C L E A N A G E N T F I R E S U P P R E S S I O N S Y S T E M S
MISSIONSEVO™ Systems exclusive mission is to develop and commercialize equipment and systems optimized for the unique properties of
3M™ Novec™ 1230 Fire Protection Fluid for the use in fire suppression, differentiating SEVO Systems from all other OEMs.
HEADQUARTERS14335 W. 97th Terrace Lenexa, KS. 66215 USA
North America: USA South America: Colombia & Brazil Europe: Spain Middle East: Jordan Africa: South Africa Asia: Malaysia
Total Flooding Clean Agent Product Lines
Engineered and Pre-Engineered Clean Agent Fire Suppression Systems
Integrated Pre-Action Clean Agent Fire Suppression Systems: FireFlex Dual and FireFlex 1230 Cabinets
Modular “Plug-n-Play” Clean Agent Fire Suppression Systems
Plug and Play Modular System
• GSM Shelter
• Substations
• Small Data Centers
• No Piping Installation
• Easy To install
SEVO Systems Detection & Control
Up to 8 – any mix
N-ANN-80 Remote LCD
N-ANN-I/O LED Driver
N-ANN-S/PG Printer
N-ANN-RLY Relay
N-ANN-LED AnnunciatorRP-2000 Series
A Heritage of Innovation
FK-5-1-12 (Novec 1230 Fluid) Was Invented To Meet Industries Need For a Sustainable
Replacement for Halon 1301
A Breakthrough in Fire Protection Science
C6 Fluoroketone (FK-5-1-12)
(3MTM NovecTM 1230 Fire Protection Fluid)
Carbon
Fluorine
Oxygen
Physical Properties of NovecTM
1230 Fluid
Agent disperses as a gas
No residue
High density
Water Insoluble
High dielectric strength
Liquid at room temperature
Agent super-pressurized with N2 in cylinder
Extinguishing Method
The Fire Tetrahedron
fuel
oxygen
heat
chainreaction
Removing one of the required components for fire
or disrupting the balance between them can cause a
fire to extinguish
Novec 1230 extinguishes a fire by removing the heat via a cooling effect
UL/FM Flooding Application Approval Tests
Large Room
Large Room
UL/FM Total Flooding Application Approval Tests
Subfloor Application
UL/FM Total Flooding Application Approval Tests
Typical Physical Properties of NovecTM
1230 Fluid
Property Unit Water Novec 1230
Boiling Point °C 100 49.0
Freezing Point °C 0 -108
Specific Heat, vapor, Cp @ 25°C kJ/kg·°C 1.87 0.891
Vapor Pressure @ 25°C kPa 3.17 40.36
Heat of Vaporization @ 25°C kJ/kg 2442 94.9
> 12X
< 25X
“Novec 1230 fluid evaporates ~ 50 times faster than water”
Shipping Of MaterialCO2 Pressurized Cylinder
IG-541(Inergen) Pressurized Cylinder
IG-55 (Argonite) Pressurized Cylinder
IG-100 (Nitrogen) Pressurized Cylinder
Halon 1301 Pressurized Cylinder
HFC-227ea (FM-200) Pressurized Cylinder
HFC- 125 (ECARO) Pressurized Cylinder
FK-5-1-12 (Novec 1230) Unpressurized Drum/Tote
OR Pressurized Cylinder
NFPA 2001 Standard on Clean Agent Fire Protection Systems
ISO 14520 Standard on Gaseous Media Fire Extinguishing Systems
UL ListedFM Approved
VdS Approved LPCB Approved
Lloyds ApprovedCNPP Approved
IMO Recognized
DNV Approved
Bureau VeritasApproved
Standards, Approvals and Listings for Novec 1230 Fluid
Novec™ 1230 Fluid Safety Margin
1 Class A Fuels2 Class B Fuels
• Low in acute and chronic toxicity• NOAEL for 4 hour acute inhalation toxicity study = 10% v/v• NOAEL for all acute inhalation toxicity end points =10% v/v• Data reviewed and conclusions corroborated
by numerous independent authorities
Safety Considerations:
Agent Design Conc. NOAEL*Safety Margin
NOAEL
Novec 1230 14.2% - 25.85% 10% 271% - 1138%
Halon 1301 5% 5% NIL
HFC-227ea (FM200) 16.25% - 28.7% 9.0% 23% - 144%
Inert Gas 34.2 - 46% 43.0% Nil - 26%
CO2 30 - 75% <5%
Lethal @ design
concentration
* No Observed Adverse Effect Level
**Allowed by the USEPA
Testing time based on Class B testing requirements of NFPA.
Generally a system using chemical clean agents knocks down
fires in less than half the time of inert gases. Fast extinguishing
keeps fires small, giving them less chance to spread.
Inert Gases
Chemical Agents;HFCs &FK-5-1-12
Green and Sustainable Solution for Fire Suppression
PropertiesFK- 5-1-12
(Novec 1230)
HFC-
227ea
(FM-200)
HFC-
125
(ECARO)
Inert
Gases
Halon
1301
Ozone Depletion
Potential (ODP)0.0 0.0 0.0 0.0 12.0
Global Warming
Potential-IPCC 20011 3220 3500 0-1 7140
Atmospheric
Lifetime (years)0.014 (5 days) 29.0 34.2
Inert
Gases65.0
Shipping Of MaterialCO2 Pressurized Cylinder
IG-541(Inergen) Pressurized Cylinder
IG-55 (Argonite) Pressurized Cylinder
IG-100 (Nitrogen) Pressurized Cylinder
Halon 1301 Pressurized Cylinder
HFC-227ea (FM-200) Pressurized Cylinder
HFC- 125 (ECARO) Pressurized Cylinder
FK-5-1-12 (Novec 1230) Unpressurized Drum/Tote
OR Pressurized Cylinder
Portable/Onsite Refilling Stations
Greenhouse Gas Emissions from an HFC discharge
=
Preventing one
discharge
from an average size
system
(approx. 348 kg of
agent)
HFC
227ea
HFC
HFC HFC Emissions Equivalent to 1,008,926 kg CO2
HFCs
Greenhouse Gas Emissions from an HFC discharge
=
Preventing one
discharge
from an average size
system
(approx. 348 kg of
agent)
Annual CO2
emissions from 211 U.S. passenger cars
HFC
227ea
HFC
HFC HFC
HFCs
Emissions from the Sustainable AlternativeNon-HFCFluoroketoneInert Gas
=
Preventing one discharge
from an average size system
(approx. 401 kg of agent)
FK
Emissions Equivalent to 401 kg CO2
0.07 cars/year
FK
FK
FK
SEVO Systems Product Line
SEVO 1230Pre-engineered/Engineered System –25 bar (360 psig) or 34.5 bar (500 psig)
D.O.T & T.C. approved
Cylinder Size (L)
Cylinder Size (Lb)
15 40
29 76
62 164
121 322
226 601
368 910
Enhanced Design Capability: SEVO™ 1230 FORCE500™
vs. traditional 360 psi (25 bar) systems
Enhanced Design Capability: SEVO™ 1230 FORCE500™
o Less Clean Agent
o Smaller Cylinder Size/Lower Quantity of Cylinders
o Increased Single Nozzle Coverage
o Pipe networks - More efficient, greater flexibility• Longer pipe lengths and larger pipe network• Remote cylinder location• Smaller pipe diameters
o Retrofit Capabilities for Halon 1301 and FM-200
Enhanced Design Capability: SEVO™ 1230 FORCE500™
o Lower cost of installation
– Smaller piping
– Less clean agent required
– Smaller and/or fewer cylinders
o Expanded limitations of pipe networks
– Remote cylinder location
o Retrofitting capability for both Halon 1301 and HFC-227ea installations.
Less Clean Agent Needed: SEVO™ 1230 FORCE500™
Smaller and/or Fewer Cylinders: SEVO™ 1230 FORCE500™
Smaller
360 psi vs. FORCE500™ at 500psi25 bar vs. 34.5 bar
Fewer
360 psi 25 bar
FORCE500™34.5 bar
20% Avg. Cost Savings
FORCE500 Test Comparison 1360psi (25 bar) FORCE500
Amount of Novec 1230
1573.3KG 1573.3KG
Size of Cylinder's 368.0 Liter 368.0 Liter
Quantity of Cylinders 6 5
Discharge Time 10 9.7
Network Volume 986.0 Liter 789.1 Liter
Nozzle Quantity and Size
6 - 2", 6 1 1/2" 6 - 2", 6 1 1/2"
Remote Cylinder Location: SEVO™ 1230 FORCE500™
Smaller pipe diameters
80% - 300% longer pipe runs allow for remote cylinder locations away from protected hazard.
Increased Single Nozzle Coverage: SEVO™ 1230 FORCE500™
System ft³Nozzle
QuantityNozzle Size
FORCE500™ 500 1 2 ½”
Competitors 500 2 2”
Reduced Extinguishment Time: SEVO™ 1230 FORCE500™
o Higher vaporization rateo Agent dispersed out of nozzle as a vaporo 3 Point Mixing Nozzle: FORCE500 design is beneficial in the mixing of Novec 1230 fluid
o How is this possible?• Higher saturation & absorption of N2 into Novec 1230 fluid• 40 – 60% over traditional 360 psi system• Nozzle mixing (orifice plate design)
o Conclusion• Minimizes byproducts produced during extinguishment• Decreases damage & loss to equipment due to product combustion and extinguishing decomposition
Standards, Approvals and Listings for SEVO Systems
UL Listed
FM Approved
IMO Recognized
Lloyds Approved
DNV Approved
Bureau VeritasApproved
ABS Approved
CE Approved
VNIIPO ApprovedRussian Marine Register Approved
APPLICATIONS
Electrical Applications• Power Rooms• Equipment Rooms• UPS Rooms• Power Supply Rooms
Data Center Applications• Power Data Centers• Data Exchange Server Rooms• Equipment Rooms• MDM Rooms
Telecommunications•Telecommunications Rooms•Battery Compartment Rooms•Switch Gear Rooms
•GSM Shelter
INDUSTRY REFERENCES– Telecommunications
o AT&To Etsilato Qatar Telecomo Sprinto TimeWarnero Telekom Malaysiao Telefonicao VerizonWirelesso VodaFone
– Data & Control Rooms
o HSBC, Malaysiao HPo Dell, BRAZILo IBMo Malaysian Airlineso US Capital
– Marine & Offshore Oilo Chevrono Indian Oilo ONGC
– Hospitalso St. Cloudo Phoenix Children's
o Miningo Vale, BRAZILo Sands, Canada
– Electricity
o BC Hydro, Canada
o Hydro Quebec, Canada
o Iberdrola, Spain
o Red Electrica Espana, Spain
o Kansas City Power, USA
o Saudi Electricity Company, Saudi Arabia
o TNB (Tenega National), Malaysia
-- Museums
o Taipei National Historical Museum
o US Capital Archive
– Oil and Gas
o Alyeska (Alaska Pipeline)
o ARAMCO, SAUDI ARABIA
o BP (British Petroleum)
o Kappa Ethanol
o Conoco Phillips
– Pharmaceuticals
o Sonofi-Aventis
o Hoffman-LaRoche
o Phizer
o Teva
o Wyeth
Worldwide Protection: SEVO Mission Critical ServicesEngineering Design Specifications• Design• Specification• Hydraulic Flow Calculations• Mechanical & Electrical Drawings• Submittal Drawings• Installation Drawings
TrainingSEVO Systems offers training sessions to provide classroom instruction and hands-on training for the SEVO 1230 product line and 3M™ Novec™ 1230 Fire Protection Fluid.
Inspection of Installation• Verification of code compliance•Preconstruction project review• Mechanical equipment review & verification• Room Integrity Test – Preliminary/AHJ Requirements• Retrofit Certification – replacement of Halon 1301 Systems
SERVICES
DESIGN
INPSECTION
ROOM INTEGRITY TESTING
TRAINING
REFILL
Ph: +27 72 438 1857JohannesburgSouth Africa
Emerging Issues For Fire Suppression:
Clean Agent And Water System Installationsin Hot Aisle/Cold Aisle Data Center Design