Upload
lethuy
View
414
Download
60
Embed Size (px)
Citation preview
NA016 - Manual - 06 - 2011
MANUAL
NA016PHASE & RESIDUAL OVERCURRENT
PROTECTION RELAY
2 NA016 - Manual - 06 - 2011
TABLE OF CONTENTS
1 INTRODUCTION 4Scope and liability ...........................................................................................................................................................................................4Applicability ......................................................................................................................................................................................................4Conformity ........................................................................................................................................................................................................4Technical support ............................................................................................................................................................................................4Copyright ...........................................................................................................................................................................................................4Warranty ...........................................................................................................................................................................................................4Safety recommendations ...............................................................................................................................................................................4Insulation tests ................................................................................................................................................................................................4Product identification .....................................................................................................................................................................................5Environment .....................................................................................................................................................................................................5Graphical conventions ...................................................................................................................................................................................5Glossary/definitions ........................................................................................................................................................................................5
2 GENERAL 9Preface ............................................................................................................................................................................................................. 9Photo ................................................................................................................................................................................................................ 9Main features ................................................................................................................................................................................................ 10
3 TECHNICAL DATA 113.1 GENERAL ............................................................................................................................................................................................................11
Mechanical data ...........................................................................................................................................................................................11Insulation ........................................................................................................................................................................................................11EMC tests for interference immunity .........................................................................................................................................................11Voltage dip and interruption ........................................................................................................................................................................11EMC tests for interference immunity .........................................................................................................................................................11Emission ..........................................................................................................................................................................................................12Mechanical tests ...........................................................................................................................................................................................12Climatic tests ..................................................................................................................................................................................................12Safety ..............................................................................................................................................................................................................12Certifications ..................................................................................................................................................................................................12
3.2 INPUT CIRCUITS .............................................................................................................................................................................................. 13Auxiliary power supply U aux ...................................................................................................................................................................... 13Phase current input circuits ....................................................................................................................................................................... 13Residual current input circuit ..................................................................................................................................................................... 13Binary input circuits ..................................................................................................................................................................................... 13
3.3 OUTPUT CIRCUITS ........................................................................................................................................................................................... 13Output relays ................................................................................................................................................................................................. 13
3.4 MMI .....................................................................................................................................................................................................................143.5 COMMUNICATION INTERFACES ...................................................................................................................................................................14
Local port ........................................................................................................................................................................................................14Remote ports ..................................................................................................................................................................................................14
3.6 GENERAL SETTINGS ........................................................................................................................................................................................14 3.7 PROTECTIVE ELEMENTS .................................................................................................................................................................................14
Phase overcurrent - 50/51 ............................................................................................................................................................................14Residual overcurrent - 50N/51N .................................................................................................................................................................15
3.8 CONTROL AND MONITORING ........................................................................................................................................................................16Trip Circuit Supervision - 74TCS ..................................................................................................................................................................16Circuit Breaker monitoring ..........................................................................................................................................................................16Oscillography (DFR) ......................................................................................................................................................................................16
3.9 MEASURES ........................................................................................................................................................................................................16
4 FUNCTION CHARACTERISTICS 174.1 HARDWARE DESCRIPTION .............................................................................................................................................................................17
Power supply board ......................................................................................................................................................................................17CPU board ...................................................................................................................................................................................................... 18Input board .................................................................................................................................................................................................... 18MMI (keyboard, LED and display) ............................................................................................................................................................. 18
4.2 SOFTWARE DESCRIPTION ............................................................................................................................................................................. 19Kernel ............................................................................................................................................................................................................. 19Drivers ............................................................................................................................................................................................................ 19Application..................................................................................................................................................................................................... 19Base protocol (kernel) ................................................................................................................................................................................. 19Calibration (kernel) ....................................................................................................................................................................................... 19Communication (drivers) ............................................................................................................................................................................. 19MMI (drivers) ................................................................................................................................................................................................ 19Data Base (application/drivers) ................................................................................................................................................................. 20Self-test (application) .................................................................................................................................................................................. 20
3NA016 - Manual - 06 - 2011
Development tools ....................................................................................................................................................................................... 204.3 I/O DESCRIPTION ..............................................................................................................................................................................................21
Metering inputs .............................................................................................................................................................................................21Signal processing ..........................................................................................................................................................................................21Use of measured values ...............................................................................................................................................................................22Binary inputs ................................................................................................................................................................................................. 23Output relays ..................................................................................................................................................................................................24LED indicators ................................................................................................................................................................................................25Communication interfaces ...........................................................................................................................................................................26
4.4 PROTECTIVE ELEMENTS .................................................................................................................................................................................27Rated values ...................................................................................................................................................................................................27Phase overcurrent - 50/51 ........................................................................................................................................................................... 29Residual overcurrent - 50N/51N .................................................................................................................................................................31
4.5 CONTROL AND MONITORING ....................................................................................................................................................................... 33Data Logger ................................................................................................................................................................................................... 33Trip circuit supervision - 74TCS.................................................................................................................................................................. 33Circuit breaker supervision .........................................................................................................................................................................35 Test ..................................................................................................................................................................................................................36Oscillography ................................................................................................................................................................................................36
5 MEASURES, LOGIC STATES AND COUNTERS 37Measures ........................................................................................................................................................................................................37Circuit breaker ...............................................................................................................................................................................................37Counters ..........................................................................................................................................................................................................37Fault recording - SFR ....................................................................................................................................................................................37Event recording - Events ..............................................................................................................................................................................37Setting changes - Settings ......................................................................................................................................................................... 38Info .................................................................................................................................................................................................................. 38Protections trip ............................................................................................................................................................................................. 38Self-test .......................................................................................................................................................................................................... 38Oscillography - DFR ..................................................................................................................................................................................... 39
6 INSTALLATION 416.1 PACKAGING .......................................................................................................................................................................................................416.2 MOUNTING ........................................................................................................................................................................................................416.3 ELECTRICAL CONNECTIONS ......................................................................................................................................................................... 436.4 NOMINAL CURRENT In AND IEn SETTING ................................................................................................................................................. 486.5 NOMINAL CURRENT In SETTING FOR LPCT .............................................................................................................................................. 506.6 LED ALLOCATION ..............................................................................................................................................................................................516.7 FINAL OPERATIONS .........................................................................................................................................................................................51
7 PROGRAMMING AND SETTINGS 527.1 SW ThySetter.....................................................................................................................................................................................................52
ThySetter installation ....................................................................................................................................................................................52ThySetter use .................................................................................................................................................................................................52
7.2 MMI (Man Machine Interface) ..................................................................................................................................................................... 53Reading variables (READ) ........................................................................................................................................................................... 53Setting modifying (SET) ............................................................................................................................................................................... 53Test ...................................................................................................................................................................................................................54Communication ..............................................................................................................................................................................................55Reset ................................................................................................................................................................................................................55DEFAULT (Option) ..........................................................................................................................................................................................55Data/time setting (Time) ...............................................................................................................................................................................55
7.3 MENU TREE........................................................................................................................................................................................................567.4 MAINTENANCE ................................................................................................................................................................................................ 587.5 REPAIR ............................................................................................................................................................................................................... 587.6 PACKAGING ...................................................................................................................................................................................................... 58
8 APPENDIX 598.1 APPENDIX A1 - Inverse time IEC curves .................................................................................................................................................... 59
Mathematical formula ................................................................................................................................................................................. 59Phase overcurrent 50/51 - Standard inverse time curve (IEC 60255-3/BS142 type A) ..................................................................... 60Phase overcurrent 50/51 - Very inverse time curve (IEC 60255-3/BS142 type B) ..............................................................................61Phase overcurrent 50/51 - Extremely inverse time curve (IEC 60255-3/BS142 type C) .....................................................................62
8.2 APPENDIX B1 - I/O Diagram .......................................................................................................................................................................... 638.3 APPENDIX B2 - Interfaces ..............................................................................................................................................................................648.4 APPENDIX B3 - Connection diagrams ..........................................................................................................................................................658.5 APPENDIX C - Dimensions ............................................................................................................................................................................. 688.6 APPENDIX D - Revisions history ................................................................................................................................................................... 698.7 APPENDIX E - EC Declaration of conformity ............................................................................................................................................... 70
44 NA016 - Manual - 06 - 2011 INTRODUCTION
1 I N T R O D U C T I O N1 I N T R O D U C T I O NScope and liability
This document describes the functions, the technical data of NA016 devices; instructions for mount-ing, setting and commissioning are included.This manual has been checked out, however, deviations from the description cannot be completely ruled out, so that no liability in a legal sense for correctness and completeness of the information or from any damage that might result from its use is formally disclaimed.The information given in this document is reviewed regularly; any corrections and integration will be included in subsequent editions that are identifi ed by the date of revision.We appreciate any suggestions for improvement.We reserve the right to make technical improvements without notice.
ApplicabilityThis manual is valid for NA016 devices with fi rmware version 1.00 and following.Revision history is listed in appendix.
ConformityThe product complies with the CEE directives:
EMC Council Directives: 89/336/EECLow voltage Directives: 73/23/EEC
Technical supportContact: THYTRONIC Technical Service www.thytronic.it
CopyrightAll right reserved; It is forbidden to copy, modify or store material (document and sw) protected by copyright without Thytronic consent.
WarrantyThytronic warrants devices against defects in materials and workmanship under normal use for a period of ONE (1) YEAR from the date of retail purchase by the original end-user purchaser (“War-ranty Period”).
Safety recommendationsThe warming contained in this document are all-important for safety; special attention must be paid to the following symbols:
Installation and commissioning must be carried out by qualifi ed person; Thytronic assumes no re-sponsibility for damages caused from improper use that does not comply all warning and caution in this manual.In particular the following requirements must be met:
Remove power before opening it.Verify the voltage absence by means suitable instrumentation on relay connections; attention must be paid to all circuits supplied by external sources (binary input, CT, etc...) Care must be taken when handling metal parts (front panel, connectors).
Insulation testsAfter insulation tests, hazardous voltages (capacitor charges,...) may be arise; it is advisable to grad-ually reduce the test voltage avoiding to erase it abruptly.
••
••
•
WARNING Death, severe personal injury or substantial property damage can result if proper precautionsare not taken.WARNING Death, severe personal injury or substantial property damage can result if proper precautionsare not taken.
CAUTION Minor personal injury or property damage can result if proper precautions are not takenCAUTION Minor personal injury or property damage can result if proper precautions are not taken
CAUTIONSettings must be established on the basis of a coordination study.Numerical values inside examples have educational purpose only; they don’t be used, in no way,for actual applications.
CAUTIONSettings must be established on the basis of a coordination study.Numerical values inside examples have educational purpose only; they don’t be used, in no way,for actual applications.
5NA016 - Manual - 06 - 2011INTRODUCTION
Product identifi cationEach device is equipped with:
Identifi cation label installed on the front side with following informations: code number, phase and residual nominal currents, auxiliary voltage range and CE mark:
Test label with following informations: data, serial number and test operator signature.
EnvironmentThe NA016 device must be employed according to the environment conditions shown (see technical data).In case of different environment conditions, appropriate provisions must be provided (conditioning system, humidity control, etc...).If contaminants are present (dust, corrosive substances, etc...), filters must be provided.
Graphical conventionsThe CEI/IEC and ANSI symbols is employed where possible:e.g.: 51 = ANSI code concerning the overcurrent element.Following text formats are used:The ThySetter[1] menu: Phase overcurrent -50/51The parameter description (measures, thresholds, operate time,...) and related value: First threshold 50/51 defi nite time I>defThe display messages (MMI) are shown as: NA016Notes are highlighted with cursive letters inside colored bar
Note: Useful description note
Glossary/defi nitionsI En Relay residual nominal currentI Enp Residual CT primary nominal currentI n Relay phase nominal currentI np Phase CT primary nominal current50/51 Phase overcurrent ANSI code50N/51N Residual overcurrent ANSI code74CT CT supervision74TCS Trip Circuit Supervision
DFR Digital Fault Recorder (Oscillography)SER Sequential Event RecorderSFR Sequential Fault RecorderANSI American National Standard Institute
Note 1 The graphic interface and the operation of the ThySetter software are described in the relative chapters
•
•
Standard CTs - Logger Standard CTs - No Logger
LPCT inputs - Logger LPCT inputs - No Logger
NA016#xx00
In 5A 1A
50-5150N-51N
5A
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx10
In 5A 1A
50-5150N-51NCB OPENCB CLOSEDTCS
5A
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx01
In Rated 50...500A/Extended 50...1250A
50-5150N-51N
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx11
In Rated 50...500A/Extended 50...1250A
50-5150N-51NCB OPENCB CLOSEDTCS
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
Standard CTs - Logger Standard CTs - No Logger
LPCT inputs - Logger LPCT inputs - No Logger
NA016#xx00
In 5A 1A
50-5150N-51N
5A
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx10
In 5A 1A
50-5150N-51NCB OPENCB CLOSEDTCS
5A
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx01
In Rated 50...500A/Extended 50...1250A
50-5150N-51N
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx11
In Rated 50...500A/Extended 50...1250A
50-5150N-51NCB OPENCB CLOSEDTCS
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
66 NA016 - Manual - 06 - 2011 INTRODUCTION
IEEE Institute of Electrical and Electronics EngineersIEC International Electrotechnical CommissionCENELEC Comité Européen de Normalisation Electrotechnique
52 o CB (Circuit Breaker) Circuit Breaker52a Auxiliary contact in the breaker that is in the same position as the
breaker. It can be assigned to a binary input to locate the CB posi-tion (Breaker failure and/or CB diagnostic functions). (52a open = CB open)
52b Auxiliary contact in the breaker that is in the opposite position as the breaker (52b open = CB closed)
K1...K4 Output relaystTR1... tTR4 Output relay minimum pulse widthLatched Output relay with latched operation (manual reset) Output relay with
latched operation (automatic reset)
No-latched Output relay with no-latched operation (automatic reset)
CT or TA Current TransformerLPCT Low Power Current Transformer
P1 IEC nomenclature for primary polarity mark of CTs (as an alternative to a ANSI dot)
P2 IEC nomenclature for primary polarity mark of CTs (as an alternative to a ANSI no-dot)
S1 IEC nomenclature for secondary polarity mark of CTs (as an alternative to a ANSI dot)
S2 IEC nomenclature for secondary polarity mark of CTs (as an alternative to a ANSI no-dot)
Self test DiagnosticStart Leave an initial condition or reset condition (Pickup)Trip Operation (with operate time)
Operating time Duration of time interval between the instant when the character-istic quantity in reset condition is changed, under specifi ed condi-tions, and the instant when the relay operates
Dropout ratio The ratio of a reset value to an operate value in well-specifi ed con-ditions. The dropout ratio may be lower or greater than 1 according as an over or under element is considered
Reset time Duration of the time interval between the instant when the charac-teristic quantity in operate condition is changed, under specifi ed conditions, and the instant when the relay operates.
The stated reset time is related to a step variation of characteristic quantity in operate condition to the reset condition.
Overshoot time The critical impulse time for a relay which is in its reset condition, is the longest duration a specifi ed change in the input energizing quantity(ies) (characteristic quantity), which will cause the relay to change to operate condition, can be applied without the relay switches. The overshoot time is the difference from the operate time and the critical impulse time.
The declared values for the overshoot time are applicable with the lower setting value of the operation time.
MMI (Man Machine Interface) Operator front panel
ThySetter Setting and monitoring softwareLog fi le A text fi le that lists actions that have occurred (ThySetter).J2SE Java Platform Standard EditionSw SoftwareFw FirmwareUpgrade Firmware upgradeXML eXtensible Markup Language
7NA016 - Manual - 06 - 2011INTRODUCTION
Symbols.ai
Symbols
I>> Star t
I>> BF_OUT
IPh Block2
Logic internal signal (output); may be a logical state (e .g . I>> Star t) or a numerical valueIt is available for reading (ThySetter + communication interface)
Logic external signal (intput); may be a command coming from a binary input or a sw commandIt is available for reading (ThySetter + communication interface)
Internal signal (e.g. Breaker Failure output state concerning to the 2nd threshold of the 50 element) It is not available for reading (missing arrow)
AND and NAND logic gates
OR and NOR logic gates
Limit block (I>> threshold).
Computation block (Max phase current)
Threshold setting (e.g. pickup I >>).The value is available for reading and is adjustable by means ThySetter + MMI.
Switch
ON delay timer with reset (tON delay)
ON delay timer without reset (tON delay)
OFF delay timer (dropout) without reset (tDROP delay)
Curve type (definite/inverse time)0T
I L3
M a x [ I L1 ,I L2 ,I L3 ]I L2
I L1
tON tON tON tON
t
RESET
INPUT
OUTPUT
tDROPtON tON
t
INPUT
OUTPUT
tON tON tON
t
INPUT
OUTPUT
0TtON
& &
≥1 ≥1
EXOR logic gate
tDROP
=1
I >>
II ≥ I >>
tON
RESET
0T
0 T
88 NA016 - Manual - 06 - 2011 INTRODUCTION
Symbols1 .ai
tON tON tON
t
RESET
INPUT
OUTPUT
tDROP
tDROP
tDROP tDROP
Minimum pulse width operation for output relays (tTR) tTR
t
tTR
INPUT
OUTPUT
tTR
0 T
tTR
t
tTR
INPUT
OUTPUT
Latched operating mode for output relays and LEDs
Pulse operating mode for output relays
t
INPUT
OUTPUT
Latched
tTR
T0RESET
OFF delay timer (dropout) with reset (tDROP delay)
9NA016 - Manual - 06 - 2011GENERAL
2 G E N E R A L2 G E N E R A LPreface
The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent protection can be used on feeders of any length, while in ungrounded or Petersen coil and/or resistance grounded systems, the residual overcurrent protection can be used on feeders of small length in order to avoid unwanted trippings due to the capacitive current contribution of the feeder on external ground fault.The NA016 protection relay may be shipped with traditional CTs or low power (LPCT) current inputs.
Following input circuits are available:Three phase current and one residual current inputs with nominal currents independently select-able at 1 A or 5 A using DIP-switch (CT inputs) or 50...1250 primary amperes (LPCT inputs).Three binary inputs.
In addition to the main protection element, the Trip Circuit Supervision (TCS) is also provided.Setting, programming and reading operations must be effected by means of Personal Computer with ThySetter software or by means of remote communication interface (RS485 bus); all operations must be performed through MMI.The NA016 hardware case is suitable for fl ash and rack mountingOther options are:
Auxiliary power supply operating range.Communication protocols (Modbus or IEC60870-5-103).
Photo
•
•
••
1010 NA016 - Manual - 06 - 2011 GENERAL
Main featuresMetallic case. Backlight LCD 2x16 Display.Eight LEDs that may be joined with matrix criteria to many and various functions.RESET key to clear LED indications and latched output relays.Free settable three binary inputs.Independently settable for start, trip, self-test and control four output relay (K1...K4) Each output relay may be set with normally energized or normally de-energized operating mode and manual or automatic reset (latched/no-latched).Rear RS485 port, with ModBus protocol.RS232 front serial port (local communication for Thysetter).Real time clock with super capacitor backup.
The most signifi cant constructive features are:Galvanically insulated input and output circuits (communication and binary circuits included).Fast sampling rate for inputs.Optimum fi ltering of input signals through combined use of analog and digital fi lters.Traditional electromechanical-type fi nal output contacts with continuous monitoring of control coil continuity.Auxiliary supply comprising a switching-type voltage stabilizing circuit having a very wide working range and a very small power dissipationNominal frequency: 50 or 60 Hz.
The most signifi cant operating features are:Programming of operating modes and parameters by means of the front keys and alphanumeric display, with a programming procedure based on carrying out guided selections and on explicit and immediate signalling of the operations being performed, so that such procedure can be carried out without coding tables or mnemonic informations.The feature modifi cation operations do not interrupt the normal functions of the relay.Impossibility of programming unacceptable parameter values, thanks to the automatic limitation of top and bottom scale values for the relative setting ranges.Currents are sampled 64 times per period and measured in the effective value (RMS) of the funda-mental component using the DFT (Discrete Fourier Transform) algorithm and digital fi lters.The fault recorder (SFR) runs continuously capturing in circular mode the last twenty events upon trigger of binary input/output and/or element pickup (start-trip).The event recorder (SER) runs continuously capturing in circular mode the last three hundred events upon trigger of binary input/output.Recording of the last setting changes (Logger).Digital fault recorder (DFR) in COMTRADE format (oscillography).
••••••
•••
••••
•
•
•
••
•
•
•
••
11NA016 - Manual - 06 - 2011TECHNICAL DATA
3 T E C H N I C A L D A T A3 T E C H N I C A L D A T A
3.1 GENERAL
Mechanical dataMounting Flush, RackExternal dimensions 177 x 107 x 105 (high x width x depth)Terminals screw connectionMass 1.2 kg
Reference standards EN 60529, EN 60529/A1Degrees of protection provided by enclosures (IP Code)Front IP52Terminals IP20
Insulation
Reference standards EN 60255-5 IEC 60255-5
High voltage test (50 Hz 60 s) Auxiliary power supply 2 kVInput circuits 2 kVOutput circuits 2 kVOutput circuits (between open contacts) 1 kVCommunication interfaces 500 V
Impulse voltage withstand test (1.2/50 μs):Auxiliary power supply 5 kVInput circuits 5 kVOutput circuits 5 kVOutput circuits (between open contacts) 2.5 kV
Insulation resistance >100 MΩ
EMC tests for interference immunityReference standards
Product standard for measuring relays EN 50263Generic standards immunity for industrial environments EN 61000-6-2Electromagnetic compatibility requirements for measuring relays and protection equipment
EN 60255-26
Apparati di automazione e controllo per centrali e stazioni elettricheCompatibilità elettromagnetica - Immunità ENEL REMC 02
• Normativa di compatibilità elettromeccanica per apparati e sistemi ENEL REMC 01
Voltage dip and interruption
Reference standards EN 61000-4-29 IEC 60255-22-11Voltage dips, short interruptions and voltage variations on dc input power port immunity tests
Auxiliary power supply in dc energizing quantity Interruption (UT=40%) 100 msInterruption (UT=0%) 50 ms
• Voltage variations (UT=80...120%) 10 s
EMC tests for interference immunityReference standards EN 60255-22-1 IEC 60255-22-1 EN 61000-4-12 EN 61000-4-12Damped oscillatory wave
0.1 MHz and 1 MHz common mode 2.5 kV0.1 MHz and 1 MHz differential mode 1.0 kVRing wave common mode 2.0 kVRing wave differential mode 1.0 kV
Reference standards EN 60255-22-2 IEC 60255-22-2 EN 61000-4-2 IEC 61000-4-2Electrostatic discharge
Contact discharge 6 kVAir discharge 8 kV
Reference standards EN 60255-22-3 IEC 60255-22-3 EN 61000-4-3 IEC 61000-4-3Radiated radio-frequency fi elds
80...1000 MHz AM 80% 10 V/m 900 MHz Pulse modulated 10 V/m
•••
•••••
••••
•••
••
••
••••
••
••
1212 NA016 - Manual - 06 - 2011 TECHNICAL DATA
Reference standards EN 60255-22-4 IEC 60255-22-4 EN 61000-4-4 IEC 61000-4-4 Fast transient burst (5/50 ns)
Auxiliary power supply 2 kVInput circuits 4 kV
Reference standards EN 60255-22-5 IEC 60255-22-5 EN 61000-4-5 IEC 61000-4-5High energy pulse
Uaux (line-to-ground 10 ohm, 9 μF) 2 kVUaux (line-to-line 0 ohm, 18 μF) 1 kVI/O ports (line-to-ground 40 ohm, 0.5 μF) 2 kVI/O ports (line-to-line 40 ohm, 0.5 μF) 1 kV
Reference standards EN 60255-22-6 IEC 60255-22-6 EN 61000-4-6 IEC 61000-4-6Conducted radio-frequency fi elds
0.15...80 MHz AM 80% 1kHz 10 V
Reference standards EN 60255-22-7 IEC 60255-22-7 EN 61000-4-16 IEC 61000-4-16Power frequency immunity tests
Dc voltage 30 V50 Hz continuously 30 V50 Hz 1 s 300 V0.015...150 kHz 30 V
Reference standards EN 61000-4-8 IEC 61000-4-8Magnetic fi eld 50 Hz
50 Hz continuously 100 A/m50 Hz 1 s 1 kA/m
Reference standards EN 61000-4-10 IEC 61000-4-10Damped oscillatory magnetic fi eld
Damped oscillatory wave 0.1 MHz 30 A/m• Damped oscillatory wave 1 MHz 30 A/m
Emission
Reference standards EN 60255-25 IEC 60255-25 EN 61000-6-4 IEC 61000-6-4 EN 55011 CISPR 11Electromagnetic emission tests
Conducted emission auxiliary power supply 0.15...0.5 MHz 79 dB μVConducted emission auxiliary power supply 0.5...30 MHz 73 dB μVRadiated emission 30...230 MHz 40 dB μV/m
• Radiated emission 230...1000 MHz 47 dB μV/m
Mechanical testsReference standards EN 60255-21-1 EN 60255-21-2 RMEC01Vibration, shock, bump and seismic tests on measuring relays and protection equipment
EN 60255-21-1 Vibration tests (sinusoidal) Class 1• EN 60255-21-2 Shock and bump test Class 1
Climatic tests
Reference standards IEC 60068-x ENEL R CLI 01 CEI 50Operating temperature -25...+70 °CStorage temperature -40...+85 °CPermissible relative humidity 10...95 %Atmospheric pressure 70...110 kPa
Safety
Reference standards EN 61010-1Safety requirements for electrical equipment for measurement, control and laboratory usePollution degree 3Reference voltage 250 VOvervoltage category III
Certifi cationsReference standardsProduct standard for measuring relays EN 50263 CE Conformity
EMC Directive 89/336/EECLow Voltage Directive 73/23/EECType tests IEC 60255-6
••
••••
•
••••
••
•
•••
•
•••
13NA016 - Manual - 06 - 2011TECHNICAL DATA
3.2 INPUT CIRCUITS
Auxiliary power supply U aux VoltageNominal value (range)[1] 24...230 V~/-Operative range 19...265 V~/19...300 V-
Inrush current (max)24 V- 3 A, 1 ms48 V- 5 A, 1 ms110 V- 10 A, 1 ms230 V~ 40 A, 1 ms
Frequency (for alternate voltage supply) 45...66 HzMax distortion factor ( for alternating voltage supply) 15%Max alternating component (for dc voltage supply):
Full wave rectifi ed sine wave 100 %Sine wave 80 %
Power consumption: Maximum (energized relays, three LEDs, backlight ON) 4.5 W (UAUX = 24 V-)
• Maximum (energized relays, three LEDs, backlight ON) 9 VA (UAUX = 230 V~)
Phase current input circuitsStandard CTs:
Connections M4 terminalsRelay nominal phase current In 1 A or 5 A selectable by DIP-switchPermanent overload 25 AThermal overload (1 s) 500 ADynamic overload (half cycle) 1250 ARated consumption (for any phase) ≤ 0.002 VA with In=1 A ≤ 0.04 VA with In=5 A
LPCT - Low Power Current Transformers:Connections RJ45 plugRelay nominal phase current In 100 AExtended primary current 50 A...1250 A selectable by DIP-switchMax primary current 12.5 kANominal secondary voltage (with Inp = 100 A) 22.5 mV
Residual current input circuitRelay nominal residual current IEn 1 A or 5 A selectable by DIP-switch Permanent overload 25 AThermal overload (1 s) 500 ADynamic overload (half cycle) 1250 ARated consumption ≤ 0.006 VA with IEn=1 A ≤ 0.12 VA with IEn=5 A
Binary input circuitsQuantity 2Type optocouplerOperative range 24...265 V~/-Min activation voltage UDIGmin 18 VMax consumption, energized 3 mA
3.3 OUTPUT CIRCUITS
Output relaysQuantity 4Type of contacts changeover (SPDT, type C) Nominal current 8 ANominal voltage/max switching voltage 250 V~/400 V~Breaking capacity:
Direct current (L/R = 40 ms) 50 W (K1, K2, K4 trip)Direct current (L/R = 40 ms) 30 W (K3 signalling)Alternating current (λ = 0,4) 1250 VA
Make 1000 W/VAShort duration current (0,5 s) 30 AMinimum switching load 300 mW (5 V/ 5 mA)Life:
Mechanical 106 operationsElectrical 105 operationsMinimum pulse width (K1tTR...K4tTR) 0.01...0.50 s (step 0.01 s)
Note 1 The different versions must be select on order
••••
••
•
•••
•
1414 NA016 - Manual - 06 - 2011 TECHNICAL DATA
3.4 MMI
Display 16x2 LCD backlight module
LEDs Quantity 8
ON/fail (green) 1Start (yellow) 1Trip (red) 1Trip I>, I>>, I>>> (red) 1Trip IE>, IE>> (red) 152a - Circuit Breaker position (red) 152b - Circuit Breaker position (red) 1TCS - Trip Circuit Supervision (red) 1
Keyboard 8 keys[1]
3.5 COMMUNICATION INTERFACES
Local portConnection RJ10Baud rate 19200 bpsParity NoneProtocol Modbus RTU®
Remote ports
RS485Connection screw terminalsBaud rate 1200...57600 bpsProtocol[2] ModBus®RTU
IEC 60870-5-103
3.6 GENERAL SETTINGS
Relay nominal frequency fn 50, 60 HzPhase CT primary nominal current Inp [3] 1 A...1250 A 1...99 A (step 1 A) 100...1250 A (step 5 A)Residual CT primary nominal current IEnp [4] 1 A...1000 A 1...99 A (step 1 A) 100...1000 A (step 5 A)
3.7 PROTECTIVE ELEMENTS
Phase overcurrent - 50/51I> Element
I> Curve type (I>Curve) Inverse[5] IEC/BS A, B, C
50/51 First threshold inverse time (I>inv) 0.100...2.50 In 0.100...0.999 In (step 0.001 In) 1.00...2.50 In (step 0.01 In)Operating time (t>inv) 0.02...60.0 s 0.02...9.99 s (step 0.01 s) 10.0...60.0 s (step 0.1 s)
Nota 1 The “ O” and “ I” keys are not actives
Note 2 The different versions must be select on order
Note 3 The nominal current settings doesn’t concern the 50/51 protection elements; they must agree with nominal primary current for traditional CT inputs or dip-switch 50...1250 A for LPCT inputs for a right reading of the phase current primary values (Reading Direct).
Note 4 The nominal current settings doesn’t concern the 50N/51N protection elements; they must agree with nominal primary current of the CT inputs for a right reading of the residual current primary values (Reading Direct).
Note 5 Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t>inv / [(I/I>inv)0.02 - 1] Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t>inv / [(I/I>inv) - 1] Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t>inv / [(I/I>inv)2 - 1] t : operate time I> inv: pickup value t>inv: operate time setting Asymptotic reference value: 1.1 I>inv Minimum operate time: 0.1 s Equation is valid for 1.1 ≤ I/I>inv ≤ 20: - with traditional CTs and setting I>inv ≥ 2.0 In, the measuring upper limit is 40 In - with LPCT sensors and setting I>inv = 1.0 In and In = 625 A the measuring upper limit is 12500 A
••••••••
•••
15NA016 - Manual - 06 - 2011TECHNICAL DATA
I>> Element50/51 Second threshold defi nite time (I>>def)[1] 0.100...20.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...20.0 In (step 0.1 In)I>>def Operating time (t>>def) 0.03...10.00 s (step 0.01 s)I>> Reset time delay (t>>RES) 0.00...1.00 s (step 0.01 s)
I>>> Element50/51 Third threshold defi nite time (I>>>def) 0.100...20.0 In 0.100...0.999 In (step 0.001 In) 1.00...9.99 In (step 0.01 In) 10.0...20.0 In (step 0.1 In)I>>>def Operating time (t>>>def) 0.03...10.00 s (step 0.01 s)I>>> Reset time delay (t>>>RES) 0.00...1.00 s (step 0.01 s)
Pickup time ≤ 0.03 sDropout ratio 0.95...0.98Dropout time ≤ 0.04 sOvershoot time 0.03 sPickup accuracy ± 4% ± 1% InOperate time accuracy 5% or ± 10 ms
Residual overcurrent - 50N/51NIE> Element
50N/51N First threshold defi nite time (IE>def) 0.005...5.00 IEn 0.005...0.999 IEn (step 0.001 IEn) 1.00...5.00 IEn (step 0.01 IEn)IE>def Operating time (tE>def) 0.03...180 s 0.03...9.99 s (step 0.01 s) 10.0...99.9 s (step 0.1 s) 100...180 s (step 1 s)IE> Reset time delay (tE>RES) 0.00...1.00 s (step 0.01 s)
IE>> Element50N/51N Second threshold defi nite time (IE>>def) 0.005...5.00 IEn 0.005...0.999 IEn (step 0.001 IEn) 1.00...5.00 IEn (step 0.01 IEn)IE>>def Operating time (tE>>def) 0.03...10.00 s (step 0.01 s)IE>> Reset time delay (tE>>RES) 0.00...1.00 s (step 0.01 s)
Pickup time ≤ 0.03 sDropout ratio 0.95...0.98Dropout time ≤ 0.04 sOvershoot time 0.03 sPickup accuracy ± 4% ± 1% IEnOperate time accuracy 5% or ± 10 ms
Note 1 For all defi nite time elements the upper limit for measuring is 40 In for traditional CT input versions or 12.5 kA (primary current) for LPCT input versions:
- 40 In for traditional CT input versions - 12500 A (primary current) for LPCT input versions, so the maximum threshold adjustment depends on the In setting (Dip switch); eg: with In = 1000 A the max setting for I>>def and I>>>def thresholds is 12500/1000 = 12.5 In
1616 NA016 - Manual - 06 - 2011 TECHNICAL DATA
3.8 CONTROL AND MONITORING
Trip Circuit Supervision - 74TCSEnable (74TCS) On / OffOperating time 40 sReset time delay 6 s
Circuit Breaker monitoringCircuit breaker diagnostic
Diagnostic (CB Diagnostic) On / Off
Oscillography (DFR)Format COMTRADENumber of records 2Recording mode circularSampling rate 16 samples / power cycle
Set trigger:Pre-trigger time 0...63 T[1] [2]
Trigger inputs IN1, IN2, IN3Triggeroutputs K1...K4Manual Trigger ThySetterGeneral Trigger general from start / trips Start, TripTrigger from start / trips Start I>, I>>, ...Trip I>...
Set analog channels:Analog 1...Analog 4
Instantaneous currents value iL1, iL2, iL3, iERMS value of the fundamental component for phase currents IL1, IL2, IL3RMS value of the fundamental component for residual current IE
Set digital channels:Inputs IN1, IN2, IN3Outputs K1...K4General from start / trips Start, Trip
3.9 MEASURES
RMS value of the fundamental component for phase currents (IL1, IL2, IL3)RMS value of the fundamental component for residual current (IE)
Note 1 - T = number of power cyclesExample, with setting T=4 the pre-trigger is 80 ms with f = 50 Hz
••••••
•••
•••
17NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
4 F U N C T I O N C H A R A C T E R I S T I C S4 F U N C T I O N C H A R A C T E R I S T I C S
4.1 HARDWARE DESCRIPTION
The following fi gure illustrates the basic structure of the relay.
Printed boards hold the circuit components arranged according to a modular allocation of the main functions.
Power supply boardAll the components necessary for conversion and stabilization functions are present.Two versions are envisaged suited to the input range 24...230 V. The circuit provides stabilized voltages of +5 V and -5 V, required for the analogue measurement and +3.3 V for supplying the digital circuits. The circuit board additionally comprises:INPUT CIRCUITS:
Three binary input circuits, The logical input circuits and the block circuits include photo-couplers which provide for galvanic separation. OUTPUT CIRCUITS:
Four output relays (k1...K4).
•
•
hw.ai
RTC
CPU BOARD
POWER SUPPLY BOARD
INPUT MODULE
CTs
DSP
1A/5A
≈≈≈≈
EEprom
RS48
5
RELAYS
K1...K4 Output contacts
RS232
MMILCD
LEDs
BINARY INPUTS
IN1
InputIN2
IN3
POWER SUPPLY
+5 V
+10
V
0 V
+24
V-1
0 V
POW
ER F
AIL
RESE
T
Uaux
≈≈≈ L
PCTs
CUR
REN
T IN
PUTSIL1
IL2
IL3
L1
L2
SettingLPCT
800 A400 A
200 A100 A
50 A
L3
In=50...1250A
hw.ai
RTC
CPU BOARD
POWER SUPPLY BOARD
INPUT MODULE
CTs
DSP
1A/5A
≈≈≈≈
EEprom
RS48
5
RELAYS
K1...K4 Output contacts
RS232
MMILCD
LEDs
BINARY INPUTS
IN1
InputIN2
IN3
POWER SUPPLY
+5 V
+10
V
0 V
+24
V-1
0 V
POW
ER F
AIL
RESE
T
Uaux
≈≈≈ L
PCTs
CUR
REN
T IN
PUTSIL1
IL2
IL3
L1
L2
SettingLPCT
800 A400 A
200 A100 A
50 A
L3
In=50...1250A
1818 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
CPU boardThis circuit board contains all the circuits necessary for performing the analogue and digital pro-cessing of the signals.
Analog processingThe following are envisaged:
Anti aliasing fi lter circuits, .Amplifi er circuits for conditioning the input signals, Reference voltage adjustment circuits for the measurement A/D converter.
The relays usea a DSP processor operating at 40 MHzThe input currents are sampled at a frequency of 64 samples per period by means of a dual conversion system which allows the attainment of infor-mation pertaining to polarity and amplitude with high resolution. The measurement criterion allows precise measurement of even those signals having a unidirectional component, such as transient currents with overlapping exponential, which typically appear during faults. The circuit board also houses the output relays with the corresponding command and control cir-cuits, communication circuits, buttons, LCD display, LEDs and the key switch.
CPUA 32 bit DSP is provided. The following are envisaged:
Real Time Clock circuits with oscillator and super capacitor,RS232 communication port,RS485 communication port,
Memories:Ram: high speed static memoryFlash memory,EEprom memory: used for calibration data storage,
Input boardThree CTs committed for phase currents acquisition,One CT committed for residual current acquisition.
The input circuits are suitable for 1 A or 5 A external CTs.[1]
MMI (keyboard, LED and display)The MMI module (Man Machine Interface) includes:
An eight keys 8 keyboard,a backlight LCD display,Eight signalling LEDs,RS232 communication port.
Note 1 The phase and residual nominal currents must be adjusted by means dip-switch.
•••
•••
•••
••
••••
19NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
4.2 SOFTWARE DESCRIPTION
The program which handles operation of the Pro-N relays is made up of three fundamental elements shown in the following block diagram.
KernelThe kernel represents the nucleus of the system: it includes the processing functions closest to the electronic circuits; particularly the algorithms providing for the generation of the synchronisms (tim-ers) for sampling the analogue signals and numerical processing. The software is structured with interrupts operating with various priority levels in a non “pre-emp-tive” task system. By means of Discrete Fourier Transform calculation, based on 32 samples/period, information is deduced in relation to the amplitude and phase of all the current measurements; these are constantly updated and at the disposal of all the protection and control application algorithms. In addition, the kernel manages a service communication protocol known as Basic Protocol (BP).
DriversThe driver library contains all the specialised modules for the command and control functions which make up the connection ring between the kernel and the application. Examples of drivers include the Modbus communication and LCD display modules.
ApplicationThe application contains all the elements which carry out the protection and control functions. The main modules are:
- diagnostic function,- input management (logical inputs and block signal), - protective functions, - event recording, - output management (output relays, LEDs and block signals).
Each element (Kernel, Drivers and Application) may, in turn, be split into modules:
Base protocol (kernel)The module known as the Basic Protocol (BP) manages the service communication between the kernel and the other modules through the communication buses:
- direct for internal functional call,- SPI over synchronous serial, - SCI over asynchronous serial. The activities which may be performed by means of BP include:
- measurement confi guration ,- measurement reading,- measurement enabling.
Calibration (kernel)Calibration is performed using the base protocol functions for coordinating the calibration and test-ing stages with the automatic testing equipement (ATE).
Communication (drivers)The protective device implements the MODBUS RTU protocol for communicating via the RS232 inter-face with the ThySetter setting software and via the RS485 interface with the fi eld bus. All major codes according to the Modbus standard are envisaged; for a complete description and map of the addresses, please refer to the appendix mentioned further in this manual.
MMI (drivers)This handles the menus, available both on the panel and by means of Modbus messages, which may be run from commands using the keyboard, LEDs and LCD display. MMI information is stored in EEPROM and may be loaded remotely by means of the basic protocol functions.
APPLICATION
DRIVERS
timers
KERNELsampling
APPLICATION
DRIVERS
timers
KERNELsampling
2020 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
Data Base (application/drivers)Using modular criteria, the database is structured in three sections:
- RAM containing the volatile data, - REE and PAR containing the data recorded in non-volatile memory. Duplication of the data into two memory banks is envisaged with a continuous control system based on the cross checking of the consistency of the stored data. Modification of the calibration pa-rameters is split into two stages; in particular, data undergoing modification is placed in temporary memory and subsequently confirmed permanently (Store command) or discarded (Clear command). Instead, the area identified as REE is set aside for recording data which does not require the Store command for storage, or date written directly by the application (e.g.: counters,...)
Self-test (application)This function cyclically monitors the operation of the main hardware and software functions without affecting the process cycle with any signifi cant delays. In particular, the functions monitored are the following,
- the reference voltage levels,- output relay coil continuity, - the program fl ow control by monitoring the execution times and stack area occupancy,- checking the pilot wires (accelerated logic system), - the consistency of the data in the REE and PAR blocks, duplicated in the EEPROM.
Development toolsFor the development of the project, a CASE instrument has been developed, responsible for the opti-mized production of software code for the management of collaboration, the database and the MMI data and the Xml files used for communication. The automatic code generation criteria ensures the quality of the result in terms of the reusability, verifiability and maintainability of the software life cycle.
21NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
4.3 I/O DESCRIPTION
Metering inputsThe following input are provided:
Three phase current inputs fo traditional CTs or LPCTs (Low Power Current Transformers).One residual current input.The nominal currents are independently adjustable at 1 A or 5 A through DIP-switches (CTs inputs).
The input circuits are appropriately dimensioned in order to withstand the currents which arise when a fault occurs, both in transient and steady state condition.
Signal processingVarious processing levels are involved:
Acquisition (base level).Direct measures of physical channels (fi rst level).Calculated measures (second level).Derived (third level).
The measures concerning a level are based on data worked out in the previous level.For each level the required resources concerning the priority for tasks (conditioning circuits, DSP) are on hand.
ACQUISITION (base level)The input signals are sampled 24 times per power cycle
- iL1...iL3 phase currents instantaneous value- iE residual current instantaneous value
From the sampled quantities, several measures are computed for protection, monitoring and meter-ing purposes.
Samples are processed by means DFT (Discrete Fourier Transform) algorithm and the phase and amplitude of fundamental are computed:
Phase currents IL1, IL2, IL3
Residual current IE
•••
••••
•
•
sensor i .a i
NA016
3 phase CT current inputs
3 phase LPCT current inputs
one residual current input
sensor i .a i
NA016
3 phase CT current inputs
3 phase LPCT current inputs
one residual current input
acquis i t ion.ai
ACQUISITION
INSTANTANEOUS VALUES≈
acquis i t ion.ai
ACQUISITION
INSTANTANEOUS VALUES≈
IL1 .a i
(In)
ACQUISITION
iL1, iL2, iL3DFT
TA
≈ IL1, IL2, IL3
IL1 .a i
(In)
ACQUISITION
iL1, iL2, iL3DFT
TA
≈ IL1, IL2, IL3
IE .a i
(IEn)
ACQUISITION
iEDFT
TA
≈ IE
IE .a i
(IEn)
ACQUISITION
iEDFT
TA
≈ IE
2222 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
Use of measured values
i L1, i
L2, i
L3
I L1, I
L2, I
L3
i E I E Bin
ary
inpu
t IN
1
inar
y in
put I
N2,
inar
y in
put I
N3
Star
t (ST
ART)
Rel
ay K
1...K
4Tr
ip (T
RIP)
Rel
ay K
1...K
4Sr
art (
STAR
T) L
EDTr
ip (T
RIP)
LED
Trip
(50/
51) L
EDTr
ip (5
0N/5
1N) L
EDTr
ip (C
B OP
EN) L
EDTr
ip (C
B CL
OSED
) LED
(TCS
) LED
PROTECTIONPhase overcurrent (50/51) g g g g g gResidual overcurrent (50N/51N) g g g g g g
CONTROL & MONITORINGCircuit Breaker Position (52b) g g gCircuit Breaker Position (52a) g g gTrip Circuit Supervision (TCS) g gDiagnosticProtection statesInput statesOutput states
MEASURESPhase current gResidual current g
EVENT RECORDINGEvent 0 g g g g gEvent 1 g g g g gEvent ... g g g g gEvent 99 g g g g g
FAULT RECORDINGFault 0 g g g g gFault 1 g g g g gFault ... g g g g gFault 19 g g g g g
OSCILLOGRAPHYRecord 1 g g g g g g g g gRecord 2 g g g g g g g g g
23NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
Binary inputsThree binary inputs are available.The dry inputs must be powered with an external voltage, (usually the auxiliary power supply).The connections are shown in the schematic diagrams.
Every input is customized for a defi ned function.
FUNCTIONBinary input
IN1 IN2 IN3
52a (auxiliary CB contact) g
52b (auxiliary CB contact) g
TCS (Trip Circuit Supervision) g
TCSTrip Circuit Supervision.Supervision with one binary input may be performed.The exhaustive treatment of the TCS function is described in the concerning paragraph.
52a and 52bThe CB position can be acquired by means of binary inputs connected to the auxiliary contacts: the information is used to acquire the CB position (open-closed-fault).
TRIP
R
+UAUX
-UAUX
52a 52b52
NA016
Binary input IN3 Towards 74TCS logic
Trip Circuit Supervision - 74TCS
TRIP
R
+UAUX
-UAUX
52a 52b52
NA016
Binary input IN3 Towards 74TCS logic
Trip Circuit Supervision - 74TCS
CB positionCB diagnostic
52a52
52b
+UAUX
-UAUX
IN2
IN1
Binary input allocation for CB state acquisition
CB positionCB diagnostic
52a52
52b
+UAUX
-UAUX
IN2
IN1
Binary input allocation for CB state acquisition
2424 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
Output relaysFour output relays are available (K1...K4) with two changeover contacts (SPDT, type C):[1]
K1, K2 and K4 are trip relays.K3, is a signalling relay.[2]
Each output relay may be programmed with following operating mode:Operation MODE (No latched, Latched).Logic (Energized/De-energized).
To each output relay a programmable timer is matched (Minimum pulse width parameter).All parameters are available inside the Set \ Relays menu.
Any change to the settings can be affected at any time, also with the relay on duty, separately for each relay.Notes:
When de-energized operating mode is set, the relay remains in rest condition if no trip command is in progress.When energized operating mode is set, the relay remains in operating condition if no trip command is in progress and the auxiliary supply is powered on.When no-latched operating mode is set (Kx Mode No-latched), the output relay reset at the end of the trip condition. To each output relay a programmable timer is matched (minimum pulse width operation).When latched operating mode is set Kx Mode Latched, the output relay doesn’t reset at the end of the trip condition; it stays ON until a reset command is issued (RESET key, ThySetter or com-munication command).It is advisable to make sure that the output contact technical data are suitable for load (Nominal current, breaking capacity, make current, switching voltage,...).
Matching every output relay to any protective element is freely programmable inside the Setpoints submenus according a tripping matrix structure.[3][4]
FUNCTIONRELAY
K1 K2 K3 K4
Self-test relay g g g g
I> Start relays (Start I>) g g g g
I> Trip relays (Trip I>) g g g g
I>> Start relays (Start I>>) g g g g
I>> Trip relays (Trip I>>) g g g g
I>>> Start relays (Start I>>>) g g g g
I>>> Trip relays (Trip I>>>) g g g g
IE> Start relays (Start IE>) g g g g
IE> Trip relays (Trip IE>) g g g g
IE>> Start relays (Start IE>>) g g g g
IE>> Trip relays (Trip IE>>) g g g g
TCS Trip relays (Trip TCS) g g g g
Self test CB g g g g
Note 1 Schematic diagram are shown inside APPENDIX B1.
Note 2 Reduced breaking capacity for the K3 relays compared to that of K1, K2 and K4 relays.
Note 3 Matching of the output relay to the protective and control functions can be defi ned so that any collision from other function is avoided. All output relay are unassigned in the default setting.
Note 4 Self test relay: it is advisable to plan the following settings: - Energized operating mode, - No-latched , in order that it stays ON for normal conditions and the other way round it goes OFF if any fault is detected and/or the auxiliary supply turns OFF.
••
••
•
•
•
•
•
Input
No-latched operation
Latched operation
Output relay operation Relay-operat ion-t imers.ai
t
Minimum pulse widthtTR
Input
No-latched operation
Latched operation
Output relay operation Relay-operat ion-t imers.ai
t
Minimum pulse widthtTR
25NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
LED indicatorsEight LEDs are available.
One green LED “ON”: if turned on it means that the device is properly working, if fl ashing the inter-nal self-test function has detected an anomaly.One yellow LED “START” tagged for START of one or more protective elements. (I>, I>>, I>>>, IE>, IE>>)One red LED “TRIP” tagged for TRIP of one or more protective elements (I>, I>>, I>>>, IE>, IE>>).One red LED 1, latched, tagged for TRIP of one or more protective elements I>, I>>, I>>>One red LED 2, latched, tagged for TRIP of one or more protective elements IE>, IE>>One red LED 3, no latched, tagged for binary input state visualization 52a (CB position)[1]
One red LED 4, no latched, tagged for binary input state visualization 52b (CB position)[1]
One red LED 5, no latched, tagged for binary input state visualization TCS.[1]
FUNCTIONSLED
START TRIP 1 2 3 4 5
Start I> g
Trip I> g g
Start I>> g
Trip I>> g g
Start I>>> g
Trip I>>> g g
Start IE> g
Trip IE> g g
Start IE>> g
Trip IE>> g g g
Trip TCS g g
CB OPEN g
CB CLOSED g
Note 1 The LEDs 3, 4 (CB position) and 5 (TCS) are enabled only when the logger is enabled
•
•
••••••
Start
TCS (TCS trip)CB CLOSED (52b)CB OPEN (52a)
50-51 (I>, I>>, I>>> elements)50N-51N (IE>, IE>> elements)
Trip
Key not active
Key not active
Start
TCS (TCS trip)CB CLOSED (52b)CB OPEN (52a)
50-51 (I>, I>>, I>>> elements)50N-51N (IE>, IE>> elements)
Trip
Key not active
Key not active
2626 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
Communication interfacesSeveral communication ports are provided:
RS232 port on the front side for local communication (ThySetter).RS485 port on the rear side for bus communication.
RS232A simple DIN to RJ adapter can be used; the L10041 cable can be supplied.The RS232 port has high priority compared with the RS485 port.
If RS232 port is not available on Personal Computer, an USB-RS232 converter must be employed.[1]
The serial port is the simplest access for setting by means the ThySetter software.RS485
Several protocol are implemented:ModBus RTU. Modbus is a serial communications protocol. It is a de facto standard communica-tions protocol in industry, and is now the most commonly available means of connecting industrial electronic devices also inside electric utilities and substation. IEC 60870-5. The IEC 60870-5 suite of protocol is used for communications from master station to substation, as well within the substation; the IEC 60870-5-103 (Protection equipment) is available together the Modbus protocol on some version of Pro-n devices (code NA016#xCxx).
Note 1 After installation, the same communication port must be selected to defi ne the Thysetter parameters (typically COM4, COM5,...).
••
•
•
ser ia l -sch.ai
L10041
TXD
RXD
DTR
GND
4
3
1
2
1
2
3
4
6
7
8
95
Female connector
RJ10 Connector Pin1
ser ia l -sch.ai
L10041
TXD
RXD
DTR
GND
4
3
1
2
1
2
3
4
6
7
8
95
Female connector
RJ10 Connector Pin1
27NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
4.4 PROTECTIVE ELEMENTS
Rated valuesTraditional CT inputs
Relay phase nominal current InThe rated value must be set by means dip-switch to 1 A or 5 A, same as the secondary CTs nominal current.
Relay residual nominal current IEnThe rated value must be set by means dip-switch to 1 A or 5 A, same as the secondary nominal current of the residual CT.
Dip-switch is located on the CPU board; the exhaustive treatment of Dip setup is described in the “6.4 SETTING NOMINAL CURRENTS In AND IEn” paragraph.
Low Power CT inputsRelay phase nominal current InThe rated value must be set by means dip-switch to 50 A to 1250 A, same as the primary nominal current of the protected plant. All settings of the current thresholds are referred to the rated cur-rent of the relay In, that corresponds to the primary value automatically set as just described.Dip-switches are located on the rear board; the exhaustive treatment of Dip setup is described in the “6.5 NOMINAL CURRENT In SETTING FOR LPCT” paragraph.
Relay residual nominal current IEnThe rated value must be set by means dip-switch to 1 A or 5 A, same as the secondary nominal current of the residual CT. Dip-switch is located on board of the CPU board; the exhaustive treatment of Dip setup is de-scribed in the “6.4 and 6.5 SETTING NOMINAL CURRENTS In AND IEn” paragraph.
SettingsInside the Set \ Base menu the following parameters can be set:
Primary rated values (phase and residual), employed for measures relative to primary values.Measurements reading mode (Reading Direct or Relative).
Phase CT primary current InpThis parameter affects the measure of the phase currents when the primary measurement reading mode is selected (Reading Direct). It must be programmed to the same value of the phase CT primary nominal current Traditional CTs) or to the value set for the LPCT inputs.
Phase CT primary current InpThis parameter affects the measure of the phase currents when the primary measurement reading mode is selected (Reading Direct). It must be programmed to the same value of the phase CT primary nominal current Traditional CTs) or to the value set for the LPCT inputs.
Example
The phase CT primary current Inp must be set as: Inp = 500 A
Residual CT primary current IEnpThis parameter affects the measure of the residual current when the primary measurement read-ing mode is selected with traditional CTs inputs. It must be programmed to the same value of the residual CT(s) primary nominal current.
Example 1
•
•
•
••
••
•
•
•
Es-In.ai
KTA = 500A/5A=100
52
In
NA016
IL1...IL3
LPC
Ts C
URRE
NT
INPU
TSL1
L2
In = 500 A
In = 500 A
In = 500 A
LPCT Setting
800 A400 A
200 A100 A
50 A
L3
In=50...1250A
1A/5A
Es-In.ai
KTA = 500A/5A=100
52
In
NA016
IL1...IL3
LPC
Ts C
URRE
NT
INPU
TSL1
L2
In = 500 A
In = 500 A
In = 500 A
LPCT Setting
800 A400 A
200 A100 A
50 A
L3
In=50...1250A
1A/5A
Es1-IEn.ai
1x KTA = 100 A /1 A
52
IEn= 1 A
NA016
Es1-IEn.ai
1x KTA = 100 A /1 A
52
IEn= 1 A
NA016
2828 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
The residual CT primary current IEnp must be set as: IEnp = 100 AExample 2
The residual CT primary current IEnp must be set as: IEnp = 100 A
Measurement reading mode- With Reading Relative setting all measures are related to the nominal value,- With Reading Direct setting all measures are related to the primary value.
•
Es2-IEn.ai
3xKTA = 100A / 5A
52
IEn= 5 A
NA016
Es2-IEn.ai
3xKTA = 100A / 5A
52
IEn= 5 A
NA016
29NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
Phase overcurrent - 50/51Preface
Three operation thresholds, independently adjustable (I>, I>>, I>>>) with adjustable delay (t>, t>>, t>>>).The fi rst one may be programmed with inverse time according the IEC 60255-3/BS142 standard.The second and third thresholds have a defi nite time characteristic.For the defi nite time thresholds a reset time can be set (t>>RES, t>>>RES) useful to reduce the clearing time for intermittent faults.
Operation and settingsEach phase fundamental frequency current is compared with the setting value. Currents above the associated pickup value are detected and a start is issued. After expiry of the associated operate time a trip command is issued; if instead the current drops below the threshold, the element it is restored.The fi rst threshold (I>) may be programmed with defi nite or inverse time according the following characteristic curves:
Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t>inv / [(I/I>inv)0.02 - 1]Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t>inv / [(I/I>inv) - 1]Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t>inv / [(I/I>inv)2 - 1]
Where:t: operate timeI>inv: threshold settingt>inv: operate time setting
For all inverse time characteristics, following data applies:Asymptotic reference value (minimum pickup value): 1.1 I>invMinimum operate time: 0.1 sRange where the equation is valid:[1] 1.1 ≤ I/I>inv ≤ 20
For all defi nite time elements the upper limit for measuring is 40 In for traditional CT input versions or 12.5 kA (primary current) for LPCT input versions (e.g. 25 In with In = 500 A).All overcurrent elements can be enabled or disabled by setting the relative start and/or trip output to a selectable relay inside the Set \ Relays menu.The fi rst overcurrent element can be programmed with inverse time characteristic by setting the I>Curve parameter (DEFINITE, IEC/BS A, IEC/BS B, IEC/BS C) available inside the Set \ 50/51 menu.An adjustable reset time delay is provided for second and third threshold (t>>RES, t>>>RES).
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
•••
•••
t - int-F50-51.ai
II>>def I>>>def
I>inv
t>>>def
t>>def
I>inv
t
General operation time characteristic for the phase overcurrent elements - 50/51
TRIP
t - int-F50-51.ai
II>>def I>>>def
I>inv
t>>>def
t>>def
I>inv
t
General operation time characteristic for the phase overcurrent elements - 50/51
TRIPTRIP
Timers-F50-51.ai
I>> Start
I>> Trip
t>>def t>>def
INPUT
t>>RES t>>RES t>>RES
tI>> element - 50/51 - phase overcurrent timers Timers-F50-51.ai
I>> Start
I>> Trip
t>>def t>>def
INPUT
t>>RES t>>RES t>>RES
tI>> element - 50/51 - phase overcurrent timers
3030 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
Fun_50-51S1.ai
I L1
t>inv
0T≥1
I >inv
t>inv
Star t I>
Tr ip I>
I L1 ≥ I >inv
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
I> Curve
0TI L2
I L2 ≥ I >inv
I L3
I L3 ≥ I >inv
I>Start relays I>Start LEDs
I>Trip relays I>Trip LEDs
I L1
t>>def
0T≥1
I >>def
t>>def
Star t I>>
Tr ip I>>
I L1 ≥ I >>def
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
I L2
I L2 ≥ I >>def
I L3
I L3 ≥ I >>def
I>>Start relays I>>Start LEDs
I>>Trip relays I>>Trip LEDs
t >>RES
T0
t >>RES
I L1
t>>def
0T≥1
I >>>def
t>>>def
Star t I>>>
Tr ip I>>>
I L1 ≥ I >>>def
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
I L2
I L2 ≥ I >>>def
I L3
I L3 ≥ I >>>def
I>>>Start relays I>>>Start LEDs
I>>>Trip relays I>>>Trip LEDs
t >>>RES
T0
t >>>RES
General logic diagram of the phase overcurrent elements - 50/51
31NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
Residual overcurrent - 50N/51NPreface
Three operation thresholds, independently adjustable (IE>, IE>>, IE>>>) with adjustable delay (tE>, tE>>, tE>>>).For each threshold a reset time can be set (tE>RES, tE>>RES, tE>>>RES) useful to reduce the clearing time for intermittent faults.
Operation and settingsThe residual fundamental frequency current) is compared with the setting value. Current above the associated pickup value is detected and a start is issued. After expiry of the associated operate time a trip command is issued; if instead the current drops below the threshold, the element it is restored.
For all elements the upper limit for measuring is 10 IEn.All elements can be enabled or disabled by setting the relative start and/or trip output to a selectable relay inside the Set \ Relays menu.
An adjustable reset time delay is provided for every threshold tE>RES, tE>>RES, tE>>>RES).
t - int-F50N-51N.aiIE
t E>def
IE>def IE>>def
t E>>def
t
TRIP
General operation time characteristic for the residual overcurrent elements - 50N/51N
t - int-F50N-51N.aiIE
t E>def
IE>def IE>>def
t E>>def
t
TRIPTRIP
General operation time characteristic for the residual overcurrent elements - 50N/51N
Timers-F50N-51N.ai IE> element - 50N/51N - residual overcurrent timers
IE> Start
IE> Trip
tE> tE>
INPUT
tE>RES tE>RES tE>RES
t
Timers-F50N-51N.ai IE> element - 50N/51N - residual overcurrent timers
IE> Start
IE> Trip
tE> tE>
INPUT
tE>RES tE>RES tE>RES
t
3232 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
t>RES
T0
t E>RES
I E
IE>def t E>def
Fun_50N-51NS1.ai
t E>def
0T
Star t IE>
Tr ip IE>
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
I E ≥ I E>def
IE>Start relays IE>Start LEDs
IE>Trip relays IE>Trip LEDs
t>>RES
T0
t E>>RES
I E
IE>>def t E>>def
t E>>def
0T
Star t IE>>
Tr ip IE>>
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
I E ≥ I E>>def
IE>>Start relays IE>>Start LEDs
IE>>Trip relays IE>>Trip LEDs
General logic diagram of the residual overcurrent elements - 50N/51N
33NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
4.5 CONTROL AND MONITORING
Data LoggerPreface
When remotely controlled by shunt trip coil is employed a data Logger is advisable to provide a full monitoring of the protection system.[1]
Any power down of the auxiliary power supply are logged inside the 100 events; Power up and Power down are stored inside distinct eventsA dedicated element is provided for the Trip Circuit Supervision function; any fail inside the trip circuit is monitored (break on the coil and the circuit, power supply failure). The congruity of the auxiliary contact is detected in run time mode (52a and 52b), any failure is detect and stored inside the 100 events.Any setting change is logged and information is stored inside ten memory register with time stamp (date-time); any change is always stored inside the 100 events.Any start and/or trip of a protection element is stored inside the 100 events with time stamp (date-time); moreover a detailed information (trip cause, input currents, I/O states, faulted phase) is stored inside twenty memory register.The relay diagnostic (self-test) is verifi ed; any failure may drive relays and LEDs.
Trip circuit supervision - 74TCSPreface
The trip circuit can be monitored to signal possible anomalies that would lead to the missing opening of circuit breaker when trip and/or operator command are issued.Circuit interruption as well as missing of auxiliary voltage and/or coil faults are detected.
Operation and settingsThe 74TCS element may be enabled or disabled; to enable it, the 74TCS Enable parameter must be set to ON inside the Set \ Circuit breaker menu.By means of the right sizing of a resistor, the trip circuit supervision may be performed even with lower control voltage (e.g. when the control voltage is less than 36 V required for driving of two binary inputs, typically UAUX = 24V). The binary input is connected to the trip and an external resistor must be connected the 52b auxiliary contact.
Note 1 The Data Logger function is available on request (to be selected on order ).
•
•
•
•
•
50N 51N
50 51
DG
TA
TO
PG
74TCS
NA016
SELF
LOGGER
50N 51N
50 51
DG
TA
TO
PG
74TCS
NA016
SELF
LOGGER
TCS1s.ai
TRIP
R
+UAUX
-UAUX
52a 52b52
NA016
IN3
Binary input INx Towards 74TCS logic
Trip Circuit Supervision - 74TCS TCS1s.ai
TRIP
R
+UAUX
-UAUX
52a 52b52
NA016
IN3
Binary input INx Towards 74TCS logic
Trip Circuit Supervision - 74TCS
3434 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
The fault condition of the trip circuit is detected by binary input power down.With healthy circuit and TRIP contact closed, the binary input is feed across the 52a path (CB closed) or across the resistor R and 52b path (CB open).When the TRIP contact turns ON, the binary input becomes short-circuited; to avoid untimely opera-tions the previous condition are checked every 80 ms and the output is issued after a 40 s delay in order to allow the fault clearing and the consequent reset of the TRIP protection. Outputs are reset to zero after 6 s from the TRIP contact open.[1]
How to calculate resistanceBoth the following conditions must be fi lled:
The circuit breaker coil must no be powered when the CB is open and an open command is is-sued;The binary input is energized when the trip contact open.
If the circuit breaker is just open an unnecessary excitation must be avoided; the most critical event arises when the TRIP contact is closed (e.g. manual or test command), so with minimal series resistance. To avoid an unwanted excitation the series resistance must be higher than a minimum value defi ned as:
Rmin = RTC · (UAUX - UTCmin) / UTCminwhere: UTCmin: minimum coil excitation voltage UAUX: auxiliary voltage RTC: coil resistance
To energize the binary input circuit when the TRIP contact and CB open, the series resistance must be lowerer than a maximum value defi ned as:
Rmax = [(UAUX - UDIGmin) / IDIG] - RTCwhere: UDIGmin: minimum binary input excitation voltage (18 V) UAUX: auxiliary voltage RTC: coil resistance IDIG: binary input excitation current (0.003 A)
To satisfy the above requirements, the R value must be chosen between the Rmin and Rmax values; typically the normalized value nearest the arithmetic mean:
R = (Rmin + Rmax) / 2
The power dissipated by the R resistor is:
PR = R · I 2 = R · [UAUX / (R + RTC)] 2
ExampleUAUX = 110 Vcc (auxiliary voltage)PTC = 50 W (coil power)RTC = UAUX2 / PTC = 242 Ω (coil resistance)UTCmin = 77 V (minimum coil excitation voltage = 70% UAUX )UDIGmin = 18 V (minimum binary input excitation voltage)IDIG = 0.003 A (binary input excitation current)
Rmin = RTC · (UAUX - UTCmin) / UTCmin = 242 · (110 - 77) / 77 = 103.7 Ω
Rmax = [(UAUX - UDIGmin) / IDIG] - RTC = [(110 - 18) / 0.003] - 103.7 = 30563 Ω
R = (Rmin + Rmax) / 2 = (103.7 + 30563) / 2 = 15333 Ω ~ 15 k Ω
PR (Power dissipated by the R resistor) = UAUX2 /R = 1102 / 15000 = 0.8 W
PR = R · I 2 = R · [UAUX / (R + RTC)] 2
Note 1 The trip contact (TRIP) of the protection relays must be set with automatic reset (No-latched operating mode).
1)
2)
1)
2)
Fun-74TCS1.ai
040 s
T 06 s
T&Enable (ON≡Enable)
74TCS
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
IN3
Tr ip 74TCS
Relay Tr ip 74TCSLED Tr ip 74TCS
Tr ip 74TCS
Logic diagram concerning the Trip Circuit Supervision - 74TCS Fun-74TCS1.ai
040 s
T 06 s
T&Enable (ON≡Enable)
74TCS
TRIP
PING
MAT
RIX
(L
ED+R
ELAY
S)
IN3
Tr ip 74TCS
Relay Tr ip 74TCSLED Tr ip 74TCS
Tr ip 74TCS
Logic diagram concerning the Trip Circuit Supervision - 74TCS
35NA016 - Manual - 06 - 2011FUNCTION CHARACTERISTICS
Circuit breaker supervisionPreface
By means 52a and 52b auxiliary contacts, the CB position is acquired. Depending on such information the Open and/or Close commands can be safely issued by user.
The wrong congruity of the auxiliary contact is detected in run time mode (52a and 52b), by means of two binary inputs; any failure is detect and stored inside the 100 events (Data Logger).
Operation and settings52a is the auxiliary contact in the breaker that is in the same position as the breaker (52a open = CB open). It must be assigned to the IN2 binary input.52b is the auxiliary contact in the breaker that is in the opposite position as the breaker (52b open = CB closed)). It must be assigned to the IN1 binary input.
Fun-CB-position.ai
TRIP
PING
MAT
RIX
(L
ED)
52a ON/OFF
t mask
0T
t mask
CB moni tor ing
52b ON/OFF
52a52
52b
+UAUX
-UAUX
IN2
IN1=1
Logic diagram concerning the Circuit Breaker monitoring Fun-CB-position.ai
TRIP
PING
MAT
RIX
(L
ED)
52a ON/OFF
t mask
0T
t mask
CB moni tor ing
52b ON/OFF
52a52
52b
+UAUX
-UAUX
IN2
IN1=1
Logic diagram concerning the Circuit Breaker monitoring
3636 NA016 - Manual - 06 - 2011 FUNCTION CHARACTERISTICS
TestThe test function allows the checking of each 50-51 and 50N-51N protection function threshold by means of the introduction of a dummy signal, with twice the setting threshold value and duration as to cause the start and/or tripping of the threshold itself, into the input circuit stages of the relay. This test does not include checking the system measuring transformers and the relevant connec-tions to the digital protection relay. Having activated the test function mode, the threshold relating to the protective function to be checked and the relevant test method must be selected. The latter may or may not include changing the status of the output relays assigned as the selected threshold start and /or trip. For the thresholds relating to protective functions 50 and 51 the dummy signal is applied simultane-ously over all phases. Example, with setting t>inv = 1 s, the operate time for the fi rst element 50/51is:
10 s with IEC/BS A characteristic13.5 s with IEC/BS B characteristic26.6 s with IEC/BS C characteristic
In cases involving selection of the test mode without any changes in the status of the output relays (“blank” Testing), upon tripping of the selected threshold, the corresponding LED is lit and the test outcome recorded as the most recent event. The test condition is shown by means of the blinking green LED ON.[1]
Test I> ledTest I>> ledTest I>>> ledTest IE> ledTest IE>> led
In cases involving selection of the test mode with changes in the status of the output relays, at the start and/or tripping of the selected threshold the corresponding programmed output relay is switched, the corresponding LED lit and the outcome recorded as the most recent event. The test condition is shown by means of the blinking green ON.[2]
Test I> fullTest I>> fullTest I>>> fullTest IE> fullTest IE>> full
For both modes the test may be ended by means of the Test off command; in any case they are ended after 2 minutes.
Oscillography Set trigger
Following parameters, available inside the Oscillography \ Setting menu, are user-programmable:
Pre-trigger time.
With setting of the Trigger parameter General start or General trip the recording starts with state change of any protection elements.With setting of the Trigger parameter Manual the recording starts with manual command (Thy-Setter).With setting of the Trigger parameter K1...K4 the recording starts with state change of the se-lected output relay.With setting of the Trigger parameter IN1, IN2, IN3 he recording starts with state change of any binary input.With setting of the rigger aux parameter Start I>, Start I>>, Start I>>>,.... the recording starts with state change of start or trip of the selected protection element.
Set measured channels
The analog measures ((iL1, iL2, iL3, iE), IL1, IL2, IL3, IE) may be select inside the Oscillography \ Setting \ Analog channel 1...4 menu.Everyone of four analog channel may be associated to one of the selected measures.
Set digital channelsThe desired I/O signals may be select inside the Oscillography \ Setting \ Digital channels menu(General start, General trip, K1... K4, , IN1, IN2, IN3).
Note 1 The test is performed (LED) even if the concerning element is assigned to almost one output relay
Note 2 The test is performed (LED & relays) even if the concerning element is assigned to almost one output relay
•••
•••••
•••••
•
•
•
•
•
•
trigger.ai
Trigger
Timepre-trigger
record length
post-trigger
0...63 T
trigger.ai
Trigger
Timepre-trigger
record length
post-trigger
0...63 T
37NA016 - Manual - 06 - 2011MEASURES, LOGIC STATES AND COUNTERS
5 M E A S U R E S , L O G I C S T A T E S A N D C O U N T E R S 5 M E A S U R E S , L O G I C S T A T E S A N D C O U N T E R S Measures
RMS value of fundamental component for phase currents (IL1, IL2, IL3)RMS value of fundamental component for measured residual current (IE)
Circuit breaker
The CB and Trip Circuit Supervision states are providedPosition Open - Closed - UnknownTCS On - Off
and the binary inputs state:IN1-52b On/OffIN2-52a On/OffIN3-TCS On/Off
CountersFor every protective element and control function several counters are available; the partial coun-ters can be cleared by the user.Every partial counter is reset to zero when ten thousand count is passed. All partial counters can be cleared by means a single command; for this purpose the Reset coun-ters command must be issued available inside the Reset menu.
Counter ST I>Counter ST I>>Counter ST I>>>Counter ST IE>Counter ST IE>>Counter TR I>Counter TR I>>Counter TR I>>>Counter TR IE>Counter TR IE>>
Fault recording - SFRRecording[1] is triggered by:
Relay activation (OFF-ON)External trigger (binary input) programmed as Fault triggerElement start or trip
Twenty events are recorded into a circular FIFO (First In, First Out) buffer.[2]
Following information are stored in every record (Read \ Faults \ Info menu):Fault counter (Faults stored)[3]
Last faultDate and time (S-Year)Date and time (S-Year)Date and time (S-Month)...Date and time (S-MillisecondFault cause (F-Cause)Phase currents (F-IL1, F-IL2, F-IL3, F-IE)Residual current IEr or IECrInputsOutputsFault cause info (F-Phases)
The fault log may be erased by means of the command available inside the Read \ Faults \ Reset menu.
Event recording - EventsRecording is triggered by:
Power up and/or Power down.Element start or trip.Binary input switch (OFF-ON or ON-OFF).Setting modify.Control function trip (TCS OFF-ON or ON-OFF and CB switch OFF-ON or ON-OFF).
One hundred events are recorded into a circular FIFO (First In, First Out) buffer (Read \ Events \ Info menu).[4]
Following information are stored in every record (Read \ Faults \ Event menu):Event counter (Events stored) [5]
Last Event
Note 1 Data concerning the twenty events are stored into non volatile memory; they are held in spite of power down
Note 2 Fault 0 is the newest event, while the Fault 19 is the oldest event
Note 3 Counter is updated at any new record; it may be cleared by means ThySetter
Note 4 The newest event data are stored inside the event addressed by the Last event parameter (1...100)
Note 5 Counter is updated at any new record; it may be cleared by means ThySetter
••
••
•••
••••••••••
•••
•••••••••••••
•••••
••
3838 NA016 - Manual - 06 - 2011 MEASURES, LOGIC STATES AND COUNTERS
Date and time (S-Year)Data e ora (S-Year)Data e ora (S-Month)...Data e ora (S-Millisecond)Event cause (E-Cause)
Setting changes - SettingsAny change on the following parameters are stored:
Output relays (function, logic and mode).CB position monitoring enabling.TCS enabling.Threshold changes.
Ten events are recorded into a circular FIFO (First In, First Out) buffer.[1]
Following information are stored in every record (Read \ Faults \ Info menu):Fault counter (Setting stored)[2]
Last settingFollowing information are stored (Read \ Settings \ Setting menu):
S-Number counterS-I>CurveS-I>inv (I>threshold)S-t>inv (I> operate time)S-I>>def (I>> threshold)S-t>>def (I>> operate time)S-I>>>def (I>>> threshold)S-t>>>def (I>>> operate time)S-IE>def (IE> threshold)S-tE>def (IE> operate time)S-IE>>def (IE>> threshold)S-tE>>def (IE>> operate time)S-CB DiagnosticS-74 TCSS-K1 (K1 assignment)S-K1 logic (K1 logic)S-K1 mode (K1 mode)S-K2 (K2 assignment).....S-Year (Date)S-Month (Date)...S-Second (Time)
InfoCode NA016-aSerial ...... (Serial number)Firmware release ...... (eg: 2.00)Nominal freq. (eg: 50 or 60 Hz)Firmware release ...... (ef: 1.00)Protocol release ...... (eg: 1.00)
Protections tripProtections trip (eg: Trip I>>)
Self-testFollowing information are available (Read \ Self test \ Info menu):
TypeSelf-test causeSelf-test latch
The relay self-test function classifi es relay operational anomalies according to three levels: - MINOR ANOMALY: The device continues to function within the possible limits with the protective devices activated; - MAJOR ANOMALY: Operation of the device may be corrected by the operator by resetting the initial (default) confi guration and hence the desired settings; - FATAL ANOMALY: All logic and protective functions are inoperative and the relay must be returned to the factory. The internal self-test function is capable of detecting the following anomalies and indicating them by means of messages: - defective auxiliary power supply (FATAL ANOMALY); - output relay coil breakage (FATAL ANOMALY); - alteration of the calibration data stored in EEPROM memory (FATAL ANOMALY); - alteration of the parameters (threshold setting, times, relays… etc.) in EEPROM memory (MAJOR ANOMALY);
Note 1 The last change on settings ia stored inside memory addressed by the Last setting (1...10) parameter
Note 2 Counter is updated at any new record; it may be cleared by means ThySetter
••••••
••••
••
•••••••••••••••••••••••
••••••
•
•••
39NA016 - Manual - 06 - 2011MEASURES, LOGIC STATES AND COUNTERS
- alteration of the data (counters, records, ...etc.) in EEPROM memory (FATAL ANOMALY);Upon detection of at least one of the above mentioned anomalies, the output relay programmed for Self-test is switched and the information is recorded (latched).
Oscillography - DFR[1]
Upon programmable trigger, the fault records are recorded in COMTRADE[2] format; the sampled measures (16 sample per cycle) are stored in a circular memory buffer. The fault record are self-triggered; two records are stored in sequential order.An operating procedure example for the digital fault recording is illustrated inside the ThySetter section.
Following parameters are user-programmable:[3]
Pre-trigger time (0...63 T where T = number of power cycles; Example, with settings T=4 the pre-trig-ger duration is 80 ms with f = 50 Hz).
Selected sampled quantities.Analog channels (1...4) allocation.Digital channels allocation (output relay and/or binary inputs).Trigger setup; the information storage starts when a state transition on the selected signal occurs. (protective element start and/or trip, output relay and/or binary input switching).
Since the buffer size fi xed, the duration of the two recordings is variable and is then given the user-defi ned setting, with the following parameters:
Pre-trigger times (number of periods)Number of allocated channels.
Example 1With the following setting:
Analog channel 1: iL1Analog channel 2: iL2Analog channel 3: iL3Analog channel 4: iL4Digital channel: K1Pre-trigger: 1 T (20 ms)
the stored record length of the two records with f = 50 Hz is 240 ms
Example 2With the following setting:
Analog channel 1: iL1Analog channel 2: -Analog channel 3: -Analog channel 4: -Digital channel: K1Pre-trigger: 1 T (20 ms)
the stored record length of the two records with f = 50 Hz is 640 ms
Note 1 The oscillographic recorder requires a licence; to purchase it please contact Thytronic.
Note 2 COMTRADE format; (Common Format for Transient Data); This is a standard for the data exchange for various types of tests or simulation data, etc, for power system applications.
The measurements are recorded in ASCII or BINARY format. COMTRADE fi les always come by pairs: The “.CFG”-fi le describing the confi guration: number of analog and digital channels, sampling rate, scale factors, etc. The “.DAT”-fi le containing the data The COMTRADE is part of IEC 60255-24 standard. The recording can be analyzed by mean of ThySetter sw or any other standard compliant viewer.
Note 3 As all settings, the settings take effect only after sending the Store command
•
••••
••
••••••
••••••
trigger.ai
Trigger
Timepre-trigger
record length
post-trigger
0...63 T
trigger.ai
Trigger
Timepre-trigger
record length
post-trigger
0...63 T
trigger.ai
Trigger
Time240 ms
1 T20 ms
trigger.ai
Trigger
Time240 ms
1 T20 ms
4040 NA016 - Manual - 06 - 2011 MEASURES, LOGIC STATES AND COUNTERS
oscillo-phase.aiPhase/to/phase fault record
Display exampleThe fi gure below shows the registration of the followings:
Instantaneous value of phase current IL1 (IL1)Value of fundamental component of phase current IL1 (IL1 Measure)Logic state input IN1
Recording is started (triggers), with pre-trigger = 2T, I> start (General start).
•••
41NA016 - Manual - 06 - 2011INSTALLATION
6 I N S T A L L A T I O N6 I N S T A L L A T I O N
6.1 PACKAGING
Packaging consists of a paperboard packaging guaranteeing adequate protection for transport and storage under normal environmental conditions. The Pro-N protection relays must be stored within the required temperature limits; the relative hu-midity should not cause condensation or formation of frost.It is recommended that the devices are stored in their packaging; in the case of long storage, espe-cially in extreme climatic conditions.It is recommended that the packaging not be disposed of into the environment, but kept in case the relay should be moved at some later time.
6.2 MOUNTING
The devices are housed inside metal cases suitable assembly:Flush mountingRack9”.
Flush mountingThe fi xed case, fi tted with special fastening brackets, is mounted on the front of electric control board, previously drilled as indicated in the drawing.In case of side-by-side mounting of several relays the minimum drilling distance is determined by the front dimensions indicated in the overall dimensions drawing, increased by 3 mm, to ensure an adequate tolerance and gasket space between adjacent relays.The depth dimension, as indicated in the drawing, must be increased by as much as needed to allow room for the wiring.
Remove the upper tile and open the little door to access the fastening screws.
••
•
75 30107
177
ON 41 32 5
TRIP
START
102.5 ±0.3
70
161
154
N.4 fori ø 3.5
101
171
149
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8
E1
75 30107
177
ON 41 32 5
TRIP
START
102.5 ±0.3
70
161
154
N.4 fori ø 3.5
101
171
149
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8
E1
Remove-t i le.aiRemoving tie to access the fastening screws Remove-t i le.aiRemoving tie to access the fastening screws
4242 NA016 - Manual - 06 - 2011 INSTALLATION
The fi xed case is fastened by means of four screws onto the panel as indicated in the drawing.
Rack mountingFor mounting inside a standardized 19-inch system (EIA 310-D, IEC 60297 and DIN 41494 SC48D), the MAR adapter is required (available on request).
To allow opening of the keyboard door a one unit space must be provided when several rack are overlapping mounted.
•
Flush-mount1.aiFlush-mount1.ai
Rack-mount.aiRack mounting
177
(4U)
101.
6
482.6465
ON 41 32 5
TRIP
START ON 41 32 5
TRIP
START ON 41 32 5
TRIP
START ON 41 32 5
TRIP
START
Rack-mount.aiRack mounting
177
(4U)
101.
6
482.6465
ON 41 32 5
TRIP
START ON 41 32 5
TRIP
START ON 41 32 5
TRIP
START ON 41 32 5
TRIP
START
Rack-mount1.aiRack mounting Rack-mount1.aiRack mounting
43NA016 - Manual - 06 - 2011INSTALLATION
6.3 ELECTRICAL CONNECTIONS
Electrical connections should be made by referring to the connection diagram; in cases where cer-tain of the circuits (communication, block, or others) are not used, the relevant connections must remain open. Examples of connection diagrams are reported on Appendix to this manual.
For the A1...A22 connections and E1...E3 (RS485), screw terminals with following characteristics are available:
Nominal cross section: 0.14...2.5 mm2 (AWG 26...16) for single conductor da 0.14 a 0.75 mm2 for two conductors with same cross section
Tightening torque: 0.5-0.6 NmStripping length: 8 mm
The connections to the current signal inputs C1...C8 can be made by ring lugs suitable for M4 screws and an insulating panel covering the terminals may be mounted for safety purposes.
•
••
Devices must be installed by qualified personnel only. No liability is accepted from Thytronic due to improper use.CAUTION Devices must be installed by qualified personnel only. No liability is accepted from Thytronic due to improper use.CAUTION
Amperometric phase inputs from traditional CTs
Amperometric input from residual CT
Amperometric input from residual CT
Amperometric phase inputs from LPCTs
RS485
12
3
B-
A+UAUX
≅
A4A5K2
A2A1
A3K1
A11A10
A12K4
A13A14
A9
A7A8
A6
K3
A15A16A17A18A19
IN1
A20A21A22
IN2
IN3
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8
E1
31
2
RS485
12
3
B-
A+C7 C8
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
E1
31
2
L1
(100+200)300A
EX. In=
LPCT50
L3
200400
100
800
Setting
L2
L3
L2
L1
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
UAUX
≅
A5A4
A6K1
A11A10
A12K4
A13A14
A3
A1A2K3
A9
A7A8K2
A15A16A17A18A19
IN1
A20A21A22
IN2
IN3
Amperometric phase inputs from traditional CTs
Amperometric input from residual CT
Amperometric input from residual CT
Amperometric phase inputs from LPCTs
RS485
12
3
B-
A+UAUX
≅
A4A5K2
A2A1
A3K1
A11A10
A12K4
A13A14
A9
A7A8
A6
K3
A15A16A17A18A19
IN1
A20A21A22
IN2
IN3
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8
E1
31
2
RS485
12
3
B-
A+C7 C8
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
E1
31
2
L1
(100+200)300A
EX. In=
LPCT50
L3
200400
100
800
Setting
L2
L3
L2
L1
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
UAUX
≅
A5A4
A6K1
A11A10
A12K4
A13A14
A3
A1A2K3
A9
A7A8K2
A15A16A17A18A19
IN1
A20A21A22
IN2
IN3
4444 NA016 - Manual - 06 - 2011 INSTALLATION
Core balanced CTProper installation is shown in fi g. 1a and 1b.The current balance transformer, when used for measuring residual current, must be crossed in the same direction by all active conductors and hence, also by the neutral conductor if distributed, with the exception of the ground connection protective conductor. The drawing below shows cases of assembly of the toroid on unscreened and screened cables; prior to proceeding with assembly, it is necessary to check that there are no screen-to-ground connections upstream of the sensor.
In order to ensure a linear response from the sensor, the cables must be positioned in the centre of the transformer so that the magnetic effect of the three cables is perfectly compensated in the absence of residual current (Fig.2a). Hence, the assembly indicated in the drawing of fi g.2b, in which phase L3 causes local magnetic saturation whereby the vectorial sum of the three currents would be non-null, should be avoided. The same considerations also apply when the sensor is positioned near bends in the cabling. It is recommended that the transformer be placed away from bends in the conductors).The use of a balance transformer with an inside diameter about twice the diameter of the the cable going through it is recommended.
Fig. 1a Fig. 1b
Armoring
Load Load
Source Source
Insulated cables
Shielded cables
Armoring
Toroide.ai Current balanced transformerFig. 1a Fig. 1b
Armoring
Load Load
Source Source
Insulated cables
Shielded cables
Armoring
Toroide.ai Current balanced transformer
Fig. 2a Fig. 2b Fig. 2c
L1
L3L2
L1
L3L2
Toroide.ai Current balanced transformer
45NA016 - Manual - 06 - 2011INSTALLATION
EarthA protective ground connection is required, which must be connected to the suitable screw with a separate lead of at least 2.5 mm2; the connection from A21 or a22 terminal and the ground srew is also required.[1]
CT amperometric inputsThe amperometric input circuits are assembled inside the fi xed module, so no short circuit on the secondary CTs must be provided when the removable module is pulled outIn the event of case replacement, some camps must be provided externally to shorting the second-ary CTs circuits to avoid secondary open circuit of CTs that may endanger equipment or people.
When making the current connections, attention must be paid to not exceeding the performance of the line current transformers. To be exact, the total load, constituted by the protective relay, any other protective relays or measuring instruments and the resistance of the connections, must not ex-ceed the line CT performance. In particular, consumption of the relay input circuit must not exceed 0.2 VA while the load (expressed in VA) constituted by the conductors is given by:
0.018 × L × In2 / Swhere: L the overall length, expressed in m, of the two conductors in relation to each phase; In nominal current of the line CT expressed in A;S cross sectional area of the current conductors expressed in mm2.It is recommended that cabling of a suitable thickness be used in order to limit wear of the CT sec-ondary circuits.
LPCT amperometric inputsThe amperometric input are designed for Low Power Current Transformer with 100 A - 22.5 mv ratio. Connections to NA016 device must be carried out by means RJ45 plugs, forming a part of the Trans-former.[2]
Note 1 The A21 and A22 terminal are link together inside the relay
Nota 2 For technical data please call Thytronic.
In case of disconnection CT wiring to the case, pay attention must to do not open live circuits.CAUTION In case of disconnection CT wiring to the case, pay attention must to do not open live circuits.CAUTION
rear.aiEarthing
4646 NA016 - Manual - 06 - 2011 INSTALLATION
Binary inputsThe dry input circuits, despite being galvanically isolated, must preferably be supplied with the same auxiliary voltage of the control panel.The inputs are polarity free with wide voltage range.
The optocupled inputs are immune to transitory interferences, however the following recommenda-tion must be considered in high disturbed environments:
Position input wiring away from high energy sources.Use shielded cables with ground connection on only one end (preferably at the relay side.
Output relaysFour output relays are available (SPDT, type C):
K1, K2 and K4 (trip relays).K3 (signalling relay).
It is advisable to verify that the technical characteristic of the contacts be suitable for the applied load (about current, nominal voltage, make and break current , etc..).All contacts are shown in de-energized state for standard reference
RS232 portThe link from PC and NA10 serial port must be established by means a L10041 cable.
When no RS232 port is available on Personal Computer, a suitable USB to RS232 converter must be employed.After installation, the same communication port must be selected to defi ne the Thysetter parameters (typically COM4, COM5,...).
••
••
+UAUX
-UAUX
A13
A14 IN1
A B
A15
A16 IN2
A17
A18 IN3
+UAUX
-UAUX
A13
A14 IN1
A B
A15
A16 IN2
A17
A18 IN3
serial1-sch.ai
L10041
Female connector(solder side view) USB-RS232 converter
(if none RS232 PC port is available)
TXD
RXD
DTR
GND
4
3
1
2
1
2
3
4
6
7
8
95
RJ10 Connector Pin1
serial1-sch.ai
L10041
Female connector(solder side view) USB-RS232 converter
(if none RS232 PC port is available)
TXD
RXD
DTR
GND
4
3
1
2
1
2
3
4
6
7
8
95
RJ10 Connector Pin1
47NA016 - Manual - 06 - 2011INSTALLATION
RS485 portRS485 communication circuit connections must be made using screened twisted pair cable observ-ing the polarities; screening must only be connected to the end terminating at the RS485 interface circuit pertaining to the monitoring unit. It is recommended to terminate the line at the extremities of the same; this must be performed on the RS485 line control unit and on the NA016 device placed at the furthest point connecting the specially provided resistor; termination can be made by means a jumper between the E1-E2 terminals.Termination resistors allow adjusting the impedance of the line, reducing the infl uence of the induc-tive components of the same, which might compromise good communication.
RS485
120 Ω
SUPERVISION UNIT
OUTP
UT R
ELAY
S
UAUXA1 ≅
A2
A9
A10
A11A12
A13
A14
E1
E1
THYB
US
D1
ETHE
RNET
A3A4A5A6A7A8
K2
K3
K4
K5
K6
K1
RS48
5
F1F2F3F4F5A+
A+
B-
B-
BLOC
K OU
T
BLOC
K IN A15BLOUT-
BLOUT+ A16
BIN
ARY
INPU
TSA19
A18A17
IN1
IN2
A20A21A22
C1IL1
IL2
IL3
IE
CURR
ENT
INPU
TSC2C3
C4C5
C6
C7
C8
Pro-N
RS23
2
FRONT PANEL
RS485-wir ing.ai
NA016
RS48
5
1
23A+
B-
4848 NA016 - Manual - 06 - 2011 INSTALLATION
6.4 NOMINAL CURRENT In AND IEn SETTING
CT amperometric phase inputsFactory default settings:
Nominal phase current In: 5 ANominal residual current IEn: 1 A
To modify settings, the dip-switches placed on the front board must be changed (the case must be open).
The following operations must be performed:Remove the auxiliary supplyRemove the upper tile and open the little door to access the fastening screws.
Unscrew gradually back to back the four fastening screw in order avoid loss of the internal washer.Unmounting of the case from the switchboard is not needed.Rotate the MMI module with care to not disconnect the fl at cable.
Avoid touching the printed circuit and connections[1],
Note 1 There are components present which are sensitive to electrostatic discharge. When the module is removed, it is important to pay particular attention to avoid any accidental contact with the internal components. In order to avoid the static electricity accumulated in the human body from causing damage, it is recommended to observe the following precautions: - eliminate any potential differences between the human body and the device by touching the metallic case, - avoid touching the printed circuit and connections (tracks, component terminals), - avoid handing the device to others, - set the programming DIPs by using antistatic tools.
••
••
•••
•
Turn off power supply before opening the case.CAUTION Turn off power supply before opening the case.CAUTION
Remove-t i le.aiRemoving tie to access the fastening screws Remove-t i le.aiRemoving tie to access the fastening screws
49NA016 - Manual - 06 - 2011INSTALLATION
Set the dip-switches on the top of the circuit board in accordance with the drawing shown below,.
Move dip-switches according the following layout.[1]
Note 1 Place switches 1 ... 4 according to the number on the printed circuit board (not considering the numbers on the component)
•
•
Dip-swithes positionDip-swithes position
Dip-switch localization concerning the nominal current setting inside the front board
Default settings:- In =5 A- IEn =1 A
Settings:- In =5 A- IEn =5 A
Settings:- In =1 A- IEn =1 A
Settings:- In =1 A- IEn =5 A
1 A
5 A
ON
IL1
IL3
IL2
IE
1 A
5 A
ON
IL1
IL3
IL2
IE
1 A
5 A
ON
IL1
IL3
IL2
IE
1 A
5 A
ON
IL1
IL3
IL2
IE
1234
1234
1234
1234
5050 NA016 - Manual - 06 - 2011 INSTALLATION
6.5 NOMINAL CURRENT In SETTING FOR LPCT
LPCT amperometric phase inputs
Factory default settings: Primary nominal phase current In: 300 ANominal residual current IEn: 1 A as shown in the previous pages)
To modify the phase rated currents, the dip-switches placed on the rear panel must be set. [1]
Note 1 For LPCT versions the dip-switch position, located inside the CPU board, concerning the phase 1 A or 5 A current setting are irrelevant
••
C7 C8
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
E1
31
2
LPCTSetting
(100+200)300A
EX. In=
50
200400
100
800
50
200400
100
800
L3
L2
L1
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5 In= 300 A (100 + 200) Factory default setting
In= 50 A Minimum setting
In= 1250 A (800 + 400 + 50) Maximum setting
configurations not allowed !
cursor
51NA016 - Manual - 06 - 2011INSTALLATION
6.6 LED ALLOCATION
Eight indicator LEDs[1] and six keys[2] are available on the front panel:
6.7 FINAL OPERATIONS
Before energizing the electric board, it is advisable to check that:The auxiliary voltage in the panel falls within the operative range of relays.The rated current of the line CT’s corresponds to the settings of relay.All wirings are correct.All screws are tightly screwed.
Note 1 The LEDs 3, 4 (CB position) and 5 (TCS) are enabled only when the logger is enabled
Note 2 The “I” e “0“ keys are disabled
••••
Start
TCSCB CLOSED (52b)CB OPEN (52a)
50-51 (I>, I>>, I>>>)50N-51N (IE>, IE>>)
Trip
Key disabled
Key disabled
Start
TCSCB CLOSED (52b)CB OPEN (52a)
50-51 (I>, I>>, I>>>)50N-51N (IE>, IE>>)
Trip
Key disabled
Key disabled
5252 NA016 - Manual - 06 - 2011 SETTING AND COMMISSIONING
7 P R O G R A M M I N G A N D S E T T I N G S7 P R O G R A M M I N G A N D S E T T I N G S
All relay programming and adjustment operations may be performed through MMI (keyboard and display) or using a Personal Computer with the aid of the ThySetter software.
7.1 SW ThySetter
The ThySetter sw is a “browser” of data (setting, measure, etc..); it implements an engine that is afford to rebuild the menu set up and the relationships to data concerning all Thytronic protective relays by means of XML fi les.
ThySetter installationThe latest release of ThySetter can be downloaded free of charge from the www.thytronic.it site (Products - Software).[1]
ThySetter usePlease refer to ThySetter user manual for detailed instructions.The document is available on www.thytronic.it (Product / Sotware / ThySetter - Download area).
Note 1 Starting from the 3.5.9 release it is necessary to download and install not only the application setup but the Template setup also. In case off updating download and install only the new release.
WARNINGFor safety reasons, a change of the following parameters become active only after an hw reset:- Relay nominal frequency (fn)- Ethernet communication parameters (IP host address, IP net mask, Autonegotiation).
WARNINGFor safety reasons, a change of the following parameters become active only after an hw reset:- Relay nominal frequency (fn)- Ethernet communication parameters (IP host address, IP net mask, Autonegotiation).
53NA016 - Manual - 06 - 2011SETTING AND COMMISSIONING
7.2 MMI (Man Machine Interface)
On the front panel there are eight buttons which allow the user to perform all the settings, reading and modifi cation operations.[1]
The adjustment of the settings and the operation mode of the output relays must be performed while the unit is electrically powered; the alphanumeric display shows the necessary information with reference to the operations performed through the keyboard. All preset values are permanently stored in the nonvolatile memory.The buttons take the following operations:
- (Up) move the cursor upwards to the preceding menu options
- (Down) move the cursor downwards to the subsequent menu options
- (Left) move the cursor upwards to the preceding menu options
- (Right) move the cursor downwards to the subsequent menu options
- (Enter) access to the selected menu with the option of modifying any given parameter
- (Reset) abort the current changes and/or accessing the previous menu
At power-up, the display shows the text:“THYTRONICNA016date and time: (01/01/2000 00:00”The ON green Led points out the auxiliary power supply voltage (permanent lighted) and possible faults (blink lighted).The display backlight is automatically activated when any key switch is set.
By means of the (Up) or (Down) buttons, it is possible to cyclically browse through the menu op-tions: Read, Set, Oscillography, Communication, Test, Reset, Time, Option
Having identifi ed the sub-menu of interest, it is possible to gain access by using the (Right) button
and then analogously, run through the relevant options by using the (Up) or (Down) buttons. The full menu tree and some examples are showed in the following pages (numerical values and settings are pointed out as examples and does not agree with real situations.
Reading variables (READ)All data (measure, settings, parameters, etc...) may be displayed:“Measures >”“Circuit breaker >”“Counters >”“Last fault >”“Info >”“Protection trip >”“Self-test >”
Setting modifying (SET)To effect a change, having identifi ed the parameter intended for change, the following procedure must be performed:
Select the parameter going through the menus by means the , and keys.
Begin the setting phase by means of the key; the he modifi cation in progress status is high-lighted by the symbol “E” fl ashing in the upper right area of the display.
Change the parameter by means the (increment) or (decrement) buttons.
Nota 1 The “I” and “0“ keys are disabled
•
•
•
Start
TCSCB CLOSED (52b)CB OPEN (52a)
50-51 (I>, I>>, I>>>)50N-51N (IE>, IE>>)
Trip
Key disabled
Key disabled
Start
TCSCB CLOSED (52b)CB OPEN (52a)
50-51 (I>, I>>, I>>>)50N-51N (IE>, IE>>)
Trip
Key disabled
Key disabled
5454 NA016 - Manual - 06 - 2011 SETTING AND COMMISSIONING
Press the (Enter) button; acceptance of the change is indicated by the disappearance of the fl ashing “E” to be replaced by the symbol “!”. On must be remember that changes are NOT ac-tive until the Store command, located in the “Set” menu has been used; in this regard, once the
“Store” message is displayed, it is necessary to use the (Enter) button; this results in the
“execute” message with the symbol “C” fl ashing.
Browse the menu by means of the and or keys to go in the Store menu.
Press the (Enter) button; once more concludes the save procedure with the temporary appear-
ance of the message “ok!”. After one or more modifi cations, the status of having data that has still not been permanently saved is indicated by the “!” symbol in the top right and the display message “WARNING set Clear..
Store” which appears while browsing through the main menu with the use of the or keys.
The Clear command may be used to abandon unsaved changes (prior to use of the Store com-mand); the same effect is achieved by switching the key to the OFF position or removing the auxil-iary power supply to the relay.
ExampleTo set the K1 relay with Energized mode and latched mode (Energized, Latched) the following sequence must be operated:
Select the Set menu “Set >”by means of the key.
Press the key; the message “Base >” is displayed.
Browse the menus with “Relays >”“50/51 >”“50N/51N >”“Circuit breaker >”“Clear >”“Store >”
Select the “Relays >”, menu; the message “K1 None >” is displayed.
Press the key; the message “K1 Logic De-energized” is displayed.
Press the key; the he modifi cation in progress status is highlighted by the symbol “E” fl ashing in the upper right area of the display.
Change the parameter by means the or keys; the message “K1 Logic Energized” is displayed.
Press the key; acceptance of the change is indicated by the disappearance of the fl ashing “E” to be replaced by the symbol “!”.
Press the key; the message “K1 mode No-latched” is displayed.
Press the key; acceptance of the change is indicated by the disappearance of the fl ashing “E” to be replaced by the symbol “!”.
Change the parameter by means the (increment) or (decrement) buttons; the message “K1 mode Latched” is displayed.
Press the (Enter) button; acceptance of the change is indicated by the disappearance of the fl ashing “E” to be replaced by the symbol “!”
Press the key and or to go inside the Store menu.
Press the key; this results in the “execute ?” message with the symbol “C” fl ashing.
Answer with key to confi rm setting.The end of the setting sequence is signalled by the “ok!” message.
The Reset key may be used to abort unsaved changes (prior to use of the Store command); the same effect is achieved by switching the key to the OFF position or removing the auxiliary power supply to the NA016 relay.
TestThe operational tests with or without command of the associated output relays may be performed.
Browse the main menu by means the or keys until the “Test” message is displayed; press
the key to enter and subsequently select the test by means of the or keys.
Test I> ledTest I>> ledTest I>>> ledTest IE> ledTest IE>> ledTest I> fullTest I>> full
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•••••••
55NA016 - Manual - 06 - 2011SETTING AND COMMISSIONING
Test I>>> fullTest IE> fullTest IE>> full
ExampleTo set the K1 test on the I> element, the following sequence must be operate:
Select the “Test I> full >” menu.
Press the key to enter ; this results in the “execute ?” message with the symbol “C” fl ashing.
Press the key to enter; the test in progress condition is marked by “ok! “ message and blinking of the led ON.[1]
To stop test select the “Test off >” menu, press the key and answer with a further activa-
tion of the key to the “Test off execute? >>” message.
CommunicationInside the Communication menu the setting data of the serial communication ports (rate, stop bit, parity and address) for RS485 Modbus and IEC60870-5-103 may be adjusted.
Browse the main menu by means the or keys until the “Protocol RS485 Modbus >”
message is displayed; press the key to enter; the he modifi cation in progress status is highlighted by the symbol “E” fl ashing in the upper right area of the display.
Select the right menu by means of the or keys “Protocol RS485 Modbus >” or “Protocol RS485 IEC60870-5-103 >”
By means of the or keys adjust the address; the “Address 1” message is displayed and enter the intended value. Similarly for all the parameters:
“Address 1” “Baudrate RS485 9600” “Enable TX delay 2 ms” “Start TX delay 2 ms”
By means of the key and next or go inside the Store menu.
Press the key; this results in the “execute ?” message with the symbol “C” fl ashing.
Answer with key to confi rm settingThe end of the setting sequence is signalled by the “ok!” message.
The Reset h key may be used to abort unsaved changes (prior to use of the Store command); the same effect is achieved by switching the key to the OFF position or removing the auxiliary power supply to the NA016 relay.
ResetInside the Reset menu the clearing of counters (Reset counters) LEDs and relays (Reset alarm) may be operated.
DEFAULT (Option)Available inside the Option menu are the confi guration parameter reset (Default) commands.Set default PARSet default REEIn case of any anomalies detected by the self-test function, where confi guration data has become corrupted, it is possible to restore the factory default settings. In particular, using the command “Set default PAR”, the calibration data is restored (thresholds, times, output relay assignment etc), whilst with the command “Set default REE” all the updated variables (counters, ...etc) and the serial com-munication parameters are automatically reset. Except for extraordinary situations, it is not necessary to use such commands which in any case allow the restoration of the factory set default values following an anomaly. Following use of this command, it is necessary to then proceed with the setting of the desired set-tings and/or the calibration of the voltages just as in the case for first installation.
Data/time setting (Time)To effect a change, (year, month,...) the modifi cation may be confi rmed by using the key. Likewise the Set menu the modifi cation in progress status is highlighted by the symbol “E” fl ashing in the upper right area of the display.
Subsequently, it is possible to alter the parameter by means of the or keys (the “E” symbol continues to fl ash to highlight the Editing status); upon reaching the desired value, it is necessary to
once more use the key. Acceptance of the change is indicated by the disappearance of the fl ashing “E” to be replaced by the symbol “!” Differently from the Set menu the changes are stored and became active immediately without the Store command.
Nota 1 I test sono attivi solo se le funzione selezionata è assegnata ad un relè fi nale
•••
•
•
•
•
•
•
•
•
•
5656 NA016 - Manual - 06 - 2011 SETTING AND COMMISSIONING
7.3 MENU TREE
Self-test None
Self-test latch NoneSelf-test cause None
IL1 0.0000 A/InIL2 0.0000 A/InIL3 0.0000 A/InIE 0.00000 A/IEn
Reading Direct
Inp value 300Inp unit A
IEnp unit AIEnp value 100
Measures
Position UnknownTCS OffIN1 - 52b OffCircuit breaker
F - Month 7
F - Number 1F - Cause aaa
F - IL1 0.0000 InF - IL2 0.0000 InF - IL3 0.0000 InF - IE 0.00000 IEnF - Year 2009
F - Phases aaa
Last fault
Serial 35322Info
Self-test
Read
Reading Direct
Inp value 300Inp unit AIEnp value 100IEnp unit A
Base
K1 Trip I>>-Trip I>>>-Trip IE>K1 logic De-energized
K2 mode No-latched
K2 None
K2 tTR 200 msK3 None
K1 tTR 200 ms
K3 logic De-energizedK3 mode No-latched
K4 NoneK4 logic De-energized
K3 tTR 200 ms
RelaysSet
Cunter ST I> 22
Cunter TR IE>> 22
Cunter ST IE> 22Cunter ST IE>> 22Cunter TR I> 22Cunter TR I>> 22
Cunter TR IE> 22
Cunter ST I>> 22
Counters
K4 tTR 200 ms
K2 logic De-energized
g gK1 mode No-latched
p p p
F - Day 22F - Hour 9 hF - Minute 45 mF - Second 44 sF - Millisecond 567 ms
Cunter TR I>>> 22
Cunter ST I>>> 22
IN2 - 52a OffIN3 - TCS Off
pp
p
Protection trip NoneProtection trip
Code NA016-a
Firmware release 1.00Nominal freq. 50 Hz
57NA016 - Manual - 06 - 2011SETTING AND COMMISSIONING
CB Diagnostic Off74 TCS Off
IE>def 0.030 lEn
tE>RES 50 msIE>>def 0.050 lEntE>def 0.04 s
tE>def 1.00 s
tE>>RES 50 ms
50N / 51N
Circuit breaker
Clear
Store
Set
Test
Reset
g
Records stored 0Last record 0Records state Acquire
InfoOscillography
protocol RS485 ModbusAddress 1Baudrate RS485 9600Enable TX delay 2 msStart TX delay 1 ms
y
p
Test I> led >Test I>> led >Test I>>> led >Test IE> led >Test IE>> led >Test I> full >Test I>> full >Test I>>> full >Test IE> full >Test IE>> full >
Reset counters >Reset alarm >
Option Set default PARSet default REE
Test off >
Set month 7Set day 24Set hour 9 h
y
Set minute 22 mSet second 0 s
Set year 2009y
Communication
Time
I curve IEC/BS BI>inv 1.00 ln
I>>def 7.00 lnt>inv 1.00 s
t>>def 0.03 st>>RES 0 msI>>>def 7.00 lnt>>>def 0.03 st>>>RES 0 ms
50 / 51
5858 NA016 - Manual - 06 - 2011 SETTING AND COMMISSIONING
7.4 MAINTENANCE
The devices do not require any particular maintenance; all circuits use high quality static com-ponents, the subassembly products undergo dynamic checks on their functioning before the fi nal assembling of the complete equipment. The dedicated circuits and the fi rmware for the self-test function continuously check the relay operation; the continuously operating auto-zeroing function dynamically corrects the measuring errors due to offset, heat dependent drifts, aging of components, etc.The microprocessor is equipped with a watch-dog circuit which restores the correct operation of the fi rmware in case of fault.The possibility of reading the value of the signals measured on the display (the relay used as an am-meter) allows one to check both the system parameters and the operation of the protection relays at any time. The relay can be preset as well to show the current values referred to the nominal current of the current transformers, as directly in primary amperes (according to the preset value of CT’s nominal primary current); the same is done for the input voltages.If connected to the central control unit, all data available on the display can be checked and pro-cessed thus performing a continuous check and maintenance.
7.5 REPAIR
No repair of possible faults by the client is foreseen; if following to any irregularity of operation, the above tests confi rm the presence of a fault, it will be necessary to send the relay to the factory for the repair and the consequent settings and checks.
7.6 PACKAGING
The devices must be stored within the required temperature limits; the relative humidity should not cause condensation or formation of frost.It is recommended that the devices are stored in their packaging; in the case of long storage, espe-cially in extreme climatic conditions, it is recommended that the device is supplied with power for some hours before the commissioning, in order to bring the circuits to the rating conditions and to stabilize the operation of the components.
59NA016 - Manual - 06 - 2011APPENDIX
8 A P P E N D I X8 A P P E N D I X
8.1 APPENDIX A1 - Inverse time IEC curves
Mathematical formulaThe mathematical formula, according the IEC 60255-3/BS142 standards is:[1]
Where:t = operate time (in seconds)tI>inv = setting time multiplier (in seconds)I = input currentI>inv = threshold setting
K coeffi cient:K = 0.14 for IEC-A curve (Normal inverse)K = 13.5 for IEC-B curve (Very inverse)K = 80 for IEC-C curve (Extremely inverse)
α curve shape constant:α = 0.02 for IEC-A curve (Normal inverse)α = 1 for IEC-B curve (Very inverse)α = 2 for IEC-C curve (Extremely inverse)
For all inverse time characteristics, following data applies:Asymptotic reference value (minimum pickup value): 1.1 I>invMinimum operate time: 0.1 sRange where the equation is valid:[2][3] 1.1 ≤ I /I>inv ≤ 20 If I> pickup ≥ 2.5 In, the upper limit is 50 In
Note 1 Symbols are concerning the overcurrent element. The comprehensive overview of the inverse time characteristics concerning the 50/51 and 50N/51N elements is dealt within the PROTECTIVE ELEMENTS section
Note 2 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
Nota 3 With setting more than 2.5 In for the 50/51 elements and 0.5 IEn for the 50N/51N elements, the upper limit of the measuring range is limited to 50 In and 10 IEn respectively.
••••
•••
•••
••••
t = t>inv · [(I/I>inv)α-1]
Kt = t>inv · [(I/I>inv)α-1]
K
6060 NA016 - Manual - 06 - 2011 APPENDIX
Phase overcurrent 50/51 - Standard inverse time curve (IEC 60255-3/BS142 type A)
F_51-IECA-Char.ai
1.12 3 4 5 6 7 8 9 10 20 I /I>inv0.01
0.1
1
10
100
1000
10000t [s]
t>inv = 10 s
t>inv = 60 s
t>inv = 5 s
t>inv = 1 s
t>inv = 0.5 s
t>inv = 0.2 s
t>inv = 0.1 s
t>inv = 0.02 s
t = t>inv · [(I/I>inv)0.02-1]
0.14
Note: match of operating and setting time takes place when I/I>inv = 700
61NA016 - Manual - 06 - 2011APPENDIX
Phase overcurrent 50/51 - Very inverse time curve (IEC 60255-3/BS142 type B)
F_51-IECB-Char.ai
1.12 3 4 5 6 7 8 9 10 20 I /I>inv0.01
0.1
1
10
100
1000
10000t [s]
t>inv = 10 s
t>inv = 60 s
t>inv = 5 s
t>inv = 1 s
t>inv = 0.5 s
t>inv = 0.2 s
t>inv = 0.02 s
t>inv = 0.1 s
t = t>inv · [(I/I>inv) -1]
13.5
Note: match of operating and setting time takes place when I/I>inv = 14.5
6262 NA016 - Manual - 06 - 2011 APPENDIX
Phase overcurrent 50/51 - Extremely inverse time curve (IEC 60255-3/BS142 type C)
F_51-IECC-Char.ai
1.12 3 4 5 6 7 8 9 10 20
I /I >inv0.01
0.1
1
10
100
1000
10000
100000t [s]
t>inv = 10 s
t>inv = 60 s
t>inv = 5 s
t>inv = 1 s
t>inv = 0.5 st>inv = 0.2 st>inv = 0.02 s t>inv = 0.1 s
t = t>inv · [(I/I>inv)2-1]
80
Note: match of operating and setting time takes place when I/I>inv = 9
63NA016 - Manual - 06 - 2011APPENDIX
8.2 APPENDIX B1 - I/O Diagram
NA016-I-O.aiInput-output circuits
Traditional CT input circuits Low powerCT input circuits (LPCTs)
NA016
C1IL1
IL2
IL3
IE
CURR
ENT
INPU
TS
C2C3
C4C5
C6
C7
C8
RS23
2
FRONT PANEL
A13IN1
IN2
IN3
A14
A15
A16
A17
A18
OUTP
UT R
ELAY
S A4A6A5
K2
A2A1A3
K1
A11A12A10
K4
A9A8A7
K3
UAUXA19 ≅
A20
A22A21
B- E1
RS48
5
1
2
3
120Ω
A+
CIrcuit Breaker Monitoring
Trip CircuitSupervision (TCS)
NA016
IE
CURR
ENT
INPU
TS
C7
C8
RS23
2
FRONT PANEL
A13IN1
IN2
IN3
A14
A15
A16
A17
A18
OUTP
UT R
ELAY
S A9A8A7
K2
A5A4A6
K1
A11A12A10
K4
A3A2A1
K3
UAUXA19 ≅
A20
A22A21
B- E1
RS48
5
1
2
3
120Ω
A+
CIrcuit Breaker Monitoring
Trip CircuitSupervision (TCS)
L1
L2
L3
6464 NA016 - Manual - 06 - 2011 APPENDIX
8.3 APPENDIX B2 - Interfaces
Interfaces.ai
NA016
RS23
2
FRONT PANEL
A22A21
B- E1
RS48
5
1
2
3
120Ω
A+
65NA016 - Manual - 06 - 2011APPENDIX
8.4 APPENDIX B3 - Connection diagramsNote: Some typical connection diagram are shown. All diagram must be considered just as example; they cannot be comprehensive for real applications. For all diagrams the output contacts are shown in de-energized state for standard reference.
NA016-SCH.ai
CB position
NA016
C1IL1
IL2
IL3
P1S1S2
P2C2C3
C4C5
C6
C7
C8
A13IN1
IN2
IN3
A14
A15
A16
A17
A18
DG
50/51
IE
P1S1S2
P2
50N/51N
CIrcuit Breaker Monitoring
Trip CircuitSupervision (TCS)
Three phase CTs and residual current from core balanced CT
6666 NA016 - Manual - 06 - 2011 APPENDIX
NA016-SCH2.ai
C2
C1
C3
C4C5
C6
P1S1S2
P2
IL1
IL2
IL3
CB position
NA016
A13IN1
IN2
IN3
A14
A15
A16
A17
A18
DG
50/51
IE
P1S1S2
P2
C7
C8 50N/51N
Two phase CTs and residual current from core balanced CT
CIrcuit Breaker Monitoring
Trip CircuitSupervision (TCS)
67NA016 - Manual - 06 - 2011APPENDIX
Connection diagram with Data Logger
NA016
C1IL1
IL2
IL3
IE
CURR
ENT
INPU
TS
P1S1S2
P2
P1S1S2
P2
C2C3
C4C5
C6
C7
C8
RS23
2
FRONT PANEL
A13IN1
IN2
IN3
A14
A15
A16
A17
A18
OUTP
UT R
ELAY
S A4A6A5
K2
A2A1A3
K1
A11A12A10
K4
A9A8A7
K3
UAUXA19 ≅
A20
A22A21
B- E1
RS48
5
1
2
3
120Ω
A+
DG
TRIP
52a 52b 52a 52b
-UAUX
-UAUX
+UAUX
+UAUX
+UAUX
R
CIrcuit Breaker Monitoring
Trip CircuitSupervision (TCS)
6868 NA016 - Manual - 06 - 2011 APPENDIX
8.5 APPENDIX C - Dimensions
Traditional CT inputs Low power CT inputs
Traditional CT inputs Low power CT inputs
LEDs 3, 4 and 5 enabledfor Logger versions only
75 3075 30
10717
7
102.5 ±0.3
70
161
154
SIDE VIEW CUTOUT
FRONT VIEW
ON 41 32 5
TRIP
START
REAR VIEW
IDENTIFICATION LABEL LEDs
N.4 holes ø 3.5
101
171
149
101
171
149
F1
D1
RX
TX
F2F3F4F5
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
B1B2B3B4B5B6B7B8
C1 C2
C4C3
C5 C6
C7 C8 C7 C8
E1
A1A2
A3A4A5
A6A7A8
A9A10A11
A12A13A14
A15A16
A17A18
A19A20
A21A22
E1
31
2
31
2
(100+200)300A
EX. In=
LPCT
50
200400
100
800
Setting
L3
L2
L1
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
31
2
31
2
CTs standard inputs - No LoggerCTs standard inputs - Logger
LPCT inputs - Logger LPCT inputs - No Logger
ON: Power ON and diagnostic OK
NA016#xx11
In Rated 50...500A/Extended 50...1250A
50-5150N-51NCB OPENCB CLOSEDTCS
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx00
In 5A 1A
50-5150N-51N
5A
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx01
In Rated 50...500A/Extended 50...1250A
50-5150N-51N
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
NA016#xx10
In 5A 1A
50-5150N-51NCB OPENCB CLOSEDTCS
5A
UAUX 24-230 Vac/dcIEn 5A 1A 5A
12345
69NA016 - Manual - 06 - 2011APPENDIX
8.6 APPENDIX D - Revisions history
DSPFirmwareRelease
SWRelease
Documentation Communication Date Description
1.001.00
1.00
1.00
--
-
-
NA016-Manual-08-2009NA016-Manual-08-2010
NA016-Manual-06-2011
NA016-Manual-06-2011
ThySetter 3.5.3ThySetter 3.5.8
ThySetter 3.6.2
ThySetter 3.6.4
--
-
16-06-2012
First editionNotes LED 3, 4, 5 pag. 25, , removed RESET signal in the diagrams of functions and 50N/51N 50/51, replaced photo, improved oscillographic description (Ch. 4 and 5), updated dimensions design, added references to versions with and without loggersMore details for In settings for LPCT versions (Cap 6), typographic detailsUpdated technical data of replaced K4 relay (from signalling relay to command relay)
Headquarters: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - Fax +39 02 574 037 63Factory: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 48 - Tel. +39 049 894 770 1 ra - Fax +39 049 870 139 0
www.thytronic.it www.thytronic.com [email protected]
8.7 APPENDIX E - EC Declaration of conformity
Manufacturer: THYTRONIC S.p.A.
Address: Piazza Mistral 7 - 20139 MILANO
The undersigned manufacturer herewith declares that the product
Protection relay - type NA016
is in conformity with the previsions of the following EC directives (including all applicable amendments) when installed in accordance with the installation instructions:
Reference n° title
2006/95/EC2004/108/EC
Low Voltage DirectiveEMC Directive
Reference of standards and/or technical specifi cations applied for this declaration of conformity or parts thereof:
- harmonized standards:
nr issue title
EN 61010-1
EN 50263
EN 61000-6-4 (EN 50081-2)
EN 61000-6-2 (EN 50082-2)
11.2001
08.2000
11.2007
12.2005
Safety requirements for electrical equipment for measurement, control and laboratory use
Electromagnetic compatibility (EMC)Product standard for measuring relays and protection equipments
Electromagnetic compatibility (EMC)Emission standard for industrial environments
Electromagnetic compatibility (EMC)Immunity standard for industrial environments
- other standards and/or technical specifi cations:
nr issue title
CEI 0-16
EN 61810-1
EN 60255-6 (CEI 95-1)
IEC 60255
07.2008
02.2004
05.1998
Regola tecnica di riferimento per la connessione di Utenti attivi e passivi alle reti AT e MT delle imprese distributrici di energia elettrica
Electromechanical elementary relaysGeneral and safety requirements
Electrical relays - Part 6: General requirements for measuring relays and protection equipment
Electrical relays
Year of CE marking: 2009
Signature ............................................. Name FIORE Ing. GIOACCHINO Title Managing director Date 07-2009