Louver Calculations 1 n No ofoperating blowers 1 2 Pm Installed Power Kw ofmotor 15 3 Pb Absorbed power in Kw !"5 Amount of #eat generated $w%&'#r ( n)*Pm)+"15,Pb)+"12-.3/++ ( 122+0 K&'#r Cooling air flow re uired for #eat re moval Cp pecific #eatofair 1++5 K&'%g'#r P ensit4 ofair 1"11 Kg'm3 a.imum wor%ing blower ambient 6emperat0575+ deg C select 05 deg C IP55 Class 8( 9utside air temp 0+ deg C 6 6emperature gradient 5 deg C $1 :lower capacit4 3!+ m3'#r $r 21;<"!<! m3'#r 6otal Air re uired 25<;"+ m3'#r Area of opening A ( $r'*C)=- +"<1/1+5 m3's C(9pening percentage +"3 =( =elocit4 ofwind 0 m's Area of louver +"5!< m2

Louver Calculations

  • Upload
    hrk65

  • View
    2

  • Download
    0

Embed Size (px)

DESCRIPTION

LOVER CALCULATIONS FOR BLOWER ROOM

Citation preview

Sheet1Louver Calculations1nNo of operating blowers12PmInstalled Power Kw of motor153PbAbsorbed power , in Kw9.5Amount of heat generatedQw,kj/hr =n*(Pm*0.15+Pb*0.12)x3600=12204Kj/hrCooling air flow required for heat reqmovalCpSpecific heat of air1005Kj/kg/hrPDensity of air1.11Kg/m3Maximum working blower ambient Temperature45-50deg Cselect45deg CIP55 Class F= Outside air temp40deg CTTemperature gradient5deg CQ1Blower capacity390m3/hrQr2187.9790237999m3/hrTotal Air required2578.0m3/hrArea of openingA= Qr/(C*V)0.7161052844m3/sC=Opening percentage0.3V= Velocity of wind4m/sArea of louver0.597m2