  • Industrial Generator Sets

    Models:

    20-3250 kWControllers:

    Decision-Makerr 550

    Software (Code) Version 3.4.3 or higher

    TP-6200 3/17l

    Operation

  • Engine exhaust from this product containschemicals known to the State of Californiato cause cancer, birth defects, or otherreproductive harm.

    WARNINGCalifornia Proposition 65

    This product contains and/or emitschemicals known to the State of California tocause cancer, birth defects, or otherreproductive harm.

    WARNINGCalifornia Proposition 65

    Breathing diesel engine exhaust exposesyou to chemicals known to the State ofCalifornia to cause cancer and birth defectsor other reproductive harm.S Always start and operate the engine in awell-ventilated area.

    S If in an enclosed area, vent the exhaustto the outside.

    S Do not modify or tamper with exhaustsystem.

    S Do not idle the engine except asnecessary.For more information go towww.P65warnings.ca.gov/diesel

    WARNINGCalifornia Proposition 65

    Product Identification Information

    Product identification numbers determine service parts.Record the product identification numbers in the spacesbelow immediately after unpacking the products so thatthe numbers are readily available for future reference.Record field-installed kit numbers after installing thekits.

    Generator Set Identification Numbers

    Record the product identification numbers from thegenerator set nameplate(s).

    Model DesignationSpecification NumberSerial Number

    Accessory Number Accessory Description

    Engine Identification

    Record the product identification information from theengine nameplate.

    ManufacturerModel DesignationSerial Number

    Controller Identification

    Record the controller description from the generator setoperationmanual, spec sheet, or sales invoice. Recordthe Controller Serial Number from the controllernameplate.

    Controller Description Decision-Makerr 550Controller Serial Number

    Firmware/Software Version Numbers

    Record the version and reference numbers as shippedfrom the manufacturer. Determine the ApplicationProgram Version Number as shown in Menu 20.Determine the Personality Profile Reference Numberfrom the disk supplied with the literature packet.

    Application Program Version NumberPersonality Profile Reference NumberUser Parameter File Reference Number

    Version Number Upgrades/Updates

    Record the version number upgrade/updates wheninstalled.

    Version No./Date Installed

    Software Options

    Record the software options.

    Number and Description

  • Table of Contents

    TP-6200 3/17 Table of Contents 3

    Product Identification Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Safety Precautions and Instructions 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Introduction 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Abbreviations 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .List of Related Materials 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Service Assistance 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Section 1 Specifications and Features 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.1 Introduction 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 Controller Features 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.1 Annunciator Lamps 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.2 Digital Display and Keypad 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.3 Switches and Controls 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.4 Controller Circuit Boards 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.5 Fuses 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.6 Terminal Strips and Connectors 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2.7 Circuit Board Interconnections for Calibration Procedure 22. . . . . . . . . . . .1.2.8 Communication Ports 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3 Controller Logic Specifications 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3.1 Status Event and Fault Specifications 23. . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3.2 Voltage Regulator and Calibration Specifications 33. . . . . . . . . . . . . . . . . . .1.3.3 Voltage Regulator Adjustments 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Section 2 Operation 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 Prestart Checklist 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2 Exercising Generator Set 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.3 Operation in Cold Weather Climates 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4 Controller Operation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.4.1 Starting 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4.2 Stopping (User Stopping and Fault Shutdown) 37. . . . . . . . . . . . . . . . . . . . .2.4.3 Emergency Stop Switch Resetting 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4.4 Status Lamps 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4.5 System Warning Lamp 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4.6 System Shutdown Lamp 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4.7 Controller Resetting (Following System Shutdown or Warning) 45. . . . . . .

    2.5 Menu List Summary 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.6 Reviewing Digital Display 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.6.1 Keypad Operation 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.6.2 Auto-Scroll Function 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.6.3 Request and Error Messages 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.7 Monitoring and Programming Setup 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.7.1 PC Communications 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.7.2 Modbus Communications 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.8 Reviewing Menu Displays 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.1 Menu 1—Generator Monitoring 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.2 Menu 2—Engine Monitoring 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.3 Menu 3—Analog Monitoring 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.4 Menu 4—Operational Records 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.5 Menu 5—Event History 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.6 Menu 6—Time and Date 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.7 Menu 7—Generator System 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.8 Menu 8—Time Delays 65. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.9 Menu 9—Input Setup 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.10 Menu 10—Output Setup 68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.11 Menu 11—Voltage Regulator 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Table of Contents, continued

    TP-6200 3/17Table of Contents4

    2.8.12 Menu 12—Calibration 72. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.13 Menu 13—Communications 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.14 Menu 14—Programming Mode 74. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.15 Menu 15—Protective Relays (PR) 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.8.16 Menu 18—Battery Chargers (Version 3.4.3 or Higher) 76. . . . . . . . . . . . . .2.8.17 Menu 20—Factory Setup (Version 2.10) 78. . . . . . . . . . . . . . . . . . . . . . . . . .2.8.18 Menu 20—Factory Setup (Version 2.21) 79. . . . . . . . . . . . . . . . . . . . . . . . . .2.8.19 Menu 20—Factory Setup (Version 3.01) 80. . . . . . . . . . . . . . . . . . . . . . . . . .

    2.9 Local Programming Mode On 81. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.1 Menu 1—Generator Monitoring 82. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.2 Menu 2—Engine Monitoring 86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.3 Menu 3—Analog Monitoring 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.4 Menu 4—Operational Records 93. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.5 Menu 5—Event History 95. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.6 Menu 6—Time and Date 96. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.7 Menu 7—Generator System 97. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.8 Menu 8—Time Delays 105. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.9 Menu 9—Input Setup 107. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.10 Menu 10—Output Setup 113. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.11 Menu 11—Voltage Regulator 123. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.12 Menu 12—Calibration 129. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.13 Menu 13—Communications 134. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.14 Menu 14—Programming Mode 140. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.15 Menu 15—Protective Relays (PR) 142. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.16 Menu 18—Battery Chargers 146. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9.17 Menu 20—Factory Setup 151. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Section 3 Scheduled Maintenance 153. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 Alternator Service 153. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2 Engine Service 153. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3 Service Schedule 154. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4 Alternator Bearing Service 156. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.1 20--300 kW Models 156. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4.2 300--2250 kW Models with Single-Bearing Alternator 156. . . . . . . . . . . . . . .3.4.3 1250 kW and Larger Models with Two-Bearing Alternator 156. . . . . . . . . . .

    3.5 Diesel Fuel Systems 156. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.5.1 Bleeding Air from Fuel System 156. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.5.2 Subbase Fuel Day Tank Electronic Control Module (ECM) 157. . . . . . . . . .3.5.3 Subbase Inner Fuel Tank Alarm 158. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.6 Gaseous Fuel Systems 159. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.1 Gaseous Fuel System Concept

    (Single Fuel) 159. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.2 LPG Liquid Withdrawal Fuel System Concept 159. . . . . . . . . . . . . . . . . . . . .3.6.3 Natural Gas and LPG Conversion 159. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6.4 Fuel System Changeover Kits (Dual Fuel) 161. . . . . . . . . . . . . . . . . . . . . . . . .3.6.5 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1 161. . . . . . . . . . . . .

    3.7 Air Cleaner Restriction Indicator (if equipped) 162. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.8 Cooling System 162. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.8.1 Coolant Level Check 162. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.8.2 Cooling System Component Inspection 162. . . . . . . . . . . . . . . . . . . . . . . . . . .3.8.3 Procedure to Drain Cooling System 163. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.8.4 Procedure to Flush and Clean Cooling System 163. . . . . . . . . . . . . . . . . . . .3.8.5 Procedure to Refill Cooling System 163. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.9 Radiator Fan Bolt Retorque 163. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.10 Radiator Expansion Joint Loosening—Initial Setup Only 164. . . . . . . . . . . . . . . . . . . .3.11 Radiator Fan Bearing Lubrication 165. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Table of Contents, continued

    TP-6200 3/17 Table of Contents 5

    3.12 Battery 166. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.12.1 Clean Battery 166. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.12.2 Electrolyte Level Inspection 167. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.12.3 Specific Gravity Check 168. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.12.4 Charge Battery 168. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.13 Detroit Diesel Engine Control Systems 169. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.13.1 Features 169. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.13.2 DDEC Engine Diagnostics 169. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.14 Engine Control Systems 170. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.15 Storage Procedure 170. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.15.1 Lubricating System 171. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.15.2 Cooling System 171. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.15.3 Fuel System 171. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.15.4 Internal Engine Components (Gaseous-Fueled Engines) 171. . . . . . . . . . . .3.15.5 Exterior 172. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.15.6 Battery 172. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Section 4 General Troubleshooting 173. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 General Troubleshooting Chart 174. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2 Controller Display and Voltage Regulation Troubleshooting Chart 177. . . . . . . . . . . .

    Section 5 Generator Set Reconnection 179. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1 Introduction 179. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2 Voltage Reconnection Procedure 180. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Section 6 Accessories 185. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1 Accessories and Connections 185. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.1.1 Audiovisual Alarm Kit 185. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.2 Common Failure Relay Kit 186. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.3 Battery Charger Kit with Alarm Option 186. . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.4 Controller (Customer) Connection Kit 187. . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.5 Ground Fault Annunciation 188. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.6 Idle (Speed) Mode Feature 189. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.7 Low Fuel (Level/Pressure) Switch 190. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.8 Prime Power Switch Kit 190. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.9 Remote Emergency Stop Kit 191. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.10 Remote Reset Feature 191. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.11 Remote Serial Annunciator (RSA) 192. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.12 Remote Speed Adjust Kit

    (ECM Models) 194. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.13 Remote Speed Adjustment Potentiometer Kit (Non-ECM Models) 194. . . .6.1.14 Run Relay Kit 195. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.15 Shunt-Trip Line Circuit Breaker 195. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.16 Single-Relay Dry Contact Kit 196. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.17 Ten-Relay Dry Contact Kit 196. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1.18 Twenty-Relay Dry Contact Kit 198. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.2 Accessory Connections 199. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix A Abbreviations 205. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix B User-Defined Settings 207. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix C Voltage Regulator Definitions and Adjustments 217. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix D Alternator Protection 223. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix E Inputs and System Events by Application 225. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix F Controller Displays from the Engine ECM 229. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Appendix G DEC 550 Controller Fault Displays 231. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 6 TP-6200 3/17

    Notes

  • 7Safety Precautions and InstructionsTP-6200 3/17

    Safety Precautions and Instructions

    IMPORTANTSAFETY INSTRUCTIONS.Electromechanical equipment,including generator sets, transferswitches, switchgear, and accessories,can cause bodily harm and poselife-threatening danger whenimproperly installed, operated, ormaintained. To prevent accidents beaware of potential dangers and actsafely. Read and follow all safetyprecautions and instructions. SAVETHESE INSTRUCTIONS.

    Thismanual has several types of safetyprecautions and instructions: Danger,Warning, Caution, and Notice.

    DANGER

    Danger indicates the presence of ahazard that will cause severepersonal injury, death, orsubstantialproperty damage.

    WARNING

    Warning indicates the presence of ahazard that can cause severepersonal injury, death, orsubstantialproperty damage.

    CAUTION

    Caution indicates the presence of ahazard that will or can cause minorpersonal injury or property damage.

    NOTICENotice communicates installation,operation, or maintenance informationthat is safety related but not hazardrelated.

    Safety decals affixed to the equipmentin prominent places alert the operatoror service technician to potentialhazards and explain how to act safely.The decals are shown throughout thispublication to improve operatorrecognition. Replace missing ordamaged decals.

    Accidental Starting

    Accidental starting.Can cause severe injury or death.

    Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

    WARNING

    Disabling the generator set.Accidental starting can causesevere injury or death. Beforeworking on the generator set orequipment connected to the set,disable the generator set as follows:(1) Move the generator set masterswitch to the OFF position.(2) Disconnect the power to the batterycharger. (3) Remove the batterycables, negative (--) lead first.Reconnect the negative (--) lead lastwhen reconnecting the battery. Followthese precautions to prevent starting ofthe generator set by an automatictransfer switch, remote start/stopswitch, or engine start command fromaremote computer.

    Battery

    Sulfuric acid in batteries.Can cause severe injury or death.

    Wear protective goggles andclothing. Battery acid may causeblindness and burn skin.

    WARNING

    Explosion.Can cause severe injury or death.Relays in the battery chargercause arcs or sparks.

    Locate the battery in a well-ventilatedarea. Isolate the battery charger fromexplosive fumes.

    WARNING

    Battery electrolyte is a dilutedsulfuric acid. Battery acid cancausesevere injury or death. Battery acidcan cause blindness and burn skin.Always wear splashproof safetygoggles, rubber gloves, and bootswhen servicing the battery. Do notopen a sealed battery or mutilate thebattery case. If battery acid splashes inthe eyes or on the skin, immediatelyflush the affected area for 15 minuteswith large quantities of clean water.Seek immediatemedical aid in the caseof eye contact. Never add acid to abattery after placing the battery inservice, as thismay result in hazardousspattering of battery acid.

    Battery acid cleanup. Battery acidcan cause severe injury or death.Battery acid is electrically conductiveand corrosive. Add 500 g (1 lb.) ofbicarbonate of soda (baking soda) to acontainer with 4 L (1 gal.) of water andmix the neutralizing solution. Pour theneutralizing solution on the spilledbattery acid and continue to add theneutralizing solution to the spilledbattery acid until all evidence of achemical reaction (foaming) hasceased. Flush the resulting liquid withwater and dry the area.

  • 8 Safety Precautions and Instructions TP-6200 3/17

    Battery gases. Explosion can causesevere injury or death. Battery gasescan cause an explosion. Do not smokeor permit flames or sparks to occur neara battery at any time, particularly whenit is charging. Do not dispose of abattery in a fire. To prevent burns andsparks that could cause an explosion,avoid touching the battery terminalswith tools or other metal objects.Remove all jewelry before servicing theequipment. Discharge static electricityfrom your body before touchingbatteries by first touching a groundedmetal surface away from thebattery. Toavoid sparks, do not disturb the batterycharger connections while the batteryis charging. Always turn the batterycharger off before disconnecting thebattery connections. Ventilate thecompartments containing batteries toprevent accumulation of explosivegases.

    Battery short circuits. Explosioncan cause severe injury or death.Short circuits can cause bodily injuryand/or equipment damage.Disconnect the battery beforegenerator set installation ormaintenance. Remove all jewelrybefore servicing the equipment. Usetools with insulated handles. Removethe negative (--) lead first whendisconnecting the battery. Reconnectthe negative (--) lead last whenreconnecting the battery. Neverconnect the negative (--) battery cableto the positive (+) connection terminalof the starter solenoid. Do not test thebattery condition by shorting theterminals together.

    Battery gases. Explosion can causesevere injury or death. Incorrect useof the equalize charge statemay lead tohazardous situations. Equalization isONLY applicable for flooded lead acid(FLA) type batteries and will damagegel, absorbed glass mat (AGM), ornickel-cadmium (NiCad) type batteries.In the controller menu or SiteTechtsettings, verify that the battery topologyis set correctly for thebattery typeused.Do not smoke or permit flames, sparks,or other sources of ignition to occurnear a battery at any time.

    Engine Backfire/FlashFire

    Risk of fire.Can cause severe injury or death.

    Do not smoke or permit flames orsparks near fuels or the fuel system.

    WARNING

    Servicing the fuel system. A flashfire cancausesevere injuryordeath.Do not smoke or permit flames orsparks near the carburetor, fuel line,fuel filter, fuel pump, or other potentialsources of spilled fuels or fuel vapors.Catch fuels in an approved containerwhen removing the fuel line orcarburetor.

    Servicing the air cleaner. A suddenbackfire can cause severe injury ordeath. Do not operate the generatorset with the air cleaner removed.

    Combustible materials. A fire cancause severe injury or death.Generator set engine fuels and fuelvapors are flammable and explosive.Handle these materials carefully tominimize the risk of fire or explosion.Equip the compartment or nearby areawith a fully charged fire extinguisher.Select a fire extinguisher rated ABC orBC for electrical fires or asrecommended by the local fire code oran authorized agency. Train allpersonnel on fire extinguisheroperation and fire preventionprocedures.

    Exhaust System

    Carbon monoxide.Can cause severe nausea,fainting, or death.

    The exhaust system must beleakproof and routinely inspected.

    WARNING

    Generator set operation. Carbonmonoxide can cause severe nausea,fainting, or death. Carbon monoxideis an odorless, colorless, tasteless,nonirritating gas that can cause death ifinhaled for even a short time. Avoidbreathing exhaust fumeswhenworkingon or near the generator set. Neveroperate the generator set inside abuildingunless theexhaust gas is pipedsafely outside. Never operate thegenerator set where exhaust gas couldaccumulate and seep back inside apotentially occupied building.

    Carbon monoxide symptoms.Carbon monoxide can cause severenausea, fainting, or death. Carbonmonoxide is a poisonous gas present inexhaust gases. Carbonmonoxide is anodorless, colorless, tasteless,nonirritating gas that can cause death ifinhaled for even a short time. Carbonmonoxide poisoning symptoms includebut are not limited to the following:D Light-headedness, dizzinessD Physical fatigue, weakness injoints and muscles

    D Sleepiness, mental fatigue,inability to concentrateor speak clearly, blurred vision

    D Stomachache, vomiting, nauseaIf experiencing any of these symptomsand carbon monoxide poisoning ispossible, seek fresh air immediatelyand remain active. Do not sit, lie down,or fall asleep. Alert others to thepossibility of carbon monoxidepoisoning. Seek medical attention ifthe condition of affected persons doesnot improvewithinminutes of breathingfresh air.

  • 9Safety Precautions and InstructionsTP-6200 3/17

    Fuel System

    Explosive fuel vapors.Can cause severe injury or death.

    Use extreme care when handling,storing, and using fuels.

    WARNING

    The fuel system. Explosive fuelvapors can cause severe injury ordeath. Vaporized fuels are highlyexplosive. Use extreme care whenhandling and storing fuels. Store fuelsin a well-ventilated area away fromspark-producing equipment and out ofthe reach of children. Never add fuel tothe tank while the engine is runningbecause spilled fuel may ignite oncontact with hot parts or from sparks.Do not smoke or permit flames orsparks to occur near sources of spilledfuel or fuel vapors. Keep the fuel linesand connections tight and in goodcondition. Do not replace flexible fuellines with rigid lines. Use flexiblesections to avoid fuel line breakagecausedby vibration. Donot operate thegenerator set in the presence of fuelleaks, fuel accumulation, or sparks.Repair fuel systems before resuminggenerator set operation.

    Explosive fuel vapors can causesevere injury or death. Takeadditional precautions when using thefollowing fuels:

    Gasoline—Store gasoline only inapproved red containers clearlymarked GASOLINE.

    Propane (LPG)—Adequate ventilationis mandatory. Because propane isheavier than air, install propane gasdetectors low in a room. Inspect thedetectors per the manufacturer’sinstructions.

    Natural Gas—Adequate ventilation ismandatory. Because natural gas rises,install natural gas detectors high in aroom. Inspect the detectors per themanufacturer’s instructions.

    Fuel tanks. Explosive fuel vaporscan cause severe injury or death.Gasoline and other volatile fuels storedin day tanks or subbase fuel tanks cancause an explosion. Store only dieselfuel in tanks.

    Draining the fuel system. Explosivefuel vapors can cause severe injuryor death. Spilled fuel can cause anexplosion. Usea container to catch fuelwhendraining the fuel system. Wipeupspilled fuel after draining the system.

    Gas fuel leaks. Explosive fuelvapors can cause severe injury ordeath. Fuel leakage can cause anexplosion. Check the LPG vapor ornatural gas fuel system for leakage byusinga soapandwater solutionwith thefuel system test pressurized to6--8 ounces per square inch(10--14 inches water column). Do notuse a soap solution containing eitherammonia or chlorine because bothprevent bubble formation. A successfultest depends on the ability of thesolution to bubble.

    LPG liquid withdrawal fuel leaks.Explosive fuel vapors can causesevere injury or death. Fuel leakagecan cause an explosion. Check theLPG liquid withdrawal fuel system forleakage by using a soap and watersolution with the fuel system testpressurized to at least 90 psi(621 kPa). Do not use a soap solutioncontaining either ammonia or chlorinebecause both prevent bubbleformation. A successful test dependson the ability of the solution to bubble.

    Hazardous Noise

    Hazardous noise.Can cause hearing loss.

    Never operate the generator setwithout a muffler or with a faultyexhaust system.

    CAUTION

    Engine noise. Hazardous noise cancause hearing loss. Generator setsnot equipped with sound enclosurescan produce noise levels greater than105 dBA. Prolonged exposure to noiselevels greater than 85 dBA can causepermanent hearing loss. Wear hearingprotection when near an operatinggenerator set.

  • 10 Safety Precautions and Instructions TP-6200 3/17

    Hazardous Voltage/Moving Parts

    Hazardous voltage.Will cause severe injury or death.

    Disconnect all power sources beforeopening the enclosure.

    DANGER

    Hazardous voltage.Can cause severe injury or death.

    Operate the generator set only whenall guards and electrical enclosuresare in place.

    Moving parts.

    WARNING

    Hazardous voltage.Backfeed to the utility system cancause property damage, severeinjury, or death.

    If the generator set is used forstandby power, install an automatictransfer switch to prevent inadvertentinterconnection of standby andnormal sources of supply.

    WARNING

    Grounding electrical equipment.Hazardous voltage can causesevere injury or death. Electrocutionis possible whenever electricity ispresent. Ensure you comply with allapplicable codes and standards.Electrically ground the generator set,transfer switch, and related equipmentand electrical circuits. Turn off themaincircuit breakers of all power sourcesbefore servicing the equipment. Nevercontact electrical leads or applianceswhen standing in water or on wetground because these conditionsincrease the risk of electrocution.

    High voltage test. Hazardousvoltage can cause severe injury ordeath. Follow the instructions of thetest equipment manufacturer whenperforming high-voltage tests on therotor or stator. An improper testprocedure can damage equipment orlead to generator set failure.

    Installing the battery charger.Hazardous voltage can causesevere injury or death. Anungrounded battery charger maycause electrical shock. Connect thebattery charger enclosure to thegroundof a permanent wiring system. As analternative, install an equipmentgrounding conductor with circuitconductors and connect it to theequipment grounding terminal or thelead on the battery charger. Install thebattery charger as prescribed in theequipment manual. Install the batterycharger in compliance with local codesand ordinances.

    Connecting the battery and thebattery charger. Hazardous voltagecan cause severe injury or death.Reconnect the battery correctly,positive to positive and negative tonegative, to avoid electrical shock anddamage to the battery charger andbattery(ies). Have a qualifiedelectrician install the battery(ies).

    Short circuits. Hazardousvoltage/current can cause severeinjury or death. Short circuits cancause bodily injury and/or equipmentdamage. Do not contact electricalconnections with tools or jewelry whilemaking adjustments or repairs.Remove all jewelry before servicing theequipment.

    Engine block heater. Hazardousvoltage can cause severe injury ordeath. The engine block heater cancause electrical shock. Remove theengine block heater plug from theelectrical outlet before working on theblock heater electrical connections.

    Handling the capacitor. Hazardousvoltage can cause severe injury ordeath. Electrical shock results fromtouching the charged capacitorterminals. Discharge the capacitor byshorting the terminals together.(Capacitor-excited models only)

    Electrical backfeed to the utility.Hazardous backfeed voltage cancause severe injury or death. Installa transfer switch in standby powerinstallations to prevent the connectionof standby and other sources of power.Electrical backfeed into a utilityelectrical system can cause severeinjury or death to utility personnelworking on power lines.

    Testing live electrical circuits.Hazardous voltage or current cancause severe injury or death. Havetrained and qualified personnel takediagnostic measurements of livecircuits. Use adequately rated testequipment with electrically insulatedprobes and follow the instructions of thetest equipment manufacturer whenperforming voltage tests. Observe thefollowing precautions when performingvoltage tests: (1) Remove all jewelry.(2) Standonadry, approvedelectricallyinsulated mat. (3) Do not touch theenclosure or components inside theenclosure. (4) Be prepared for thesystem to operate automatically.(600 volts and under)

    Airborne particles.Can cause severe injury orblindness.

    Wear protective goggles and clothingwhen using power tools, hand tools,or compressed air.

    WARNING

    Servicing the generator set when itis operating. Exposedmoving partscan cause severe injury or death.Keep hands, feet, hair, clothing, andtest leads away from the belts andpulleys when the generator set isrunning. Replace guards, screens, andcovers before operating the generatorset.

  • 11Safety Precautions and InstructionsTP-6200 3/17

    Heavy Equipment

    Unbalanced weight.Improper lifting can cause severeinjury or death and equipmentdamage.

    Do not use lifting eyes.Lift the generator set using lifting barsinserted through the lifting holes onthe skid.

    WARNING

    Hot Parts

    Hot coolant and steam.Can cause severe injury or death.

    Before removing the pressure cap,stop the generator set and allow it tocool. Then loosen the pressure capto relieve pressure.

    WARNING

    Hot engine and exhaust system.Can cause severe injury or death.

    Do not work on the generator set untilit cools.

    WARNING

    Servicing the alternator. Hot partscan cause severe injury or death.Avoid touching the alternator field orexciter armature. When shorted, thealternator field and exciter armaturebecome hot enough to cause severeburns.

    Servicing the exhaust system. Hotparts can cause severe injury ordeath. Do not touch hot engine parts.The engine and exhaust systemcomponents become extremely hotduring operation.

    Notice

    NOTICE

    This generator set has beenrewired from its nameplate voltageto

    246242

    NOTICEVoltage reconnection. Affix a noticeto the generator set after reconnectingthe set to a voltage different from thevoltage on the nameplate. Ordervoltage reconnection decal 246242from an authorized servicedistributor/dealer.

    NOTICECanadian installations only. Forstandby service connect the output ofthe generator set to a suitably ratedtransfer switch in accordance withCanadian Electrical Code, Part 1.

  • 12 Safety Precautions and Instructions TP-6200 3/17

    Notes

  • 13IntroductionTP-6200 3/17

    Introduction

    This manual provides operation instructions for 20 kWand larger generator sets equipped with the followingcontroller:

    D Decisionr 550, Software (Code) Version 2.10 orhigher

    Version 2.10 refers to the controller applicationsoftware. To determine the generator set controllersoftware version, go to Menu 20—Factory Setup andscroll down to Code Version. The code version is thecontroller software version.

    Wiring diagram manuals are available separately.Refer to the engine operation manual for generator setengine scheduled maintenance information.

    Information in this publication represents data availableat the time of print. Kohler Co. reserves the right tochange this publication and the products representedwithout notice and without any obligation or liabilitywhatsoever.

    Read this manual and carefully follow all proceduresand safety precautions to ensure proper equipmentoperation and to avoid bodily injury. Readand follow theSafety Precautions and Instructions section at thebeginning of this manual. Keep this manual with theequipment for future reference.

    The equipment service requirements are very importantto safe and efficient operation. Inspect the parts oftenand perform required service at the prescribedintervals. Maintenance work must be performed byappropriately skilled and suitably trained maintenancepersonnel familiar with generator set operation andservice.

    The disk supplied with this generator set is a backupcopy of the generator set personality programcontaining data specific to the engine and alternator.The engine and alternator data was preprogrammed inthe controller at the factory and no further use of the diskshould be necessary. Typically, your authorizeddistributor stores this disk for possible future use suchas controller replacement or other circumstancesrequiring a backup.

    AbbreviationsThis publicationmakes use of numerous abbreviations.Typically, the word(s) are spelled out along with theabbreviation in parentheses when shown for the firsttime in a section. Appendix A, Abbreviations, alsoincludes many abbreviation definitions.

    List of Related MaterialsSeparate literature contains communication andsoftware information not provided in this manual.Figure 1 lists the available literature part numbers.

    Communication and SoftwareManual Description Literature Part No.

    550 Controller Spec Sheet G6-46

    Generator Set/ControllerWiring Diagram Manual

    Multiple Part NumbersContact your

    Distributor/Dealer

    550 Communications Spec Sheet G6-50

    Monitor III Converters, Connections,and Controller Setup TT-1405

    Monitor III Software Spec Sheet G6-76

    Monitor III Converter,Modbusr/Ethernet Spec Sheet G6-79

    Monitor III Software Operation Manual TP-6347

    Modbusr Communications ProtocolOperation Manual TP-6113

    Setup and Application Manual TP-6140

    Service Parts Controllers TP-6780

    Program Loader Software Installation TT-1285

    SiteTecht Software Operation Manual TP-6701

    Remote Serial Annunciator (RSA) TT-1377

    Remote Serial Annunciator (RSA II) TT-1485

    Controller Service Replacement TT-1310

    Figure 1 Related Literature

    Modbusr is a registered trademark of Schneider Electric.

  • 14 Service Assistance TP-6200 3/17

    Service Assistance

    For professional advice on generator set powerrequirements and conscientious service, pleasecontact your nearest Kohler distributor or dealer.

    D Consult the Yellow Pages under the headingGenerators—Electric.

    D Visit the Kohler Power Systems website atKOHLERPower.com.

    D Look at the labels and decals on your Kohler productor review the appropriate literature or documentsincluded with the product.

    D Call toll free in the US and Canada 1-800-544-2444.

    D Outside theUSandCanada, call the nearest regionaloffice.

    Headquarters Europe, Middle East, Africa(EMEA)Kohler Power Systems Netherlands B.V.Kristallaan 14761 ZC ZevenbergenThe NetherlandsPhone: (31) 168 331630Fax: (31) 168 331631

    Asia PacificPower Systems Asia Pacific Regional OfficeSingapore, Republic of SingaporePhone: (65) 6264-6422Fax: (65) 6264-6455

    ChinaNorth China Regional Office, BeijingPhone: (86) 10 6518 7950

    (86) 10 6518 7951(86) 10 6518 7952

    Fax: (86) 10 6518 7955

    East China Regional Office, ShanghaiPhone: (86) 21 6288 0500Fax: (86) 21 6288 0550

    India, Bangladesh, Sri LankaIndia Regional OfficeBangalore, IndiaPhone: (91) 80 3366208

    (91) 80 3366231Fax: (91) 80 3315972

    Japan, KoreaNorth Asia Regional OfficeTokyo, JapanPhone: (813) 3440-4515Fax: (813) 3440-2727

  • TP-6200 3/17 15Section 1 Specifications and Features

    Section 1 Specifications and Features

    1.1 IntroductionThe spec sheets for each generator set provide model-specific generator and engine information. Thecontroller spec sheet provides specifications for thiscontroller. Refer to the respective spec sheet for datanot supplied in this manual. Consult the generator setservice manual, installation manual, engine operationmanual, and engine service manual for additionalspecifications.

    1.2 Controller FeaturesThe controller features include the annunciator lamps,digital display and keypad, switches and controls, andfuses and terminal strip. The following paragraphsdetail the features by general topics.

    The controller features, accessories, and menudisplays depend upon the engine electronic controlmodule (ECM) setup and features. Controller featuresapply to generator set models with ECM and non-ECMengines unless otherwise noted.

    Note: Press any key on the keypad to turn on thecontroller lights and display. The lights anddisplay turn off 5 minutes after the last keypadentry.

    Note: Measurements display in metric or English. UseMenu 7—Generator System to change themeasurement display.

    See Figure 1-1 for an illustration of the controller frontpanel. See Figure 1-2 for an illustration of the controllerwith the keyswitch option.

    1. Emergency stop switch2. Alarm horn (see keypad for alarm silence)3. Annunciator lamps (see keypad for lamp test)4. Generator set master switch, run/off-reset/auto positions

    5. Digital display6. Keypad7. Operating guide8. Controller terminal strips (on circuit board)

    TP-6083-2

    1 2 4 5

    78

    3 6

    Figure 1-1 550 Controller with Three-Position Selector Switch

  • TP-6200 3/1716 Section 1 Specifications and Features

    1. Generator set master switch, run/off-reset/auto positions(keyswitch option)

    2. Emergency stop switch3. Alarm horn (see keypad for alarm silence)4. Annunciator lamps (see keypad for lamp test)

    5. Digital display6. Keypad7. Operating guide8. Controller terminal strips (on circuit board)

    TP-6083-2

    1 2 4 5

    78

    3 6

    Figure 1-2 550 Controller with Keyswitch Option

    1.2.1 Annunciator Lamps

    Five annunciator lamps provide visual generator setstatus. See Figure 1-3.

    TP-6083-2

    Figure 1-3 Annunciator Lamps

    System Ready. Green lamp illuminates when thegenerator set master switch is in the AUTO (automaticstart) position and the system senses no faults. The unitis ready to start.

    Not in Auto (NIA). Yellow lamp illuminates when thegenerator set master switch is not in the AUTO(automatic start) position.

    Programming Mode. Yellow programming lampindicates the user selected programming mode. SeeFigure 1-4.

    Programming Lamp Programming Mode Selection

    Lamp Flashing Local Programming

    Lamp Steady On Remote Programming

    Lamp Off Programming Disabled

    Figure 1-4 Programming Lamp Mode

    Note: Find additional information for the programmingmode lamp function and access to the local orremote programming modes in Section 2.9,Local Programming Mode On,Menu 14—Programming Mode.

  • TP-6200 3/17 17Section 1 Specifications and Features

    System Warning. Yellow lamp identifies an existingfault condition that does not shut down the generatorset. A continuing system warning fault condition maycause a system shutdown. Correct all systemwarningsas soon as practical.

    See Section 2.4.5, System Warning Lamp, fordefinitions of the items listed.

    The following conditions cause a system warning:

    D Engine functions:d ECM yellow alarm(DDC/MTU engine with MDEC/ADEC)

    d High battery voltaged High coolant temperatured Low battery voltaged Low coolant temperatured Low fuel (level or pressure)*d Low oil pressured Speed sensor faultd Starting aid (system status)d Weak battery

    D General functions:d Auxiliary—Analog up to 7 user-selectable inputseach with a high and low programmable warninglevel

    d Auxiliary—Digital up to 21 user-selectablewarnings

    d Battery charger communication errord Battery charger fault*

    Note: Optional input sensors not required withcharger GM87448.

    d Battery charger value mismatch errord Emergency power system (EPS) supplying loadd Engine cooldown delayd Engine start delayd Load shed kW overloadd Load shed underfrequencyd Master switch not in AUTO (automatic start)position

    d NFPA 110 fault (National Fire ProtectionAssociation)

    d System ready (system status)

    D Alternator functions:d AC sensing lossd Ground fault*d Overcurrent

    * Requires optional input sensors

    Note: See Figure 2-8 in User Inputs for factory-reserved analog and digital inputs that are notuser-selectable.

    System Shutdown. Red lamp indicates that thegenerator set has shut down because of a faultcondition. The unit will not start without resetting thecontroller, see Section 2.4.7, Controller ResetProcedure.

    See Section 2.4.6, System Shutdown Lamp, fordefinitions of the items listed.

    The following conditions cause a system shutdown:

    D Engine functions:d Air damper closed (status), if equippedd Coolant temperature signal lossd ECM red alarm(DDC/MTU engine with MDEC/ADEC)

    d Engine stalled (ECM only)d High coolant temperatured High oil temperatured Low coolant leveld Low oil pressured Oil pressure signal lossd Overcrankd Overspeed

    D General functions:d Auxiliary—Analog up to 7 user-selectable inputseach with a high and low programmableshutdown level

    d Auxiliary—Digital up to 21 user-selectableshutdowns

    d ECM communications loss (ECM models only)d Emergency stopd Internal faultd Master switch in OFF/RESET positiond Master switch errord Master switch opend NFPA 110 fault

    D Alternator functions:d AC output overvoltaged AC output undervoltaged Alternator protection against overload and shortcircuits

    d Field overvoltage(M4, M5, M7, or M10 alternator only)

    d Locked rotor (failed to crank)d Overfrequencyd Underfrequency

    Note:See Figure 2-8 in User Inputs for factory-reserved analog and digital inputs which arenot user-selectable.

  • TP-6200 3/1718 Section 1 Specifications and Features

    1.2.2 Digital Display and Keypad

    Figure 1-5 illustrates the digital display and keypad.

    Note: Press any key on the keypad to turn on thecontroller lights and display. The lights anddisplay turn off 5 minutes after the last keypadentry.

    The 2-line vacuum fluorescent display providesgenerator set and engine condition information.

    The 16-button keypad gives the user informationaccess and local programming capability.

    Keypad Functions

    Alarm (Horn) Off key silences the alarm horn at theoperator’s discretion. Place the generator set masterswitch in the AUTO position before silencing the alarmhorn. See Section 2.4.7, Controller Reset Procedure,and Section 1.2.3, Switches and Controls.

    AM/PM key provides time of day data entries whenprogramming.

    Enter keyprovides confirmationentrywhenselectingmenu or programming.

    Lamp Test key tests the controller indicator lamps,horn, and digital display. See Section 1.2.3, Switchesand Controls.

    Menu down key provides navigation within menuswhen necessary.

    Menu right key provides navigation within menuswhen necessary.

    Numeric 0--9 keys provide numeric data entries whenselecting menus or programming.

    Reset Menu key exits a menu, clears incorrect entries,and cancels the auto-scroll feature.

    Stop Prog (Program) Run key allows the user to stopany previously programmed generator set runsequence. See Section 1.2.3, Switches and Controls.

    Yes/No keys provides data answer entries whenprogramming.

    TP-5829-2

    Figure 1-5 Digital Display and Keypad

    Alternator Output Displays (Menu 1)

    AC Amps displays the alternator output current. Thedisplay shows each line of 3-phase models.

    AC Volts displays the alternator output voltages. Thedisplay shows all line-to-neutral and line-to-line voltagecombinations.

    Alternator Duty Level displays the actual load kWdivided by the nameplate kW rating as a percentage.

    Frequency displays the frequency (Hz) of alternatoroutput voltage.

    Hourmeter displays the generator set operating hoursloaded and unloaded for reference in schedulingmaintenance.

    KVAdisplays the total and individual L1, L2, andL3kVA.

    KVAR displays the total and individual L1, L2, and L3kVAR.

    Power Factor displays the kW/kVA and the individualline power factor values.

    Watts displays the total and individual L1, L2, and L3kilowatts.

  • TP-6200 3/17 19Section 1 Specifications and Features

    Engine Displays (Menu 2)

    Some engine displays are available with selectedgenerator set engines using engine ECMs only. Thecontroller display shows N/A (not available) for itemsthat are unavailable. See the controller spec sheet forapplicable generator set models.

    Ambient Temperature displays the generator set areaambient temperature.

    Charge Air Pressure displays the engine turbochargerboost air pressure.

    Charge Air Temperature displays the engineturbocharger boost air temperature.

    Coolant Level displays the engine coolant level.

    Coolant Pressure displays the engine coolantpressure.

    Coolant Temperature displays the engine coolanttemperature.

    Crankcase Pressure displays the engine crankcasepressure.

    DC Volts displays the voltage of starting battery(ies).

    Fuel Pressure displays the fuel supply pressure.

    FuelRate displays the calculated fuel consumption ratebased on fuel injector outputs.

    Fuel Temperature displays the fuel supplytemperature.

    Oil Level displays the engine oil level as a percent of fullcapacity.

    Oil Pressure displays the engine oil pressure.

    Oil Temperature displays the engine oil temperature.

    RPM (Tachometer) displays the engine speed.

    Used Last Run displays the accumulated amount offuel used since last reset by the engine DDEC reader.

    Operational Record Displays (Menus 4 and 5)

    The operational record displays events since last reset.See Section 2.9.4, Menu 4—Operational Records, forresetting procedure.

    Engine Start Countdown displays the time remainingbefore the next generator set startup.

    Event History displays up to 100 stored system eventsincluding status, warnings, and shutdowns.

    Last Start Date displays the date when the generatorset last operated.

    Number of Starts displays the total number ofgenerator set startup events.

    Number of Starts (Since) Last Maintenance displaysthe total number of generator set startup events sincethe last maintenance date.

    Operating Days (Since) Last Maintenance displaysthe total number of days of operation since the lastmaintenance date. A counted day of operation can be1--24 hours.

    Run Time displays the total loaded hours, totalunloaded hours, and total kW hours.

    Run Time Since Maintenance displays the totalloaded hours, total unloaded hours, and total kW hours.

    Time Delay Displays (Menu 8)

    The time delays are user adjustable. SeeSection 2.9.8,Menu 8—TImeDelays, for timedelay adjustments. SeeSection 1.3.1, Status Event and Fault Specifications, forrange and default settings.

    Crank On/Crank Pause displays the time allocated forgenerator set crank on and crank pause inminutes:seconds.

    Engine Cooldown displays the time delay for enginecooldown while the master switch is in the AUTO orRUN positions and not in the idle mode.

    Engine Start displays the time delay before thegenerator set starts while the master switch is in AUTOor RUN positions.

    Overcrank Shutdown (Number of) Crank Cyclesdisplays the number of unsuccessful crank cycles(crank on/crank pause) before the generator set shutsdown on an overcrank fault.

    Overvoltage displays the time delay before thegenerator set shuts down because of an overvoltagecondition.

    Starting Aid displays the engine starting aid activationtime.

    Undervoltage displays the time delay before thegenerator set shuts down because of an undervoltagecondition.

  • TP-6200 3/1720 Section 1 Specifications and Features

    1.2.3 Switches and Controls

    See Figure 1-6 and Figure 1-8 for switches andcontrols.

    TP-6083-2

    1. Emergency stop switch2. Alarm horn3. Generator set master switch

    1 2 3

    Figure 1-6 Switches and Alarm Horn

    Note: Find additional switches and controls inSection 2.6.1, Keypad Operation.

    Alarm Horn. The alarm horn alerts the operator orother attendants that a shutdown or warning conditionexists. SeeSection 1.3,Controller LogicSpecifications,for conditions. Place the generator set master switch inthe AUTO position before silencing the alarm horn. Thealarm horn cannot be silenced unless the generator setmaster switch is in the AUTO position. SeeSection 2.4.7, Controller Reset Procedure.

    Alarm (Horn) Off. The keypad switch silences thealarm horn at the operator’s discretion. Place thegenerator setmaster switch in theAUTOposition beforesilencing the alarm horn. Restore alarm horn switchesat all locations including those on remote annunciatorand audiovisual alarm kits to the normal position aftercorrecting the fault shutdown to avoid reactivating thealarm horn. See Section 2.4.7, Controller ResetProcedure.

    AM/PM. This keypad switch provides time of day dataentries when programming.

    Emergency Stop. The operator-activated pushbuttonimmediately shuts down the generator set inemergency situations. Reset the emergency stopswitch after shutdown by pulling the switch knoboutward. Use the emergency stop switch foremergency shutdowns only. Use the generator setmaster switch for normal shutdowns.

    Generator Set Master Switch (Run/Off-Reset/Auto).This switch resets the controller fault lamps andstart/stops the generator set. Refer to Section 2.4.1,Starting, Section 2.4.2, Stopping, and Section 2.4.3,Emergency Stop Switch Reset Procedure.

    The generator set master switch with the keyswitchoption (Figure 1-7) is available tomeet appropriate localcode requirements. The key is removable in the AUTOposition only.

    TP-6083-2

    Figure 1-7 Generator Set Master Switch withKeyswitch Option

    Lamp Test. The keypad switch tests the controllerindicator lamps, horn, and digital display. Press thereset menu key before pressing the lamp test key.

    Stop Prog (Program) Run. Keypad switch allows theuser to stop any previously programmed generator setrun sequence.

    1

    2

    TP-5829-2

    1. Lamp test2. Alarm horn silence3. Stop program run

    3

    Figure 1-8 Keypad Switches

  • TP-6200 3/17 21Section 1 Specifications and Features

    1.2.4 Controller Circuit Boards

    The controller has five circuit boards—indicator,interconnection, keypad, digital display, and main logic/communication. See Figure 1-9 for circuit boardlocations.

    1 2

    GM10193B-A

    34

    1. AC fuse block (TB5)2. Interconnection circuit board TB1, TB2, TB3, and TB4

    terminal strips and F1, F2, and F3 fuses3. Main logic (microprocessor)/communication circuit board4. Keypad and digital display circuit boards5. Indicator circuit board (LED and alarm horn)

    5

    Figure 1-9 Controller Circuit Boards and Fuses(Controller Top View)

    Indicator (Status) Circuit Board includes the LEDstatus lamps, alarm horn, and generator set masterswitch.

    Interconnection Circuit Board provides the terminalstrips to connect the controller (customer) connectionboard and/or dry contact kits and three DC fuses (F1,F2, and F3). See 6.1.4 for more information.

    Keypad (Switch Membrane) Circuit Board providesthe keypad to navigate the generator set displays andenter data.

    Digital Display Circuit Board provides the vacuumfluorescent display (VFD) for monitoring the generatorset functions and output values.

    Main Logic (Microprocessor)/CommunicationCircuit Board provides the controller operation logicand provides PC communication locally (direct) orremotely (via modem) using RS-232 or RS-485connectors.

    1.2.5 Fuses

    AC Circuit Fuses (TB5). Fuses are located inside thecontroller. See Figure 1-9.

    D 1.5-Amp (V7) fuse protects L1 sensing input tointerconnection circuit board.

    D 1.5-Amp (V8) fuse protects L2 sensing input tointerconnection circuit board.

    D 1.5-Amp (V9) fuse protects L3 sensing input tointerconnection circuit board.

    DC Circuit Fuses fuses are located on the controllerinterconnection circuit board.

    D 5-Amp Remote Annunciator (F1) fuse protects thedry contact kit if equipped and the controller panellamps.

    D 5-Amp Controller (F2) fuse protects the controllercircuitry.

    D 15-Amp Engine and Accessories (F3) fuseprotects the engine/starting circuitry andaccessories.

    1.2.6 Terminal Strips and Connectors

    Terminal strips and connectors for inputs and outputsare located on the interconnection circuit board. SeeSection 6, Accessories.

    TB1 Input Connection Terminal Strip provides inputconnections for remote start and emergency stop(E-Stop).

    TB2 Analog Input Connection Terminal Stripprovides analog input connections, including non-ECMsensor connections.

    TB3 Accessory Power Output Connection TerminalStrips provides a generator set power supply for factoryuse.

    TB4 Digital Input Connection Terminal Stripsconnect external devices (engine ECM and usersupplied) to the generator set digital inputs.

    P23 Connector connects the interconnection circuitboard to the controller (customer) connection terminalstrip (connector P25) inside the junction box. See 6.1.4for more information.

  • TP-6200 3/1722 Section 1 Specifications and Features

    Figure 1-10 shows locations of the terminal strips on thecontroller interconnection circuit board. SeeSection 6.2,Accessory and Connections, for specific terminalidentification information. Refer to the wiring diagramsfor additional information on connecting accessories tothe terminal strips.

    1. TB1 terminal strip2. TB2 terminal strip3. P1 Connector

    ADV-6533-A

    2 41 5 6

    4. P23 Connector5. TB3 terminal strip6. TB4 terminal strip

    3

    Figure 1-10 Interconnection Circuit Board TerminalStrips and Connectors

    1.2.7 Circuit Board Interconnections forCalibration Procedure

    The interconnection circuit board shown in Figure 1-11contains a ribbon connector that requires disconnectionduring the calibration procedure in Menu 12—Calibration. Disconnect ribbon connector P2 prior tozeroing out (resetting) the auxiliary analog inputs.

    2

    4

    1

    1. Interconnection circuit board2. P2 ribbon connector3. P12 ribbon connector4. Main logic circuit board

    ADV-6533-A

    4

    Figure 1-11 Interconnection Circuit Board RibbonConnector P2 (Top View of CircuitBoard)

  • TP-6200 3/17 23Section 1 Specifications and Features

    1.2.8 Communication Ports

    The main logic circuit board contains severalcommunication ports for Modbusr and KBUSconnections. See Figure 1-12. Refer to the List ofRelated Materials in the Introduction for correspondingcommunication installation information.

    1. P19—Modbus (ISO2), RS-485 port2. P21—KBUS isolated connection (ISO1), RS-485 port3. P18—KBUS or Modbusr, RS-232 port

    (Monitor III connection)4. P20—Modbus, RS-485 port (Monitor III connection)5. P22—ECM connector6. Main logic circuit board

    ADV-6533-A

    1 2 3 4 5

    6

    Figure 1-12 Main Logic Circuit Board CommunicationPorts (Top View of Circuit Board)

    1.3 Controller Logic SpecificationsThe controller logic specifications section is anoverview of the various features and functions of thecontroller. Certain features function only when optionalaccessories are connected. See Section 2, Operation,for details.

    The default selection time delays and relay driveroutputs (RDOs) are factory set and adjustable with theprogramming mode on (Menu 14). Some data entriesrequire using a PC in the Remote Programming mode.See the monitor software operation manual for details.

    Inhibit Time Delay. The inhibit time delay is the timeperiod following crank disconnect during which thegenerator set stabilizes and the controller does notdetect a fault or status event. Select the desired inhibittime delay from 0 to 60 seconds.

    TIme Delay (Shutdown or Warning). The time delayfollows the inhibit time delay. The time delay is the timeperiod between when the controller first detects a faultor status event and the controller warning or shutdownlamp illuminates. The delay prevents any nuisancealarms. Select the desired time delay from 0 to60 seconds.

    1.3.1 Status Event and FaultSpecifications

    The table starting on the next page contains all statusevents and faults with ranges and time delays includingitems that do not have adjustments.

    Note: The engine ECMmay limit the crank cycle even ifthe controller is set to a longer time period.

    Modbusr is a registered trademark of Schneider Electric.

  • TP-6200 3/1724 Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    Referto

    Menu Digital Display

    RelayDriverOutput(RDO)

    AlarmHorn Lamp Range Setting

    DefaultSelection

    InhibitTimeDelay(sec.)

    TimeDelay(sec.)

    Access Code(password)

    14 User-Selectable 0 (zero)

    AC Sensing Loss 10 AC SENSINGLOSS

    RDO-25 * On Warning

    Air Damper Control(if used) **

    10

    Air Damper Indicator(if used), see D20 **

    Air/Fuel Module(AFM) Engine StartDelay ]

    10 AFM ENGSTART DELAY

    Fixed

    Air/Fuel Module(AFM) RemoteStart]

    10 AFM REMOTESTART

    RDO-25 ] Off

    Air/Fuel Module(AFM) Shutdown(see D11) ]

    Alternator ProtectionShutdown

    10 ALTERNATORPROTECTION

    On Shutdown

    Analog Aux. Input 0 9 LOCAL BATTVDC

    Fixed

    Analog Aux. InputsA01--A07

    9 USER-DEFINEDA01--A07

    On Shutdownor

    Warning

    Default Values withWarning Enabled:HI warning 90%LO warning 10%HI shutdown 100%LO shutdown 1%

    30 sec.inhibit,

    5 sec. delay

    0--60 0--60

    Analog Aux. InputA01 (non-ECM only)

    9 A01COOLANTTEMP

    On Shutdownor

    Warning

    Default Values withWarning Enabled:HI/LO warning andHI/LO shutdown areall engine dependent

    30 sec.inhibit,

    0 sec. delaywarning,

    5 sec. delayshutdown

    Analog Aux. InputA02 (non-ECM only)

    9 A02OIL

    PRESSURE

    On Shutdownor

    Warning

    Default Values withWarning Enabled:HI/LO warning andHI/LO shutdown areall engine dependent

    (255 psi max.)

    30 sec.inhibit,

    0 sec. delaywarning,

    5 sec. delayshutdown

    Analog Aux. InputA03 ]

    9 A03INTAKE AIR

    TEMP

    Shutdownor

    Warning

    Default Values withWarning Enabled:HI/LO warning andHI/LO shutdown areall engine dependent

    30 sec.inhibit,

    0 sec. delaywarning

    Analog Aux. InputA04 *

    9 A04FUEL LEVEL

    Default Values withWarning Enabled:HI/LO warning areengine dependent

    30 sec.inhibit,

    0 sec. delaywarning

    Analog Aux. InputA04 ]

    9 A04OIL TEMP

    On Warning Default Values withWarning Enabled:HI/LO warning areengine dependent

    30 sec.inhibit,

    0 sec. delaywarning

    Analog Aux. InputA06 VSG (Volvo,GM, Doosan, KDIonly)

    9, 12 A06 ANALOGAUXILIARY IN

    Off

    Analog Aux. InputA07

    9 A07ANALOG VOLT

    ADJUST

    10% of systemvoltage over the range

    of 0.5--4.5 VDC

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/17 25Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Battery ChargerCommunication Error

    CHRG COMMERROR

    On Warning

    Battery Charger Fault(see D01) **Note: On chargerGM87448, BatteryCharger Fault iscommunicatedthrough CANcommunication andD01 is not used.

    BATTERYCHRGR FAULT

    On Warning

    Battery ChargerValue Error

    CHGR VALERROR

    On Warning

    Battle Switch(Fault ShutdownOverride Switch)

    9 BATTLESWITCH

    Off Warning Fixed

    Block HeaterControl[[

    10 BLOCK HEATERCONTROL

    RDO only

    Breaker Trip w 10 BREAKERTRIP

    RDO-30 Off Warning

    Charger AbsorptionCurrent TerminationTarget (A)

    18 ABSORPTIONTERMINATION 1 – 5 2

    Charger AutomaticEqualize Enable

    Note: Equalize isonly available withFLA/VRLA topologyselected.

    18AUTOMATICEQUALIZEENABLED

    ActiveInactive Inactive

    Charger ChargeCycles Between AutoEqualize Cycles

    Note: Equalize isonly available withFLA/VRLA topologyselected.

    18 0 – 99

    Charger CustomProfile Enable 18

    CUSTOMCHARGINGPROFILEENABLE

    ActiveInactive Inactive

    Charger DepletedBattery Current Limit 18 1 – 5 2

    Charger DepletedBattery VoltageTarget 18

    4 – 12(12 V)

    18 – 24(24 V)

    10(12 V)

    20(24 V)

    Charger EqualizeStage Duration (Min)

    Note: Equalize isonly available withFLA/VRLA topologyselected.

    18 60 – 480

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/1726 Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Charger ManualEqualize CycleActivation

    Note: Equalize isonly available withFLA/VRLA topologyselected.

    18MANUALEQUALIZEACTIVE

    ActiveInactive Inactive

    Charger MaximumAbsorption TimeThreshold (Min.)

    18MAX

    ABSORPTIONTIME

    60 – 360

    60 – 600 (NiCad only)240

    Charger MaximumBulk Time Threshold(Min)

    18 MAX BULKTIME 60 – 600 480

    Charger RefreshCharge Cycle Time(Hr)

    18 0,23 – 672 335

    Charger Return ToBulk State VoltageThreshold (V) 18

    BULK STATERETURNVOLTAGE

    10 – 13(12 V)20 – 26(24 V)

    12.8(12 V)

    25.6(24 V)

    Charger StarterBattery Topology

    Note: Verify that thebattery topology isset correctly for thebattery type that isused. Incorrectcharger outputsystem voltage maycause irreversibledamage to thebattery and abnormalout gassing.

    18 BATTERYTOPOLOGY

    DefaultFLA/VRLA

    AGMGel

    NiCad

    Default

    Charger SystemBattery Voltage

    Note: Verify that thesystem voltage is setcorrectly for thebattery type that isused. Incorrectcharger outputsystem voltage maycause irreversibledamage to thebattery and abnormalout gassing.

    18CHARGERSYSTEMVOLTAGE

    System 12 VDC

    System 24 VDC12 VDC

    Charger TemperatureCompensationEnable 18

    TEMPCOMPENSA--

    TIONENABLED

    ActiveInactive Inactive

    Charger TemperatureCompensation Slope(mV/_C) 18

    TEMPERA--TURE COMP

    SLOPE

    --40 – 0(12 V)

    -80 – 0(24 V)

    -30(12 V)

    --60(24 V)

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/17 27Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Charger VoltageAbsorption (V)

    18 ABSORPTIONVOLTAGE

    13 – 15(12 V)26 – 30(24 V)

    14.25(12 V)

    28.5(24 V)

    Charger Voltage Bulk(V)

    18 BULKVOLTAGE

    13 – 15(12 V)26 – 30(24 V)

    14.25(12 V)

    28.5(24 V)

    Charger VoltageEqualize (V)

    Note: Equalize isonly available withFLA/VRLA topologyselected.

    18 EQUALIZEVOLTAGE

    14 – 16(12 V)

    28 – 32(24 V)

    Charger VoltageFloat (V)

    18 FLOATVOLTAGE

    13 – 14(12 V)26 – 28(24 V)

    13.25(12 V)

    26.5(24 V)

    Common ProtectiveRelay Output w

    10 COMMON PROUTPUT

    RDO-31 w Off Warning

    Critical OvervoltageShutdown

    10 CRITICALOVERVOLTAGE

    On Shutdown Fixed 275 volts(L1--L2)

    Cyclic Cranking 8 Off 1--6 crank cycles10--30 sec. crank on1--60 sec. pause

    315 sec.15 sec.

    Defined CommonFaults(each input value isset separately)

    10 DEFINEDCOMMONFAULT

    RDO-18(lead 32A)

    On Shutdownor

    Warning

    Default shutdownsinclude:

    Emergency stopHigh coolant tempLow oil pressure

    OvercrankOverspeed

    30 sec.inhibit,

    5 sec. delay

    0--60 0--60

    Detonation Shutdown(see D13) ]

    Detonation Warning(see D12) ]

    Digital Aux. InputD01--D21

    9, 10 USER-DEFINEDD01--D21

    On Shutdownor

    Warning

    30 sec.inhibit,

    5 sec. delay

    0--60 0--60

    Digital Aux. InputD01 Battery ChargerFault **(On chargerGM87448, BatteryCharger Fault iscommunicatedthrough CANcommunication andD01 is not used.)

    9, 10 D01 BATTERYCHARGERFAULT

    RDO-11(lead 61)

    On Warning Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD02 Low FuelWarning **

    9, 10 D02LOW FUELWARNING

    RDO-08(lead 63)

    On Warning Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD03 Low CoolantTemperature **

    9, 10 D03 LOWCOOLANTTEMP

    RDO-05(lead 35)

    On Warning Fixed 0 sec.inhibit,

    0 sec. delay

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/1728 Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Digital Aux. InputD04 FieldOvervoltage (M4, M5,M7, or M10 alt. only)

    9, 10 D04FIELD

    OVERVOLTAGE

    On Shutdown Fixed 1 sec.inhibit,15 sec.delay

    Digital Aux. InputD05 BreakerClosed w

    9, 10 D05BREAKERCLOSED

    Off Warning Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD06 w

    9, 10 D06 ENABLESYNCH

    20 sec.inhibit, 0sec. delay

    Digital Aux. InputD09 Low FuelPressure Shutdown(125RZG only)

    9, 10 D09LOW FUELSHUTDOWN

    On Shutdown Fixed 5 sec.inhibit,

    0 sec. delay

    Digital Aux. Input D11Air/Fuel Module(AFM) Shutdown ]

    9, 10 D11AFM

    SHUTDOWN

    On Shutdown Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD12 DetonationWarning ]

    9, 10 D12DETON

    WARNING

    On Warning Fixed 2 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD13 DetonationSensing Module(DSM) Shutdown ]

    9, 10 D13DETON

    SHUTDOWN

    On Shutdown Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD13 Knock DetectionModule (KDM)Shutdown ]

    9, 10 D13KNOCK

    SHUTDOWN

    On Shutdown Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. Input D14Low Coolant Level,(with LCL switch) **

    9, 10 D14 LOWCOOLANT LVL

    RDO-19 On Shutdown Fixed 30 sec.inhibit,

    5 sec. delay

    Digital Aux. InputD15 RemoteShutdown

    9, 10 D15 REMOTESHUTDOWN

    On Shutdown 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD16 Remote Reset

    9, 10

    Digital Aux. InputD17 VAR/PF mode

    9, 10

    Digital Aux. InputD18 Voltage Lower

    9, 10

    Digital Aux. InputD19 Voltage Raise

    9, 10

    Digital Aux. InputD20 Air DamperIndicator (if used) **

    9, 10 D20AIR DAMPER

    RDO-23 *(lead 56)

    On Shutdown Fixed 0 sec.inhibit,

    0 sec. delay

    Digital Aux. InputD21 Idle (speed)Mode Function

    9, 10 D21IDLE MODEACTIVE

    RDO-21 Off Warning Fixed inhibit time 0 sec.inhibit,60 sec.delay

    0--600or 9:99for

    infinity

    ECM Red Alarm(was MDEC RedAlarm) [[

    10 ECM REDALARM

    On Shutdown

    ECM Yellow Alarm(was MDEC YellowAlarm) [[

    10 ECM YELLOWALARM

    On Warning

    EEPROM WriteFailure

    10 EEPROM WRITEFAILURE

    On Shutdown

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/17 29Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Emergency StopShutdown

    10 EMERGENCYSTOP

    RDO-14(lead 48)

    On Shutdown

    Engine Cooldown(see Time Delay--)

    Engine Derate Active 10 ENGINEDERATEACTIVE

    (Engine) J1939 CANShutdown(ECM only)

    10 J1939 CANSHUTDOWN

    On Shutdown

    Engine Stalled(ECM only)

    10 ENGINESTALLED

    On Shutdown

    Engine Start(see Time Delay--)

    EPS (EmergencyPower System)Supplying Load

    10 EPS SUPPLYINGLOAD

    RDO-22 Off Warning Fixed 1% of ratedline current

    Equalize CurrentLimit (A)

    Note: Equalize isonly available withFLA/VRLA topologyselected.

    18 1–5

    Field Overvoltage(see D04)

    Forced Charge CycleReset 18

    ActiveInactive Inactive

    Fuel Level (see A04)

    Fuel Valve Relay ] 10 FUEL VALVERELAY

    RDO-23 ]

    Generator SetRunning

    10 RDO-15(lead 70R)

    Off

    Ground FaultDetected

    10 GROUNDFAULT

    On Warning

    High Battery Voltage 10 HIGHBATTERYVOLTAGE

    RDO-13 Off Warning 14.5--16.5 V (12 V)29--33 V (24 V)

    16 V (12 V)32 V (24 V)

    10

    High CoolantTemperatureShutdown

    10 HI COOL TEMPSHUTDOWN

    RDO-03(lead 36)

    On Shutdown 30 5

    High CoolantTemperature Warning

    10 HI COOL TEMPWARNING

    RDO-06(lead 40)

    On Warning 30

    High Oil TemperatureShutdown

    10 HI OIL TEMPSHUTDOWN

    On Shutdown 30 5

    High Oil TemperatureWarning ] [[

    10 HI OIL TEMPWARNING

    On Warning 30

    Idle (speed) ModeFunction (see D21)

    In Synch w 10 IN SYNCH RDO-29 *

    Intake AirTemperatureShutdown [[

    10 INTAKE AIRTEMP SDWN

    On Shutdown 30

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/1730 Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Intake AirTemperature Warning[[

    10 INTAKE AIRTEMP WARN

    On Warning 30

    Intake Air TempWarning (see A03) ]

    Intake Air TempShutdown (see A03)]

    Internal FaultShutdown

    10 INTERNALFAULT

    On Shutdown

    J1939 CANShutdown (seeEngine J1939 CANShutdown)

    Knock Shutdown(see D13) ]

    kW Overload(see Load Shed)

    Load ShedkW Overload ]]

    10 LOAD SHEDKW OVER

    RDO-30 ]] Off Warning 80%--120% 100% of kWrating with5 sec. delay

    2--10

    Load Shed OverTemperature [[(Activated by a HighCoolant Temp.shutdown)

    10 LOAD SHEDOVER

    TEMPERATURE

    RDO only

    Load ShedUnderfrequency [

    10 LOAD SHEDUNDER

    FREQUENCY

    RDO-31 [ Off Warning 59 Hz(60 Hz)49 Hz(50 Hz)

    5

    Locked RotorShutdown

    10 LOCKEDROTOR

    On Shutdown

    Loss of ECMCommunication(ECM only)

    10 LOSS OF ECMCOMM

    RDO-26 * On Shutdown 4

    Loss of FieldShutdown w

    10 SD LOSS OFFIELD

    On Shutdown

    Low Battery Voltage 10 LOW BATTERYVOLTAGE

    RDO-12(lead 62)

    Off Warning 10--12.5 V (12 V)20--25 V (24 V)

    12 V (12 V)24 V (24 V)

    0 10

    Low Coolant Level(see D14) (with LCLswitch) **

    Low CoolantTemperature (seeD03) **

    Low CoolantTemperatureShutdown [[

    10 LOW COOLANTTEMP

    SHUTDOWN

    On Shutdown

    Low Fuel (Level orPressure) Warning(see D02) **

    Low Fuel PressureShutdown (see D09)(125RZG only)

    (Low) Oil PressureShutdown

    10 OILPRESSURESHUTDOWN

    RDO-04(lead 38)

    On Shutdown 30 5

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/17 31Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    (Low) Oil PressureWarning

    10 OILPRESSUREWARNING

    RDO-07(lead 41)

    On Warning 30

    Maintenance Due 10 MAINTENANCEDUE

    Master Not In Auto(Generator SetSwitch)

    10 MASTER NOTIN AUTO

    RDO-09(lead 80)

    On Warningand NotIn Auto

    Master Switch Error 10 MASTERSWITCHERROR

    On Shutdown

    Master Switch to Off 10 MASTERSWITCH TO

    OFF

    On Shutdownand Not in

    Auto

    Master Switch Open 10 MASTERSWITCH OPEN

    On Shutdown

    NFPA 110 Fault ** 10 NFPA 110FAULT

    RDO-10(lead 32)

    On Shutdownor

    Warning

    No Air TemperatureSignal Warning ]

    10 NO AIR TEMPSIGNAL

    On Warning 30 4

    No CoolantTemperature Signal

    10 NO COOLTEMP SIGNAL

    On Shutdown 30 4

    No Oil PressureSignal

    10 NO OILPRESSURESIGNAL

    On Shutdown 30 4

    No Oil TemperatureSignal Warning ]

    10 NO OIL TEMPSIGNAL

    On Warning 30 4

    Output Enable 18 Fixed Active

    Overcrank Shutdown 8, 10 OVER CRANK RDO-02(lead 12)

    On Shutdown 0--6 Cycles 3 Cycles

    Overcurrent 10 OVERCURRENT

    On Warning 110% 10

    Over Current PRShutdownw

    10 SD OVERCURRENT PR

    On Shutdown

    OverfrequencyShutdown

    7, 10 OVERFREQUENCY

    RDO-28 On Shutdown 102%--140% 110% Std.103% FAA

    10

    Over PowerShutdown w

    10 SD OVERPOWER

    On Shutdown 102% Stdby112% Prime

    Overspeed Shutdown 7, 10 OVER SPEED RDO-01(lead 39)

    On Shutdown 65--70 Hz (60 Hz)55--70 Hz (50 Hz)

    70 (60 Hz)70 (50 Hz)

    0.25

    OvervoltageShutdown

    7, 8,10

    OVERVOLTAGE

    RDO-20(lead 26)

    On Shutdown 105%--135%of nominal

    115%2-sec timedelay[135%

    10-sec timedelayw

    2--10

    Password(see Access Code)

    Pre Lube Relay ] 10 PRE LUBERELAY

    RDO-26 ] 4

    Remote Reset(see D16)

    Remote Shutdown(see D15)

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/1732 Section 1 Specifications and Features

    Factory-Defined Settings

    Status Eventor Fault

    TimeDelay(sec.)

    InhibitTimeDelay(sec.)

    DefaultSelectionRange SettingLamp

    AlarmHorn

    RelayDriverOutput(RDO)Digital Display

    Referto

    Menu

    Reverse PowerShutdown w

    10 SD REVERSEPOWER

    On Shutdown

    Speed Sensor Fault 10 SPEEDSENSORFAULT

    RDO-24 On Warning

    Starting Aid (seeTime Delay StartingAid)

    System Ready 10 RDO-17(lead 60)

    Off SystemReady

    Time Delay EngineCooldown (TDEC)

    8, 10 DELAY ENGCOOLDOWN

    RDO-16(lead 70C)

    Off 00:00--10:00min:sec

    5:00

    Time Delay EngineStart (TDES)

    8, 10 DELAY ENGSTART

    Off 00:00--5:00min:sec

    00:01

    Time Delay StartingAid

    8, 10 Off 0--10 sec.

    TurbochargerTemperatureShutdown(1750/2000REOZMD)

    10 TURBO TEMPSHUTDOWN

    On Shutdown 30

    TurbochargerTemperature Warning(1750/2000REOZMD)

    10 TURBO TEMPWARNING

    On Warning 30

    Underfrequency 7, 10 UNDERFREQUENCY

    RDO-29 ] On Shutdown 80%--97% 97% FAA90%[80%w

    10

    UndervoltageShutdown

    7, 8,10

    UNDERVOLTAGE

    RDO-27 On Shutdown 70%--95% 85%10-sec timedelay[70%

    30-sec timedelayw

    5--30

    Variable SpeedGovernor (VSG)(see A06)

    VAR/PF Mode(see D17)

    Voltage Lower(see D18)

    Voltage Raise(see D19)

    Weak Battery 10 WEAKBATTERY

    Off Warning 60% ofnominal

    2

    * All models, except Waukesha-powered models. ** NFPA applications[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC] Waukesha-powered models ]] FAA onlyw Paralleling applications Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to thebattery charger operation manual.

  • TP-6200 3/17 33Section 1 Specifications and Features

    CalibrationRefer toMenu Digital Display Range Setting Default Selection

    Voltage Adjustment 11 VOLT ADJ 10% of system voltage—Version 2.10

    20% of system voltage—Version 2.11 or higher

    System voltage

    Underfrequency UnloadFrequency Setpoint

    11 FREQUENCYSETPOINT

    40 to 70 Hz 1 Hz below system frequency (ECM)2 Hz below system frequency (non-ECM)

    Underfrequency UnloadSlope

    11 SLOPE 0--10% of rated voltagevolts per cycle

    3.1% of system voltage

    Reactive Droop 11 VOLTAGEDROOP

    0--10% of system voltage 4% of system voltage

    VAR Control 11 KVAR ADJ 0 to rated kVAR generating0 to 35% of rated kVAR absorbing

    0

    Power Factor (PF) AdjustControl

    11 PF ADJ 0.7 to 1.0 leading0.6 to 1.0 lagging

    0.8 lagging

    Controller Gain 11 REGULATORGAIN

    1--10000 100

    VAR/PF Gain or UtilityStability

    11 VAR/PF GAIN 1--10000 100

    Figure 1-13 Settings for Controller Internal Voltage Regulation

    1.3.2 Voltage Regulator and CalibrationSpecifications

    The 550 controller has a voltage regulation function thatis internal to the processor. Thismeans that no externalvoltage regulator is necessary. The voltage regulationof the controller uses root mean square (rms) sensingfor fast response to changes in indicated and regulatedvoltages resulting in excellent regulation accuracy.

    RMS voltage regulation is available for both parallelingand utility application to control changes in the reactiveloads due to load changes, prime mover speedvariation, thermal drift, and other variations. SeeFigure 1-13 for data on the 550 controller voltageregulation. Refer to Appendix C to customizeadjustments for specific applications.

    1.3.3 Voltage Regulator Adjustments

    The descriptions of the voltage regulator adjustmentsand features follow. SeeAppendixC,VoltageRegulatorDefinitions and Adjustments, for additional information.

    Voltage Adjustment. The voltage adjustment allowsthe user to enter the desired generator set output level.This regulated level setting is the average of the threeline-to-line voltages in three-phase configurations orL1-to-L2 in single ph