102
Operating instructions Date Name No. 4600 en Issued: May 31, 2017 C. Balkum Page 1/102 Pages Operation Manual Invertronic compact Inverter (24V DC / 48V DC / 60V DC ) (120Vac) Synchronized single-phase Inverter system (19" rack; HOT-PLUG design, DSP technology)

Invertronic Compact Manual 120Vac 24-48-60Vdc...Operating instructions Date Name No. 4600 en Issued: May 31, 2017 C. Balkum Page 1/102 Pages Operation Manual Invertronic compact Inverter

  • Upload
    others

  • View
    7

  • Download
    2

Embed Size (px)

Citation preview

  • Operating instructions

    Date Name No. 4600 en

    Issued: May 31, 2017 C. Balkum Page 1/102 Pages

    Operation Manual

    Invertronic compact Inverter

    (24VDC / 48VDC / 60VDC)

    (120Vac)

    Synchronized single-phase Inverter system

    (19" rack; HOT-PLUG design, DSP technology)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    2/102 4600 en

    Contents

    1 Preface .................................................................................................................. 9

    2 Presentation ......................................................................................................... 10

    3 Safety .................................................................................................................. 12

    3.1 General safety instructions .................................................................................... 13

    3.1.1 Personnel safety .......................................................................................... 17

    3.1.2 Product safety .............................................................................................. 18

    3.1.3 Special safety measures ............................................................................... 18

    3.2 Transport and storage ........................................................................................... 19

    3.2.1 Storage of inverters ..................................................................................... 21

    3.3 Maintenance, service and faults ............................................................................ 22

    4 Environmental compatibility ............................................................................... 23

    4.1 Packaging ............................................................................................................. 23

    4.2 Disposing of inverters at the end of their life ......................................................... 23

    5 Introduction ......................................................................................................... 24

    5.1 General principle of operation .............................................................................. 26

    6 Technical Data ..................................................................................................... 28

    6.1 Electrical data ....................................................................................................... 28

    6.2 Electrical data ....................................................................................................... 28

    6.2.1 Inverter 24/48/60VDC ................................................................................... 30

    6.2.2 Inverter 110VDC: ......................................................................................... 31

    6.2.3 Electronic changeover device (SBS, ECD) .................................................. 32

    6.2.4 Static bypass (MBS, MCD) ......................................................................... 32

    6.2.5 General data ................................................................................................ 33

    6.2.6 Norms ......................................................................................................... 33

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    3/102 4600 en

    6.3 Dimensions and layout ......................................................................................... 34

    6.3.1 INVERTRONIC compact drawings ............................................................. 34

    6.3.2 System component dimensions .................................................................... 36

    6.3.3 Floor area, floor loading and weight ............................................................ 39

    6.3.4 Recommended inverter installation, minimum distances .............................. 40

    7 INVERTRONIC compact system description ...................................................... 41

    7.1 System configurations .......................................................................................... 41

    7.2 INVERTRONIC compact inverter system components ......................................... 45

    7.2.1 Inverter ........................................................................................................ 45

    7.2.2 Electronic changeover device (SBS, ECD, bypass) ...................................... 48

    7.2.3 Manual bypass switch (MBS) ...................................................................... 52

    7.2.4 MCU 2500 .................................................................................................. 54

    7.2.5 INVERTRONIC compact customer interfaces ............................................. 54

    7.2.6 Software interfaces ...................................................................................... 54

    8 Electrical connection ........................................................................................... 55

    8.1 Behaviour under special operating conditions ....................................................... 56

    8.1.1 Overload ..................................................................................................... 56

    8.1.2 Short circuit on load bar .............................................................................. 56

    8.1.3 Mains supply not in tolerance ...................................................................... 56

    8.1.4 System faults ............................................................................................... 56

    8.1.5 Fan failure ................................................................................................... 56

    8.2 Cable cross sections / Fuses .................................................................................. 57

    8.3 Bus connection ..................................................................................................... 58

    8.4 Terminal connections ........................................................................................... 62

    8.5 System population sequence (fitting modules) ...................................................... 62

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    4/102 4600 en

    9 Configuring the inverter system ........................................................................... 64

    9.1 Electronic changeover device menu structure: ...................................................... 66

    9.1.1 Main menu .................................................................................................. 73

    9.1.2 The "Measured values" menu ...................................................................... 73

    9.1.3 The "Device management" menu ................................................................. 74

    9.1.4 The "System set-up" menu........................................................................... 79

    9.1.5 Entering and changing the user password .................................................... 80

    10 Commissioning the inverter system ..................................................................... 82

    10.1 Inverter system without electronic changeover device ........................................... 82

    10.2 Inverter system with electronic changeover device ............................................... 82

    10.3 Inverter module switch-on sequence ..................................................................... 84

    10.4 Inverter module switch-off sequence .................................................................... 84

    11 Re-configuring the system ................................................................................... 85

    11.1 Upgrading by adding further modules ................................................................... 87

    11.2 Replacing an inverter module ............................................................................... 88

    11.3 Replacing the electronic changeover device (SBS) ............................................... 89

    11.4 Replacing the manual bypass switch (MBS) ......................................................... 91

    12 Status and alarm indicators .................................................................................. 93

    13 Maintenance and service ...................................................................................... 95

    13.1 Manual bypass switch ........................................................................................... 95

    13.2 Terminals and plug-and-socket connectors ........................................................... 97

    13.3 Contactors, relays ................................................................................................. 97

    13.4 Service and fault report ......................................................................................... 99

    13.5 Service hotline .................................................................................................... 101

    13.6 Maintenance and service contracts ...................................................................... 101

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    5/102 4600 en

    14 Circuit diagrams ................................................................................................ 102

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    6/102 4600 en

    List of diagrams

    Figure 1: Symbols 10

    Figure 2: Transporting with forklift truck and crane 19

    Figure 3: Use of lifting eyes 20

    Figure 4: Block diagram 26

    Figure 5: Single and parallel operation of maximum 5 inverters in one shelf 27

    Figure 6: INVERTRONIC compact with 3 inverter modules, MBS and SBS 34

    Figure 7: INVERTRONIC compact with 5 inverter modules 34

    Figure 8: INVERTRONIC compact with 8 inverter modules, SBS, MBS and MCU 35

    Figure 9: Inverter module dimensions 36

    Figure 10: SBS dimensions 36

    Figure 11: Manual Bypass Switch (MBS) dimensions 37

    Figure 12: Shelf dimensions 37

    Figure 13: Populated shelf, with 3 Inverters, SBS and MBS 38

    Figure 14: Populated shelf, 5 inverters 38

    Figure 15: Enclosure PSJ2066 – Dimensions 39

    Figure 16: Floor area and weight 39

    Figure 17: Welding PSJ cabinets 40

    Figure 18: Recommended inverter installation (for PSJ2066) 40

    Figure 19: Parallel operation of Inverters in one shelf 41

    Figure 20: 3 Inverters with SBS and MBS in one shelf 41

    Figure 21: Parallel operation of 15 inverters in 3 sub-systems / (racks) 42

    Figure 22: Parallel operation of 13 inverters, SBS and MBS in 3 sub-systems / (racks) 43

    Figure 23: 3 independent single-phase inverter systems (1 inverter system per equipment rack) 44

    Figure 24: Inverter module 45

    Figure 25: Electronic changeover device (SBS) 48

    Figure 26: INVERTRONIC compact module with MBS and SBS 49

    Figure 27: Section of an INVERTRONIC compact module with MBS and SBS 49

    Figure 28: SBS display 51

    Figure 29: Manual bypass switch assembly (MBS) 52

    Figure 30: Manual bypass switch positions (MBS) 52

    Figure 31: Fault, position of relay contacts 54

    Figure 32: Jumper positions (X700, X701) for parallel operation of max. 5 INV without ECD, 4 INV with SBS

    or 3 INV with SBS and MBS 58

    Figure 33: Jumper positions (X700, X701) for parallel operation of max. 10 INV without SBS or 9 INV with

    SBS, or 8 INV with SBS and MBS 59

    Figure 34: Jumper positions (X700, X701) for parallel operation of max. 15 INV without SBS or 14 INV with

    SBS, or 13 INV with SBS and MBS 60

    Figure 35: Jumper positions when connecting a distribution card and DSP adapter 61

    Figure 36: Shelf with modules and front panel 85

    Figure 37: Shelf with modules, without front panel 85

    Figure 38: Fitting an inverter module 87

    Figure 39: Replacing the electronic changeover device (SBS) 90

    Figure 40: Replacing the manual bypass switch (MBS) 92

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    7/102 4600 en

    List of tables

    Table 1: Abbreviations 11

    Table 2: Conductor cross sections for a 110VDC battery 57

    Table 3: Conductor cross sections for a 220VDC battery 57

    Table 4: INV n | Fault 75

    Table 5: Static bypass | Fault 77

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    8/102 4600 en

    The information given in this operating manual corresponds to the state of de-

    velopment at the time of printing. BENNING takes no responsibility for direct,

    indirect or incidental damage to persons or material caused by wrong interpre-

    tation of or unintended errors in these operating instructions. This document

    may neither be copied nor otherwise reproduced without the explicit written

    consent of BENNING.

    Trademarks:

    All trademarks used are the property of their respective owners.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    9/102 4600 en

    1 Preface

    The operating instructions provide information for the operation and mainte-

    nance of the system. To ensure the safe and correct operation of the system, the

    user should read thoroughly these instructions. All the information contained

    therein must be observed.

    This will avoid:

    • danger during operation

    • risks to the operator

    • downtime, and enhances the reliability and lifespan of the system.

    These instructions should be kept in a safe place for later use.

    BENNING specializes in the development and production of inverter systems.

    The criteria and methods applied by BENNING for development and produc-

    tion comply with the strictest quality standards.

    BENNING has been certified for all areas in accordance with the international

    quality standard ISO9001/EN29001.

    Service Center

    For reasons of operational safety and operational availability, we recommend

    that the devices and systems be regularly maintained.

    Benning committed to excellence in dependability and customer satisfaction.

    If you have any questions or issues, please contact Benning’s Customer Service

    Department at: 1.800.910.3601, Press option #1 or 214.553.1444

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    10/102 4600 en

    2 Presentation

    In this manual, the words converter and inverter are understood to have the

    same meaning.

    The following symbols are used in this manual:

    Denotes instructions, which if not observed could present a risk to

    health, functional capability or safety.

    Warning against dangerous electrical voltage.

    Warning when handling batteries.

    Do not extinguish with water.

    Denotes additional information and instructions.

    Recycling mark

    Identification of assemblies, which are subject to electronic scrap-

    ping regulations.

    Identification of assemblies or parts, which must be disposed of in

    a specific manner. Never dispose of these components in the

    household waste.

    Protect against the effects of the weather

    Fragile.

    This way up.

    Figure 1: Symbols

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    11/102 4600 en

    Explanation of abbreviations used:

    INV Inverter

    SBS Static Bypass Switch

    MBS Manual Bypass Switch

    DSP Digital signal processor

    DC Direct Voltage

    AC Main Mains voltage

    DC Load Load voltage

    AC in Input voltage

    BCU Battery Connection Unit

    BCB Battery Circuit Breaker

    Table 1: Abbreviations

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    12/102 4600 en

    3 Safety

    The connection of the electrical equipment is part of the installation in readi-

    ness for operation. Note that the electrical installation and the connection of the

    inputs and outputs must be carried out in accordance with the local regulations.

    The system must be operated by experienced personnel.

    Protective earth

    The protective earth must be connected before the supply cables are connected.

    The system must not be operated without a protective earth.

    Installation

    This system must be installed by qualified specialists. Only VDE-tested and

    CE-marked mains cables may be used to connect inverters to the building in-

    stallation. This also applies to the connection of the loads. Do not connect any

    loads to the inverter, which could overload the unit. Connecting cables should

    be kept as short as possible. Connect the system using cables of adequate cross

    section. Check the cables for damage to the insulation. Refer to the data sheet

    for the rating of the back-up fuse. Pay attention to the polarity of the DC cable

    connections. All cables must be fixed to the cable clamp rails and relieved from

    stress. Check that all contacts used are securely fitted.

    Hazards such as tripping, crushing, pinching etc. must be avoided.

    Outbreak of fire

    Dangerous voltages are present within the inverter even when fuses have

    blown. For this reason, if fire should break out, do not use water to extinguish

    the fire. Use sand, carbon dioxide or powder extinguishers.

    Personnel training

    All personnel must be trained in how to shut down the system in an emergency.

    To isolate the unit in an emergency, the main fuse in the mains input and the

    battery fuse (battery cabinet or external rack) must be removed. The system

    must be operated by trained (experienced) personnel.

    REFER TO THE INSTALLATION INSTRUCTIONS BEFORE CONNECTING TO THE POWER SUPPLY

    TN513289

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    13/102 4600 en

    3.1 General safety instructions

    These operating instructions and the safety instructions contained there-

    in must be carefully read before the system (also referred to as the in-

    verter) is installed or put into operation. The operating instructions must

    always be kept close to the unit for later reference.

    Installation, operation, maintenance and repair of the inverter sys-

    tem may only be carried out by qualified and trained specialists.

    You must be absolutely sure that L and N and the polarity of the battery

    connections are correct, as any incorrect connections will cause damage

    to the system.

    Make absolutely sure that the battery is not earthed. Neither the plus nor

    the minus pole must be earthed (battery floating).

    Earth faults on unearthed batteries necessitate a protective device for

    each pole.

    Units must be fitted in the rack in the following order. The SBS is al-

    ways fitted at the extreme right-hand end of the rack, the MBS on the

    left next to the SBS, and the inverters must be fitted from left to right.

    Even when the inverter is switched off, components within the system

    are live as long as the supply network and/or battery and connected.

    Live parts are exposed when you open the housing or remove covers;

    danger to life if touched! Refit the covers properly on completion of the

    work.

    BENNING takes no responsibility for consequential damage caused by

    work incorrectly carried out on the inverter system.

    High fault currents (leakage currents):

    A proper earth connection must be ensured before the mains is connect-

    ed!

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    14/102 4600 en

    This inverter complies with norm EN 55022 Class B

    This is a product for commercial and industrial use in the second envi-

    ronment. Restrictions regarding the installation or additional measures

    may be necessary to prevent interference.

    A suitable isolating device must be provided in all supply circuits.

    It must be possible to disconnect all poles of the battery supply.

    As standard, the inverter system is suitable only for mounting on fire-

    resistant surfaces.

    Unused module slots must be fitted with a blanking plate. (Part No.

    514414)

    CAUTION! The electronic changeover device (SBS) may only be removed from the

    rack if the manual bypass switch (MBS) is logged on.

    CAUTION! Initially withdraw modules from the rack by 50 mm (plug disconnect-

    ed). Then wait for at least 10 seconds. Only then remove the units com-

    pletely from the rack.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    15/102 4600 en

    CAUTION!

    An inverter system with an SBS may only be used on earthed networks. Once

    the unit has been installed and commissioned, the earthed mains point or neu-

    tral conductor must not be disconnected. The neutral conductor of the bypass

    supply and the neutral conductor of the load must always be linked in the in-

    verter system.

    In inverter systems without SBS, the neutral conductor of the inverter output

    must be connected to the protective conductor terminal. If an SBS is fitted to

    such a system retrospectively, this link must be removed and the requirements

    for an inverter system with SBS apply.

    For connecting the INVERTRONIC compact, terminal strips for power con-

    nections (mains, load, battery) are provided in the bottom third of the cabinet.

    Access to the terminals is obtained by undoing the screws and removing the

    front protective covers.

    The cables can be routed to the cabinet from all four sides and fed in through

    the cabinet bottom. A double floor in the installation area is not absolutely es-

    sential. Please refer to the following tables and drawings for information on

    where the cables are to be connected and what size they must be in accordance

    with DIN VDE 0298.

    You must be absolutely sure that the neutral conductor and the phase sequence

    of the bypass supply and the polarity of the battery connections are correct, as

    any incorrect connections will cause damage to the system.

    Be sure to refit the front protective covers when assembly is complete.

    A clear inscription, which provides adequate information as to how the

    whole installation is to be isolated, must be fitted to every isolating de-

    vice.

    Be sure to observe all the safety instructions!

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    16/102 4600 en

    Within locked battery rooms:

    If the inverter is located in a locked battery room, a warning notice

    must be attached to all upstream isolating switches external to the in-

    verter.

    The warning notice should carry the following or similar wording:

    Outside locked battery rooms:

    If the inverter is located outside a locked battery room, a warning notice

    must be attached to all upstream primary supply isolating switches ex-

    ternal to the inverter to inform electricians that the circuit concerned

    feeds an inverter.

    The warning notice should carry the following or similar wording:

    If you should require more warning notices, contact our service centre under

    telephone number:

    1-800-910-3601 and Press #1

    TN: 10007161 – Warning notice within locked battery rooms

    TN: 10007163 – Warning notice outside locked battery rooms

    TN: 513289 – Information at the point of connection

    TN: 10007164 – Isolate the inverter

    SWITCH OFF ALL SUPPLIES TO THE UNIT

    BEFORE STARTING WORK ON THIS EQUIPMENT.

    TN10007161

    SWITCH OFF THE INVERTER BEFORE STARTING WORK ON THIS CIRCUIT.

    TN10007163

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    17/102 4600 en

    3.1.1 Personnel safety

    The inverter must be installed in a room with limited access rights (qualified

    personnel as defined by the norm EN62040-1-2).

    If the isolator for the supply cable is not located in the same room as the

    inverters, a warning notice must be attached to the inverters with the in-

    scription:

    Dangerous voltages are present within the inverters. The unit must only be

    opened by qualified personnel.

    CAUTION! Initially withdraw modules from the rack by 50 mm (plug disconnect-

    ed). Then wait for at least 10 seconds. Only then remove the units com-

    pletely from the rack.

    Caution: A dangerous voltage is still present on the battery isolator (BCB)

    when the inverters are withdrawn.

    In order to avoid any accidents, it is essential to follow the instructions below:

    • Do not operate the inverter if the temperature and humidity exceed the specified maximum values.

    The inverter must be earthed.

    It must be disposed of in accordance with the applicable local regulations.

    ISOLATE THE INVERTER BEFORE WORKING ON THIS EQUIPMENT!

    TN10007164

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    18/102 4600 en

    3.1.2 Product safety

    • The electrical supply cable must be protected by a backup fuse, which is accessible at all times.

    • Do not install the inverter in the vicinity of liquids or in an environment with too high humidity.

    • Do not allow liquids or foreign bodies to get into the system.

    • Do not cover the air vents of the inverter.

    • Do not subject the inverter to direct sunlight or other sources of heat.

    • Units must be fitted in the rack in the following order. The SBS is always fitted at the extreme right-hand end of the rack, the MBS on the left next

    to the SBS, and the inverters must be fitted from left to right.

    3.1.3 Special safety measures

    Be sure to observe the connection instructions in this manual. Check the infor-

    mation on the equipment rating label. This must correspond with your electri-

    cal supply network and the total power demand of the connected unit.

    If the inverter should be put into storage before use, make sure that the storage

    location is clean and dry. The storage temperature must be in the range -10°C

    to +45°C. The inverter has been designed for normal ambient conditions such

    as those stated in Chapter 6.1.5 under installation altitude, operating tempera-

    ture and relative humidity, and for the stated transportation and storage condi-

    tions.

    Although correct operation is guaranteed if the inverter is operated at the limits

    of the specified values, the life of some components may be shortened.

    Special protective measures must be taken if unusual operating conditions pre-

    vail:

    • Moisture, steam, saline environment, dripping water or outdoor installa-tion,

    • Explosive mixtures of dust and gas

    • Severe temperature fluctuations

    • Poor ventilation

    • Heat conducted or radiated from other heat sources

    • Strong electromagnetic fields

    • Radioactivity which exceeds the natural level of radiation

    • Fungi, insects, parasites, etc.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    19/102 4600 en

    3.2 Transport and storage

    The inverter must only be transported to the intended location in its original

    packaging. The same applies for removals or returns. The unit must only be

    transported and stored in an upright position. Make sure that the unit is shipped

    in the correct transport position and take the centre of gravity into account. In

    the case of inverter systems, slight changes in position can lead to the units

    suddenly toppling due to the heavy weight. It must also be ensured that the

    units have a firm footing when placed in storage.

    The unit is delivered complete from the factory. The unit must always be trans-

    ported in an upright position. If the unit is transported with a forklift truck, then

    the forks must always be applied from the rear of the unit so that the front door

    with its instruments is not damaged.

    Figure 2: Transporting with forklift truck and crane

    Unpacked units must only be transported in a closed lorry. The units must al-

    ways be securely anchored to prevent them from slipping or toppling over. In

    particular, it must be ensured that the paintwork is protected against scuffing

    and scratching. Lifting belts must be used when transporting the unit in an un-

    packed state. These must be positioned so that the instruments and switches on

    the front door cannot be damaged.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    20/102 4600 en

    The information shown in Figure 3 must be observed when transporting the

    unit using lifting eyes.

    Figure 3: Use of lifting eyes

    Lifting eyes must only be used with the protective cover and bolts re-

    moved.

    When the units have been unloaded on site, they must be inspected immediate-

    ly for possible damage. It must also be checked that all parts according to the

    packing list are present. In the event of damage, the responsible party must be

    identified – if possible – and in all cases a written report must be immediately

    sent to the supplier/manufacturer (within 6 working days).

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    21/102 4600 en

    3.2.1 Storage of inverters

    The ability of the units to be stored depends on the selected packaging.

    Units with short-term packaging should be unpacked immediately on arrival at

    the intended location and stored in a suitable place. In doing so, the tempera-

    ture must not be allowed to drop too low or condensation allowed to form.

    When the units are placed in store, the doors should be opened for a few hours

    to allow the units to adapt to the new temperature without the formation of

    condensation. If the units are placed into interim storage for an extended peri-

    od, they must be covered with film and inspected for condensation from time to

    time.

    When units are supplied with long-term packaging, they must be stored in this

    packaging. When doing so, the packaging must first be checked for damage.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    22/102 4600 en

    3.3 Maintenance, service and faults

    CAUTION! – Risk of electric shock!

    Even when isolated from the mains supply, the inverter is still connected to the

    battery circuit and is at a dangerous voltage potential. Therefore, disconnect the

    battery circuit and check that the equipment is dead before carrying out service

    or maintenance work.

    Work may only be carried out on batteries by persons with the appropriate spe-

    cialist knowledge of the required safety rules and must be supervised. Unau-

    thorised personnel must be kept away from batteries.

    The following safety rules must be observed when working on inverters:

    • Wristwatches, rings and other metal objects must be removed

    • Use only insulated tools

    • Inverters must not be dismantled

    If you require a system check at regular intervals for safety reasons, e.g. an an-

    nual inspection, then please contact us. We will be pleased to submit a quota-

    tion for an appropriate contract.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    23/102 4600 en

    4 Environmental compatibility

    BENNING is particularly concerned with the environmental compatibility of

    its products and therefore adopts an eco-project engineering approach for the

    whole life of the inverters.

    4.1 Packaging

    Please observe the relevant local regulations for the recycling of packaging.

    4.2 Disposing of inverters at the end of their life

    We recommend that the relevant local regulations for the disposal and recy-

    cling of the components be observed when the life of the inverters has expired.

    Should you have any questions or concerns please contact Benning’s Customer

    Service line.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    24/102 4600 en

    5 Introduction

    This manual provides information on the INVERTRONIC compact inverter

    system, their principle of operation and the action to be taken in the event of

    operational faults. This manual also contains information relating to the trans-

    portation, storage, handling and installation of inverter systems. The planning

    guidelines in this manual relate only to the special requirements of inverter sys-

    tems. It is essential that the national and local regulations for electrical installa-

    tions be followed when installing the equipment.

    The content of this manual may change due to advancing technology. We have

    strived to make the content as correct and clear as possible. If errors should

    have occurred however, we would be grateful for information provided to up-

    date on the next release.

    We accept no liability for errors in this manual and for consequences resulting

    therefrom.

    The inverter system (inverter) is designed to protect sensitive electrical equip-

    ment against interference, which can occur due to poor current/voltage quality,

    or even loss of supply. Sensitive systems require comprehensive protection

    against electrical faults.

    These can be external faults (e.g. thunderstorms, operational faults) or interfer-

    ence from adjacent equipment (e.g. motors, welding systems etc.). Mains faults

    can be summarised as follows:

    • Fast and slow mains voltage peaks and variations

    • Mains failure

    • Fast and slow frequency peaks and variations

    • Signals or transients superimposed on the supply

    The inverter system conditions the mains voltage and ensures a constant output

    voltage.

    When the inverter is in operation, mains interference is therefore kept away

    from operationally critical equipment, and software and hardware cannot be

    damaged.

    CAUTION!

    THE INVERTER MUST ONLY BE INSTALLED AND OPERATED BY QUALIFIED PERSONNEL.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    25/102 4600 en

    For customer service requirements our service centre can be contacted under

    the telephone number

    1-800-910-3601 Press #1

    You can write to our service center at the following address:

    Benning Power

    1220 Presidential Drive, Suite 100

    Richardson, TX 75081

    For general product inquiries, you can contact us on the following numbers:

    Phone: 214-553-1444

    Fax: 214-553-1355

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    26/102 4600 en

    5.1 General principle of operation

    The inverter system from the INVERTRONIC compact product family is a

    compact AC power supply for widely differing applications in the telecommu-

    nications and industrial fields. The different system configurations enable the

    system to be matched to the specific requirements.

    Depending on the design, the output power of the inverter system can be ex-

    panded in 1000VA (24Vdc) or 2000VA (48 and 60Vdc) increments by plug-

    ging further inverters into the shelf’s. The nominal DC input voltages can be

    24Vdc, 48Vdc or 60Vdc.

    System states can be set up and read off on the SBS LCD display. It is possible

    to display measured values for the mains supply, the loads and the individual

    system components.

    With the help of a manual bypass switch (MBS), the inverter system can be

    maintained, expanded and repaired without interrupting the supply to the con-

    nected loads.

    The inverter system is controlled and monitored by digital signal processors

    (DSP), which are programmed with appropriate algorithms.

    Individual components communicate with one another by means of a CAN-

    BUS system (Controller Area Network), which guarantees a high level of im-

    munity against interference.

    By means of serial interfaces, the system states can be determined when carry-

    ing out a service, and during software updates.

    Figure 4: Block diagram

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    27/102 4600 en

    Widely differing systems with regard to power, freedom from interruption and

    redundancy can be assembled using the individual components of the inverter

    system in a similar way to a building block system.

    Only inverters with the same KVA rating, input voltage and output voltage can

    be connected in parallel.

    Up to 5 inverters can be connected in parallel in an appropriate shelf without an

    SBS and MBS.

    Figure 5: Single and parallel operation of maximum 5 inverters in one shelf

    In the case of simple parallel operation of inverters, the maximum system pow-

    er is 8kVA (24Vdc) or 16 kVA (48 and 60Vdc). Here 8 inverters are connected

    in parallel divided between 2 equipment shelves.

    With parallel operation, it is essential to ensure that the shelfs are

    mounted one above the other.

    A Manual Bypass Switch (MBS) is always incorporated in all inverter

    systems with a Static Bypass Switch (SBS). This enables the system to

    be maintained and repaired without interrupting the supply to the loads.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    28/102 4600 en

    6 Technical Data

    6.1 Electrical data

    Module output power: 1000VA

    General inverter data

    Output power 1000VA, single phase,

    PF = 0.8

    DC-DC converter using MOSFET technology

    Single-phase inverter using IGBT technology

    Input voltage: 24VDC

    Output voltage: 110 to 127Vac, at 50 or 60Hz

    General bypass data

    • SBS incorporates thyristor technology

    • MBS (rotary switch)

    • INVERTER fault and SBS fault alarms via voltage-free contacts

    • Service interface, RS 232 interface on Manual Bypass Switch (MBS)

    6.2 Electrical data

    Module output power: 2000VA

    General inverter data

    Output power 2000VA, single phase,

    PF = 0.8

    DC-DC converter using MOSFET technology

    Single-phase inverter using IGBT technology

    Input voltage: 48VDC and 60VDC

    Output voltage: 110 to 127Vac, at 50 or 60Hz

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    29/102 4600 en

    General bypass data

    • SBS incorporates thyristor technology

    • MBS (rotary switch)

    • INVERTER fault and SBS fault alarms via voltage-free contacts

    • Service interface, RS 232 interface on Manual Bypass Switch (MBS)

    System description

    The INVERTRONIC compact inverter system is a compact AC power supply

    for different applications in the telecommunications and industrial fields. The

    various system configurations enable the system to be matched to the specific

    requirements.

    The output power of the inverter system can be extended in 1000 VA steps for

    an input voltage of 24Vdc or 2000 VA for an input voltage of 48Vdc or 60Vdc

    by inserting inverter modules (INV). The inverter system is controlled and

    monitored by digital signal processors (DSP).

    Individual components communicate with one another by means of a CAN-

    BUS system (Controller Area Network), which guarantees a high level of im-

    munity against interference.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    30/102 4600 en

    6.2.1 Inverter 24/48/60VDC

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    31/102 4600 en

    6.2.2 Inverter 110VDC:

    2 Inverter 110VDC / TN121082 2.1 Type Inverter

    2.2 Project INVERTRONIC compact 1500

    2.3 Part No. 121082

    2.4 Type G110E230/6,52/2...3rfg-PWT

    2.5 Input voltage 110VDC

    2.6 Switching thresholds 93.5V ; 113.0V ; 132.0V ; 155.0V

    2.7 Permissible deviation -15 ... +40% of nominal value

    2.8 Input current: 12A (at rated active power and rated input voltage = 100%)

    8.3A (at rated active power and overvoltage = 140%)

    14A (at rated active power and undervoltage = 85%)

    300mA on no load at rated voltage

    2.9 Permissible ripple 5% eff.

    2.10 Rated power: 1.5kVA (at cos phi = 0.8)

    2.11 Rated output active power 1.2kW (at cos phi = 1)

    2.12 Rated output voltage 220 / 230 / 240 VAC

    2.13 Voltage tolerance ±1% steady-state

    2.14 Rated output current 6.8 / 6.52 / 6.25 A

    2.15 Rated output frequency 50Hz or 60Hz (switchable on SBS, ECD)

    2.16 Efficiency

    91.4% at 100% load "provisional"

    91.0% at 75% load "provisional" 89.7% at 50% load "provisional"

    85.6% at 25% load "provisional"

    2.17 Power loss 98W at 100% load "provisional"

    typ. 33W at 0% load

    2.18 Permissible power factor cos phi = 0.7ind. to cos phi = 0.8cap.

    2.19 Settling time < 20 milliseconds

    2.20 Transformer Isolating transformer provided in DC/DC converter

    2.21 Frequency tolerance

    Mains commutated: max. ±5% (with external electronic changeover device

    only)

    self commutated: ±0.1% (quartz-controlled)

    2.22 Distortion factor (EN 62040-1)

    16.5Aeff for 4 sec

    Switch-off after max 4 sec if the bypass voltage is not available. Inverter itself is short-circuit proof. ???

    (EN 62040-1-1)

    2.26 Overload capability – continuous

    110% IN (at 25°C)

    2.27 Output fuse T10A/250V (high rupturing capacity)

    2.28 Load fuse The short-circuit current can blow slow-acting fuses with 1/3 the nominal

    current rating (e.g. for Neozed)

    2.29 Changeover device None

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    32/102 4600 en

    6.2.3 Electronic changeover device (SBS, ECD)

    3 Electronic changeover device (SBS, ECD) / TN121083 3.1 Type Changeover device

    3.2 Project INVERTRONIC compact 1500

    3.3 Part No. 121083

    3.4 Type EUE115...230/100/2...3/110/220T

    3.5 Input voltage 110VDC / 220VDC

    3.6 Permissible deviation -15 ... +25%

    3.7 Nominal mains voltage 220 / 230 / 240 VAC

    3.8 Nominal mains frequency 50 / 60Hz

    3.9 Permissible frequency range ±5% (inverter synchronisation range)

    3.10 Inverter rated voltage 220 / 230 / 240 VAC

    3.11 Rated output voltage 220 / 230 / 240 VAC

    3.12 Voltage tolerance ±15% (steady-state for mains operation)

    ±1% (steady-state for inverter operation)

    3.13 Output frequency 50 / 60Hz

    3.14 Max. frequency deviation ±5% (for mains operation)

    50 / 60Hz ±0.1% (under quartz control)

    3.15 Max. output current 100A

    3.16 Overload behaviour 120% for 10 minutes

    1000% for 10 milliseconds

    3.17 Permissible power factor cos phi = 0.7ind. to cos phi = 0.8cap.

    3.18 Mains fuse max. 125AgL (upstream)

    3.19 Load fuse Ensure selectivity with the chosen mains fuse when fusing the load cir-

    cuits.

    3.20 Changeover time

    2 ms ( typical value)

    max. 1.5 ms...4 ms (depending on the phase relationship of the mains sup-

    ply)

    3.21 Reset 0 ms reset at phase zero crossover

    3.22 Operating mode Inverter priority / Mains priority (switchable)

    3.23 Type of fault alarm Common fault, SBS fault (ECD) and inverter fault

    The minimum interruption times are equal to the changeover times. Interruption times may be longer de-

    pending on the mains impedance, the fuses used, cable lengths, etc.

    6.2.4 Static bypass (MBS, MCD)

    4 Manual bypass switch (MBS, MCD) / TN10000863 4.1 Type Changeover device

    4.2 Project INVERTRONIC compact 1500

    4.3 Part No. 10000863

    4.4 Type MBS115...230/100/2...3/T

    4.5 Max. switching current 100A

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    33/102 4600 en

    6.2.5 General data

    5 General data 5.1 Protection class IP 20 (DIN/VDE 0470 Part 11/92, IEC529), higher on request

    5.2 Insulation class DIN/VDE 0110, overvoltage category 2

    5.3 EMC class DIN EN55022 class B

    5.4 Design (module) Hot Plug in Benning cabinet

    5.5 Cable entry (cabinet) From below; optionally from above

    (by means of cable cabinet, width 200 mm)

    5.6 Cooling Force cooled, fan temperature-controlled and monitored

    Fans can be replaced from the front of the inverter

    Power block is monitored against over-temperature (fault alarm)

    5.7 Inlet air temperature 0°C to 40°C

    27°F to 104°F

    5.8 Limitation above 40°C, 104°F 12.5% per 5° (max. 50°C, 114°F)

    5.9 Relative humidity 0 to 95% (non-condensing)

    Class DIN/IEC 721 2-1-09/86

    5.10 Storage temperature -40°C to 85°C

    -40°F to 185°F

    5.11 Installation altitude up to 2000m ASL without limitation

    5.12 Connection method Backplane (Hot – Plug)

    5.13 Dimensions (H X W X D) 3 U; 1/5 19-inch; 300mm

    85.6 x 132.6 x 301.5mm

    5.14 Weight ca. 3.1kg per inverter module, ca. 2.9kg per ECD/MBS module

    5.15 Finish RAL 7035 / other finishes on request

    5.16 Protection class I

    5.17 Noise Noise level (1 metre)

    Dependent on configuration level, load and environment 50dB (A) in normal operation (5 x inverter in one rack)

    65dB (A) at full load and overtemperature

    5.18 Individual relay contacts with

    SBS, ECD only

    (voltage-free changeover)

    1 x SBS, ECD – Fault

    1 x Inverter – Fault

    5.19 Interfaces RS232 or CAN on SBS (ECD)

    6.2.6 Norms

    6 Norms 6.1 Norms EN 60950, 2006-11 / UL 60950 Compliant

    EN 55022 class B

    EN 61000-4-4, 2005-07, level 4. Burst, Rectifier Input: (4kV) EN 61000-4-4, 2005-07, level 4. Burst, Bypass Input: (4kV)

    EN 61000-4-4, 2005-07, level 4. Burst, System Output: (4kV)

    EN 61000-4-5, 2007-06, level 4. Surge, Rectifier Input:

    (2kVsym. / 4kVasym.)

    EN 61000-4-5, 2007-06, level 4. Surge, Bypass Input:

    (2kVsym. / 4kVasym.)

    EN 61000-4-5, 2007-06, level 4. Surge, System Output:

    (2kVsym. / 4kVasym.)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    34/102 4600 en

    6.3 Dimensions and layout

    6.3.1 INVERTRONIC compact drawings

    Figure 6: INVERTRONIC compact with 3 inverter modules, MBS and SBS

    Figure 7: INVERTRONIC compact with 5 inverter modules

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    35/102 4600 en

    Figure 8: INVERTRONIC compact with 8 inverter modules, SBS, MBS and MCU

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    36/102 4600 en

    6.3.2 System component dimensions

    Inverter module dimensions:

    Abluft

    Exhaust air Zu luft

    Ventilation

    301,5

    1,585,6

    132,6

    123

    83,8

    Figure 9: Inverter module dimensions

    Static Bypass Switch (SBS) dimensions:

    Abluft

    Exhaust a ir

    Zuluft

    Ventilation

    85,6

    301,5

    1,5 83,8

    132,6

    123

    Figure 10: SBS dimensions

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    37/102 4600 en

    Manual Bypass Switch (MBS) dimensions:

    85,6 1,5

    301,5

    83,5

    132,6

    123

    Figure 11: Manual Bypass Switch (MBS) dimensions

    Shelf dimensions:

    132,5

    372,4

    2

    481,0

    329,4

    Figure 12: Shelf dimensions

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    38/102 4600 en

    Populated shelf:

    481,0

    372,4

    2

    132,5

    329,5

    Figure 13: Populated shelf, with 3 Inverters, SBS and MBS

    481,0

    372,4

    2

    329,4

    132,5

    Figure 14: Populated shelf, 5 inverters

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    39/102 4600 en

    6.3.3 Floor area, floor loading and weight

    Design:

    Equipment cabinet: PSJ cabinet, Type: PSJ 2066

    Shelfs: see Figure 14

    INTERIOR VIEW OF DOOR

    B T

    H

    Height

    H

    Width

    B

    Depth

    T

    2000

    600

    600

    Other designs possible at

    customer's request

    Figure 15: Enclosure PSJ2066 – Dimensions

    140

    LAT

    60

    IT T

    LB

    LAB

    B

    30

    Cabinet type: PSJ 2066

    B - inches 23.62

    LB – inches 521.65

    LAB – inches 21.65

    T - inches 23.62

    LT – inches 20.08

    LAT - inches 18.90

    Cabinet Weight - without

    modules

    176.37 Ibs.

    (cab)

    Weight - per module 6.83 Ibs.

    Figure 16: Floor area and weight

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    40/102 4600 en

    If the unit has to be welded in place, please refer to the information in Figure 18

    Figure 17: Welding PSJ cabinets

    6.3.4 Recommended inverter installation, minimum distances

    >600

    INVERTRONIC

    compact

    >=0 min. 600

    Zuluft

    Ventilation

    Abluft

    Exhaust air

    Figure 18: Recommended inverter installation (for PSJ2066)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    41/102 4600 en

    7 INVERTRONIC compact system description

    7.1 System configurations

    Different systems with regard to power, freedom from interruption and redun-

    dancy can be assembled using the components of the inverter system.

    The simplest systems are single operation (1 inverter) and the parallel opera-

    tion of several inverters without electronic changeover device (SBS, ECD).

    Only inverters with the same input and output voltage can be connected in par-

    allel.

    Up to 5 inverters can be connected in parallel in an appropriate shelf.

    Figure 19: Parallel operation of Inverters in one shelf

    System

    Inv 1 Inv 2 Inv 3

    MBS SBS

    UDC

    UAC, Load

    =~

    = =~ ~

    UAC, Mains

    Figure 20: 3 Inverters with SBS and MBS in one shelf

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    42/102 4600 en

    II.

    Inv 1.2 Inv 2.2 Inv 3.2 Inv 4.2 Inv 5.2

    UD

    C

    UA

    C, Load

    =~

    = = = =~ ~ ~ ~

    =~

    =~

    =~

    =~

    =~

    =~

    =~

    =~

    =~

    =~

    I.

    III.

    Inv 1.1 Inv 2.1 Inv 3.1 Inv 4.1 Inv 5.1

    Inv 1.3 Inv 2.3 Inv 3.3 Inv 4.3 Inv 5.3

    System

    Figure 21: Parallel operation of 15 inverters in 3 sub-systems / (racks)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    43/102 4600 en

    In the case of parallel operation of inverters, the maximum system power is

    15.0 kVA or 30kVA. Above are 15 inverters connected in parallel divided be-

    tween 3 identical shelves.

    In order to increase the reliability of the supply to the loads, an SBS can be in-

    corporated into the inverter system. Three inverters, one SBS and one MBS can

    then be installed in a shelf accommodating these modules. They are installed in

    the right two positions in the shelf. The maximum number of inverters is re-

    duced to 13 modules. The maximum system power is 13.0 kVA for the 24Vdc

    module or 26kVA for the 48/60Vdc type modules.

    A shelf with SBS and MBS positions is always incorporated in all inverter sys-

    tems with an electronic changeover device. This enables the system to be main-

    tained and repaired without interrupting the supply to the loads. A system con-

    figuration with SBS and MBS is recommended as the default configuration on

    account of the increased reliability of the extended measuring and control func-

    tions.

    Figure 22: Parallel operation of 13 inverters, SBS and MBS in 3 sub-systems / (racks)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    44/102 4600 en

    System 1

    Inv 1.1 Inv 1.2 Inv 1.3

    MBS 1 SBS 1

    UDC1

    UAC1, Load

    =~

    = =~ ~

    UAC1, Mains

    System 2

    Inv 2.1 Inv 2.2 Inv 2.3

    MBS 2 SBS 2

    UDC2

    UAC2, Load

    =~

    = =~ ~

    UAC2, Mains

    System 3

    Inv 3.1 Inv 3.2 Inv 3.3

    MBS 3 SBS 3

    UDC3

    UAC3, Load

    =~

    = =~ ~

    UAC3, Mains

    Figure 23: 3 independent single-phase inverter systems (1 inverter system per equipment

    rack)

    Each shelf can be configured independently enabling independent single-phase

    systems to be realised within a cabinet configuration.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    45/102 4600 en

    7.2 INVERTRONIC compact inverter system components

    The system comprises the following main components:

    7.2.1 Inverter

    Abluft

    Exhaust air Zuluft

    Ventilation

    Figure 24: Inverter module

    General - The direct voltage is converted into a single-phase alternating voltage

    with constant amplitude and stable frequency in the inverter. A high efficiency

    is achieved even in the partial load range using pulse width modulation and

    IGBT power transistors. The failure of a component or the power stage does

    not lead to an interruption in the supply to the load. The inverter is disconnect-

    ed from the busbar and the load is switched to the mains supply without inter-

    ruption by means of the electronic changeover device. A fault is indicated at

    the same time.

    Output - The waveform (sine wave) of the output voltage is controlled by

    means of software by a microcontroller (DSP = digital signal processing). This

    keeps the distortion factor low, particularly in the case of a non-linear load.

    The output is fed via filter circuits and protected by a fuse. In the event of a

    short circuit, the short-circuit-proof inverter delivers a short-circuit current of

    >250% and switches off and remain off after 4 seconds.

    Neutral conductor - The neutral conductor of the inverter output is electrically

    isolated from the inverter enclosure.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    46/102 4600 en

    Frequency control - The inverter output frequency is controlled by a PLL,

    which depending on the operating state of the system, guarantees synchronisa-

    tion with the internal clock pulse, the mains supply (only when an SBS/ECD is

    provided) or parallel inverters.

    If the controlling frequency (bypass supply) deviates by more than the adjusta-

    ble value of a minimum of ± 1% and a maximum of ± 5%, the system switches

    to the internal clock pulse and then ensures that the frequency remains constant

    ± 0.1%.

    LEDs for indicating the inverter module states:

    LED Colour Meaning

    red Fault

    green Output voltage present and connected

    to load / SBS

    Green LED illuminates:

    Voltage on output,

    load less than 90% of max. power

    Green LED flashes:

    Voltage on output,

    the inverter is close to the load limit >

    90%

    Green LED flashes and red LED

    illuminates:

    Voltage on output,

    load > 100% (overload indication)

    Red LED illuminates:

    Inverter fault,

    no voltage on output

    Green and red LEDs flash:

    Voltage on output, inverter is being ad-

    dressed via the display (SBS, ECD)

    When connected, all connectors on the back panel are at mains potential.

    Dangerously high voltages can also be present on the connectors even

    when disconnected due to charged capacitances within the unit.

    All ventilation openings must be free in order to achieve adequate cool-

    ing.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    47/102 4600 en

    Inverter module connections:

    1

    2

    3

    456

    7

    Item Meaning

    1 Battery +

    2 Battery -

    3 Communication and data connections

    4 PE

    5 N – Out

    6 L – Out

    7 Service interface

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    48/102 4600 en

    7.2.2 Electronic changeover device (SBS, ECD, bypass)

    Abluft

    Exhaust air

    Zu luft

    Ventilation

    Figure 25: Electronic changeover device (SBS)

    The electronic changeover device (static switch) consists of two static micro-

    processor-controlled (DSP) thyristor modules (2 anti parallel thyristors) in the

    mains bypass and in the inverter path. If the output voltage deviates from the

    set values by an appropriate amount (e.g. in the case of an inverter fault), they

    switch the connected loads automatically and without interruption to the bypass

    supply. The bypass has an overload capability of 120% for 10 min and 1000%

    for 10 ms.

    The static switch automatically switches the load back to the inverter when

    normal operation is resumed (e.g. after an overload or a short circuit).

    In synchronous mode, the changeover from inverter to mains and back again

    takes place absolutely without interruption at a zero crossover.

    The thyristors are fused in the connection panel.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    49/102 4600 en

    Electronic changeover device instrumentation:

    The electronic changeover device is controlled by means of 4 buttons.

    A mimic diagram in which the power flow is shown is displayed on the graph-

    ical LCD display.

    The operating state and any operational faults are indicated by means of the

    LCD panel. The LCD display is also used for reading off information or for

    clear guidance by means of the menu. Important menu items are protected by a

    password.

    The display and operating unit with LCD display displays the following meas-

    urements:

    Inverter: Input voltage, output voltage and output current

    Bypass: Load voltage, current, frequency, power and mains voltage

    ~

    ~

    ~~

    Figure 26: INVERTRONIC compact module with MBS and SBS

    ~

    Figure 27: Section of an INVERTRONIC compact module with MBS and SBS

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    50/102 4600 en

    SBS module state indicators

    1

    2

    LED Colour Meaning

    red Continuous: Fault active

    Flashing: Fault no longer active

    green Running/Ready for operation

    1 Display for indicating different system states and measured values

    2 Keys for operating the display menu

    All connections and controls for the electronic changeover device are accessi-

    ble from the outside. There are no components inside the unit that users need to

    access for normal operation.

    SBS module connections:

    2 1

    34

    5

    6

    7

    89

    Item Meaning

    1 PE

    2 Output

    3 Mains L

    4 Inverter L

    5 Battery +

    6 Battery-

    7 Communication and data connections

    8 PE

    9 N

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    51/102 4600 en

    7.2.2.1. SBS graphical display

    All states and measured values of the power supply system can be interrogated

    by means of the 4 buttons on the graphic display. Safety-critical menu levels

    are accessible by means of passwords. The use of the input keys and the mean-

    ing of the displayed states will be explained later.

    ~

    ~

    ~~

    ~

    ~

    ~~

    1 2 3

    4567

    Figure 28: SBS display

    In the initial state, the display always shows the schematic diagram for the in-

    verter system. Each symbol has its assigned meaning and provides information

    on the system state in different ways.

    1 Mains voltage symbol

    2 MBS symbol for mains bypass

    When the contact is closed and the symbol flashes, the mains bypass

    is active (only visible when the MBS is logged on)

    3 SBS symbol

    Inverter operation or mains operation is indicated depending on the

    position of the switch element. (Here: Inverter operation)

    4 Load voltage symbol; inverter system output voltage

    5 MBS symbol for inverter bypass

    When the contact is closed and the symbol flashes, the inverter bypass

    is active (only visible when the MBS is logged on)

    6 Symbol for the inverter(s) in the system

    7 Inverter input voltage symbol

    A tick after a symbol indicates the correct state/operation. A flashing symbol

    indicates a faulty state/operation.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    52/102 4600 en

    7.2.3 Manual bypass switch (MBS)

    Figure 29: Manual bypass switch assembly (MBS)

    The manual bypass switch assembly is always fitted on the left of the electron-

    ic changeover device in the shelf. (See, for example, Figure 7 or 14). The man-

    ual bypass switch, electronic changeover device and inverter modules are cov-

    ered by a screwed front panel.

    The main operating instructions can be found on this panel.

    In standard ECD mode (switch position 0), the electronic changeover device

    should not be withdrawn from the shelf. This would cause the supply to the

    loads to be interrupted.

    Meaning of the switch positions:

    Position 0: ECD (change-over de-

    vice) mode:

    Position 1: Mains bypass

    Position 2: Inverter bypass

    Figure 30: Manual bypass switch positions (MBS)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    53/102 4600 en

    MBS module connections:

    1 2

    Item Meaning

    1 CAN – Bus (service interface)

    2 RS232 (service interface)

    2 1

    34

    5

    67

    Item Meaning

    1 PE

    2 Output

    3 Mains L

    4 Inverter L

    5 Communication and data connections

    6 PE

    7 N

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    54/102 4600 en

    7.2.4 MCU 2500

    The MCU 2500 can be connected to the INVERTRONIC compact system ret-

    rospectively by means of the DSP adapter. You will find the configuration and

    operation of the MCU 2500 in the separate operating manual

    Description number for the MCU 2500: 4339

    Description number for the DSP adapter: 4186

    7.2.5 INVERTRONIC compact customer interfaces

    2 voltage-free changeover relays with the following assignment:

    1. SBS (ECD) alarm

    2. Inverter alarm

    The following diagram shows the relay positions in the event of a fault:

    X800:3

    X800:1

    X800:2

    X800:5

    X800:6

    X800:4

    1 2

    Figure 31: Fault, position of relay contacts

    7.2.6 Software interfaces

    RS232, serial interface (service interface)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    55/102 4600 en

    8 Electrical connection

    CAUTION!

    A dangerously high battery voltage exists inside the unit even when the mains

    voltage is switched off! All connection and commissioning work must only be

    carried out by a skilled electrician. Before starting work on the system, this

    specialist must familiarise himself with the particular features of this inverter

    range by reading the manual and the installation instructions. All requirements

    for the environmental and operating conditions listed in the technical data must

    be adhered to in order to guarantee trouble-free operation of the inverter.

    For connecting the INVERTRONIC compact, terminal strips for power con-

    nections (bypass, load, battery) are provided in the cabinet. The cables can be

    routed to the cabinet from all four sides and fed in through the cabinet bottom.

    A double floor in the installation area is not absolutely essential. Please refer to

    the following tables and drawings for information on where the cables are to be

    connected and what size they must be in accordance with DIN VDE 0298.

    Cabling to and from the inverter system must only be laid by qualified

    specialist personnel.

    It is imperative that the safety instructions in Chapter 3 be observed.

    Make absolutely sure that the battery is not earthed. Neither the plus nor

    the minus pole must be earthed (battery floating).

    Make absolutely sure that L and N and the polarity of the battery con-

    nections are correct, as any incorrect connections will cause damage to

    the system.

    Units must be fitted in the rack in the following order. The SBS is al-

    ways fitted at the extreme right-hand end of the rack, the MBS on the

    left next to the SBS, and the inverters must be fitted from left to right.

    Please first check the configuration level of the inverter system to be in-

    stalled. Be sure to pay attention to the enclosed terminal diagrams and,

    in case of doubt, compare these with the markings on the connecting

    terminals.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    56/102 4600 en

    8.1 Behaviour under special operating conditions

    8.1.1 Overload

    The inverter can supply 200% of its rated power for 4 seconds, 120% for 60

    seconds and 110% continuously. For higher overload, the system switches to

    bypass. If the bypass mains supply is not available, the inverter switches off af-

    ter 4 seconds.

    (→ red LED illuminates and green LED flashes)

    8.1.2 Short circuit on load bar

    A short circuit occurring in the downstream load network must be switched off

    within max. 10 milliseconds to ensure that the other loads can continue opera-

    tion without disruption.

    In this case, the inverter system switches immediately to bypass so that the up-

    stream load fuse can blow.

    If the short circuit occurs during battery operation and if the bypass mains sup-

    ply is not available at that time, the output current is limited to 2.5 x rated cur-

    rent (standard).

    8.1.3 Mains supply not in tolerance

    In normal operation, the inverter is synchronised with the mains supply. As

    soon as the mains frequency goes outside the tolerance range (standard ±5 %),

    the inverter switches to the internal clock pulse. The return to normal operation

    is initiated by the control system.

    8.1.4 System faults

    Inverter If a fault occurs in the inverter, the system switches to bypass without any in-

    terruption.

    Battery If the battery voltage becomes too low, the inverters switch off and the loads

    are fed from the bypass supply.

    8.1.5 Fan failure

    In the event of a fan failure, the inverter provides its output voltage until the

    overtemperature trip level is reached. After this, the system switches to bypass

    without interruption.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    57/102 4600 en

    8.2 Cable cross sections / Fuses

    Inverter systems with 110VDC / 1.5kVA / 230VAC inverters

    System

    power

    Min. conductor cross section 1 Max. external fuse

    Mains feed DC feed Mains feed DC feed 1.5kVA 1.5mm² 2.5mm² 10A 20A

    3.0kVA 1.5mm² 4.0mm² 16A 35A

    4.5kVA 2.5mm² 6.0mm² 25A 50A

    6.0kVA 4.0mm² 10mm² 35A 63A

    7.5kVA 6.0mm² 16mm² 50A 80A

    9.0kVA 6.0mm² 25mm² 50A 100A

    10.5kVA 10mm² 35mm² 63A 125A

    12.0kVA 10mm² 35mm² 63A 125A

    13.5kVA 16mm² 50mm² 80A 160A

    15.0kVA 16mm² 50mm² 80A 160A

    16.5kVA 25mm² 70mm² 80A 200A

    18.0kVA 25mm² 70mm² 100A 200A

    19.5kVA 25mm² 70mm² 100A 200A

    21.0kVA 25mm² 95mm² 100A 250A

    22.5kVA 35mm² 95mm² 125A 250A

    Table 2: Conductor cross sections for a 110VDC battery

    Inverter systems with 220VDC / 1.5kVA / 230VAC inverters

    System

    power

    Min. conductor cross section2 Max. external fuse

    Mains feed DC feed Mains feed DC feed 1.5kVA 1.5mm² 1.5mm² 10A 10A

    3.0kVA 1.5mm² 1.5mm² 16A 16A

    4.5kVA 2.5mm² 2.5mm² 25A 25A

    6.0kVA 4.0mm² 4.0mm² 35A 35A

    7.5kVA 6.0mm² 6.0mm² 50A 50A

    9.0kVA 6.0mm² 10mm² 50A 50A

    10.5kVA 10mm² 10mm² 63A 63A

    12.0kVA 10mm² 10mm² 63A 63A

    13.5kVA 16mm² 16mm² 80A 80A

    15.0kVA 16mm² 16mm² 80A 80A

    16.5kVA 25mm² 25mm² 80A 100A

    18.0kVA 25mm² 25mm² 100A 100A

    19.5kVA 25mm² 25mm² 100A 100A

    21.0kVA 25mm² 35mm² 100A 125A

    22.5kVA 35mm² 35mm² 125A 125A

    Table 3: Conductor cross sections for a 220VDC battery

    RE = round conductor, single-strand, RM = round conductor, multi-strand.

    Installation type: Group 3

    1 Depending on the conditions on site, a larger cross section should be chosen to prevent the

    voltage drop on the DC supply cable from becoming too large.

    2 Depending on the conditions on site, a larger cross section should be chosen to prevent the

    voltage drop on the DC supply cable from becoming too large.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    58/102 4600 en

    Check the installed cable cross sections when upgrading the inverter

    system. The cable cross sections must be changed to suit the upgrade.

    Earth faults on unearthed batteries necessitate a protective device for

    each pole.

    The earth connection must be made first in accordance with VDE DIN. There

    is no need to follow a particular installation sequence.

    8.3 Bus connection

    For reliable and fault-free operation of the inverter systems, the CAN-Bus must

    be "terminated" on the back panel cards. This is achieved by fitting jumpers in

    defined positions.

    Complete systems are fully configured in the factory for the cus-

    tomer's specific requirements. The bus connection is only required

    when re-configuring or replacing an shelf.

    Jumper positions (X700, X701) for only 1 shelf:

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R100

    X700 X701

    R101

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Figure 32: Jumper positions (X700, X701) for parallel operation of max. 5 INV without ECD,

    4 INV with SBS or 3 INV with SBS and MBS

    - X700 bridged

    - X701 bridged

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    59/102 4600 en

    Jumper positions (X700, X701) for 2 shelfs:

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R100

    X700 X701

    R101

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R101

    X700 X701

    R100

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Figure 33: Jumper positions (X700, X701) for parallel operation of max. 10 INV without SBS

    or 9 INV with SBS, or 8 INV with SBS and MBS

    1st rack:

    - X700 bridged

    2nd rack:

    - X701 bridged

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    60/102 4600 en

    Jumper positions (X700, X701) for 3 shelfs:

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R100

    X700 X701

    R101

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R101

    X700 X701

    R100

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R101

    X700 X701

    R100

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Figure 34: Jumper positions (X700, X701) for parallel operation of max. 15 INV without SBS

    or 14 INV with SBS, or 13 INV with SBS and MBS

    2nd rack:

    - no bridge

    1st rack:

    - X700 bridged

    3rd rack:

    - X701 bridged

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    61/102 4600 en

    Jumper positions for configuration with DSP adapter and distribution card:

    Note: A distribution card must be installed for cable lengths of 0.5 m and

    above.

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R100

    X700 X701

    R101

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    Teilekennzeichnung

    R100

    X600

    X700

    K100

    V102

    K200 K300

    V101

    X601

    V100

    X701

    R101

    X800

    R101

    X700 X701

    R100

    zu X800

    X801

    zu X801

    X500

    X400

    X300

    X200

    X100

    X8

    X6

    X5

    X4X3

    X2

    X1

    X7

    K50 1111 2222 3333X30

    K3

    X70

    RS 232 RS 485

    X200

    CAN-BUS

    X100 1 21 21 21 2 3333X20

    K2

    1111 33332222

    X10

    K1

    11 21 21 2 3333

    X300

    120Ohm

    max. 0.5m

    max. 0

    .5m

    1 2

    3

    Figure 35: Jumper positions when connecting a distribution card and DSP adapter

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    62/102 4600 en

    1 Connect back panel card and distribution card via X7-X3 with patch

    cable (Caution! Cable is not standard)

    734837 Cable connection RJ45 / 2m

    734838 Cable connection RJ45 / 3.5m

    2 Fit termination resistor (120Ω) on X8 (distribution card)

    3 Connect distribution card and DSP adapter via X4-X100 with patch

    cable (Caution! Maximum length 0.5 m)

    759123 Patch cable 2xRJ45 / 0.5m

    8.4 Terminal connections

    See circuit diagrams and terminal diagrams related to the contract.

    (Customer-specific documentation, such as circuit diagrams, terminal

    diagrams and test reports, is supplied in separate documents)

    8.5 System population sequence (fitting modules)

    It is assumed in the following that the configuration of the inverter system has

    been defined and the appropriate shelfs are fitted and wired in a 19" cabinet

    system.

    Chapter 11: Re-configuring the system, contains detailed diagrams for

    fitting and removing the modular components.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    63/102 4600 en

    CAUTION! Have all the inverters and the electronic changeover device been set up

    for the same voltage and frequency?

    Have all device settings been made and checked?

    • If a manual bypass switch (MBS) has been installed as a separate

    assembly, move the switch to Position 1. The manual bypass switch

    must always be fitted directly on the left of the electronic changeo-

    ver device (SBS).

    • Slot the electronic changeover device into the extreme right-hand

    position of the appropriate shelf. The front panel must be flush with

    the frame of the shelf.

    • Slot the inverters into the shelf. The order and positions can be

    chosen at will. The front panel must be flush with the frame of the

    shelf.

    • Cover all free slots with a blanking plate.

    • Screw all units and blanking plates to the shelf.

    All the electrical connections are automatically made when the units are slotted

    into the shelf.

    It is imperative that the safety instructions in Chapter 3 be observed.

    The upstream isolators must be opened in order to isolate the inverter

    system from the supply sources (to make it completely dead).

    If an emergency stop or EPO circuit is to be implemented, these circuits

    must be additionally installed externally. Approved isolating devices

    must then galvanically isolate all AC and DC inputs (AC supply and

    battery inputs).

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    64/102 4600 en

    9 Configuring the inverter system

    CAUTION! The safety instructions must be observed at all times during installation,

    connection and commissioning.

    When the inverter system has been assembled, connected and commissioned,

    all the components are fully ready for operation. No additional settings or ad-

    justments are necessary during operation under any operating conditions.

    When choosing a location for the inverter system, it must be ensured that the

    floor is firm and level. The inverter system is designed for use in closed and

    dry rooms. The maximum permissible ambient temperature is 40°C (see Tech-

    nical Data). During installation, it must be ensured that the inverter system is

    not exposed to aggressive substances and the passage of cooling air is not

    hampered.

    CAUTION! Any changes to settings must only be made by trained and qualified

    personnel. The modified inverter system settings must be available at

    all times. Only then is it possible to obtain an overview of the current

    system configurations. This simplifies the specific replacement of

    components and fault diagnosis.

    All inverter system components are set up in the factory to the values and oper-

    ating modes specified by the user or to default values. No changes to the set-

    tings are necessary for correct operation.

    If, however, system configurations are changed or new systems are configured

    from individual components, or components are replaced or added, some set-

    tings and functions must be checked.

    Shelfs

    The types of shelf may vary depending on the required system configuration.

    In order for the CAN-Bus system to work without any problems, the cable ends

    of the CAN-Bus system must be fitted with a termination resistor/jumper on

    each shelf in accordance with a defined scheme. In addition, the shelfs must be

    suitably connected by means of data cables.

    These measures are only required in the event of a completely new inverter

    system design. As this is only rarely undertaken by the user, it will not be de-

    scribed in more detail.

    Electronic changeover device configuration (SBS)

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    65/102 4600 en

    Every electronic changeover device is set up in the factory to the values speci-

    fied by the user or to default values. The values set can be seen from the con-

    figuration data sheet and the equipment marking.

    • System voltage; permissible voltage tolerance

    • Frequency, permissible frequency tolerance

    • Operating mode "Inverter priority" or "Mains priority"

    Inverters

    Every inverter is set up in the factory to the values specified by the user or to

    default values. In the case of an inverter system without electronic changeover

    device, these values cannot be changed. The values set can be seen from the

    configuration data sheet and the equipment marking.

    • Output voltage

    • Frequency

    • Switching thresholds for the input voltage monitoring

    Changing these values using the display and operating menu of the electronic

    changeover device is described in more detail in chapter 6.

    These settings should be checked and changed if necessary before fitting the

    units.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    66/102 4600 en

    9.1 Electronic changeover device menu structure:

    The menu structure clearly displays the system setting and system information

    options.

    Each menu item can be accessed and settings can be made using the four menu

    keys under the display. However, some menu items are protected by a pass-

    word. The system automatically returns to the main window from any menu

    item when no button has been pressed for about 2 minutes.

    Function key assignment for selecting individual menu items

    Confirmation of the selected menu item

    Return to next higher menu level.

    Selection of individual menu items within a menu

    level

    Function key assignment for changing system settings

    As above

    Changing the set values

    Function key assignment for entering the password

    Selecting the position of a number

    Changing the numerical value

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    67/102 4600 en

    Main menu

    Measured values

    Device management

    System set-up

    Delete all messages

    Service portal

    Software version display

    Load voltage

    U = 227V

    Measured values

    Load voltage

    Load current

    Load frequency

    Load power

    Mains voltage

    Inverter values

    Load current

    I = 36.0A

    Load frequency

    f = 50.0Hz

    Mains voltage

    U = 230V

    Load power

    Active power

    Apparent power

    Reactive power

    Measured values

    Inverter 1

    Inverter 2

    • Inverter n

    Inverter n

    Input voltage

    Output voltage

    Output current

    Inverter n:

    Input voltage

    U = 51.8V

    Inverter n:

    Output voltage

    U = 230V

    Inverter n:

    Output current

    I = 2.5A

    Active power

    P = 8.6kW

    Apparent power

    S = 9.3kVA

    Reactive power

    Q = 2.8kVAr

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    68/102 4600 en

    Main menu

    Measured values

    Device management

    System set-up

    Delete all messages

    Service portal

    Software version display

    INV n

    Fault

    Status

    Nominal value settings

    Identify unit

    Log off unit

    Software version

    Status codes

    Device management

    INV1 (ok)

    INV2 (Fault)

    INV3 (ok)

    • INVn (ok)

    Static bypass (ok)

    Other "adr" (Fault)

    AC rated voltage

    U = 230V

    Rated frequency

    f = 50Hz

    All LEDs for signal-

    ling the output pow-

    er of the identified

    unit flash.

    Fault list

    No faults found

    Status

    � Ready for operation

    Fault

    � Parallel operation

    Switched off

    All inverters off

    Settings

    AC rated voltage

    Rated frequency

    Identify unit

    Single unit

    All units

    Software version

    V **

    607672.xx

    Status codes

    A:0020

    D:000C:000

    B:0000

    All LEDs for signal-

    ling the output pow-

    er of all identified

    units flash.

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    69/102 4600 en

    Main menu

    Measured values

    Device management

    System set-up

    Delete all messages

    Service portal

    Software version display

    Static bypass

    Fault

    Status

    Nominal value settings

    Software version

    Status codes

    Fault delay

    Device management

    INV1 (ok)

    INV2 (Fault)

    INV3 (ok)

    • INV n

    Static bypass (ok)

    Other "adr" (Fault)

    AC rated voltage

    110V / 115V / 120V or

    220V / 230V / 240V

    Rated frequency

    f = 50Hz or 60Hz

    Fault list

    No faults found

    Status

    Mains priority

    � Inverter priority

    Mains operation

    � Inverter operation

    � Ready for operation

    Fault

    Settings

    Voltage range

    Rated voltage

    Rated frequency

    Priority type

    Software version

    V **

    607673.xx

    Status codes

    A:0020

    D:000C:000

    B:0000

    Priority type

    � Inverter priority

    Mains priority

    Fault delay

    Other fault

    Config. error

    Regeneration

    Syncline fault

    CAN bus error

    Frequency

    Reference voltage

    Auxiliary voltage

    Inverter voltage

    Contact fault

    Mains voltage

    Load voltage

    Overtemperature

    Overload

    Alarm

    � on

    delayed

    off

    Fault delay

    = 10s

    Voltage range

    U = 115V or 230V

  • Operating instructions

    INVERTRONIC compact

    31.05.17

    70/102 4600 en

    Main menu

    Measured values

    Device management

    System set-up

    Delete all messages

    Service portal

    Software version display

    Other "adr"

    Fault

    Identify unit

    Log off unit

    Software version

    Status codes

    Device management

    INV1 (ok)