364 g Multilin Motor Protection Enhanced Motor Overload Protection with Thermal Modeling Simple configuration and system monitoring using EnerVista TM 239 Setup software Reduced cost and commissioning time with Protection, Monitoring, and Control in a single device Scalable protection with optional RTD inputs and advanced Motor Protection elements Simplified testing and commissioning with built in simulation features Field upgradable firmware and relay options Easy access to system and relay information using Modbus RTU Multiple groups of protection settings allows flexible protection for flexible systems Small to Medium sized three phase AC induction and synchronous motors Pumps, conveyors, compressors, fans, etc. Status/current/temperature display Fault diagnosis Trending Trip record, last 5 Process control Optional analog output Monitoring and Metering User Interface Protection and Control Thermal Overload (15 selectable curves) - Trip and alarm, immediate current overload alarm Phase short circuit Mechanical jam Thermal memory lockout Single-Phasing /Current unbalance Ground fault - trip and alarm Overtemperature: via thermistor or optional RTD inputs Undercurrent Breaker Failure Trip/alarm/auxiliary/service outputs Multi-speed motor protection Motor start supervision 40 Character backlit display for easy viewing of settings and actual values 6 Motor and relay status LED’s Multiple programming keys to allow easy access to system values and relay settings FEATURES APPLICATIONS KEY BENEFITS 239 MOTOR PROTECTION SYSTEM Motor protection and management for small to medium size motors Communications RS485 Serial Communications Modbus RTU protocol EnerVista TM Software State of the art software for configuration and commissioning GE Multilin products Document and software archiving toolset to ensure reference material and device utilities are up-to-date EnerVista TM Integrator providing easy integration of data in the 239 into new or existing monitoring and control systems

239 Motor Protection Relay

  • Upload
    des1982

  • View
    97

  • Download
    9

Embed Size (px)

Citation preview

Page 1: 239 Motor Protection Relay

364g Multilin

Mot

or P

rote

ctio

n

• EnhancedMotorOverloadProtectionwithThermalModeling

• SimpleconfigurationandsystemmonitoringusingEnerVistaTM239Setupsoftware

• ReducedcostandcommissioningtimewithProtection,Monitoring,andControlinasingledevice

• ScalableprotectionwithoptionalRTDinputsandadvancedMotorProtectionelements

• Simplifiedtestingandcommissioningwithbuiltinsimulationfeatures

• Fieldupgradablefirmwareandrelayoptions• Easyaccesstosystemandrelayinformationusing

ModbusRTU

• Multiplegroupsofprotectionsettingsallowsflexibleprotectionforflexiblesystems

• SmalltoMediumsizedthreephaseACinductionandsynchronousmotors

• Pumps,conveyors,compressors,fans,etc.

• Status/current/temperaturedisplay• Faultdiagnosis• Trending• Triprecord,last5• Processcontrol• Optionalanalogoutput

Monitoring and Metering

User Interface

Protection and Control• ThermalOverload(15selectablecurves)-Tripandalarm,

immediatecurrentoverloadalarm• Phaseshortcircuit• Mechanicaljam• Thermalmemorylockout• Single-Phasing/Currentunbalance• Groundfault-tripandalarm• Overtemperature:viathermistororoptionalRTDinputs• Undercurrent• BreakerFailure• Trip/alarm/auxiliary/serviceoutputs• Multi-speedmotorprotection• Motorstartsupervision

• 40Characterbacklitdisplayforeasyviewingofsettingsandactualvalues

• 6MotorandrelaystatusLED’s• Multipleprogrammingkeystoalloweasyaccessto

systemvaluesandrelaysettings

FeatUres

aPPlICatIons

Key BeneFIts

239Motor ProteCtIon

systeMMotorprotectionandmanagement

forsmalltomediumsizemotors

Communications• RS485SerialCommunications• ModbusRTUprotocol

enerVistatM software• Stateoftheartsoftwareforconfigurationand

commissioningGEMultilinproducts• Documentandsoftwarearchivingtoolsettoensure

referencematerialanddeviceutilitiesareup-to-date• EnerVistaTMIntegratorprovidingeasyintegrationofdata

inthe239intoneworexistingmonitoringandcontrolsystems

Page 2: 239 Motor Protection Relay

www.GeMultilin.com

239 Motor Protection system

365

Mot

or P

rote

ctio

n

Protection and ControlThe239isadigitalmotorprotectionsystemdesignedfor threephaseACmotorsandassociated mechanical equipment .Advancedprotectionfeaturesinclude:

thermal overload

This function calculates the thermalcapacity used by the motor duringdifferent stages of themotor operation.Thevalue isupdatedbasedonthetime-currentoverloadcharacteristicsand themotoroverloadlockouttimesetpoints.

Motor starting

Duringacceleration,themotorisprotectedbyanI2tovercurrentcurvewhichpassesthrough the setpoints “Locked RotorCurrent” and cold “Safe Stall Time.” Therunningoverloadcurveisnotactiveduringacceleration,thereforeprovidingstartingprotection independent of runningprotection.

Motor running

To protect the motor against overloadswhile it is running, select one of 15different curves to accurately matchthe motor overload characteristic.Curves automatically adjust for hotmotor compensation to ensure correctthermalmodeling. For somenon-typicalapplications,therelaycanbeorderedwithadditionalcustomprogrammableoverloadcurves,allowingtheusertoconstructtheprecise curve thatmatches the thermalcharacteristics of the protected motor(MOD506).A user-programmable overload lockouttime controls the motor cooling rate. If

theprocesscriteriarequireshortercoolingperiods, particularly for small motors, adifferenttimecanbeused.The minimum level of thermal capacitythattherelaywillcalculateundernormaloperationwillbedeterminedbytheHot/Cold stall time ratio, which distinguishesbetweencoldandhotmotorconditions.AnAutoResetfeatureresetstheoverloadtriponcethethermalcapacityhasdecreasedto15%orless.An immediate overload alarm alertsthe operator. This may be useful forsystemsthatdonotnormallyexperienceoverloads.

An immediate overload pickup setpointis also available. The relay can also beorderedwiththeoptiontoallowtherelaytolearnthethermalcapacityusedduringsuccessfulstarts.

Hot Motor

Thisfunctionutilizesthermalcapacityused(TCU) value to initiateahotmotoralarmwhen the TCU is approaching themotorthermallimit(100%TCU).

Immediate overload alarm

Thisfunctionisusedtoalarmonamotoroverload condition that requires an

immediate intervention to eliminate thecauseofthesuddenoverload.

Phase short Circuit

Thiselementprovidescompletephase-to-phase and Phase-to-ground protection.TriporAuxiliarycontactscanbeselectedtooperateinstantaneously,orwithatimedelayupto60seconds.

Mechanical Jam

This function prevents motor damageduring abnormal operational conditions.Quick motor shut down can reducedamage to gears, bearings, and othermechanical parts associated with thedrivesystem. Acurrentsurgewillcausetherelayassignedtothemechanicaljamprotection to become active. The usermaysetthepickuplevel,timedelay,andinhibits.

Undercurrent

This function is typicallyused toprotectpumps from loss of suction, fans fromlossofairflowduetoacloseddamper,orconveyorsystemsfromabrokenbelt .Thisfunctioncanbeusedasanalarmorasatrip,ordisabledifnotrequired.Alternativelythisfeaturecanbeusedasapre-overloadwarning by setting the undercurrentpickup above the normal operatingcurrent but below the rated full loadcurrent.

single-Phase (Unbalance)

Currentunbalance is another significantcontributor to motor overheating. Theunbalance protection function has anunbalance pickup level and time delaythatcantriggeratriporanalarm.Typicalpickup is intended to detect and clearsinglephasing.Use thealarm level asawarningforsystemvoltageunbalance.

Breaker Failure

Thisfunctionallowstrippingofallbreakersfeedingafaultintheeventthatthebreakerprotectedbythe239failstooperateandclearthefault .

Ground Fault Protection

Agingandthermalcyclingcancausethestatorinsulationtobreakdown,resultingin ground faults. Ground faults can alsooccurinmotorsbecauseofenvironmentalconditionssuchasmoistureorconductive

15CURVE

1297

4

3

2

1

10

819765A8.cdr

PHASE CURRENT(multiples of full load)

1Full LoadSetpoint

239 OVERLOAD CURVES

0.1

10,000

1,000

100

TR

IPT

IME

(sec

on

ds)

10

1

Trip time overload curves, data and formulae are provided for protection and co-ordination.

MOTOR CURRENT

SEPARATE START AND RUN PROTECTION

TR

IPT

IME

(sec

)

SAFESTALL

TIME

RUNCURVE

STARTCURVE

LOCKEDROTOR CURRENT

x1FLC

819769A5.cdr

Separate start and run modeling provides optimum rotor and stator protection.

Page 3: 239 Motor Protection Relay

www.GeMultilin.com 366

239 Motor Protection system

Mot

or P

rote

ctio

n

dust.The239cantriggeratriporanalarmif the ground pickup level is exceeded.A time delay may be entered for timecoordinationofsystemswithseverallevelsofgroundfaultdetection. Therearetwogroundinputsavailableinthe239,allowingtwomethodsofgroundprotection.

• Corebalance(Zerosequence)HighImpedanceGroundFault(HGF)currenttransformerswith5Asecondary

• Corebalance(Zerosequence)currenttransformerswitha50:0.025Ampcurrentratioforsensitivecurrentdetection.

WhentheresidualconnectionofthephaseCTs is used to detect ground currents,nuisancetripscanoccurduringstartdueto unequal saturation of CTs. This maycauseZerosequencecurrentstoappear,ofsufficientmagnitudetoreachthepickupsetting of the Ground Fault protectionfunction. Toavoid this, the239has twoindependent timedelaysettings,one formotorstarting,andoneformotorrunning.The239canbeorderedwithMOD512for1AgroundcurrentinputandMOD509fordirectiongroundfaultsensing.

overheating

Direct temperature sensing isnecessarytodetecttheeffectsofmotoroverheatingdue to blocked ventilation or highambient temperature. Temperaturerise under these types of conditions isusuallyslowenoughtoallowtheaccuratesensingoftheactualmotortemperature.Amotortemperatureinputforathermistorisstandardonthe239.Additionally,threeRTDslocatedinthestatorand/orbearingscanbeconnectedtothe239withtheRTDtemperaturesensingoption.Thisprovidesdisplayedtemperaturesaswellasalarmand trip settings for both bearing andstatorRTDs.FourRTDtypesaresupported:100Pt , 120Ni, 100Ni, and 10Cu. A RTDfailurealarmisalsoprovided.

Monitoring and MeteringThe 239 provides users with advancedmonitoring andmetering functions thatinclude:

Metering

Measuredvaluesinclude:

• Phasecurrent

• Groundcurrent

• Currentunbalance

• Current%offullload

• Motorloadcurrentasa%offullload

• Motorthermalcapacityused

• Statortemperature(RTDoption)

• Bearingtemperature(RTDoption)

Multi-speed Motors

Optional switches allow alternateparameterstobeactivatedforprotectionofmulti-speedmotors.Additionalsettingsprovided with multiple speed motorprotectioninclude:

• PhaseCTprimary

• Fullloadcurrent

• Overloadcurve

• Shortcircuittripsettings

Motor start supervision (MoD 505)

The239relaycanbe furnishedwith thisfunction,whichisanenhancedprotectionagainst multiple starts. The functionconsistof2elements:

• TimeBetweenStarts

• StartsperHour

819763AF.cdr

51

49

38

50

37

86/94

74

46

50G

39

MOTORLOAD

AUXILIARYRELAY

SERVICERELAY

RS485

ALARMRELAY

TRIPRELAYMECHANICAL JAM

SHORT CIRCUIT

TIMED OVERLOAD

INSTANTANEOUSGROUND FAULT

STATOR OVERTEMPERATUREBEARING OVERTEMPERATURE

UNBALANCE

UNDERCURRENT

SERVICEALARM

FAULT/ALARM/PROCESSCONTROL

FAULT/PROCESSALARM

523 PHASE4160V BUS

400A

FUSEDCONTACTOR

3PHASE CTs

TRIP

GROUNDCT

THERMISTOR/STATOR RTD

BEARINGRTDs

RS485 REMOTECOMMUNICATION

239 Motor Protection System

Functional Block Diagram

DeviceNumber Function

37 Undercurrent/minimumload

38 Motor/loadbearingOvertemperature

39 Mechanicaljam46 Currentunbalance49 Statorwindingovertemperature50 Phaseshortcircuit51 Timedoverload

50G/50N Groundfaultinstantaneousordefinitetime

74 Alarmrelay86/94 Lockoutandtriprelay

ANSIDeviceNumbers&Functions

Page 4: 239 Motor Protection Relay

www.GeMultilin.com

239 Motor Protection system

367

Mot

or P

rote

ctio

n

Fault Diagnosis

The239keepsarecordofthecauseofthelast five trips issued. The relaywill alsorecordthephasecurrent,groundcurrent,and RTD temperaturesmeasured at thetimeofthelasttrip.

Motor alarmingAlarm functions include immediateoverloadwarning,unbalance,undercurrentand internal self check fault . Often analarmcanbegeneratedsoonenoughtoenablecorrectiveactiontobetakenbeforeatripoccurs.

testing

While periodic calibration is notrequired,thePICKUPLEDisusefulduringcommissioning or routine verificationto indicate the pickup point for phaseoverload or ground. A simulation modeis also available that enables simulatedcurrentstobeusedwithouttheneedforarelaytestset.Thisisidealforverificationofsettingsand training. Itallows forcingofoutputrelays,LEDs,switchinputs,RTD,Thermistor input resistance, and Analogoutputs.

automation

analog output option

The analog output option provides anisolated0to1,0to20,or4to20mAsignalforinterfacetoaPLC.Thisoutputcanbeprogrammedas:averagephasecurrent ,motorfullload%,thermalcapacityused,or RTD temperature. For local operatormonitoring, a thermal capacity metercanbeusedwiththisoutput.Informationsuchasprocessloadingandproximitytotrippingor overheating canbeobtainedwiththisoutput.

output relays

The239hasthreeoutputrelays.Theyarethe Trip, Alarm, and Aux contacts. Thetriprelayactsasthemainlatchedoutputrelay.The Alarm and Auxiliary relays may beprogrammed for latched or unlatchedmodes. All relays may be programmedfail-safeornonfail-safe. Ifconfiguredaslatched relays, they canbe reset via anexternalresetswitchconnectedtooneofthe239digitalinputs,fromthekeypadorviaserialcommunication.

switch Inputs

The 239 has three fixed and two userdefinableswitchinputs:

• Setpointaccess:theseterminalsmustbeshortedtogetherforkeypadsetpointconfiguration

• Emergencyrestart:momentarilyshortingtheseterminalstogetherwhenthemotorisstoppedwillresetthethermalcapacityusedto0%,allowingforanimmediaterestartafteranoverloadtrip.Asthiswillcompromisethethermalprotectionfunctionsofthe239,makingitpossibletodamagethemotor,thisfunctionshouldonlybeusedinemergencysituations

• Externalreset:thisinputallowsremoteorautomaticresetingoflatchedtripsoralarms

CommunicationsThe 239 features an RS485 connectionwithModBus®RTUprotocoltocommunicatewithmosttypesofPLCsandcomputers.This allows anymonitored value, status

Use Viewpoint monitoring to receive instant feedback of the motor and relay status

Troubleshoot motor faults using the 239 Cause Of Last Trip record

Page 5: 239 Motor Protection Relay

www.GeMultilin.com 368

239 Motor Protection system

Mot

or P

rote

ctio

n

and setpoints to be remotely accessedbyaPLCorSCADAsystem.AfrontpanelLED verifies correct operation of thecommunicationport.The 239 is also capable of beingintegrated into a local area networkusing the MultinetTM Serial to Ethernetconverter.Networkingallowseasyaccessto information frommultiplemonitoringandcontroldevicessuchasSCADA’sandHMI’s.

User InterfaceThe40characterLCDandkeypadprovideconvenient local communications andcontrol.Setpointscanbemodifiedlocallyusing the keypad and display. To helpprevent unauthorized setpoint changes,asetpointaccess inputmustbeshortedbeforechangescanbemade.

leD Indicators

Six LED indicators on the front panelprovidequickvisualindicationofstatus.

enerVistatM softwareTheEnerVista™Suiteisanindustryleadingsetofsoftwareprogramsthatwillsimplifyeveryaspectofusingthe239relay.Toolstomonitorthestatusofyourmotor,maintainyour relay, and integrate informationmeasuredbythe239 intoHMIorSCADAmonitoringsystemsareavailable.

enerVista™ launchpad

EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneeded for configuring andmaintainingGE Multilin products. Launchpad allowsconfiguringdevicesinreal-timebycommunicatingusingserial,Ethernet ,ormodemconnections,orofflinebycreatingsettingfilestobesenttodevicesatalater

time.IncludedinLaunchpadisadocumentarchivingandmanagement system thatensurescriticaldocumentationisup-to-dateandavailablewhenneeded.Documentsmadeavailableinclude:

•Manuals

•ApplicationNotes

•GuideformSpecifications

•Brochures

•WiringDiagrams

•FAQ’s

•ServiceBulletins

Viewpoint Monitoring

Viewpoint Monitoring is a powerful yetsimple-to-use monitoring and datarecording of small systems. ViewpointMonitoring provides a complete HMIpackagewiththefollowingfunctionality:

•Plug-&-PlayDeviceMonitoring

•Single-LineMonitoring&Control

•AnnunciatorAlarming

•TrendingReports

enerVista™ Integrator

EnerVistaTM Integrator is a toolkit that

allowsseamlessintegrationofGEMultilindevices intoneworexistingautomationsystems.IncludedinEnerVistaTMIntegratoris:

•OPC/DDEServer

•GEMultilinDrivers

View motor current, temperature, statistics and status.

Enter setpoints directly to the 239 or copy/save relay settings to a file.

Use Viewpoint monitoring to receive instant feedback of the motor and relay status

KEYPADRubber keypad makes installed unit dust tight and splash proof. Meets IP53/NEMA12.

PROTECTIVE DOORCovers keys when not in use.

COMPACT DESIGNReplaces many discrete compo nents with one

819790AG.cdr

CUSTOMER ACCESSIBLE FUSEDoor slides open for easy access to fuse.

PHASE CT INPUTS3 isolated phase CT inputs. Accept 1 amp or 5 amp secondary.

GROUND CT INPUT5 A or 50:0.025 CT input for residually connected phase CTs or separate core balance CT.

AC/DC CONTROL POWERUniversal control power 90-300 VDC/70-265 VAC.

TEMPERATURE SENSINGNTC or PTC thermistor input.

OPTIONAL ANALOG OUTPUTSelect output as: thermal capacity used, current as a % of full load, average current, RTD 1 Ð 3 temperature. Isolated 4 Ð 20 mA for PLC process input or 0 Ð 1 mA for thermal capacity meter.

COMMUNICATIONSRS485 serial communications, 1200 Ð 19200 baud for remote monitoring, setpoint programming, and commands. Modbus¨ RTU protocol.

OPTIONAL 3 RTD INPUTSMix RTD types. Separate stator and bearing monitoring.

OPTIONAL DIRECTIONAL GROUND SENSINGPolarizing voltage input for directional ground sensing(MOD 509)

standard unit.

User Interface

Page 6: 239 Motor Protection Relay

www.GeMultilin.com

239 Motor Protection system

369

Mot

or P

rote

ctio

n

typical Wiring

2 CT CONNECTION(NO GROUND)

RESIDUAL GROUND CONNECTION

ZERO SEQUENCE GROUND CONNECTION

PHASE A CT PHASE A CT

PHASE A CTSTARTER

80-300 VDC70-265 VAC 50/60 Hz

CONTROL POWER

SUPPLY 50:0.025GROUND CT

CONTACTORCOIL

SWITCHGEARGROUND BUS

PHASE C CT PHASE C CT

PHASE C CT

PHASE B CT

PHASE B CT

L1 L1

L1L1A

B

C

TWISTLEADS

L2 L2

L2L2MOTOR

L3 L3

L3L3

1 1

1

2 2

2

3 3

3

4 4

4

5 5

5

6 6

6

7 7

7

8 8

8

9 9

9

10 10

10

11 11

11

12 12

12

5A 5A

5A

5A 5A

5A

5A 5A

5A

5A 5A

5A

1A 1A

1A

1A 1A

1A

1A 1A

1A

COM COM

COM

COM COM

COM

COM COM

COM

COM COM

COM

PHASE A PHASE A

PHASE A

PHASE B PHASE B

PHASE B

PHASE C PHASE C

PHASE C

GROUND GROUND

GROUND

50:0.025 50:0.025

50:0.025

CONTROLPOWERN L

START STOP

GENERAL ALARM

CONTROLPOWER

232425

NO

NO

NO

NO

IN

IN

IN

IN

IN

COM

COM

COM

COM

COM

COM

COM

COM

COM

NC

NC

NC

NC

262728293031323334

43384439454046414742

SETPOINTACCESS

ACCESSKEY SWITCH

EMERGENCYRESTART

EMERGENCYRESTART

EXTERNALRESET

EXTERNALRESET

OPTION 1OPTION 1

OPTION 2OPTION 2

S1

S2

S3

S4

S5

SW

ITC

H IN

PU

TS

OU

TP

UT

RE

LAY

S

RELAY #1TRIP

RELAY #2ALARM

RELAY #3AUXILIARY

RELAY #4SERVICE

CURRENT INPUTS

13 14 36 37SAFETY

GROUNDFILTER

GROUNDL

+N

-

RS485 +

RS485 -

485 GROUNDSE

RIA

L

RT

D#1

RT

D#2

RT

D#3

RT

D T

EM

PE

RA

TU

RE

SE

NS

ING

AN

ALO

GO

UT

0-1m

A

4-20

mA

151617

181920SHIELD

USE SHIELDED TWISTEDPAIR WIRE

RS485

THERMALCAPACITY

THERMISTORIN+

COM

2122

4849505152

SHIELD

HOT

COMP

RET

HOT

5354555657

COMP

RET

HOT

COMP

RET

STATORTHERMISTOR

STATORRTD

STATOR/BEARING RTD

STATOR/BEARING RTD

USE SHIELDED WIRE

819829B7.cdr819751B5.DWG

NOTES:

1) 3)

4)2)

RELAY CONTACT STATE SHOWN WITHCONTROL POWER NOT APPLIED.

SHIELD TERMINALS ARE INTERNALLYCONNECTED TO SAFETY GROUNDTERMINAL 13

RTD TEMPERATURE SENSINGAND ANALOG OUTPUT OPTIONAL

RELAY FACTORY DEFAULTS:TRIP, ALARM, AUXILIARY: SERVICE:

NON-FAILSAFEFAILSAFE

CC

Multilin 239Motor Protection Systemg

Page 7: 239 Motor Protection Relay

www.GeMultilin.com 370

239 Motor Protection system

Mot

or P

rote

ctio

n

technical specificationsCoMMUnICatIonstype: RS4852wire,halfduplex,isolatedBaud rate: 1200–19,200bpsProtocol: ModBus®RTUFunctions: Read/writesetpoints,readactual

values,executecommands

aPProValsManufacturedunderanISO9001registeredsystemUl: RecognizedunderE83849Csa: ApprovedunderLR41286

ProDUCtIon testsDielectric strength: 1.836kVACfor1sectorelays,

CTs,powersupply

enVIronMentaltemperature range operating: 0°Cto60°C storage: -40°Cto70°CambientHumidity: 95%non-condensingPollution degree: 2overvoltage category: 2IP class: 40Insulation voltage: 300Vnote:LCDcontrastimpairedbelow-20°C

*Specificationssubjecttochangewithoutnotice.

PaCKaGInGshipping box: 8.5”Lx6”Hx6”D

(215mmx152mmx152mm)ship weight: 5lbs(2.3kg)

FUse tyPe/ratInG5x20mm,2.5A,250VSlowblow,highbreakingcapacity

ProteCtIontHerMal MoDel / oVerloaDoverload Curves: separate start and run overload Curves run: 15Curves,fixedshape start: PerEquation:T(I)=TsstxI2

I2LRCWhere: Tsst=SaveStallTime

ILRC=LockedRotorCurrentsave stall time range: 1.0-600.0seclocked rotor Current range:

0.5-11.0xFLCoverload Pickup range (FlC):

0.1-150 A for CT Pri Set < 50A1-1500AforCTPriSet>50A

accuracy:Pickup: ±1%ofdisplayedvaluetime: ±2%oftriptimeor±1sec

whicheverisgreateroverload Pickup Inhibit range:

1.0-5.0xFLCHot Motor alarm Pickup range:

1-100%Hot Motor alarm time: InstantaneousCooling Features: Separatestopandruncooling

rates.Exponentialcooldownlockout time (cool down rate):stop: 1-5000minprogrammable

±20%powerONorOFFrun: 50%ofstoppedcoolingtimeHot/Cold stall time ratio range:

5-100%oVerloaD CUrVes trIP tIMe Curves: 15curves,fixedshapeoverload pickup inhibit: 1.0–5.0xFLCPickup level: 1–1500Aaccuracy:Pickup: ±1%ofdisplayedvaluetime: ±2%oftriptimeor±1sec

whicheverisgreatersHort CIrCUIt anD GroUnD trIPGround trip level: 0.05–15A(50:0.025CT)

3–100%(5ACT)s/C trip level: 1–11xCTPRI/OFFIntentional delay: INST.or10msto60000ms

programmableInstantaneous: 20–45ms*total delay: Instantaneous+intentional*trip time accuracy guaranteed if current >1.4 x trip level setting BreaKer FaIlUre tIMInGDelay: INST.or10msto60000ms

programmableInstantaneous: 20–45ms*total delay: Instantaneous+intentional*trip time accuracy guaranteed if current >1.4 x trip level settingstart ProteCtIonthermal: Separatestartandrun

protectionactivation: Inrush3phasecurrentincrease

from<5%to>101%FLCin1sec

Deactivation: Currentdropsto<100%FLCrunningifcurrent>5%FLC

locked rotor: 0.5–11.0xFLCsafe stall time: 1.0–600.0secUnBalanCerange: 5–100%/OFFaccuracy: ±2%Delay: 0–60sec

UnDerCUrrentRange: 5–100%FLC/OFFDelay: 0–250sec

Calculation: Im-Iav ifIav>IFLCUB%=|______|x100 Iav Im-Iav ifIav<IFLCUB%=|______|x100 IFLC

where: Iav=averagephasecurrent Im=currentinphasewithmaximum deviationfromIav IFLC=fullloadcurrentsetting

ProteCtIontHerMal MoDel / oVerloaDrtDs (oPtIon)Inputs: 3RTDs,stator/bearing

programmableType: 100Pt(DIN43760),100Ni,120

Ni10CuprogrammableRange: -40to200°C/-40to400°FTrip/alarmrange: 0to200°C/0to400°FDeadband: 2°C/4°FAccuracy: ±2°C/4°FLeadResistance: PtorNiRTD:25 max

CuRTD:3 max3-wireleadresistancecompensation

tHerMIstorType: PTCorNTCprogrammableHotresistance: 100–30,000 Coldresistance: 100–30,000 Delay: 2secAccuracy: ±5%or100 (whicheveris

greater)

MeterInGPHase CUrrent InPUtsConversion: TrueRMS,16samples/cycleCt Input: 1Aand5Asecondaryrange: 0.1to11xphaseCTprimaryFrequency: 20–300Hzaccuracy: ±2%offullscaleGroUnD CUrrent InPUtsConversion: TrueRMS,16samples/cycleCt input: 5Asecondaryand50:0.025range: 0.03to1.4xCTprimary(5ACT)

0.05to16.0A(50:0.025CT)Frequency: 20–300Hzaccuracy 5a Ct: ±2%offullscale(5ACT) 50:0.025 Ct: ±0.03A(0–0.49A)

±0.07A(0.50–3.99A)±0.20A(4.00–16.00A)

InPUtssWItCH InPUtstype: Drycontactsoutput: 29VDC,10mA(pulsed)Duration: 100msminimum

Ct InPUt(a)

BUrDen(Va) (Ž)

Phase Ct (1 a)1 0.009 0.015 0.2 0.0120 3.5 0.01

Phase Ct (5 a)5 0.04 0.00225 0.9 0.002100 16 0.002

Ground Ct (5 a)5 0.04 0.00225 1.1 0.002100 17 0.002

Ground Ct (50:0.025)

0.025 0.07 1160.1 1.19 1190.5 30.5 122

WItHstanD1 seC x Ct 5 seC x Ct ContInUoUs

x CtPhase Ct (1 a) 100 40 3Phase Ct (5 a) 100 40 3

Ground Ct (5 a) 100 40 3

50:0.025GROUNDINPUTWITHSTANDContinuous 150mAMaximum 12Afor3cycles

50:0.025inputcanbedrivenbya50:0.025CT

PoWer sUPPlyInput: 90–300VDCor70–265VAC,

50/60HzPower: 10VA(nominal),20VA(max)Holdup non-failsafe trip: 200ms Failsafe trip: 100msbothtimes

at120VAC/125VDCNote:Itisrecommendedthatall239relaysbepoweredupatleastonceperyeartoavoiddeteriorationofelectrolyticcapacitorsinthepowersupply.

oUtPUtsanaloG oUtPUt (oPtIon)

ProgrammableoUtPUt 0–1mA 0–20mA 4–20mA

Max loaD 2400 600 600Max oUtPUt 1.1mA 21mA 21mA

accuracy: ±2%offullscalereadingIsolation: 36VDCisolated,activesource

oUtPUt relays

VOLTAGE M/CCONT.

M/C0.2SEC

BREAK

DCResistive 30VDC 10A 30A 10A125VDC 10A 30A 0.5A250VDC 10A 30A 0.3A

DCInductive 30VDC 10A 30A 5A125VDC 10A 30A 0.25A

(L/R=7ms) 250VDC 10A 30A 0.15AACResistive 120VAC 10A 30A 10A

250VAC 10A 30A 10AACInductive 120VAC 10A 30A 10APF=0.4 250VAC 10A 30A 10AConfiguration: FormCNO/NC

ContactMaterial: SilverAlloy

tyPe testsInsulation resistance: IEC255-5500VDCtransients: ANSIC37.90.1oscillatory

2.5kV/1MHzANSIC37.90.1fastrise5kV/10nsOntarioHydroA-28M-82IEC255-4impulse/highfrequencydisturbanceclassIIIlevel

Impulse test: IEC255-50.5J5kVrFI: 50MHz/15WtransmittereMI: C37.90.2electromagnetic

interference@150MHzand450MHz,10V/m

static: IEC801-2staticdischargeenvironment: IEC68-2-38temperature/humidity

cycleDust/moisture: NEMA12/IP53Dielectric strength: 2.0kVACfor1mintorelays,CTs,

powersupplytemperature: -10°Cto60°Cambient

InstallatIonWarning: Hazardmayresultiftheproductis

notusedforitsintendedpurpose.Ventilation requirements: NoneCleaning requirements: None

Page 8: 239 Motor Protection Relay

www.GeMultilin.com

239 Motor Protection system

371

Mot

or P

rote

ctio

n

239 * * * 239 Basicunit rtD 3RTDs:stator/bearing;programmabletype:platinum,nickel,copper an Singleisolated,analogoutput:0–1,0–20,4–20mA

Programmableoutputparameters:thermalcapacity,%fullload, phasecurrent,RTD1,RTD2,RTD3temperature

H Harshenviornmentconformalcoating

ordering

082611-v6

• ViewpointMonitoring VP-1

• 50:0.025GroundCT HGF3

• MultinetSerialtoEthernetconverterMULTINET-FE

• 2.25”ShallowMountCollar 1009-0068

accessories for the 239 • ViewGuideformSpecifications

• Downloadtheinstructionmanual

• Reviewapplicationsnotesandsupportdocuments

• Buyan239online

Visit www.GeMultilin.com/239 to:

ModificationsMOD500: Portabletest/carryingcaseMOD501: 20to60VDC/20to48VACcontrolpowerMOD504: RemovableterminalblocksMOD505: EnhancedstartprotectionMOD506: CustomprogrammableoverloadcurveMOD509: Directionalgroundsensingwith120VACpolarizingvoltageMOD512: 1AmpgroundCTinputMOD513: Class1Division2operationMOD517: AustralianMinesapproval