AFFIX REP SEAL HERE www.energycodes.gov/comcheck COMMERCIAL COMPLIANCE FORM - Chicago Energy Conservation Code B. Prescriptive Path (check one) A. Comcheck C. Total Building Performance RECOMMENDED METHOD Download Com check free at Print and attach Com check compliance certificate. ( required) Permit Application Number: _______________________________________________________________________ Project Address: _________________________________________________________________________________ Instructions: Select compliance method A, B, C, D or E by marking the appropriate check box, and then select all required sub -boxes as applicable. Sign and complete contact information and attached back -up as required. Report, Check List, Certificate, Project Details, Permit Date 504: Service Water Heating (504 is in addition to Comcheck) 503: Mechanical Systems 503.3: Simple HVAC Systems 503: Mechanical Systems 503.4: Complex HVAC Systems Article 5 502, 504, and 505 Article 5 502, 504, and 505 *Article 5 Comcheck Article 5 506, Total Building Performance OR ------------------------------------------------ -------------------------------------------------- OR ------------------------------------------------ -------------------------------------------------- OR ------------------------------------------------ -------------------------------------------------- OR D. ASHRAE/IESNA 90.1-2004 E. ASHRAE/IESNA 90.1-2004 (Energy Cost Budget) OR OR OR OR ------------------------------------------------ -------------------------------------------------- ------------------------------------------------------------------------------------------------------- (check one option for section 5, 6 and 9) I certify that I am a Registered Energy Professional (REP). I also certify that to the best of my knowledge and belief the plans for the project listed above fully comply with the requirements of Chapter 18-13, Energy Conservation, of the Municipal Code of Chicago as effective April 22, 2009, including all relevant provisions of Article 1. The method of compliance used for this property is clearly marked on the flowchart above. Signed: Address: Telephone: Email: Print Name: Date: Illinois License #: 5: Envelope (5.1, 5.4, 5.7, 5.8) 6: HVAC (6.1, 6.7, 6.8) 9: Lighting (9.1, 9.4) 5.5 5.6 6.3 6.4 9.5 9.6 Ashrae/IESNA 90.1-2004 Ashrae/IESNA 90.1-2004 11: Energy Cost Budget 7: Service Water Heating (7.1, 7.4, 7.5, 7.7, 7.8) 8: Power (8.1, 8.4, 8.7) 10: Other Equipment (10.1, 10.4, 10.8) CERTIFICATE OF COMPLIANCE Reg. No. Date These drawings and plans comply with the requirements in the building provisions of the City of Chicago Building Code. I hereby certify that these drawings and plans were prepared by me or under my direct supervision, and that I am a duly Registered Engineer under the laws of the State of Illinois. ANWAR SULTAN 09/06/18 312-279-1875 [email protected] 36 S. WABASH AVE, CHICAGO, IL 430 EAST 51ST PLACE, CHICAGO, IL 60615 SYMBOLS SUPPLY DUCT RISE RETURN DUCT RISE EXHAUST DUCT RISE OPPOSED BLADE VOLUME DAMPERS OR FLEXIBLE DUCT SINGLE LINE DUCT RISE OR DROP ELBOW WITH TURNING VANES SINGLE LINE DUCTWORK VOLUME DAMPER BACKDRAFT DAMPER SUPPLY DUCT DROP RETURN DUCT DROP EXHAUST DUCT DROP EXISTING SINGLE LINE DUCT CAPPED DUCTWORK CAPPED PIPING OR SINGLE DUCTWORK OR EXISTING ITEM TO BE REMOVED DUCT OFF - SET DN (IN DIRECTION OF FLOW) DUCT OFF - SET UP (IN DIRECTION OF FLOW) RECTANGULAR DUCT DIMENSIONS (SIZE IN INCHES, FIRST DIMENSION IS SHOWN) ROUND DUCT DIMENSIONS (DIAMETER) OVAL DUCT DIMENSIONS (SIZE IN INCHES, FIRST DIMENSION IS SHOWN) MOTORIZED DAMPER FIRE, SMOKE/FIRE, OR SMOKE DAMPER FD, FS, OR SD NEW DUCT EXISTING DUCT DEMOLISHED DUCT BDD 24x12 OV 24x12 24"Ø DN UP TP DIRECTION OF FLOW PIPE ANCHOR PIPE GUIDE FLEXIBLE CONNECTION TRAP PIPING FLOW METER T TEMPERATURE SENSOR (IN DUCT OR PIPE) RECTANGULAR WYE DUCT FITTING POINT OF CONNECTION (NEW TO EXISTING) OR FM POINT OF DISCONNECTION FROM EXISTING T VARIABLE SPEED DRIVE T R S ELECTRICAL CONNECTION (BY DIVISION 26) FREEZESTAT FLOW SWITCH RELAY HUMIDITY SENSOR SWITCH SENSING ELEMENT - AIR STREAM SENSING ELEMENT - LIQUID SEPARABLE WELL ANALOG OUTPUT DIGITAL OUTPUT DIGITAL INPUT ELECTRICAL CONNECTION (BY DIVISION 26) ANALOG OUTPUT, PNEUMATIC ELECTRIC - PNEUMATIC SWITCH PNEUMATIC - ELECTRIC SWITCH SMOKE ANALOG INPUT, PRESSURE ANALOG INPUT, TEMPERATURE FIRESTAT SMOKE DETECTOR THERMOSTAT WITH LOCKING COVER PUMP CARBON DIOXIDE SENSOR P PRESSURE GAUGE OR PUSH BUTTON PB VSD OCCUPANCY SENSOR ANALOG INPUT TEMPERATURE SENSOR OXYGEN SENSOR ANALOG INPUT, FLOW 26 AI AIF AIP AIT AO AOP CO ² DI DO E P E FIRE FS F H OS O ² E P 1 M0101 SECTION INDICATOR TOP INDICATES SECTION NUMBER BOTTOM INDICATES SHEET NUMBER ROOM PRESSURIZATION MONITOR DUCT SMOKE DETECTOR CURRENT SENSOR SX CFM SUPPLY AIR DEVICE - (REFER TO SCHEDULE FOR SIZE) FIRST NO. TYPE, SECOND NO. CFM (REFER TO SPECIFICATION FOR AIR DEVICE TYPE) LINEAR DIFFUSER SUPPLY/ RETURN/EXHAUST SIDEWALL GRILLE - FIRST NO. CFM, SECOND NO. TYPE BOTTOM NO. WIDTH BY HEIGHT OF GRILLE (REFER TO SPECIFICATION FOR AIR DEVICE TYPE) RETURN AIR DEVICE - (REFER TO SCHEDULE FOR SIZE) FIRST NO. CFM, SECOND NO. TYPE (REFER TO SPECIFICATION FOR AIR DEVICE TYPE) EXHAUST AIR DEVICE - (REFER TO SCHEDULE FOR SIZE) FIRST NO. CFM, SECOND NO. TYPE (REFER TO SPECIFICATION FOR AIR DEVICE TYPE) AIR FLOW MEASURING STATION OFF ON AUTO STARTER NEW EQUIPMENT EXISTING EQUIPMENT CALLOUT INDICATOR TOP INDICATES NUMBER ON THE SHEET BOTTOM INDICATES SHEET NUMBER FM 1 M0101 CS D EXISTING EQUIPMENT TYPE EQUIPMENT TYPE TYPE NO. ABBREVIATIONS DEMOLITION NOTES GENERAL NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR - COOLED CONDENSING UNIT ACH AIR CHANGES PER HOUR ACU AIR CURTAIN ACW AFTER COOLER WATER AD ACCESS DOOR AF AIR FOIL FAN AFF ABOVE FINISHED FLOOR AFMS AIR FLOW MEASURING STATION AHU AIR HANDLING UNIT ALT ALTERNATE ALUM ALUMINUM AMP AMPERE AP ACCESS PANEL APD AIR PRESSURE DROP APPROX APPROXIMATE ARCH ARCHITECT/ARCHITECTURAL AS AIR SEPARATOR ATD AIR TRANSFER DUCT AUTO AUTOMATIC AVG AVERAGE AWT AVERAGE WATER TEMPERATURE AXF AXIAL FAN BB BASEBOARD RADIATION BDD BACK DRAFT DAMPER BF BOILER FEED WATER BG BOTTOM GRILLE (3" - 12" ABOVE FLOOR) BHP BRAKE HORSEPOWER BLDG BUILDING BMS BUILDING MANAGEMENT SYSTEM BOD BOTTOM OF DUCT BR BOTTOM REGISTER (3" - 12" ABOVE FLOOR) BSMT BASEMENT BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNIT PER HOUR CA COMPRESSED AIR CAP CAPACITY CC COOLING COIL CCW COUNTER CLOCKWISE CD CONDENSATE DRAIN CENTRIF CENTRIFUGAL CF CUBIC FEET CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE CH CABINET HEATER CHR CHILLER CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CI CAST IRON CL CENTER LINE CLG COOLING CO CLEAN OUT CO2 CARBON DIOXIDE COMP COMPRESSOR CONC CONCRETE CONN CONNECTION CONST CONSTRUCTION CONT CONTINUOUS, CONTINUATION CONTR CONTRACTOR CONV CONVECTOR CP CONTROL PANEL CT COOLING TOWER CU CONDENSING/ER UNIT CU FT CUBIC FEET CV CONSTANT VOLUME CV CONSTANT VOLUME CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY D DRAIN OR DRYER DB DECIBEL OR DRY BULB TEMPERATURE DDC DIRECT DIGITAL CONTROL DEG.F DEGREE FAHRENHEIT DEMO DEMOLISH DG DOOR GRILLE DIA DIAMETER DIAG DIAGONAL DIFF DIFFUSER DIM DIMENSION DISCH DISCHARGE DN DOWN DP DIFFERENTIAL PRESSURE DPDT DOUBLE POLE, DOUBLE THROW DPST DOUBLE POLE, SINGLE THROW DTR DUAL TEMPERATURE RETURN DTS DUAL TEMPERATURE SUPPLY DWDI DOUBLE WIDTH, DOUBLE INLET DWG DRAWING DX DIRECT EXPANSION E/P ELECTRIC - PNEUMATIC EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EBB ELECTRIC BASEBOARD HEATER EC EXPANSION COMPENSATOR/JOINT ECWR EQUIPMENT COOLING WATER RETURN ECWS EQUIPMENT COOLING WATER SUPPLY EDB ENTERING DRY BULB TEMPERATURE EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN EFF EFFICIENCY EHC ELECTRIC HEATING COIL EL/ELEV ELEVATION ELEC ELECTRIC/ELECTRICAL ELEM ELEMENT ELEV ELEVATOR EMD END OF MAIN DRIP (STEAM) EMER EMERGENCY ENG ENGINEER ENT ENTERING ERP ELECTRIC RADIANT PANEL ESP EXTERNAL STATIC PRESSURE EST ESTIMATE ET EXPANSION TANK ETO ETHYLENE OXIDE EUH ELECTRIC UNIT HEATER EV EXHAUST AIR VALVE EVAP EVAPORATOR EVF FUME HOOD EXHAUST AIR VALVE EVL LAB EXHAUST AIR VALVE EWB ENTERING WET BULB TEMPERATURE EWT ENTERING WATER TEMPERATURE EXH EXHAUST EX EXISTING (E) OR ETR EXISTING TO REMAIN EXIST EXISTING EXT EXTERNAL F FAHRENHEIT F&T FLOAT & THERMOSTATIC STEAM TRAP F.D. FLOOR DRAIN FD FIRE DAMPER FA FREE AREA FC FORWARD CURVED FCU FAN COIL UNIT FD FIRE DAMPER FF FINAL FILTER FH FUME HOOD FLA FULL LOAD AMPERES FLEX FLEXIBLE FLR FLOOR FLT FLASH TANK FM FLOW METER FOG FUEL OIL GAUGE FOR FUEL OIL RETURN FOS FUEL OIL SUPPLY FOV FUEL OIL VENT FP FIRE PROTECTION FPB FAN POWERED TERMINAL UNIT FPM FEET PER MINUTE FPS FEET PER SECOND FR FINNED RADIATION FSD FIRE SMOKE DAMPER FSTAT FREEZESTAT FT FEET FV FACE VELOCITY G NATURAL GAS GA GAUGE GAL GALLON GCWR GEOTHERMAL CONDENSER WATER RETURN GCWS GEOTHERMAL CONDENSER WATER SUPPLY GD GRAVITY DAMPER GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GR GLYCOL RETURN GRL GRILLE GRV GRAVITY RELIEF VENT GS GLYCOL SUPPLY GV GRAVITY VENTILATOR OR NATURAL GAS VENT HTG HEATING HTWR HIGH TEMPERATURE WATER RETURN HTWS HIGH TEMPERATURE WATER SUPPLY HUM HUMIDIFIER HVAC HEAT, VENTILATION, & AIR CONDITIONING HVU HEATING & VENTILATING UNIT HWR HOT WATER RETURN HWS HOT WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ ID INSIDE DIAMETER IN OR " INCHES IN W.C. INCHES WATER COLUMN IN W.G. INCHES WATER GAUGE INSUL INSULATION INT INTERNAL JW JACKET WATER KW KILOWATT KWH KILOWATT HOUR LAT LEAVING AIR TEMPERATURE LBS POUNDS LDB LEAVING DRY BULB TEMPERATURE LF LINEAR FEET LPG LIQUID PETROLEUM GAS LPR LOW PRESSURE CONDENSATE RETURN LPS LOW PRESSURE STEAM LRA LOCKED ROTOR AMPERES LVG LEAVING LVR LOUVER LWB LEAVING WET BULB TEMPERATURE LWT LEAVING WATER TEMPERATURE M MOTOR OPERATOR MAINT MAINTENANCE MAU MAKE - UP AIR UNIT MAX MAXIMUM MBH THOUSAND BTU PER HOUR MCC MOTOR CONTROL CENTER MECH MECHANICAL MERV MINIMUM EFFICIENCY REPORTING VALUE MEZZ MEZZANINE MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MPR MEDIUM PRESSURE CONDENSATE RETURN MPS MEDIUM PRESSURE STEAM MTD MOUNTED N.C. NORMALLY CLOSED N.O. NORMALLY OPEN NC NOISE CRITERIA NIC NOT IN CONTRACT NO. OR # NUMBER NR NOT REQUIRED NTS NOT TO SCALE NV NATURAL VENTILATION OA OUTSIDE AIR OAI OUTSIDE AIR INTAKE OBD OPPOSED BLADE DAMPER OED OPEN END DUCT OFCI OWNER FURNISHED/CONTRACTOR INSTALLED OFOI OWNER FURNISHED/OWNER INSTALLED OH OVERHEAD OPNG OPENING Δ P/DP DIFFERENTIAL PRESSURE P PUMP P/E PNEUMATIC - ELECTRIC SWITCH PA PASCAL PCD PUMPED CONDENSATE DISCHARGE/RETURN PCF POUNDS PER CUBIC FOOT PCWR PROCESSED CHILLED WATER RETURN PCWS PROCESSED CHILLED WATER SUPPLY PD PRESSURE DROP PF PROPELLER FAN PG PRESSURE GAUGE PH PHASE PLBG PLUMBING PRESS PRESSURE PROP PROPELLER PRV PRESSURE REDUCING VALVE PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PSIA POUNDS PER SQUARE IN ABSOLUTE PSIG POUNDS PER SQUARE IN GAUGE QTY QUANTITY R RETURN RA RETURN AIR RAD RADIATION RAF RETURN AIR FAN REBAL REBALANCE REG REGISTER REV REVISED RH RELATIVE HUMIDITY RHC REHEAT COIL RHG REFRIGERANT HOT GAS RL REFRIGERANT LIQUID RM ROOM RO RELIEF OPENING RP RADIANT PANEL RPM REVOLUTIONS PER MINUTE RS REFRIGERANT SUCTION RTU ROOF TOP UNIT RV REFRIGERANT VENT OR RELIEF VALVE (VENT) RV RETURN AIR VALVE S/W SUMMER - WINTER SA SUPPLY AIR OR SOUND ATTENUATOR SCR SILICON CONTROLLED RECTIFIER SD SMOKE DETECTOR SD SMOKE DAMPER SENS SENSIBLE LOAD SF SMOKE - FIRE DAMPER SHT SHEET SM SMOKE DAMPER SOL SOLENOID SP STATIC PRESSURE SQ SQUARE SQ. FT. SQUARE FEET SS STAINLESS STEEL STD STANDARD STL STEEL STM STEAM STRUC STRUCTURE/STRUCTURAL SV SUPPLY AIR VALVE SWSI SINGLE WIDTH, SINGLE INLET TC TEMPERATURE CONTROL TD TRANSFER DUCT TEMP TEMPERATURE TL TOTAL LOAD TO TRANSFER OPENING TSP TOTAL STATIC PRESSURE TSTAT THERMOSTAT TU TERMINAL UNIT TYP TYPICAL UGRD UNDERGROUND UH UNIT HEATER (HYDRONIC OR STEAM) UNO UNLESS NOTED OTHERWISE UPS UNINTERRUPTIBLE POWER SUPPLY UV UNIT VENTILATOR V VOLT OR VENT VAV VARIABLE AIR VOLUME VD VOLUME DAMPER VEL VELOCITY VERT VERTICAL VI VIBRATION ISOLATION VIF VERIFY IN FIELD VOL VOLUME VR VACUUM RETURN VRV VARIABLE REFRIGERANT VOLUME VSD VARIABLE SPEED DRIVE VTR VENT THROUGH ROOF (X) EXISTING TO BE DEMOLISHED W WATT W.G. WATER GAUGE W/ WITH W/O WITHOUT WB WET BULB TEMPERATURE WC WATER COLUMN WMS WIRE MESH SCREEN WPD WATER PRESSURE DROP WT WEIGHT WTR WATER 1. ALL DEMOLITION WORK SHALL BE PERFORMED WITH “DUE CARE AND DILIGENCE” SO AS TO PREVENT THE UNNECESSARY DESTRUCTION AND/OR DAMAGE TO SYSTEMS THAT SHALL REMAIN IN OPERATION AT THE CONCLUSION OF THIS WORK. DETERMINE THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DEVICES AND WIRING BEFORE COMMENCING WORK. 2. LOCATE AND PRESERVE ALL PORTIONS OF THE EXISTING HVAC SYSTEMS WHICH SHALL REMAIN. 3. CONTROLS DEVICES AND WIRING ARE NOT SHOWN ON THE DEMOLITION PLAN AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. 4. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING HVAC DEVICES, EQUIPMENT, AND WIRING BEFORE COMMENCING WORK, THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES THAT MIGHT OCCUR BECAUSE OF THE CONTRACTORS FAILURE TO ACCURATELY DISCOVER, LOCATE, AND PROTECT ANY AND ALL PORTIONS OF THE EXISTING HVAC SYSTEM. 5. EXISTING DUCTWORK AND CONTROLS WIRING MAY BE RE-USED WHERE THEY ARE OF THE TYPE SPECIFIED, MEET THE REQUIREMENTS FOR THE NEW WORK AS DEFINED BY THE CONTRACT DOCUMENTS, AND REMAIN IN GOOD CONDITION. 6. REMOVE AND RE-INSTALL (OR PROTECT IN PLACE) ALL EXISTING EQUIPMENT AND DEVICES TO REMAIN ON OR IN WALLS, CEILINGS AND FLOORS WHICH SHALL BE EXPOSED TO DEMOLITION AND CONSTRUCTION ACTIVITIES AND WHICH MAY BE DAMAGED BY DUST, DEBRIS, ETC. 7. WHERE EXISTING EQUIPMENT AND DEVICES SHALL BE REMOVED, THE CONTRACTOR SHALL REMOVE ALL THE ASSOCIATED DUCTWORK, PIPING, AND CONTROLS THAT SHALL NOT REMAIN IN OPERATION BACK TO THEIR RESPECTIVE SOURCE OR TO THE POINT ON A SHARED SYSTEM FROM WHERE THE EQUIPMENT OR DEVICE IS SERVED. 8. RELOCATE AS NECESSARY ALL EXISTING DUCTWORK, PIPING, AND CONTROLS FOUND PASSING THROUGH THE AREA OF CONSTRUCTION, AND WHICH ARE PRESENTLY IN USE OTHER PORTIONS OF THE BUILDING UNAFFECTED BY THIS PROJECT PHASE, TO MAINTAIN THE CONTINUITY OF SERVICES AND GROUNDING, AND TO CONCEAL THEM ABOVE NEW CEILINGS. 9. ALL EXISTING DAMAGED DUCTWORK, GRILLES, AND DEVICES WITHIN THE AREA OF CONSTRUCTION AND SHOWN TO REMAIN IN OPERATION SHALL BE REPLACED WITH NEW MATERIALS CONFORMING TO THESE CONTRACT DOCUMENTS AT NO COST TO OWNER. 10. ALL EQUIPMENT, DEVICES, AND MATERIALS REMOVED DURING DEMOLITION WORK AND NOT INDICATED TO BE REUSED OR TURNED OVER TO THE OWNER SHALL BECOME THE RESPONSIBILITY OF THE CONTRACTOR FOR DISPOSAL. 11. THE CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING NECESSARY TO REPAIR ANY DAMAGE CAUSED BY CONSTRUCTION ACTIVITIES PERFORMED BY THE CONTRACTOR. THIS WORK INCLUDES AREAS OUTSIDE ANY LIMITS OF CONSTRUCTION LINES SHOWN ON THE DRAWINGS. H HUMIDISTAT OR HUMIDIFIER HC HEATING COIL HEPA HIGH EFFICIENCY PARTICULATE AIR FILTER HG HOT GAS HL HIGH LIMIT HORIZ HORIZONTAL HP HORSEPOWER OR HEAT PUMP HPR HIGH PRESSURE CONDENSATE RETURN HPS HIGH PRESSURE STEAM HR HOUR HRC HEAT RECOVERY COIL HT HEIGHT HTG HEATING 1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALL CEILING AIR DEVICE LOCATIONS. 2. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR LOCATION OF WALL MOUNTED MECHANICAL ITEMS. 3. LOCATE ALL DUCT BALANCING DAMPERS ABOVE ACCESSIBLE CEILINGS, OR PROVIDE ACCESS DOORS. MINIMUM ACCESS DOOR SIZE SHALL BE 18x18 UNLESS OTHERWISE APPROVED BY ENGINEER. 4. PROVIDE VOLUME DAMPERS AT ALL SUPPLY, RETURN AND EXHAUST DUCT BRANCH TAKE-OFFS. SEE DUCT CONSTRUCTION DETAILS. 5. COORDINATE SCHEDULE FOR HOOKUPS TO EXISTING SYSTEM AND REMOVAL OR RELOCATION OF EQUIPMENT WITH THE OWNER. PERFORM THIS WORK AT SUCH TIMES TO ENSURE THAT PERIODS OF SHUTDOWN WILL BE ACCEPTABLE TO THE OWNER. 6. VERIFY EXACT LOCATION OF CONNECTION POINTS (NEW TO EXISTING) IN FIELD PRIOR TO CONSTRUCTION. 7. COORDINATE INSTALLATION OF NEW DUCTWORK AND PIPING WITH EXISTING BUILDING STRUCTURE, DUCTWORK, PIPING, ELECTRICAL CONDUIT, LIGHTING, ETC. 8. TAKE DOWN AND REINSTALL EXISTING CEILINGS IN ALL AREAS WHERE MECHANICAL WORK IS INDICATED AND EXISTING CEILINGS REMAIN. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN DRAWINGS FOR LOCATIONS WHERE EXISTING CEILINGS REMAIN. REPLACE CEILING TILES DAMAGED DURING WORK. 9. PATCH ALL WALLS, FLOORS, CEILINGS, AND ROOFS TO MATCH EXISTING IN ALL CASES WHERE EXISTING WALLS, FLOORS, CEILINGS AND ROOFS REMAIN AND HVAC DEMOLITION IS INDICATED. # - # (E)XXX TYPE NO. RX CFM EX CFM SX CFM SX CFM H C HUMIDISTAT CO SENSOR Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing. This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled. Not published - All rights reserved. No. Date Issue Sheet Name Drawing No. Project Number Drawn Checked Proj. Arch./Eng. Project Name Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part. Department of Capital Planning & Policy Bureau of Asset Management AS SS AJG SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES M0001 Provident Hospital - Renal Dialysis Center 430 East 51st Place Chicago, Illinois 60615 15849 1. MINIMUM OA AIRFLOW ACHIEVED BY BASE-BUILDING VENTILATION SYSTEM. MINIMUM OVERALL AIRFLOW RATE ACHIEVED VIA USE OF BASE BUILDING VENTILATION SYSTEM. NOTES: TOTALS 5,050 2,565 890 2,910 6,720 6,575 117A W.C. TOILET ROOM 50 0 0 100 50 100 (E)AHU-1 EF-4 116A NURSE TREATMENT ROOM 169 105 35 55 125 125 (E)AHU-1 (E)AHU-1 113B STAFF TOILET TOILET ROOM 50 0 0 100 50 100 (E)AHU-1 (E)TE-4 113A CHANGING ROOM LOCKER ROOM 20 50 20 50 50 50 (E)AHU-1 (E)AHU-1 100D CORRIDOR CORRIDOR 425 0 0 0 325 100 (E)AHU-1 (E)AHU-1 100C CORRIDOR CORRIDOR 224 0 0 0 100 0 (E)AHU-1 (E)AHU-1 125 WATER TREATMENT NA 317 0 0 0 350 350 (E)AHU-1 EF-2 124 MECH NA 102 0 0 0 200 200 (E)AHU-1 (E)EF-1 123 ELEC NA 118 0 0 0 75 0 (E)AHU-1 (E)AHU-1 122 STORAGE STORAGE INACTIVE 114 0 0 0 50 50 (E)AHU-1 (E)AHU-1 121 LAB LABORATORY 63 80 30 80 100 100 (E)AHU-1 (E)AHU-1 120 EQUIP REPAIR STORAGE ACTIVE 147 75 25 75 150 150 (E)AHU-1 (E)AHU-1 119 CLEAN SUPPLY STORAGE ACTIVE 100 50 20 50 100 75 (E)AHU-1 (E)AHU-1 118 SOILED STORAGE LABORATORY 100 120 40 120 120 150 (E)AHU-1 EF-3 117 PRIVATE PAT./ISOLATION PATIENT ROOM 132 50 20 50 250 275 (E)AHU-1 EF-4 116 TREATMENT AREA TREATMENT ROOM 862 520 175 260 900 800 (E)AHU-1 (E)AHU-1 115 MED PREP TREATMENT ROOM 92 60 20 50 150 150 (E)AHU-1 (E)AHU-1 114 PAT. TOILET TOILET ROOM 40 0 0 80 0 100 (E)AHU-1 EF-5 113 STAFF LUNCH ROOM 210 315 105 315 350 350 (E)AHU-1 (E)AHU-1 112 JANITOR'S CLOSET JANITOR'S CLOSET 33 0 0 70 0 75 (E)AHU-1 (E)TE-3 111 I.T. STORAGE INACTIVE 62 0 0 0 300 300 (E)AHU-1 (E)AHU-1 110 DIR. OFFICE OFFICE 83 50 20 50 150 150 (E)AHU-1 (E)AHU-1 109 OFFICE OFFICE 75 50 20 50 125 125 (E)AHU-1 (E)AHU-1 108 MEN'S TOILET ROOM 103 0 0 210 200 225 (E)AHU-1 EF-5 107 WOMEN'S TOILET ROOM 103 0 0 210 200 225 (E)AHU-1 EF-5 106 EXAM ROOM DOCTOR EXAM ROOM 108 65 25 50 75 75 (E)AHU-1 (E)AHU-1 105 RECEPTION OFFICE 71 50 20 50 100 100 (E)AHU-1 (E)AHU-1 104 SOCIAL WORKER OFFICE 101 65 25 50 100 100 (E)AHU-1 (E)AHU-1 103 DIETITIAN OFFICE 94 60 20 50 225 225 (E)AHU-1 (E)AHU-1 102 CONFERENCE OFFICE 212 130 45 65 750 750 (E)AHU-1 (E)AHU-1 101 WAITING WAITING ROOM 670 670 225 670 1,000 1,000 (E)AHU-1 (E)AHU-1 NUMBER NAME CATEGORY (SQ. FT.) SUPPLY OA ROOM EXHAUST SUPPLY EXHAUST SYSTEM SYSTEM ROOM ROOM OCCUPANCY AREA CFM AIR CFM AIR CFM AIR CFM AIR CFM ROOM SUPPLY ROOM EXHAUST REMARKS CMC FLOOR MECHANICAL VENTILATION MECHANICAL VENTILATION CITY OF CHICAGO ORDINANCE REQUIREMENTS ACTUAL REQUIREMENTS VENTILATION SCHEDULE Note: This table is to show conformity to Section 18-28-501.4. Total Actual Continuous Exhaust (CFM) 1800 Total Ordinance Required Outside Air (CFM) 1980 BUILDING PRESSURIZATION TABLE Owner, Contractor or Owner’s licensed engineer representative. Signed: __________________________________________ I hereby certify that the heating system will heat all rooms regularly occupied by humans to an inside temperature of 68° when the outside temperature is minus 10° F (As required by the Sections 34(13-196-410) and 13(13-196-170) of the 2018 Chicago Building Code and by Paragraph 1204.1 of Chapter 18-12 (Interior Environment) of the proposed Building Planning and Life Safety portion of the Code). HEATING CERTIFICATION STATEMENT VAV ELECTRIC REHEAT COILS... 160 (E)CUH-3 (MBH) 7.5 (E)CUH-2 (MBH) 19.4 CUH-1 (MBH) 19.4 (E)AHU-1 (MBH) 400 Heating System Equipment... Heating System Output Capacit... 606.3 Total Heating Load (MBH) 530 Ventilation Load (MBH) 448 Building Load (MBH) 82 HEATING TABLE (E) AHU-1 ROOF R-407 35 COPELAND 2 10/5 10/5 UNIT NO. LOCATION REFRIG. TYPE LBS. OF REFRIG. COMPRESSOR MANUFACTURER NO. OF COMPS TONS (EA) HP (EA) REFRIGERATION SCHEDULE (FOR REFERENCE) 1 09/07/2018 ISSUE FOR BID COC COMMERCIAL COMPLIANCE FORM CITY OF CHICGAO NOTES 1. ALL SYSTEMS MUST COMPLY WITH THE CURRENT CITY OF CHICAGO ENERGY CONSERVATION CODE.2. INCLUDING CONTROLS, TEMPERATURE/HUMIDITY SENSORS, EQUIPMENT, ETC.NOISE LEVEL AT LOT LINE SHALL NOT EXCEED 55 DbA. 2. ALL WORK SHALL CONFORM TO THE CURRENT CITY OF CHICAGO CODES AND ORDINANCES. 3. ALL FLEXIBLE LOW-PRESSURE DUCTWORK SHALL BE INSULATED, CITY OF CHICAGO APPROVED & NOT TO EXCEED 5'-0" IN LENGTH. MFG. WIREMOLD TYPE WK UL-181, CLASS I. 4. ALL DIRECT EXPANSION DEVICES, VALVES AND ETC. SHALL BE REMOVED FROM EQUIPMENT AND DUCTWORK AIR STREAMS. 5. TRANSFER AIR DUCTWORK SHALL NOT EXCEED 5'-0" IN LENGTH. 6. ALL OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 15'-0" AWAY FROM ANY EXHAUST, FLUES, VENTS AND ETC. AND A MINIMUM OF 10'-0" ABOVE PUBLIC WAY. 7. ALL DUCTWORK SYSTEMS TO BE CONSTRUCTED OF SHEET METAL CONFORMING TO SMACNA CONSTRUCTION STANDARDS. 8. ROOF PENETRATIONS SHALL BE FLASHED TO PREVENT ENTRY OF WATER THROUGH THE ROOF. 9. UNITS SHALL BE LISTED AND LABELED, AND SHALL BEAR A LABEL SHOWING THE MANUFACTURER'S NAME AND ADDRESS, THE UNIT'S MODEL NUMBER, THE UNIT'S SERIAL NUMBER, THE UNIT'S MAXIMUM AND MINIMUM ALLOWABLE OPERATING PRESSURES AND THE TYPES OF HEAT TRANSFER FLUIDS COMPATIBLE WITH THE UNIT. THE LABEL SHALL MAKE IT CLEAR THAT THESE SPECIFICATIONS APPLY ONLY TO THE THERMAL STORAGE UNIT. 10. ALL PIPING SERVING AS PART OF A HEATING OR COOLING SYSTEM SHALL BE THERMALLY INSULATED IN ACCORDANCE WITH TABLE 18-13-803.3.7. 11. NOT IN CONTRACT (NIC) SPACES DENOTE AREAS OF NO CHANGE TO PREVIOUSLY PERMITTED ORDINANCE VENTILATION REQUIREMENTS. 12. ALL DAMPERS TO BE LOCK TYPE.

M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

AFFIX REP SEAL HERE

www.energycodes.gov/comcheck

COMMERCIAL COMPLIANCE FORM - Chicago Energy Conservation Code

B. Prescriptive Path (check one)

A. Comcheck

C. Total Building Performance

RECOMMENDED METHOD Download Comcheck free at

Print and attach Com check compliance certificate. ( required)

Permit Application Number: _______________________________________________________________________

Project Address: _________________________________________________________________________________

Instructions: Select compliance method A, B, C, D or E by marking the appropriate check box, and then select allrequired sub-boxes as applicable. Sign and complete contact information and attached back -up as required.

Report, Check List,Certificate, Project

Details, Permit Date

504: Service Water Heating

(504 is in addition to Comcheck)

503: Mechanical Systems503.3: Simple HVAC Systems

503: Mechanical Systems503.4: Complex HVAC Systems

Article 5 502, 504, and 505

Article 5 502, 504, and 505

*Article 5Comcheck

Article 5 506, Total Building Performance

OR------------------------------------------------ --------------------------------------------------

OR------------------------------------------------ --------------------------------------------------

OR------------------------------------------------ --------------------------------------------------

OR

D. ASHRAE/IESNA 90.1-2004

E. ASHRAE/IESNA 90.1-2004 (Energy Cost Budget)

OR OR OR

OR------------------------------------------------ --------------------------------------------------

-------------------------------------------------------------------------------------------------------

(check one option for section 5, 6 and 9)

I certify that I am a Registered Energy Professional (REP). I also certify that to the best of my knowledge and belief the plans for the project listedabove fully comply with the requirements of Chapter 18-13, Energy Conservation, of the Municipal Code of Chicago as effective April 22, 2009,including all relevant provisions of Article 1. The method of compliance used for this property is clearly marked on the flowchart above.

Signed:

Address:

Telephone:

Email:

Print Name:

Date:

Illinois License #:

5: Envelope(5.1, 5.4, 5.7, 5.8)

6: HVAC(6.1, 6.7, 6.8)

9: Lighting(9.1, 9.4)

5.5 5.6 6.3 6.4 9.5 9.6

Ashrae/IESNA90.1-2004

Ashrae/IESNA90.1-2004

11: Energy Cost Budget

7: Service Water Heating(7.1, 7.4, 7.5, 7.7, 7.8)

8: Power(8.1, 8.4, 8.7)

10: Other Equipment(10.1, 10.4, 10.8)

CERTIFICATE OF COMPLIANCE

Reg. No.Date

These drawings and plans comply with therequirements in the building provisions of the City ofChicago Building Code. I hereby certify that thesedrawings and plans were prepared by me or under mydirect supervision, and that I am a duly RegisteredEngineer under the laws of the State of Illinois.

ANWAR SULTAN

09/06/18

[email protected]

36 S. WABASH AVE, CHICAGO, IL

430 EAST 51ST PLACE, CHICAGO, IL 60615

SYMBOLS

SUPPLY DUCT RISE

RETURN DUCT RISE

EXHAUST DUCT RISE

OPPOSED BLADE VOLUME DAMPERS

OR FLEXIBLE DUCT

SINGLE LINE DUCT RISE OR DROP

ELBOW WITH TURNING VANES

SINGLE LINE DUCTWORK

VOLUME DAMPER

BACKDRAFT DAMPER

SUPPLY DUCT DROP

RETURN DUCT DROP

EXHAUST DUCT DROP

EXISTING SINGLE LINE DUCT

CAPPED DUCTWORK

CAPPED PIPING OR SINGLE DUCTWORK

OR

EXISTING ITEM TO BE REMOVED

DUCT OFF-SET DN (IN DIRECTION OF FLOW)

DUCT OFF-SET UP (IN DIRECTION OF FLOW)

RECTANGULAR DUCT DIMENSIONS(SIZE IN INCHES, FIRST DIMENSION IS SHOWN)

ROUND DUCT DIMENSIONS (DIAMETER)

OVAL DUCT DIMENSIONS(SIZE IN INCHES, FIRST DIMENSION IS SHOWN)

MOTORIZED DAMPER

FIRE, SMOKE/FIRE, OR SMOKE DAMPER

FD, FS, OR SD

NEW DUCT

EXISTING DUCT

DEMOLISHED DUCT

BDD

24x12 OV

24x12

24"Ø

DN

UP

TP

DIRECTION OF FLOW

PIPE ANCHOR

PIPE GUIDE

FLEXIBLE CONNECTION

TRAP

PIPING FLOW METER

T TEMPERATURE SENSOR (IN DUCT OR PIPE)

RECTANGULAR WYE DUCT FITTING

POINT OF CONNECTION (NEW TO EXISTING)

OR

FM

POINT OF DISCONNECTION FROM EXISTING

T

VARIABLE SPEED DRIVE

T

R

S

ELECTRICAL CONNECTION (BY DIVISION 26)

FREEZESTAT

FLOW SWITCH

RELAY

HUMIDITY SENSOR

SWITCH

SENSING ELEMENT - AIR STREAM

SENSING ELEMENT - LIQUID SEPARABLE WELL

ANALOG OUTPUT

DIGITAL OUTPUT

DIGITAL INPUT

ELECTRICAL CONNECTION (BY DIVISION 26)

ANALOG OUTPUT, PNEUMATIC

ELECTRIC-PNEUMATIC SWITCH

PNEUMATIC-ELECTRIC SWITCH

SMOKE

ANALOG INPUT, PRESSURE

ANALOG INPUT, TEMPERATURE

FIRESTAT

SMOKE DETECTOR

THERMOSTAT WITH LOCKING COVER

PUMP

CARBON DIOXIDE SENSOR

P PRESSURE GAUGE

OR

PUSH BUTTONPB

VSD

OCCUPANCY SENSOR

ANALOG INPUT

TEMPERATURE SENSOR

OXYGEN SENSOR

ANALOG INPUT, FLOW

26

AI

AIF

AIP

AIT

AO

AOP

CO²

DI

DO

E

PE

FIRE

FS

F

H

OS

EP

1

M0101

SECTION INDICATOR TOP INDICATES SECTION NUMBER BOTTOM INDICATES SHEET NUMBER

ROOM PRESSURIZATION MONITOR

DUCT SMOKE DETECTOR

CURRENT SENSOR

SXCFM

SUPPLY AIR DEVICE -(REFER TO SCHEDULE FOR SIZE)FIRST NO. TYPE, SECOND NO. CFM(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

LINEAR DIFFUSER

SUPPLY/ RETURN/EXHAUST SIDEWALL GRILLE-FIRST NO. CFM, SECOND NO. TYPEBOTTOM NO. WIDTH BY HEIGHT OF GRILLE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

RETURN AIR DEVICE -(REFER TO SCHEDULE FOR SIZE)FIRST NO. CFM, SECOND NO. TYPE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

EXHAUST AIR DEVICE -(REFER TO SCHEDULE FOR SIZE)FIRST NO. CFM, SECOND NO. TYPE(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)

AIR FLOW MEASURING STATION

OFF

ONAUTOSTARTER

NEW EQUIPMENT

EXISTING EQUIPMENT

CALLOUT INDICATOR TOP INDICATES NUMBER ON THE SHEET BOTTOM INDICATES SHEET NUMBER

FM

1

M0101

CS

D

EXISTING

EQUIPMENT TYPE

EQUIPMENT TYPE

TYPE NO.

ABBREVIATIONS

DEMOLITION NOTESGENERAL NOTES

A/C AIR CONDITIONINGA/E ARCHITECT/ENGINEERAAV AUTOMATIC AIR VENT (VALVE)ABV ABOVEACCU AIR-COOLED CONDENSING UNITACH AIR CHANGES PER HOURACU AIR CURTAINACW AFTER COOLER WATERAD ACCESS DOORAF AIR FOIL FANAFF ABOVE FINISHED FLOORAFMS AIR FLOW MEASURING STATIONAHU AIR HANDLING UNITALT ALTERNATEALUM ALUMINUMAMP AMPEREAP ACCESS PANELAPD AIR PRESSURE DROPAPPROX APPROXIMATEARCH ARCHITECT/ARCHITECTURALAS AIR SEPARATORATD AIR TRANSFER DUCTAUTO AUTOMATICAVG AVERAGEAWT AVERAGE WATER TEMPERATUREAXF AXIAL FANBB BASEBOARD RADIATIONBDD BACK DRAFT DAMPERBF BOILER FEED WATERBG BOTTOM GRILLE (3"-12" ABOVE FLOOR)BHP BRAKE HORSEPOWERBLDG BUILDINGBMS BUILDING MANAGEMENT SYSTEMBOD BOTTOM OF DUCTBR BOTTOM REGISTER (3"-12" ABOVE FLOOR)BSMT BASEMENTBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNIT PER HOURCA COMPRESSED AIRCAP CAPACITYCC COOLING COILCCW COUNTER CLOCKWISECD CONDENSATE DRAINCENTRIF CENTRIFUGALCF CUBIC FEETCFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECH CABINET HEATERCHR CHILLERCHWR CHILLED WATER RETURNCHWS CHILLED WATER SUPPLYCI CAST IRONCL CENTER LINECLG COOLINGCO CLEAN OUTCO2 CARBON DIOXIDE COMP COMPRESSORCONC CONCRETECONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUOUS, CONTINUATIONCONTR CONTRACTORCONV CONVECTORCP CONTROL PANELCT COOLING TOWERCU CONDENSING/ER UNITCU FT CUBIC FEETCV CONSTANT VOLUME CV CONSTANT VOLUMECWR CONDENSER WATER RETURNCWS CONDENSER WATER SUPPLY

D DRAIN OR DRYERDB DECIBEL OR DRY BULB TEMPERATUREDDC DIRECT DIGITAL CONTROLDEG.F DEGREE FAHRENHEITDEMO DEMOLISHDG DOOR GRILLEDIA DIAMETERDIAG DIAGONALDIFF DIFFUSERDIM DIMENSIONDISCH DISCHARGEDN DOWNDP DIFFERENTIAL PRESSUREDPDT DOUBLE POLE, DOUBLE THROWDPST DOUBLE POLE, SINGLE THROWDTR DUAL TEMPERATURE RETURNDTS DUAL TEMPERATURE SUPPLYDWDI DOUBLE WIDTH, DOUBLE INLETDWG DRAWINGDX DIRECT EXPANSIONE/P ELECTRIC-PNEUMATICEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEBB ELECTRIC BASEBOARD HEATEREC EXPANSION COMPENSATOR/JOINTECWR EQUIPMENT COOLING WATER RETURNECWS EQUIPMENT COOLING WATER SUPPLYEDB ENTERING DRY BULB TEMPERATUREEER ENERGY EFFICIENCY RATIOEF EXHAUST FANEFF EFFICIENCYEHC ELECTRIC HEATING COILEL/ELEV ELEVATIONELEC ELECTRIC/ELECTRICALELEM ELEMENTELEV ELEVATOREMD END OF MAIN DRIP (STEAM)EMER EMERGENCYENG ENGINEERENT ENTERINGERP ELECTRIC RADIANT PANELESP EXTERNAL STATIC PRESSUREEST ESTIMATEET EXPANSION TANKETO ETHYLENE OXIDEEUH ELECTRIC UNIT HEATEREV EXHAUST AIR VALVEEVAP EVAPORATOREVF FUME HOOD EXHAUST AIR VALVEEVL LAB EXHAUST AIR VALVEEWB ENTERING WET BULB TEMPERATUREEWT ENTERING WATER TEMPERATUREEXH EXHAUSTEX EXISTING(E) OR ETR EXISTING TO REMAINEXIST EXISTINGEXT EXTERNALF FAHRENHEITF&T FLOAT & THERMOSTATIC STEAM TRAPF.D. FLOOR DRAINFD FIRE DAMPERFA FREE AREAFC FORWARD CURVEDFCU FAN COIL UNITFD FIRE DAMPERFF FINAL FILTERFH FUME HOODFLA FULL LOAD AMPERESFLEX FLEXIBLEFLR FLOORFLT FLASH TANKFM FLOW METERFOG FUEL OIL GAUGEFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFOV FUEL OIL VENTFP FIRE PROTECTIONFPB FAN POWERED TERMINAL UNITFPM FEET PER MINUTEFPS FEET PER SECONDFR FINNED RADIATIONFSD FIRE SMOKE DAMPERFSTAT FREEZESTATFT FEETFV FACE VELOCITYG NATURAL GASGA GAUGEGAL GALLONGCWR GEOTHERMAL CONDENSER WATER RETURNGCWS GEOTHERMAL CONDENSER WATER SUPPLYGD GRAVITY DAMPERGPH GALLONS PER HOURGPM GALLONS PER MINUTEGR GLYCOL RETURNGRL GRILLEGRV GRAVITY RELIEF VENTGS GLYCOL SUPPLYGV GRAVITY VENTILATOR OR NATURAL GAS VENT

HTG HEATINGHTWR HIGH TEMPERATURE WATER RETURNHTWS HIGH TEMPERATURE WATER SUPPLYHUM HUMIDIFIERHVAC HEAT, VENTILATION, & AIR CONDITIONINGHVU HEATING & VENTILATING UNITHWR HOT WATER RETURN HWS HOT WATER SUPPLY HX HEAT EXCHANGERHZ HERTZID INSIDE DIAMETERIN OR " INCHESIN W.C. INCHES WATER COLUMNIN W.G. INCHES WATER GAUGEINSUL INSULATIONINT INTERNALJW JACKET WATERKW KILOWATTKWH KILOWATT HOURLAT LEAVING AIR TEMPERATURELBS POUNDSLDB LEAVING DRY BULB TEMPERATURELF LINEAR FEETLPG LIQUID PETROLEUM GASLPR LOW PRESSURE CONDENSATE RETURNLPS LOW PRESSURE STEAMLRA LOCKED ROTOR AMPERESLVG LEAVINGLVR LOUVERLWB LEAVING WET BULB TEMPERATURELWT LEAVING WATER TEMPERATUREM MOTOR OPERATORMAINT MAINTENANCEMAU MAKE-UP AIR UNITMAX MAXIMUMMBH THOUSAND BTU PER HOURMCC MOTOR CONTROL CENTERMECH MECHANICALMERV MINIMUM EFFICIENCY REPORTING VALUEMEZZ MEZZANINEMFR MANUFACTURERMIN MINIMUMMISC MISCELLANEOUSMPR MEDIUM PRESSURE CONDENSATE RETURNMPS MEDIUM PRESSURE STEAMMTD MOUNTED

N.C. NORMALLY CLOSEDN.O. NORMALLY OPENNC NOISE CRITERIANIC NOT IN CONTRACTNO. OR # NUMBERNR NOT REQUIREDNTS NOT TO SCALENV NATURAL VENTILATIONOA OUTSIDE AIROAI OUTSIDE AIR INTAKEOBD OPPOSED BLADE DAMPEROED OPEN END DUCTOFCI OWNER FURNISHED/CONTRACTOR INSTALLEDOFOI OWNER FURNISHED/OWNER INSTALLEDOH OVERHEADOPNG OPENINGΔP/DP DIFFERENTIAL PRESSUREP PUMPP/E PNEUMATIC-ELECTRIC SWITCHPA PASCALPCD PUMPED CONDENSATE DISCHARGE/RETURNPCF POUNDS PER CUBIC FOOTPCWR PROCESSED CHILLED WATER RETURNPCWS PROCESSED CHILLED WATER SUPPLYPD PRESSURE DROPPF PROPELLER FANPG PRESSURE GAUGEPH PHASEPLBG PLUMBINGPRESS PRESSUREPROP PROPELLERPRV PRESSURE REDUCING VALVEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE IN ABSOLUTEPSIG POUNDS PER SQUARE IN GAUGEQTY QUANTITYR RETURNRA RETURN AIRRAD RADIATIONRAF RETURN AIR FANREBAL REBALANCEREG REGISTERREV REVISEDRH RELATIVE HUMIDITYRHC REHEAT COILRHG REFRIGERANT HOT GASRL REFRIGERANT LIQUIDRM ROOMRO RELIEF OPENINGRP RADIANT PANELRPM REVOLUTIONS PER MINUTERS REFRIGERANT SUCTIONRTU ROOF TOP UNITRV REFRIGERANT VENT OR RELIEF VALVE (VENT)RV RETURN AIR VALVES/W SUMMER-WINTERSA SUPPLY AIR OR SOUND ATTENUATORSCR SILICON CONTROLLED RECTIFIERSD SMOKE DETECTORSD SMOKE DAMPERSENS SENSIBLE LOADSF SMOKE-FIRE DAMPERSHT SHEETSM SMOKE DAMPERSOL SOLENOIDSP STATIC PRESSURESQ SQUARESQ. FT. SQUARE FEETSS STAINLESS STEELSTD STANDARDSTL STEELSTM STEAMSTRUC STRUCTURE/STRUCTURALSV SUPPLY AIR VALVESWSI SINGLE WIDTH, SINGLE INLETTC TEMPERATURE CONTROLTD TRANSFER DUCTTEMP TEMPERATURETL TOTAL LOADTO TRANSFER OPENINGTSP TOTAL STATIC PRESSURETSTAT THERMOSTATTU TERMINAL UNITTYP TYPICALUGRD UNDERGROUNDUH UNIT HEATER (HYDRONIC OR STEAM)UNO UNLESS NOTED OTHERWISEUPS UNINTERRUPTIBLE POWER SUPPLYUV UNIT VENTILATOR

V VOLT OR VENTVAV VARIABLE AIR VOLUMEVD VOLUME DAMPERVEL VELOCITYVERT VERTICALVI VIBRATION ISOLATIONVIF VERIFY IN FIELDVOL VOLUMEVR VACUUM RETURNVRV VARIABLE REFRIGERANT VOLUMEVSD VARIABLE SPEED DRIVEVTR VENT THROUGH ROOF(X) EXISTING TO BE DEMOLISHED W WATTW.G. WATER GAUGEW/ WITHW/O WITHOUTWB WET BULB TEMPERATUREWC WATER COLUMNWMS WIRE MESH SCREENWPD WATER PRESSURE DROPWT WEIGHTWTR WATER

1. ALL DEMOLITION WORK SHALL BE PERFORMED WITH “DUE CARE AND DILIGENCE” SO AS TO PREVENT THE UNNECESSARY DESTRUCTION AND/OR DAMAGE TO SYSTEMS THAT SHALL REMAIN IN OPERATION AT THE CONCLUSION OF THIS WORK. DETERMINE THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DEVICES AND WIRING BEFORE COMMENCING WORK.

2. LOCATE AND PRESERVE ALL PORTIONS OF THE EXISTING HVAC SYSTEMS WHICH SHALL REMAIN.

3. CONTROLS DEVICES AND WIRING ARE NOT SHOWN ON THE DEMOLITION PLAN AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

4. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING HVAC DEVICES, EQUIPMENT, AND WIRING BEFORE COMMENCING WORK, THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES THAT MIGHT OCCUR BECAUSE OF THE CONTRACTORS FAILURE TO ACCURATELY DISCOVER, LOCATE, AND PROTECT ANY AND ALL PORTIONS OF THE EXISTING HVAC SYSTEM.

5. EXISTING DUCTWORK AND CONTROLS WIRING MAY BE RE-USED WHERE THEY ARE OF THE TYPE SPECIFIED, MEET THE REQUIREMENTS FOR THE NEW WORK AS DEFINED BY THE CONTRACT DOCUMENTS, AND REMAIN IN GOOD CONDITION.

6. REMOVE AND RE-INSTALL (OR PROTECT IN PLACE) ALL EXISTING EQUIPMENT AND DEVICES TO REMAIN ON OR IN WALLS, CEILINGS AND FLOORS WHICH SHALL BE EXPOSED TO DEMOLITION AND CONSTRUCTION ACTIVITIES AND WHICH MAY BE DAMAGED BY DUST, DEBRIS, ETC.

7. WHERE EXISTING EQUIPMENT AND DEVICES SHALL BE REMOVED, THE CONTRACTOR SHALL REMOVE ALL THE ASSOCIATED DUCTWORK, PIPING, AND CONTROLS THAT SHALL NOT REMAIN IN OPERATION BACK TO THEIR RESPECTIVE SOURCE OR TO THE POINT ON A SHARED SYSTEM FROM WHERE THE EQUIPMENT OR DEVICE IS SERVED.

8. RELOCATE AS NECESSARY ALL EXISTING DUCTWORK, PIPING, AND CONTROLS FOUND PASSING THROUGH THE AREA OF CONSTRUCTION, AND WHICH ARE PRESENTLY IN USE OTHER PORTIONS OF THE BUILDING UNAFFECTED BY THIS PROJECT PHASE, TO MAINTAIN THE CONTINUITY OF SERVICES AND GROUNDING, AND TO CONCEAL THEM ABOVE NEW CEILINGS.

9. ALL EXISTING DAMAGED DUCTWORK, GRILLES, AND DEVICES WITHIN THE AREA OF CONSTRUCTION AND SHOWN TO REMAIN IN OPERATION SHALL BE REPLACED WITH NEW MATERIALS CONFORMING TO THESE CONTRACT DOCUMENTS AT NO COST TO OWNER.

10. ALL EQUIPMENT, DEVICES, AND MATERIALS REMOVED DURING DEMOLITION WORK AND NOT INDICATED TO BE REUSED OR TURNED OVER TO THE OWNER SHALL BECOME THE RESPONSIBILITY OF THE CONTRACTOR FOR DISPOSAL.

11. THE CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING NECESSARY TO REPAIR ANY DAMAGE CAUSED BY CONSTRUCTION ACTIVITIES PERFORMED BY THE CONTRACTOR. THIS WORK INCLUDES AREAS OUTSIDE ANY LIMITS OF CONSTRUCTION LINES SHOWN ON THE DRAWINGS.

H HUMIDISTAT OR HUMIDIFIERHC HEATING COILHEPA HIGH EFFICIENCY PARTICULATE AIR FILTERHG HOT GASHL HIGH LIMITHORIZ HORIZONTALHP HORSEPOWER OR HEAT PUMPHPR HIGH PRESSURE CONDENSATE RETURNHPS HIGH PRESSURE STEAMHR HOURHRC HEAT RECOVERY COILHT HEIGHTHTG HEATING

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALL CEILING AIR DEVICE LOCATIONS.

2. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR LOCATION OF WALL MOUNTED MECHANICAL ITEMS.

3. LOCATE ALL DUCT BALANCING DAMPERS ABOVE ACCESSIBLE CEILINGS, OR PROVIDE ACCESS DOORS. MINIMUM ACCESS DOOR SIZE SHALL BE 18x18 UNLESS OTHERWISE APPROVED BY ENGINEER.

4. PROVIDE VOLUME DAMPERS AT ALL SUPPLY, RETURN AND EXHAUST DUCT BRANCH TAKE-OFFS. SEE DUCT CONSTRUCTION DETAILS.

5. COORDINATE SCHEDULE FOR HOOKUPS TO EXISTING SYSTEM AND REMOVAL OR RELOCATION OF EQUIPMENT WITH THE

OWNER. PERFORM THIS WORK AT SUCH TIMES TO ENSURE THAT PERIODS OF SHUTDOWN WILL BE ACCEPTABLE TO THE OWNER.

6. VERIFY EXACT LOCATION OF CONNECTION POINTS (NEW TO EXISTING) IN FIELD PRIOR TO CONSTRUCTION.

7. COORDINATE INSTALLATION OF NEW DUCTWORK AND PIPING WITH EXISTING BUILDING STRUCTURE, DUCTWORK, PIPING, ELECTRICAL CONDUIT, LIGHTING, ETC.

8. TAKE DOWN AND REINSTALL EXISTING CEILINGS IN ALL AREAS WHERE MECHANICAL WORK IS INDICATED AND EXISTING CEILINGS REMAIN. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN DRAWINGS FOR LOCATIONS WHERE EXISTING CEILINGS REMAIN. REPLACE CEILING TILES DAMAGED DURING WORK.

9. PATCH ALL WALLS, FLOORS, CEILINGS, AND ROOFS TO MATCH EXISTING IN ALL CASES WHERE EXISTING WALLS, FLOORS, CEILINGS AND ROOFS REMAIN AND HVAC DEMOLITION IS INDICATED.

#

-

#

(E)XXX

TYPE NO.

RXCFM

EXCFM

SXCFM

SXCFM

H

C

HUMIDISTAT

CO SENSOR

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

SYMBOLS, ABBREVIATIONS,

AND GENERAL NOTES

M0001

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

1. MINIMUM OA AIRFLOW ACHIEVED BY BASE-BUILDING VENTILATION SYSTEM. MINIMUM OVERALL AIRFLOW RATE ACHIEVED VIA USE OF BASE BUILDING VENTILATION SYSTEM.

NOTES:

TOTALS 5,050 2,565 890 2,910 6,720 6,575

117A W.C. TOILET ROOM 50 0 0 100 50 100 (E)AHU-1 EF-4

116A NURSE TREATMENT ROOM 169 105 35 55 125 125 (E)AHU-1 (E)AHU-1

113B STAFF TOILET TOILET ROOM 50 0 0 100 50 100 (E)AHU-1 (E)TE-4

113A CHANGING ROOM LOCKER ROOM 20 50 20 50 50 50 (E)AHU-1 (E)AHU-1

100D CORRIDOR CORRIDOR 425 0 0 0 325 100 (E)AHU-1 (E)AHU-1

100C CORRIDOR CORRIDOR 224 0 0 0 100 0 (E)AHU-1 (E)AHU-1

125 WATER TREATMENT NA 317 0 0 0 350 350 (E)AHU-1 EF-2

124 MECH NA 102 0 0 0 200 200 (E)AHU-1 (E)EF-1

123 ELEC NA 118 0 0 0 75 0 (E)AHU-1 (E)AHU-1

122 STORAGE STORAGE INACTIVE 114 0 0 0 50 50 (E)AHU-1 (E)AHU-1

121 LAB LABORATORY 63 80 30 80 100 100 (E)AHU-1 (E)AHU-1

120 EQUIP REPAIR STORAGE ACTIVE 147 75 25 75 150 150 (E)AHU-1 (E)AHU-1

119 CLEAN SUPPLY STORAGE ACTIVE 100 50 20 50 100 75 (E)AHU-1 (E)AHU-1

118 SOILED STORAGE LABORATORY 100 120 40 120 120 150 (E)AHU-1 EF-3

117 PRIVATE PAT./ISOLATION PATIENT ROOM 132 50 20 50 250 275 (E)AHU-1 EF-4

116 TREATMENT AREA TREATMENT ROOM 862 520 175 260 900 800 (E)AHU-1 (E)AHU-1

115 MED PREP TREATMENT ROOM 92 60 20 50 150 150 (E)AHU-1 (E)AHU-1

114 PAT. TOILET TOILET ROOM 40 0 0 80 0 100 (E)AHU-1 EF-5

113 STAFF LUNCH ROOM 210 315 105 315 350 350 (E)AHU-1 (E)AHU-1

112 JANITOR'S CLOSET JANITOR'S CLOSET 33 0 0 70 0 75 (E)AHU-1 (E)TE-3

111 I.T. STORAGE INACTIVE 62 0 0 0 300 300 (E)AHU-1 (E)AHU-1

110 DIR. OFFICE OFFICE 83 50 20 50 150 150 (E)AHU-1 (E)AHU-1

109 OFFICE OFFICE 75 50 20 50 125 125 (E)AHU-1 (E)AHU-1

108 MEN'S TOILET ROOM 103 0 0 210 200 225 (E)AHU-1 EF-5

107 WOMEN'S TOILET ROOM 103 0 0 210 200 225 (E)AHU-1 EF-5

106 EXAM ROOM DOCTOR EXAM ROOM 108 65 25 50 75 75 (E)AHU-1 (E)AHU-1

105 RECEPTION OFFICE 71 50 20 50 100 100 (E)AHU-1 (E)AHU-1

104 SOCIAL WORKER OFFICE 101 65 25 50 100 100 (E)AHU-1 (E)AHU-1

103 DIETITIAN OFFICE 94 60 20 50 225 225 (E)AHU-1 (E)AHU-1

102 CONFERENCE OFFICE 212 130 45 65 750 750 (E)AHU-1 (E)AHU-1

101 WAITING WAITING ROOM 670 670 225 670 1,000 1,000 (E)AHU-1 (E)AHU-1

NUMBER NAME CATEGORY (SQ. FT.) SUPPLY OA ROOM EXHAUST SUPPLY EXHAUST SYSTEM SYSTEM

ROOM ROOM OCCUPANCY AREA CFM AIR CFM AIR CFM AIR CFM AIR CFM ROOM SUPPLY ROOM EXHAUST REMARKS

CMC FLOOR MECHANICAL VENTILATION MECHANICAL VENTILATION

CITY OF CHICAGO ORDINANCE REQUIREMENTS ACTUAL REQUIREMENTS

VENTILATION SCHEDULE

Note: This table is to show conformity to Section 18-28-501.4.

Total Actual Continuous Exhaust (CFM) 1800

Total Ordinance Required Outside Air (CFM) 1980

BUILDING PRESSURIZATION TABLE

Owner, Contractor or Owner’s licensed engineerrepresentative.

Signed: __________________________________________

I hereby certify that the heating system will heat all roomsregularly occupied by humans to an inside temperature of 68°when the outside temperature is minus 10° F (As required bythe Sections 34(13-196-410) and 13(13-196-170) of the 2018Chicago Building Code and by Paragraph 1204.1 of Chapter18-12 (Interior Environment) of the proposed Building Planningand Life Safety portion of the Code).

HEATING CERTIFICATION STATEMENT

VAV ELECTRIC REHEAT COILS... 160

(E)CUH-3 (MBH) 7.5

(E)CUH-2 (MBH) 19.4

CUH-1 (MBH) 19.4

(E)AHU-1 (MBH) 400

Heating System Equipment...

Heating System Output Capacit... 606.3

Total Heating Load (MBH) 530

Ventilation Load (MBH) 448

Building Load (MBH) 82

HEATING TABLE

(E) AHU-1 ROOF R-407 35 COPELAND 2 10/5 10/5

UNIT NO. LOCATIONREFRIG.

TYPE

LBS. OF

REFRIG.

COMPRESSOR

MANUFACTURER

NO. OF

COMPSTONS (EA) HP (EA)

REFRIGERATION SCHEDULE (FOR REFERENCE)

1 09/07/2018 ISSUE FOR BID

COC COMMERCIAL COMPLIANCE FORM

CITY OF CHICGAO NOTES

1. ALL SYSTEMS MUST COMPLY WITH THE CURRENT CITY OF CHICAGO ENERGY CONSERVATION CODE.2. INCLUDING CONTROLS, TEMPERATURE/HUMIDITY SENSORS, EQUIPMENT, ETC.NOISE LEVEL AT LOT LINE SHALL NOT EXCEED 55 DbA.

2. ALL WORK SHALL CONFORM TO THE CURRENT CITY OF CHICAGO CODES AND ORDINANCES.

3. ALL FLEXIBLE LOW-PRESSURE DUCTWORK SHALL BE INSULATED, CITY OF CHICAGO APPROVED & NOT TO EXCEED 5'-0" IN LENGTH. MFG. WIREMOLD TYPE WK UL-181, CLASS I.

4. ALL DIRECT EXPANSION DEVICES, VALVES AND ETC. SHALL BE REMOVED FROM EQUIPMENT AND DUCTWORK AIR STREAMS.

5. TRANSFER AIR DUCTWORK SHALL NOT EXCEED 5'-0" IN LENGTH.

6. ALL OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 15'-0" AWAY FROM ANY EXHAUST, FLUES, VENTS AND ETC. AND A MINIMUM OF 10'-0" ABOVE PUBLIC WAY.

7. ALL DUCTWORK SYSTEMS TO BE CONSTRUCTED OF SHEET METAL CONFORMING TO SMACNA CONSTRUCTION STANDARDS.

8. ROOF PENETRATIONS SHALL BE FLASHED TO PREVENT ENTRY OF WATER THROUGH THE ROOF.

9. UNITS SHALL BE LISTED AND LABELED, AND SHALL BEAR A LABEL SHOWING THE MANUFACTURER'S NAME AND ADDRESS, THE UNIT'S MODEL NUMBER, THE UNIT'S SERIAL NUMBER, THE UNIT'S MAXIMUM AND MINIMUM ALLOWABLE OPERATING PRESSURES AND THE TYPES OF HEAT TRANSFER FLUIDS COMPATIBLE WITH THE UNIT. THE LABEL SHALL MAKE IT CLEAR THAT THESE SPECIFICATIONS APPLY ONLY TO THE THERMAL STORAGE UNIT.

10. ALL PIPING SERVING AS PART OF A HEATING OR COOLING SYSTEM SHALL BE THERMALLY INSULATED IN ACCORDANCE WITH TABLE 18-13-803.3.7.

11. NOT IN CONTRACT (NIC) SPACES DENOTE AREAS OF NO CHANGE TO PREVIOUSLY PERMITTED ORDINANCE VENTILATION REQUIREMENTS.

12. ALL DAMPERS TO BE LOCK TYPE.

Page 2: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

H

C

T

H

C

T

?

?

?

?

?

??

?

?

?

?

?

?

TT

T

T

T

T

T

T

T

T

T

T

T

?

?

?

T

T

T

T

321

A

B

C

D

S-1100

S-1200

R-1100

R-1225

R-1300

R-1100S-1

100

S-175R-1

400

R-175

R-1300

R-1350

S-1125

S-1150

R-1125 R-1

150

S-1100

S-1150

S-1100

R-150

S-1150

R-1100

S-1100

S-1150

R-150

S-150

S-150

S-150

R-1350

S-1175

R-150

R-175

S-1100

S-1120

S-1100

S-1100

S-1125

S-1100

S-150

1

(E)H

R-1150

R-1900

12x12 UP THRUROOF TO EF-5

12x6 SA (E)

S-1200

6"⌀ ROUND DUCT TO ALL PLENUM

SLOT DIFFUSERS (TYP. 3)

8"⌀ ROUND DUCT TO ALL PLENUM

SLOT DIFFUSERS (TYP. 5)

6"⌀ ROUND DUCT TO ALL PLENUM

SLOT DIFFUSERS (TYP. 5)

S-5 75

S-2 75

S-2 75

S-2200

S-2200

S-2200

S-2200

S-2200

S-2150

S-2150

S-2150

S-2150

S-5150

(E) 12x12 UP THRU ROOF TO (E)TE-4

(E) 12x12 UP THRU ROOF TO (E)TE-3

(E) 12x12 UP THRU ROOF TO EF-1

14x10 S

A

18x12 S

A

16x14 RA 20x14 RA

20x16 R

A

18x18 SA (E)

24x18 S

A (

E)

16"Ø SA (E)

12x8 S

A

12x8 S

A8x8 S

A

12x8 R

A

14x10 RA

12x10 S

A

16x14 RA

16x14 R

A

14x8 R

A

6x6 R

A

10x10 R

A

8x6 R

A

(E)TR-1200

(E)S-475 3

(E)CUH

2

(E)CUH

9

VAV

11

VAV

10

VAV

12

VAV

13

VAV

2

(E)H

8

(E)VAV

3

(E)VAV

12x10 SA

12x8 SA

12x8 S

A

8x8 R

A

8x6 SA

10x8 S

A8x6 S

A

16x10 SA

6x6 S

A

S-1100

(E) 24x18 SA UP THRUROOF TO AHU-1

E) 36x18 RA UP THRU ROOF TO AHU-1

1

CUH

6"Ø SA (E)

6x6 RA

12x6 EA

8x8 SA

6"Ø SA

18x18 SA (E)

18x12 SA

12x8 SA

10x8 R

A12x12 EA

6x6 SA

6x6 SA

6x6 RA

6x6 RA

2

1

1

1

1

3

1

6x6 RA

10x10 S

A

14x12 RA

6x6 SA

S-350

12x6 SA

E-3100

H-1

VAV-2

VAV-3

(E) CUH-3

CUH-1

VAV-6

VAV-7

VAV-9

VAV-5

VAV-11VAV-10

VAV-12

VAV-1

H-2

(E) GAS UPTO AHU-1

(E) GAS METER

WOMENS107

MENS108

OFFICE109

STAFF113

STAFFTOILET113B

TELECOM111

JANITOR'SCLOSET

112

CORRIDOR100B

SOILEDSTORAGE

118

STORAGE122

LAB121

MECHANICAL124

ELECTRICAL123

W.C.117A

WATERTREATMENT

125

CLEANSUPPLY

119

CONFERENCE102

SOCIALWORKER

104

DIRECTOROFFICE

110

EXAM106 EQUIP.

REPAIR120

1

2

3

4

5 6 7

9

10

12

MED. PREP.115

PAT. TOILET114

RECEPTION105

DIETITIAN103

WAITINGROOM

101

NURSESTATION

116A

TREATMENTAREA116

CHANGINGROOM113A

CORRIDOR100C

CORRIDOR100D

PRIVATEPAT./ISOLATION

117

12x12 UP THRU ROOF TO EF-3

8"Ø UP THRU ROOF FOR EXHAUST

20x10 SA

8"Ø SA

8"Ø SA

8"Ø SA

8"Ø SA

8"Ø SA

10

M0701

6"Ø SA

6"Ø

SA

6"Ø

SA

6"Ø SA

6"Ø SA

6"Ø SA

6"Ø

SA

8

4

5

6

14

VAV

S-4350

CAV-1

E-1350

6"Ø SA

12x12 SA

6x6 RA

4"Ø

SA

10x8 UP THRU ROOF TO EF-4

7

7

7 7E-2225

E-2225

10x8 EA

7

8x6 SA

14x10 RA

8"Ø EA

1

E-375

12x8 S

A

12x10 SA

S-1200

S-1200

9

VAV-4

50CFM

P

4

VAV

1

VAV

5

VAV

6

VAV

7

VAV

14x14 S

A

16x10 S

A

16x10 SA

16x10 S

A

R-1400

DROP

DROP

DROP

DROP

DROP

DROP

RISE

DROP

15

VAV

DR

OP

S-1250

E-2150

E-2275

S-350

8x8 EA

E-3100

S-350

S-1175

6"Ø

EA

18x12 RA

6"Ø

SA

4"Ø SA

12x8 RA

50CFM

RISE

12x12 E

A (

E)

E-3100

E-2150

8x6 SA

8x4 S

A

8x6 S

A

4"Ø SA

12x6 SA

8x6 EA

8"Ø SA

8"Ø SA

6"Ø SA

R-2300 12x6 RA (E)

S-2100

S-2100

S-2100

3

3

3

1

1

1

50CFM

9

50CFM

6x6 EA

(E)CUH-2

10

1

(E)AC

12x8 SA

DROP

R-2350

8x8 S

A

CAV-2

VAV-8

6

EF

S-1200

S-1200

12"Ø SA

6"Ø SA

14x8 RA

14x10 SA

10"Ø SA

8x6 SA 16x10 SA

8x6 S

A

8x6 S

A

8x6 S

A

16x10 S

A

6"Ø SA

12"Ø

SA

VAV-1311

R-1900

11

M0701

20x14 RA

VAV-16 16

VAV

S-4350

(E) GAS TO AHU-1

(E) GAS TO AHU-1

12

M0701

1

WH

6"Ø FLUE GAS UP THRU ROOF

1" GAS TO WATER HEATER

12

13

10x8 UP THRU ROOF TO EF-2

6"Ø COMBUSTION AIR INTAKE

2" GAS

2" GAS

14

10x8 S

A

14x14 S

A

6x6 S

A

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

LEVEL 01 - HVAC DUCTWORK

PLAN

M0101

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

GENERAL NOTES:

A. COORDINATE EXACT LAYOUT OF SUPPLY/RETURN/EXHAUST AIR DIFFUSERS/GRILLES WITH ARCHITECTURAL AND ELECTRICAL REFLECTED CEILING PLANS.

B. ALL SUPPLY DIFFUSERS SHALL BE HARD DUCTED WITH NO MORE THAN 5'-0" OF FLEXIBLE DUCT.

C. TEST AND BALANCE SHALL BE PERFORMED FOR ALL NEW AND EXISTING SYSTEMS IN THE AREA. SUBMIT REPORT TO ENGINEER FOR RECORD.

D. SEE ARCHITECTURAL PLANS FOR OPENING REQUIREMENTS AT LOAD BEARING WALL, RE-USE EXISTING OPENINGS AS PRACTICAL.

KEYED NOTES:1. INSTALL NEW VAV BOX WITH ELECTRIC REHEAT COIL, EXTEND

AND CONNECT UPSTREAM DUCT TO EXISTING MEDIUM PRESSURE DUCT AND DOWNSTREAM DUCT TO NEW SUPPLY AIR DIFFUSERS.

2. EXTEND AND CONNECT NEW SUPPLY AIR DIFFUSERS TO EXISTING VAV BOX. PROVIDE NEW THERMOSTAT AND INTERFACE WITH VAV BOX SERVING THE AREA. REBALANCE EXISTING VAV BOXES TO NEW AIRFLOW INDICATED

3. REPLACE EXISTING SLOT DIFFUSERS AND RETURN GRILLE IN THE VESTIBULE WITH NEW. EXTEND AND CONNECT TO EXISTING DUCTWORK.

4. PROVIDE NEW HUMIDISTAT FOR H-1. REPLACE CO SENSOR AND MOUNT AT LOCATION INDICATED.

5. PROVIDE NEW HUMIDISTAT FOR H-2. REPLACE CO SENSOR AND MOUNT AT LOCATION INDICATED.

6. NEW LOCATION OF VFD'S. PROIVDE NEW SUPPLY AND RETURN FAN VFD'S IN THE ELECTRICAL ROOM (TOTAL - 2VFD'S). CONTRACTOR SHALL PROVIDE NEW CONTROL WIRING FROM MCQUAY MICROTEC CONTROLLER TO VFD FOR SPEED CONTROL AND FEEDBACK. COORDINATE WITH MANUFACTURER AND SITE CONDITIONS FOR PROTOCOL USED, WIRE SIZE AND TYPE.

7. REPLACE EXISTING SUPPLY/EXHAUST DIFFUSERS WITH NEW. EXTEND AND CONNECT TO EXISTING DUCTWORK.

8. CEILING MOUNTED 250CFM FAN SIMILAR TO BROAN MODEL L250. PROVIDE 8"Ø DUCT AND TERMINATE ON ROOF W/ MANUFACTURER ROOFCAP ASSEMBLY. AUTOMATIC BACKDRAFT DAMPER TO BE LOCATED WITHIN DUCT CONNECTOR.

9. EXTEND AND CONNECT DUCTWORK FROM NEW DIFFUSER TO EXISTING EXHAUST FAN DUCTWORK.

10. ISOLATION ROOM CONTROL ROOM PRESSURE MONITOR. PROVIDE WITH LCD DISPLAY, COORDINATE LOCATION OF DISPLAY WITH END-USER.

11. PROVIDE INSULATION ON BACK OF THERMOSTAT PLAT.

12. 6"Ø FLUE. TERMINATE ON ROOF, PROVIDE WITH MANUFACTURER CAP ASSEMBLY. PROVIDE GAS PIPING WITH ISOLATION VALVE AND PRESSURE REGULATOR.

13. 6"Ø COMBUSTION AIR INTAKE. TERMINATE ON WALL WITH MANUFACTURER WALL KIT. COORDINATE DUCT ROUTING WITH MARCOR WATER TREATMENT EQUIPMENT.

14. EXISTING GAS SERVICE SERVING AIR HANDLING UNIT ONLY (500 MBH). LOAD OF 120 MBH FOR WATER HEATER IS ADDED TO THE SYSTEM. UPGRADE SERVICE AS REQUIRED TO HANDLE TOTAL LOAD OF 720 MBH. REPLACE EXISTING GAS PIPE WITH 2" LINE FROM THE GAS METER UP TO THE LOCATION INDICATED.

1/4" = 1'-0"1

LEVEL 01 - HVAC DUCTWORK PLAN

1 09/07/2018 ISSUE FOR BID

Page 3: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

3

(E)TE

1

(E)AHU

1

(E)EF

2

EF

1

2

3

EF

3

4

4

EF

60x20 EA (E)

(E) 24x18 SA DN

(E) 36x18 RA DN

5

5

5

(E) FRESH AIR31.4 SQ.FT. FREE AREA OPENING

(E) 5,370 CFM EXHAUST 11.8 SQ.FT. FRE AREA OPENING

1

1

5

EF

4

(E)TE

1980 CFM MIN6100 CFM MAX

(E) SKYLIGHT

EXISTING ROOF HATCH

6"Ø FLUE, TERMINATE W/ MANF. CAP

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

ROOF - HVAC DUCTWORK PLAN

M0102

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

1/4" = 1'-0"1

ROOF - HVAC DUCTWORK PLAN

GENERAL NOTES:

A. PROVIDE 6" HOUSEKEEPING PAD FOR ALL NEW ROOF MOUNTED EQUIPMENT.

NOTES:1. EXISTING EXHAUST FAN TO REMAIN.

2. REPLACE EXISTING TOILET EXHAUST FAN TE-1 WITH NEW. RECONNECT TO EXISTING TOILET EXHAUST DUCTWORK. CONTROLS TO MATCH EXISTING.

3. PROVIDE NEW VFD'S AND INSTALL IN THE ELECTRICAL ROOM. COORDINATE WITH ELECTRICAL CONTRACTOR TO RE-ROUTE THE POWER TO NEW LOCATION. PROVIDE NEW CONTROL WIRING IN CONDUIT FROM EXISTING MCQUAY MICRO CONTROLLER TO VFD'S FOR SPEED CONTROL AND FEEDBACK.

4. PROVIDE MANUFACTURER ROOF CAP ASSEMBLY FOR NEW FAN.

5. COORDINATE NEW EXHAUST FAN DUCT OPENINGS WITH ARCHITECTURAL PLANS.

1 09/07/2018 ISSUE FOR BID

Page 4: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

SCHEDULES

M0501

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

COMME...

SIGNATURE DATE

AIR BALANCE TECHNICIAN NAME AND COMPANY

AND/OR NFPA 99 (FOR OR's LABS, ETC.) AND THE ILLINOIS HOSPITAL LICENSING ACT.

I CERTIFY THAT THE AIR CONDITIONING AND VERIFICATION SYSTEMS HAVE BEEN TESTED AND BALANCED IN ACCORDANCE WITH THE PLANS AND SPECIFICATION, NFPA 90A/90B

NOTE: ACTUAL VALUES LISTED THAT ARE MORE THAN 10% DEPARTURE FROM DESIGN VALUES WITHOUT CLARIFICATION WILL NOT BE ACCEPTED.

- NEGATIVE EXCEEDS 10% OR 50 CFM (WHICHEVER IS GREATER) RETURN/EXHAUST CFM OVER SUPPLY CFM.

+ POSITIVE EXCEEDS 10% OR 50 CFM (WHICHEVER IS GREATER) SUPPLY CFM OVER RETURN/EXHAUST CFM.

= EQUAL WITHIN +/- 10% OF DESIGN CFM SUPPLY AND RETURN/EXHAUST.

PRESSURI...

TOTAL: 5052 6720 4775 1800

117A W.C. TOILET ROOM 52 468 50 0 100 -

116A NURSE STATION OFFICE 169 1521 125 125 0 =

113B STAFF TOILET TOILET ROOM 50 450 50 0 100 -

113A CHANGING ROOM STAFF LOCKER 20 160 50 50 0 =

100D CORRIDOR CORRIDOR 425 4037.5 325 100 0 =

100C CORRIDOR CORRIDOR 224 2128 100 0 0 =

125 WATER TREATMENT NA 317 4438 350 0 350 =

124 MECH NA 102 867 200 0 200 =

123 ELEC NA 118 1003 75 0 0 =

122 STORAGE STORAGE ROOM 114 1083 50 50 0 =

121 LAB WORKROOM 63 598.5 100 100 0 =

120 EQUIPMENT REPAIR NA 147 1396.5 150 150 0 =

119 CLEAN SUPPLY STORAGE ROOM 100 950 100 75 0 +

118 SOILED STORAGE STORAGE ROOM 100 950 120 0 150 -

117 PRIVATE PAT./ISOLATION PATIENT ROOM 132 1584 250 0 275 -

116 TREATMENT AREA PATIENT ROOM 862 10344 900 800 0 =

115 MED PREP WORKROOM 92 782 150 150 0 =

114 PAT. TOILET TOILET ROOM 40 320 0 0 100 -

113 STAFF LOUNGE LOUNGE 210 1680 350 350 0 =

112 JANITOR'S CLOSET NA 33 297 0 0 75 -

111 I.T. NA 62 496 300 300 0 =

110 DIR. OFFICE OFFICE 83 664 150 150 0 =

109 OFFICE OFFICE 75 600 125 125 0 =

108 MENS TOILET ROOM 103 824 200 0 225 -

107 WOMENS TOILET ROOM 103 824 200 0 225 -

106 EXAM ROOM EXAM ROOM 108 1026 75 75 0 =

105 RECEPTION OFFICE 71 674.5 100 100 0 =

104 SOCIAL WORKER OFFICE 101 959.5 100 100 0 =

103 DIETITIAN OFFICE 94 752 225 225 0 =

102 CONFERENCE OFFICE 212 1696 750 750 0 =

101 WAITING OFFICE 670 5360 1000 1000 0 =

ROOM

NUMBERROOM NAME ROOM USE

FLOOR AREA SQ.

FT.

SPACE

VOLUME CU.

FT.

SUPPLY RETURN EXHAUSTPRESSURE

RELATIONSHIPSUPPLY RETURN EXHAUST SUPPLY RETURN EXHAUST

ACTUAL # AIR

CHANGES PER HOUR

DESIGN CFM VAV MIN/MAX ACTUAL CFM VAV MIN/MAX % OF DESIGN

TO BE COMPLETED BY DESIGN ENGINEER TO BE COMPLETED BY TEST AND AIR BALANCE TECHNICIAN

IDPH VENTILATION SCHEDULE AIR BALANCING MATRIX IDPH NUMBER

6. CONTROL THROUGH THE BUILDING AUTOMATION SYSTEM (BAS).

5. EXISTING EXHAUST FAN TO REMAIN. 11. PROVIDE WITH BACKDRAFT DAMPER.

4. PROVIDE MOTORIZED DAMPER W/ ACTUATOR INTERLOCKED W/... 10. E.C. TO PROVIDE WALL SWITCH AND WIRE TO FAN.

3. PROVIDE WEATHER PROOF DISCONNECT. 9. EXISTING CONTROL THROUGH SPACE THERMOSTAT TO REMAIN.

2. PROVIDE WITH DIRECT DRIVE SPEED CONTROLLER. 8. EXHAUST FAN TO RUN CONTINUOUSLY 24/7.

1. PROVIDE VIBRATION ISOLATORS 7. EXISTING CONTROL THROUGH AN OCCUPANCY SENSOR VIA THE...

NOTES:

EF-6 STAFF 113 CEILING STAFF ROOM 250 CEILING MOUNTED 0.45 - - None 120/60/1 830 DIRECT 23.1 GREENHECK G-095-D 1,10,11

EF-5 ROOF TOILET ROOMS 550 ROOF MOUNTED 0.53 0.12 1/8 None 115/60/1 1,550 DIRECT 32 GREENHECK G-095-D 1,2,3,4,8

EF-4 ROOF PRIVATE/PAT. ISOLATION 375 ROOF MOUNTED 0.5 0.12 1/8 None 115/60/1 1,550 DIRECT 32 GREENHECK G-095-D 1,2,3,4,8

EF-3 ROOF SOILED UTILITY 150 ROOF MOUNTED 0.5 0.04 1/20 None 115/60/1 1,550 DIRECT 32 GREENHECK G-080-D 1,2,3,4,8

EF-2 ROOF WATER TREAMENT 350 ROOF MOUNTED 0.59 0.08 1/15 None 115/60/1 1,550 DIRECT 32 GREENHECK G-090-D 1,2,3,4,8

(E)TE-4 ROOF TOILET EXHAUST 100 ROOF EXHAUSTER 0.5 0.08 1/6 None 115/60/1 1,394 DIRECT 30 GREENHECK G-070-6 5,6

(E)TE-3 ROOF TOILET EXHAUST 75 ROOF EXHAUSTER 0.5 0.08 1/6 None 115/60/1 1,394 DIRECT 30 GREENHECK G-070-6 5,7

(E)EF-1 ROOF MECH ROOM 200 ROOF EXHAUSTER 0.5 0.08 1/6 None 115/60/1 1,394 DIRECT 30 GREENHECK G-080-6 5,9

IN. WC. BHP HP CONTROL V/HZ/PH RPM DRIVE LBS.

TAG LOCATION AREA SERVED CFM TYPE S.P. MOTOR WEIGHT BASED ON REMARKS

MOTOR FAN DATA UNIT

FAN SCHEDULE

6. EXISTING VAV BOX TO REMAIN. PROVIDE NEW THERMOSTAT AT LOCATION INDICATED ON PLANS.

5. SET AT CONSTANT AIR VOLUME INDICATED ON PLANS.

4. PROVIDE MANUFACTURER ACCESS DOOR OPTION UPSTREAM OF REHEAT COIL.

3. REFER TO PLANS FOR ACTUAL CFM REQUIREMENTS.

2. FACTORY INSTALLATION OF CONTROLLER AND ACTUATOR.

1. SPACE TEMPERATURE SENSOR PROVIDED BY CONTROLS CONTRACTOR.

NOTES: 46.5

VAV-16 350 350 0.5 12x8 6" 2.0 SCR 120/1/60 58 76 TITUS DESV 1,2,3

VAV-15 400 400 0.5 12x8 6" 3.0 SCR 120/1/60 58 82 TITUS DESV 1,2,3

VAV-14 350 350 0.5 12x8 6" 2.0 SCR 120/1/60 58 76 TITUS DESV 1,2,3

VAV-13 900 300 0.5 12x8 12" 5.5 SCR 408/3/60 58 116 TITUS DESV 1,2,3,4

VAV-12 200 75 0.5 12x8 4" 1.0 SCR 120/1/60 58 100 TITUS DESV 1,2,3,4

VAV-11 150 75 0.5 12x8 4" 1.5 SCR 120/1/60 58 121 TITUS DESV 1,2,3,4

VAV-10 250 125 0.5 12x8 6" 2.5 SCR 120/1/60 58 121 TITUS DESV 1,2,3,4

VAV-9 800 275 0.5 14x12 10" 4.0 SCR 208/1/60 58 104 TITUS DESV 1,2,3,4

(E)VAV-8 350 125 0.5 12x8 6" 2.5 SCR 120/1/60 58 121 TITUS DESV 3,6

VAV-7 300 150 0.5 12x8 6" 2.0 SCR 120/1/60 58 100 TITUS DESV 1,2,3,4

VAV-6 450 150 0.5 12x8 8" 3.0 SCR 120/1/60 58 121 TITUS DESV 1,2,3,4

VAV-5 600 200 0.5 12x8 8" 3.5 SCR 120/1/60 58 113 TITUS DESV 1,2,3,4

VAV-4 900 300 0.5 20x18 12" 5.5 SCR 408/3/60 58 116 TITUS DESV 1,2,3,4

(E)VAV-3 75 75 0.5 12x8 6" - - - 58 58 TITUS DESV 3

VAV-2 300 300 0.5 12x8 6" 2.5 SCR 120/1/60 58 84 TITUS DESV 5,6

VAV-1 1000 500 0.5 24x18 12" 6.0 SCR 408/3/60 58 96 TITUS DESV 1,2,3,4

MAX MIN IN W.G. INCHES INCHES KW CONTROL STEPS V/PH/HZ (%%DF) (%%DF)

TAG CFM PRESSURE SIZE (WxH) SIZE (DIA.) COIL MIN # OF POWER E.A.T. L.A.T. BASED ON REMARKS

PRIMARY AIRFLOW RANGE INLET OUTLET INLET REHEAT REHEAT REHEAT COIL

VARIABLE AIR VOLUME SCHEDULE

3. PROVIDE ELECTRIC HEATING COIL COMPLETE WITH MAGNETIC CONTRACTOR, HIGH TEMP CUTOUT WITH AUTOMATIC RESET, AND FAN MOTOR INTERLOCK.

2. PROVIDE HORIZONTAL CONCEALED UNIT COMPLETE WITH INLET AND OUTLET BOTTOM STAMPED LOUVER AND HIGH STATIC FAN MOTOR.

AND UNIT MOUNTED FAN SPEED SWITCH, CITY OF CHICAGO APPROVED DISCONNECT SWITCH.

1. PROVIDE COMPLETE WITHINLET AIR FILTER, BUILT-IN THERMOSTAT, BUILT-IN CONTROL TRANSFORMER,

NOTES:

(E) CUH-3 MECH ROOM 2.2 7.5 189 208 3 1 869.0 0.03 8.19 15 TRANE FORCEFLO 030 EXISTING

(E) CUH-2 FRONT VESTIBULE 5.7 19.4 300 208 3 1 1068.0 0.1 20.54 25 TRANE FORCEFLO 040 EXISTING

CUH-1 WATER TREATMENT 5.7 19.4 300 208 3 1 1068.0 0.1 20.54 25 TRANE FORCEFLO 040 MODEL D ALL

TAG LOCATION KW MBH CFM VOLT PHASE STAGES RPM HP MCA MROPD

HEATING ELEMENT DATA MOTOR TOTAL UNIT

MANUFACTURER MODEL REMARKS

CABINET UNIT HEATER

901 TO 1050 CFM - 18" NK 901 TO 1050 CFM - 18" NK

751 TO 900 CFM - 16" NK 751 TO 900 CFM - 16" NK

551 TO 750 CFM - 14" NK 551 TO 750 CFM - 14" NK

401 TO 550 CFM - 12" NK 401 TO 550 CFM - 12" NK

251 TO 400 CFM - 10" NK 251 TO 400 CFM - 10" NK

101 TO 250 CFM - 8" NK 101 TO 250 CFM - 8" NK

TAG "S1" 50 TO 100 CFM - 6" NK TAG "R1" 50 TO 100 CFM - 6" NK

4. PROVIDE WITH EXTENDED PLENUM UP TO 16 INCHES. 12-1/2" x 5-1/4" OVAL INLET CONNECTION TO BE 1" OFF THE TOP.

3. NO OPPOSED BLADE DAMPER UNLESS INDICATED ON DRAWINGS.

2. COORDINATE BORDER TYPE WITH ARCHITECTURAL.

1. REFER TO DRAWINGS FOR AIRFLOW REQUIREMENTS.

NOTES:

R-2 RETURN REGISTER 12" x 12" NO STEEL RECTANGULAR REGISTER, 35 DEG. FIXED DEFLECTION BLADES, 1/2" SPACING, O.B.D. TITUS MODEL 355FL 1,2,3

R-1 RETURN GRILLE 24" x 24" NO STEEL PERFORATED CEILING GRILLE, SQUARE NECK TITUS MODEL PAR 1,2

E-3 EXHAUST GRILLE 12" x 12" NO STEEL PERFORATED CEILING GRILLE, SQUARE NECK TITUS MODEL PAR 1,2

E-2 EXHAUST GRILLE 24" x 24" NO STEEL PERFORATED CEILING GRILLE, SQUARE NECK TITUS MODEL PAR 1,2

E-1 EXHAUST REGISTER 12" x 12" NO STEEL RECTANGULAR REGISTER, 35 DEG. FIXED DEFLECTION BLADES, 1/2" SPACING, O.B.D. TITUS MODEL 355FL 1,2,3

S-5 SUPPLY LINEAR 36" NO STEEL PLENUM SLOT DIFFUSER - 1 1/2" SLOT, 2 SLOT, 36" LONG TITUS MODEL TBDI-80 1,2,4

S-4 SUPPLY GRILLE 12" x 12" NO STEEL RECTANGULAR REGISTER, 35 DEG. FIXED DEFLECTION BLADES, 1/2" SPACING, O.B.D. TITUS MODEL 355FL 1,2,3

S-3 SUPPLY SQUARE 12" x 12" NO STEEL ARCHITECTURAL CEILING DIFFUSER, 12"x12" SQUARE FACE, ROUND NECK TITUS MODEL OMNI 1,2

S-2 SUPPLY LINEAR 48" NO STEEL PLENUM SLOT DIFFUSER - 1 1/2" SLOT, 2 SLOT, 48" LONG TITUS MODEL TBDI-80 1,2,4

S-1 SUPPLY SQUARE 24" x 24" NO STEEL ARCHITECTURAL CEILING DIFFUSER, 24"x24" SQUARE FACE, ROUND NECK TITUS MODEL OMNI 1,2

FACE AREA DAMPER FINISH

TAG SERVICE TYPE LENGTH OR BLADE MATERIAL/ TYPE BASED ON REMARKS

OPPOSED

REGISTER AND DIFFUSER SCHEDULE

1.) RELOCATE EXISTING SUPPLY AND RETURN FAN VFD TO THE ELECTRICAL ROOM. CONTRACTOR SHALL PROVIDE NEW CONTROL WIRING FROM

MCQUAY MICROTEC CONTORLLER TO VFD FOR SPEED CONTROL AND FEEDBACK. COORDINATE WITH MANUFACTURER AND SITE CONDITIONS

FOR PROTOCOL USED, WIRE SIZE AND TYPE. PROVIDE LOCAL DISCONNECT FOR ROOFTOP UNIT.

NOTES: UNIT IS PROVIDED WITH REFRIGERANT 407C PER U.S. GREEN BUILDING COUNCIL (USGBC) LEED REQUIREMENTS.1 30.1 225

AHU-1 199.9 164 500 400 78.1 64.5 53.5 63.5 58 118.2 6,100 1.5 3.22 1,125 4.1 7.5 22.3 5,370 0.75 628 1.2 1.5 4.8 2 1 4.2 1 14.7 124 91.4 110 208 3 8,200 McQUAY RPS

TOTAL SEN INPUT OUTPUT EDB EWB LDB LWB EDB LDB CFM ESP TSP RPM BHP HP FLA CFM ESP RPM BHP HP FLA QTY HP (EA) FLA (EA) QTY RLA (EA) LRA (EA) MCA MROPD VOLT PHASESUMMER WINTERTAG

COOLING CAP... HEATING CAP...DESIGN CONDITIONS (%%DF) SUPPLY AIR FAN RETURN AIR FAN CONDENSER FANS COMPRESSORS TOTAL UNIT ELECTRICAL WEIGH... MANUFACTURER

AND MODEL

EXISTING ROOF TOP UNIT SCHEDULE

1 09/07/2018 ISSUE FOR BID

Page 5: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

GENERAL NOTES:

EXISTING FACILITY CONTROL ARE INTEGRATED WITH HOSPITAL BUILDING AUTOMATION SYSTEM WHICH IS ALERTRON PLATFORM.

CONTRACTOR SHALL PROVIDE ALL NEW DDC CONTROLLERS, DEVICES, AND SENSORS ALONG WITH PROGRAMMING.

THE DDC SYSTEM SHALL BE FULLY CAPABLE OF IMPLEMENTING ALL CONTROL STRATEGIES AND CONTROL FUNCTIONS USING STAND ALONE DDC CONTROLLERS INTEGRATED INTO OVERALL BAS SYSTEM. LOSS OF COMMUNICATION BETWEEN CONTROLLERS OR FRONT END SHALL NOT PREVENT THE EQUIPMENT FROM OPERATING.

ALL CONTROL WIRING SHALL BE INSTALLED IN METAL CONDUIT. THE CONTRACTOR SHALL PROVIDE ALL CONTROL CONDUIT ROUGH-IN AS WELL AS ALL CONTROL WIRING, END-DEVICES, PROGRAMMING, START-UP AND TROUBLE SHOOTING, ETC. FOR A COMPLETELY FUNCTIONAL SYSTEM.

CONTRACTOR SHALL UPDATE ALL FRONT END GRAPHICS TO INCLUDE EXISTING AND NEW EQUIPMENT.

TEMPERATURE CONTROL

SYMBOLS

HS

TSP

THS

HS

WS

CO2

SD

C

R

SD

HS

AFMS

FM

CO

DP

AIR FLOW MEASURING STATION

CHLORINE SENSOR

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

DIFFERENTIAL PRESSURE TRANSMITTER

FLOW METER

SMOKE DETECTOR

REFRIGERANT SENSOR

TOTAL STATIC PRESSURE MONITOR / ALARM

TEMPERATURE AND HUMIDITY SENSOR

SENSOR / SWITCH

DUCT HUMIDITY SENSOR

HUMIDITY SENSOR / HUMIDISTAT

PS PRESSURE SENSOR

DUCT SMOKE DETECTOR

SS STATIC PRESSURE SENSOR

S

TH

THERMOSTAT OR TEMPERATURE SENSORT

T DUCT THERMOSTAT

COMBINED TEMPERATURE / HUMIDITY SENSOR

TEMPERATURE SENSORTS

BDP BUILDING DIFFERENTIAL PRESSURE SENSOR

DPT DIFFERENTIAL PRESSURE TRANSDUCER

OAT/OAH OUTSIDE AIR TEMPERATURE / OUTSIDE AIR HUMIDITY

BTU BRITISH THERMAL UNIT METER

CS CURRENT SENSOR

ANALOG OUTPUT

END SWITCHES

ANALOG INPUT

DIGITAL INPUT

DIGITAL OUTPUT

AO

AI

DI

DO

HUMIDITY SENSOR

WATER SENSOR

OCCUPANCY SENSOROS

SILICON CONTROL RECTIFIERSCR

THE BAS CONTRACTOR SHALL INTEGRATE EXHAUST FANS INTO THE DDC SYSTEM. FANS SHALL BE

PROGRAMMED TO OPERATE CONTINUOUSLY.

UPON SYSTEM START-UP, THE DDC SYSTEM SHALL COMMAND THE FAN ON.

UPON A MANUAL COMMAND TO DISABLE THE SYSTEM, THE FAN SHALL BE COMMANDED OFF AND A VISIBLE

INDICATION OF FAN-OFF SHALL BE INDICATED AT THE FRONT-END GRAPHICS.

PROVIDE ALARM TO DDC SYSTEM IF THE FAN IS COMMANDED ON BUT NO FAN STATUS IS INDICATED.

FOR INTERMITTENT EXHAUST FANS, OPERATION SHALL BE MANUAL. THE BAS CONTRACTOR SHALL PROVIDE

A CURRENT SENSOR AND PROVIDE FAN STATUS AT FRONT-END GRAPHICS. IN THE EVENT THAT NO CURRENT

IS INDICATED, INDICATE AN ALARM AT FRONT-END GRAPHICS.

CS DISUPPLY FAN STATUS

FLOWMETER

RH

C

T

VAV BOXDISCHARGE

AIR

DDC CONTROLLER

INTEGRATEDACTUATOR

PNEUMATICTUBING

PRIMARY AIR DAMPER

PRIMARY AIRFLOW

SPACE TEMPERATURE

VELOCITYPRESSURE

SENSOR

SUPPLY AIR BOX CONTROL:THE DDC CONTROLLER SHALL MODULATE THE VAV BOX DAMPER TO MAINTAIN SPACE

TEMPERATURE SETPOINT OF 72°F (ADJ.) BASED ON A SIGNAL FROM THE WALL TEMPERATURE

SENSOR. THE DAMPER SHALL MODULATE BETWEEN MAXIMUM AND MINIMUM SETPOINT.

WHEN THE DAMPER IS AT MINIMUM POSITION AND THE SPACE TEMPERATURE CONTINUES TO

DROP, THE DDC CONTROLLER SHALL BEGIN TO MODULATE THE ELECTRIC REHEAT COIL IN

UNISON WITH THE VAV BOX DAMPER UNTIL THE SPACE TEMPERATURE IS MAINTAINED OR THE

BOX REACHES IT'S MAXIMUM HEATING DAMPER POSITION. UPON AN INCREASE IN SPACE

TEMPERATURE, MODULATE SEQUENCE IN REVERSE.

IN UN-OCCUPIED MODE, THE DAMPER AND REHEAT COIL SHALL MODULATE TO MAINTAIN A

SPACE TEMPERATURE SETPOINT OF 65°F (ADJ.) WHEN OUTDOOR TEMP IS 55°F (ADJ.) OR

BELOW AND 80°F (ADJ.) WHEN OUTDOOR TEMP IS 56°F (ADJ.) OR ABOVE.

WHEN THE BUILDING IS IN SUMMER MODE, THE TERMINAL UNIT ELECTRIC REHEAT COIL SHALL

BE LOCKED-OUT AND DEACTIVATED EXCEPT FOR CONSTANT VOLUME BOXES.

ALARMS

IF THE SPACE TEMPERATURE FALLS 10°F (ADJ.) BELOW SETPOINT

PRIMARYAIR

DISCHARGE AIR TEMPERATURE

REHEAT COIL

AITS

AO

AO

AI

TS

AI

SCR

VAV VAV VAV VAV

EXISTINGDDC PANEL

24V BY TCC 24V BY TCC 24V BY TCC 24V BY TCC

NOTES:

THE ABOVE DDC SYSTEM ARCHITECTURE DIAGRAM IS FOR REFERENCE ONLY AND IS NOT

INTENDED TO REPRESENT A SPECIFIC WIRING REQUIREMENT. IT IS ONLY INTENDED TO

PROVIDE A GENERAL OVERVIEW.

THE RENOVATION SHALL CONTAIN ALL NEW CONTROLS FOR THE SYSTEM AND SHALL BE

INTEGRATED INTO THE EXISTING BUILDING CONTROL.

THE NEW CONTROL SYSTEM SHALL INCLUDE ALL NEW DDC SENSORS AND DEVICES ALONG

WITH PROGRAMMING. THE NEW BAS CONTROLS PROGRAMMING SHALL BE INCLUDED ON THE

FRONT END CONTROLS SYSTEM AND SHALL HAVE GRAPHICS ADDED FOR MONITORING AND

CONTROL OF SYSTEM POINTS.

THE CONTRACTOR SHALL PROVIDE ALL CONTROL CONDUIT ROUGH-IN AS WELL AS ALL CONTROL

WIRING, END DEVICES, PROGRAMMING, START-UP AND TROUBLE SHOOTING, ETC. FOR A COMPLETE

FUNCTIONAL SYSTEM.

WEB

EXISTING AHU

SMART REFRIGERATORS

24V BY TCC

REFER TO PLAN FOR EXACT QUANTITY OF EQUIPMENT AND TYPE.

MARCOR WATER TREATMENT EQUIP.

24V BY TCC

FLOWMETER

RH

C

T

VAV BOXDISCHARGE

AIR

DDC CONTROLLER

INTEGRATEDACTUATOR

PNEUMATICTUBING

PRIMARY AIR DAMPER

PRIMARY AIRFLOW

SPACE TEMPERATURE

VELOCITYPRESSURE

SENSOR

CAV BOX CONTROL:

PRIMARYAIR

DISCHARGE AIR TEMPERATURE

ELECTRIC REHEAT COIL

AITS

AO

AO

AI

TS

AI

SCR

ISOLATION ROOM SHALL BE PROVIDED WITH A DEDICATED CONSTANT VOLUME AIRFLOW BOX TO ENSURE THE ROOM REMAINS IN NEGATIVE PRESSURE. THE BAS CONTRACTOR SHALL PROVIDEA ROOM PRESSURIZATION MONITOR MODEL #CRC-RPM1, MANUFACTURER CRITICAL ROOM CONTROL. THE PRESSURE MONITOR SHALL BE INTEGRATED INTO THE BAS SYSTEM AND SHALL INCLUDEVISUAL DISPLAY FOR OBSERVATION OF SPACE PRESSURIZATION BY THE OCCUPANT.

THE DDC CONTROLLER SHALL MODULATE THE VAV BOX DAMPER TO MAINTAIN A CONSTANTAIRFLOW TO THE SPACE. THE AIRFLOW SHALL BE DETERMINED BY THE BALANCING CONTRACTORAND SHALL BE BALANCED AGAINST THE CONSTANT VOLUME EXHAUST IN THE TOILET ROOM.

SPACE TEMPERATURE SETPOINT OF 72°F (ADJ.) BASED ON A SIGNAL FROM THE WALL TEMPERATURE SENSOR SHALL BE MAINTAINED BY THE DDC CONTROLLER MODULATING THE ELECTRIC REHEAT COIL.

ASSOCIATED TOILET EXHAUST FAN STATUS SHALL BE DETERMINED BY THE DDC SYSTEM. WHEN THE TOILET EXHAUST FAN IS NOT OPERATIONAL, THE ISOLATION ROOM CAV BOX SHALL CLOSE.UPON RECEIVING AN EXHAUST FAN ON SIGNAL, THE CAV SHALL BE MODULATED TO AIRFLOWSETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:• VAV BOX ACTUAL AIRFLOW EXCEEDS SETPOINT BY 10% (ADJ.)

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

CONTROL DIAGRAMS

M0601

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

2EXHAUST FANS

1SUPPLY AIR UNIT WITH ELECTRIC REHEAT

4DDC SYSTEM ARCHITECTURE

NOT TO SCALE3

ISOLATION ROOM CONTROL WITH ELECTRIC REHEAT

1 09/07/2018 ISSUE FOR BID

Page 6: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

MIN 2 DIAMETERS

STRAIGHT DUCT

MEDIUM PRESSURE SUPPLY DUCT

TERMINAL UNIT

ELECTRIC REHEAT COIL

DUCT TRANSITIONAS REQUIRED(MAX 15° ANGLE)

ACCESS PANEL

FLEXIBLE DUCT

2'-0" MAX &30° MAX OFFSET

CONICAL DUCT FITTING

SUPPLY DUCT

NOTES:

1. PROVIDE ACCESS DOOR(S) FOR COIL CLEANING UPSTREAM &

DOWN STREAM OF REHEAT COIL.

2. INLET DUCT SIZE TO MATCH TERMINAL. INCREASE SIZE 2INCHES FOR DISTANCES FROM MAIN OVER 5'-0".

RECTANGULAR SUPPLY TEERECTANGULAR SUPPLY TEESPLITTER

> 84"

60"-84"

36"-60"

24"-36"

12"-24"

< 12"

WIDTH

VANE SCHEDULE

RECTANGULAR TO ROUND

3

6

5

4

VANESNO. OF

1

2

RECTANGULAR DUCT SUPPLY

VD

RECTANGULAR DUCT SUPPLY

SPLITTER

RECTANGULAR DUCT SUPPLYBRANCH TAKE-OFF

VD

BRANCH TAKE-OFF

VD

RECTANGULAR DUCT SUPPLYBRANCH TAKE-OFF

SPLITTER

BRANCH TAKE-OFF

VD

SHORT RADIUS ELBOW WITH ONE VANE(S)

STANDARD RADIUS ELBOW

R SHALL EQUAL OR BEGREATER THAN W.

ROUND TO RECTANGULAR

15° MAX.

15° MAX.

WR

30° MAX.

TRANSITION PIECE

WR

1. PROVIDE STANDARD RADIUS ELBOWS WHEN POSSIBLE - SHORT RADIUS WHERE REQUIRED2. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED & FASTENED AS RECOMMENDED BY SMACNA.3. NO SQUARE OR RECTANGULAR HEEL ELBOWS SHALL BE ALLOWED.

1. IF R IS LESS THAN W, THEN FULL ARC TURNING VANE(S) SHALL BE PROVIDED, SEE SCHEDULE BELOW.

2. INSIDE BEND MAY BE SQUARE FORW > 12", NO SQUARE HEELS PERMITTED.

NOTES

NOTES

VOLUMEDAMPER

DUCT

CEILING AIRDEVICE

1 x DUCT DIA. MIN.

FLEXIBLE DUCT 5'-0"MAX. LENGTH, 90°

MAX. OFFSET SAMESIZE AS DIFFUSER

NECK (TYP.)

AIR CUSHION 1 1/2

TIMES NECK ∅ (MIN.)

METAL DRAW BAND

CONICAL TAKE-OFF FITTING

45° TAKE-OFF

VOLUMEDAMPER

DUCT

1 x DUCT DIA. MIN.

FLEXIBLE DUCT 5'-0"MAX. LENGTH, 90°

MAX. OFFSET SAMESIZE AS DIFFUSER

NECK (TYP.)

ROUND DUCT

CEILING AIRDEVICE

CONICAL BELLMOUTHOR MITERED RECT.TO ROUND TAKE-OFFFITTING

METAL DRAW BAND

FLEX

VOLUMEDAMPER

T-BAR GRID

CEILING TILE

LONG RADIUS SHEETMETAL ELBOW

FLEXIBLE DUCT 5'-0"MAX. LENGTH, 90° MAX.OFFSET SAME SIZE ASDIFFUSER NECK (TYP.)

CONICAL BELLMOUTH ORMITERED RECT. TO ROUNDTAKE-OFF FITTING

METAL DRAW BAND

DUCT

CEILING AIRDEVICE

VOLUME DAMPERROUND

DUCT

1 x DUCTDIA. MIN.

CONICAL BELLMOUTHOR MITERED RECT.

TO ROUNDTAKE-OFF FITTING

METALDRAWBAND

DUCT

VOLUMEDAMPER

FLEXIBLE DUCT 5'-0"MAX. LENGTH, 90°

MAX. OFFSET SAME SIZEAS DIFFUSER NECK (TYP.)

1 x DUCTDIA. MIN.

SQUARE ORRECTANGULARLINED PLENUM

CEILING AIRDEVICE

RECTANGULARDUCT

1. SPIN COLLARS SHALL NOT BE PERMITTED.2. SPECIAL CONDITIONS THAT CAN NOT MEET ONE OF THESE STANDARDS SHALL BE

BROUGHT TO THE ENGINEER'S ATTENTION ON A CASE BY CASE BASIS.3. DETAILS ILLUSTRATE INSTALLATION WITH ROUND NECK DIFFUSERS AND DUCTS.

SQUARE OR RECTANGULAR NECK DIFFUSERS AND DUCTS SHALL BE SIMILAR.4. FLEXIBLE DUCTWORK MAY NOT BE USED IN PLACE OF A 90° ELBOW.5. NO LINED DUCTWORK OR PLENUM BOOTS.

NOTES

STRAP HANGER TRAPEZE HANGER

WASHER & NUT

40" MAX.

C-CLAMP (TYP.)

NOTE:1. NO POP UP RIVETS ALLOWED, USE SELF-TAPPING SHEETMETAL SCREWSONLY

HANGER RODS HANGER RODS

SUPPLEMENTAL STEELOR

BUILDING STRUCTURE

1'=0" MIN.

1'=0" MIN.

REFER TO PLAN FORSIZE OF GRILLE ORREGISTER

FINISHED CEILING

AIR TRANSFER BOOT

FIRE WALL

FIRE DAMPER

(SEE DETAIL)

ELEVATION

AIR FLOW

ROOM WITH

FINISHED CEILING

NOTES:

1. FOR CONSTRUCTION WITH INSULATION ABOVE ROOF SLAB, DECK,ETC. SUPPORT CURB DIRECTLY ON ROOF STRUCTURE.

2. COORDINATION INSTALLATION OF ROOF CURB WITHLANDLORD'S ROOFING CONTRACTOR TO MAINTAIN WARRANTY.

3. PROVIDE HINGE & RESTRAINT CABLE KIT FOR DAMPER ACCESS.

14"

EXISTING ROOF

EXHAUST FANSEE SCHEDULE FORCAPACITY & MFG. DATA

FASTEN FAN TO CURB WITHS.S. LAG SCREW & WASHERSMINIMUM (2) PER SIDEPREFABRICATED ROOF CURBWITH BUILT-IN CANT, 12"HIGH MINIMUM

PACK & SEALANNULAR SPACE

DUCT

16X16 ACCESS DOOR

DAMPERSEE SCHEDULE

FOR TYPE REQUIREMENT

MINIMUM1"

CLEARANCE

ROOFING UP& OVER CURB

COUNTERFLASHING

NEOPRENE

GASKET

3" MIN. 3" MIN.

WALL

DUCT ACCESS PANEL (TYP.)

BREAK-AWAY

DUCT/SLEEVE

CONNECTION

DUCT

DAMPER SLEEVE. SLEEVE GAUGEMUST BE EQUAL TO OR GREATERTHAN THE DUCT CONNECTION TO IT.

MINIMUM 1/4"CLEARANCE

1" MIN. OVERLAP

(FOUR SIDES)

1 1/2" x 1 1/2" x 16 GAGEMOUNTING ANGLES FOR

DAMPERS50"x60" OR SMALLER. 14 GAGE

ANGLE FOR LARGER DAMPERS.

MOUNTING ANGLES FASTENED TO

THE DAMPER SLEEVE WITH BOLTS,

SCREWS, OR WELDING MAX. 6" O.C.

EXISTING WALL FIELD VERIFY CONSTRUCTION.

SHEET METAL WALL SLEEVE.EXTEND SLEEVE TO ANAPPROPRIATE LENGTH SUCHTHAT DUCT CONNECTION CANBE MADE.

ANCHOR

SILICONE SEALANT. APPLYCONTINUOUS BEAD AROUNDPERIMETER OF LOUVER.

ANGLE CLIP AROUND INSIDE OF LOUVER

1/2"x1/2" GALVANIZED WIRE MESH INSIDE OF LOUVER.

LOUVER (SEE PLANS FOR SIZES)

SHEET METAL FLASHING

DUCTWORK TOEQUIPMENT

PROVIDE BURGLAR BARS ON ALL LOUVERS LARGER THAN 12"X12"

PIPE OR DUCT

INSULATION SHALL TERMINATEAT EACH SIDE OF SLEEVE

FULL HEIGHT RATED PARTITION

EXTENDED FLOOR SLEEVE - 1/4" EXPOSED AREASAND 2" WET AREAS

VAPOR BARRIER (WHERE REQUIRED) AND INSULATIONTO BE FITTED TIGHT TO SLEEVE. SEAL WITH CONTINUOUSBEAD OF NON-HARDENING CAULKING

FILL ENTIRE VOID BETWEEN SERVICE AND OPENINGWITH CAULK AND SEALANT AS SPECIFIED

SLEEVEWALL

FLOOR

SLEEVE WHERE REQUIRED

BLOCK WALL

100 LEVEL+0' - 0"

T.O. STEEL+17' - 0"

Level 5+9' - 8"

100 LEVEL0'-0"

ROOF LEVEL20'-0"

Level 59'-8"

8"Ø SA

10x20 SAT.O. STEEL

+17' - 0"

2

Level 5+9' - 8"

Level 59'-8"

20x14 RA

14x14 SA

14x12 RA

VOLUME DAMPERIN VERTICALR-1

900

NOTE: TYPICAL RETURN AIR DIFFUSER CONNECTION TO MAIN RETURN DUCT IN TREATMENT ROOM, CONFERENCE 102

ROUND RAIN CAP

FLUE - SIZE ASINDICATED ON PLANS

STORM COLLAR

SUPPORT PLATE

SHEET METAL THIMBLESEAL WEATHERTIGHT TOROOF CONSTRUCTION

ROOF

ROOF FLASHING

VERIFY HEIGHTAS REQUIREDWITH ALLAPPLICABLECODES ADJUSTABLE TALL CONE

ROOF FLASHING

1ST FLOOR

DIRT LEG

EQUIPMENT

SHUT-OFF VALVE

PRESSURE REGULATOR PIPE VENT OUTLET WITH DOWNTURN ELBOW

UNIONINTERIOR EXTERIOR

SEAL ANNULAR SPACE BETWEEN PIPE AND SLEEVE WITH THUNDERLINE "LINK-SEAL" OR EQUAL.

SCH 40 GALV STEEL SLEEVE SECURED TO PARTITION

PIPE WITH OR WITHOUT INSULATION. TERMINATE INSULATION EACH SIDE OF "LINK-SEAL".

SCH 40 GALV STEEL SLEEVESECURED TO PARTITION

INSULATIONAND JACKET PIPE WITH OR WITHOUT

INSULATION TERMINATE INSULATION ON EACH SIDE OF "LINK-SEAL".

ESCUTCHEON PLATEWHERE EXPOSED.(TYPICAL EACH SIDE)

SEAL ANNULAR SPACE BETWEEN PIPE AND SLEEVE WITH THUNDERLINE "LINK-SEAL" OR EQUAL.

NOTES:1. TYPICAL FOR NON-INSULATED PIPING AND CONDUIT.2. TYPICAL FOR MASONRY OR CONCRETE WALL.3. FOR WALL PENETRATION WITH FIRE RATINGS GREATER THAN (1) HOUR, USE THUNDERLINE "PYRO-PAC"

SEALS OR EQUAL.4. WHERE PIPING EXPOSED AT FINISHED WALL, FLUSH MOUNT SLEEVE, AND PROVIDE AN ESCUTCHEON

PLATE.

INTERIOR EXTERIOR

INTERIOR

PIPE WITH OR WITHOUT INSULATION

CAULK AND SEAL ANNULAR SPACE BETWEEN PIPE AND SLEEVE

NOTES:1. TYPICAL FOR NON-INSULATED PIPE AND CONDUIT.2. ALL CAULKING AND SEALANT SHALL BE FIRE RATED (SEE

SPECIFICATIONS).3. WHERE PIPING IS EXPOSED AT FINISHED WALL, FLUSH MOUNT

SLEEVE AND PROVIDE AN ESCUTCHEON PLATE.

SCH 40 GALV STEELSLEEVE SECURED TOPARTITION

T.O. STEEL+17' - 0"

Level 5+9' - 8"

Level 59'-8"

6x6 SA 6x6 SA

16x10 SA

S-1100

S-1100

EXISTING BAR JOIST

INSULATED SUPPLYAIR DUCT

8x8 SA

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

DETAILS

M0701

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

NONE1

VAV BOX W/ REHEAT

NONE7

TYPICAL DUCT DETAIL

NONE3

TYPICAL AIR DEVICE (INLET/OUTLET) INSTALLATION DETAIL

NONE5

DUCT HANGER DETAIL

NONE4

AIR TRANSFER TO SIDEWALL GRILLE DETAILNONE

2ROOF EXHAUST FAN DETAIL

NONE8

TYPICAL FIRE DAMPER IN WALL1/8" = 1'-0"

6LOUVER ASSEMBLY DETAIL

NO SCALE9

DUCT OR PIPE WALL AND FLOOR PENETRATION DETAIL1/4" = 1'-0"

10DUCTWORK ROUTING AT EXISTING HEADER (TYPICAL)

1 09/07/2018 ISSUE FOR BID

1/4" = 1'-0"11

RETURN DIFFUSER IN TREATMENT ROOM

1/8" = 1'-0"13

FLUE VENT AND FLASHING DETAILNO SCALE

14GAS PIPING CONNECTION EQUIPMENT DETAIL

1/8" = 1'-0"15

PIPE PENETRATION THRU EXTERIOR WALLS1/8" = 1'-0"

16PIPE PENETRATION THRU INTERIOR WALLS

1/4" = 1'-0"12

SUPPLY AIR DUCT ROUTING BETWEEN JOISTS

Page 7: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

T

T C T T

T

T CT C

?

?

?

T

321

A

B

C

D

36x18

RA

(E) 12x12 EA UPTO TE-1

18x18 SA(E)

(E) TRANSFER AIR 200CFM

2

2

21

2

2

2

2

2

(E) GAS METER & REGULATOR

5

5

4

6(E) GAS LINE UP TO AHU-1

77

24x18 S

A(E

)

16"Ø SA (E)

18x18 SA(E)

6"Ø SA

10x10 (E)

8

(E)VAV

4

(E)VAV

3

(E)VAV

2

(E)VAV

1

(E)VAV

5

(E)VAV

6

(E)VAV7

(E)VAV

2

(E)H1

(E)H

2

(E)CUH

1

CUH

3

(E)CUH

(E) 12x12 EA UPTHRU ROOF TO EF-1

36x18 RA UP TO AHU-1

1

(E)AC

VAV-5VAV-6

VAV-7

CUH-2

(E) VAV-3

12x12 TOILET EXUP THRU ROOF

TO TE-2

12x12 TOILET EXUP THRU ROOF TO TE-4

12x12 TOILET EXUP THRU ROOF TO TE-3

8 (E)CUH-3

9

10

(E) GAS LINE UP TO AHU-1

6

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

AS

SS

AJG

LEVEL 01 - HVAC DEMOLITION

PLAN

MD101

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

1/4" = 1'-0"1

LEVEL 01 - HVAC DEMOLITION PLAN

GENERAL NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL VENTILATION LAYOUTS PRIOR TO STARTING DEMOLITION.

B. VENTILATION PLAN SHOW BASED-OFF OF EXISTING AS-BUILT DRAWINGS AND GENERAL SITE OBSERVATIONS.

NOTES :

1. EXISTING VAV BOX TO REMAIN. DISCONNECT AND REMOVE ALL SUPPLY DUCTWORK, DIFFUSERS AND ASSOCIATED ACCESSORIES DOWNSTREAM OF VAV BOX AS INDICATED.

2. EXISTING VAV BOX TO BE DEMOLISHED. DISCONNECT AND REMOVE DUCTWORK AND ACCESSORIES FROM UPSTREAM AND DOWNSTREAM OF THE BOX. DISCONNECT AND REMOVE ASSOCIATED DIFFUSERS AND CONTROLS.

3. DISCONNECT AND REMOVE EXISTING RETURN DUCTWORK, DIFFUSERS AND ALL ACCESSORIES AS INDICATED.

4. EXISTING CABINET UNIT HEATER TO BE DEMOLISHED. DISCONNECT AND REMOVE ALL ASSOCIATED DUCTWORK, DIFFUSERS AND CONTROLS.

5. EXISTING CABINET UNIT HEATER TO REMAIN. REPLACE EXISTING DIFFUSERS WITH NEW.

6. EXISTING GAS SERVICE SERVING AIR HANDLING UNIT ONLY (500 MBH). LOAD OF 120 MBH FOR WATER HEATER IS ADDED TO THE SYSTEM. UPGRADE SERVICE AS REQUIRED TO HANDLE TOTAL LOAD OF 720 MBH. REPLACE EXISTING GAS PIPE WITH 2" LINE FROM THE GAS METER UP TO THE LOCATION INDICATED.

7. EXISTING HUMIDIFIER TO REMAIN.

8. RELOCATE EXISTING THERMOSTAT FOR VAV-3 TO THE ELECTRICAL ROOM.

9. DEMOLISH EXISTING AIR COMPRESSOR AND ALL ASSOCIATED PIPING AND ACCESSORIES. DEMOLISH HOUSEKEEPING PAD AND PATCH FLOOR TO MATCH EXISTING.

10. REMOVE EIXSTING RETURN AIR REGISTER. PATCH WALL TO MATCH EXISTING 2-HOUR FIRE RATING OF THE ELECTRICAL ROOM.

1 09/07/2018 ISSUE FOR BID

Page 8: M0001 - Cook County Health...GENERAL NOTES DEMOLITION NOTES A/C AIR CONDITIONING A/E ARCHITECT/ENGINEER AAV AUTOMATIC AIR VENT (VALVE) ABV ABOVE ACCU AIR -COOLED …

4

(E)TE

3

(E)TE

1

(E)TE

2

(E)TE

1

(E)AHU

2

3

1 1

4

Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.

This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.

Not published - All rights reserved.

No. Date Issue

Sheet Name

Drawing No.

Project Number

Drawn

Checked

Proj. Arch./Eng.

Project Name

Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.

Department of Capital Planning & Policy

Bureau of Asset Management

Checker

Author

Approver

ROOF - HVAC DEMO PLAN

MD102

Provident Hospital - Renal

Dialysis Center

430 East 51st PlaceChicago, Illinois 60615

15849

1 09/07/2018 ISSUE FOR BID

1/4" = 1'-0"1

ROOF - DEMO HVAC DUCTWORK PLAN

GENERAL NOTES:

A. MECHANICAL CONTRACTOR SHALL COORDINATE ALL REQUIRED SYSTEM SHUT-DOWNS IN ORDER TO ISOLATE THE BUILDING FROM ACTIVE SERVICES.

B. INFORMATION ON EXISTING SYSTEMS SHOWN ON THESE PLANS IS BASED OFF OF ORIGINAL DESIGN DRAWINGS AND LIMITED FIELD SURVEY OF EXISTING CONDITIONS. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO COMMENCING WORK AND REPORT ANY DISCREPANCY TO THE A/E PRIOR TO DEMOLITION .

NOTES:1. EXISTING EXHAUST FAN TO REMAIN.

2. EXISTING TOILET EXHAUST FAN (E)TE-1 TO BE REPLACED WITH NEW. DISCONNECT AND REMOVE FAN AND PREPARE FOR NEW FAN RECONNECTION TO EXISTING DUCTWORK.

3. EXISTING TOILET EXHAUST FAN (E)TE-2 TO BE REMOVED COMPLETE. REMOVE ASSOCIATED DUCTWORK AND ACCESSORIES. COORDINATE PATCHING OF DUCT PENETRATION THRU BUILDING STRUCTURE WITH ARCHITECTURAL.

4. EXISTING SUPPLY AND RETURN FAN VFD'S TO BE REPLACED WITH NEW AND RELOCATED TO THE ELECTRICAL ROOM (TOTAL - 2VFD'S). CONTRACTOR SHALL PROVIDE NEW CONTROL WIRING FROM MCQUAY MICROTEC CONTROLLER TO VFD FOR SPEED CONTROL AND FEEDBACK. COORDINATE WITH MANUFACTURER AND SITE CONDITIONS FOR PROTOCOL USED, WIRE SIZE AND TYPE.