Upload
doanngoc
View
229
Download
0
Embed Size (px)
Citation preview
Subject to technical modifications
Damper actuators
LM..A 2) NM..A 2) SM..A 2) GM..A 2)
5 Nm 10 Nm 20 Nm 40 Nm
For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2
Open-close actuators
AC/DC 24 V LM24A NM24A SM24A GM24A
with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S
AC 230 V LM230A NM230A SM230A GM230A
with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA
AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR
AC 230 V LM230ASR NM230ASR SM230ASR
Parameterisable actuators parameterisable 1)
AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF
Technical data
Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm
Running time 150 s / 90°
Manual override Gear disengagement with push button, can be locked
Connection Cable 1 m / Terminals
Direction of rotation Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Position indication Mechanical, pluggable
Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s
Degree of protection IP 54
EMC CE according to 2004/108/EC
Ambient temperature –30...+50°C
Non-operating temperature –40...+80°C
Ambient humidity 95% r.h., non-condensating
1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection
Other versions on request.
Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..
Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V
U = DC 2...10 VY = Control signalU = Measuring voltage
Y = DC 0...10 VU = DC 2...10 V
Direction of rotation
1
0
1
2 3
1
0
–
T
~
N L
+
0...100%
S1 S2 S3
1
2 3
0
1
0
–
T
~
N
L
+
0...100%
S1 S2 S3
Y
U
1 32 5
–
T
~
+
Y
U
1 32 5
1
2
N L
T
SG..24
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
LV..A NV..A SV..A AVK..A EV..A RV..A
Actuatingtime
(Control)Operatingrange
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
AC/DC 24 V
150 s Nominal stroke (NS) 3-point LV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
150 s NS 35 s NS 3-point NVK24A-
3-TPCAVK24A- 3-TPC
AC 230 V 150 s NS 3-point LV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
150 s NS 35 s NS 3-point NVK230A-3 AVK230A-3
AC/DC 24 V 35 s NS
DC (0) 0.5...10 V
DC (0) 2...10 V LVC24A- SR-TPC
NVC24A- SR-TPC
SVC24A- SR-TPC EVC24A-SR
150 s NS 35 s NS
DC (0) 0.5...10 V
DC (0) 2...10 V NVKC24A- SR-TPC
150 s NS
DC (0) 0.5...10 V
DC (0) 2...10 V LV24A- SR-TPC
NV24A- SR-TPC
SV24A- SR-TPC
EV24A- SR-TPC RV24A-SR
150 s NS 35 s NS
DC (0) 0.5...10 V
DC (0) 2...10 V NVK24A- SR-TPC
AVK24A- SR-TPC
AC/DC 24 V 35 s NS DC (0) 0.5...10 V LVC24A-
MP-TPCNVC24A- MP-TPC
SVC24A- MP-TPC EVC24A-MF
150 s NS 35 s NS DC (0) 0.5...10 V NVKC24A-
MP-TPC
150 s NS DC (0) 0.5...10 V LV24A- MP-TPC
NV24A- MP-TPC
SV24A- MP-TPC
EV24A- MP-TP RV24A-MF
150 s NS 35 s NS DC (0) 0.5...10 V NVK24A-
MP-TPCAVK24A- MP-TPC
M
M
M
M
M
M
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3-po
int
Mod
ulat
ing
Mul
tifun
ctio
nal2)
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3)
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3)
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3)
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3)
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3)
Subject to technical modifications
SuperCap actuators
SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A
2 Nm 40 Nm 6 Nm 150 N 450 N
For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2
Open-close actuators
AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA
AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100
Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100
Parameterisable actuators parameterisable 1)
AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100
External SuperCap module
AC 230 V SKM230-T-B12.1
Technical data
Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm
Running time MotorEmergency control function
75 s / 90°15 s / 90°
150 s / 90°35 s / 90°
4 s / 90°4 s / 90°
120 s / 100 mm35 s / 100 mm
Manual override Gear disengage-ment with magnet
Gear disengagement with push button
Connection Terminals Cable 1 mDirection of rotation Selectable with
actuator 2)Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor
Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s
≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s
≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s
≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s
≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s
Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right
Other versions on request.
Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF
SKM230.. CM24K.. Open-close control modulating parameterisable
2 1
–
3
+
2 13 1N2L
T~
OUT 1 OUT 2 IN
CM24K.. CM24K.. AC 198 ... 264 V
50/60 Hz
–+
SKM230-T-B12
1 2 3
– +
L
R
L
R
1 2 3
1
0
– +
T
~
..-SR: Y = DC 0...10 V U = DC 2...10 V
..-SZ: Y = DC 0...10 V U = DC 0...10 V
Y = Control signalU = Measuring voltage
Y
U
1 32 5
–
T
~
+
3)
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
tting
pos
ition
Flange ISO 7005
PN 16Tmax=120°C 1)
Range of useClosed / open circuits (pH > 7)
2-wayDN
[mm]kvs
[m3/h]∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611N 15 0.63 1300 400 1600 400 1600 400
H612N 15 1
H613N 15 1.6
H614N 15 2.5
H615N 15 4 1300
H620N 20 6.3 900 1600
H625N 25 10 500 400 1300
H632N 32 16 350 350 1000 1600
H640N 40 25 150 150 500 400 900
H650N 50 40 70 70 300 300 550 400
H664N 65 58 140 140 280 280
H665N 65 63 400 400 550 400 1100 400
H679N 80 90 80 80 160 160
H680N 80 100 250 250 350 350 700 400
H6100N 100 145 150 150 200 200 450 400
Globe valves. Control Valves – flange
continues on next page
Subject to technical modifications
Damper actuators
LM..A 2) NM..A 2) SM..A 2) GM..A 2)
5 Nm 10 Nm 20 Nm 40 Nm
For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2
Open-close actuators
AC/DC 24 V LM24A NM24A SM24A GM24A
with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S
AC 230 V LM230A NM230A SM230A GM230A
with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S
Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA
AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR
AC 230 V LM230ASR NM230ASR SM230ASR
Parameterisable actuators parameterisable 1)
AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF
Technical data
Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm
Running time 150 s / 90°
Manual override Gear disengagement with push button, can be locked
Connection Cable 1 m / Terminals
Direction of rotation Selectable with switch
Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops
Position indication Mechanical, pluggable
Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s
Degree of protection IP 54
EMC CE according to 2004/108/EC
Ambient temperature –30...+50°C
Non-operating temperature –40...+80°C
Ambient humidity 95% r.h., non-condensating
1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection
Other versions on request.
Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..
Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V
U = DC 2...10 VY = Control signalU = Measuring voltage
Y = DC 0...10 VU = DC 2...10 V
Direction of rotation
1
0
1
2 3
1
0
–
T
~
N L
+
0...100%
S1 S2 S3
1
2 3
0
1
0
–
T
~
N
L
+
0...100%
S1 S2 S3
Y
U
1 32 5
–
T
~
+
Y
U
1 32 5
1
2
N L
T
SG..24
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Globe valves
Flange (ISO 7005) PN 6Tmax = 120°C 1)
Range of useClosed circuits2-way 3-Weg
DN[mm]
kvs[m3/h]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H611R...H615R H711R...H715R 15 0.63 / 1 / 1.6 / 2.5 / 4 600 400 600 400 600 400H620R H720R 20 6.3 600 400 600 400 600 400H625R H725R 25 10 500 400 600 400 600 400H632R H732R 32 16 350 350 600 400 600 400H640R H740R 40 25 150 150 500 400 600 400H650R H750R 50 40 70 70 300 300 550 400H664R H764R 65 58 140 140 280 280H679R H779R 80 90 80 80 160 160H6100R H7100R 100 145 150 150 200 200 450 400
1) Medium temperature –10...+5°C with spindle heating2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the
parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted)
Globe valves, PN 6, 120°C LV..A.. NV..A.. SV..A.. AVK..A.. EV..A.. RV..A..
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm
Actuating time(Control) Operating range
3-point AC/DC 24 V 150s/Nominal stroke 3-pointLV24A-TPC NV24A-TPC SV24A-TPC EV24A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK24A-3-TPC AVK24A-3-TPC
AC 230 V 150s/Nominal stroke 3-pointLV230A-TPC NV230A-TPC SV230A-TPC EV230A-TPC
M 150s/Nom. stroke / 35s/Nom. stroke 3-point 3)NVK230A-3 AVK230A-3
modu- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-SZ-TPC NVC24A-SZ-TPC SVC24A-SZ-TPC EVC24A-SZ
lating DC (0) 2...10 VLVC24A-SR-TPC NVC24A-SR-TPC SVC24A-SR-TPC EVC24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-SZ-TPC
DC (0) 2...10 V 3)NVKC24A-SR-TPC
150s/Nominal stroke DC (0) 0.5...10 VLV24A-SZ-TPC NV24A-SZ-TPC SV24A-SZ-TPC EV24A-SZ-TPC RV24A-SZ
DC (0) 2...10 VLV24A-SR-TPC NV24A-SR-TPC SV24A-SR-TPC EV24A-SR-TPC RV24A-SR
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-SZ-TPC AVK24A-SZ-TPC
DC (0) 2...10 V 3)NVK24A-SR-TPC AVK24A-SR-TPC
multi- AC/DC 24 V 35s/Nominal stroke DC (0) 0.5...10 VLVC24A-MP-TPC NVC24A-MP-TPC SVC24A-MP-TPC EVC24A-MF
func- M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVKC24A-MP-TPC
tional 2) 150s/Nominal stroke DC (0) 0.5...10 VLV24A-MP-TPC NV24A-MP-TPC SV24A-MP-TPC EV24A-MP-TPC RV24A-MF
M 150s/Nom. stroke / 35s/Nom. stroke DC (0) 0.5...10 V 3)NVK24A-MP-TPC AVK24A-MP-TPC
Emer
genc
y co
ntro
l fun
ctio
n
Emer
genc
y se
ttin
g po
sitio
n
Flange ISO 7005
PN 16Tmax=120°C 1)
Range of useClosed / open circuits (pH > 7)
3-wayDN
[mm]kvs
[m3/h]∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
∆ps[kPa]
∆pmax[kPa]
H711N 15 0.63 1300 400 1600 400 1600 400
H712N 15 1
H713N 15 1.6
H714N 15 2.5
H715N 15 4 1300
H720N 20 6.3 900 1600
H725N 25 10 500 400 1300
H732N 32 16 350 350 1000 1600
H740N 40 25 150 150 500 400 900
H750N 50 40 70 70 300 300 550 400
H764N 65 58 140 140 280 280
H765N 65 63 400 400 550 400 1100 400
H779N 80 90 80 80 160 160
H780N 80 100 250 250 350 350 700 400
H7100N 100 145 150 150 200 200 450 400
H7125N 125 220 130 130 290 290
H7150N 150 320 80 80 190 190
1) Medium temperature –10...+5°C with spindle heating.
2) MP types: Running times, control signal, stroke limitation and other functions can be parameterized with PC-Tool or the parameterising device MFT-H (delivery condition: modulating, operating range 0.5...10 V)
3) Emergency setting position (NO/NC) manually adjustable at the actuator. Presetting: actuator spindle is retracted H..R, H..B, H..N, H7..X.., H7..Y.. have their closing points at top (valve stem extended) H..S, H6..SP, H6..X.. have their closing points at buttom (valve stem retracted).
Subject to technical changes.
LV..A NV..A SV..A AVK..A EV..A RV..A
500 N15 mm
1000 N20 mm
1500 N20 mm
2000 N32 mm
2500 N40 mm
4500 N40 mm