LOVER CALCULATIONS FOR BLOWER ROOM
Citation preview
Sheet1Louver Calculations1nNo of operating blowers12PmInstalled Power Kw of motor153PbAbsorbed power , in Kw9.5Amount of heat generatedQw,kj/hr =n*(Pm*0.15+Pb*0.12)x3600=12204Kj/hrCooling air flow required for heat reqmovalCpSpecific heat of air1005Kj/kg/hrPDensity of air1.11Kg/m3Maximum working blower ambient Temperature45-50deg Cselect45deg CIP55 Class F= Outside air temp40deg CTTemperature gradient5deg CQ1Blower capacity390m3/hrQr2187.9790237999m3/hrTotal Air required2578.0m3/hrArea of openingA= Qr/(C*V)0.7161052844m3/sC=Opening percentage0.3V= Velocity of wind4m/sArea of louver0.597m2