View
233
Download
0
Embed Size (px)
Citation preview
Introducing GAC’s New Line of Intelligent Generator Set Controllers
The InteliLite: iL-MRS17
• Stand-By and Prime Mover Applications• Features:
128 x 64 LCD6 / 6 Discrete Inputs and Outputs (Configurable) Expandable
to 14 / 143 Analog Inputs (Fuel Level, Coolant Temp., Oil Press.)
Expandable to 7 Inputs and 1 OutputSpeed Measurement (Mag Pick-Up)3 Phase Generator Voltage and Current MeasurementRS232 for Direct CommunicationMeets NFPA110 (w/ Remote Annunciator,
iGL-RA15)Remote Communication (via modem)
iL-MRS17 Connections
3 Phase GeneratorVoltage
3 Phase Generator Current 6 Configurable Discrete Inputs
Direct PC or Modem* Connection
12 or 24 V DC
3 Analog Inputs (Oil, Temp., Fuel.)
Mag. Pick-up
2 Relay Outputs (Starter, Fuel Solenoid) 4 Config. Outputs
Connection for iGL-RA15*
iGL-RA15
• 15 three-color LEDS• User definable labeling• LED color is selected from front panel buttons(R/G/Y)• CAN Bus connection to unit• 1 connection for siren• Horn reset and lamp test keys• Max. distance from unit is 200m
IOM / PTM Module
PO WER
8-36V DC
BIN ARY OUTPUTS
BIN ARY INPU TS AN ALOG INPU TS AN ALOG OUT
BO
8B
I8
BI7
BI6
BI5
BI4
BI3
BI2
CO
M AI4
BI1
BO
1
BO
2
BO
3
BO
4
BO
5
BO
6
BO
7S eria l No.
IG-IOMIG
-CU
RS
232
9 Discrete Inputs w/ Active LED
4 Analog Inputs* 1 Analog Output
12 or 24 V DC w/Power LED
9 Discrete Outputs w/ Active LED
RS232 Connection to InteliGen
RS232 for Direct PC Connection
DIN Rail Mounting
InteliLite’s User Friendly Operating Software
• Free•User Friendly• PC Format
Controller
Setpoints
Values
Open Direct ConnectionOpen Modem Connection
Open Off Line Connection
Controller• Same as Keypad• Essential Metering• Alarm List
Value Screen
All Metered Values in Real Time.
Screen Selection
Metering
Setpoints• Change any Setpoint • Current Value• Range
Screen Selection
Value
Acceptable Rangefor Parameter
Analog Sensor Plots• Ability to plot up to ten Points• iL can store up to 3 distinct graphs
Customizable Software
• ParametersNominal RPM 80 300
• Multilingual Texts
Overspeed Überdrehzahl Sobrevelocidad• Units
°C F; kPa bar psi• Text
Water temp Coolant temp
Modem connection to remote monitoring
Local connection to the Control System
Communications
Controller Screens
Water Temp 91°C
Oil Pressure 5.1bar
Fuel level 75%
Battery voltage 25.2V
• Analog Meters• Bar Graphs• Numeric Values• Controller Screens Allow for Similar Interface as LiteEdit Software
MAINS:230 228 233V 50.0Hz GENERATOR: 1517RPM221 223 220V 50.6Hz872 896 932A 0.98L 183 194 208kW 118kVAr
Running in Island
Setpoint Adjustment
PARAMETERS MF-Start Delay 3sStart Attempts 5 Mains OK-Delay 10sCooling time 30s
• Adjustable via MRS Keypad• One Level Password Protection
• Adjustable Delay Settings• Three Protective Actions
– Warning– Slow stop – Shut-down
• Reset Function (Horn + Flashing Light)
Protection Handling
Protections
• Generator Over / Under Voltage and Frequency• Voltage and Current Asymmetry• OverCurrent• OverLoad• Oil Pressure (two level: warning, shutdown)• Coolant Temp. (three level: low temp warning, high temp warning, and high temp shutdown)• Fuel Level (two level: warning, shutdown)
Summary
The MRS Controller Offers Features and Functionsthat the Competitors don’t for a Lower Price.