MICHIGAN DIT LSHC Blue Bus Expansion Power Distribution Units (PDU's) Submitted To Z/E <EKy BILL THIESSE –CONSULTING ENGINEERS Submitted For APPROVAL Project Specification Section Date 10/12/15 Tag & Model# LIEBERT FPC SERIES MODEL FPA30C Quantity 6 Ref. Proposal# Submittal Provided By KARL HUFFMAN 300 KVA FPC PDU 6<67(0S

MICHIGAN DIT LSHC Blue Bus Expansion - BidNet MICHIGAN DIT LSHC Blue Bus Expansion Power Distribution Units (PDU's) Submitted To Z/ E

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

  • MICHIGAN DIT LSHC

    Blue Bus Expansion

    Power Distribution Units (PDU's)

    Submitted To BILL THIESSE –CONSULTING ENGINEERS

    Submitted For APPROVAL

    Project Specification Section

    Date 10/12/15

    Tag & Model# LIEBERT FPC SERIES MODEL FPA30C

    Quantity 6

    Ref. Proposal#

    Submittal Provided By KARL HUFFMAN

    300 KVA FPC PDU S

  • HHHEEEDDDRRRIIICCCKKK AAASSSSSSOOOCCCIIIAAATTTEEESSS2360 Oak Industrial Dr. N.E. Grand Rapids, MI 49505 (616) 454-1218 Fax: (616) 454-5336 Email: [email protected]

    MICHIGAN DIT LSHC BLUE BUS EXPANSION Liebert FPC PDU Systems

    Project Name: MICHIGAN DIT LSHC BLUE BUS EXPANSION Date: 10/01/2015Reference No.: Q02271809Model Number: FPA30CQty: 6

    Module Input: 480V 60Hz Module Output: 208/120V 60Hz

    SYSTEM TYPE• Standard Transformer, 4 Wire Input 3 Phase 3 Wire plus Ground• Door - EZ-View• Side Panels - Both Sides• Main Color: ZP-7021 Black Gray Matte• Panel Color: ZP-7021 Black Gray Matte

    OUTPUT DISTRIBUTION• GE Bolt-In Panelboard• Four Panelboard - 168 Poles• ABB Panelboard Main Breaker

    MONITORING• Liebert Distribution Monitoring (LDMF) with Display with SiteScan Interface• Liebert LDM Branch Circuit Monitoring

    OPTIONAL EQUIPMENT• Lightning/Surge Arrester• Liebert ACV120Y200RKE Surge Suppression System

    LIEBERT SERVICE• Startup Services• Monitoring Start-up• Site Configuration & Owners Training Services

  • 225A 42 POLES

    ISOLATIONTRANSFORMER

    MIB

    225A (OPT.) 42 POLES

    225A (OPT.) 42 POLES

    225A (OPT.) 42 POLES

    MAIN INPUTJUNCTION BOX

    (OPT.)

    INPUT

    3 PHASE3 WIRE + G

    SUBFEED OUTPUT BREAKER(OPT.)

    REF. DWG.

    CHK BY

    DRAWN BY SHEET NO.

    ECN NO.

    P.O. BOX 29186COLUMBUS, OHIO 43229

    LiebertDATEREV. NO.

    FILE NAME:

    DWG. NO.K. STACY

    B. BARCUS

    1 OF 1

    6/14/06

    FPC12000

    I:\APPL\Ohio Appl\FPC\One-Line\FPC12000-00.dwg0

    ORDER NO.

    ONE LINE DIAGRAMWITH TRANSFORMER

    FPC

    INPUTLIGHTING/SURGE

    ARRESTOR(OPT.)

    OUTPUTSPIKE

    SUPPRESSIONMODULE

    (OPT.)

    SUGGESTED MINIMUM INPUT WIRE SIZE DATA

    SUGGESTEDFEEDER WIRE SIZE

    MIBTRIPAMPS

    FULLLOADAMPS

    kVAINPUT

    VOLTAGESUGGESTED

    FEEDER WIRE SIZE

    MIBTRIPAMPS

    FULLLOADAMPS

    kVAINPUT

    VOLTAGE

    15

    208 43 60 #6 AWG240 38 50 #8 AWG380 24 30 #10 AWG400 23 30 #10 AWG415 22 30 #10 AWG480 19 25 #10 AWG600 15 20 #12 AWG

    30

    208 87 110 #2 AWG240 75 100 #2 AWG380 48 60 #6 AWG400 45 60 #6 AWG415 44 60 #6 AWG480 38 50 #8 AWG600 30 40 #8 AWG

    50

    208 145 200 #3/0 AWG240 125 175 #2/0 AWG380 79 100 #2 AWG400 75 100 #2 AWG415 72 90 #2 AWG480 63 80 #4 AWG600 50 70 #4 AWG

    75

    208 215 300 350 kcmil240 186 250380 118 150 #1/0 AWG400 112 150 #1/0 AWG415 108 150 #1/0 AWG480 93 125 #1 AWG600 74 100 #2 AWG

    100

    208 286 400 (2) #3/0 AWG240 248 350 (2) #2/0 AWG380 157 200 #3/0 AWG400 149 200 #3/0 AWG415 143 200 #3/0 AWG480 124 175 #2/0 AWG600 99 125 #1 AWG

    250 kcmil

    125

    150

    200

    225

    300

    208 358 450 (2) #4/0 AWG240 310 400380 196 250 250 kcmil400 186 250415 179 225 #4/0 AWG480 155 200 #3/0 AWG600 124 175 #2/0 AWG208240380400415480600

    (2) #3/0 AWG

    250 kcmil

    427370234223215185148

    600500300300300250200

    (2) 350 kcmil(2) 250 kcmil

    250 kcmil350 kcmil350 kcmil350 kcmil

    #3/0 AWG380400415480600

    312297286247197

    400400400350250

    --- --- --- ------ --- --- ---

    (2) #3/0 AWG(2) #3/0 AWG(2) #3/0 AWG(2) #2/0 AWG

    250 kcmil

    380400415480600------

    352334322278222

    450450450350300

    --- ------ ---

    (2) #4/0 AWG(2) #4/0 AWG(2) #4/0 AWG(2) #2/0 AWG

    350 kcmil------

    380400415480600------

    469446430372297

    600600600500400

    --- ------ ---

    ------

    (2) #3/0 AWG(2) 250 kcmil(2) 350 kcmil(2) 350 kcmil(2) 350 kcmil(2) @ 400A Each

    huffmankRectangle

    huffmankLine

    huffmankLine

  • 48.6"(1235mm)

    47.0" (1194mm)WITHOUT SIDE PANELS .9"

    (22mm)

    39.5" (1003mm)INCLUDING HINGE &BEZEL PROJECTION

    FRONT VIEW RIGHT SIDE VIEW BACK VIEW

    36.4"(925mm)

    1.5"(38mm)

    78.5"(1995mm)

    PANELBOARD WINDOW

    PEDESTAL LOCATIONSØ0.9 (22mm)

    (4 LOCATIONS TYP.)

    1.33"(34mm)

    DETAIL A

    WEIGHT - LBS [KG]

    50 HZ60 HZ

    UNITKVA

    XFMRWITHOUT

    FULL LOAD

    BTU/HR [KW]HEAT OUTPUT

    3045 [1381]2845 [1290]300 18,450[5.4]1390 [631]

    NOTES:1. CLEARANCE OF 18" (457mm) ABOVE UNIT IS RECOMMENDED FOR COOLING AIR FLOW.

    2. CLEARANCE OF 36" (914mm) MINIMUM ISRECOMMENDED AT FRONT & REAR FOR SERVICEACCESS.

    3. COOLING AIR: 600CFM PER FAN

    4. REFER TO INSTALLATION DRAWING FPC17100 FORSEISMIC FLOOR STAND.

    5. TOP (KNOCKOUT) AND BOTTOM (PLUG) PLATES AREINTERCHANGEABLE.

    6.0"(152mm)

    35.0"(889mm)

    33.8"(859mm)

    FRONTBASE FOOTPRINT SHADED

    AREA INDICATES FLOORCUTOUT DIMENSIONS FORCOOLING AIR AND CABLE

    ENTRY/EXIT

    1.3"(33mm)

    36.4"(925mm)

    47.0"(1194mm)

    REF. DWG.

    CHK BY

    DRAWN BY SHEET NO.

    ECN NO.

    1050 DEARBORN DRIVEP.O. BOX 29186

    COLUMBUS, OHIO 43229

    DATE REV. #

    FILE NAME:

    DWG. NO.AND EZ-VIEW REAR DOORS, REV. A47" CABINET WITH SIDE PANELS

    300 KVA FPCOUTLINE DRAWING

    ORDER NO.1

    I:\APPL\Ohio Appl\FPC\Outlines\47inch-cabinet\FPC13224-01.DWGFPC13224 6/22/12

    1 OF 1

    B. BARCUS

    K. STACY

    2.17"(55mm)

    BOTTOM VIEW

    31.87"(809mm)

    43.94" (1116mm)

    SEE DETAIL A

    FRONT

    84 PLUGS PERPLATE FOR 1/2" CONDUIT

    (SEE NOTE 4)

    AREA FOR COOLING

    OPENING FOR INPUT ANDSUBFEED BREAKER CONDUIT43.6" x 9.6" (1108mm x 245mm)

    CONDUIT PLATE LOCATEDABOVE OPENING INSIDE

    THE CABINET

    TOP VIEW

    R 25.3" (643mm) x180° DOOR SWING

    R 25.3" (643mm) x180° DOOR SWING

    OUTPUT LANDING PLATES(2) @ 11.9" x 15.7"(302mm x 400mm)

    SUBFEED BREAKERLANDING PLATE

    (3) @ 5.4" x 10"(167mm x 254mm)

    CONTROL WIRING(2) 1 1/2" (38mm) HOLES

    INPUT LANDING PLATE5.4" x 10"(167mm x 254mm)

    FRONT

    84 KNOCKOUTS PERPLATE FOR 1/2" CONDUIT

    (SEE NOTE 4)

    R 25.3" (643mm) x180° DOOR SWING

    R 25.3" (643mm) x180° DOOR SWING

    MONITORING LANDING PLATE9.6" x 19.1"(244mm x 485mm)

    huffmankLine

  • FPC 47" CABINET, REV. AFOR VPMP, CPM, AND LDMF

    ELECTRICAL FIELD CONNECTIONS

    ORDER NO.0

    I:\APPL\Ohio Appl\FPC\Elect_Field_Connections(FPC15000)\FPC15253-00.DWGFPC15253 8/5/11

    1 OF 1

    B. BARCUS

    K. STACY

    DETAIL A

    FRONT VIEW

    DETAIL CADAPTER BOARD -

    LOCATED ON TOP OF THE MONITORINGENCLOSURE(SEE DRAWING LDM13009

    FOR CONNECTION DETAILS)

    DETAIL B(SEE NOTE 1)

    VPMP SETUP PORT(DB9 CONNECTOR)

    SEE DETAIL B

    VPMP OPTION(NO MONITORING)

    LDMF 1 OPTION(CPM)

    LDMF 2 OPTION(CPM)

    NOTES:1. DRAWING SHOWS ALL MONITORING OPTION BOARD LOCATIONS FPC IS AVAILABLE WITH. A - NO MONITORING B - VPMP C - VPMP WITH CURRENT PLUS (CPM) D - VPMP WITH LDMF E - CURRENT PLUS2. SOME SLOTS MAYBE EMPTY DEPENDING ON OPTIONS ORDERED.

    INTELLISLOTS(TO INSTALL INTELLISLOT CARDS,

    REMOVE AND DISCARD COVER) SEE DETAIL A

    SEE DETAIL D

    DETAIL DBUILDING INTERFACE RELAY -

    (SEE DRAWING LDM13009FOR CONNECTION DETAILS)

    LDMF1 SETUP PORT(DB9 CONNECTOR)

    LDMF2 SETUP PORT(DB9 CONNECTOR)

    SEE DETAIL C

  • SEE DETAIL A

    FPC 47", REV. ASITESCAN MONITORING INTERFACEELECTRICAL FIELD CONNECTIONS

    ORDER NO.0

    I:\APPL\Ohio Appl\FPC\Elect_Field_Connections(FPC15000)\FPC15252-00.DWGFPC15252 7/20/11

    1 OF 1

    B. BARCUS

    K. STACY

    DETAIL A

    100

    LAN

    LIN

    K

    10/1

    00 B

    ase

    TE

    ther

    net P

    ort

    BA

    Cne

    t

    Net

    +

    Shi

    eld

    Net

    -

    Gro

    und

    + 12

    V

    Rne

    t +

    Rne

    t -

    Xne

    t +

    Gnd

    Xne

    t -

    AR

    Cne

    tP

    ort

    Rne

    t

    Xne

    tR

    emot

    eE

    xpan

    sion

    Loca

    lA

    cces

    s

    FRONT VIEW

  • REAR VIEWWITHOUT DOORS &ACCENTS PANELS

    PANELBOARD MAIN CIRCUIT BREAKERFACTORY WIRED.

    42 POLE DISTRIBUTION PANELBOARDS

    DISTRIBUTION CABLE CONDUIT CONNECTION.CABLE TRAY 7/8" [22.2mm] HOLES FOR1/2" CONDUIT FITTINGS PROVIDED FOR SECURINGOPTIONAL DISTRIBUTION CABLES.

    NEUTRAL CONNECTIONS.DISTRIBUTION CABLES NEUTRALSCONNECTED TO DISTRIBUTIONPANELBOARD NEUTRAL BUS BAR.

    DISTRIBUTION CABLE CONDUIT CONNECTION.CABLE TRAY 7/8 [22.2 mm] HOLES FOR1/2" CONDUIT FITTINGS PROVIDED FOR SECURINGOPTIONAL DISTRIBUTION CABLES.

    GROUND CONNECTIONS.DISTRIBUTION CABLE GROUNDSCONNECTED TO DISTRIBUTIONPANELBOARD GROUND BUS BAR.

    LDM CURRENT SENSORS

    FRONT VIEWWITHOUT DOORS& ACCENT PANEL

    SUBFEED CIRCUIT BREAKER (OPTIONAL).SUBFEED OUTPUT POWER CONNECTIONS.100-250A LUG ACCEPTS 6AWG-350KCMIL CABLE,300-400A TWO HOLE LUGS ACCEPTS 3/0-250KCMILCABLE PROVIDED FOR CUSTOMER CONNECTIONOF 3-PHASE POWER CONDUCTORS.

    GROUND ELECTRODE CONDUCTORCONNECTION.CUSTOMER CONNECTION OFCONTINUOUS GROUND ELECTRODECONDUCTOR. (NOT NEEDED ONSYSTEMS WITHOUT TRANSFORMER.)

    SAFETY GROUND CONNECTION.CUSTOMER CONNECTION OFINPUT SAFETY GROUND CONDUCTORFOR UNITS WITHOUT MAIN JUNCTION BOX.

    MAIN INPUT NEUTRAL CONNECTION.FOR UNITS WITHOUT ISOLATIONTRANSFORMER AND WITHOUT MAININPUT JUNCTION BOX, CUSTOMERCONNECTS MAIN INPUT NEUTRALDIRECTLY TO NEUTRAL BUS BAR.

    SUBFEED OPTION OUTPUT NEUTRAL ANDGROUND CONNECTIONS.CUSTOMER CONNECTS SUBFEEDNEUTRAL & GROUND DIRECTLYTO MAIN NEUTRAL AND GROUNDBUS BARS.

    MAIN INPUT POWER CONNECTION.FOR UNITS WITHOUT MAIN INPUTJUNCTION BOX, BUS BARS WITH TWO0.56 DIA HOLES ON 1.75"CENTERSARE PROVIDED ON THE MAIN INPUTCIRCUIT BREAKER FOR CUSTOMERCONNECTION OF 3-PHASE POWER.

    ACCUVAR SPIKE SUPPRESSION(OPTIONAL)

    REF. DWG.

    CHK BY

    DRAWN BY SHEET NO.

    ECN NO.

    DATE REV. #

    FILE NAME:

    DWG. NO.

    FPC 47" CABINETELECTRICAL FIELD CONNECTION WITH LDM

    ORDER NO.1

    I:\APPL\Ohio Appl\FPC\Elect_Field_Connections\FPC15203-01.dwgFPC15203 5/2/12

    1 OF 1

    B. BARCUS

    K. STACY

  • huffmankLine

  • PM4 ADAPTER BOARDFOR REMOTE EPO AND SUMMARY ALARM

    ELECTRICAL FIELD CONNECTIONS

    ORDER NO.0

    I:\APPL\Ohio Appl\Liebert-Display-Monitoring (LDM)\Elect_Field_Connections(LDM13XXX)\LDM13010-00.DWGLDM13010 8/12/11

    1 OF 1

    B. BARCUS

    K. STACYP3

    8

    S1

    R1R2

    J2

    P1

    P2R6

    K1

    R4

    J1

    R5R3

    E1

    R7

    J3

    TB1

    TB2

    P1

    TB1

    P38

    K1P2 -2

    4V+

    _

    +R

    S48

    5C

    US

    TO

    ME

    R A

    LAR

    MS

    #5 NC

    #4 NO

    #3 NO

    #2 NO

    #1 NO

    COMMON

    J2J3

    SU

    MM

    AR

    YA

    LAR

    M

    NO

    NC

    COM

    RE

    MO

    TE

    EP

    O

    NOREPO

    24vDC

    REPOCOM

    NCREPO

    24vDC

    AUTO

    MAN

    UAL

    SUMMARY ALARM NO

    SUMMARY ALARM NC

    SUMMARY ALARM COMMON

    P1 TO INTELLISLOT ONLY

    J1

    3

    6

    9 7

    4

    1

    AB

    W200

    BUILDING INTERFACE RELAY

    REMOVE JUMPER WHEN NORMALLYCLOSED (N.C.) REPO IS USED

    N.O. REPO

    BLK

    WHT

    GRN

    N.C.REPO

  • LDMF PM4 INTERFACE BOARDELECTRICAL FIELD CONNECTIONS

    ORDER NO.1

    I:\APPL\Ohio Appl\Liebert-Display-Monitoring (LDM)\Elect_Field_Connections(LDM13XXX)\LDM13005-01.DWGLDM13005 8/2/11

    1 OF 1

    B. BARCUS

    K. STACY

    BRANCH AND SUBFEED BREAKERSCT's CONNECTIONS INDICATES CT WHITE WIRE.

    CONNECTOR P3 (A) WIRE COLOR

    PINS

    CT CT9 OR IG

    9

    B W

    CT8

    8

    B W

    CT7

    7

    B W

    CT6

    6

    B W

    CT5

    5

    B W

    CT4

    4

    B W

    CT3

    3

    B W

    CT2

    2

    B W

    CT1

    1

    B W

    CONNECTOR P4 (B) WIRE COLOR

    PINS

    CT CT18 OR IG

    9

    B W

    CT17

    8

    B W

    CT16

    7

    B W

    CT15

    6

    B W

    CT14

    5

    B W

    CT13

    4

    B W

    CT12

    3

    B W

    CT11

    2

    B W

    CT10

    1

    B W

  • CT REPLACEMENT WIRING DIAGRAMCT SENSOR MODULE

    LDMF PM4 MONITOR BOARDELECTRICAL FIELD CONNECTIONS

    ORDER NO.0

    I:\APPL\Ohio Appl\Liebert-Display-Monitoring (LDM)\Elect_Field_Connections(LDM13XXX)\LDM13004-00.DWGLDM13004 10/2/09

    1 OF 1

    B. BARCUS

    K. STACY

    CONNECTION LOCATION FOR CT MODULE6 REPLACEMENT CT's. INDICATES PIN 1.CONNECT CT WHITE WIRE TO PIN 1CONNECT CT BLACK WIRE TO PIN 2

    NOTES:1. REMOVE CT FROM THE BOX. ROUTE WIRING FROM THE TRANSFORMER THROUGH THE PANEL TO THE LDM CONTROL BOARD.2. CONNECT THE CT CONNECTOR TO THE PROPER PANEL LOCATION USING THE FIRST AVAILABLE CONNECTION A. FOR PANELBOARD "A" USE P2(A1), P3(A2), P4(A3) B. FOR PANELBOARD "B" USE P5(B1), P6(B2), P7(B3) ENSURE ALL ROUTED WIRING IS PROPERLY SECURED TO THE PANEL WITH TIE WRAPS.3. THE TOP PIECE OF THE CURRENT TRANSFORMER (CT) IS REMOVABLE BY PULLINGAWAY FROM THE CENTER OF THE TRANSFORMER (ITEM 2).4. PLACE THE MAIN BODY OF THE CURRENT TRANSFORMER AROUND THE CABLE, MAKING SURE THE CT IS INSTALLED IN THE DIRECTION SHOWN (SEE ITEM 2).5. REPLACE THE TOP PIECE OF THE CT TO COMPLETE SECURING THE CT AROUND THE CABLE (SEE ITEM 3). USING THE ENCLOSED TIE WRAPS TO SECURE THE CT TO THE CABLE.

    *WARNING: DO NOT OPEN CIRCUIT THE SECONDARY WINDINGS OF CURRENT TRANSFORMERS. FAILURE TO FOLLOW THESE INSTRUCTIONS NAY RESULT IN SERIOUS INJURY OR DEATH.

    ITEM 2 ITEM 3

    LOAD

    POWER SOURCE

    LOAD

    POWER SOURCE

    DETAIL APANELBOARD A PANELBOARD B

    REPLACEMENT CT(6 PL. TYP.)

    BRANCH CIRCUIT BRANCH CIRCUIT

  • SILENCE/ RESET

    LCD DISPLAYOUTLINE DRAWING

    ORDER NO.1

    I:\APPL\Ohio Appl\Liebert-Distribution Monitoring (LDM)\Outline_Drawing(LDM12XXX)\LDM12002-01.DWGLDM12002 7/12/11

    1 OF 1

    B. BARCUS

    K. STACY

    ALARMPOWER

    F1 F2 F3 F4 HELP

  • HHHEEEDDDRRRIIICCCKKK AAASSSSSSOOOCCCIIIAAATTTEEESSS 2360 Oak Industrial Dr. N.E. Grand Rapids, MI 49505 (616) 454-1218 Fax: (616) 454-5336

    Email: [email protected]

    LIEBERT UPS AND POWER DISTRIBUTION SYSTEMS

    ELECTRICAL INSTALLER RESPONSIBILITIES The Electrical Contractor installation scope for Liebert UPS & PDU systems includes, but is not limited to:

    1) Receiving & Unloading: Schedule delivery with the trucking company. The trucker name and phone number along the tracking number will be available from Hedrick Associates one day after the equipment leaves the factory. Delivery may consist of multiple deliveries. The installer shall mark the shipping papers with notes if any damage is noticeable to the packaging. Upon un-packaging the equipment the installer shall notify Hedrick Associates if any concealed damage is uncovered.

    2) Installation Manuals Installer shall review the equipment installation manuals and install the

    equipment to the manufacturers recommended procedures as outlined in the installation manual. Where not specifically outlined in the manuals or submittals the installer shall follow common electrical installation practices.

    3) Submittals Drawings Installer shall review equipment submittal drawings and note any concerns to Hedrick Associates and the owner. The installer shall review all notes on the submittals to confirm the equipment will be installed to the manufacturer’s specifications. Wire and conduit sizing shall meet local codes and shall be sized to meet capacities as required by the equipment manufacturer.

    4) External Overcurrent Protection Devices with size, type, and with accessories required per

    submittal drawings, shall be supplied and installed by electrical installer. Power wiring and lug accessories, sized per NEC requirement or engineer’s cabling schedule, shall also be supplied and terminated per UPS and PDU installation manual requirement.

    5) Control Wiring between the multiple system cabinets may or may not be included by Liebert, depending on equipment layout. Reference submittal drawings to determine if they are provided by Liebert, or provided by installer. Installation and termination of control wiring is the responsibility of the installer.

    6) Pre-Installation Site Visits; Factory Start up and Owners training - The installer shall coordinate

    with Hedrick Associates the scheduling of factory start up service and required testing and training services. Two week’s notice of the start-up date is required for scheduling the service technician.

    Provided By: Hedrick Associates