Page 1: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-2Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-2-7

Page 2: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-2Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 2.5 A*

Input BTU/hr. 199 MBH / 59 KW Min. Gas Pressure Required 2" W.C.

Output BTU/hr. 179 MBH / 53 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 5.4 Water Volume 3.9 gal.

Electrical Requirements 120VAC/ 60 hz/ 1PH Operating Weight 563 lbs. / 256 kg.

BOILER TRIM & CONTROLSMain Gas Valve Dungs GB-WND Air Switch Cleveland NS-2

Ignition Control Fenwal 35-60 Blower Motor Ametek

Operating Control HeatNet® Relief Valve 30, 50, 75 & 100 PSI

High Limit P-SW-13004-X

A.S.M.E.ASME Sect IV Fire Side Htg Surface 7.88 Sq. Ft. / 0.73 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 7.10 Sq. Ft. / 0.66 Sq. M.

CV. GPM (1PSID) 20

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

18.0 1.14 1.87 5.6 9.0 .57 .47 1.40 6.00 .38 .21 .62 4.5 .28 .12 .35 3.6 .23 .07 .22

SKN-2-7

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

3.6 18.0 20 100 6 100 0 100

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 3: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-4Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-4-7

Page 4: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-4Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 5 A*

Input BTU/hr. 399 MBH / 117 KW Min. Gas Pressure Required 2" W.C.

Output BTU/hr. 359 MBH / 105 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 10.7 Water Volume 5.9 gal.

Electrical Requirements 120VAC/ 60 hz/ 1PH Operating Weight 827 lbs. / 375 kg.

BOILER TRIM & CONTROLSMain Gas Valve Dungs GB-WND Air Switch Cleveland NS-2

Ignition Control Fenwal 35-60 Blower Motor Ametek

Operating Control HeatNet® Relief Valve 30, 50, 75 & 100 PSI

High Limit P-SW-1300-4-X

A.S.M.E.ASME Sect IV Fire Side Htg Surface 14.53 Sq. Ft. / 1.35 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 14.21 Sq. Ft. / 1.32 Sq. M.

CV. GPM (1PSID) 40

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

36.0 2.30 1.90 5.60 18.0 1.10 .50 1.40 12.0 .80 .21 .60 9.00 .60 .12 .30 7.2 .50 .07 .22

SKN-4-7

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

7.2 36 20 100 6 100 0 100

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 5: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-6Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-6-12

25635

71 17/321817

35 1/8892

12 1/2315

33833

1 1/3226

18 21/32474

15 1/2398

36 1/32915

WIRINGCONNECTIONS

1 NPTGAS INLET

SIDE VIEWASUB-5_L

TOP VIEWASUB-5_L

4 FLUE OUTLET

CONDENSATE DRAIN3/4 HOSE BARB

23 9/16598

7 1/16179

23/3218

42 9/161081

2 1/264

20508

25635

1 3/444

4X 5/816

21 5/8549

12 31/32329

3 7/3282

12 1/2318

17 11/32441

21 13/16554

9 1/8232

20 1/2521

46 15/161192

64 13/321636

6 AIR INLET

3 NPTBOILER INLET

3 NPTBOILER OUTLET

BOTTOM VIEWASUB-5_L

REAR VIEWASUB-5_L

FRONT VIEWASUB-5_L

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

INDOOR UNIT

Page 6: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-6Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 13.1 A*

Input BTU/hr. 600 MBH / 176 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 540 MBH / 158 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 16.3 Water Volume 7.9 gal.

Electrical Requirements 120VAC/ 60 hz/ 1PH Operating Weight 1150 lbs. / 522 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 1" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit Honeywell L4006E L.W.C.O. 800

Main Ball Valve 1" Apollo Relief Valve 30, 50, 75 & 100 PSI

Pilot Cock 1/4" Conbraco Pilot Regulator Maxitrol RV12LT

A.S.M.E.ASME Sect IV Fire Side Htg Surface 21.18 Sq. Ft. / 1.97 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 21.32 Sq. Ft. / 1.98 Sq. M.

CV. GPM (1PSID) 62

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

54.0 3.40 1.75 5.20 27.0 1.70 .44 1.30 18.0 1.10 .19 .60 13.5 .90 .11 .30 10.8 .70 .07 .20

SKN-6-12

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

10.8 54.0 20 100 6 120 0 120

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 7: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-6

SKN-6-12

OUTDOOR UNIT

30 17/32775

32 15/16837

40 11/321024

45 23/321161

24 5/16618

73 3/161859

70 1/161779

92 7/162348

34 3/8873

25635

12 7/16316

50 9/161284

60 15/161548

26 13/16681

21 1/4

540

70 3/161782

10 15/16278

59 1/41505

33 3/4857

23 5/32588

19 9/32490

1 13/3235

65 7/161662

21534

1 NPTGAS INLET

WIRINGCONNECTIONS

CONDENSATE DRAIN3/4 HOSE BARB

TOP VIEWASUB-32_E

VENT ASSEMBLYCAP

16 15/32418

11 1/8283

1 3/444

28 1/2724

25635

9 3/8238

6 15/32

164

20508

2 1/264

4X 5/816

25635

BOTTOM VIEWASUB-32_E

15 3/32383

13 15/16354

46 9/161182

9 1/8232

20 1/2521

3 7/3282

12 1/2318

17 11/32441

21 13/16554

21 5/8549

1 7/3231

REAR VIEWASUB-32_E

4VENT ASSEMBLY

3 NPTBOILER OUTLET

3 NPTBOILER INLET

BOILERDRAINVALVE

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

FRONT VIEWASUB-32_E

SIDE VIEWASUB-32_E

Page 8: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-10Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-10-12

INDOOR UNIT

25635

35 3/32892

25635

12 1/2314

71 17/321817

32 21/32829

43 13/321102

19483

18 21/32474

13/1620

WIRINGCONNECTIONS

1 NPTGAS INLET

SIDE VIEWASUB-4_L

TOP VIEWASUB-4_L

4 FLUE OUTLET

CONDENSATE DRAIN3/4 HOSE BARB

8 3/32205

49 15/161268

7 1/32179

30 15/16786

20508

2 1/264

32 1/8816

1 3/444

4X 5/816

12 1/2318

9 1/8232

20 1/2521

46 15/161192

21 5/8549

3 7/3282

17 11/32441

21 13/16554

12 31/32329

64 13/321636

6 AIR INLET

3 NPTBOILER INLET

3 NPTBOILER OUTLET

BOTTOM VIEWASUB-4_L

REAR VIEWASUB-4_L

FRONT VIEWASUB-4_L

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

Page 9: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-10Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 13.1 A*

Input BTU/hr. 1000 MBH / 293 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 900 MBH / 264 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 26.9 Water Volume 11.9 gal.

Electrical Requirements 120VAC/ 60 hz/ 1PH Operating Weight 1557 lbs. / 707 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 1 1/4" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit Honeywell L4006E L.W.C.O. 800

Main Ball Valve 1 1/4" Apollo Relief Valve 30, 50, 75 & 100 PSI

Pilot Cock 1/4" Conbraco Pilot Regulator Maxitrol RV12LT

A.S.M.E.ASME Sect IV Fire Side Htg Surface 34.48 Sq. Ft. / 3.20 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 35.54 Sq. Ft. / 3.30 Sq. M.

CV. GPM (1PSID) 100

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

90.0 5.70 1.87 5.60 45.0 2.80 .47 1.40 30.0 1.90 .21 .60 22.5 1.40 .12 .30 18.0 1.10 .07 .20

SKN-10-12

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

18.0 90.0 20 100 6 120*** 0 120

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.***A maximum equivalent length of 80 ft. utilizing 4" vent diameter and 120 ft. utilizing 5" vent diameter.

*Add circulator amps.

Page 10: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-10

SKN-10-12

OUTDOOR UNIT

30 17/32775

32 15/16837

40 11/321024

45 23/321161

24 5/16618

73 3/161859

70 1/161779

92 7/162348

34 1/32864

12 13/32315

25635

57 29/321471

68 9/321735

34 3/16868

21 1/4540

70 3/161782

10 15/16278

59 1/41505

33 3/4857

23 5/32588

19 9/32490

72 25/321849

1 5/3229

24 1/2621

1 NPTGAS INLET

WIRINGCONNECTIONS

CONDENSATE DRAIN3/4 HOSE BARB

TOP VIEWASUB-33_E

1 3/444

32 1/8816

7 5/8194

16 15/32418

11 5/32284

2 1/2

64

20508

6 15/32164

4X 5/816

24 15/16633

35 5/8905

BOTTOM VIEWASUB-33_E

15 3/32383

9 1/8232

20 1/2521

46 15/161192

21 5/8549

3 7/3282

12 1/2318

17 11/32441

21 13/16554

1 7/3231

REAR VIEWASUB-33_E

4VENT ASSEMBLY

3 NPTBOILER OUTLET

3 NPTBOILER INLET

BOILERDRAINVALVE

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

FRONT VIEWASUB-33_E

SIDE VIEWASUB-33_E

Page 11: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-16Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-16-9

INDOOR UNIT

25635

34 31/32888

71 3/81813

33837

12 1/2313

1 7/3231

18 27/32479

59 7/321504

23 1/2598

WIRINGCONNECTIONS

1 1/2 NPTGAS INLET

SIDE VIEWASUB-16_G

TOP VIEWASUB-16_G

6FLUE OUTLET

CONDENSATE DRAIN3/4 HOSE BARB

7178

41 9/321048

18 1/4463

20508

2 1/264

43 1/41099

1 3/444

4X 5/816

8 AIR INLET

65 7/321657

46 15/161192

9 1/8232

20 1/2521

16 23/32425

21 5/8549

3 7/3282

12 1/2318

17 11/32441

21 13/16554

3 NPTBOILER INLET

3 NPTBOILER OUTLET

BOTTOM VIEWASUB-16_G

REAR VIEWASUB-16_G

FRONT VIEWASUB-16_G

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

Page 12: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-16Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 13.1 A*

Input BTU/hr. 1600 MBH / 469 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 1440 MBH / 422 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 43.0 Water Volume 17.9 gal.

Electrical Requirements 230VAC/60 hz/1PH (with neutral) Operating Weight 2360 lbs. / 1070 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 1-1/2" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit Honeywell L4006E L.W.C.O. 800

Main Ball Valve 1-1/2" Apollo Relief Valve 30, 50, 75 & 100 PSI

Pilot Cock 1/4" Conbraco Pilot Regulator Maxitrol RV12LT

A.S.M.E.ASME Sect IV Fire Side Htg Surface 54.43 Sq. Ft. / 5.06 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 56.86 Sq. Ft. / 5.28 Sq. M.

CV. GPM (1PSID) 140

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

144.1 9.10 2.44 7.30 72.0 4.50 .61 1.80 48.0 3.00 .27 .80 36.0 2.30 .15 .50 28.8 1.80 .10 .30

SKN-16-9

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

28.8 144.1 20 100 6 120 0 120

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 13: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-16

SKN-16-9

OUTDOOR UNIT

30 17/32775

32 15/16837

41 11/161059

45 23/321161

24 5/16618

73 3/161859

70 1/161779

96 3/322441

25635

12 17/32318

33 13/16859

691753

85 1/42166

78 1/21994

45 1/41149

21 1/4540

70 3/161782

10 15/16278

59 1/41505

33 3/4857

23 5/32588

30768

7/822

19 9/32490

1 1/2 NPTGAS INLET

WIRINGCONNECTIONS

CONDENSATE DRAIN3/4 HOSE BARB

TOP VIEWASUB-34_F

9 1/32230

43 1/41099

1 3/444

20508

2 1/264

6 7/16163

16 15/32418

11 7/32285

46 3/41187

24 15/16633

4X 5/816BOTTOM VIEW

ASUB-34_F

14 3/32358

21 5/8549

9 1/8232

20 1/2521

46 15/161192

3 7/3282

12 1/2318

17 11/32441

21 13/16554

1 7/3231

REAR VIEWASUB-34_F

6VENT ASSEMBLY

3 NPTBOILER OUTLET3 NPT

BOILER INLET

BOILERDRAINVALVE

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

FRONT VIEWASUB-34_F

SIDE VIEWASUB-34_F

Page 14: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-20Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-20-12

INDOOR UNIT

25635

71 29/321826

34 29/32886

12 1/2313

33836

61 13/161570

27684

125

19 3/8492

WIRINGCONNECTIONS

1 1/2 NPTGAS INLET

SIDE VIEWASUB-3_L

TOP VIEWASUB-3_L

6FLUE OUTLET

CONDENSATE DRAIN 3/4 HOSE BARB

66 19/321691

7178

48 21/321236

25 19/32650

1 3/444

50 3/81280

4X 5/816

2 1/264

20508

12 1/2318

9 1/8232

3 7/3282

8 AIR INLET

17 11/32441

21 13/16554

21 5/8549

46 15/161192

20 1/2521

16 13/16427

65 23/321670

3 NPTBOILER INLET

3 NPTBOILER OUTLET

BOTTOM VIEWASUB-3_L

REAR VIEWASUB-3_L

FRONT VIEWASUB-3_L

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

Page 15: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-20Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 13.1 A*

Input BTU/hr. 1999 MBH / 586 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 1799 MBH / 527 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 53.7 Water Volume 21.9 gal.

Electrical Requirements 230VAC/60 hz/1PH (with neutral) Operating Weight 2714 lbs. / 1232 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 1-1/2" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit Honeywell L4006E L.W.C.O. 800

Main Ball Valve 1-1/2" Apollo Relief Valve 30, 50, 75 & 100 PSI

Pilot Cock 1/4" Conbraco Pilot Regulator Maxitrol RV12LT

A.S.M.E.ASME Sect IV Fire Side Htg Surface 67.72 Sq. Ft. / 6.29 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 71.08 Sq. Ft. / 6.60 Sq. M.

CV. GPM (1PSID) 161

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

180.0 11.40 2.88 8.60 90.0 5.70 .72 2.20 60.0 3.80 .32 1.00 45.0 2.80 .18 .50 36.0 2.30 .12 .30

SKN-20-12

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

36.0 180.0 20 100 6 120 0 120

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 16: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-20

SKN-20-12

OUTDOOR UNIT

30 17/32775

32 15/16837

41 5/81057

45 23/321161

24 5/16618

73 3/161859

70 1/161779

96 3/322441

25635

12 1/2317

33 23/32857

76 13/321941

85 7/82181

52 5/81337

21 1/4540

70 3/161782

10 15/16278

59 1/41505

33 3/4857

23 5/32588

19 9/32490

5/816

92 5/82353

34860

1 1/2 NPTGAS INLET

WIRINGCONNECTIONS

CONDENSATE DRAIN3/4 HOSE BARB

TOP VIEWASUB-35_E

2 1/264

20508

6 15/32164

50 3/81280

1 3/444

9 1/16230

16 15/32418

11 1/4285

4X 5/816

24 15/16633

53 7/81368

BOTTOM VIEWASUB-35_E

9 1/8232

14 3/32358

20 1/2521

46 15/161192

21 5/8549

3 7/3282

12 1/2318

17 11/32441

21 13/16554

1 7/3231

REAR VIEWASUB-35_E

6VENT ASSEMBLY

3 NPTBOILER OUTLET3 NPT

BOILER INLET

BOILERDRAINVALVE

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

SIDE VIEWASUB-35_E

FRONT VIEWASUB-35_E

Page 17: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-26Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-26-8

INDOOR UNIT

25635

71 29/321826

32819

12 1/2312

34 9/32871

74 13/161900

126

19 3/8492

33840

WIRINGCONNECTIONS

1 1/2 NPTGAS INLET

SIDE VIEWASUB-12_F

TOP VIEWASUB-12_F

8FLUE OUTLET

CONDENSATE DRAIN3/4 HOSE BARB

77 29/321979

59 23/321517

12 1/16306

37 17/32953

2 1/264

1 3/444

20508

62 5/161583

4X 5/816

8 AIR INLET

65 23/321670

9 1/8232

20 1/2521

46 1/161170

16 31/32431

21 5/8549

3 27/3298

12 1/2318

17 11/32441

21 7/32539

4" ANSI FLANGEBOILER INLET

4" ANSI FLANGEBOILER OUTLET

BOTTOM VIEWASUB-12_F

REAR VIEWASUB-12_F

FRONT VIEWASUB-12_F

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

Page 18: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-26Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 10.7 A*

Input BTU/hr. 2600 MBH / 762 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 2340 MBH / 686 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 70 Water Volume 27.7 gal.

Electrical Requirements 230VAC/60 hz/3PH Operating Weight 3425 lbs. / 1555 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 1-1/2" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit (Manual Reset) Honeywell L4006E L.W.C.O. 800

High Limit (Auto Reset) Honeywell L4006A Relief Valve 30, 50, 75 & 100 PSI

Main Ball Valve 1-1/2" Apollo Pilot Regulator Maxitrol RV12LT

Pilot Cock 1/4" Conbraco

A.S.M.E.ASME Sect IV Fire Side Htg Surface 87.69 Sq. Ft. / 8.15 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 92.41 Sq. Ft. / 8.59 Sq. M.

CV. GPM (1PSID) 222

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

234.1 14.80 2.57 7.70 117.0 7.40 .64 1.90 78.0 4.90 .29 .90 58.5 3.70 .16 .50 46.8 3.00 .10 .30

SKN-26-8

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

46.8 234.1 20 100 6 120 0 120

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 19: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-26

SKN-26-8

OUTDOOR UNIT

30 17/32775

32 15/16837

41 5/81057

45 23/321161

24 5/16618

73 3/161859

70 1/161779

87 1/22223

25635

12 7/16316

33 3/32840

92 5/162345

110 1/82797

101 1/82569

68 11/161745

21 1/4540

70 3/161782

10 15/16278

59 1/41505

33 3/4857

23 5/32588

19 9/32490

21/3217

43 1/2

1104

1 1/2 NPTGAS INLET

WIRINGCONNECTIONS

CONDENSATE DRAIN3/4 HOSE BARB

TOP VIEWASUB-36_E

16 15/32418

16 3/16411

1 3/444

62 5/161583

13 1/8334

6 15/32164

2 1/264

20508

24 15/16633

4X 5/816

65 13/161672

BOTTOM VIEWASUB-36_E

13 3/32333

9 1/8232

20 1/2521

45 13/161164

21 5/8549

3 27/3298

12 1/2318

17 11/32440

21 1/4540

1 7/3231

REAR VIEWASUB-36_E

8VENT ASSEMBLY

4" ANSI FLANGEBOILER OUTLET

4" ANSI FLANGEBOILER INLET

BOILERDRAINVALVE

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

FRONT VIEWASUB-36_E

SIDE VIEWASUB-36_E

Page 20: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-30Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-30-11

INDOOR UNIT

25635

71 29/321826

12 1/2312

32818

34 9/32871

82 1/42089

1 1/3226

19 3/8492

37934

WIRINGCONNECTIONS

1 1/2 NPTGAS INLET

SIDE VIEWASUB-10_G

TOP VIEWASUB-10_G

8FLUE OUTLET

CONDENSATE DRAIN3/4 HOSE BARB

67 3/321705

12 1/32306

85 9/322166

44 7/81140

1 3/444

69 11/161770

4x 5/816

2 1/264

20508

16 13/16427

65 23/321670

8 AIR INLET

21 5/8549

3 27/3298

12 1/2318

17 11/32441

21 7/32539

9 1/8232

20 1/2521

46 1/161170

4" ANSI FLANGEBOILER INLET

4" ANSI FLANGEBOILER OUTLET

BOTTOM VIEWASUB-10_G

REAR VIEWASUB-10_G

FRONT VIEWASUB-10_GNOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

Page 21: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-30Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 10.7 A*

Input BTU/hr. 3000 MBH / 879 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 2700 MBH / 791 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 80.7 Water Volume 31.7 gal.

Electrical Requirements 230VAC/60 hz/3PH Operating Weight 3850 lbs. / 1748 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 1-1/2" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit (Manual Reset) Honeywell L4006E L.W.C.O. 800

High Limit (Auto Reset) Honeywell L4006A Relief Valve 30, 50, 75 & 100 PSI

Main Ball Valve 1-1/2" Apollo Pilot Regulator Maxitrol RV12LT

Pilot Cock 1/4" Conbraco

A.S.M.E.ASME Sect IV Fire Side Htg Surface 100.98 Sq. Ft. / 9.38 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 106.63 Sq. Ft. / 9.91 Sq. M.

CV. GPM (1PSID) 246

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

270.1 17.0 2.78 8.30 135.1 8.50 .70 2.10 90.0 5.70 .31 .90 67.5 4.30 .17 .50 54.0 3.40 .11 .30

SKN-30-11

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

54.4 270.1 20 100 6 120 0 120

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 22: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-30

SKN-30-11

OUTDOOR UNIT

30 17/32775

32 15/16837

41 5/81057

45 23/321161

24 5/16618

73 3/161859

70 1/161779

87 1/22223

33 1/32839

12 7/16316

25635

101 11/162583

117 1/22984

108 1/22756

78 1/161983

21 1/4540

70 3/161782

10 15/16278

59 1/41505

33 3/4857

23 5/32588

19 9/32490

21/3217

491246

1 1/2 NPTGAS INLET

WIRINGCONNECTIONS

CONDENSATE DRAIN3/4 HOSE BARB

TOP VIEWASUB-37_E

18 3/16462

16 15/32418

69 11/161770

1 3/444

15 5/32385

2 1/264

6 15/32164

20508

4X 5/816

73 3/161859

24 15/16633

BOTTOM VIEWASUB-37_E

13 3/32333

9 1/8232

20 1/2521

45 13/161164

21 5/8549

3 27/3298

12 1/2318

17 11/32440

21 1/4540

1 7/3231

REAR VIEWASUB-37_E

8VENT ASSEMBLY

4" ANSI FLANGEBOILER OUTLET

4" ANSI FLANGEBOILER INLET

BOILERDRAINVALVE

NOTES:

1. SYMBOL INDICATES CENTER OF GRAVITY.

2. DIMENSIONS ARE NOMINAL AND SUBJECT TO MANUFACTURING VARIATION AND SHOULD NOT BE USED FOR "ROUGHING IN".

3. ALL DIMENSIONS ARE INCHES [mm].

FRONT VIEWASUB-37_E

SIDE VIEWASUB-37_E

Page 23: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

CODE OPTIONS

CSD-1 STANDARDKN-40Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

SKN-40-2

INDOOR UNIT

Page 24: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

KN-40Category II or Category IV Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

A.G.A. CERTIFIED RATINGS & CAPACITIESFuel Type Natural/LP Gas Boiler FLA 14.9 A*

Input BTU/hr. 4000 MBH / 1172 KW Min. Gas Pressure Required 3" W.C.

Output BTU/hr. 3540 MBH / 1037 KW Max. Gas Pressure Allowed 14" W.C.

Boiler HP 105.8 Water Volume 41.6 gal.

Electrical Requirements 230VAC/60 hz/3PH Operating Weight 4627 lbs. / 2101 kg.

SCCR Rating 5kA

BOILER TRIM & CONTROLSMain Gas Valve Dungs MBC Air Switch Huba

Firing Valve 2" Apollo Flow Sensor SIKA

Ignition Control Honeywell RM7895C Blocked Flue Switch Cleveland NS2

Operating Control HeatNet® Blower Motor Ametek

High Limit (Manual Reset) Honeywell L4006E L.W.C.O. 800

High Limit (Auto Reset) Honeywell L4006A Relief Valve 30, 50, 75 & 100 PSI

Main Ball Valve 2" Apollo Pilot Regulator Maxitrol RV12LT

Pilot Cock 1/4" Conbraco

A.S.M.E.ASME Sect IV Fire Side Htg Surface 134.23 Sq. Ft. / 12.47 Sq. M. Design Data 100 PSI & 250°F

ASME Sect IV Water Side Htg Surface 142.17 Sq. Ft. / 13.21 Sq. M.

CV. GPM (1PSID) 271

TEMPERATURE RISE / PRESSURE DROP (Based on Full Input)20°F / 11.1°C 40°F / 22.2°C 60°F / 33.3°C 80°F / 44.4°C 100°F / 55.5°C

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

DropFlow Rate

Pressure Drop

Flow RatePressure

Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

354.1 22.3 3.94 11.8 177.1 11.2 .99 2.90 118.0 7.40 .44 1.30 88.5 5.60 .25 .70 70.8 4.50 .16 .50

SKN-40-2

Flow GPM Temp. Rise** (°F) Vent Length (Equiv. Ft.) Air Inlet Length (Equiv. Ft.)

Min Max Min Max Min Max Min Max

70.8 354.1 20 100 6 100 0 100

**Min/Max delta t reflects boiler operation at full input. For applications requiring operation above/below these parameters please consult factory.

*Add circulator amps.

Page 25: KN-2literature.mestek.com/dms/Hydrotherm Boilers/KN Series...SKN-2-7 REP FIRM SUBMITTED BY JOB NAME ARCHITECT ENGINEER CONTRACTOR DATE KN-2 Category II or Category IV Appliance (see

KN-40

SKN-40-2

OUTDOOR UNIT