to help prevent water from wicking.

Page 15: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

6.0 BASE TRIM INSTALLATION

LAST REVISIONDATE: 07-27-2017BY: EGB CHK: EGB

DETAIL NAME IF APPLICABLEWSEM0090.dwg PAGE 15

6.2 OPTIONAL BASE TRIM

Before lapping trim, field cut the back vertical leg of the adjoining trim piece 1” as shown below. This will help to make the trim lap more readily.

If job has optional foam panel closures, attach to inside of wall panel at base and fasten through panel and closure, into base trim. (as shown) Fastening pattern will vary per wall panel type. Refer to this manual; sections 7.1-7.4 and/or the const drawing set for more fastening info

At Optional Base Trim laps, apply a bead of polyurethane tube caulk (H3152) to all adjoining surfaces and lap 1”.

See the erection drawing details for base trim corner termination parts numbers.

INSULATION HINT: At the base, fold the insulation backer over the fiber to help prevent water from wicking.

Page 16: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

7.0 FASTENER REQUIREMENTS FOR EACH PANEL TYPE

LAST REVISIONDATE: 08-01-2012BY: AES CHK: EGB

DETAIL NAME IF APPLICABLEWSEM0100.dwg PAGE 16

7.0 FASTENER REQUIREMENTS FOR EACH PANEL TYPE7.1 FASTENER REQUIREMENTS FOR “CLASSIC” WALL PANEL

REFER TO THE ELEVATIONS FOR LOCATION REQUIREMENTS.ERECTOR NOTE: 1/2" SIDELAP MASTIC (H3010) IS REQ'D IN SNOWDRIFT CONDITIONS.

EAVE

N.B.S. "CLASSIC WALL" ERECTION NOTESBASE

H1060 AT 12" O.C.

CORNER TRIM

AT TRIM

WALL PANEL

SIDE LAP

H1060 AT

GIRTS

STITCH

STRUCTURAL

(H1040)

(H1060)

6"6"6" 6" 6"36" (NET LAY)

6"

30" O.C. MAX.

FASTENER

FASTENER

CORNERTRIM

36" (NET LAY)

CLASSIC PANELFasten to base and eave structuralmembers with 12-14 x 1 1/4" TCP 2structural fasteners (H1040) at 6"o.c. (next to each rib)

Fasteners to intermediate structuralmembers with 12-14 x 1 1/4" TCP 2structural fasteners (H1040) at 12"o.c. (3" each side of rib)

Fasten sidelaps with 12-14 x 7/8"self-drilling screws (H1060): - At girts - 30" o.c. between supports

Fasten trim with 12-14 x 7/8"delf-drilling screws (H1060) at 12"O.C.

NOTE: USE NOSE CONES ON SCREW GUNS TOPREVENT DISTORTING THE PANEL AND TO HELPAVOID OVER-DRIVING THE FASTENERS

Page 17: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

7.0 FASTENER REQUIREMENTS FOR EACH PANEL TYPE

LAST REVISIONDATE: 08-02-2012BY: AES CHK: EGB

DETAIL NAME IF APPLICABLEWSEM0110.DWG PAGE 17

7.2 FASTENER REQUIREMENTS FOR “ACCENT” WALL PANEL

12"

36"

12"12"

N.B.S. "ACCENT PANEL" ERECTION NOTESERECTOR NOTE: 1/2" SIDELAP MASTIC (H3010) IS REQ'D IN SNOWDRIFT CONDITIONS. REFER TO THE ELEVATIONS FOR LOCATION REQUIREMENTS.

36" (NET LAY)

BASE

H1060 AT 12" O.C.AT TRIM

CORNER TRIM

EAVE

TRIMCORNER

H1060 AT

SIDE LAP

WALL PANEL

30" O.C. MAX.

GIRTS

STITCH

FASTENERSTRUCTURAL

FASTENER

(H1040)

(H1060)

ACCENT PANEL:Fasten structural memberswith 12-14 x 1 1/4" TCP 2 structuralfasteners (H1040) at 12" o.c. (in each rib)

Fasten sidelaps with 12-14 x 7/8" TCP1self-drilling screws (H1060): - At girts - 30" o.c. between supports

Fasten trim with 12-14 x 7/8" TCP1 self-drilling screws (H1060) at 12" O.C.

NOTE: USE NOSE CONES ON SCREW GUNS TOPREVENT DISTORTING THE PANEL AND TO HELPAVOID OVER-DRIVING THE FASTENERS

Page 18: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

7.0 FASTENER REQUIREMENTS FOR EACH PANEL TYPE

LAST REVISIONDATE: 08-02-2012BY: AES CHK: EGB

DETAIL NAME IF APPLICABLEWSEM0120.DWG PAGE 18

7.3 FASTENER REQUIREMENTS FOR “REVERSE CLASSIC” WALL PANEL

36"

N.B.S. REVERSE "CLASSIC WALL" ERECTION NOTES

12"12"12"

36" (NET LAY)

REFER TO THE ELEVATIONS FOR LOCATION REQUIREMENTS.ERECTOR NOTE: 1/2" SIDELAP MASTIC (H3010) IS REQ'D IN SNOWDRIFT CONDITIONS.

CORNER TRIM

AT TRIMH1060 AT 12" O.C.

BASE

CORNERTRIM

EAVE

FASTENER

STRUCTURAL FASTENER

STITCH

30" O.C. MAX.

WALL PANEL

SIDE LAP

H1060 AT

GIRTS

(H1040)

(H1060)

REVERSE CLASSIC PANEL:Fasten structural memberswith 12-14 x 1 1/4" TCP 2 structuralfasteners (H1040) at 12" o.c. (in each rib)

Fasten sidelaps with 12-14 x 7/8" TCP1self-drilling screws (H1060): - At girts - 30" o.c. between supports

Fasten trim with 12-14 x 7/8" TCP1self-drilling (H1060) screws at 12" o.c.

NOTE: USE NOSE CONES ON SCREW GUNS TOPREVENT DISTORTING THE PANEL AND TO HELPAVOID OVER-DRIVING THE FASTENERS

Page 19: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

7.0 FASTENER REQUIREMENTS FOR EACH PANEL TYPE

LAST REVISIONDATE: 05-14-2007BY: KMC CHK: RJF

DETAIL NAME IF APPLICABLEWSEM0130.DWG PAGE 19

7.4 PROPER FASTENER SEQUENCE DETAIL

NOTE: "CLASSIC" Profile shown. Refer to Sections 7.2 and 7.3 for Fastener quantity requirements for "ACCENT" and "REVERSE CLASSIC" profiles.

Eave Strut

Side Lap with H1060 Fasteners at 30" On Center MAXIMUM

Page 20: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

8.0 CORNER TRIM INSTALLATION

LAST REVISIONDATE: 3-31-2014BY: AES CHK:

DETAIL NAME IF APPLICABLEWSEM0180.DWG PAGE 20

8.0 CORNER TRIM INSTALLATION8.1 “CLASSIC” PANEL

Steel Line3 1/2" Max.

Rib

"CLASSIC" PANEL OUTSIDE CORNER DETAIL

LCRefer to the Erection Drawing Sheeting Elevations for Start Panel Centerline of Rib Location.

Structural Fastener at Each Support, Stitch Fastener at 12" o.c. Between Supports (Typical at Corner Trim).

Filler Trim, IF REQUIRED, As Noted on Erection Drawing Wall Sheeting Elevations

Girt (Typical)

Outside Corner Trim

"CLASSIC" Panel (Typ.) NOTE: It is possible that Filler Trim is required at both the Endwall and the Sidewall. Refer to the Erection Drawing Sheeting Elevations for Requirements and Part Numbers.

ALSO: Refer to Section 5.2 of this Manual for proper Panel Orientation.

"CLASSIC" PANEL INSIDE CORNER DETAIL

Refe

r to

the

Ere

ctio

n D

rawi

ng

Shee

ting

Ele

vati

ons

for

Star

t Pa

nel

Cent

erlin

e of

Rib

Loc

atio

n.

Stee

l Lin

e3

1/2"

LRi

bC

(Max

imum

)

"CLASSIC" Panel (Typ.)

Filler Trim, IF REQUIRED, As Noted on Erection Drawing Wall Sheeting Elevations

Structural Fastener at Each Support, Stitch Fastener at 12" o.c. Between Supports (Typical at Corner Trim).

Inside Corner Trim

Girt (Typical)

NOTE: It is possible that Filler Trim is required at both the Endwall and the Sidewall. Refer to the Erection Drawing Sheeting Elevations for Requirements and Part Numbers.

ALSO: Refer to Section 5.2 of this Manual for proper Panel Orientation.

Page 21: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

8.0 CORNER TRIM INSTALLATION

LAST REVISIONDATE: 3-31-2014BY: AES CHK:

DETAIL NAME IF APPLICABLEWSEM0190.DWG PAGE 21

8.2 “ACCENT” PANEL

Outside Corner Trim

"ACCENT" PANEL OUTSIDE CORNER DETAIL

Steel Line 6"

Rib

Structural Fastener at Each Support, Stitch Fastener at 12" o.c. Between Supports (Typical at Corner Trim).

Filler Trim, IF REQUIRED, As Noted on Erection Drawing Wall Sheeting Elevations

CL

"ACCENT" Panel (Typ.)

Girt (Typical)

Refer to the Erection Drawing Sheeting Elevations for Start Panel Centerline of Rib Location.

NOTE: It is possible that Filler Trim is required at both the Endwall and the Sidewall. Refer to the Erection Drawing Sheeting Elevations for Requirements and Part Numbers.

ALSO: Refer to Section 5.2 of this Manual for proper Panel Orientation.

"ACCENT" PANEL INSIDE CORNER DETAIL Refe

r to

the

Ere

ctio

n D

rawi

ng

Shee

ting

Ele

vati

ons

for

Star

t Pa

nel

Cent

erlin

e of

Rib

Loc

atio

n.

6"Ri

bLC

Stee

l Lin

e(W

ith

Std.

Tri

m)

"ACCENT" Panel (Typ.)

NOTE: It is possible that Filler Trim is required at both the Endwall and the Sidewall. Refer to the Erection Drawing Sheeting Elevations for Requirements and Part Numbers.

ALSO: Refer to Section 5.2 of this Manual for proper Panel Orientation.

Structural Fastener at Each Support, Stitch Fastener at 12" o.c. Between Supports (Typical at Corner Trim).

Girt (Typical)

Filler Trim, IF REQUIRED, As Noted on Erection Drawing Wall Sheeting Elevations

Inside Corner Trim

Page 22: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

8.0 CORNER TRIM INSTALLATION

LAST REVISIONDATE: 3-31-2014BY: AES CHK:

DETAIL NAME IF APPLICABLEWSEM0200.DWG PAGE 22

8.3 “REVERSE CLASSIC” PANEL

"REVERSE CLASSIC" PANEL OUTSIDE CORNER DETAIL

NOTE: It is possible that Filler Trimis required at both the Endwall andthe Sidewall. Refer to the ErectionDrawing Sheeting Elevations forRequirements and Part Numbers.

ALSO: Refer to Section 5.2 of thisManual for proper Panel Orientation.

Refer to the Erection Drawing Sheeting Elevationsfor Start Panel Centerline of Rib Location.

Rib

Steel Line

LC

6"

Structural Fastener at EachSupport, Stitch Fastener at12" o.c. Between Supports(Typical at Corner Trim).

Girt (Typical)

Outside Corner Trim

Filler Trim, IF REQUIRED,As Noted on ErectionDrawing Wall SheetingElevations

"REVERSE CLASSIC"Panel (Typical)

"REVERSE CLASSIC" PANEL Refe

r to

the

Ere

ctio

n D

rawi

ngSh

eeti

ng E

leva

tion

s fo

r St

art

Pane

lCe

nter

line

of R

ib L

ocat

ion.

Rib

C LSt

eel L

ine

(Wit

h St

d. T

rim

)6"

NOTE: It is possiblethat Filler Trim isrequired at both theEndwall and the Sidewall.Refer to the ErectionDrawing SheetingElevations forRequirements and PartNumbers.

ALSO: Refer to Section5.2 of this Manual forproper Panel Orientation.

Structural Fastener at EachSupport, Stitch Fastener at12" o.c. Between Supports(Typical at Corner Trim).

Girt (Typical)

Filler Trim, IFREQUIRED, AsNoted on ErectionDrawing WallSheeting Elevations

Inside Corner Trim

"REVERSE CLASSIC"Panel (Typical)

INSIDE CORNER DETAIL

Page 23: Nucor Building Systems - FOR FIELD USE PLEASE ......NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL 1.0 TABLE OF CONTENTS LAST REVISION DATE: 04-13-2007 BY: EGB CHK: RJF DETAIL

NUCOR BUILDING SYSTEMS WALL SHEETING ERECTION MANUAL

9.0 GENERAL NOTE

LAST REVISIONDATE: 3-31-2014BY: AES CHK:

DETAIL NAME IF APPLICABLEPAGE 23

9.0 GENERAL NOTES9.1 TRANSLUCENT PANEL

NBS 5’-4” translucent panels are to be used strictly in vertical wall applications. This panel is not to be installed in a roof application where fall hazards could occur. NBS assumes no responsibility for the misuse of this panel.

9.2 FRAMED OPENING TRIM INSTALLATION

See Erection Drawings for Framed Opening trim installation instructions.