Lighting in Cold Storage

Aaron Kless, PE

Director of Application Engineering

Digital Lumens

Agenda

• Energy Usage in Cold Storage

• Lighting Energy and Heat Load

• Lighting Technology Alternatives

• Case Study – Ardo, UK

2

Page 2: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Typical Cold Storage Energy Profile

SOURCE: A. Lekov, L. Thompson, A. McKane, A. Rockoff, M.A. Piette, Opportunities for

Energy Efficiency and Automated Demand Response in Industrial Refrigerated Warehouses in

California (2009), Lawrence Berkeley National Laboratory

3

Refrigeration

Electric Defrost

Lighting

Office HVAC

Battery Charging Exhaust Fans/Misc Equipment

Where is the energy going?

Typical Heat Loads

• Typical Heat Loads on Refrigeration System include:

• Product

• Transmission

• Infiltration

• Defrost

• Internal Generation

• personnel, lights, other equipment

12/29/104

Page 3: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Energy Balance - Lighting

Light Energy

Heat

Energy

Sound

Energy

Electric Energy

Light is absorbed by product and

structure and re-radiated as heat

energy – this becomes chiller load

Load on Refrigeration System

• Assuming steady state operation, 90% Load Factor

• The chiller will have to remove 1.25 billion BTUs of energy each

year from the lights alone - enough energy to melt over 4,300

tons of ice!

6

Number of Lights 100

Light Fixture Power (HPS) 465 W

Total Lighting Power 46.5 kW

Total Lighting Power (BTU/hr) 158,658 BTU/hr

Max Refrigeration Load 13.2 Tons Refrigeration

Page 4: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Upgrading the lighting system results in direct savings from

lighting energy usage reduction and real additional

savings for heat load reduction

How Much Are You Spending To Remove

Heat From Lights?

• Typical Coefficient of Performance

(COP) for Industrial Refrigeration

System is 2-5

• COP = [(heat energy removed)/(system energy input)]

7

Lighting Alternatives

8

• Lower energy alternatives include HIF, LED, and LED with

intelligent controls

• The key to significant energy usage reduction in cold storage

is taking advantage of control systems

Intelligence

LED power

reduction

(watts)

Incentives

Fine-tuning

HVAC &

chiller load

reduction

Maintenance

Intelligent Lighting SystemSavings Summary

Page 5: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Fine Tuning Controls

• Motion Sensor timeout has a

significant impact on energy

savings

• Shorter timeouts drive greater

savings

• Low time threshold is technology

driven

• Solid state lighting lifetime not

affected by excessive cycling

9

Sensor Settings & Energy Cost:

Integrated System Maximizes Savings

Sensor Delays and Energy Savings

4:30pm 5:30pm

Sensor

Delay

% “Active” ILE Energy

Cost*

(160W)

HIF Energy Cost*

@ 15 mins (220W)

30 sec 25.2 % 27.13 € 147.29 €

60 sec 40.8 % 44.19 € 147.29 €

90 sec 52.4 % 56.59 € 147.29 €

3 min 72.5 % 79.07 € 147.29 €

5 min 89.3 % 96.90 € 147.29 €

10 min 98.6 % 106.98 € 147.29 €

* 10¢ /kWh

Page 6: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Case Study – Ardo, UK

• Frozen Vegetable Distribution Center

• 80,000 cubic meters

• Movable racking system

• -27 °C

• 7,000 operating hours/year

• 165 x 400W High Pressure Sodium Fittings (456 W)

11

Case Study – Ardo, UK

Solution:

• Digital Lumens Intelligent LED

Lighting System installed in July of

2012

• 165 x 160W ILE HB-3 fixtures with

LightRules control and monitoring

system

• Motion sensor and wireless controls

integrated into every fixture

12

Page 7: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Case Study – Ardo, UK

Overview Presentation13

Occupancy data from LightRules system:

Average Occupancy, Week of 27 Sep 3.11%

Average Weekly Occupancy 9%

Case Study – Ardo, UK

Overview Presentation14

•Extending motion sensor timeout from one minute to fifteen minutes would

drive light usage up by over 2.5 times

•Short sensor timeout drives significant savings

Analysis from LightRules system:

Page 8: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

Case Study – Ardo, UK

15

Previous

(HPS)

Current (LED)

Annual Direct Lighting Energy Usage 540,000 kWh 20,200 kWh

Annual Lighting Heat Load 1.8 x 109 BTU 6.9 x 107 BTU

Usage Summary:

Case Study – Ardo, UK

16

Total Annual Energy Savings 750,000 kWh

Tonnes CO2 Saved Annually 400

Simple Payback 1.8 years

Project Summary:

97% Total Energy Savings

Page 9: Lighting in Cold Storage - Cool Chain Associationcoolchain.org/Websites/cca/images/CCA-ECSLA_Madrid/... · 2012-10-25 · Lighting in Cold Storage Aaron Kless, PE Director of Application

• Deployed in the world’s leading industrial facilities

• Cold Storage, Warehouses, Manufacturing, etc.

• More than 200 large-scale deployments

17

Digital Lumens: Tested & Proven

Summary

• Energy Usage in Cold Storage

• Lighting Energy and Heat Load

• Lighting Technology Alternatives

• Case Study – Ardo, UK

18