Upload
iformat
View
220
Download
0
Tags:
Embed Size (px)
DESCRIPTION
Marketing TecBeam Installation Guide
Citation preview
BEAM
Strong, lightweight composite structural ‘I’-Beam.
BEAM
Installation Guide
2
ContentsThis Installation Guide has been prepared as a source of information to provide general guidance to consultants – and in no way replaces the services of the professional consultant and relevant engineers designing the project.
It is the responsibility of the architectural designer and engineering parties to ensure that the details in this Installation Guide are appropriate for the intended application.
The recommendations of this guide are formulated along the lines of good building practice, but are not intended to be an exhaustive statement of all relevant data.
Introduction 3
1.1 General Notes 3
1.2 Web Hole Alignment 3
1.3 Strongbacks (SB) 4
1.4 Blocking & Bracing 8
1.5 Load Spreaders 9
1.6 Bearing Support 10
1.7 Web Stiffeners 11
1.8 Internal Walls 13
1.9 Trimming, Notching or Docking 13
1.10 Connection and Fixing Details 14
IntroductionTECBEAM™ is a composite structural ‘I’-Beam which has a continuous galvanized steel web and timber flanges resulting in a lightweight beam with structural properties closely resembling those of a steel beam rather than a solid beam. TECBEAM™ is designed and manufactured in Australia by licensed fabricators and holds worldwide patents for its technology.
1.1 General NotesConventional framing practices can also apply to TECBEAM™ installations: however, to gain maximum benefit from using the TECBEAM™ system, builders are strongly advised to take advantage of its unique features by adopting the following guidelines.
To meet the requirements of the Building Code of Australia (BCA), all works must comply with AS 1684.2-1999 and where applicable with TECBEAM™ Installation Guidelines.
For details not covered in this manual, please refer to either: TECBEAM Australasia P/L, local TECBEAM™ fabricator or a registered structural engineer.
1.2 Web Hole Alignment For installation of strongbacks (SB) and services
To achieve alignment of web holes, for the installation of strongbacks and services, TECBEAM™ joists have been colour marked at one end, called the COMMON END. Refer to the Floor Framing Plan for set out reference lines (RL)
3
Strongback Strongback
Common end
Common end
1.3 Strongbacks (SB)Strongbacks have been proven to:
• significantlyreducefloorvibration
• loadshareaconcentratedload
• bemoreeffectivethansolidblocking
• actasinternalsupportbeams
1.3.1 General• Beforesecuringwedges,ensurestrongbacksarebelow15%MoistureContenttoavoidsqueakyfloors
• MinimumMGP10grade
• Ifhighercomfortlevelsfromfloorvibrationarerequired,useMGP12,F17,LVLorincreasethenumberofstrongbacks
Recommended Sizes
• T25series–140x45
• T30series–190x45or200x45LVL
• T35series–190x45or200x45LVL
• Forhigherloading,steelsectionscanbeusedasstrongbackorinternalbeams;refertoTECBEAMAustralasiaorastructuralengineer
Restrictions
• Formaximumefficiency,avoidcuttingholeswithadiametergreaterthanonethirdthedepthofthestrongback
• Forlongjoistspans,planthelocationofservicesandpositionofstrongbackstoavoidcuttingasmuchaspossible.Thisistokeepfloorvibrationundercontrol
4
Strongback
Pair of wedges
1.3.2 Installation• Strongbacksmustbesecuredtightwithapairofwedgesateachjoist;itisrecommendedwedgesaregluedand
nailed. See 1.3.4 Wedges
• Whereapointloadoccurs,locateastrongbackthroughthewebholeclosesttothepointloadandlongenoughtofix through at least two joists each side of the joist carrying the load
• Installstrongbackswithaminimumlapofone(1)bay
• Lapsinstrongbacksmaybeinstalledin
a) the same hole or b) the next adjacent hole
• Min.strongbackslengths:2100mmfor450crsand2400mmfor600crs
5
a) Strongbacks overlap in same hole (3 & 4) or
b) Strongbacks overlap in next adjacent holes (1 & 2)
Strongback
Support
POINTLOAD(>500kg)
Web Stiffener
Strongback
Min. overlap = 1 bay
3 4
2
1
1.3.3 SpecificationsMinimum recommendations for vibration control
• Installonerowofstrongbacksmidspanwherethejoistsarewithin0.75mto1.5mofthetabulatedspan.
• Wherethejoistspanisover6morwithin0.75mofthetabulatedspan,installtworowsofstrongbacks;placedapproximately at one third points of the joist span.
• Forcontinuousspans–addaStrongbackintheshorterspanevenifitislessthanthespansindicatedabove.
6
Within0.75–1.5mofmaxtabulatedspan
Strongback
Mid
span
Within0.75mofmaxtabulatedspanorspanover6m
Strongback
Strongback
1/3
of sp
an1/
3 of
span
1/3
of sp
an
SPAN
SPAN
1.3.4 Wedges• Wedgesareusedtosecurethestrongbacktoeachjoist.Looseorpoorlyfittedwedgesmayresultinthefloor
squeaking
• Itisrecommendedthatwedgesareinstalledinpairs,hammeredhardagainsttheopposingwedgethenglued&nailed
• MustbedrywithaMoistureContent<15%beforefixing
7
Timber wedges glued and nailed or screw fixed, centred about the web
(Alternative: wedges can be fixed on top of web)
1.4 Blocking & Bracing (in the floor plane)
• TECBEAM™joistsdonotrequireintermediateblockingwherethereiseitherfullfloorsheetingandceilinglining,orstrongbacks (Note: Strongbacks are more effective than solid blocking)
• Installblockinginthefollowinglocations:
a) at cantilevers along the support line and in alternate bays at the outer end if no trimmer is indicated, b) alongallsupportlines–maximumspacing1.8m,c) incontinuousspans–alongintermediatesupports,d) under partition walls running parallel to the joists.
8
Blocking in alternate bays
1.5 LoadSpreaders (or rimboards)
• Wherejoistsareoffsetfromloadbearingstuds,PlywoodLoadSpreaders(orrimboards)canbeusedinsteadofextrastuds, wall plate blocking or a double top plate
• Loadspreadersshouldbeminimum12mmF11constructionplywood,cuttotheexactjoistdepthandfittedtightbetweenthewallplateandflooring
• Installjoistswitha15mmsetbackfromtheoutsidefaceofthewallframe.Fixeachoffsetjoistwithaminimum8/40x2.8mmnails
• LoadSpreadersshouldspanatleastthreestudsorminimum1350mm
• Offsetjoistscarryingloadsinadditiontonormalresidentialfloorloads,mayrequireextrafixings–refertostructuralengineer
• PlywoodLoadSpreadersalsoprovidein-floor-planebracing,eliminatingendblocking,orcrossstrapping
• Whenusedasendbracingonly,the15mmsetbackisnotrequired;fixwithaminimumoffournailsperjoist
9
Rim Board nailed at ends of TECBEAM™ joists
1.6 Bearing Support• Recommendedminimumbearinglength:45mm
Alternately,TECBEAM™joistscanbestaggeredatinternalloadbearingwallsforfull90mmbearing
10
Blocking as specified
45mmbearing
90mmLBW
45mm
90mm
Blocking as specified
90mmbearing
90mmLBW
1.7 WebStiffeners (or web blocks)
• arerequiredtotransfershearloadsintooroutofthesteelweb
• areusedtobracethewebinhighloadcases
1.7.1 Minimum Requirements:• MinimumSize:70x35seasonedtimber,tightfittingbetweentimberflangesoneachsideofthewebandnailed
together
• Minimumnailing: T25–8/65x2.7mm
T30–8/65x2.7mm
Web stiffeners are required at:
a) the ends of all joists
b) the support line for cantilevers
c) at the supporting walls, beams, posts, in continuous spans
11
Flooring
Strongback
b) Support line for cantilevers
Blocking every third bayWeb Stiffener each side of TECBEAM™ joists
a) End of joist
Timber packer
Intermediate support
Blocking at alternate bays
Web Stiffener each side of TECBEAM™ joists
d) underpointloadsexceeding500kg
e) perimeter walls
• Underperimeterloadbearingwalls,asingleTECBEAM™joistfittedwithextrawebstiffenersreplacestwosolidtimberjoists
• Recommendedwebstiffenerspacing:
MetalRoofs: 1350mmcrsTileRoofs: 900mmcrsupto10mspanHeavierLoads:600mmcrs
Note: If a web hole occurs over the support, add a pair of web stiffeners as close to the support as possible but covering the steel web sufficiently to fix the minimum nailing required through the web.
12
Web Stiffener
Web Stiffener
Strongback
Support
Web Stiffener
POINTLOAD(>500kg)
1.8 Internal Walls (non load-bearing)
CrossingFloorJoists–Forasinglewallwithinthemiddlehalfofthejoistspanandalsowithin300mmofthetabulated span, one of the following measures is required:
• addanextrajoistevery1800mmcrsor
• reducejoistspacing,e.g.600mmto450mmcrs,450mmto350mmcrs,or
• upgradetonextjoistsize
Note: for additional walls crossing the joists, check with TECBEAM Australasia or a structural engineer
ParalleltoFloorJoists–Whereawallcoversover65%ofthejoistspan,checkthefollowing:
• Joists@600crs–ifthespaniswithin500mmofthetabulatedspan,addanextrajoistunderthewall
• Joists@450crs–ifthespaniswithin900mmofthetabulatedspan,addanextrajoistunderthewall
Notes:
1.Installastrongbackatmidspan2100mmlongtoevenoutdeflections
2.Supportwallslocatedbetweenjoistswitheithershortstrongbacksorsolidblocking@1800mmcrs
1.9 Trimming, Notching or Docking• Trimming,notchingordockingispermissableonlyatendsupports
• The“CommonEnd”hasapairofeither140mmor190mmwidewebstiffenersfittedwiththesteelwebsetback70mmor90mmrespectively.Thisfeatureallowsforthetimbertrimming,notching,ordocking
1.9.1 Restrictions on Notching:Bottom Flanges
TECBEAM™joistbottomflangescanbenotchedupto15mmandnolongerthan100mm.Ifgreaternotchingisrequired, refer to TECBEAM Australasia, or a structural engineer.
13
Trip-L-grip or skew nailing
Web blocking in alternate bays
100mmMax.
15mmMax.
Top Flanges
Canbenotchedtothefulldepthoftheflangeandhalfthewidthofthestiffener.
1.10 ConnectionandFixingDetails• Generally,standardtimberframingconnectorsandframingmethodsaresuitablewithTECBEAM™joists
• Forhigherloadcapacityapplications,heavydutyconnectorsmaybenecessary(refertoastructuralengineer)
1.10.1 Connection to Timber Beams• Undernormalfloorloads,StandardJoisthangersareusedtoconnectTECBEAM™joiststotimberbeams
14
Timber beam
Standard joist hanger
Trip-L-grip or skew nailing
70/95mm
140/190mm
• WhereTECBEAM™joistscarryhigherloadse.g.doublejoistatstairvoid,acombinationofajoisthangerononejoist and a steel angle bracket fixed with 2M12 bolts on the other joist can be used. Refer to TECBEAM™ Standard Details
1.10.2 Connection to Steel Beams
A. Notching – install against the beam web and bearing on the flangeA1. Steel beams with a height similar to TECBEAM™ joists
• Notchthejoistinsidethesteelbeam(refernotchinglimitations)withthejoistsbearingonthebottomflangeofthesteel beam
15
2M12galvanisedboltsat60mmcentres or M12 all thread
Double TECBEAM™ floor joists carrying high loads e.g. stair landing
Joist Hanger
Waler plate bolted to wall
Not visible in this view:100x75x6MSangles: 300mmlong(T30) 240mmlong(T25)2-D16 (M12 thread) dynabolt anchors per angle 60mmembedmentat: 180mmcrs(T30) 130mmcrs(T25)
Trip-L-grip or skew nailing
Bolt, Tek screw, or power fasten to web
Block alternate bays
Joist Hanger
A2. Larger Steel beams – TECBEAM™ joists shallower in depth than steel beams (no notching)
• Installsolidtimberblockinginalternatebays
• Fixblockingsecurelytothewebofthesteelbeambybolting,TekscrewsorRamsetpowerfasteners
A3. Larger Steel beams – Shallower TECBEAM™ joists with timber bearing plate
• Installsolidtimberblockinginalternatebays
• Fixblockingsecurelytothewebofthesteelbeambybolting,TekscrewsorRamsetpowerfasteners
16
Trip-L-grip or skew nailing
Bolt, Tek screw, or power fasten to web
Block alternate bays
Trip-L-grip or skew nailing
Bolt, Tek screw, or power fasten to web
Block alternate bays
Bearingplate–boltorpowerfastentoweb
17
B. Beam Cleats – use where it is not practical to bear on the flange• Weldsteelcleats,orfixanglestothebeamwebandinstallboltsthroughthejoistwebstiffenerasshown
• Boltsindicatedarefornormalfloorloadsonly
Joist Bolts Minimum
a b c
T25 2M10 70 50 25
T30,T35 2M12 85 80 30
6mm Welded web cleat
Welded web cleat
a
b
c
C. Continuous solid timber packing• Packthesteelbeamwithcontinuoussolidtimber
• Boltpackingtosteelbeamwebasperengineer’sspecificationsandfixTECBEAM™withjoisthangerorTrip-L-Grip
• Ensurethesteelbeamisbracedagainstrotationcausedbytheoffsetloading
‘I’ Beam
or (PFC):
18
Beam braced against rotation
Trip-L-Grip or joist hanger
Boltstoengineer’sdesign
Continuous timber packing
PFC
Trip-L-Grip or joist hanger
Boltstoengineer’sdesign
Continuous timber packing
25mmMax.overhang
Design notes:
19
BEAM
48–50HallamSouthRoad HallamVIC3803
Tel 1800333162 Fax 0397963449
email [email protected]
Design by TheSHAPEGroup