Introducing GAC’s New Line of Intelligent Generator Set Controllers. The InteliSys. Stand-By, Prime Mover (single and multiple set), and Parralel to Utility (single and multiple set) Applications Features: 320 x 240 LCD 16 / 14 Discrete Inputs and Outputs (Configurable) Expandable - PowerPoint PPT Presentation
Citation preview
The InteliSys• Stand-By, Prime Mover (single and multiple set), and Parralel to Utility (single and multiple set) Applications• Features:
320 x 240 LCD16 / 14 Discrete Inputs and Outputs (Configurable) Expandable
to 128 / 704 Analog Inputs (Fuel Level, Coolant Temp., Oil Press.)
Expandable to 68 and 1 Analog OutputSpeed Measurement (Mag Pick-Up)3 Phase Generator / Utility Voltage 3 Phase Generator / 1 Phase Utility Current MeasurementRS232 for Direct CommunicationRemote Communication (Analog, Internet, and GSM)
InteliSys Connections
1 Phase Utility Current
3 Phase GeneratorCurrent 3 Phase Generator /
Utility Voltage
16 Configurable Discrete Inputs
RS232 for direct and modem connection
CAN ConnectionFor Extension Modules
CAN Connection for Multiple Set Applications
InteliSys Connections Cont.Load Sharing Line
Governor Output
Output for AVRi Interface
Analog Output
4 Analog Inputs
Mag.Pick-up
2 Relay Outputs(Starter, Fuel Solenoid)
14 Configurable Discrete Outputs
12 or 24 V DC
InteliSys’s Versions
InteliSys has three versions depending on the application it is intended for:
• iS-PCM, Power ControlFor single sets that will parallel with the Utility.
• iS-PCLSM, Power Control with Load SharingFor multiple sets that may or may not parallel with the Utility.
• iS-PCLSM-PMS, Load Sharing and Power ManagementThe same as PCLSM with the added features of Voltand PF control.
• AVR control (needs 18 V AC power supply)• Expandable I / O• Communications
• Modem Support (multiple set applications, iG-MU)• Internet Support (iG-IB)
InteliSys’s Modules
iS-BIN16/8
• CAN Communication with InteliSys• 16 Discrete Inputs and 8 Discrete Outputs• Must Assign Controllers Address in InteliSys and on Module• Up to 7 of these modules can be Connected to InteliSys
AVRi Module
Input from PCLSM
18 V AC Power Supply
Output for AVR Control
DIN Rail Mounting
Output Level Adjustment (turn pot)
iS-AIN8• CAN Communication with InteliSys• 8 Analog Inputs• Must Assign Controllers Address in InteliSys and on Module• Up to 8 of these modules can be Connected to InteliSys
InteliMains: InteliGen With Special Software
• Mains (= Utility) Circuit Breaker Control–Reverse Synchronization–Vector surge protection (locally required)
• Power Management - Engine Usage Optimization–Number of running engines: Dependent on required load–Engine starting order: Dependent on running hours
• Import/Export Control
InteliSys’s User Friendly Operating Software
• Free•User Friendly• PC Format
Controller Setpoints
ValuesHistory
Setpoints• Change any Setpoint • Current Value• Range
Screen Selection
Value
Acceptable Rangefor Parameter
Customizable Software• Parameters
Nominal RPM 80 300• Multilingual Texts
Overspeed Überdrehzahl Sobrevelocidad• Units
°C °F; kPa bar psi• Controller Operating Mode
SPM SSB SPtM MINT MEXT• Text
Water temp Coolant temp
Local connection to the Control System
Modem connection to remote monitoring*
SMS (Mobile phones) connection*
Internet connection*
Communications
Controller Screens
Water Temp 91°C
Oil Pressure 5.1bar
Fuel level 75%
Battery voltage 25.2V
• Analog Meters• Bar Graphs• Numeric Values• Controller Screens Allow for Similar Interface as WinEdit Software
MAINS:230 228 233V 50.0Hz GENERATOR: 1517RPM221 223 220V 50.6Hz872 896 932A 0.98L 183 194 208kW 118kVAr
Running in Island
Setpoint Adjustment
PARAMETERS MF-Start Delay 3sStart Attempts 5 Mains OK-Delay 10sCooling time 30s
• Adjustable via iS Keypad• Three Level Password Protection
History Screens
121 125 124A 62kVAr 27 29 29kW 72 73 71A 48kVAr 17 18 16kW 0 0 0A 0 0 0kW 0 0 0A 0 0 0kW
-15 FINISHED HOUR 07:00:00 16.10.-16 GCB CLOSED-ISLAND 06:23:53 16.10.-17 ENGINE START 06:23:49 16.10.-18 MF-MCB OPENED 06:23:44 16.10.
85kW 1503RPM 0.81L 88C 6.1bar 24.9V 84% 50kW 1495RPM 0.72L 25C 5.3bar 24.7V 87% 0kW 0RPM - 22C 0.0bar 25.8V 87% 0kW ORPM - 22C 0.0bar 25.8V 87%
M 0 0 0V 0.0HzG233 227 229V 50.1HzM 0 0 0V 0.0HzG230 228 223V 49.8HzM 0 0 0V 0.0HzG 0 0 0V 0.0HzM190 195 201V 48.7HzG 0 0 0V 0.0Hz
• History Events Can be Viewed From iS Screens as well as WinEdit• Viewed on Multiple Screens
• Adjustable Delay Settings• Five Protective Actions
– Warning– Slow stop – Shut-down – Unloading – History Record
• Reset Function (Horn + Flashing Light)
Protection Handling
Protections
• Generator / Utility Over / Under Voltage and Frequency• Voltage and Current Asymmetry• OverCurrent• OverLoad• Oil Pressure (two level: warning, shutdown)• Coolant Temp. (two level: warning, shutdown)• Fuel Level (two level: warning, shutdown)• …