175
GE Multilin Motor Protection Seminar - 2005

Motor Protection Relay Setting Guide

Embed Size (px)

DESCRIPTION

This presentation delt with Motor protection relay and it's setting creteria !

Citation preview

Page 1: Motor Protection Relay Setting Guide

 

GE Multilin

Motor ProtectionSeminar - 2005

Page 2: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

2

Motor History & Facts

The first U.S. patent for a motorwas issued to Thomas Davenportin 1837.

In 1888, Nikola Tesla patentedthe first AC poly-phase motor.

Today in U.S. more then 1 billionmotors are in service.

Motors consume 23% ofelectricity in North America.

Electricity consumption bymotors in manufacturing sectoris 70%. In oil, gas and miningindustries around 90%.

Three phase squirrel-cageinduction motors account forover 90% of the installed motorcapacity.

Page 3: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

3

Motor Downtime

Motor initial cost could be as low as 2% of the lifetimeoperational cost.

The driven process downtime in some cases is moreexpensive than motor.

Motor downtime contributors are:• Power system failures.

• Load failure

• Motor failure

• Inadvertent shutdown because of human mistake ormotor protection maloperation

Page 4: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

4

Motor Failure Rates and Cost 

Motor failure rate isconservatively estimatedas 3-5% per year.

In Mining, Pulp and Paperindustry motor failure rateis up to 12%.

Motor failure costcontributors:

• Repair or Replacement.

• Removal andInstallation.

• Loss of Production.

AVERAGE

FAILURE CONTRIBUTOR % FAILED COMPONENT % %

Persistent Overload 4.20% Stator Ground Insulation 23.00

Normal Deterioration 26.40% Turn Insulation 4.00

Bracing 3.00

Core 1.00

Cage 5.00

Electrical Related Total 30.60% Electrical Related Total 36.00%

High Vibration 15.50% Sleeve Bearings 16.00

Poor Lubrication 15.20% Antifriction Bearings 8.00

Trust Bearings 5.00

Rotor Shaft 2.00

Rotor Core 1.00

Mechanical Related

Total30.70%

Mechanical Related

Total32.00%

High Ambient Temp. 3 Bearing Seals 6.00

Abnormal Moisture 5.8 Oil Leakege 3.00

Abnormal Voltage 1.5 Frame 1.00

Abnormal Frequency 0.6 Wedges 1.00

Abrasive Chemicals 4.2

Poor Ventilation Cooling 3.9

Other Reasons 19.7 Other Components 21.00

Environmental Related &

Other Reasons: Total38.70%

Maintanence Related &

Other Parts: Total32.00%

Mechanical

Related Failures

31%

Environmental,

Maintanence &

Other Reasons

Related Failures

36%

EPRI STUDYIEEE STUDY

Electrical

Related Failures

33%

Page 5: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

5

Thermal Stress Causes Motor Failure

Many of the motor failure contributors (IEEE Survey) and failed motorcomponents (EPRI Survey) are related to motor overheating.

Thermal stress potentially can cause the failure of all the major motorparts: Stator, Rotor, Bearings, Shaft and Frame.

STATOR

ROTOR

BEARINGS

FRAME

SHAFT

Page 6: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

6

• Setting of the motor protection relay is basedon the motor datasheets information andsystem configuration.

• Datasheets are normally provided by motormanufacturer.

• System configuration data can be obtainedfrom single line diagram.

Page 7: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

7

Starting Current:

• When rated voltage and

frequency is applied to NEMA B

motor, it will typically draw

600% of full-load current and

decrease to rated value as

rotor comes up to speed

600%

100%

Motor Specifications

Page 8: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

8

Thermal Modeling: Motor Thermal Limits Curves

Ideally, curves have beenprovided for both a hot andcold motor. A hot motor isdefined as one that has beenrunning for a period of time atfull load such that the statorand rotor temperatures havesettled at their ratedtemperature. Conversely, acold motor is defined as amotor that has been stoppedfor a period of time such thatthe rotor and statortemperatures have settled atambient temperature. Formost motors, the motorthermal limits are formed intoone smooth homogeneouscurve.

The motor thermal limits curves consist of three distinct segments which are based on thethree running conditions of the motor:

• The locked rotor or stall condition.

• Motor acceleration.

• Motor running overload.

Page 9: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

9

Thermal Modeling: Motor Thermal Limits CurvesThe acceleration curves are an indication of the amount of current andassociated time for the motor to accelerate from a stop condition to a normalrunning condition. In this particular example, there are two acceleration curves:

The first is the accelerationcurve at rated stator voltagewhile the second is theacceleration at 80% of ratedstator voltage; a soft starteris commonly used to reducethe amount of inrush voltageand current during starting.As can be seen on the curveshown, since the voltage andcurrent are lower, it takeslonger for the motor to start.Therefore starting the motoron a weak system can resultin voltage depression,providing the same effect asa soft-start.

Page 10: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

10

Motor Data Sheets

Motor Performance Data Thermal Limit Curves

Page 11: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

11

Motor Thermal Limit Curves

Thermal Limit Curves:

B. Hot Running OverloadB

A. Cold Running OverloadA

D. Hot Locked Rotor CurveD

C

C. Cold Locked Rotor Curve

F. Acceleration curve @100%voltage

F

E. Acceleration curve @ 80% ratedvoltageE

Page 12: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

12

Motor Thermal Parameters

Motor Data Sheet Parameters

G. Temperature Rise, Insulation Class

G

J

J. Locked Rotor Time; Cold/Hot

K

K. Number of Starts; Cold/Hot

I. Locked Rotor Current

I

H. Full Load Current

H

Page 13: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

13

Motor Specifications

Horsepower:

• Engineering unit of power33,000 lb 1ft in 1 min.

• HP = 1.341 X KW• KW = 0.746 X HP

Motor rating (per NEMA MG-1)

• Large Motors: > 500HP (1800 & 3600 rpm)

• Medium Motors: 1-500HP (1800 & 3600 rpm)

Page 14: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

14

Efficiency:

An indication of how much electrical energy is converted tooutput shaft mechanical energy expressed as a percentage.

Core loss

Stator loss

Rotor Loss

Friction andWindage

Stray loss

Losses

Electrical Energy in = Mechanical Energy out + Losses (mostly heat)

MechanicalEnergy

ElectricalEnergyin

Motor Specifications

Page 15: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

15

Hot/Cold Safe StallTime Ratio   COLD

 HOT 

 LRT 

 LRT  HCR =Motor Data Sheet

Overload CurveMethod

 

LRC=5.5FLA

LRTcold=8sec

LRThot=6sec

Motor Specifications

Page 16: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

16

Thermal Model. Hot/Cold Stall Time Ratio (HCR)

Typically motor manufacturer provides the values of the locked rotorthermal limits for 2 motor conditions:

• COLD : motor @ ambient temperature

• HOT : motor @ rated temperature for specific class and service factor.

40°C

110°C

120°C

HCR defines the proportional increase of Thermal Capacity Used (TCU) ofthe motor running fully loaded at settled temperature in comparison to themotor resting at ambient temperature.

40°C

AMBIENT CLASS A

40°C

130°C

140°C

CLASS B

40°C

155°C

165°C

CLASS F

40°C

180°C

190°C

CLASS H

NEMA standardtemperature rises formotors up to 1500HPand Service Factors 1and 1.15respectively.

Page 17: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

17

Service Factor:

When the voltage and frequency are maintained at the values specifiedon the nameplate, the motor may be overloaded up to the horsepowerobtained by multiplying the nameplate horsepower by the servicefactor.

At the service factor load greater than 1.0 the motor’s efficiency, powerfactor and speed will differ from nameplate. But the locked rotorcurrent and breakdown torque will remain the same.

For a given insulation, motors with a 1.15 service factor have a lowerrise then those with a service factor of 1.0. This allows the motor tooperate close to the service factor without exceeding ratedtemperature limits of the insulation. If the motor is operated at theservice factor, the motor will have a temperature rise in excess of the100% rated rise for motors with a 1.0 service factor. This will shortenthe life expectancy considerably.

Motor Specifications

Page 18: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

18

Information required to set Thermal Model:

• Motor FLA

• Locked Rotor Current

• Locked Rotor Time Hot

• Locked Rotor Time Cold

• Service Factor

• Motor Damage Curves

Motor Specifications

Page 19: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

19

Motor Management Relays have three basiccategories of protection elements:

• TRIPS

• ALARMS

• BLOCKS

Motor Management Relays

Page 20: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

20

Thermal Protection Algorithm Requirements

 ACCURACY  Precise estimate of the motor thermal image

SIMPLICITY  Easy to understand and calculate thermalestimate

DEPENDABILITY  Capability of constant thermal imagemonitoring

COMPLIANCE TO INDUSTRY STANDARDS 

EASY SETUP  Use of standard readily available motorparameters

RELIABILITY  Alternative backup method of the thermal

estimate

FLEXIBILITY  Compatibility with different motor applications

Page 21: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

21

Thermal Model Enhancements and Additions

Motor Start Inhibit

Standard, Custom and Voltage Dependant Overload Curves

Thermal Model Biasing by Current Unbalance

Thermal Model Biasing by RTD Inputs

Separate Thermal Time Constants for Running and StoppedMotor Conditions

Independent Current Unbalance Detector

Acceleration Limit Timer

Mechanical Jam Detector

Start and Restart Supervision

Page 22: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

22

Important Motor Protection Device Functionsand Features

Phase Short Circuit, Differential Protection (largemotors), Ground Fault Protection

Voltage and Frequency Elements, Phase ReversalDetection

Reactive and Active Power, Power Factor

Protection Device Failure Detector

Event Recorder, Data Logger, Oscilography

Communication Capability, Integration into DCS/SCADA

User Friendly Software Interface

Rugged Construction, Easy Installation

Page 23: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

23

Two Main Risks for an Overheated Motor

Stator Windings Insulation Degradation

Insulation lifetimedecreases by half ifmotor operatingtemperature exceedsthermal limit by 10ºC

0

10

20

30

40

50

60

70

80

90

100

110

0 50 100 150 200 250

TEMPERATURE (ºC)

   P   E   R   C   E   N   T   A   G   E   O   F   L   I   F   E   (   %   )

A-CLASS (105 ºC)

B-CLASS (130ºC)

F-CLASS (155 ºC)

H-CLASS (180 ºC)

A B F H

Rotor Conductors Deforming or MeltingIn most cases, rotor thermal limit is defined by the allowedmotor stall time. These motors are classified as rotor limited.Stator limited motors - if voltage rating is 10 times greaterthan HP rating: For example: 500HP, 6900V 

For F class insulationstator temperature of165ºC causes motorlifetime to decreaseto 50%

Page 24: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

24

Thermal Model - Motor States

Motor Stopped: Current < “0” threshold &

contactor/breaker is open.

Motor Starting: Previous state is “Stopped” & Current > “0”

threshold. Motor current must increase to the level higherthan overload pickup within 1 second otherwise motor

algorithm will declare the “Running” state.

Motor Running: Previous state is “Starting” or

“Overloading” & Current drops below overload pickup level.

Motor Overloading: Previous state is “Running” & Current

raises above overload pickup level. Thermal Capacity Used(TCU) begins to accumulate

Page 25: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

25

The primary motor protective element of the motor protection relay is the thermaloverload element and this is accomplished through motor thermal image modeling.

This model must account for thermal process in the motor while motor is starting,running at normal load, running overloaded and stopped. Algorithm of the thermalmodel integrates both stator and rotor heating into a single model.

Thermal Overload Curves

Overload Pickup Level

Motor Current Unbalance Biasing

Main Factors and Elements Comprising the Thermal Model are:

Overload Pickup Level and Overload Curve

Running and Stopped Cooling Time Constants

Hot/Cold Stall Time Ratio

RTD & Unbalance Biasing

Motor State Machine

Start Inhibit

Thermal Modeling

Page 26: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

26

Thermal Modeling 

600%

If the motor has been designed conservatively, the portion of the acceleration curveunder the motor thermal limits curve is less than a third to a half in terms of trip time,and the motor has been applied conservatively (during acceleration or running theacceleration and thermal limits curve do not cross) then thermal model settings canbe set easily.

If the acceleration curvesand the thermal overloadcurves are very close,accuracy in the settingsbecomes very important inorder to ensure reliablemotor protection withoutnuisance tripping.

Page 27: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

27

Thermal Model - Thermal Capacity Used

Thermal Capacity Used (TCU) is a criterion selected in thermalmodel to evaluate thermal condition of the motor.

TCU is defined as percentage of motor thermal limit utilizedduring motor operation.

Thermal Limit of the model is dictated by overload curveconstructed in the motor protection device in the reference tothermal damage curves normally supplied by motormanufacturer.

IEEE Std 620-1996 provides the guidelines for the presentationof motor thermal limit curves.

Motor protection device is equipped with set of standardcurves and capable to construct customized curves for anymotor application.

Page 28: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

28

Thermal Model - Thermal Capacity Used

We will use the following model to aid in a better understanding of motor thermalmodeling concepts. The motor’s thermal capacity, that is to say, the amount of heatenergy the motor can hold, will be represented by the glass vessel. The lava like fluidfilling the vessel will represent thermal energy or heat energy that has beenabsorbed by the motor.

Page 29: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

29

Thermal Model - Thermal Capacity Used

The sources of thermal energy that will fill the vessel or heating the motor are:

• Ambient temperature

• Motor losses due to current unbalances and I squared T

• Motor heating due to a start

Page 30: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

30

Thermal Model - Thermal Capacity Used

Motor cooling will be represented by:

• The vapour evaporating from the surface of the liquid when the motor is runningor stopped will represent the motors ability to dissipate heat.

• The fan is representative of the additional cooling effect of the motor’s coolingsystem which is commonly a fan mounted on the motor shaft.

Page 31: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

31

% Motor current

Time

Motor Thermaldamage curve

600%

100

30

100% 300%

5

1

2

10

MotorAcceleration curve

Thermal Modeling

Now that we understand what thethermal model is trying to do let’s seehow it accomplishes this task withthe following hypothetical situation.

For a given motor, the thermaldamage and acceleration curves areshown in this diagram. From a quicklook at the motor curves we can seethat the acceleration curve barely fitsunder the stall limits portion of thethermal limits curve. The protectionrelay tripped 10 second into the start.The customer notes from the relay

data that during the start, the motordrew 600% rated current for for 4seconds and then the currentdropped to 300% for only 6 secondsbefore the relay tripped.

Given that the thermal damage curvewas selected correctly the customerwants to know why the relay trippedthe motor even though the currentdraw did not exceed the thermaldamage curve limits?

Page 32: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

32

TCU Calculation for the Hot Motor 

Example: Cold and Hot Safe Stall Times are 10 and 8 seconds.

HCR is calculated as 8 sec / 10 sec= 0.8

TCU of the Hot Motor running at allowed overload (SF•FLA) fora long time is calculated as (1-0.8) • 100% = 20%

Thermal algorithm effectively shifts an overload curve down,decreasing time before trip by 20%

In the hot motor TCU calculation, thermal algorithm accountsfor loads lower than the allowed overload.

%1001   ×

×

=  HCRFLA SF 

 I TCU 

  eq

 END

• Ieq – equivalent heating motor current; FLA – full load motorcurrent; SF – motor service factor.

Page 33: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

33

The area under the thermal damage curve represents the thermal capacity of themotor and the area under the acceleration curve represents the thermal capacity usedto start the motor. During the first 4 seconds of the start, the motor draws 600%current. This current level is greater than the motors full load current rating andtherefore the percentage of thermal capacity used will increase, (the vessel will fill).

TCU Example

From the graph we can seethat if the motor drew600% for 5 seconds 100%of the motors thermalcapacity would have beenused.

The motor draws 600% for4 seconds, so four fifth’s or80% of the motors thermalcapacity was used duringthis portion of the motorsacceleration. This can beimagined as 80% of thevessel being filled withthermal energy.

Page 34: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

34

TCU ExampleTo determine how long the motor can run when the motor’s current draw drops to300%, the thermal capacity already used at 600% must be taken into account. Fromthe graph we can see that motor can draw 300% of its rated current for 30 seconds ifno thermal capacity had been used. Since 80% of the motors thermal capacity hasalready been used which represents 24 of the 30 seconds available at 300% themotor can only draw 300% current for an additional 6 seconds. This can berepresented visually by moving the area of 4 seconds at 600% current into the areaof 30 seconds by 300% current.

When the motor’s currentdraw dropped to 300%, therelay could allow the motorto continue to run for anadditional 6 seconds beforethe motor’s ThermalCapacity Used reached100% at which time therelay had to trip the motor.

Page 35: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

35

Start Inhibit Upon a start, the inrush current is above the motor’s full load current causing thethermal capacity used within the motor to rise rapidly. GE Multilin MotorManagement Relays “learn” the amount of thermal capacity required to start themotor and if the start inhibit function is enabled, use this information in addition tothe thermal capacity used data to ensure that there is enough thermal capacitywithin the motor for a successful start before a start is attempted.

Page 36: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

36

Start Inhibit Example

Under such a condition, if the relay had the Start Inhibit feature enabled, the relaywould lock-out the motor start until the thermal capacity of the motor haddropped to 60% such that a successful motor start could be achieved without thethermal capacity used exceeding the volume of the vessel.

Page 37: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

37

• Select O/L Curve

• Determine Overload Pickup

• Hot/Cold Safe Stall Ratio

• Unbalanced Bias

• Cooling Times and Start Inhibit

• RTD Biasing

Thermal Model

Page 38: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

38

Typical Motor Thermal limits Curves

   T    i   m   e    i   n   s   e   c   o   n    d   s

Phase current in multiplies of FLC

Acceleration curve@100% voltage

Acceleration curve @80% rated voltage

Thermal limit curve whenmotor is cold

Thermal limit curvewhen motor is hot

Page 39: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

39

Thermal Model - Thermal Limit Curves Thermal limit plot includes

hot and cold runningoverload limit curves (5 & 6)and hot and cold lockedrotor limit curves (3 & 4 ) asa standard.

In special cases plot can befurnished with accelerationcurves for the range ofoperational voltages.

MPD (motor protectiondevice) Overload curve (2)should be selected to fit inbetween cold and hot motorthermal limit curves.

Page 40: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

40

Relay overload curve 3

Thermal Model - Thermal Limit Curves

Page 41: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

41

Standard Overload Curves Equation

Where:TDM is relay setpoint “TDMultiplier”

I - current in multiples of FLA

Page 42: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

42

Overload Curve SelectionThe overload element uses a Thermal Capacity algorithm to determine when to activatean overload trip. The volume of this vessel is representative of the thermal capacity ofthe motor. A running motor will have some level thermal capacity used due to the losseswhich will be represented by a certain level of thermal capacity in our vessel .

Page 43: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

43

Overload Curve Selection

Whenever the current exceeds the Overload Pickup, the vessel begins to fill with heat energy. Thevalve that controls how fast the vessel is filled is proportional to the amount of overload current.For example if the current is just over the overload pick up level, the imaginary valve is partiallyopen and the vessel is being filled slowly, versus the situation where the current far exceeds thepickup level, in which case one could imagine the valve as fully open and the vessel being quicklyfilled with thermal energy. When the vessel is full, the vessel starts to overflow and a trip is issued.

If there is some thermal energyin the vessel from a previousoverload condition, theremaining volume of vessel willbe first filled before a tripcommand is issued by therelay. The overload trip willonly occur at the time specifiedon the curve and the overloadcurrent is being drawn atstable rate (no ramping ofcurrent).

Page 44: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

44

If the motor startingcurrent begins toinfringe on thethermal damagecurves or if themotor is called uponto drive a highinertia load suchthat theacceleration timeexceeds the safestall time, custom orvoltage dependentoverload curve maybe required.

Overload Curve Selection

Page 45: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

45

Thermal Model Behavior - Long Starts

The main issue is that the duration of the high inertia loadstarts is longer than the allowed motor safe stall time. Thatis why the standard thermal algorithm method can not beapplied.

For these starts, thermal model must account for thecurrent change during acceleration and also use theacceleration thermal limits for TCU calculations.

Motor thermal limit is growing along with motor rotationspeed during acceleration.

Starting current is proportional to system voltage duringmotor acceleration, thus voltage could be a good indicationof the current level corresponding to the locked rotorconditions.

Voltage dependant dynamic thermal limit curve isemployed to enhance the thermal model algorithm.

Page 46: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

46

Overload Curve Selection

The two graphs illustrate the resultantoverload protection curves for 80% and100% line voltage, respectively. Forvoltages in between, the motor relay willshift the acceleration thermal limit curvelinearly and constantly based on measuredline voltage during a motor start.

Page 47: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

47

Thermal Model Behavior - Long Starts (cont.)

Let us assume that in the high inertia start application, themotor data is the same except the safe stall times, i.e. coldSST @ 100% is 8 seconds.

1

10

100

1000

0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00

PER UNIT CURRENT (X FLA)

   T   I   M   E   (   S   E   C   )

0

10

20

30

40

50

60

70

80

90

100

0 2 4 6 8 10 12 14

TIME (SEC)

   T   C   U   (   %   )

Application of the standard thermal model curve causes thetrip in about 10 seconds in the middle of the acceleration.

Page 48: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

48

Thermal Model Behavior - Long Starts (cont.)

For high inertia starts, one should apply the accelerationthermal limit curves instead of locked rotor thermal limitcurves and motor can start successfully without tripping.

This method is relevant for the situation with the constantterminal voltage of 100%.

What happens if voltage deviates from 100% ?

1

10

100

1000

0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00

PER UNIT CURRENT (X FLA)

   T   I   M   E   (   S   E   C   )

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 2 4 6 8 10 12 14 16 18

TIME (SEC)

   T   C   U   (   %   )

Page 49: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

49

Thermal Model Behavior - Why motor is in danger? 

MOTOR VOLTAGE MOTOR SPEEDMOTOR CURRENT

(TIMES OF FLA)

THERMAL LIMIT

TIME (SEC)

THERMAL LIMIT

( I²T)

0% 6 8 288

80% 4.8 40 922

0% 4.8 12.5 288

80% 3.8 62 922

100%

80%

Thermal Limit is a function of the motor speed. Starting current is proportional to the terminal voltage. Let us assume that the motor current is the only parameter

to be sensed by motor relay and the acceleration thermallimit curve from the previous slide is applied to protect themotor.

This situation implies the danger to burn the stalled motor. @ 80% voltage start motor trip time is 40 seconds instead

of required 12.5 seconds.

Page 50: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

50

Thermal Model Behavior - Voltage Dependant Curves

Voltage dependant overload curve in 469 motor relay is provided tohandle the situation described in the previous slide.

The acceleration section of the overload curve dynamically shifts inresponse to motor voltage deviations.

Thermal model accumulates almost the same TCU during 100% and80% voltage motor starts.

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

100.00

0 5 10 15 20 25 30 35 40

TIME (SEC)

   T   C   U   (   %   )

1

10

100

1000

0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00

PER UNIT CURRENT (X FLA)

   T   I   M   E   (   S   E   C   )

 

100% VOLTAGE STARTTIME-17 SEC, TCU-91%

80% VOLTAGE STARTTIME-36 SEC, TCU-93%

Page 51: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

51

• Select O/L Curve

• Determine Overload Pickup

• Hot/Cold Safe Stall Ratio

• Unbalanced Bias

• Cooling Times and Start Inhibit

• RTD Biasing

Thermal Model

Page 52: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

52

Determining The Overload Pickup:

• The protection engineer will typically set the overload pickup to 100%of the motors capability. For motors with a 1.15 service factor, amaximum pickup of 125% of the full load current can be selectedwhile the maximum pickup for 1.0 service factor motors is 115% of fullload current. Having said this, it is common practice to set the pick upto no more than the rated motor full load current plus no more than10% of the service factor unless there is another independentmeasure of motor temperature such as stator RTD's.

• If the motor’s winding temperature is also being directly monitoredby an RTD biasing function to the thermal model, the overload pickupcan be safely increased to the maximum allowable value for thatmotor.

• Note that the motor feeder cables are normally sized at 1.25 times themotor’s full load current rating which would limit the motor overloadpickup setting to a maximum of 125%.

Thermal Model

Page 53: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

53

• Select O/L Curve

• Determine Overload Pickup

• Hot/Cold Safe Stall Ratio (2 methods)

• Unbalanced Bias

• Cooling Times and Start Inhibit

• RTD Biasing

Thermal Model

Page 54: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

54

Thermal Model

If the thermal limits curves are being used to determine

the HOT/COLD ratio proceed as follows:

• From the thermal limits curves run a lineperpendicular to the current axis that intersects thehot and cold curves at the stall point

• Draw a lines from each points of intersection to thetime axis.

Page 55: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

55

• Record the corresponding times. In this case 10 and 15seconds respectively.

• The Hot/cold ratio can now be calculated as follows:The HOT/COLD ratio = 10/15 = 0.67

NOTE:

If hot and cold times are not provided and only one

curve is given verify with the manufacturer that it is the

hot curve ( which is the worst case). If the supplied curve

is the hot curve then the Hot/ Cold ratio can be set to 1.0

Thermal Model

Page 56: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

56

Hot/Cold Safe StallTime Ratio

COLD

 HOT 

 LRT 

 LRT  HCR =

Motor Data SheetMethod

Thermal Model

HCR = 30s/35s = 0.86

Page 57: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

57

With no negative sequence or motor unbalance currents:

TC_end = I pu(1-hot/cold) x100%

If we assume 1pu TC = 1 (1-10/15) 100%

= (1-0.667)100%

= 33.3% (After 5 time constants)

Thermal Model

If you have an ideal motor on a perfectly balanced system, that is a system that issupplying power with no negative sequence components, using the hot/cold stall ratio youcould calculate the thermal capacity that the motor would have used once the motor hasbeen running at rated current for an extended period of time.

For example, the motor would have used 33.3% of its total thermal capacity under thefollowing conditions:

• Hot/cold ratio was 10/15.

• Motor had run for at least 5 times its running cooling time constant.

• motor was drawing 100% rated current.

• Zero current unbalance

Unfortunately, there are no ideal motors or power systems that provide purely positivesequence power and so we need to deal with this next.

Page 58: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

58

• Select O/L Curve

• Determine Overload Pickup

• Hot/Cold Safe Stall Ratio

• Unbalanced Bias

• Cooling Times and Start Inhibit

• RTD Biasing

Thermal Model

Page 59: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

59

Thermal Model - Current Unbalance

A positive sequence set of vectors consists of three equal vectors that aredisplaced by 120 degrees and have a rotational phase sequence of ABC.

A negative sequence set of vectors consist of three equal vectors that aredisplaced by 120 degrees, but have a rotational phase sequence of ACB.

In the real world, the power system is never perfectly balanced thereforenegative sequence currents will always exist.

Page 60: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

60

• Rotor Bars

• Rotor 

• Stator 

N

S

N    

    N

    S

       S

       S

S  

  S   N  

 N

    N

Thermal Model - Current Unbalance

Negative sequence currents (orunbalanced phase currents) will causeadditional rotor heating that will not beaccounted for by electromechanicalrelays and may not be accounted for insome electronic protective relays.

Page 61: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

61

Thermal Model - Current Unbalance

Current Unbalance causes extra heating not accounted by theregular thermal model.

Main causes of current unbalance Blown fuses

Loose connections

Stator turn-to-turn faults

System voltage distortion and unbalance

Faults

Page 62: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

62

Thermal Model - Current Unbalance

Equivalent heating motor current is employed to bias thermalmodel in response to current unbalance.

))(1(  2

12

2 I  I  K  I  I 

 M  EQ  ×

Im - real motor current; K - unbalance bias factor; I1 & I2 - positiveand negative sequence components of motor current.

K factor reflects the degree of extra heating caused by the negativesequence component of the motor current. Enter K value into motorrelay settings.

IEEE guidelines for typical and conservative estimates of K.

2175

 LRC  I  K  = TYPICAL   2

230 LRC 

 I  K  = CONSERVATIVE

• ILRC - Motor Locked Rotor Current @ 100% voltage (in pu)

Page 63: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

63

Thermal Model - Current Unbalance

The graph shows recommended motor derating as a function of voltage unbalancethat is recommended by NEMA. Assuming a typical induction motor with an inrush of6 x the motors Full Load Current rating and a negative sequence impedance of 0.167,voltage unbalances of 1,2,3,4,5 % are equivalent to a current unbalances of6,12,18,24,30% respectively.

Based on this assumption, thegraph illustrates the amount ofmotor derating for differentvalues of k entered for thesetpoint Unbalance Bias kFactor. Note that the curvecreated when k=8 is almostidentical to the NEMA deratingcurve.

If a k value of 0 is entered, theunbalance biasing is defeatedand the overload curve willtime out against the measuredper unit motor current.

K = 8

Page 64: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

64

• Select O/L Curve

• Determine Overload Pickup

• Hot/Cold Safe Stall Ratio

• Unbalanced Bias

• Cooling Times and Start Inhibit

• RTD Biasing

Thermal Model

Page 65: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

65

Thermal Model - Motor Cooling Curves

TCU decay of the motorrunning @ full load.

0

10

20

30

40

50

60

70

80

90

100

0 1 2 3 4 5 6

TIME (MULTIPLES OF TAU)

   T   H   E   R   M   A   L   C   A   P   A   C   I   T   Y   U   S   E   D   (   %   )

0

10

20

30

40

50

60

70

80

90

100

0 1 2 3 4 5 6

TIME (MULTIPLES OF TAU)

   T   H   E   R   M   A   L   C   A   P   A   C   I   T   Y   U   S   E   D   (   %   )

 

TCU start

TCU after time=τ

ExpectedTCU end

TCU decay of thestopped motor.

TCU start

TCU after time=τ

ExpectedTCU end

Page 66: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

66

Thermal Model - Motor Cooling Motor cooling is characterized by separate cooling time

constants (CTC) for running and stopped motor states. Typicalratio of the stopped to running CTC is 2/1

CTC defines the rate of the TCU exponential decay, whenmotor current doesn’t exceed the overload level.

Thermal Model Cooling Motor Tripped

Page 67: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

67

Thermal Model Cooling 100% load

TCUSED_END= (1/1)(1-0.8/1)X100%

TCUSED_END= 20%

TCUSED_END= 20%

Thermal Model - Motor Cooling

Page 68: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

68

Thermal Model Cooling 80% load

TCUSED_END= (0.8/1)(1-0.8/1)X100%

TCUSED_END= 16%

TCUSED_END= 16%

Thermal Model - Motor Cooling

Page 69: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

69

Thermal Model Cooling100% load - Running

Thermal Model - Motor Cooling

• Enter the Running & Cooling Time Constants into the motor relay settings

• Do not enter the actual cooling time in the motor relay settings

• It takes the motor typically 5 time constants to cool.

• If the motor data sheet says it takes 150 mins to cool, enter a time constant of 30minutes.

• If the motor data sheet says it takes 75 mins to cool, enter a time constant of 15minutes.

Thermal Model Cooling Motor Tripped

Page 70: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

70

Thermal Model Cooling Motor Stopped Thermal Model Cooling Motor Tripped

Thermal Model - Motor Cooling

When the motor is stopped, it’s thermal capacity used value will decay according to thesame formula shown previously. If the thermal capacity used were at 100% before stoppingthe motor, the thermal capacity used will take 5 time constants or 2.5 hours to decay. Notethat after only three time constants, the motor would be within 5% of its final value of zerofrom it’s initial value. If the same motor were stopped with 85% of its thermal capacityused, it would decay according to the same formula taking 5 time constants to decay to zerocompletely and would be within 5% of zero form it’s initial value after 3 time constants.

Page 71: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

71

• Select O/L Curve

• Determine Overload Pickup

• Hot/Cold Safe Stall Ratio

• Unbalanced Bias

• Cooling Times and Start Inhibit

• RTD Biasing

Thermal Model

Page 72: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

72

Thermal Model - RTD Biasing 

MAX POINTTEMP: 155°CTCU: 100%

MID POINTTEMP: 130°C

TCU: 25%

MIN POINTTEMP: 40°C

TCU: 0%

TCU calculation at centerpoint of RTD bias curve:

%100)1(   ×−=   HCRTCU CENTER

TCU Calculation at lowersection of RTD bias curve:

CENTER

 MIN CENTER

 MIN  ACTUAL

 RTD  TCU 

T T 

T T TCU    ×

  

 

−=

TCU Calculation at highersection of RTD bias curve:

( )  CENTERCENTER

CENTER MAX 

CENTER ACTUAL

 RTD  TCU TCU 

T T 

T T TCU    +−×

  

 

−=   100

Page 73: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

73

RTD Bias Curve Example

• RTD input is a indicator of the thermalcapacity used dependent on statortemperature (very slow).

• The relay will use the calculated thermalcapacity unless the RTD thermalcapacity is higher.

Thermal Model - RTD Biasing

Page 74: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

74

Additional Common Induction and Synchronous MotorProtective elements:

• Short circuit• Ground Fault• Differential Trip• Current Unbalance• Single Phasing• Undervoltage & Overvoltage Protection• Mechanical Jam Detection• Undercurrent• Underpower• Acceleration Timer

 Additional Protection Elements

Page 75: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

75

Short Circuit Trip

The short circuit element provides protection for excessively high overcurrentfaults.

Phase-to-phase and phase-to-ground faults are common types of short circuits.

The Short Circuit trip element is coordinated with external up stream fuses suchthat the element will operate first.

Page 76: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

76

Short Circuit Trip

When a motor starts, the starting current(which is typically 6 times the Full Load Current(FLC) rating of the motor) has asymmetricalcomponents. These asymmetrical currentsmay cause one phase to see as much as 1.7times the normal RMS starting current. As aresult the pickup of the short circuit elementmust be set higher than the maximumasymmetrical starting currents seen by thephase CTs to avoid nuisance tripping. The ruleof thumb is to set the the short circuitprotection pick up to a value which is at least1.7 times the maximum expected symmetricalstarting current of the motor. This allows themotor to start without nuisance tripping.

It is important to note that the device that therelay is to control under such conditions musthave an interrupting capacity equal to orgreater then the maximum available faultcurrent.

 

1

10

100

1000

10000

100000

        2        0

        6        0

        1        0        1

        1        4        0

        1        8        0

        2        2        0

        2        6        0

        3        0        0

        3        4        0

        3        8        0

        4        2        0

        4        6        0

        5        0        0

        5        4        0

        5        8        0

        6        0        5

Percent Full Load

   T   i  m  e   (  s  e  c  o  n   d  s   )

 Acceleration curve (motor

current during starting)

Locked Rotor cur rent

Motor Thermal Limit

Instantaneous

Overcurrent

Protection

Page 77: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

77

1

10

100

1000

10000

100000

        2        0

        6        0

        1        0        1

        1        4        0

        1        8        0

        2        2        0

        2        6        0

        3        0        0

        3        4        0

        3        8        0

        4        2        0

        4        6        0

        5        0        0

        5        4        0

        5        8        0

        6        0        5

Percent Full Load

   T   i  m  e

   (  s  e  c  o  n

   d  s

   )

 Acceleration curve (motor

current during starting)

Locked Rotor current

Motor Thermal Limit

Instantaneous

Overcurrent

Protection

Short Circuit Protection

Page 78: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

78

Resistive Grounded System and a Inductive Grounded System

Ground Fault 

Page 79: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

79

Ground Fault 

A ground fault is a fault that creates a path for current to flowfrom one of the phases directly to the neutral through the earthbypassing the load.

This current is sometimes referred to as zero sequence current.

Damage to a phase conductors insulation and internal shorts dueto moisture within the motor are common causes of groundfaults.

A strategy that is typically used to limit the level of the groundfault current is to connect an impedance between the suppliesneutral and ground. This impedance can be in the form of aresistor or grounding transformer sized to ensure that themaximum ground fault current is limit to no more then 10 ampsto reduce the chances of metal damage to the motor.

Page 80: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

80

Best

Zero Sequence CT

Ground Fault 

Page 81: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

81

Zero Sequence CT Connection

Ground Fault 

All phase conductors are passed through the window of the same CTreferred to as the zero sequence CT. Under normal circumstances, thethree phase currents will sum to zero resulting in an output of zero fromthe Zero Sequence CT’s secondary. If one of the motors phases were toshort to ground, the sum of the phase currents would no longer equalzero causing a current to flow in the secondary of the zero sequence.This current would be detected by the motor relay as a ground fault.

There are several ways by which a groundfault can be detected. The most desirablemethod is to use the Zero Sequence CTapproach, which is considered the bestmethod of ground fault detection methodsdue to its sensitivity and inherent noiseimmunity.

Page 82: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

82

Residual Ground Fault Connection

Ground Fault 

Page 83: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

83

Residual Ground Fault Connection

Ground Fault 

This configuration is inherently less sensitive then that of the zerosequence configuration owing to the fact that the CTs are not perfectlymatched. During the motor start, the motor’s phase currents typicallyrise to magnitudes in excess of 6 times the motors full load current. Theslight mismatch of the CTs combined with the relatively large phasecurrent magnitudes produce a false residual current which will be seenby the relay. This current will be misinterpreted by the motor relay as aground fault unless the ground fault element’s pickup is set high enoughto disregard this error.

If the cables are too large to fit throughthe Zero sequence CT’s window or thetrench is too narrow to fit the ZeroSequence CT, the residual ground faultconfiguration can be used.

Page 84: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

84

DC Offset

Ground Fault - Asymmetrical Starting Current 

This diagram shows the Asymmetrical Starting Currents. When a motor first starts using aresidual ground fault connection, the three phases do not sum to zero because of the DCoffset in each of the three phase CTs. This difference appears as a ground fault current andwill cause a ground fault trip if the trip level and time delay are programmed correctly. Ifthe residual ground fault connection is to be used, the Ground Fault trip delay must be setto a delay other than instantaneous to avoid a nuisance ground fault trip, in addition toallowing enough time for the asymmetrical starting current offsets to even out.

Page 85: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

85

Ground Fault 

This slide shows the noise generated during a start and a run whenresidual ground scheme is used.

None of this noise would be seen by the motor relay using a zerosequence CT scheme.

Page 86: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

86

Phase Differential

Consists of three instantaneous overcurrent elements for phasedifferential protection.

Differential protection may be considered the first line ofprotection for internal phase to phase or phase to groundfaults. In the event of such faults, the quick response of thedifferential element may limit the damage that may haveotherwise occurred to the motor.

Page 87: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

87

Phase Differential

The Differential Trip element function can only be used if both sides of each stator phaseare brought out of the motor for external connection such that the phase current goinginto and out of each phase can be measured.

The differential element subtracts the current coming out of each phase from the currentgoing into each phase and compares the result or difference with the differential PickupLevel. If this difference is equal to or greater then the pickup level for a period of timegreater a user specified delay, a trip will occur.

Separate pickup levels and delay times are provided for the motor starting and runningconditions.

GE Multilin motor protective relays support both 3 and 6 CT configurations. In thisexample both sides of each of the motors stator phases are being past through a singleCT. This is called core balance method and is the most desirable owing to it’s sensitivityand noise immunity.

The level may be set more sensitive if the Differential CTs are connected in core balanceconfiguration (3 CTs).

Core Balance Method

Page 88: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

88

Phase Differential

If 6 CTs are used in a summing configuration, during motor starting, the values from thetwo CTs on each phase may not be equal as the CTs are not perfectly identical.

Asymmetrical currents may cause the CTs on each phase to have different outputs. Toprevent nuisance tripping in this configuration, the starting differential level may have tobe set less sensitive, or the starting differential time delay may have to be extended toride through the problem period during start. The running differential delay can then befine tuned to an application such that it responds very fast and is sensitive to lowdifferential current levels.

Summation Method

Page 89: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

89

Phase Differential

This method allows different CT ratios for system/line and neutral

This method has a dual slope characteristic. The main purpose of the percent-slope characteristic is toprevent a maloperation caused by unbalances between CTs during external faults. CT unbalances ariseas a result CT accuracy errors or CT saturation.

This method has a built-in CT Saturation Detector. External faults near generators typically result in verylarge time constants of DC components in the fault currents. Also, when energizing a step-uptransformer, the inrush current being limited only by the machine impedance may be significant and maylast for a very long time. When saturation is detected the element will make an additional check on the

angle between the neutral and output current. If this angle indicates an internal fault, then tripping ispermitted.

Percent Differential Method

Page 90: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

90

Current Unbalance and Single Phasing Protection

Current Unbalance Detection (Alarm)

System voltage unbalance1% voltage imbalance translates into a

6% current unbalance

Stator turn-to-turn faults

If voltage unbalance is typically 2%, thenset alarm to 15% (> 2 x 6%)

Motor Single Phasing (Trip)

Blown Fuses

Bad Connections

20% Trip Level is recommended

%1002 _ 

1 _  ××= I 

 I  K  I 

UN 

Where, K – adjustment factorI_1 –positive sequence currentI_2 –negative sequence current

 FLA

 AVG

 FLA AVG

 FLA AVG

 I 

 I  K then I  I if  

 K then I  I if  

=≤

=≥   1

Current Unbalance (%)

K Adjustment Factor

Single Phasing is declared when: 2 seconds after 40% current unbalance has been detected. Average current is above 25% of FLA and the current in one of the phases is

less then 2% of FLA.

Page 91: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

91

If an induction motor operating at full load is subjected toan under voltage condition, the following effects willoccur (Moisey, 1997):

• Full load speed will decrease

• Efficiency will decrease

• Power factor will increase

• Full load current will increase

• Temperature will increase

Under Voltage

Page 92: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

92

When the motor is running in an overvoltage condition,the following affects will occur (Moisey, 1997):

• Slip will decrease because slip is inverselyproportional to the square of the voltage

• Efficiency will increase slightly and power factorwill decrease because the current being drawn bythe motor will decrease

• Temperature rise will decrease because the currenthas decreased (based on the formula I2t)

• Most motors are designed close to the saturationpoint……..increasing the V/HZ ratio could causesaturation of air gap flux causing heating

Over Voltage

Page 93: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

93

The overall result of an under or overvoltage condition is an increase incurrent and motor heating and a reduction in overall motor performance.

The undervoltage trip should be set to 90% of nameplate unless otherwisestated on the data sheets. Motors that are connected to the same source,may experience a temporary undervoltage when one of motors starts. Tooverride these temporary sags, a time delay setpoint has beenincorporated into undervoltage element.

The over voltage element should be set to 110% of the motors nameplateunless otherwise started in the data sheets.

The undervoltage element can be considered as backup protection for thethermal overload element. If the voltage decreases, the current willincrease, causing an overload trip. In some cases, if an undervoltagecondition exists it may be desirable to trip the motor faster than theoverload element.

Under & Over Voltage Protection

Page 94: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

94

Possible causes of motor mechanical jam:

• Worn motor bearings

• Load mechanical breakage

• Driven load process failure

Element is used to disconnect the motor on abnormaloverload conditions before motor stalls.

The Mechanical Jam element is designed to operatefor running load jams.

In terms of relay operation, element prevents motorfrom reaching 100% of thermal capacity whileMechanical Jam is detected. It helps to avoidmechanical breakage of the driven load and reducestart inhibit waiting time.

Mechanical Jam

Page 95: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

95

TRIP

Undercurrent Block Undercurrent Alarm Delay

Undercurrent 

The Undercurrent element is active only when the motor is running. It is blockedupon the initiation of a motor start for the time defined by the U/C BLOCK FROMSTART setpoint.

A trip or alarm will occurs once the magnitude Ia, Ib, or Ic falls below the pickuplevel for the time specified by the UNDERCURRENT ALARM DELAY.

This is useful forindicating the ofloss of suction ina pumpapplication, or abroken belt in aconveyorapplication.

Page 96: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

96

Trip orAlarm

Underpower 

• A value other then zero must be entered to ensure the underpower element is blockedwhen the motor is stopped. The Underpower element is active only when the motor isrunning, and will be blocked upon the initiation of a motor start for a period of time definedby the BLOCK ELEMENT FROM START setpoint. This time delay may be useful inapplications which require the motor to be running for a period of time before full power isrequired as is the case in centrifugal pump or fan applications.

• When enabled, if the magnitude of the three phase total power falls below the pickup Levelfor a period of time specified by the delay, a trip or alarm will be generated.

The secondmethod of loadloss detection isto use theunderpowerelement.

Page 97: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

97

 Acceleration Timer 

For example, a given motor should always complete a start within 2 seconds. If the safestall time is 8 seconds and a failure occurred such that the motor was held in a stallcondition, the motor would normally remain at stall for a total of 8 seconds before thethermal model would generate a trip. The accelerator timer could be configured togenerate a trip if the motor remained at stall for more then 3 seconds thereby reducingthe stress on both the motor and driven equipment.

Note that some soft starts limit the motors starting current to less then the motors ratedfull load current. Therefore if the relay does not see the motor’s current rise to a valuegreater than the motors rated full load current within 1 second after a start, theacceleration timer will be ignored.

The motor relay’s Thermal Model isdesigned to protect the motor under bothstarting and overload conditions.

The Acceleration Timer may enhance themotor protection scheme.

Page 98: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

98

Additional Protective Elements for SynchronousMachines:

• Field application

• Field temp. monitoring

Monitoring/Control Elements for SynchronousMachines:

• Power Factor Correction

 Additional Protection Elements

Page 99: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

99

• Starts per hour

• Time between starts

• RTD alarm and trip settings (stator, bearing, etc.)

• Two speed motor protection

• Load averaging filter for cyclic load applications

• Reduced voltage starting supervision

• Variable frequency filter allowing accurate sensing and calculation of theanalog values in VFD applications

• Analog input differential calculation for dual drives applications

• Speed counter trip and alarm

• Universal digital counter trip and alarm

• Pulsing KWh and Kvarh output

• Trip coil supervision

• Emergency Restart Input

• Undervoltage auto restart (additional element per special order).

• Experimental broken rotor bar detection system

 Additional Special Features Available In MotorManagement Relays

Page 100: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

100

CT Rating, Voltage Sensing

FLA & Ground CT

Thermal Model Settings

Overload Pickup, Overload Curve, Unbalance Bias K Factor, Hot/Cold Safe Stall Ratio,Running & Stopped Cooling Time Constants, RTD Bias

Short Circuit Trip

Current Unbalance Alarm & Trip

Ground Fault

Acceleration Trip

Start Inhibit

Starts per hour, Time Between Starts

RTD Alarm & Trip

Phase Differential Trip

Undervoltage, Overvoltage Trip

Setting Example

The following is example of how todetermine the relay setpoints for a specificmotor that has been appliedconservatively. This is only an example forteaching purposes and may not address allissues relating to your specific application.It is recommended that the setpoints foryour motor protective relaying applicationbe determined by your local protectionengineer.

Page 101: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

101

CT: 50% <FLA <100%

300/5

Setting ExampleSelect CT Rating, Voltage Sensing

Phase CT

The phase CT should be chosen such thatthe FLA is 50% to 100% of CT primary. Sincethe FLA is 297 a 300:5 CT may be chosen.

Voltage Sensing

Enter the connection type and ratio. Entermotor nameplate voltage. In this case, a14400/120 PT will be used, so 120:1 ratio.

Page 102: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

102

Set:

FLA = 297 A

GF <=> System ?

Setting ExampleSelect FLA, Ground CT

Motor FLC

Set the Motor Full Load Amps to 297A,as specified by the data sheets.

Ground CT

For high resistive grounded systems,sensitive ground detection is possiblewith the 50:0.025 CT. On solidlygrounded or low resistive groundedsystems where the fault current ismuch higher, a 1A or 5A secondaryCT should be used. If residual groundfault connection is to be used, theground fault CT ratio most equal thephase CT ratio. If residualconnection is used, pickup levels andtimers must be set with respect tothe acceleration time. The zerosequence CT chosen needs to be ableto handle all potential fault levelswithout saturating.

Page 103: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

103

Set:

Overload Pickup= 1.15 x FLA

Setting ExampleThermal Overload Pickup

 

Overload Pickup

The overload pickup is set to the maximumallowed by the service factor of the motor.

For motors with a 1.15 service factor, amaximum pickup of 125% of the full loadcurrent can be selected.

While the maximum pickup for 1.0 servicefactor motors is 115% of full load current.

Having said this, it is common practice to setthe pick up to no more than the rated motorfull load current plus no more than 10% ofthe service factor unless there is anotherindependent measure of motor temperaturesuch as stator RTD's.

If the motor’s winding temperature is alsobeing directly monitored by an RTD biasingfunction to the thermal model the overloadpickup can be safely increased to themaximum allowable value for that motor.

Note that the motor feeder cables arenormally sized at 1.25 times the motor’s fullload current rating which would limit themotor overload pickup setting to a maximumof 125%.

If service factor is unknown, we must assume1.0

Page 104: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

104

Setting ExampleSelect Overload Curve for Thermal Model

 

Overload Curve

The standard overload curve to be just below the cold thermal limit andabove the hot thermal limit to give maximum process uptime, withoutcompromising protection.

The best fitting curve is curve 3

Page 105: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

105

K=175/LRA 2 = 175/ 5.4 2 = 6

(Typical)

Setting ExampleDetermine Unbalance Bias K Factor for Thermal Model

Unbalance Bias Of Thermal Capacity

Enable the Unbalance Bias of ThermalCapacity so that the heating effect ofunbalance currents is added to theThermal Capacity Used.

K=230/LRA 2 = 230/ 5.4 2 = 8

(Conservative)

Page 106: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

106

Hot/Cold Ratio =30/35

=> 0.86

Setting ExampleDetermine Hot/Cold Safe Stall Ratio for Thermal Model (method 1)

Hot/Cold Curve Ratio

The hot/cold curve ratio is calculated by simply dividing thehot safe stall time by the cold safe stall time or use the motorthermal limits curve. For this example, both are available.Using the data sheets the Hot/Cold Curve Ratioequals 30 / 35 = 0.86

COLD

 HOT 

 LRT 

 LRT  HCR =

Page 107: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

107

Determining Hot/Cold Curve Ratio

Hot/Cold Curve Ratio

If the thermal limits curves are being used to determine the

HOT/COLD ratio proceed as follows:

• From the thermal limits curves run a line perpendicularto the current axis that intersects the hot and coldcurves at the stall point

• Draw lines from each points of intersection to the timeaxis.

• Record the corresponding times. In this case, 6 and 8seconds respectively.

• The Hot/cold ratio can now be calculated as follows:= 6s/8s = 0.75

NOTE:

• If hot and cold times are not provided and only onecurve is given verify with the manufacturer that it is thehot curve ( which is the worst case), then the Hot/ Coldratio should be set to 1.0

Overload Curve Method

 

LRC = 5.4FLA

LRTcold = 8sec

LRThot = 6sec

Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 2)

Page 108: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

108

Thermal Model Cooling100% load - Running

Thermal Model - Motor Cooling

• Enter the Running & Cooling Time Constants into the motor relay settings

• Do not enter the actual cooling time in the motor relay settings

• It takes the motor typically 5 time constants to cool.

• If the motor data sheet says it takes 150 mins to cool, enter a time constant of 30minutes.

• If the motor data sheet says it takes 75 mins to cool, enter a time constant of 15minutes.

Thermal Model Cooling Motor Tripped

Page 109: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

109

Setting ExampleStopped & Running Cool Time Constants

Stopped and Running Cool Time Constants

This information is usually supplied by the motor manufacturerbut is not part of the data that was given with this motor. If RTD’s are present and will be wired to the relay biasing of thethermal model will be used so it is not critical to have thesecooling times from the manufacturer: the default values of 15and 30 minutes can be used for the running and stopped cooltimes respectively.

Page 110: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

110

Setting ExampleDetermine RTD Bias Setpoints for Thermal Model

Enable RTD Biasing

This will enable the temperature from the Stator RTD sensors, to beincluded in the calculations of Thermal Capacity. RTD bias modeldetermines the Thermal Capacity Used based on the temperature of theStator and is separate from the overload model for calculating ThermalCapacity Used. RTD biasing is a back up protection element whichaccounts for such things as loss of cooling or unusually high ambienttemperature. This measured temperature is used to bias or modify thethermal capacity value stored in the motor relay.

 

MAX POINTTEMP: 155°CTCU: 100%

MID POINTTEMP: 130°C

TCU: 25%

MIN POINT

TEMP: 40°CTCU: 0%

Page 111: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

111

Setting ExampleDetermine RTD Bias Setpoints for Thermal Model

 

RTD Bias Function

Set to Enabled/YES

RTD Bias Minimum

Set to 40 ° C which is the ambient temperature obtained from thedata sheets.

RTD Bias Center Point

The center point temperature is set to the motor’s hot runningtemperature and is calculated as follows:

Temperature Rise of Stator + Ambient Temperature.

The temperature rise of the stator is 80 ° C + 10% hot spotallowance, obtained from the data sheets.Therefore, the RTD Center point temperature is set to 900C + 400Cor 130 ° C.

RTD Bias Maximum

This setpoint is set to the rating of the insulation or slightly less.A class F insulation is used in this motor which is rated at 155 ° C,so setting should be 155 ° C.

MAX POINTTEMP: 155°CTCU: 100%

MID POINTTEMP: 130°C

TCU: 25%

MIN POINTTEMP: 40°C

TCU: 0%

• RTD input is a indicator of the thermalcapacity used dependent on statortemperature (very slow).

• Motor relay will use the calculated thermalcapacity unless the RTD thermal capacity is

higher.

Page 112: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

112

Short Circuit Trip

When a motor starts, the starting current(which is typically 6 times the Full Load Current(FLC) rating of the motor) has asymmetricalcomponents. These asymmetrical currentsmay cause one phase to see as much as 1.7times the normal RMS starting current. As aresult the pickup of the short circuit elementmust be set higher than the maximumasymmetrical starting currents seen by thephase CTs to avoid nuisance tripping. The ruleof thumb is to set the the short circuitprotection pick up to a value which is at least1.7 times the maximum expected symmetricalstarting current of the motor. This allows themotor to start without nuisance tripping.

It is important to note that the device that therelay is to control under such conditions musthave an interrupting capacity equal to orgreater then the maximum available faultcurrent.

 

1

10

100

1000

10000

100000

        2        0

        6        0

        1        0        1

        1        4        0

        1        8        0

        2        2        0

        2        6        0

        3        0        0

        3        4        0

        3        8        0

        4        2        0

        4        6        0

        5        0        0

        5        4        0

        5        8        0

        6        0        5

Percent Full Load

   T   i  m  e   (  s  e  c  o  n   d  s   )

 Acceleration curve (motor

current during starting)

Locked Rotor cur rent

Motor Thermal Limit

Instantaneous

Overcurrent

Protection

Page 113: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

113

Setting ExampleDetermine Short Circuit Trip Settings

 

Short Circuit Trip

The short circuit trip should be set above the maximum locked rotor current but below the shortcircuit current of the fuses. The data sheets indicate a maximum locked rotor current of 540%FLC or 5.4 x FLC. A setting of 6 x FLC with a instantaneous time delay will be ideal but nuisancetripping may result due to the asymmetrical starting currents and DC offset. If asymmetricalstarting currents limits the starting capability, set the S/C level higher to a maximum of 9.2 x FLCto override this condition (1.7 x 5.4 = 9.2 where 1.7 is the maximum DC offset for an

asymmetrical current). With 300:5 CT, 9.2 x FLC = 9.2 x 297/300 = 9.10 CT

Page 114: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

114

Setting ExampleDetermine Current Unbalance Alarm/Trip Settings

 

Unbalance Alarm and Trip

The unbalance settings are determined by examining the motor application andmotor design. The heating effect of unbalance will be protected by enablingunbalance input to thermal memory; described previously.

A setting of 10% x FLA for the Unbalance Alarm with a delay of 10 seconds would beappropriate

Trip can be set to 25% x FLA with a delay of 5 seconds.

Page 115: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

115

Setting ExampleGround Fault & Acceleration Trip Settings

 

Ground Fault

Limit the ground fault current to less than 10amps.

In this example, use 0.16 x CT or 0.16 x 50 = 8A

Acceleration Trip

This setpoint should be set higher than the maximum starting time to avoidnuisance tripping when the voltage is lower or for varying loads during acceleration.A value greater than 15 seconds should be entered (based on motor data sheet).

Page 116: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

116

Setting ExampleEnable Start Inhibit

 

Enable Start Inhibit

This function will limit starts when the motor is already hot. The motor relay learnsthe amount of thermal capacity used at start. If the motor is hot, thus having somethermal capacity used, the relay will not allow a start if the available thermalcapacity is less than the required thermal capacity for a start.

For example, if the THERMAL CAPACITY USED for the last 5 starts is 24, 23, 27, 25,and 21% respectively, the LEARNED STARTING CAPACITY is 27% × 1.25 = 33.75%used. If the motor stops with 90% thermal capacity used, a start block will beissued. When the motor has cooled and the level of thermal capacity used hasfallen to 66%, a start will be permitted. If the COOL TIME CONSTANT STOPPEDsetpoint is programmed for 30 minutes, the lockout time will be equal to:

Page 117: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

117

Start Inhibit Upon a start, the inrush current is above the motor’s full load current causing thethermal capacity used within the motor to rise rapidly. GE Multilin MotorManagement Relays “learn” the amount of thermal capacity required to start themotor and if the start inhibit function is enabled, use this information in addition tothe thermal capacity used data to ensure that there is enough thermal capacitywithin the motor for a successful start before a start is attempted.

Page 118: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

118

TCU / Start Inhibit Example

27%

80%

80%

66%

Thermal Capacity required to start

Thermal Capacity used due to Overload

When the motor has cooled and the level ofthermal capacity used has fallen to 66%, astart will be permitted.

If the motor had been running in an overload conditionprior to stopping, the thermal capacity would be somevalue; say 80%.

For example, if the THERMAL CAPACITY USED forthe last 5 starts is 24, 23, 27, 25, and 21%respectively, the LEARNED STARTING CAPACITY is27% × 1.25 = 33.75% used.

If Motor is Stopped:

33%

Page 119: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

119

Setting ExampleStarts/Hr, Time Between Starts

 

Starts/Hour

Starts/Hour can be set to the # of cold starts as per the data sheet.For this example, it is 2

Time Between Starts

In some cases, the motor manufacturer will specify the time between motorstarts. In this example, this information is not given so this feature can bedisabled. However, if the information is given, the time provided on themotor data sheets should be programmed.

Page 120: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

120

Setting ExampleRTD Alarm & Tripping

 

Stator RTDs

RTD trip level should be set at or below the maximum temperature rating ofthe insulation. This example has a class F insulation which has atemperature rating of 155°C, therefore the Stator RTD Trip level should beset to between 140°C to 150°C, with 150° C being maximum. The RTD alarmlevel should be set to a level to provide a warning that the motortemperature is rising.

Bearing RTDs

The Bearing RTD alarm and trip settings will be determined by evaluatingthe temperature specification from the bearing manufacturer.

Page 121: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

121

Phase Differential

The Differential Trip element function can only be used if both sides of each stator phaseare brought out of the motor for external connection such that the phase current goinginto and out of each phase can be measured.

The differential element subtracts the current coming out of each phase from the currentgoing into each phase and compares the result or difference with the differential PickupLevel. If this difference is equal to or greater then the pickup level for a period of timegreater a user specified delay, a trip will occur.

Separate pickup levels and delay times are provided for the motor starting and runningconditions.

Motor protective relays support both 3 and 6 CT configurations. In this example bothsides of each of the motors stator phases are being past through a single CT. This iscalled core balance method and is the most desirable owing to it’s sensitivity and noiseimmunity.

The level may be set more sensitive if the Differential CTs are connected in core balanceconfiguration (3 CTs).

Core Balance Method

Page 122: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

122

Phase Differential

If 6 CTs are used in a summing configuration, during motor starting, the values from the two CTs oneach phase may not be equal as the CTs are not perfectly identical.

Asymmetrical currents may cause the CTs on each phase to have different outputs. To preventnuisance tripping in this configuration, the starting differential level may have to be set less sensitive,and the starting differential time delay may have to be extended to ride through the problem periodduring start. The running differential delay can then be fine tuned to an application such that it

responds very fast and is sensitive to low differential current levels.

Summation Method

Page 123: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

123

The overall result of an under or overvoltage condition is an increase incurrent and motor heating and a reduction in overall motor performance.

The undervoltage trip should be set to 90% of nameplate unless otherwisestated on the data sheets. Motors that are connected to the same source,may experience a temporary undervoltage when one of motors starts. Tooverride these temporary sags, a time delay setpoint should be set.

The overvoltage element should be set to 110% of the motors nameplateunless otherwise started in the data sheets.

Under & Over Voltage Protection

Page 124: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

124

Motor ProtectionMotor Protection

•• 239239

•• 369369

•• 469469

•• M60M60

•• SPMSPM

•• MM2MM2

•• LM10LM10

Page 125: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

125

• Small to medium sized motors

• Pumps, conveyors, compressors, fans, sawmills, mines

• Thermal overload (15 selectable curves)

• Phase short circuit

• Locked rotor / mechanical jam

• Thermal memory lockout

• Single phase/unbalance

• Ground fault O/C

• Overtemperature via stator thermistor and optional 3RTDs (RTD)

• Undercurrent

• Trip/alarm/auxiliary/service outputs

• Setpoint Access, Emergency Restart, External Reset,Option 1, Option 2 digital inputs

• Two speed motor protection

• Current, unbalance, motor load, thermal capacity,temperature metering

• Optional analog output (AN)

• Fault diagnosis – last 5 trip records

• AC/DC control power & flash memory

• RS485 ModBus™ communications

• 40 character illuminated display

• 6 LED indicators

239 Motor Protection

239-RTD-AN

Page 126: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

126

239 Motor Protection

Page 127: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

127

239 Motor Protection

Page 128: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

128

• Thermal model biased with Unbalance

• Thermal Overload Curves (15 + 1 custom)

• Phase short circuit, locked rotor / mechanical jam,variable lockout time

• Single phase/unbalance, ground fault O/C

• Overtemperature 12 RTDs and RTD ThermalCompensation (R)

• Starts/hour, time between starts

• Undercurrent

• Phase Reversal (M)

• Back-Spin Detection (B)

• Ability to "learn" individual motor parameters motorinrush current, cooling rates, and acceleration time

• Starter Failure Feature, Motor Load Averaging Interval

• AC/DC control power & flash memory

• 5 pre-defined digital inputs

• Trip/Alarm/Aux1/Aux2 Relay Outputs

• Load, current, unbalance metering

• Voltage/frequency/power metering (M)

• Event recorder (last 40), waveform capture

• 4 analog outputs (M)

• Front RS232 port & 3 rear RS485 ports

• Modbus Protocol

• Fiber optic link (F)

• Ethernet Port (E)

• 40 character display, 10 LEDs and keypad

369 Motor Protection

369-HI-R-M-0-E

Page 129: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

129

369 Motor Protection

Page 130: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

130

369 Motor Protection

Page 131: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

131

369-RRTD Application

369RRTD

Module

Switchgear Location Motor Location

RS-485 or 

Fiberoptic

Up to

 12 RTDs

or 

Process

Inputs

Power Power,

 AC Sensing,

Control CIrcuits

Page 132: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

132

• Medium & large motors, driven equipment

• Thermal model biased with RTD and/or Unbalance

• Voltage Dependant Curve for Large Inertia Loads

• Phase differential protection

• Mechanical jam, short circuit trip, overload alarm,undercurrent, ground fault, current unbalance

• Starting current & capacity, acceleration time,average motor load, max RTDs, min/max analoginputs

• Power setpoints (PF, W, Var, Underpower)

• Undervoltage & overvoltage

• Underfrequency & overfrequency

• Monitoring setpoints (demand, counters)

• Dual overload curves for 2 speed motors

• Reduced voltage starting control

• A, V, W, var, VA, PF, Hz, Wh, varh, demand, torque,temperature

• Event recorder & waveform capture

• 12 programmable RTDs

• 5 pre-defined & 4 assignable digital inputs, 6 outputs

• 4 analog inputs & 4 programmable analog outputs

• RS232 & RS485 ports

• Modbus protocol

• Complete drawout construction

• New enhanced display (E)

• Available with 10BaseT Ethernet (T)

469 Motor Protection

469-P5-HI-A20-T

Page 133: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

133

469 Motor Protection

Page 134: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

134

469 Motor Protection

Page 135: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

135

• Stator Differential (87) with CT Saturation Detection• Current/Amp Unbalance• Thermal Model (RTD/Unbalance Bias, Programmable Curves)• Voltage Dependant Curve for Large Inertia Loads• Phase, Ground, Neutral IOC• Phase and Neutral Directional OC• Ground TOC• Starts per hour, Time between starts, Restart time delay• Emergency Restart, Mechanical Jam• Acceleration Time Logic• Sensitive Directional Power (32)• Phase Undervoltage & Overvoltage (27/59P)• Auxiliary Undervoltage & Overvoltage (27/59X)• Neutral Overvoltage• VT Fuse Failure for Supervision of Voltage Dependant Functions• Breaker Failure (50BF)• Negative Sequence Overvoltage• FlexLogic with gates and timers• Transducer I/O• Contact Inputs/Outputs• Virtual Inputs/Outputs• Remote Inputs/Outputs• FlexElements (16)• Programmable LED Panels & Optional Pushbuttons• Metering, Event Recorder & Oscillography• DNP, Modbus RTU & UCA Protocols• 6 Setting Groups• Ethernet Port and RS485 port

M60 Motor Protection

M60-G00-HPH-F8F-H6P-M8H-P5C-U5D-WXX

Page 136: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

136

M60 Motor Protection

Page 137: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

137

• Field application

• Reluctance torque synchronizing (collector ring)

• Cage winding & stall protection during start

• Restart lockout for hot rotor

• Reduced voltage starting

• Power factor (pull-out) trip with auto resynchronizing

• Incomplete sequence trip

• Loss of DC field current trip

• Loss of DC field voltage trip

• Field winding overtemperature trip

• PF regulation maximizes efficiency (optional)

• Field voltage, field current, motor amp calibration

• Contactor status input, reduced voltage status input

• Trip/FAR/FCX outputs

• Metering

> AC stator current

> Power factor

> DC field current

> DC field voltage

> DC field resistance (Exc field)

> Motor running time

> Type of trips (counters)

• Rear RS485 Modbus port

• Windows based SPMPC software

> Trending capability

• Drawout construction

SPM Synchronous Motor Protection & Control

SPM-PF

Page 138: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

138

SPM Synchronous Motor Protection & Control

Page 139: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

139

SPM

Page 140: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

140

• Motor protection & management system for low voltage, lowhorsepower motors

• Specifically designed for Motor Control Center applications

• Front panel control buttons (start A, start B, stop, manual, auto)

• Protection & Control> Thermal Overload (12 different overload curves)

> Single phase / Current unbalance

> Locked/stalled rotor

> Ground fault

> Undervoltage, overvoltage, overtemperature

> Undercurrent and underpower

> Configurable motor start controller

> Contactor failure, undervoltage auto restart

• Monitoring & Metering> Motor operational parameters and historical data

> Process data

> Display phase current, ground current, thermal capacity, analoginput, power, energy, etc.

> Status of relay inputs

> Trip record and pre-trip values

> Maintenance information

• Remote monitoring - via serial communications

> RS485 ModBus™ , 1200 - 19,200 bps

• Outputs: 2 contactor, 2 programmable

• Inputs: 6 fixed, 10 programmable

• Front Panel

> 11 LEDs, key pad, and 2x20 LCD display

• Includes EnerVista setup software

• MM2 unit with remote display (optional)

MM2 Motor Protection

MM20-PD-2-120

Page 141: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

141

MM2 Motor Protection

Page 142: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

142

MM2 Motor Protection

Page 143: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

143

• Low voltage motors up to 500HP

• Designed for GE Evolution MCC … but applicable to any LV MCC

• Motor Types> Full Voltage non-reversing, Full Voltage reversing, Reduced Voltage,

Two Speed- one winding, Two Speed-two winding, Custom Motor Type

• Selection of NEMA overload trip classes (Class 10, 15, 20 or 30)

• Protection> Overcurrent Trip, Cool Down Time, Current Unbalance Trip, Ground

Fault Trip, Over/Undervoltage Trip, Jam Protection, Stall Protection,Load Loss Trip, Auxiliary Sense Failure, Power Loss AutorestartFeature

• 7 Digital Inputs and 4 Relay Outputs

• Power Supply Input (96 to 140VAC range)

• DeviceNet protocol (control, status, metering, settings)> Standard Harris 5Pin Micro connector (allows daisy chain from one

unit to another)

> Hardware Selectable MAC ID & Baud Rate (Up to 63 address & 500kbps

• Status LEDs> (Module Status, Network Status, Overcurrent Trip, Gnd Fault Trip, O/C

Unbalance

• RJ11: 6C Telephone Jack> Used to connect to either PDU or PC; PC cable included, connect via

Com1 and use enerVista LM10 setup software

• Real-Time Metering> Ia, Ib, Ic, Ig, Vab, 3ph-kW, 3ph-PF, Iavg, Current Unbalance, Elapsed

Motor Hours (user can reset)

• Trip History (Last 10 faults)> Maintained in non-volatile memory

> Ia, Ib, Ic, Ig, Vab, 3ph-kW, 3ph-PF, Iavg, Current Unbalance

LM10 Low Voltage Motor Relay

LM10-D1-CT05-GF01-C1-XX

Page 144: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

144

LM10 Low Voltage Motor Relay

Page 145: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

145

LM10

Page 146: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

146

•• 369369

•• 469469

•• 489489

•• SPMSPM

•• 750/760750/760

•• 745745

Conformal Coating/Harsh Environment Option Available for:

 Avoid the Effects of Hydrogen Sulfide on Your Relays:

“Silver Whiskers is the name given to

long filaments of silver sulfide formed on

the surface of silver electrical contacts

or surfaces operating in an atmosphere

rich in hydrogen sulfide and high

humidity. Such atmospheres can exist

in sewage treatment and paper mills. If

left too long, the silver whiskers form a

potentially devastating short circuit”

•• M60M60

•• F35F35

•• F60F60

•• T60T60

•• T35T35

•• G30G30

•• G60G60

•• D30D30

•• D60D60

•• L60L60

•• C30C30

•• C60C60

•• B30B30

•• B90B90

•• L90L90Coming Soon:Coming Soon:

PQMII, 239, MMIIPQMII, 239, MMII

Page 147: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

147

Monitoring, Control &Monitoring, Control &

Communications SolutionsCommunications Solutions

•• MultiNet ConverterMultiNet Converter

•• Protocol ConverterProtocol Converter

•• MultiLink Ethernet SwitchesMultiLink Ethernet Switches

•• enerVista Viewpoint Monitoring SoftwareenerVista Viewpoint Monitoring Software

•• enerVista IntegratorenerVista Integrator

•• Automation ProjectsAutomation Projects

Page 148: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

148

One simple communications solution for all your GE Multilin IEDs

 

One simple communications solution for all your GE Multilin IEDs

Serial IEDs are connected to an Ethernet

network via the MultiNet unit.

• Converts Modbus RTU over RS485 into ModbusTCP/IP over Ethernet

• Supports both 10BaseT and 10BaseF fiberconnections

• Industrially hardened product

• Connect up to 32 RS485 serial devices to anEthernet network

• Modbus TCP/IP provides multiple SCADA mastersallowing simultaneous communications to thesame IED

• Easy to use set up software

MultiNet – RS485 to Ethernet Converter

Communication Solutions…

Coming Soon:Coming Soon:

4 RS485 port MultiNet4 RS485 port MultiNet

(any protocol translated)(any protocol translated)

Page 149: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

149

Communication Solutions…

MultiNet Connections

Page 150: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

150

Communication Solutions…

MultiNet Set-up

Page 151: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

151

Communication Solutions…

Modbus Profibus/Devicenet

Modbus to Devicenet Converter (D485)Modbus to Profibus Converter (P485)

• Connect any Modbus RTU device to a Profibus or Devicenet network

• Communicate with up to 5 Modbus devices per converter

• Software contains the memory maps for all GE Multilin devices

• Industrially hardened product

Protocol Converters

Page 152: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

152

• The GE-Multilin Solution for communicatingto all relays, meters and other powersystem devices

• Meets all Industrial standards andrequirements for Substation hardenedequipment

• Modular Construction supports manydifferent communication types for easyinteroperability with any networkingdevices devices

• Enhanced security providing reliablecommunications and protection againsttampering or message forgery

• IEC61850-3 Compliant and optimized togive priority to GOOSE Peer-to-Peermessages

• Factory Certified to work optimally with allGE Multilin products

MultiLink – Ethernet Switches

Communication Solutions…

Page 153: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

153

MultiLink – Ethernet Switches

Communication Solutions…

Page 154: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

154

3 Models Available to fit any Application

ML2400 ML1600

ML600

19” Rack Mounted Managed Switch 9” Panel Mounted Managed Switch

Compact Unmanaged Switch

MultiLink – Ethernet Switches

Communication Solutions…

Page 155: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

155

• 369 Relay

> Use MultiNet with existing relays

> Purchase “E” option (10BaseT)

• 469 Relay

> Use MultiNet with existing relays

> Purchase “T” option (10BaseT)

• 239, 269Plus, MMII & SPM Relays

> Use MultiNet with existing relays

• M60 Relay

> Purchase Ethernet option (10BaseT/F)

> Connect rear RS485 port to MultiNet

• Use MultiLink Ethernet Switches to connect relays directly or via MultiNetconverters

Ethernet Communications?

Communication Solutions…

Page 156: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

156

Monitoring/Control Software Solutions…

Page 157: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

157

Monitoring/Control Software Solutions…

Page 158: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

158

Viewpoint Monitoring is a cost

effective and simple software package for Utilities tocontrol and monitor intelligent electrical devices (IEDs)using a PC

• Windows-based software

• Connect to IEDs via modem, serial or Ethernet via

Plug-n-Play screens

• Pre-built drivers for GE Multilin digital relays,

such as UR, 750, 760, 469, 745, PQM, F60, F35,

PQMII, etc.

• Easy set-up screens & interactive help files

• Build single-line drawings, metering, annunciator,

and status screens easily

• Generic Modbus driver for other manufacturer’s

IED implementation (Control & Monitoring)

• Automatic Oscillography Retrieval & SOE Capture

Alternative EnergyRemotely monitor and manage devices without

incurring significant capital costs

Distributed GenerationUtilities can connect easily with independent

generators via LAN/Internet

UtilityControl & monitor non-SCADA sites with minimal

capital investment

Monitoring/Control Software Solutions …

Page 159: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

159

Viewpoint MonitoringPlug and Play MonitoringPre-Configured Modules for Analyzing the Health and Status of your Power System Equipment

Monitoring/Control Software Solutions …

Page 160: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

160

• Identify the status of all the devices in your powersystem on one customized single line monitoringscreen

• Monitor the magnitude of any power quantitymeasured by your metering and protection devices

• Navigate though multiple monitoring screens to viewthe status of different parts of your network

Create single-line monitoring screens in minutes

• Construct system diagrams with drag and drop ease

• Contains all necessary symbols and tools required forreplicating your power system

• Includes a library of meters and Dials to graphicallyrepresent any metered quantity

Monitor and Control all devices in your Power System

Viewpoint MonitoringSingle-Line Monitoring and Control

Monitoring/Control Software Solutions …

Page 161: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

161

Global Comtrade Viewer

View waveforms recorded from any device• Convert waveforms that were stored in CSV format to

COMTRADE compatible files• Merge and Overlay waveforms that were recorded in multiple

devices• Identify the harmonics content in all monitored parameters

Trending Reports

Historical Record of monitored data• Trend up to 500 data points• Records data with 1 minute resolution indefinitely• View data in time based graphical or tabular format

Annunciator Alarming

Instant Alarm Notification• Create alarms on any monitored analog or digital data point• Receive alarm warnings through Audio, Visual or Email

notification

Viewpoint Monitoring

Monitoring/Control Software Solutions …

Page 162: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

162

Effortless Data Archiving

• Instantly detects and retrieves any new waveform from all GE Multilin devices, EMP Meters andMicroVersa Trip Units, and saves these files on a Network location

• Automatically acquires any new events recorded in all devices and stores them in system wideSequence of Event Record

• Sort and Query through system event record to view events categorized by date, device type,timestamp, or customized criteria

• No configuration required

Viewpoint MonitoringAutomatic Event and Waveform Retrieval

Monitoring/Control Software Solutions …

Page 163: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

163

Plug-and-Play Monitoring for the 469- Trip Data -

On-screen View of Diagnostic Data Makes It Easy to Identify Cause of Motor Trip

Monitoring/Control Software Solutions …

Viewpoint Monitoring

Page 164: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

164

View Motor Status Using Digital Inputs, Analog Inputs and RTD Inputs

Monitoring/Control Software Solutions …

Plug-and-Play Monitoring for the 469- Overview -

Viewpoint Monitoring

Page 165: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

165

Monitor Temperature at Any Motor Location in One View 

Monitoring/Control Software Solutions …

Plug-and-Play Monitoring for the 469- RTDs -

Viewpoint Monitoring

Page 166: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

166

Demonstration

Viewpoint Monitoring

Software

Monitoring/Control Software Solutions …

Page 167: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

167

Easily Enhance Current Systems toDisplay Data from GE Multilin

Devices

Monitoring/Control Software Solutions …

Page 168: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

168

Makes it easy to integrate Multilin Devices into existing Systems

Monitoring/Control Software Solutions …

Page 169: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

169

Monitoring/Control Software Solutions …

Page 170: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

170

Automation Projects Available:

PMCS - Power ManagementControl SystemMonitoring, Control and Complete Automationof Power Systems

Compact Monitoring SystemCustomized Monitoring, Control, Alarming andData Archiving

Energy Cost Allocation /Billing SystemEnergy Usage Monitoring and Billing

Monitoring/Control Software Solutions …

Page 171: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

171

Compact Monitoring SystemCustomized Monitoring, Control, Alarming and Data Archiving

Ideal for:• Local monitoring and control of

substations

• Total control and remote monitoringof small Industrial and commercialfacilities

Key Benefits:• Entire site monitoring through

customized one-Line diagrams

• Access to remotely monitor status ofpower system

• Alarm operations personnel of criticalpower level changes

• Historical trending of any powersystem quantity

• Archiving and viewing of all fault data(system wide sequence of events,waveform files)

Monitoring/Control Software Solutions …

Page 172: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

172

PMCS – Power Management Control SystemMonitoring, Control and Complete Automation of Power Systems

Ideal for:• Management of power in a facility of

any size

• Automated control of all powersystem equipment

Key Benefits:• Improve visibility of entire

power system network

• Drill into operating conditions ofspecific power system equipment

• Reduce root cause analysis time

• Receive warnings of impending powersystem issues before problems occur

• Automate power system functionssuch as: load shedding, transferschemes, and initiating backupgenerators

Monitoring/Control Software Solutions …

Page 173: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

173

Project Deliveries may include:

Installation and Configuration of Meters, Relays and Other Devices• Installation and wiring at customer site• Engineering of panels• Construction and wiring of panels• Programming all devices

Setting up of Communications Networks

• Connecting device communications• Installing and configuring Ethernet switches• Connection to corporate network for remote monitoring

Integration of Monitoring and Control System• Configuration of system workstation• Installing of software components• Creating customized power system monitoring diagrams• Configuring automatic fault data collection and historical trending functions• Program system automation functionality

• Load shedding schemes• Auto-Transfer schemes

• Enabling remote monitoring of system

Customer Training• Teach operators, engineers and technicians how to navigate and control

equipment through monitoring system• Training on system troubleshooting and fault diagnostic methods• Instruct service personnel on how to maintain devices and system

Monitoring/Control Software Solutions …

Page 174: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

174

Page 175: Motor Protection Relay Setting Guide

 

GE Consumer & IndustrialMultilin

175