www.lsis.biz
GL-A,B / GL-E,F
Low-Voltage Power Centers
We also provide Total Solutionsthat encompass customizeddesigns and more advancedtechnology, as well as efficientproduction and installation, andhighly accurate testing andanalysis of power equipment.
2
LS GL-type Power Center is designed for the low-voltage equipmentused in the power plant and LV distribution systems. It meets Low Voltage Switchgear Standards such as JEM-1265 andIEC60439, 60158 so as to be used in various industrial sectors.
In response to the high tech world, the new Power Center!
C O N T E N T S
Features 3GL-A, B type Power center 6GL-E, F-type Power center 9GL-type specifications/Ratings 12Ratings of Metasol Series Air Circuit Breakers 14Ratings of Susol Series Air Circuit Breakers 16GL-type configuration 18
LS Low Voltage Power Center 3
GL type Power Center Features
Basic type A : 3∅3W Space saving typeB : 3∅4W Space saving typeE : 3∅3W Univasal typeF : 3∅4W Univasal type
GL AType numbering
An innovative next-generation solutions through the state-of-the-art technology, New concept low-voltage load centers to improve the environment and loss
4
Options responing to power plants and power distribution systems areavailable. In addition the special housing to protect against dust andother contaminants such as insects and other external environment arealso available as an option. Various options are provided to conform tointernational standards (IEC, ANSI, BS standard).
ACB's front panel and internal protection cover increase the operator safety evenin opening the front door.
GL-A, B type GL-E, F type
Space Saving TypeCable Cable Cable Cable
Universal Type
Main cable is rear accessible and control cable is front accessible for theworkability of installation and checking.
Responding to the era of the electronics the digital device is used for integratedinstrumentation, monitoring and control. It functions the transducer features suchas current, voltage, power, energy, reactive power, reactive power, power factorand frequency which enable the interface with other facilities. (4-20mA)
Conventional Power Center
GL type Power Center
ACB
Providing compact size resulting in reduced floor space requirements
Safety feature
ACB with electronics technology
Electronic control circuit
Reduced floor space
Consideration for workability
Various options
A standard feature of the breaker, ACB is the digital trip unit that provides circuitprotection, instrumentation, display and monitoring functions which meet thesystem requirements with a high level of reliability. In addition, other types ofbreakers such as economic or premium series are also available.
GIMAC-IV
LS Low Voltage Power Center 5
■ACB up to 3200AF applicable■Bus Duct applicable■Can be aligned with 1000kVA dry type Transformer■Can be aligned in case of MCCB as feeder
GL-A, B Power Center
Customer satisfaction through quality and service.World-class products From LSIS.
6
Panel type Equipment Rating Standard enclosure, (W x H x D, mm)
Transformer Dry or Cast resin type 1,000kVA Max. 2,200max.×2,300×1,400
MCCB MCCB 50AF~600AF (600~1,000)×2,300×1,400
Condenser Condenser + Series Reactor 200kVA Max. 800max.×2,300×1,400
Note 1. Continuous current ratings of breakers must be derated for ambient temperatures above 40℃. Please contact us.2. Please contact us.if external withdraw cable length is over 325mm2×2 per phase
Circuit ACB type ACB Rated Number of Standard enclosure
System Metasol(N Type) Metasol(S Type) Susol Current(A) Stack (W x H x D, mm)
AN-06D AS-06D AH-06D/E 630
AN-10D AS-10D AH-10D/E 1,000700×2,300×1,200
AN-13D AS-13D AH-13D/E 1,2502
3∅∅3W AN-16D AS-16D AH-16D/E 1,600
AN-20E AS-20D/E AH-20D/E 2,000800×2,300×1,200
AN-25E AS-25E AH-25E 2,500
AN-32E AS-32E AH-32E 3,200 1 800×2,300×1,200
AN-06D AS-06D AH-06D/E 630
AN-10D AS-10D AH-10D/E 1,000700×2,300×1,400
AN-13D AS-13D AH-13D/E 1,250
3∅∅4W AN-16D AS-16D AH-16D/E 1,600 2
AN-20E AS-20D/E AH-20D/E 2,000800×2,300×1,400
AN-25E AS-25E AH-25E 2,500
AN-32E AS-32E AH-32E 3,200 1,000×2,300×1,400
Enclosure size
Panel size suitable for alignment with GL-A, B type Power Center
LS 3.6 / 7.2kV ~ 12kV Switchgear 7
GL-A, B Power Center
System application
Skeleton
Alignment
Structures
8
Structures■Lining up suitable for functions and statistics■Aligning with panels of TR, MCCB or even
medium voltage switchgears
GL-E, F Power Center
A stable power supply and maximize energy efficiencythrough a variety of industrial electrical technologies.
LS Low Voltage GL-E, F Power Center 9
Note 1. Continuous current ratings of breakers must be derated for ambient temperatures above 40℃. Please contact us.2. Enclosure Size may change for special structure specifications , so please contact us.3. Please contact us.if external withdraw cable length is over 325mm2×2 per phase .
Panel type Equipment Rating Standard enclosure, (W x H x D, mm)
Transformer Dry or Cast resin type1,500kVA Max. 2,400Max.×2,300×1,600
2,500kVA Max. 2,800Max.×2,500×1,800
MCCB MCCB 50AF~1200AF (600~1,000)×2,300×1,600
Condenser Condenser + Series Reactor 400kVA Max. 1,000Max.×2,300×1,600
Enclosure size
Panel size suitable for alignment with GL-E, F type Power Center
GL-E, F Power Center
10
Circuit ACB type ACB Rated Number of Standard enclosure
System Metasol(N Type) Metasol(S Type) Susol Current(A) Stack (W x H x D, mm)
AN-06D AS-06D AH-06D/E 630
AN-10D AS-10D AH-10D/E 1,000
AN-13D AS-13D AH-13D/E 1,250
AN-16D AS-16D AH-16D/E 1,600 700×2,300×1,600
3∅∅3WAN-20E AS-20D/E AH-20D/E 2,000
AN-25E AS-25E AH-25E 2,500
AN-32E AS-32E AH-32E 3,200
- AS-40E/F/G AH-40E/G 4,000 1,000×2,300×1,800~2,000
- AS-50F/G AH-50G 5,000 1,100×2,300×1,800~2,000
- AS-63G AH-63G 6,300 1,300×2,300×1,800~2,000
AN-06D AS-06D AH-06D/E 630
AN-10D AS-10D AH-10D/E 1,000700×2,300×1,600
AN-13D AS-13D AH-13D/E 1,250
AN-16D AS-16D AH-16D/E 1,600
3∅∅4WAN-20E AS-20D/E AH-20D/E 2,000
900×2,300×1,600AN-25E AS-25E AH-25E 2,500
AN-32E AS-32E AH-32E 3,200 1,000×2,300×1,600
- AS-40E/F/G AH-40E/G 4,000 1,200×2,300×1,800~2,000
- AS-50F/G AH-50G 5,0001,300×2,300×1,800~2,000
- AS-63G AH-63G 6,300
2
2
1
1
System application
Skeleton
Alignment
Structures
LS Low Voltage Power Center 11
Item Standard Specifications Special SpecificationsApplicable Standards JEM 1265 and IEC 60439
GeneralClass JEM 1265 Class 3 JEM 1265 Class F
SpecificationsInstallation Environment Altitude 1,000m Max. Temperature -5℃~40℃ indoor Rated operating voltage 690VRated insulation voltage 1,000V
Circuit System 3-phase 3-wire / 3-phase 4-wireRatings
Rated current 630 ~ 6300AFrequency 50 / 60 Hz
Control circuit voltage DC 100 / 110VDoor 2.3mm 3.2mm
Enclosure Thickness Side Plate 1.6mm 2.3mmTop & Bottom Plate 1.6mm 2.3mm
Panel Exterior 5Y 7/1Specified
by CustomerPainting Instruments and relays N 1.5
Material Acrylic Resin
Nameplate Color Character Black (inside carved) SpecifiedBackground color Milk white by Customer
Material CopperGrounding Bus bar Size 3t × 25mm
Installation location Lower
Material Horizontal busbar CopperVertical busbar Copper
Plating for main busbars connections Ag platingFrom the left R.S.T.N
AC From the top R.S.T.N.
Phase array From the front R.S.T.N.From the left N.P.
Bus bar DC From the top P.N.From the front P.N.
R-phase Red
AC S-phase White
Phase array T-phase BlueN-phase Black
DC P-phase RedN-phase Blue
Type Control KIV or IVMain KIV or IV Specified
Size Control 1.25mm2 by CustomerCable Main 3.5mm2 over
Control Gray SpecifiedColor Main Black by Customer
Ground Green
Specifications
GL type Specifications & Ratings
12
Floor plans, standard
LS Low Voltage Power Center 13
Ratings of Metasol Series Air Circuit Breakers
14
Type
Ampere frame (AF)
Rated current(A) (In max) at 40℃℃
Setting current (A) Control trip relay ( ... ×× In max)
Rated current of neutral pole (A)
Rated insulation voltage(V) (Ui)
Rated operating voltage(V) (Ue)
Rated impulse withstand voltage (kV) (Uimp)
Frequency (Hz)
Number of poles (P)
Rated breaking capacity (kA sym)IEC 60947-2
220V/230V/380V/415V
AC 50/60Hz (Icu)KS C 4620
460V/480V/500V
550V/600V/690V
Rated service breaking capacity (kA) (Ics) ... %××Icu
Rated making capacity (kA peak)IEC 60947-2
220V/230V/380V/415V
AC 50/60Hz (Icm) KS C 4620
460V/480V/500V
550V/600V/690V
Rated short-time 1 sec
withstand current (kA) (Icw) 2 sec
3 sec
Operating time (ms) Maximum total breaking time
Maximum closing time
Life cycle (time) Mechanical
Electrical
Connections Draw-out / Fixed Horizontal connection
Vertical connection
Front connection
Mixed connection
Weight (kg) Draw-out type Main body Motor charging type
(3P/4P) (With cradle) Manual charging type
Cradle only
Fixed type Motor charging type
Manual charging type
External dimensions (mm) Draw-out 3P
(H××W××D) type 4P
Fixed type 3P
4P
Trip relay
Certificate & Approval
Marine clasiflcation* Refer to trip relay specification. ** �: Standard, �: Option
※ Life time means not guarantee, but limitation.Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee
H
WD
*
**
AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D
630 800 1000 1250 1600 2000
200 400
400 630 1000 1250 1600 2000
630 800
(0.4 ~ 1.0) × In max
400400
630 1000 1250 1600 2000630
800
1000
690
12
50/60
3/4
65 70
65 70
50 65
100% 100%
143 154
143 154
105 143
50 65
42 55
36 50
40
80
20,000
5,000
� -
� �
� -
� -
63/74 70/85
61/72 68/83
29/32 33/40
34/44 38/47
32/42 36/45
430×334×375
430×419×375
300×300×295
300×385×295
N, A, P type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
LS Low Voltage Power Center 15
AS-20E AS-25E AS-32E AS-40E AS-50F AS-40G AS-50G AS-63G
2000 2500 3200 4000 4000 5000 4000 5000 6300
630, 800
1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
(0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max
630, 800
1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
1,000 1000 1,000
690 690 690
12 12 12
50/60 50/60 50/60
3/4 3/4 3/4
85 100 120
85 100 120
85 85 100
100% 100% 100%
187 220 264
187 220 264
187 187 220
85 85 100
75 75 85
65 65 75
40 40 40
80 80 80
15,000 10,000 10,000
5,000 2,000 2,000
� � � �
� � � �
� - - -
� - - -
87/103 104/147 107/139 181/223 186/230
85/101 102/145 102/145 179/221 184/228
44/50 58/70 65/85 97/117 102/124
44/55 63/100 61/81 98/123 103/130
42/53 61/98 60/80 96/121 101/128
430×412×375 460×629×375 460×785×375
430×527×375 460×799×375 460×1015×375
300×378×295 300×597×295 300×751×295
300×493×295 300×767×295 300×981×295
N, A, P type N, A, P type N, A, P type
KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK
Ratings of Susol Series Air Circuit Breakers
16
Type
Ampere frame (AF)
Rated current(A) (In max) at 40℃℃
Setting current (A) Control trip relay ( ... ×× In max)
Rated current of neutral pole (A)
Rated insulation voltage(V) (Ui)
Rated operating voltage(V) (Ue)
Rated impulse withstand voltage (kV) (Uimp)
Frequency(Hz)
Number of poles (P)
Rated breaking capacity (kA sym)IEC 60947-2
220V/230V/380V/415V
AC 50/60Hz (Icu)KS C 4620
460V/480V/500V
550V/600V/690V
Rated service breaking capacity (kA) (Ics) ... %××Icu
Rated making capacity (kA peak)IEC 60947-2
220V/230V/380V/415V
AC 50/60Hz (Icm) KS C 4620
460V/480V/500V
550V/600V/690V
Rated short-time 1sec
withstand current (kA) (Icw) 2 sec
3 sec
Operating time (ms) Maximum total breaking time
Maximum closing time
Life cycle (time) Mechanical
Electrical
Connections Draw-out / Fixed Horizontal connection
Vertical connection
Front connection
Mixed connection
Weight (kg) Draw-out type Main body Motor charging type
(3P/4P) (With cradle) Manual charging type
Cradle only
Fixed type Motor charging type
Manual charging type
External dimensions (mm) Draw-out 3P
(H××W××D) type 4P
Fixed type 3P
4P
Trip relay
Certificate & Approval
Marine clasiflcation* Refer to trip relay specification. ** �: Standard, �: Option
※ Life time means not guarantee, but limitation.Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee
AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D
630 800 1000 1250 1600 2000
200 400
400 630 1000 1250 1600 2000
630 800
(0.4 ~ 1.0) × In max
400400
630 1000 1250 1600 2000630
800
1000
690
12
50/60
3/4
85
85
65
100%
187
187
143
65
60
50
40
80
20,000
5,000
� -
� �
� -
� -
63/74 70/85
61/72 68/83
29/32 33/40
34/44 38/47
32/42 36/45
430×334×375
430×419×375
300×300×295
300×385×295
N, A, P, S type
KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK
H
WD
*
**
LS Low Voltage Power Center 17
※Derating of the rated current is required according to the ambient temperature around the breaker in a panelif it is higher than the reference value. (See pages 109 to 112)
AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E
630 800 1000 1250 1600 2000 2500 3200 4000
630 800 1000 1250 1600 2000 2500 3200 4000
(0.4 ~ 1.0) × In max
630 800 1000 1250 1600 2000 2500 3200 4000
1,000
690
12
50/60
3/4
100
100
85
100%
220
220
187
85
75
65
40
80
15,000
5,000
� �
� �
� -
� -
87/103 107/139
85/101 102/145
44/55 65/85
44/55 61/81
42/53 60/80
430×412×375
430×527×375
300×378×295
300×493×295
N, A, P, S type
KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK
AH-40G AH-50G AH-63G
4000 5000 6300
4000 5000 6300
(0.4 ~ 1.0) × In max
4000 5000 6300
1,000
690
12
50/60
3/4
150
150
100
100%
330
330
220
100
85
75
40
80
10,000
2,000
�
�
-
-
181/223 186/230
179/221 184/228
97/117 102/124
98/123 103/130
96/121 101/128
460×785×375
460×1015×375
300×751×295
300×981×295
N, A, P, S type
KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK
Interlock minimize the risk of operational errors■Interlocks prevent racking of the breaker in or out when the breaker is closed■Closing and trip by electrical signals are available at the position of connection or test.
(Blocked at middle position)■Manual closing and trip are available at the position of connection or test.
(Blocked at middle position)
Main busbar and cable compartment is located at rear side. Branch bus and terminals to be connected from or to a breaker are arranged here. Bus Duct or Cable way is provided for external connection.
PT including primary and secondary fuses is mounted on drawable cradle. PT can be checked even in the service state at drawout position.
Breaker compartment
Main busbar and cable
Drawable PT, optional
GL type structure
GL Type Power Center provides front accessible breaker compartment and rear accessible main busbarand cable compartment. Control devices are installed at the door of the breaker compartment.
18
Follow the instructions shown in Figures for testing inthe compartment.Open the compartment door. Front panel of the breaker and internal coverprovide safe operation by isolating from the main circuit.
�
�
�
�
Push the trip button to make the breaker off state .
Open the racking slot cover and insert the racking tool and rotate itcounterclockwise. Connected - Test - Disconnected
Drawout sequence of the breaker, ACB
Remove the connector of control circuit at disconnected position and rotatethe racking tool counter-clockwise.
The extending rail locking is resolved automatically at Drawable position. The breaker can be drawout from the rail.
Use lifter or crane to remove the breaker out of the compartment
LS Low Voltage Power Center 19
�� For your safety, please read user's manual thoroughly before operating.
�� Contact the nearest authorized service facility for examination, repair, or adjustment.
�� Please contact a qualified service technician when you need maintenance.Do not disassemble or repair by yourself!
�� Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions
www.lsis.bizⓒ 2013.4 LSIS Co.,Ltd. All rights reserved.
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
�� HEAD OFFICEKorea Gyeonggi-do Anyang-si dongan-gu LS-ro 127 (Hogye-dong)TEL. (82-2)2034-4931/4943/4946FAX. (82-2)2034-4819
�� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea
2013. 04 Low-Voltage Power Centers (E) 2013. 04/(01) 2013. 04 Printed in Korea STAFF
�LSIS (Middle East) FZE ��Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab EmiratesTel: 971-4-886 5360 Fax: 971-4-886-5361 �Dalian LSIS Co., Ltd. ��Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 �LSIS (Wuxi) Co., Ltd. ��Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 �LSIS-VINA Co., Ltd. ��Hanoi, Vietnam
Address: Room 1311, 13th, M3-M4 Building 91 Nguyen Chi Thanh street, Hanoi, VietnamTel: 84-4-6275-8055 Fax: 84-4-6275-8056�LSIS-VINA Co., Ltd. ��Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 �LSIS Shanghai Office ��Shanghai, China
Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, ChinaTel: 86-21-5237-9977 Fax: 89-21-5237-7189 �LSIS Beijing Office ��Beijing, China
Address: Room 2306, Building B Landgent Center, No.24 Middle Road, East 3rd Ring Road, Chaoyang District,Beijing, P.R. ChinaTel: 86-10-5761-3127 Fax: 86-10-5761-3128�LSIS Guangzhou Office ��Guangzhou, China
Address: Room 1403, 14th, New Poly Tower, 2 Zhongshan Liu Road, Guangzhou, P.R ChinaTel: 86-20-8326-6784 Fax: 86-20-8326-6287�LSIS Chengdu Office ��Chengdu, China
Address: Room 1701 17Floor, huamin hanjun international Building, No1 Fuxing Road Chengdu, 610016, P.R. ChinaTel: 86-28-8670-3201 Fax: 86-28-8670-3203 �LSIS Qingdao Office ��Qingdao, China
Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. ChinaTel: 86-532-8501-6058 Fax: 86-532-8501-6057 �LSIS NETHERLANDS Co.Ltd ��Schiphol-Rijk, Netherlands
Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 �LSIS Gurgaon Office ��Gurgaon ,India
Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, IndiaTel: 91-1244-930-077 Fax: 91-1244-930-066
��Global Network