46
NDM2 Series Molded Case Circuit Breaker Shanghai Liangxin Electrical CO., LTD. Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Post code: 200137 Tel: 86-21-50412789 Fax: 86-21-58675966 E-mail: [email protected] As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Be printed on ecological paper. 2010.12 2010 - Liangxin Electrical - All rights reserved

NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Embed Size (px)

Citation preview

Page 1: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

NDM2 SeriesMolded Case Circuit Breaker

Shanghai Liangxin Electrical CO., LTD.Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Post code: 200137Tel: 86-21-50412789Fax: 86-21-58675966E-mail: [email protected]

As standards, specifications and designs changefrom time to time, please ask for confirmationof the information given in this publication.

Be printed on ecological paper.

2010.12

2010

- L

iang

xin

Elec

tric

al -

All

righ

ts r

eser

ved

Page 2: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Application Scope

Application

Product FeaturesWorking ConditionModel and ImplicationTripping CharacteristicPower ConsumptionTemperature DeratingMain SpecificationsTripping CurveDimensionAccessory Accessory Code Auxiliary Contact Alarm Contact Undervoltage Release Shunt Release Mechanical Interlock Handle Padlocking Device Motor Operator Handle Operating MechanismSectional Area of Connecting Bus and CableUsage and MaintenanceOrdering Notice

030304050505060911222324252526272829313131

NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency switching of circuits and starting of motors in 50Hz/60Hz circuits with rated working voltage of 690V and rated current up to 800A. The breaker can provide overload, short circuit and undervoltage protection to the circuit and power equipment concerned.

Be widely used for protection for factory, building, household and similar installation.

NDM2 SeriesMolded Case Circuit Breaker

Leading Low-voltage Electrical Component Manufacturer

Summary

Page 3: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 04

ND M 2

7

10

13

Type C: Basic type

Type L: Standard type

Type M: Less high breaking type

Type H: High breaking type

No code: Direct handle operation

P: Motor operation

Z: Rotary handle operation

Please refer to Table 1

Model and Implication

Product Features

According to the level of the rated ultimate short-circuit breaking capacity, the breaker can be classified into four types. Type C (Basic type), Type L (Standard type), Type M (Less high breaking type) and Type H (High breaking type). The breaker possesses the features such as compactness, high breaking capacity, short arc over and short resistance etc.

The breaker can be installed vertically (upright) as well as horizontally (crosswise).

The breaker have disconnecting function. Its corresponding symbol is shown as :

The breaker meets the criterion IEC 60947-2, GB 14048.2-2001 and has TÜV, CE and CCC certificates.

Working Condition

Altitude: ≤2000m

Ambient temperature: -5℃~+40℃

Resisting the effects by humid air

Resisting effects by salt mist and oil mist

Please refer to Main Specifications Table

No code: Fixed type

P: With extended front terminations

JK: Frame type connection for leading-in terminal, front connection forleading-out terminal. (Only for NDM2-100 and NDM2-225)

CK: Front connection for leading-in terminal, frame type connection forleading-out terminal. (Only for NDM2-100 and NDM2-225)

K: Frame type connection for both leading-in and leading-out terminals.

(Only for NDM2-100 and NDM2-225)

H: Rear connection

Z1: Rear plug-in connection

Z2: Front plug-in connection

S1: With integrated handle padlocking device

S2: With split type handle padlocking device

Tilting angle: 22.5°

Service place without explosive media, gas and

dust which are corrosive and conductive

Be mounted free from rain and snow

M means "MCCB"

2

NDM2Brand name

No. Implication

98 1110 12

Please refer to Main Specification Table

13 14

No code: normal case X: Two-pole small case (only for frame size of 125A)

14

90: Frame only, without trip unit

2: Magnetic only

3: Thermal magnetic

11No code: Power distribution

2: Motor protection

8 3, 4

Brand code

Product code

Design code

Type code

Frame size

Grade of rated ultimate shortcircuit breaking capacity

Operation method

Number of poles

Trip unit

Accessory code

Application code

N-pole type of four pole product

Rated current

Connection type

12

A: N-pole is always close without overload release

B: N-pole is open or close together with other three poles andwithout overload release

C: N-pole is open or close together with other three poles andwith overload release

Page 4: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

05 06

Main Specifications

Outline

Type

Frame size Inm (A)

Rated current In (A)

Rated voltage Ue (AC V)

Rated insulation voltage Ui(AC V)

Rated ultimate breakingcapacity lcu(KA)

Rated operating shortcircuit breaking capacityIcs(kA)

Operating cycles (times)

OutlineDimen-sions

Arcover distance (mm)

Grade of rated ultimate shortcircuit breaking capacity

W H

400V

690V

400V

690V

charged

uncharged

L

W

H

Number of poles

Rated impulse withstand voltageUimp (V)

400 690 400 690 400400

33 3 4 3 33 4

HC L C LM M

3

10

25

19

8

26 38 38 64 19 3838

8

26

35 50 50 85 25 5035 50

10

78 92 122 92 12292

81.5 8668 8668

Weight (g)

3

L

25

19

73.5

849

4

50

38

103

1952 1257 1257 1493 14931900 1257 1257 1493 1900

0, ≤50

3

M

50

38

1464

0, ≤50

800

8000

400

200010000

135

NDM2-63

63

10, 12.5, 16, 20, 25,32, 40, 50, 63

800

8000

100002000

150

NDM2-100

100

16, 20, 25, 32, 40,50, 63, 80, 100

800

8000

15008500

150

0, ≤50

NDM2-125

125

16, 20, 25, 32, 40, 50,63, 80, 100, 125

Tripping Characteristic

Rated Currentof The Trip

Unit (A)

Thermal Trip Unit(Ambient Temperature 40℃) Tripping Current ofElectromagnetic

Trip Unit (A)

12In×(1±20%)

10In×(1±20%)5In×(1±20%)10In×(1±20%)

10In×(1±20%)

Remark

Motorprotection

type

Powerdistributionprotection

type

10≤In≤63

63<In≤100

100<In≤800

Tripping Time at1.30In(hot) (h)

1

2

2

2

Tripping Time at1.20In(hot) (h)

Non-tripping Time at1.05In(cold) (h)

1

2

2

2

Non-tripping Time at1.0In(cold) (h)10<In≤630

Power Consumption

Type

NDM2-63L/MDirect Heated (10~25A)

NDM2-100C/L/M/HDirect Heated (16~25A)

NDM2-63L/MIndirect Heated (32~63A)

NDM2-100C/L/M/HIndirect Heated (32~100A)

NDM2-125C/L/MIndirect Heated (125A)

NDM2-225C/L/M/HIndirect Heated (125~225A)

NDM2-250C/L/MIndirect Heated (250A)

NDM2-400C/L/M/HDirect Heated (225~400A)

NDM2-630C/L/M/HIndirect Heated (400~630A)

NDM2-800M/HIndirect Heated (630~800A)

Total Power Consumption of Three Poles (W)

Current (A)

25

25

63

100

125

225

250

400

630

800

Front/RearConnection

262

187

115

67

62

39

35

20

40

28

Rear Plug-inConnection

--

--

--

--

42

37

42

66

73

120

Front Plug-inConnection

32

45

24

40

43

70

73

125

200

--

> Measured under the relative rated current

Temperature Derating

NDM2-63

NDM2-100

NDM2-125

NDM2-225

NDM2-250

NDM2-400

NDM2-630

NDM2-800

+40℃ (MarineApplication+45℃)

+45℃(MarineApplication+50℃)

+50℃(MarineApplication+55℃)

+55℃(MarineApplication+60℃)

+60℃(MarineApplication+65℃)

Derating Coefficient (In)

1

1

1

1

1

1

1

1

0.94

0.96

0.96

0.94

0.94

0.95

0.94

0.94

0.88

0.91

0.91

0.94

0.94

0.89

0.88

0.87

0.81

0.85

0.85

0.9

0.9

0.82

0.82

0.8

0.74

0.78

0.78

0.86

0.86

0.75

0.76

0.72

Page 5: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

07 08

Main Specifications

W H

L

W

H

NDM2-800*NDM2-400

400 800

225, 250, 315, 350, 400 630, 700, 800

800 800

8000 8000

400 690 400 400 690 400 690 400

3 3 3 34 3 3 3 3 3 34

C L M H C L M H M H

4

35 50 65

15

65 100

26 38 49

11

49 75 26 38 49

11

49 75 755656

15

35 50 65

15

65 100 10075

20

75

10004000

5002500

257 280

150 198 150 182 240 210 280 210182

106.5 115.5

5420 5420 5420 7443 5420 7116 7116 7116 9929 7116 8526 11731 8526

0, ≤50

NDM2-630

630

400, 500, 630

800

8000

40001000

270

110

0, ≤100 0, ≤100

Main Specifications

W H

400V

690V

400V

690V

Charged

Uncharged

L

W

H

400 400

3 3 3 3 3 3 44 3

H

85

64

C CL LM M

25 35 50

10

50

19 26 38

8

38

25 35 50 50

38382619

NDM2-225

0, ≤50

225

100, 125, 140, 160,180, 200, 225

800

8000

165

15008500

NDM2-250

0, ≤50

250

125, 140, 160, 180,200, 225, 250

800

8000

165

15008500

142142 107107

86 103 86 103

107

2014 20142316 2990 2316 2014 2014 2316 2990

Outline

Type

Frame size Inm (A)

Rated current In(A)

Rated voltage Ue (AC V)

Rated insulation voltage Ui(AC V)

Rated ultimate breakingcapacity Icu (KA)

Rated operating shortcircuit breaking capacityIcs (kA)

Operating cycles (times)

Arcover distance (mm)

Grade of rated ultimate shortcircuit breaking capacity

Number of poles

Rated impulse withstand voltageUimp(V)

Weight (g)

OutlineDimen-sions

Outline

Type

Frame size Inm (A)

Rated current In (A)

Rated voltage Ue (AC V)

Rated insulation voltage Ui(AC V)

Rated ultimate breakingcapacity Icu (KA)

Rated operating shortcircuit breaking capacityIcs (kA)

Operating cycles (times)

Arcover distance (mm)

Grade of rated ultimate shortcircuit breaking capacity

Number of poles

Rated impulse withstand voltageUimp(V)

Weight (g)

OutlineDimen-sions

> * NDM2-800 4P MCCB is not available now

690 400 400690

10

8

16, 20, 25, 32,40, 50, 63, 80,100, 125

400V

690V

400V

690V

charged

uncharged

NDM2X-125

0, ≤50

125

800

8000

150

15008500

400

2

35

26

64

86

1060

Page 6: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

09 10

Tripping CurveNDM2-63 Current-temperature Characteristic NDM2-63L/M Tripping Curve

NDM2-100, NDM2-125, NDM2X-125Current-temperature Characteristic

NDM2-100C/L/M/H, NDM2- 125C/L/M, NDM2X-125Tripping Curve

NDM2-225C/L/M/H, NDM2-250C/L/M Tripping CurveNDM2-225, NDM2-250Current-temperature Characteristic

0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30 4050 6080100 200 300

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

0.01

0.005

0.0020.001

Rated current (100%)

Trip

ping

Tim

es t

/s

70 80 90 100 110 120 130 In%

60

50

40

30

20

10

0

NDM2-400 Current-temperature Characteristic NDM2-400C/L/M/H Tripping Curve

NDM2-630 Current-temperature Characteristic NDM2-630C/L/M/H Tripping Curve

70 80 90 100 110 120 130 In%

60

50

40

30

20

10

00.50.6 0.8 1 2 3 4 5 6 8 10 20 30 405060 80100 200 300

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.20.1

0.05

0.02

0.01

0.005

0.0020.001

Trip

ping

Tim

es t

/s

Rated current (100%)

NDM2-800 Current-temperature Characteristic NDM2-800M/H Tripping Curve

70 80 90 100 110 120 130 In%

60

50

40

30

20

10

0

0.50.6 0.8 1 2 3 4 5 6 8 10 20 30 40 5060 80100 200 300

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

0.01

0.005

0.0020.001

Trip

pin

g T

imes

t/s

Rated current (100%)

70 80 90 100 110 120 130 140 In%

60

50

40

30

20

10

0

70 80 90 100 110 120 130 In%

60

50

40

30

20

10

0

0.50.6 0.8 1 2 3 4 5 6 8 10 20 30 40 5060 80100 200 300

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

0.01

0.005

0.002

0.001

Rated current (100%)

Trip

pin

g T

imes

t/s

0.50.6 0.81 2 3 4 5 6 8 10 20 30 405060 80100 200 300

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

0.01

0.005

0.0020.001

Trip

ping

Tim

es t

/s

Rated current (100%)70 80 90 100 110 120 130 In%

60

50

40

30

20

10

0

0.50.6 0.8 1 2 3 4 5 6 8 10 20 30 405060 80100 200 300

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

0.01

0.005

0.0020.001

Trip

ping

Tim

es t

/s

Rated current (100%)

Page 7: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

11 12

NDM2-63L/M DimensionFront connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Rear connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

H1

H

7

6

X X

H2

Model

NDM2-63L

NDM2-63M

NDM2-63 4P

73.5

81.5

90.5

98.5

20.5

28.5

H H1 H2

X X

Y

Y

4(6)- 4.2

50(4P)25(3P)

117

Aperture dimensions of the subpanel,front connection

Aperture dimensions of the subpanel,rear connection

A

X

Y

Y

X

14

25(3P)

50(4P)

4.2

117

A direction 30

50

M10

7550

NDM2-63L/M DimensionRear plug-in connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

X-X, Y-Y is the centre of 3P MCCB

104(min)(4P)

4- Φ5.5

79(min)(3P)

90(m

ax)

60

28(m

in)

50(3P)

75(3P)X X

Y

Y

36

28

M5

100 91 117

26

43 insulating plate10

2

Front plug-in connection (3P)

Dimensions of plug-in base

118.3

94.3

22

14

7825

8-M5

21

103

75

50

26

17.5

23

4026

85

31

172 50

7

957

135

142

9

Y

X

Y

N

4- 3.5

Und

ervo

ltage

rel

ease

165

150

M510

50

M4

2

4- Φ5

60

50

X X

Y

Y

Page 8: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

13

NDM2-100C/L/M/H, NDM2-125C/L/M, NDM2X-125 DimensionFront connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Rear connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Type

NDM2-100C/L

NDM2-125C/L

NDM2-100M/H

NDM2-125M

NDM2-100 4P

NDM2-125 4P

69

87

86

104

H H1Aperture dimensions of the subpanel,front connection

Aperture dimensions of the subpanel,rear connection

X X

H1

H

24

6

7

Und

ervo

ltage

rel

ease

Y

Y

X X

N26

60

923015

8

24

125

90122

6-M8

M8

21

20

87.5

7.5

132

150

34.5

50

4- 4.5

Y

4(6)- 4.5

30(3P)

60(4P)

129X X

Y

A direction53

90 60

88

M8

A 3510

164

132

Y

Y

4

30(3P)

107

132X X

60(4P)

25

4.5

ф

NDM2-100C/L/M/H, NDM2-125C/L/M DimensionRear plug-in connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

X-X, Y-Y is the centre of 3P MCCB

Dimensions of plug-in base

Front plug-in connection (3P)

766450

17.5M8

132

92

4.5

M6

168

Y

Y

X X

125(min)(4P)

94(min)(3P)

60(3P)90(4P)

90(m

ax)

56

41(m

in)

4- 6.5

Y

Y

X X

94(min)

60

90(m

ax)

56

41(m

in)

4- 6.5

168

92

M6

3

36

5360

120

9

60

X

X

15

249

219

14

Extended front terminals(optional) NDM2X-125

2.6

31.5

5

27

3.6

26

4

Page 9: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

15 16

NDM2-225C/L/M/H, NDM2-250C/L/M DimensionFront connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Rear connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Rear plug-in connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

X-X, Y-Y is the centre of 3P MCCBFront plug-in connection (3P)

Model

103 127

86 110

H H1

NDM2-225C/L

NDM2-225M/H

NDM2-250M

NDM2-225 4P

NDM2-250 4P

NDM2-250C/L

10720

Extended front terminals (optional)

30

22.5

X

35

35

132.

510

2

36

144

165

10U

nder

-vol

tage

rel

ease

55126

Y

70Y

105

6-M8

21

142

M8

4-Φ5

H1

H

24

5

5.5

X

4(6)-Φ4.5

X

Y

Y

70(4P)

35(3P)

X 126

35(3P)

3

70(4P)

X

Φ25

126

144

Φ4.5Y

Y

X

A direction89

58

105

70

35

M1010

175

144

A

Dimensions of plug-in base

143.5

4

6658

41

M6

90

183

144

94M

6

6.5

5075.5

M817.5

145(min)(4P)

Y

XX

Y

110(min)(3P)

88(m

ax)

51(m

in)

70(3P)

105(4P)

4- Φ6.5

Y

X

Y

110(min)

88(m

ax)

54(m

in)

70

4- Φ6.5

x

x

20

70

276

252

Φ9

NDM2-225C/L/M/H, NDM2-250C/L/M Dimension

Aperture dimensions of the subpanel,rear connection

54

54

Page 10: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

17

NDM2-400C/L/M/H DimensionFront connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Rear connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

NDM2-400C/L/M/H DimensionRear plug-in connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

X-X, Y-Y is the centre of 3P MCCBFront plug-in connection (3P)

X

38

63.5

4.5

106.5

146.5

44

65

57

11

6-M10

21

96150144198

Y

N

Y

13 30

1543

100

41.5

174

194

Und

er-v

olta

ge r

elea

se

224

257

128 48

4389

11

Extended frontterminals

X X 194

Y

Y

4(6)- 6.5

44(3P)94(4P)

104.5

224

M10

A

42

83

144 96

A direction

44(3P)

8

194

224

94(4P)

Y

Y

X X

32

6.5

4- 7

106.5

21M10

8560

279 22

4

169

8.5

M8

200(min)(四极)152(min)(三极)

60(三极)108(四极)

58(m

in)

129

166(

max

)

Y

Y

X X4- 8.5

152(min)

60

58(m

in)

129

166(

max

)

Y

Y

X X4- 8.5

18389.576

51.5

6

M8

X

X

30

118

387

357

11

18

Dimensions of plug-in base

Aperture dimensions of the subpanel,front connection

Aperture dimensions of the subpanel,rear connection

Page 11: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

19

NDM2-630C/L/M/H Dimension Front connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

Rear connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

NDM2-630C/L/M/H DimensionRear plug-in connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

4- 7

58

46.5

14

270

234

Und

ervo

ltage

rel

ease

40

21

X

N

13

68

X

9.89

100

4318

465 43

48

65

69

Y

116

6-M12

182

240

10

Extended front terminals (Optional)

43

8

3.5

4.5

150

110

4(6)- 7

Y

Y

X X 200

58(3P)116(4P)

104.5

M10

A

234

A direction

42

68

174 11

6

6.5

40

8

200

234

Y

Y

X X

58(3P)

116(4P)

11092

60

21

12

M12

234

300 M

817

0

Y

Y

242(max)(四极)

185(min)(三极)

100(三极)

X X158(四极)

167(

max

)

123

68(m

in)

4- 8.5

20

Dimensions of plug-in base

155115.5

8

4.5

4.5

40

44

NDM2-800M/H Dimension

Y

Y

140(4P)70(3P)

X

4(6)- 7

X 243

1444Y

X88

89.5

24

64

85

28021014070

Y

XUnd

ervo

ltage

rel

ease

Extended frontterminals (Optional)

1532

67.5

280

8

243

N

X-X, Y-Y is the centre of 3P MCCBFront connection (3P, 4P)

Aperture dimensions of the subpanel,front connection

Aperture dimensions of the subpanel,front connection

Aperture dimensions of the subpanel,rear connection

Page 12: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

21

Rear connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

NDM2-800M/H Dimension Rear plug-in connection (3P, 4P) X-X, Y-Y is the centre of 3P MCCB

A 3712

M12

295

243

16

A Direction

84

62

13

140

Y

X X

Y100

213(min)

4- 11.5

175

123

65(m

in)

ф

11272

30

123

M14

M10

243

62

302

Dimension of plug-in base

Rear plug-in connection version is not available for 700A and 800A NDM2-800 series MCCB currently.

22

48

4(6)- 7

≥3

243

Y

Y

X X

70(3P)

140(4P)

140(3P)210(4P)

Table 1 Accessory Code

00

10

20

21

30

41

50

60

61

62

40

70

71

08

18

38

48

58

68

78

28

Code

No accessory

Shunt Release

Double Auxiliary Contacts

Single Auxiliary Contact

Undervoltage Release

Shunt Release and SingleAuxiliary Contact

Shunt Release andUndervoltage Release

Two Sets Double AuxiliaryContacts

Two Sets Single AuxiliaryContact

Double Auxiliary Contacts andSingle Auxiliary Contact

Shunt Release and DoubleAuxiliary Contacts

Undervoltage Release andDouble Auxiliary Contacts

Undervoltage Release and SingleAuxiliary Contact

Alarm Contact

Shunt Release and AlarmContact

Undervoltage Release and Alarm Contact

Shunt release, Single AuxiliaryContact and Alarm Contact

Single Auxiliary andAlarm Contact

Double Auxiliary Contact, Single Auxiliary Contact

and Alarm Contact

Undervoltage Release, Single Auxiliary Contact

and Alarm Contact

Double Auxiliary Contactsand Alarm Contact

Name

MountingPosition

Type

3 4 2 3 4 3 4 3 4

NDM2-63

NDM2-100NDM2-125NDM2-225NDM2-250

NDM2X-125 NDM2-400NDM2-630 NDM2-800

Numberof Pole

Accessory Code

Handle

Left mounting Right mounting

Single auxiliary contact

Double auxiliary contacts

Alarm contact

Shunt Release

Undervoltage release

Legends

> * Single auxiliary contact and alarm contact (left) + single auxiliary contact (right) can be supplied for NDM2-63

Aperture dimensions of the subpanel,rear connection

NDM2-800M/H Dimension

Note*

Page 13: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

23 24

Auxiliary ContactAuxiliary Contact and Its Combination

Breaker in position"OPEN" or "FREE TRIP”

Breaker in position"CLOSED"

Double auxiliarycontacts

Single auxiliarycontact

From "CLOSED" to "OPEN"; From "OPEN"to "CLOSE".

F14F11F12

F14F11F12

F21F24F22

Specifications of Auxiliary Contact1> Current Parameters

3A

Conventional Thermal Current Ith

3A

Rated Current at AC 400V

0.30A

0.40A

Frame Size

Inm≤225

Inm>225

2> Electrical Endurance of Auxiliary Contact

UtilisationCategory

Making BreakingTimes Duration under

Current

OperatingFrequency(times/h)

36060506Pe

0.3

6Pe

0.3

I/Ie U/UeI/Ie U/Ue

1

1

1

1

110AC-15

DC-13 11

cosφcosφ

≥T0.95

≥0.05s

UtilisationCategory

Making BreakingTimes Duration under

Current

OperatingFrequency(times/h)

120106Pe

0.3

6Pe

0.3

I/Ie U/UeI/Ie U/Ue

1.1

1.1

1.0

1.1

1.110AC-15

DC-13 1.11.1

cosφcosφ

≥T0.95

≥0.05s

3> Making and Breaking Capacity of Auxiliary Contact

Wiring Schematic of Auxiliary Contact

F11F14

Power Supply

Turned-onloop

Turned-offloopF12

Alarm Contact

Breaker in the position"OPEN", "CLOSED"

Breaker in the position"FREE TRIP"

Alarm contact Ue=220V, Ith=3A

B11

B11

B14

B12

B11

B14B12

B14B12

Alarm Contact and Its Combination

Wiring Schematic of Alarm Contact

When breaker is open or closed normally ,the contact is

not actuated. Only after tripping or breaking due to

defect, the position of the contact will be changed from

permanently open to closed or permanently closed to

open. The contact resets when breaker re-latches.

Page 14: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

25

Undervoltage Release

Control voltage: AC 50Hz 230V110VDC

400V220V

Between 35%~70% of rated control voltage, undervoltage release should operate in security and trip breaker. When under 35% of rated voltage, it should prevent breaker from closing. Breaker closing is possible only if the power supply voltage is no less than 85% of rated voltage.

Note: Only undervoltage release be charged in advance, breaker can be closed or re-latches.

Shunt Release

Control voltage: AC 50Hz 230V24VDC

400V220V

K

A1 A 2

Power supply

Power supplyA A

kA

kA K

DC24V 1 2

Shunt release is usually installed in A phase of breaker. Between 70%~110% of rated control voltage, shunt release should trip breaker in security under any operating conditions.

Note: Below shunt controlling loop design is recommended when the power of the controlling loop is DC 24V.

KA stands for the relay in DC 24V controlling loop. The current capacity of its contract is 1A.

NDM2-63

NDM2-100

NDM2-225

NDM2-400

NDM2-630

NDM2-800

Product type Instantaneous current (A) Power consumption (W)

Instantaneous Tripping Current and Power Consumption of Shunt Release

0.28

0.288

0.313

0.197

0.199

0.538

0.434

0.425

0.412

0.325

0.314

0.898

0.341

0.341

0.341

0.4

0.4

1.134

91.6

96.8

112

67

68

163

76.1

73

68.8

62.3

58.2

153

90.7

90.7

90.7

94.4

94.4

96.2

91.2

85.3

100

100

120

4

4

3.87

3.87

3.87

5.22

AC 400V AC 230V AC 400V AC 230VDC 220V DC 24V DC 24VDC 220V

A Switch B Switch

A1A

A1A

ON

L

C

B

OFF

D

Dimension

A A1 B C D L HProduct type

NDM2-63 3P

NDM2-100 3P

NDM2-125 3P

Note

For NDM2-630 4P

For NDM2-400 4P

For NDM2-250 4P

For NDM2-225 4P

For NDM2-125 4P

For NDM2-100 4P

For NDM2-63 4P

For NDM2-800M/H

For NDM2-630C/L/M/H

For NDM2-400C/L/M/H

For NDM2-250C/L/M/

For NDM2-225C/L/M/H

For NDM2-125C/L/M

For NDM2-100C/L/M/H

For NDM2-63L/M

For NDM2-800 4P

NDM2-225 3P

NDM2-250 3P

NDM2-400 3P

NDM2-630 3P

NDM2-800 3P

NDM2-63 4P

NDM2-100 4P

NDM2-125 4P

NDM2-225 4P

NDM2-250 4P

NDM2-400 4P

NDM2-630 4P

NDM2-800 4P

78

92

92

107

107

150

182

210

103

122

122

142

142

198

240

280

102

120

120

135

135

180

235

243

132

152

152

173

173

230

295

310

38

50

50

50

50

60

60

60

38

50

50

50

50

60

60

60

22

22

22

22

22

30

28

30

22

22

22

22

22

28

30

30

118

118

118

135

135

175

198

230

125

150

150

168

168

188

240

300

13

11.5

11.5

14

14

18

16

18

13

11.5

11.5

9

9

16

12

29.5

Wiring Schematic of Shunt Release

Wiring Schematic ofUndervoltage Release

26

Mechanical Interlock

P1 P2

Power supply

Instantaneous Tripping Current and Power Consumption of Undervoltage Release

NDM2-63

NDM2-100

NDM2-225

NDM2-400

NDM2-630

NDM2-800

Product type AC 400V

10

9.75

10.88

9

8.5

5

Instantaneous Tripping Current (mA) Power Consumption (W)

13.5

14.25

14.75

11

11

7.25

AC 230V

1.6675

2.53

2.53

3.392

3.22753.105

AC 230V

4

3.95

4.352

3.6 3.4

2

AC 400V

Page 15: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

2827

Handle Padlocking Device

MS1 is integral handle padlocking device designed to avoid being opened or closed by mistake. It is now available only with NDM2-100, NDM2-125, NDM2-160, NDM2-225, NDM2-250 . Please refer to below table for installation dimension (breaker is showed in dashed frame)

w HH1

H2

L1 L

Dimension

Product type

MS1-100C/L, MS1-125C/L

W

42

52

55

66

L

9

9

L1

24

26

H H1

4

499

82

81.5

H2

62

MS1-100M/H, MS1-125M

MS1-225C/L, MS1-250C/L

MS1-225M/H, MS1-250M

Mounting Diagram of MS2 Handle Padlocking Device

MS2 is split handle padlocking device for NDM2 series MCCB designed to avoid being opened or closed by mistake. Breaker is showed in dashed frame in below diagram.

Lock

60

17.3

φ3.5

48.2

Handle

MS2 Lock

Motor Operator

X

M

Power

Input power

SB1(ON)

SB2(OFF)

Control circuit

P1 P2 S1 S2 S4

Code illustration:SB1, SB2: Operation button (prepared by user)X: Wiring terminalP1, P2: Input power

Voltage:AC 50Hz 110V, 230V; DC24V, 110V, 220V

Mounting Diagram of MS1 Handle Padlocking Device

Specifications of CD2 Motor Operator

Product Type

NDM2-63

NDM2-100, NDM2-125

NDM2-225, NDM2-250

NDM2-400

NDM2-630

NDM2-800

Tripping Current (A)

≤0.5

≤0.5

≤0.5

≤2

≤2

≤2

Motor Power (W)

14

14

14

35

35

35

Endurance

14000

14000

10000

5000

5000

5000

Operation DeviceHeight (mm)

90.5

89.5

92

142

153

146

CD2 Motor OperatorWiring Schematic

External accessory wiring diagram is showed indashed frame

CD2 Motor Operator

Page 16: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

29 30

Cutouts Sketch Map for Installation of CS1-A Handle Operating Mechanism

> Type A means rounded handle Type F means quadrate handle

> Note: The dimension for "D", which can be done according to the customer's requirement, is 150mm usually.

B H20

24

DMIN=50mm

66 o

r 96

53

X

Breaker

X XA2- 5.5

36

45

93

93

73 o

r 10

5

Y H

D

65

8

20

65

X

MIN=50mm

X

4- 4.5

42

A

66 o

r 96

YB

H

D24

MIN=50mm

16 B

Y

Y

≥200Hinge X

A

53

X X

36

45

2- 5.5

73 o

r 10

5

Y

B

A

H

16

D

8

Breaker MIN=50mm

65

B

65

Y

X

A ≥ 200mm

Hingeaxis

XX

42

4- 4.5

Handle Operating Mechanism Handle Operating Mechanism

Cutouts Sketch Map for Installation of CS1-F Handle Operating Mechanism

Cutouts Sketch Map for Installation of CS2-A Handle Operating Mechanism

Installation Method and Dimensions

HandleOperating

Mechanism

Model of ExternalAccessories

External Accessories

Manual Installation Dimensions (mm)

Vertical

InstallationMethod

Horizontal

Vertical

Horizontal

Vertical

Horizontal

Vertical

CS1-63

CS1-100

CS1-225

CS1-400

CS1-630

CS1-800

CS2-100

CS2-100

CS2-225

CS2-225

CS2-400

CS2-630

CS2-800

25

30

35

138

168

198

11.5

11.5

31

32

15

15

15

B

100

104

143

194

200

87.5

35

37

35

45

65

60

48

A

Metal

49

49

55

76

83

63

46

46

48

48

61

61

66

Plastic

/

69

72

110

110

/

/

/

/

/

/

/

/

H

/

/

/

/

/

/

/

/

/

/

/

/

/

BMatching MCCB

NDM2-63 L / M

NDM2-100, 125 C / L / M / H

NDM2-225, 250 C / L / M / H

NDM2-400 C / L / M / H

NDM2-630 C / L / M / H

NDM2-800 M / H

NDM2-100, 125 C / L / M / H

NDM2-100, 125 C / L / M / H

NDM2-225, 250 C / L / M / H

NDM2-225, 250 C / L / M / H

NDM2-400 C / L / M / H

NDM2-630 C / L / M / H

NDM2-800 M / H

Cutouts Sketch Map for Installation of CS2-F Handle Operating Mechanism

/

/

/

/

/

/

/

/

/

/

/

/

/

A

Page 17: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

31 32

Selection of Connecting Bus

2

2

2

Quantity

Sectional Area of Cable

Sectional Areaof Cable (mm2) Quantity

Dimension of Copper Bar

Rated current A

Sectional Area ofConnecting Wire (mm2)

Dimension(mm2)

500

630

700,800

2

2

2

30×5

40×5

50×5

1012.5

1620 25 32 40

50 63 80 100 125140 160

180200225

250 315350 400

1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 185 240

150

185

240

Sectional Area of Connecting Bus and Cable

Usage and Maintennce

Selection of Cable

Rated Current (A)

Do not adjust the characteristic and accessories of the breaker, which handle by the

manufacturer.

The handle of the breaker can be placed in three positions, which represent CLOSED, OPEN

and FREE TRIP individually. When the handle is in the position of FREE TRIP, it should be

turned in direction of OPEN at this moment. Then the breaker can be re-latch and closed.

The user should conform to the regulations of the storage and application. Within 18

months after delivery from the manufacturer, if the product can not work properly or be

damaged because of the quality defect, the manufacturer is responsible for changing or

repairing without charge.

The model, specification and order quantity of the breaker should be noted. When using

undervoltage release, shunt release or motor operator, please give clear indication of

operation voltage or the value of control power voltage.

For example: NDM2-100L with undervoltage release and single auxiliary contact;

before-plate wiring type; Rated current 80A; Control voltage 220V; Quantity: 10 PCS. Then

you can order as following:

NDM2-100L/3371-H 80A 220V 10PCS

It should be declared, when the ambient temperature meets the following situation: Upper

limit over +40℃ or lower limited below -5℃.

Ordering Notice

Page 18: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Shanghai Liangxin Electrical CO.,LTDAddress: No. 668 Heng An Road, Pu Dong New District, Shanghai Post code: 200137Tel: 86-21-50412789Fax: 86-21-58675966E-mail: [email protected]

As standards, specifications and designs changefrom time to time, please ask for confirmationof the information given in this publication.

NDM2E Series Electronic Molded Case Circuit Breaker

201

0 -

Lian

gxin

Ele

ctri

cal -

All

righ

ts r

eser

ved

2010.11

Page 19: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Summary

General Information

Model and Implication

Working and Installation Condition

Main Specifications

Intelligent Controller

Accessory

Accessory Code

Motor Operator

Handle Operating Mechanism

Power Consumption

Sectional Area of Connecting Bus and Cable

Dimension

Mechanical Interlock

Ordering Notice

03

06

07

08

09

12

16

18

19

20

20

20

21

30

31

Leading• Low-voltage• Electrical• Component• Manufacturer

NDM2E Series Electronic Molded Case Circuit Breaker

Page 20: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 04

Summary Product Features

New Generation Product

Application

Low-voltage distribution protection.

Motor protection.

Control broard protection.

Power transition system.

Various Models

3 poles

Fixed type, plug-in type.

Complete range of accessories.

3-segment protection functions

The breaker can provide protection functions against overload, short-circuit with delayed trip and short-circuit with

instantaneous trip. It can be adjusted by customers according to the load current.

Self-power

Intellectual controller is powered by circuit breaker itself.

Pre-alarm indication

LED "Alarm" on the panel flashes and then lights solid when the actual current reaches or exceeds pre-alarm tripping

threshold Ip.

Overload indication

LED "Over" lights solid when the load current exceeds long-time overload tripping threshold.

Instantaneous tripping function at large current

Breaker is tripped directly by electromagnetic trip unit when there is large current (≥20Inm) during operation.

Interchange ability with NDM2 series MCCB

Same frame size have the same dimensions as NDM2 series MCCB. (The dimensions of frame size 630 and 800 are the same).

NDM2E Series Electronic Molded Case Circuit Breaker(hereinafter "breaker") is suitable for

in-frequency switching of circuits and starting of motors in 50Hz circuits with rated insulation voltage

of 800V, rated working voltage of 400V and rated current up to 1200A. The breaker can provide

overload, short circuit and undervoltage protection to the circuit and power equipment concerned.

Page 21: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

05 06

General InformationAccessory In Common

Accessory Chart

Auxiliary contact. Standards

Pollution Degree

Ambient Temperature

NDM2E series electronic MCCB and accessories comply with following standards:

IEC60947-1, GB14048.1-2006.

IEC60947-2, GB14048.2-2008.

Pollution degree III for industrial environment.

Environmental Protection

NDM2E series electronic molded case circuit breakers take into

account concerns for environmental protection. Most components

are recyclable.

Isolation Function

The isolation function of breaker should comply with standard

IEC60947-2 (GB14048.2-2008):

Isolating position is corresponding to “O”(Position OFF).

Operating handle indicates“OFF”only when contact really breaks.

Reliability is not affected by rotary handle opearating meachanism

or motor operator.

Isolation protection:

Contact to show mechanical reliability.

No current leakage.

Over-voltage withstand ability between termianals in and out.

Ambient temperature ranges -25℃~+55℃. Decrease of capacity s

hould be considered when the temperature surpasses 40℃

(65℃ for motor protection).

Long-term working in general enviroment.

Storage temperature: -35℃~+85℃.

Selectivity

Total selectivity can be realized between two NDM2E series MCCBs

or between NDM2E series MCCB and other MCCB produced by Nader.

Alarm contact.

Undervoltage release.

Shunt release.

Handle operating mechanism.

Motor operator.

Terminal cover

Rear plug-in connection kit

Rear connection kit

Undervoltage release

Undervoltage release

Padlocking device

Motor operator

Handle operating mechanism

Space baffleExtended front termination kits

Shunt release

Alarm contact

Alarm contact

Singleauxiliary contact

Single auxiliary & alarm contact

Doubleauxiliary contacts

Shunt release

Single auxiliary contact

Single auxiliary & alarm contact

Double auxiliary contacts

Characteristics in nameplate:

Inm :Frame size

Ue :Rated working voltage

Ir :Setting current

Ui :Rated insulation voltage

Uimp:Rated impulse withstand voltage

Cat. :Utilization category

Icw :Short-time withstand current

Icu :Rated utimate breaking capacity

Ics :Rated operation breaking capacity

Pole :Number of poles

:With isolation function

NDM2E-250H

Page 22: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

07 08

Working and Installation Condition

NDM2E series MCCB can be mounted either in horizontal or vertical position without undergoing any derating

of their rated characteristics. But it can be supplied only from the top.

Installation Method

III for main circuit, II for auxiliary circuit and control circuit.

Installation Classification

Ambient temperature: -35℃~ +85℃.

Relative humidity: ≤95% at the temperature of +25℃.

Storage Condition

Altitude:≤2000m

Ambient temperature: -25℃~ +55℃ and its average over a period of 24h does not exceed +55℃.

The relative humidity of the air does not exceed 50% at the maximum temperature of +40℃. The average lowest

temperature does not exceed +25℃ and the average maximum relative humidity does not exceed 90% in the moistest

month. Special measures may be necessary in cases of occasional condensation due to variations in temperature.

Service place without explosive media, gas and dust which are corrosive and conductive.

No installing in particularly humid places.

External maghetic field should be 5 times smaller than geomagnetic field.

Be mounted free from rain and snow.

Working and Installation Condition

Vertical installation Horizontal installation

No code: Power distribution 2:Motor protection

H:High breaking type

2 E

Electronic type E

NDM2E

10

10

ImplicationNo.

Product code

Brand code

Design code

Frame size

M MCCB

Grade of rated ultimate short circuit breaking capacity

Operation method

Number of poles

Accessory code

Application code

No code: Direct handle operation

P: Motor operation Z: Rotary handle operation

Please refer to Table 18

Model and Implication

Page 23: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

09 10

Main Specifications

Main Specifications

Type

Number of poles

Electrical characteristics as per

Frame size (A) Inm

Rated insulation voltage (V) Ui

Rated impulse withstand voltage (kV) Uimp

Rated voltage (V) Ue AC50Hz

Grade of rated ultimate breaking capacity

Rated ultimate breaking capacity(kA) Icu AC400V

Rated service breaking capacity (kA) Ics AC400V

Utilisation category

Short-time withstand current (kA rms/sec.) Icw

Suitability for isolation

Durability (times)

Overload protection

Setting current of intelligent trip unit (A) Ir

Installation and connection

Fixed/Front connection

Fixed/Rear connection

Plug-in (on base)

Interphase barriers

Nameplate

Rotary handle

Dimensions(mm) W×H×D

Arcover distance (mm)

NDM2E-100

3

100

800

8

400

H

85

50

A

/

8000

20000

40000

40, 50, 63, 70,80, 90, 100

Electrical

Mechanical

3 poles, fixed-type

Without maintenanceWith maintenance

Without maintenanceWith maintenance

92×150×92

≤50

■■■■■■

NDM2E-250

3

250

800

8

400

H

85

50

A

/

8000

20000

40000

100, 125, 160, 180, 200, 225, 250

IEC60947-2:2006, GB14048.2-2008

107×165×90

≤50

■■■■■■

With this function■

Type

Number of poles

Electrical characteristics as per

Frame size (A) Inm

Rated insulation voltage (V) Ui

Rated impulse withstand voltage (kV) Uimp

Rated voltage (V) Ue AC50Hz

Grade of rated ultimate breaking capacity

Rated ultimate breaking capacity(kA) Icu AC400V

Rated service breaking capacity (kA) Ics AC400V

Utilisation category

Short-time withstand current (kA rms/sec.) Icw

Suitability for isolation

Durability (times)

Overload protection

Setting current of intelligent trip unit (A) Ir

Installation and connection

Fixed/Front connection

Fixed/Rear connection

Plug-in (on base)

Interphase barriers

Nameplate

Rotary handle

Dimensions(mm)W×H×D

Arcover distance(mm)

Electrical

Mechanical

3 poles, fixed-type

NDM2E-400

3

400

800

8

400

H

100

65

B

5

7500

10000

20000

200, 225, 250,

280, 315, 350,

400

■■■■■■

NDM2E-630

3

IEC60947-2:2006, GB14048.2-2008

630

800

8

400

H

100

65

B

8

7500

10000

20000

280, 315, 350,

400, 450, 500,

550, 600, 630

■■■■■■

NDM2E-800

3

800

800

8

400

H

100

65

B

10

7500

10000

20000

400, 450, 500,

550, 600, 630,

700, 750, 800

■■■■■■

With this function■

150×257×106.5

≤50

210×280×115.5

≤100

210×280×115.5

≤100

Page 24: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

11 12

Type

Number of poles

Electrical characteristics as per

Frame size (A) Inm

Rated insulation voltage (V) Ui

Rated impulse withstand voltage (kV) Uimp

Rated voltage (V) Ue AC50Hz

Grade of rated ultimate breaking capacity

Rated ultimate breaking capacity(kA) Icu AC400V

Rated service breaking capacity (kA) Ics AC400V

Utilisation category

Short-time withstand current (kA rms/sec.) Icw

Suitability for isolation

Durability (times)

Overload protection

Setting current of intelligent trip unit (A) Ir

Installation and connection

Fixed/Front connection

Fixed/Rear connection

Plug-in (on base)

Interphase barriers

Nameplate

Rotary handle

Dimensions(mm) W×H×D

Arcover distance(mm)

NDM2E-1000

3

1000

750

8

400

H

75

56.25

A

/

500

2500

5000

505, 535, 565, 600,630, 640, 680, 720,760, 800, 850, 900,

950, 1000

/

/

/

3 poles, fixed-type 210×370×110

≤100

■■

NDM2E-1200

3

1200

750

8

400

H

75

56.25

A

/

500

2500

5000

605, 645, 680, 720,755, 770, 815, 865,910, 960, 1020, 1080,

1140, 1200

/

/

/

210×370×110

≤100

■■

With this function■

Intelligent Trip Unit

7 1 2 3 4 5 6

8 9

Note: The above photograph only indicates setting values on the panel of NDM2E-250H series MCCB. For other frame size,

please refer to Table 1.

T

Protection

Other functions

1. Long-time overload protection, adjustable setting current Ir.

2. Long-time overload protection, adjustable tripping time Tr with

four settings.

3. Short-time short-circuit protection, adjustable threshold Is with

ten settings.

4. Short-time short-circuit protection, adjustable time delay Ts with

four settings.

5. Instantaneous short-circuit protection, adjustable threshold Ii with

ten settings.

6. Pre-alarm, adjustable threshold Ip with four settings.

7. Testing part, connectd to specific testing machine of NDM2E, also can be

connected to PC for online program, test and real-time check of carrent change.

8. Pre-alarm indication. When the actual current exceeds setting value of Ip,

the indicator flashes. After a certain period, the indicator lights solid.

9. Overload indication. Solid lighting means actual current is over 1.5 times

of setting value of Ir. Circuit breaker is overloaded and will be tripped

after a certain period.

① Tripping threshold for long-time overload protection

② Tripping time for long-time overload protection

③ Tripping threshold for short-time short-circuit protection

④ Tripping time for short-time short-circuit protection

⑤ Tripping threshold for instantaneous short-circuit protection

⑥ Tripping threshold of instantaneous override

⑦ Setting threshold for pre-alarm

IEC60947-2:2006, GB14048.2-2008

Main Specifications

Electrical

MechanicalWithout maintenanceWith maintenance

2E2E

Page 25: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

13 14

NDM2E-100

NDM2E-250

NDM2E-400

NDM2E-630

NDM2E-800

NDM2E-1000

NDM2E-1200

12, 60, 80, 100

12, 60, 80, 100

12, 60, 100, 150

12, 60, 100, 150

12, 60, 100, 150

5, 10, 15, 20, 30

5, 10, 15, 20, 30

Ir(A)

Parameters of Setting Current and Tripping Time

Tr(S)Frame Size

100

250

400

630

800

1000

1200

Table 1 Available Setting Values of Intelligent Trip Unit

40, 50, 63, 70, 80, 90, 100, OFF

100, 125, 160, 180, 200, 225, 250, OFF

200, 225, 250, 280, 315, 350, 400, OFF

280, 315, 350, 400, 450, 500, 550, 600, 630, OFF

400, 450, 500, 550, 600, 630, 700, 750, 800, OFF

505, 535, 565, 600, 630, 640, 680, 720, 760, 800, 850, 900, 950, 1000

605, 645, 680, 720, 755, 770, 815, 865, 910, 960, 1020, 1080, 1140, 1200

NDM2E-100

NDM2E-250

NDM2E-400

NDM2E-630

NDM2E-800

NDM2E-1000

NDM2E-1200

Is(×Ir) Ts(s)Frame Size

100

250

400

630

800

1000

1200

0.06, 0.1, 0.2, 0.3

0.06, 0.1, 0.2, 0.3

0.06, 0.1, 0.2, 0.3

0.06, 0.1, 0.2, 0.3

0.06, 0.1, 0.2, 0.3

0.1, 0.2, 0.3

0.1, 0.2, 0.3

Type

Table 1 Available Setting Values of Intelligent Trip Unit (Continued)

2, 3, 4, 5, 6, 7, 8, 10, OFF

2, 3, 4, 5, 6, 7, 8, 10, OFF

2, 3, 4, 5, 6, 7, 8, 10,OFF

2, 3, 4, 5, 6, 7, 8, 10, OFF

2, 3, 4, 5, 6, 7, 8, 10, OFF

2, 4, 6, 8, 10

2, 4, 6, 8, 10

Type

Parameters of Tripping Threshold and Time

NDM2E-100

NDM2E-250

NDM2E-400

NDM2E-630

NDM2E-800

NDM2E-1000

NDM2E-1200

100

250

400

630

800

1000

1200

3, 4, 5, 6.3, 7, 8, 9, 10, 12

3, 4, 5, 6.4, 7.2, 8, 9, 10, 12

3, 4, 5, 6, 7, 8, 9, 10, 12, 14

3, 4, 5, 6, 7, 8, 9, 10, 12, 14

3, 4, 5, 6, 7, 8, 9, 10, 12, 14

3, 6, 8, 10, 12

3, 6, 8, 10, 12

0.7, 0.8, 0.9, 1.0

0.7, 0.8, 0.9, 1.0

0.7, 0.8, 0.9, 1.0

0.7, 0.8, 0.9, 1.0

0.7, 0.8, 0.9, 1.0

0.9

0.9

Ii(×Inm) Ip(×Ir)Frame SizeType

Table 1 Available Setting Values of Intelligent Trip Unit (Continued)

Characteristics of Trip Unit

Tripping Curves of Trip Unit

Parameters of Tripping Threshold and Time

Provide protection functions against overload with inverse long time delay, short-circuit with inverse short-time delay, short-circuit

with definite short-time delay, short-circuit with instantaneous trip, etc.

Protection characteristics can be set by customers.

4ht

2h

1h

30min20min14min10min6min4min

2min

1min

30sec20sec

10sec

5sec

2sec

1sec

0.5sec

0.2sec

0.1sec

0.05sec

0.02sec

0.01sec

0.6 0.7 1 2 3 4 5 6 7 10 12 14 20 30 401.3

(×Ir)

Tripping threshold for instantaneous short-circuit protection Ii(3-14)Inm±15%

Max. tripping time for instantaneous short-circuit protection

Tripping threshold for short-time short-circuit protection Is(2-10)Ir

Tripping time for short-time short-circuit protection ts(±15%)(s)

Tripping threshold for long-time overload protection 2×IrTripping time for long-time overload protection tr(12-150)s±10%

150s100s80s60s

0.30.2

0.1

0.06

12sNote: For NDM2E-1000, NDM2E-1200, based current Io=1×Inm (Setting Value), Ir=(×Io).

Page 26: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

15 16

Long-time Overload Protection Ir, Tr

Protection Characteristics of Intelligent Trip Unit

Setting Current Ir

Tripping

Characteristics

(Inverse Time)

Tolerance <±10%>

Setting Value of Tr (s)

Inm=100、250A

12

>2h Non-tripping

<1h Tripping

60 80 100 12 60 100 150 5 10 15 20 30

21.3 106.7 142.2 177.8 21.3 106.7 177.8 266.7 80 160 240 320 480

12 60 80 100 12 60 100 150 45 90 135 180 270

0.93 4.63 6.17 7.72

±10

Setting value of base current

±20

0.93 4.63 7.72 11.57 3.5 7.0 10.5 14 21

Inm=400、630、800A Inm=1000、1200A

≤1.05Ir

>1.30Ir

At 1.5Ir, tr (s)

At 2.0Ir, tr (s)

At 7.2Ir, tr (s)

Tolerance (%)

Note: 1. Tripping curve is according to tr=(2Ir)2×Tr/I2 [when Inm=1000 or 1200, tr=(6Ir)2×Tr/I2]

tr: Tripping time for long-time overload protection

Tr: Setting tripping time for long-time overload protection I:Actual current

Ir: Setting current for long-time overload protection

2. Setting current for long-time overload protection Ir of different frame size can be found in Table 1.

Short-time Short-circuit Protection Is, Ts

Setting Tripping Threshold Is

Tripping

Characteristics

Tolerance <±10%>

Inverse Time(I2t=constant)

Is≤I<1.5Is

Definite Time1.5Is≤I<Ii

ts=(1.5Is)2×Tr/I2

±15 ±20, I2t=const OFF

ts=(8Is)2×Tr/I2, I2t=const ON

0.06 0.1 0.2 0.3

0.06

/

0.1

/

0.2

0.14

0.3

0.21

0.1 0.2 0.3

0.1

/

0.2

0.14

0.3

0.21

Setting Value of Ts (s)

Tripping Time (s) ts

Tripping Time (s) ts

Returnable Time (s)

Tolerance (%)

Note: 1. Inverse time: I2t=const ON; Definite time: I2t=const OFF

2. Inverse short-time delay tripping curve is according to ts=(1.5Is)2×Ts/I2

When Inm=1000 or 1200, ts=(8Ir)2×Ts/I2.

ts: Tripping time for short-time short-circuit protection

Ts: Setting tripping time for short-time short-circuit protection

I: Actual current Is: Setting tripping threshold for short-time short-circuit protection

3. Setting tripping threshold for short-time short-circuit protection Is of different frame

size can be found in Table 2.

Setting Tripping Threshold Ii

Tripping Time

Tolerance <±15%>

<50ms

Tripping

Characteristics

Instantaneous Short-circuit Protection Ii

NDM2E-100

NDM2E-250

NDM2E-400

NDM2E-630

NDM2E-800

NDM2E-1000

NDM2E-1200

AC230V

2.6

3.8

3.7

2.5

2.5

2.53

2.53

AC400V

3.3

3.3

2.7

2.8

2.8

2.8

2.8

Power Consumption (W)Breaker Type

Pre-alarm Indicator

Tolerance(%)

Setting Threshold Ip

Characteristics

Tolerance <±10%>

Pre-alarm Function Ip

Characteristics

1.15×Ir

Lighting solid

±10

Current Range

Overload Indicator

Tolerance (%)

Overload Indications (Peak Load)Note: Setting tripping threshold for instantaneous short-circuit

protection Ii of different frame size can be found in Table 1.

Accessory

Undervoltage Release

Table2 Power Consumption of Undervoltage Release

Shunt Release

Connect the power according to wiring terminal code of outside-hanging undervoltage release.

Voltage: AC 50Hz 230V 400V

Trips breaker when the voltage is between 35% and 75% of rated voltage.

Prevent breaker from closing when the voltage is under 35%

of rated voltage.

Breaker closing is possible only if the voltage is between 85% and 110% of rated voltage.

Note:Only undervoltage release be charged is advance, break can be closed or re-latches.

Connect the power according to the leading-out wire code. (It doesn't

matter if it's +/- of DC power).

Voltage: AC230V, 400V; DC 220V, 24V

Trips breaker reliably when control voltage is between 70% and

110% of its rated voltage.

Wiring Schematic of Undervoltage Release (Internal

accessory wiring schematic is shown in dashed frame).

Power Supply

Power Supply

C Type

Power Supply

Note: X is wiring terminals.

Wiring Schematic of Shunt Release (Internal accessory

wiring schematic is shown in dashed frame.)

K: Micro switch inside shunt release. It is connected with coil in series and normally closed. When breaker trips, the micro switch turn to open. When breaker is closed, the micro switch turn to closed. Note:Below shunt controlling loop design is recommendedwhen the power of the controlling loop is DC 24V.

KA:Stands for the relay in DC 24V controlling loop.

The current capacity of its contact is 1A.

X

From flash to lighting solid

±10

NDM2ENote:

Page 27: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Table 3 Electrical Characteristics of Auxiliary Switch

17 18

Accessory (Continued)

Auxiliary Switch

Accessory Code

Auxiliary contact

Alarm contact

Auxiliary contact and alarm contact can remote control breaks for indication,

electric interlock, control relay and etc.

Single Auxiliary Contact Alarm Contact

Table 4 Auxiliary Contact and Its Combination

Type

Auxiliary Contact

Alarm Contact

Frame size (A) Conventional Thermal

Current (A) Ith

Rated Current (A)

AC400V

0.3

0.4

0.3

0.4

0.3

3

3

3

3

3

100, 250

400, 630, 800, 1000, 1200

100, 250

400, 630

800, 1000, 1200

DC220V

0.15

0.15

0.15

0.15

0.15

Breaker in position "OPEN" or "FREE TRIP"

Breaker in position "CLOSED"From "CLOSED" to "OPEN";From "OPEN" to "CLOSED".

NDM2E-100/250/400/630/800NDM2E-1000/1200

F14

F12

F24

F22

F11

F21

Breaker in position "OPEN" or "CLOSED"

Breaker in position "FREE TRIP"

NDM2E-100/250/400/630/800NDM2E-1000/1200

B14

B12

B14

B12

B11

Table 5 Alarm Contact and Its Combination

Lelf mounting Right mounting

Handle

Note : The code is comprised of 3 numbers. From left to right, the first number "3" indicates intelligent controller with 3 segment protections, the other two

number indicate the accessories.

Table 6 Accessory Code

No accessory

Shunt Release

Double Auxiliary Contacts

Single Auxiliary Contact

Undervoltage Release

Shunt Release and Single Auxiliary Contact

Shunt Release and Undervoltage Release

Two sets Double Auxiliary Contacts

Two sets Single Auxiliary Contact

Double Auxiliary Contacts and Single Auxiliary Contact

Shunt Release and Double Auxiliary Contact

Undervoltage Release and Double Auxiliary Contacts

Undervoltage Release and Single Auxiliary Contact

Alarm Contact

Shunt Release and Alarm contact

Undervoltage Release and Alarm Contact

Shunt Release, Single Auxiliary Contact and Alarm contact

Single Contact and Alarm contact

Double Auxiliary Contacts , Single Auxiliary Contacts and Alarm Contact

Undervoltage Release, Single Auxiliary Contact and Alarm Contact

Double Auxiliary Contacts and Alarm Contact

300

310

320

321

330

341

350

360

361

362

340

370

371

308

318

338

348

358

368

378

328

Code Name

Mountingposition Type

3 3 3 3 3 3

NDM2E-100 NDM2E-250 NDM2E-400 NDM2E-630 NDM2E-800NDM2E-1000

NDM2E-1200Number of pole

Single cuxiliary contact

Double cuxiliary contacts

Alarm contact

Shunt Release

Undervoltage release

Legends

B11

Page 28: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Electrical Characteristics of Motor Operator

19 20

CD2M2E Motor Operator

Voltage: AC 50Hz 110V, 220V, 380V DC 24V, 110V, 220V, 380V

Motor operator has excellent mechanical endurance and is easy to operate.

Can be operated automatically or manually.

14

14

35

35

35

120

120

≤0.5

≤0.5

≤2

≤2

≤2

≤5.7

≤5.7

Breaker Type Tipping Current (A) Motor power (W) Endurance(times)

NDM2E-100

NDM2E-250

NDM2E-400

NDM2E-630

NDM2E-800

NDM2E-1000

NDM2E-1200

10000

8000

5000

5000

5000

5000

5000

CD2M2E Motor Operator Wiring Schematic of CD2M2E Motor Operator (Internal wiring schematic of motor operator is shown in dashed frame.)

Note: Mandatory reset following tripping due to an electrical fault.

CS M2E

Frame size

Handle operating mechanism

No. Implication

Handle type F:Quadrate handle A:Round handle

1:Center 2:Off-center

100, 250, 400, 630, 800, 1000, 1200

NDM2E

CSM6 Rotary Handle Operating Mechanism

Mounting method

MCCB incorporated

MCCB in the switchgear may be operated with the handle in the front.

There are extended handle for both "F type" and "A type".

The switchgear shouldn't open when MCCB is CLOSED.

There is an emergency unlocking device on the handle for failures at CLOSED status.

Different handles have same cutouts dimensions.

Note: Customer should confirm with Liangxin in advance for the coordination between Nader breaker and other brand's motor operator/handle operating mechanism which are purchased by customers separately. Otherwise, Liangxin disclaim all responsibility for the damage caused by the coordination problem.

Front Connection

35

62

115

190

262

303

303

Rear Connection

35

62

115

190

262

/

/

Plug-in Connection

40

70

125

210

294

/

/

Total Power Consumption of Three Poles (VA)

NDM2E-100

NDM2E-250

NDM2E-400

NDM2E-630

NDM2E-800

NDM2E-1000

NDM2E-1200

Type

100

250

400

630

800

1000

1200

Current (A)

Frame Size (A)

100

250

400

630

800

1000

1200

100

250

400

630

800

1000

1200

Sectional Area (mm2)

Cable

9K I Z OU TG R � ' X K G � S S ˜ S S �

Copper Bar

Quantity Quantity

185

240

/

/

2

2

/

/

2

2

2

2

� � ˜ �

� � ˜ �

� � ˜ �

� � ˜ �

35

95

240

Rated Current (A) Min. Sectional Area of Connecting Wire/Copper Bar (mm2)

Power

Power Supply

ON

OFF

Control Circuit

CSM2E

Power Consumption

Sectional Area of Connecting Bus and Cable

Page 29: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

NDM2E-100H 3P Dimension

21 22

Front connection

Thickness of Undervoltage Release m=21

Thickness of Undervoltage Release m=21

X-X, Y-Y is the centre of 3P MCCB

Rear connection

A Direction

For rear plug-in connection

X-X, Y-Y is the centre of 3P MCCB

NDM2E-100H 3P DimensionPlug-in connection (front/rear) X-X, Y-Y is the centre of 3P MCCB

Aperture of dimensions of subpanelfront connection

Aperture of dimensions of subpanelfront connection

Aperture of dimensions of subpanelfront connection

Dimensions of plug-in base

Front connection

Space Baffle

Extended front terminals (optional)

X-X, Y-Y is the centre of 3P MCCB

NDM2E-250H 3P Dimension

88

25

5.5

107

p

Un

der

volt

age

Rel

ease

Space Baffle

Und

ervo

ltage

Rel

ease

94 (Min.) 3P

60 (3P)

Page 30: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

23 24

Rear connection

A Direction

X-X, Y-Y is the centre of 3P MCCB

Plug-in connection (front/rear)

For rear plug-in connection

X-X, Y-Y is the centre of 3P MCCB

NDM2E-250H 3P DimensionPlug-in connection (front/rear) X-X, Y-Y is the centre of 3P MCCB

NDM2E-400H 3P Dimension

Rear connection X-X, Y-Y is the centre of 3P MCCB

Dimensions of plug-in base

25

35

126

90

75.5

83

42

173

M10

89

58

70

M10

Aperture of dimensions of subpanelfront connection

Aperture of dimensions of subpanel,front connection

Aperture of dimensions of subpanel,front connection

3P

3P

110 (Min.) 3P 194

44 (3P)

A Direction

Thickness of Undervoltage Release m=21

Space Baffle Extended front terminals (optional)

Un

der

volt

age

Rel

ease

54(m

in)

Page 31: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

25 26

Plug-in connection (front/rear) X-X, Y-Y is the centre of 3P MCCB

Front connection

Arc barrier

Extended front terminals (optional)

X-X, Y-Y is the centre of 3P MCCB

NDM2E-400H 3P Dimension

NDM2E-630H, NDM2E-800H 3P Dimension

Rear connection X-X, Y-Y is the centre of 3P MCCB

NDM2E-630H, NDM2E-800H 3P Dimension

Dimensions of plug-in base

Rear plug-in connection X-X, Y-Y is the centre of 3P MCCB

Thickness of Undervoltage Release m=21

85

Type

NDM6-630

NDM6-800

a(mm)

7

10

70

175

65(

min

123

Rear plug-in connection version is not available for 700A and 800A NMD6- 800 series MCCB currently.

11272

30

123

M14

M10

243

62

302

Aperture of dimensions of subpanelfront connection

Aperture of dimensions of subpanelfront connection

Un

der

volt

age

rele

ase

3P

152 (Min.) 3P

60 (3P)

A Direction

(3P)

213 (Min.) 3P

65(m

in)

Page 32: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

27 28

Front connection

Space Baffle

Extended front terminals (optional)

X-X, Y-Y is the centre of 3P MCCB

NDM2E-1000H/ 3P, NDM2E-1200H/3P Dimension

Motor Operator

CD2M2E Motor Operator

Motor Operator

Motor Operator Type Breaker Type H(mm) A(mm) B(mm)

CD2M2E-100

CD2M2E-250

CD2M2E-400

CD2M2E-800

HDC-80NE

NDM2E-100 3P

NDM2E-250 3P

NDM2E-400 3P

NDM2E-630, 800 3P

NDM2E -1000, 1200 3P

89.5

93

142

146

150

30

35

44

70

70

129

133.5

194

243

340

For NDM2E-100 3P For NDM2E-250 3P

For NDM2E-400 3P For NDM2E-630/800 3P

CSM2E Handle Operating Mechanism

30

104

143

35

CS1M2E-100 CS2M2E-100 CS1M2E-250 CS2M2E-250

CS1M2E-400 CS1M2E-630,CS1M2E-800

CS2M2E-400 CS2M2E-630,CS2M2E-800

198210

39

87.5

120

138

194

65

15

35

11.5

35

31

48

15

Aperture of dimensions of subpanel,front connection

Page 33: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

29 30

For NDM2E-1000/1200 3P

Mounting Diagram of CSM6 Handle Operating Mechanism

Cutouts Sketch Map for Installation of CSM2E Handle Operating Mechanism

HSC1-80NE

CS1

HSC2-80NE

F Type A Type

CS2

H120

24

DMin.=50mm

H2

16

D

8

Min.=50mm

Installation Method and Dimensions of External Accessories

NDM2E-100

H1 49

46

55

48

76

61

63

66

70

52H2

D 150mm for default. Can be customized upon request.

NDM2E-250 NDM2E-400NDM2E-630NDM2E-800

NDM2E-1000NDM2E-1200

Breaker TypeCode

Dimension

A

B

C

D

L

H

92

120

50

11.5

118

22

107

135

50

14

135

22

150

180

60

18

175

30

210

243

60

18

230

30

NDM2E-100 NDM2E-250 NDM2E-400NDM2E-630NDM2E-800

73 o

r 10

5

66 o

r 96

65

654- 4.5

42

53

2- 5.5

36

45

Switch A Switch B

A A

ON

L

C

B

OFF

D

Mechanical Interlock

Breaker Type

Code

Page 34: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency
Page 35: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

33 34

Note

Page 36: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

35 36

上海市浦东大道1139弄6号楼 1301室

地址:

021-50930891/51920563 021-50930891

Tel:Fax :

上海市商城路297号申金大厦 1902室

地址:

021-58776026021-58776027

Tel:Fax :

郑州市农业路72号国际企业中心B座1704室

地址:

0371-63298528/636913660371-63298529/63691367

Tel:Fax :

武汉市汉口解放大道686号世贸大厦1202A

地址:

027-59501427/59501747027-59501428027-59501428-808

Tel:

Fax :

成都市东大街紫东楼段11号东方广场802

地址:

028-84459506028-84451506

Tel:Fax :

广州市海珠区庭园路5号中洲中心南塔西座1109室

地址:

东莞,佛山,珠海,中山,惠州福州,厦门

联络处:

020-89231852/89231523020-89231851

Tel:Fax :

苏州市三香路353号三香广场1006室

地址:

无锡联络处:

0512-686029760512-68602976

Tel:Fax :

西安市含光路74号高层3004室

地址:

029-88462915029-88462915

Tel:Fax :

石家庄市裕华路方北新村1-2-803

地址:

0311-869746980311-86974698

Tel:Fax :

大连市沙河口区如意街46号 (天兴罗福国际中心)A-605室

地址:

0411-838987480411-83898748

Tel:Fax :

深圳市南山区艺园路115号马家龙田厦IC产业园3-009室

地址:

0755-26560518/265602990755-86241299

Tel:Fax :

北京市朝阳区北四环东路108号千鹤家园3号楼805室

地址:

唐山,包头联络处:

010-82386038/82386058010-82386078

Tel:Fax :

沈阳市沈河区奉天街346号格林自由城B座18层11号

地址:

鞍山,辽阳,锦州联络处:

024-62579902/62579903024-62579902/03-518

Tel:Fax :

哈尔滨香坊区中山路82号迷你国度大厦21层13室

地址:

0451-517132820451-86134308

Tel:Fax :

重庆市江北区建新南路11号浩博天庭7-10

地址:

023-67745931023-67865630

Tel:Fax :

长沙市五一大道湘域中央1号楼1813/14室

地址:

0731-844488760731-84445576

Tel:Fax :

济南市无影山东路38号名人时代大厦1505室

地址:

0531-859237680531-85923568

Tel:Fax :

天津市南开区卫津路18号新都大厦4号楼1门2703

地址:

022-83692122022-83692122

Tel:Fax :

南京市鼓楼区福建路31号(华富园1号)华富大厦2105室

地址:

南通,徐州联络处:

025-83479160/85158402025-83479150

Tel:Fax :

杭州市莫干山路110号华龙商务大厦412室

地址:

宁波,绍兴联络处:

青岛,淄博,威海,烟台联络处:

长春市绿园区普阳街2522号至通尚都359室内

地址:

0431-856664800431-85666480

Tel:Fax :

0571-880171200571-88017120

Tel:Fax :

Page 37: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

Shanghai Liangxin Electrical CO., LTD.Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Post code: 200137Tel: 86-21-50412789Fax: 86-21-58675966E-mail: [email protected]

As standards, specifications and designs changefrom time to time, please ask for confirmationof the information given in this publication.

201

0 -

Lian

gxin

Ele

ctri

cal -

All

righ

ts r

eser

ved

2010.05

NDM2L Series Molded Case Circuit Breakerwith Residual Current Protection

Page 38: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

NDM2L SeriesMolded Case Circuit Breakerwith Residual Current Protection

Application

Model and Implication

N-pole Type of Four Pole Product and Its Rated Current

Working Condition

Product Features

Structure Introduction

Main Specifications

Tripping Characteristic

Power Consumption

Temperature Derating

Tripping Curve

Residual Current Protection Curve

Residual Current Operating Time

Illustration of Residual Current Setting Switch

Illustration of I△n Max. Breaking Time Setting Switch (Delay Type)

Dimension

Wiring Schematic of Alarm Module Without Tripping

Accessory Code

Wiring Schematic of Auxiliary Contact

Undervoltage Release

Shunt Release

Motor Operator

Handle Operating Mechanism

Sectional Area of Connecting Bus And Cable

Usage And Maintenance

Ordering Notice

Order Form

03

03

04

04

04

04

05

05

06

06

06

09

10

10

10

11

12

13

14

14

14

15

16

18

18

18

18

Leading• Low-voltage• Electrical• Component• Manufacturer

Page 39: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 0404

The N-pole is the right one of the CBR as viewed from front of panal. Please refer to Table 1 regarding its rated current.

ND M 2

M means “MCCB”

L

2

NDM2L

Protection against residual current

Opeation method

Number of poles 4

No code: Direct handle operation

A: N-pole is always close without overload releaseB: N-pole is open or close together with other three poles and without overload releaseC: N-pole is open or close together with other three poles and with overload release

Brand

P: Motor operation Z: Rotary handle operation

Product code

Design code

Brand code

Frame rating

Accessory code Please refer to Table 2

IEC60947-2:2006, GB 14048.2-2008.

78

Model and Implication

Standards

N-pole type

Application code9

10

7 8 9 10

Application

NDM2L Series Molded Case Circuit Breaker (hereinafter “CBR”), of which insulation voltage is 690 V, will be suitable for in-frequency switching of circuits and starting of motors in 50Hz/60Hz circuits with rated working voltage of 400V and rated current up to 400A. The breaker can provide overload, short circuit and undervoltage protection to the circuit and power equipment concerned. In addition, it can also protect the circuit against fire disaster caused by long-term grounding error that can not be detected by over current protection device.

NDM2L series CBR is combined with NDM2 series MCCB and residual current protection modular. It has the characteristic of easy installation and flexible adjustment.

Working Condition

Altitude:≤2000m.Ambient temperature: -5℃~+40℃ (The average temperature in 24h should not exceed +35℃.) The relative humidity of the air does not exceed 50% at the maximum temperature of +40℃. Higher relative humidity may be prermitted at lower temperature. The average highest relative humidity should not exceed 90% when the lower average temperature of the most humid month is below +25℃. Special measures may be necessary in cases of occasional condensation due to variations in temperature.Pollution degree:3.The installing type of main circuit: Type Ⅲ. Auxiliary and controlling circuit which are not be connected to main circuit: Type II.Used in areas wirhout possibility of explosion, metal eroding and insulation destroying media and be free from rain and snow.

03

NDM2L series

L

1. Release button2. Adjusting button for rated residual current3. Fault indicator4. Pre-alarm indicator

5. Residual current testing button6. Working indicator7. Adjusting button for delay time

16

20

25

32

40

50

63

80

100

16

20

25

32

40

50

100

63

Frame Size I nm (A) Rated Current of CBR I n (A)

Rated Current of N-pole (A)

100

125

140

160

180

200

225

225

250

315

350

400

225100

125

225

250

400

Product Features

Structure Introduction

Table 1: N-pole Type of Four Pole Product and Its Rated Current Table 1: N-pole Type of Four Pole Product and Its Rated Current

Characterized by small size, high breaking capacity, short arc, sharker-resisting, and so on.Suitable for both vertical and horizontal installation.With isolating function. The symbol is“ l “.Residual current of the protecting modular is from 3 phases, making it possible to work normally in case of default of any phanese.Adjustable on the site:With three grades of residual current and three grades of delaytime. User can adjust them according to the requirements on the site.Indication of working status:Normal-Green lamp; Fault-Red lamp; Alarm-Yellow lamp (≥25%I△n).Good performance under voltage faults:Be able to perform residual current protection when phase voltage drops to 50V.

No. Implication

No code: Power distribution 2: Motor protection

Frame Size I nm (A) Rated Current of CBR I n (A)

Rated Current of N-pole (A)

100, 225, 400

Page 40: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 0604

Power Consumption

05

25

100

225

400

40

35

62

115

NDM2L-100 Direct Heated (1~25A)

NDM2L-100 Indirect Heated (32A~100A)

NDM2L-225

NDM2L-400

TypeCurrent(A)

Total Power Consumption of Four Poles (W)

Temperature Derating

Tripping Characteristic

Main Specifications

Type

100

3000

7000 6500

1500

4000

1000

≤50 ≤50 ≤50

400

690

——

——

4

50

35

400

690

——

——

4

50

35

400

690

——

——

4

65

48

225 400

16、20、25、32、40、50、63、80、100

100、125(140)、160、180、200、225

225、250、315、350、400

NDM2L-100 NDM2L-225 NDM2L-400

Rated voltage Ue (AC V)

Frame size Inm (A)

Rated current In (A)

Rated insulation voltage Ui (AC V)Number of poles

Non-delay

Delay

Electrical

Mechanical

Rated ultimate breakingcapacity Icu (kA)

Rated operating short circuit breaking capacity Ics (kA)

Rated residual operating current I△n (mA)

Rated residual non-operating current I△no (mA)

Durability (times)

Arcover distance (mm)

Rated residual current making/breakingcapacity I△m (kA)

AC690V

AC400V

AC690V

AC400V

100/300/500 300/500/1000

300/500/1000100/300/500

21— I△n

41— Icu

16≤In≤63 10In╳(1±20%)

10In╳(1±20%)

12In╳(1±20%)

5In╳(1±20%)

10In╳(1±20%)

≥1 <1

<2

<2

<2

≥2

≥2

≥2

63<In≤100

100<In≤400

10<In≤400

Rated Current of The Trip Unit (A) Non-tripping Time at

1.05In(cold) (h)

Non-tripping Time at1.0In(cold) (h)

Tripping Time at1.30In(hot) (h)

Tripping Time at1.20In(hot) (h)

Tripping Current ofElectromagnetic

Trip Unit (A)Remark

Powerdistributionprotection

type

Motorprotection

type

40°C

1

1

1

45°C

0.96

0.97

0.94

50°C

0.91

0.94

0.88

55°C

0.85

0.91

0.82

60°C

0.78

0.86

0.75

NDM2L-100

NDM2L-225

NDM2L-400

Coefficient

Temperature

Type

Derating Coefficient (×In)

Tripping Curve

Thermal Trip Unit(Ambient Temperature 40℃)

Front/Rear Connection

Current-temperature Characteristic

Current-temperature Characteristic

Max.

Delay tripping

Delay tripping

Instantaneous tripping

Instantaneous tripping

Min.

Max.

Min.

Instantaneous tripping current range (8~12)×In

Instantaneous tripping current range (8~12)×In

Current (×In)

Current (×In)

NDM2L-100 Tripping Curve (Power distribution)

NDM2L-225 Tripping Curve (Power distribution)

Ambient Temperature (℃)

Ambient Temperature (℃)

Rat

ed C

urre

nt (%

)R

ated

Cur

rent

(%)

Trip

ping

Tim

e

t (s

)Tr

ippi

ng T

ime

t

(s)

Page 41: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 080407

Current-temperature Characteristic

Current-temperature Characteristic

Current-temperature Characteristic

Current-temperature Characteristic

Ambient Temperature (℃)

Ambient Temperature (℃)

Ambient Temperature (℃)

Ambient Temperature (℃)

Rat

ed C

urre

nt (%

)R

ated

Cur

rent

(%)

Rat

ed C

urre

nt (%

)R

ated

Cur

rent

(%) Max.

Max.

Max.

Delay tripping

Delay tripping

Instantaneous trippingDelay tripping Instantaneous tripping

Delay tripping Instantaneous tripping Instantaneous tripping

Min.

Min.

Max.

Min. Min.

Instantaneous tripping current range (9.6~14.4)×In

Instantaneous tripping current range (9.6~14.4)×In

Instantaneous tripping current range (9.6~14.4)×In

Current (×In)Current (×In)

Current (×In) Current (×In)

NDM2L-400 Tripping Curve (Power distribution)

NDM2L-100 Tripping Curve (Motor protection)

NDM2L-225 Tripping Curve (Motor protection)

NDM2L-400 Tripping Curve (Motor protection)

Trip

ping

Tim

e

t (s

)Tr

ippi

ng T

ime

t

(s)

Trip

ping

Tim

e

t (s

)Tr

ippi

ng T

ime

t

(s)

Instantaneous tripping current range (8~12)×In

Page 42: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 100409

Residual Current Protection Curve Residual Current Operating Time

Illustration of Residual Current Setting Switch

Illustration of I△n Max. Breaking Time Setting Switch (Delay Type)

Residual Current

Non-delay

Delay

0.2

0.5/1.15/2.15

—— —— ——

0.25/0.9/1.9 0.25/0.9/1.90.35/1/2

0.1/0.5/1

0.1 0.04 0.04 Max. breaking time (s)

Max. breaking time (s)

Limiting non-driving time △t(s)

I△n 2I△n 5I△n 10I△nI△n = 100mA/300mA/500mA/1000mA

Residual Current (×I△n)

Residual Current (×I△n)

Residual Current (×I△n)

5 I△n Max. breaking time

2 I△n Max. breaking time 0.35s

2 I△n Max. breaking time 2s2 I△n Max. breaking

time 1s

Limiting non-drivingtime 0.1s

Limiting non-drivingtime 0.5s

Limiting non-drivingtime 1s

Non-delay Residual Current Protection Curve

I△n = 100mA/300mA/500mA/1000mADelay Residual Current Protection Curve

I△n = 100mA/300mA/500mA/1000mADelay Residual Current Protection Curve

I△n = 100mA/300mA/500mA/1000mADelay Residual Current Protection Curve

Trip

ping

Tim

e

t (s

)Tr

ippi

ng T

ime

t

(s)

Trip

ping

Tim

e

t (s

)Tr

ippi

ng T

ime

t

(s)

Rat

ed r

esid

ual

non-

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

non-

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

non-

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

non-

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

oper

atin

g cu

rren

t

Rat

ed r

esid

ual

oper

atin

g cu

rren

t

Residual Current (×I△n)

Page 43: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 120411

Dimernsion

Notes:P1, P2 are NC contact terminals

P3, P4 are NO contact terminals

P5, P6 are terminals for AC230V power

AC230V

20mm

NDM2L-100L1225 122

142

198

50

65

10

70

60

4.5

6.59438100

8

8

24

24

87

105

103

104

127

155

204

213

194

4.5

252

257

H1 H2 H3W A B1 ΦML2

NDM2L-225

NDM2L-400

Outline Dimensions Type

Installation Dimensions

Outline and installation dimensions (Front connection)

C

26

29

64

D

63

74

91

E

17.5

23.5

41.25

F

88

102

152

G

22.25

12

9.75

H

50

55

88

K

25

25

20

L

136

157

152

R

23

33

52.5

P

92

92

120

NDM2L-100

NDM2L-225

NDM2L-400

Outline Dimensions of Cover

a

10.5

10.5

10.5

b

44

51

53.5

e

6

6

6

f

113.75

129.75

176

NDM2L-100

NDM2L-225

NDM2L-400

Outline Dimensions of Cover

C

E

LK

H FG

D

Pf

Ra

b

e

Wiring Schematic of Alarm Module Without Tripping

Page 44: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

0314

0413

1> Current Parameters

Accessory Code

Auxiliary Contact

Specifications of Auxiliary Contact

Note: 1. The code is comprised of 3 numbers. From left to right, the first number “2” indicates the trip unit is magnetic only while “3” indicatesthe trip unit is thermal magnetic. 2. N-pole type should be B type or C type for double accessories.

Frame Size

Inm≤225 3 0.30

0.403Inm=400

Conventional Thermal Current Ith (A) Rated Current at AC 400V (A)

Auxiliary Contact and Its Combination

From "CLOSED" to "OPEN"; From "OPEN"to "CLOSE".

F14 F11

F12

F21F24

F22

F14 F11

F12

2> Electrical Endurance of Auxiliary Contact

AC-15 10

1 1

1 0.3

6Pe 1

1

1

1 0.3

6PeDC-136050 360

TimesMaking Breaking

I/Ie U/Ue COSΦ I/Ie U/Ue COSΦ

≥0.05s

≥T0.95

3> Making and Breaking Capacity of Auxiliary Contact

AC-15 10

1.1 1.1

1.1 10

1.1 1.1

1.10.3

6Pe

0.3

6PeDC-1310 120

I/Ie U/Ue COSΦ I/Ie U/Ue COSΦ

≥0.05s

≥T0.95

Undervoltage Release

Note: Below shunt controlling loop design is recommendedwhen the power of the controlling loop is DC 24V.

KA: The relay in DC 24V controlling loop. The current capacity of its contract is 1A.

Voltage: AC 50Hz 230V/400V; DC 220V. Between 70%~110% of rated control voltage, shunt release should trip breaker in security under any operating conditions.

Shunt Release

Wiring Schematic of Shunt Release (Internal accessory wiring schematic is shown in dashed frame.) K: Micro switch inside shunt release. It is connected with coil in series and normally closed. When breaker trips, the micro switch turn to open. When breaker is closed, the micro switch turn to closed.

Table 2 Accessory Code

210, 310

220, 320

221, 321

230, 330

240, 340

241, 341

260, 360

261, 361

262, 362

270, 370

271, 371

208, 308

228, 328

258, 358

268, 368

Shunt Release

Double Auxiliary Contacts

Single Auxiliary Contact

Undervoltage Release

4 4 4

NDM2L-100 NDM2L-225 NDM2L-400

Handle

Left mounting Right mounting

Single auxiliary contact

Single auxiliary contact/Alarm contact

Double auxiliary contactsShunt ReleaseUndervoltage release

Legends

Code Name

TypeNumberof Pole

Shunt Release and SingleAuxiliary Contact

Two Sets Double AuxiliaryContacts

Two Sets Single AuxiliaryContact

Double Auxiliary Contacts andSingle Auxiliary Contact

Shunt Release and DoubleAuxiliary Contacts

Undervoltage Release andDouble Auxiliary Contacts

Undervoltage Release and SingleAuxiliary Contact

Alarm Contact

Single Auxiliary/Alarm Contact

Double Auxiliary Contacts, Single Auxiliary Contact/Alarm Contact

Double Auxiliary Contactsand Alarm Contact

Breaker in position"OPEN" or "FREE TRIP”

Breaker in position"CLOSED"

Double auxiliary contacts

Single auxiliary contact

UtilisationCategory

UtilisationCategory

Operating Frequency(times/h)

Duration underCurrent

Times Operating Frequency(times/h)

Duration underCurrent

BreakingMaking

Wiring Schematic of Auxiliary Contact

Power Supply

Turned-on loop

Turned-off loop

Control voltage: AC 50Hz 230V110VDC

400V220V

Between 35%~70% of rated control voltage, undervoltage release should operate in security and trip breaker. When under 35% of rated voltage, it should prevent breaker from closing. Breaker closing is possible only if the power supply voltage is no less than 85% of rated voltage.

Note: Only undervoltage release be charged in advance, breaker can be closed or re-latches.

Power Supply Power Supply

Page 45: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

0316

0415

Matching CBR

NDM2L-100

NDM2L-225

NDM2L-400

≤7 1540

1870

1200

≤8.5

≤8.7

10000

8000

5000

Starting Current (A) Starting Power (W) Endurance (times)

Installation Method and Dimensions of Handle Operating MechanismMotor Operator

Wiring Schematic of Motor Operator for NDM2L-100/225/400 (Externaln accessory wiring diagram is shown in dashed frame)

Electrical Characteristics of Motor Operator

Matching CBR NDM2L-100 NDM2L-225 NDM2L-400

Height of CD2 motor operator H 89.5 93 142

Height of CD2 Motor Operator

Note: Mandatory reset following tripping due to an electrical fault.

NDM2L-100/225/400

CD2 Motor Operator

Motor Operator

(ON) (OFF)

Code illustration

M: Motor

Y: Electro-magnetic brake

S3: Micro-switch

X: Terminal

S1, S2: Button

(Prepared by customers)

Cutouts Sketch Map for Installation of CS1-A Handle Operating Mechanism

Cutouts Sketch Map for Installation of CS1-F Handle Operating Mechanism

Note: Type A means rounded handle

Cutouts Sketch Map for Installation of CS2-A Handle Operating MechanismNote: Type A means rounded handle

Note: Type F means quadrate handle

Breaker

≥ 200 Hinge axis

66 o

r 96

66 o

r 96

73 o

r 10

5

Page 46: NDM2 Series - Moki, s.r.o. MCCB.pdf · NDM2 Series Molded Case Circuit Breaker (hereinafter “breaker”), of which insulation voltage is 800V, will be suitable for in-frequency

03 180417

Installation Method and Dimensions

Metal Plastic

Vertical

Vertical

Horizontal

Horizontal

Vertical

HA B

49 697255

35

30

11.5

11.5

31

32

15

35

35

45

65

37

74

46

46

48

48

61

110

/

//

/

/

/

/

/

/

//

/

/

/

/

/

/

/

/

/

/

104143

194 138

NDM2L-100

NDM2L-100NDM2L-100

NDM2L-225

NDM2L-225NDM2L-225

NDM2L-400

NDM2L-400

External Accessories

Model of External

Accessories

InstallationMethod

CS1-100

CS2-100

CS2-100

CS1-225

CS2-225

CS2-225

CS1-400

CS2-400

A B

Selection of Connecting Bus

16

20

25

32

40

5063 80 100 125

140 140200225

250 400160 350

315

2.5 6 10 16 25 35 50 70 95 120 240185

Rated current In(A)

Sectional Area of Connecting Bus and Cable

Order Form

Usage and Maintennce

Do not adjust the characteristic and accessories of the breaker, which handle by the manufacturer. The handle of the breaker can be placed in three positions, which represents CLOSED, OPEN and FREE TRIP individually. When the handle is in the position of FREE TRIP, it should be turned in direction of OPEN at this moment. Then the breaker can be re-latch and closed.

Ordering Notice

The model, specification and order quantity of the breaker should be noted. When using undervoltage release, shunt release or motor operator, please give clear indication of operation voltage or the value of control power voltage. For example: NDM2L-100/4300B, Rear connection, Delay type, Rated current 80A, Quantity: 10 PCS.

NDM2L-100

100/300/500 0.5/1.15/2.15

Alarm Function QuantityRated Current In(A)

Operating Current I△n(mA)

Non

-adj

usta

ble

Non

-del

ayD

elay

Non

-del

ayD

elay

Non

-del

ayD

elay

Without alarm function

Without alarm function

Without alarm function

Non-tripping

Tripping

Non-tripping

Tripping

Non-tripping

Tripping

Ala

rmA

larm

Ala

rm

Adj

usta

ble

Non

-adj

usta

ble

Adj

usta

ble

Non

-adj

usta

ble

Adj

usta

ble

Operating Time △T(s) Type

≤0.2

NDM2L-225

100/300/500 0.5/1.15/2.15

≤0.2

NDM2L-400

300/500/1000 0.5/1.15/2.15

≤0.2

Note: Please fill in the rated current and order quantity. And mark “√”in the selected “□”.

(If the operating current is non-adjustable, please f i l l in the value of the operating current.)

≥ 200 mm

Hin

ge a

xis

73 o

r 10

5

Cutouts Sketch Map for Installation of CS2-F Handle Operating MechanismNote: Type F means quadrate handle

Breaker

Manual Installation Dimensions (mm)Matching

MCCB

HandleOperating

Mechanism

Sectional Area ofConnecting Wire

(mm2)