111
ISA-HD Medium Voltage Soft Starters Instruction Manual

IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

  • Upload
    others

  • View
    10

  • Download
    6

Embed Size (px)

Citation preview

Page 1: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

ISA-HD

Medium Voltage Soft Starters

Instruction Manual

Page 2: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

II 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Page 3: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual III

Table of contents

1 Definitions and Warning Information .............................................................. 5

1.1 Definitions, warning information ............................................................. 5

1.2 Electrostatic sensitive devices (ESD) ..................................................... 7

1.3 Special warnings .................................................................................... 8

2 Starter Selection .............................................................................................. 10

2.1 Starter Selection - Presentation ............................................................ 10

2.2 Motor current and starting conditions ................................................... 10

2.3 Storage ................................................................................................. 11

2.4 Temperature Range & Heat Dissipation ............................................... 11

2.5 PIV (Peak Inverse Voltage) ratings....................................................... 12

2.6 Mains voltage ....................................................................................... 13

2.7 Control voltage ..................................................................................... 13

2.8 Control inputs ....................................................................................... 13

2.9 Options ................................................................................................. 14

3 Installation ....................................................................................................... 15

3.1 Prior to installation ................................................................................ 15

3.2 Mounting ............................................................................................... 15

3.3 Power section connections ................................................................... 16

4 Internal Settings .............................................................................................. 19

4.1 Internal settings - components and connections .................................. 19

4.2 Control Module ..................................................................................... 20

4.3 Memory system operation .................................................................... 20

4.4 First control voltage connection ............................................................ 21

4.5 Test and Maintenance modes .............................................................. 21

4.6 Dip switch settings ................................................................................ 27

Page 4: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

IV 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

4.7 Analog I/O (Option 5) (Terminals Gnd, Out (-), Out (+)) ...................... 30

4.8 Overload Protection Class IEC ............................................................. 32

4.9 Overload Protection Class NEMA......................................................... 33

4.10 Terminal 7 and Terminal 8 Programming ............................................. 34

4.11 Special Control for Synchronous Motors Excitation ............................ 35

5 Control Terminals ........................................................................................... 36

6 Option Boards ................................................................................................. 44

6.1 Possible options and settings ............................................................... 44

7 Control wiring .................................................................................................. 48

8 Start and Stop Parameters ............................................................................. 49

8.1 Description of start curves .................................................................... 49

8.2 Description of stop curves .................................................................... 55

9 Motor and Starter Protection .......................................................................... 59

10 Front Panel ...................................................................................................... 69

10.1 Overview of the front panel ................................................................... 69

10.2 Display Mode ........................................................................................ 72

10.3 Remote Display .................................................................................... 76

11 Parameter Setting ........................................................................................... 77

12 Menu Description .......................................................................................... 101

13 Contents of figures ....................................................................................... 107

14 Contents of tables ......................................................................................... 109

15 Notice ............................................................................................................. 110

Page 5: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Definitions and Warning Information

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 5 / 111

1 Definitions and Warning Information

1.1 Definitions, warning information

Qualified personnel

To the effect of this instruction manual and product labels, a "Qualified

Person" is someone who is familiar with the installation, mounting,

start-up and operation of the equipment and the hazards involved. He

or she must have the following qualifications:

Trained and authorized to energize, de-energize, clear, ground

and tag circuits and equipment in accordance with established

safety procedures.

Trained in the proper care and use of protective equipment in

accordance with established safety procedures.

Trained in rendering first aid.

Safety Guidelines

This manual contains notes which should be observed to ensure per-

sonal safety, as well to protect the product and connected equipment.

These notices are highlighted in the manual by a warning triangle and

are marked as follows to the level of danger.

Danger

Indicates that no observance of the relevant safety measures will re-

sult in death, serious injury and/or substantial material damage.

Warning

Indicates that no observance of the relevant safety measures can re-

sult in death, serious injury and/or substantial material damage.

Page 6: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Definitions and Warning Information

6 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Caution

Caution in conjunction with the warning triangle indicates that non ob-

servance of the relevant safety measures can result in minor or mod-

erate injury and/or material damage.

Caution

Caution without the warning triangle indicates that non observance of

the relevant safety measures can result in material damage.

Notice

NOTICE used without the warning triangle indicates that non ob-

servance of the respective notice can result in an undesirable effect or

status.

Note

A note represents important information about the product or a section

of the instructions which requests careful attention and can give valu-

able hints for the interest of the user.

For proper handling Note:

Warning

Electrical equipment contains components which are at dangerous

voltage levels.

Non observance can result in severe bodily injury and material dam-

age.

Only appropriately qualified and trained personnel is authorized to

work on this equipment or in its vicinity.

This personnel must be completely knowledgeable about all warnings

and service measures according to this instruction manual.

The successful and safe operation of this equipment is dependent on

proper handling, installation, operation and maintenance.

Page 7: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Definitions and Warning Information

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 7 / 111

Country-specific safety guidelines and regulations must be observed

carefully

Notation of Keys

Note

refers to keys on the operator panel,

refers to pushbuttons on the front door

1.2 Electrostatic sensitive devices (ESD)

ESD Guidelines

Caution

Electronic modules contain electrostatic sensitive devices that can be

destroyed easily, if they are handled incorrectly. However, if envisaged

manipulation does involve handling of such devices, the following in-

formation must be observed:

Electronics modules should not be touched unless work has to

be carried out on them.

If it is essential to touch an electronic module, the body must be

electro statically discharged beforehand.

Modules may not come into contact with electrically insulating

materials such as plastic foil, insulating table tops or clothing

made of synthetic fibers.

Modules may only be placed on electrically conducting surfaces.

Modules and electronic components should always be packed in

electrically conducting containers (such as metalized plastic

boxes or metal canisters) before being stored or shipped.

If packing containers are used, which are not conductive, mod-

ules and boards must be wrapped in a conducting material first.

Page 8: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Definitions and Warning Information

8 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Such materials are e.g. electrical conducting foam rubber or

household aluminium foil.

For easy reference, the protective measures necessary for handling

electrostatic sensitive devices are illustrated in the sketches below:

1.3 Special warnings

Figure 1 ESD-notes

General Aspects

Danger

This manual should be read carefully before operating the equipment

and the instructions contained should be observed.Installation, opera-

tion and maintenance should be performed strictly according to this

manual, national codes and good practice. Installation or operation not

performed in strict accordance with these instructions will void manu-

facturer's warranty.Disconnect all power inputs before servicing the

soft-starter and/or the motor.After installation, check and verify that no

parts (bolts, washers, etc) have fallen into the power section (IP00).

Page 9: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Definitions and Warning Information

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 9 / 111

Warning

Internal components and PCBs are at mains potential when the ISA-

HD is connected to main voltage. This voltage is extremely dangerous

and will cause death or serious injury if contacted.When the ISA-HD is

connected to the main voltage - even if control voltage is disconnected

and the motors is stopped - full voltage may appear on starter's output

and motor's terminals.Unit must be grounded to ensure correct opera-

tion, safety and to prevent damage.Power factor capacitors must not

be connected to the output side of the soft starter. If power factor ca-

pacitors are installed, they must be connected upstream the line con-

tractor.

Caution

This product is designed for compliance with IEC 947-4-2 for class A

equipment. For further information please refer to the technical speci-

fication

The manufacturer reserves the right to make any improvements

or modifications to its products without prior notice.

Page 10: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Starter Selection

10 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

2 Starter Selection

2.1 Starter Selection - Presentation

Principle description

ISA-HD is a highly sophisticated and reliable starter, designed for use

with standard medium voltage three-phase, squirrel cage induction

motors or synchronous motors. It provides the best method of reducing

current and torque during motor starting.The ISA-HD starts the motor

by supplying a slowly increasing voltage to the motor, providing soft

start and smooth acceleration, while drawing the minimum current

necessary to start the motor.The microprocessor based digital control

provides unique features like pump control, accurate motor protection

and optional analog output.The optional RS485 communication with

MODBUS, PROFIBUS and other (consult factory) protocols enables

full control (start, stop, dual adjust, command, etc.) and supervision.

Up to 32 starters or other MODBUS slaves can be connected via a

twisted shield pair to a host computer.

2.2 Motor current and starting conditions

Condition

Select the starter according to motor's Full Load Ampere (FLA) - as

indicated on its nameplate (even if the motor is not fully loaded) The

ISA-HD is designed to operate under the following conditions:

Max. ambient temp: 50°C

Max. starting current: 400 % motor's FLA

Max. starting time: 30 sec. (at 400 % FLA)

Max. starts per hour: 2 starts per hour at maximum conditions.

Page 11: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Starter Selection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111

2.3 Storage

The soft starter is designed for indoor use and must not be left out-

doors. Soft starter should be stored in a warm, dry room and protected

against dust and debris. If the soft starter is to be kept in store before

use make sure that the ambient conditions are acceptable:

Storing temperature: -20…..+70°C

Relative humidity: <95%, no condensation.

Attention

This statement only refers to standard cabinet!

For other than standard cabinet design refer to the supplied drawings

and/or consult the factory.

2.4 Temperature Range & Heat Dissipation

The ISA-HD is rated to operate within a temperature range of 0°C to

+ 50°C. Relative non-condensed humidity inside the enclosure must

not exceed 95%.

Attention

Operating the ISA-HD with a surrounding air temperature that is higher

than

50ºC will cause derating. Operating the ISA-HD with a surrounding air

temperature that is higher than 60ºC may cause damage to the ISA-

HD.

During soft start the maximum heat dissipation in Watts is as follows:

Page 12: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Starter Selection

12 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

2,300V – 24xFLC [W]

3,300V – 72xFLC [W]

4,160V – 72xFLC [W]

6,600V – 72xFLC [W]

10,000V – 120xFLC [W]

11,000V – 120xFLC [W] – for marine applications: 144xFLC [W]

13,800V – 144xFLC [W] – for marine applications: 168xFLC [W]

15,000V – 192xFLC [W]

2.5 PIV (Peak Inverse Voltage) ratings

Correlation between system voltage and PIV ratings PIV rating will be

not less than:

Table 1 PIV rating

system volt-age

PIV ratings

2300 V 6900 V

3300 V 9900 V

4160 V 12500 V

6900 V 19500 V

11000 V 33000 V

13800 V 39000 V

Page 13: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Starter Selection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 13 / 111

2.6 Mains voltage

Phase to phase

Thyristors PIV rating, internal circuitry and insulation defines the fol-

lowing voltage levels:

2300 V, 3300 V, 4160 V, 6000 V, 6600 V, 6900 V, 11000 V and 13800

V.

The starter is suitable for 50 / 60 Hz.

2.7 Control voltage

Available voltage levels

The control voltage operates the electronic circuitry. The following volt-

age levels are available:

220 - 240 V + 10% - 15 %, 50 / 60 Hz (standard)

110 - 120 V + 10% - 15 %, 50 / 60 Hz

110 VDC

125 VDC

220VDC

24VDC

Consult factory for different voltages.

2.8 Control inputs

Start, stop, etc.

Control input voltage can be the same as control supply above or

Page 14: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Starter Selection

14 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

230VAC

115VAC

24VDC

110VDC

125VDC

220VDC

24VDC

2.9 Options

For options (please refer to ordering information data)

Analog card - analog output

Tachometer feedback (on request only)

Relays card:

enables operation via communication.

to get an up-to-speed signal when starting synchronous

motors as soon as the by pass contactor is closed or In <

115% In

Multi start configuration (M67)

Lloyd’s approval for marine application (option M66)

Communication (Modbus or profibus)

Page 15: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Installation

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 15 / 111

3 Installation

3.1 Prior to installation

Check

Check that motor full load ampere (FLA) is lower than or equal to the

starter full load current (FLC) and that the main and control voltages

are as indicated on the front panel.

3.2 Mounting

Attention

The starter must be mounted vertically. Allow sufficient space for

suitable airflow above and below the ISA-HD. Verify that mini-

mum clearances specified in the applicable codes/standards are

applied. In addition, when glass epoxy of any-type or thickness

is utilized within the cabinet assembly, minimum clearances

specified in the applicable codes/standards are not lowered.

Cabinet internal temperature should not exceed 50°C.

The starter should not be mounted close to heat sources.

The starter should be protected from dust and corrosive atmos-

phere.

Temperature range and relative humidity

The starter is rated to operate within the temperature range of -10°C

(14 F) to + 50°C (122 F).Relative humidity inside the enclosure should

not exceed 95 % non-condensing

Caution

Line and load connections may not be interchanged.

Page 16: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Installation

16 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Short circuit protection

The starter must be protected against short circuit by MV fuses or Cir-

cuit Breaker in combination with a protection Relay. (For bigger cur-

rents >500A no MV Fuses are available)

Voltage transient protection

When high transients are expected, external protection should be used

(consult factory).

Danger

Power factor correction capacitors - if required - must be installed on

the line side of the ISA-HD.Do not connect three phase voltage without

starting the ISA-HD after less than 30 seconds!

3.3 Power section connections

Connection lines

Line to terminals L1, L2, and L3. Connection to mains voltage up to

15,000V. Thyristor’s PIV rating, internal circuitry and insulation defines

the following voltage levels:

2,300V +10%/ -15% 50/60Hz

4,160V +10% /-15% 50/60Hz

6,000V +10% /-15% 50/60Hz

6,600V +10% /-15% 50/60Hz

10,000V +10% / -15% 50/60Hz

11,000V +10% / -15% 50/60Hz

13,200V +10% / -15% 50/60Hz

13,800V +10% / -15% 50/60Hz

15,000V +10% / -15% 50/60Hz

Each ISA-HD is suitable for one of the above levels & for 50/60 Hz.

Page 17: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Installation

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 17 / 111

By-pass to terminals L1b, L2b, and L3b.

Preparation for bypass connection. Bypass preparation is standard in

all ISA-HD models up to 6.6kV. All ISA-HD models must be operated

with a Bypass Contactor. Bus bars and Bypass Contactor must be ar-

ranged to maintain current flow through the internal CTs after end of

the acceleration process. Otherwise, current protection of the soft

starter will not function.

Figure 2 Power section up to 6600V

This picture illustrates the Power Section of ISA-HD models up to

6.6kV.

ISA-HD models from 10kV and up have no preparation for bypass (by-

pass must be performed in the cabinet), CTs are mounted externally

to the Power Section and power supplies to the firing PCBs are

mounted externally to the Power Section.

Motor to U, V, and W.

Connection to motor

Note: Never connect power factor capacitors to soft starter output.

Power Factor capacitors, if required should be connected to the ISA-

HD line side (mains).

Page 18: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Installation

18 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Line contactor and by-pass contactors must be used.

Do not connect any devices between the line contactor and the

ISA-HD.

Power factor capacitors, if required, should be installed on the

ISA-HD line side (not on the ISA-HD load side).

Mains supply must be applied in the correct phase sequence.

Interlock the line contactor - starting relay with the “fault relay” of

the ISA-HD.

Ground connection:

For proper operation and for safety reasons the ISA-HD Power Section

must be properly grounded.

Warning

When installing into a switch gear!

Do not perform “Hi-Pot” test on the switchgear after the soft-starter

has been installed in it. It may damage the ISA-HD.

Page 19: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 19 / 111

4 Internal Settings

4.1 Internal settings - components and connections

Top view of control module

Figure 3 control board

1. Fiber optic PCB – behind Display (PC2055)

2. 15 pins connector Current and Voltage Measurement

3. Control transformer

4. Fiberoptic connectors

5. Optional PCB Terminals

6. Option PCB

Page 20: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

7. Modbus or Profibus PCB

8. DIP - switch

9. Software Version (Label)

10. Main PCB (2050)

11. Power supply PCB (2014 or 2015)

12. Terminals1-3

13. Terminals 4-9

14. Terminals 10-21

15. Optional PCB Terminals

4.2 Control Module

Control Module is the “brain” of the soft starter. It consists of the main

CPU PCB, fireboard PCB, power supply, optional PCBs (when or-

dered) and input/output interface terminals.

The Control Module for ISA-HD is identical for all ratings and suitable

for mounting in the L.V. compartment of the cabinet which should be

fully segregated from the M.V. compartment. Interposing relays should

be connected to all ISA-HD auxiliary contacts, three relays must be

incorporated: Immediate, End of Acceleration and Fault.

4.3 Memory system operation

Operating sequence

1. When control supply is switched on, the RAM is automatically

loaded from the Micro processor and parameters are displayed

on the LCD.

2. Parameters can now be modified via the keypad (if starter is in

one of the operating modes and software lock is open - DIP

switch 8 open).

Page 21: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 21 / 111

3. Start parameters can be modified during starting process and will

affect the operation immediately. Example: if current limit is set

too low and motor does not accelerate to full speed, increasing

the current limit setting will immediately affect the start process.

This enables selection of the optimal starting characteristics.

4. After completion of the adjustments, parameters should be

stored in the Micro processor. Storing of new parameters is pos-

sible at the end of each mode page by pressing <STORE> key

after “STORE ENABLE” is displayed on the LCD display.

4.4 First control voltage connection

Few seconds after first connection of control voltage the Fault LED will

flash and the LCD will display: ALARM Set Time & Date

It is advised to set the time and date as described on Parameter sec-

tion. If time and date are not set properly no time stamp to the faults

shown in the STATISTICAL DATA.

Note:

If the Reset button is pressed this message will not appear any more!!

4.5 Test and Maintenance modes

Run Self Test

Press the Mode and ▼ keys simultaneously.

The Test LED will light and the LCD will display:

TEST/MAINTENANCE

***OPTIONS***

Page 22: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

22 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Press the Select key. The LCD will display:

RUN SELF TEST ?

PUSH UP ARROW

Press the ▲ key. The Test LED will turn off and the LCD will display:

SELF TEST PASSED

And after a few seconds the LCD will display:

I1 I2 I3

0 0 0 %

View Software Version

Press the Mode and ▼ keys simultaneously. The Test LED will light

and the LCD will display:

TEST/MAINTENANCE

***OPTIONS***

Press the Select key twice. The LCD will display:

BTL-R-16/09/2008

Page 23: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 23 / 111

MVSTMB.GN-121008

Press the Mode and ▼ keys simultaneously to exit the TEST/MAINTE-

NANCE mode.

I1 I2 I3

0 0 0 %

Obtain Default Parameters

Press the Mode and ▼ keys simultaneously. The Test LED will light

and the LCD will display:

TEST/MAINTENANCE

***OPTIONS***

Press the Select key three times. The LCD will display:

STORE ENABLE

DEFAULT PARAMET.

Press the Store + Mode keys simultaneously. The Test LED will turn

off and the LCD will display:

DATA SAVED OK

And after a few seconds the LCD will display:

Page 24: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

24 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

I1 I2 I3

0 0 0 %^

Caution: Obtaining DEFAULT PARAMETERS erases all previously

modified settings and requires the operator to reprogram all parame-

ters that differ from the factory default.

Note: It is especially important to reprogram the RATED LINE VOLT-

AGE and STARTER FLC (as shown on the label of the ISA-HD) and

all other parameters in MAIN & PROTECT mod page.

Reset Statistical Data

Press the Mode and ▼ keys simultaneously. The Test LED will light

and the LCD will display:

TEST/MAINTENANCE

***OPTIONS***

Press the Select key four times. The LCD will display:

RESET STATISTICS

Press the Reset + Store keys simultaneously. The Test LED will turn

off and the LCD will display:

DATA SAVED OK

Page 25: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 25 / 111

And after a few seconds the LCD will display:

STATISTICAL DATA

- **** -

Press the Mode and go back to:

I1 I2 I3

0 0 0 %

Setting Time and Date

Press the Mode and ▼ keys simultaneously. The Test LED will light

and the LCD will display:

TEST/MAINTENANCE

***OPTIONS***.

Press the Select key seven times. The LCD will display:

hh.mm mm.dd.yy

01/19/08

The hour value blinks modify the hour value with ▼ or ▲ keys. Press

Store key. The LCD will display (now the minutes value blinks):

hh.mm mm.dd.yy

Page 26: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

26 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

01/29/08

Repeat the same procedure as for the hour settings to the minutes,

day, month and year settings. After Store key is pressed last time the

LCD will display:

TEST/MAINTENANCE

***OPTIONS***

Press the Mode and ▼ keys simultaneously to exit the TEST/MAINTE-

NANCE mode. The Test LED will turn off and the LCD will display:

I1 I2 I3

0 0 0 %

The Test LED will turn off and the LCD will display:

Three modes of test are available:

1. Test condition where the soft starter is tested for correct logical

operation without medium voltage connected to it.

2. Firing test requires only control voltage without main voltage.

Test condition with test harness and four pairs of dip - switches allow-

ing a low voltage motor test.

Page 27: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 27 / 111

4.6 Dip switch settings

PCB2050

The DIP switch module contains eight separate switches located un-

der the front cover of the control module and under the display unit.

When necessary, carefully open the front panel and set the switches

as required.

Note

All switches are factory pre-set in OFF position

Figure 4 DIP-switches

Table 2 Dip switch settings (PC2050 type)

No. switch function switch Off switch On

1 display format minimized maximized

2 tacho feedback disabled enabled

3 main / generator mains generator

4-6 LCD-language selection refer to table

7 special settings - keep in Off position

disabled enabled

8 software lock open locked

Page 28: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

28 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Switch # 1 - Display modes

For convenient operation there are two display modes:

Maximized - displays all possible parameters.

Minimized - displays pre-selected parameters only.

Setting Dip switch # 1 to Off will minimize the LCD displays.

Table 3 Display modes

maximized mode

switch 1 - On

minimized mode

switch 1 - Off

display only

main parameters

start parameters

stop parameters

dual adjustment

fault parameters

I/O programming

communication parameters

statistical data

display only

main parameters

start parameters

stop parameters

statistical data

Switch # 2 - tacho feedback (on request only)

Set DIP switch. # 2 to ON, when using incremental shaft encoder or

tacho feedback.

Note

To operate tacho feedback - consult factory for specific settings for

each application.

Page 29: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 29 / 111

Switch # 3 - mains / generator control

When starting from a diesel generator supply, the starting process can

sometimes be terminated due to instability of the supply system. To

operate generator mode set Dip switch # 3 to On and special starting

characteristics, suitable for diesel generator supply - with unstable

voltage and frequency becomes operative.

Closure of dual adjustment contact (terminal 8) initiates the special

starting characteristics.

When operating from network voltage and alternatively from diesel

generator, set normal starting characteristics for mains and suitable

parameters for the diesel generator (for example, faster acceleration,

lower current limiting, etc.) on dual adjustment setting.

Warning

When operating in generator mode or with curve “0” motor must be

loaded, otherwise vibration may occur during starting and stopping.

Switches # 4, 5, 6 – language selection

Table 4 DIP switch settings switch 4 and 6

language switch 4 switch 5 switch 6 switch position

English Off Off Off

French Off Off On

German off On Off

Spanish Off On On

Turkish on off off

Page 30: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

30 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Switch # 7 - special settings - consult factory

Warning

EXTENDED SETTINGS are for use in very special applications only!

Do not set to switch #7 to on unless ISA-HD is significantly larger than

the

motor! When using extended settings for the ISA-HD you must be

extremely careful to avoid damaging the motor or ISA-HD.

Switch # 8 - software lock

The software lock prevents undesired parameter modification.

To verify, that parameters are locked, press <Store> and <%> or <&>

keys and the LCD displays, “Unauthorized Access”.

4.7 Analog I/O (Option 5) (Terminals Gnd, Out (-),

Out (+))

Figure 5 analog card

Page 31: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 31 / 111

Ground Terminal (terminal Gnd)

Leave this terminal not connected. Ground the shield of the analog

output signal at the recipient side.

Analog Output (Terminals Out (+), Out (-))

Dip switches allow selection between: 0-10VDC, 0-20mA, 4-20mA

The analog value is related to I, 0….200% of FLA or 0….200% of

RATED MOTOR PWR.

Table 5 DIP switch settings analog card

Switch 4-20 mA* 0-20 mA 0-10VDC

S1- Switch # 1 ON ON OFF

S1- Switch # 2 On on off

S1- Switch # 3 Off off on

S1- Switch # 4 off off on

S2- Switch # 1 on off off

S2 - Switch # 2 not used not used not used

* Factory default setting

Page 32: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

32 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

4.8 Overload Protection Class IEC

The ISA-HD allows motor protection according to IEC class 5, 10, 15,

20, 25 or 30 OR according to NEMA class 5, 10, 15, 20, 25 or 30.

Page 33: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 33 / 111

4.9 Overload Protection Class NEMA

The ISA-HD allows motor protection according to IEC class 5, 10, 15,

20, 25 or 30 OR according to NEMA class 5, 10, 15, 20, 25 or 30.

Page 34: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

34 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

4.10 Terminal 7 and Terminal 8 Programming

Table 6 Terminal 7 programming

Input Terminal 7

Programmed Func-tion

Description

RESET (default setting)

Input terminal 7 is used as RESET to reset all ISA-HD faults. The RESET command will take effect only if the start command is removed (ex-cept for UNDER CURRENT fault)

TEST While input terminal 7 is on firing test can be done. Refer to service and commissioning in-struction for firing test procedure.

MULTI SOFT STOP

(Optional – only if op-tional

software is installed)

While input terminal 7 is on, the soft starter will go to Run even if current is not running through the soft starter. This will enable Multi Soft Stop operation with the ISA-HD.

Table 7 Terminal 8 programming

Input Terminal 8

Programmed Function Description

DUAL ADJUSTMENT

(default setting)

Input terminal 8 is used to start and stop from the DUAL ADJUSTMENT

PARAMETERS page. Refer to Parameter sec-tion for programming. Refer to section 7 for wir-ing.

RESET

Input terminal 8 is used as RESET to reset all ISA-HD faults. The RESET command will take effect only if the start command is removed (ex-cept for UNDER CURRENT fault)

Page 35: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Internal Settings

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 35 / 111

4.11 Special Control for Synchronous Motors

Excitation

The parameters TURN BYPAS ON AT and MIN TIME TO BYPAS are

used for special cases of synchronous motors excitation system.

These parameters are active only under the following conditions:

• Optional Relay PCB is installed

• When setting the RUN CONTACT DLY parameter, after reaching

120 seconds (maximum value) and operator keeps pressing for

additional 10 seconds the ▲ key.

The parameter TURN BYPASS ON AT determines motor current be-

low which the soft starter goes into Run condition and closes the End

Of Acceleration relay.

The parameter MIN TIME TO BYPS assures that Run condition cannot

be reached before the set time after the beginning of the starting pro-

cess.

This special feature is for synchronous motor starting applications

where the motor current at asynchronous speed may be at higher level

than regular asynchronous motor starting conditions. In this case the

level of current at which the Run condition is

Page 36: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

36 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

5 Control Terminals

Description

Figure 6 operator panel, display, I/O terminals

Terminal 1 and 3

Control voltage

Terminal 1 - Control voltage - phase (positive – for DC control).

Terminal 2 - Control voltage - neutral (return – for DC control).

The control voltage operates the electronic circuitry and the auxiliary

relay that controls the firing relay. The available control voltages are:

Page 37: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 37 / 111

115V for 115V +10%/ -15% 50/60Hz

230V for 230V +10%/ -15% 50/60Hz

24VDC for 24VDC +10%/ -15% DC

110VDC for 110V +10%/ -15% DC

125VDC for 125V +10%/ -15% DC

220VDC for 220V +10%/ -15% DC

Note

It is recommended that terminals 1-3 are connected to the control sup-

ply continuously.

Terminal 2

Firing control

An internal relay connects the control voltage from terminal 1 to termi-

nal 2 when firing is required during Soft Start and Soft Stop. Typically

external relay controlled by this terminal connect the firing transformer

which feed the firing system.

Input Terminals

Note

As standard the ISA-HD is supplied with the same voltage for control

supply and control inputs.

Terminal 4 Stop

Input – STOP command.

• Input from a N.C. contact

• To stop the motor, disconnect Control Input voltage from terminal

4 for at least 250mSec. (no SOFT STOP).

Page 38: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

38 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Control Input voltage (STOP, SOFT STOP, START, terminal inputs 7

and 8) can be the same as Control Supply (terminals 1, 3) or voltage

from a different source. The Control Inputs are opto-coupled and iso-

lated from the microprocessor circuitry.

Terminal 5 Soft stop

Input – SOFT STOP command.

• Input from a N.C. contact

• To SOFT STOP the motor disconnect Control Input voltage from

terminal 5 for at least 250mS

Note:

If SOFT STOP is not required, connect a jumper between terminals 4

and 5.

Note: Control Input voltages available:

115V for 115V +10%/ -15% 50/60Hz

230V for 230V +10%/ -15% 50/60Hz

110VDC for 110V +10%/ -15% DC

125VDC for 125V +10%/ -15% DC

220VDC for 220 VDC +10%/ -15% DC

Terminal 6 Start

Input from a N.O contact. To start the motor, connect control voltage

to terminal 6 for at least 500 msec.

Note

1. Motor will start only if stop (4) and soft stop (5) terminals are con-

nected to control voltage.

2. Reset after a fault is not possible as long as start command is

present.

3. ISA-HD ignores start within 3 sec after stop. Wait at least 3 sec

before

restarting.

Remark

Page 39: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 39 / 111

Terminal 7 Test / Reset

Input from a N.O contact. Selection between above functions is made

via the keypad or through the communication.

Test function

Test is designed to enable thyristors firing test without mains. When

connected through a N.O. contact, closing the contact operates Test.

Reset function

When reset function is selected, connect terminal 7 momentarily to

control voltage (use a N.O momentary contact) to reset the starter.

Motor Multi motor Soft Stop

connect terminal 7 to control input voltage (use a N.O. contact) to op-

erate the soft starter in a Multi Soft Stop procedure.

Terminal 8 Dual Adjust / Reset

Input from a N.O contact. Selection between above functions is made

via the keypad or through the communication (see I/O programming).

Dual adjustment function active

Dual adjustment function is selected by connects terminal 8 to control

voltage to operate starter with the dual adjustment characteristic.

Switching between primary and dual adjustment settings can be done

before and during starting. If a push-button arrangement is used, keep

control voltage connected at least until RUN LED is ON.

Note

When starting from a “small” diesel generator or weak power supply

set dip switch # 3 to on and connect terminal 8 to control voltage to

operate starter with generator parameter settings.

Page 40: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

40 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Reset function

When “RESET” function is selected, connect terminal 8 momentarily

to control voltage (use a N.O momentary contact) to reset the starter.

Terminal 9 Common A

Common for terminals 4, 5, 6, 7, 8

Note

When control supply voltage and control input voltages are from the

same source, connect a jumper between terminals 3 and 9.

Figure 7 processor board with operator panel / display

Terminals 10 - 11 - 12 Immediate / shear-pin relay internal (ext.: 33 - 34 - 35)

Terminals: 10 - N.O. 11 - N.C. 12 - common.

Floating contact 8 A, 250 VAC max.

Selection between functions is made from the keypad or through the

communication, (see I/O programming), programmable functions:

Page 41: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 41 / 111

1. Immediate (after start signal)

2. O/C (over current) shear-pin detection.

3. When immediate is selected, the contact changes its position

upon start signal. The contact returns to its original position upon

stop signal in case of a fault or control supply outage.

4. When soft stop is operated, the contact returns to the original

position at the end of the soft stop process.

The contact incorporates ON and OFF delays within 0 - 60 sec each.

The immediate contact can be used for:

• Interlocking with other systems.

• Signalling.

• Delay for opening an upstream contactor at the end of soft stop

to allow current decrease to zero before opening the contactor.

• Switch to / from dual adjustment settings with a time delay from

start signal (refer to special starting).

When O/C shear-pin is selected, the contact changes position upon detec-

tion of jam condition (starter trip can be delayed within 0 - 5 sec.)

The O/C shear-pin contact can be used for:

• Interlocking with other systems.

• Signalling

• Delay for opening an upstream contactor at the end of soft stop

to allow current decrease to zero before opening the contactor.

• Delay for operating a reversing contactor when jam is detected

to allow clearing of a jam condition.

Terminals 13-14-15 Fault Contact

Terminals: 13 - N.O. 14 - N.C. 15 - common

Page 42: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

42 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Floating contact 8 A, 250 VAC, 2000 VA max. changes its position on

fault. The contact is programmable to function as trip or trip fail safe

relay.

Trip function without wire breakage sensing

When trip function is selected - the relay is energized upon fault. The

contact returns to its original position after fault has been removed and

starter was reset or upon disconnection of control supply.

Trip function with wire breakage sensing

When trip-fail safe function is selected - the relay is energized imme-

diately when control supply is connected and de-energizes upon fault

or control supply disconnection.

Terminals 16 - 17 – 18 End of acceleration contact

Terminals: 16 - N.O. 17 - N.C. 18 - common

Floating contact 8 A, 250 VAC, 2000 VA max. changes its position at

the end of acceleration with an adjustable time delay (contact delay)

of 0 - 120 sec.

The contact returns to its original position on soft stop or stop signals

on fault condition or voltage outage.

The end of acceleration contact must be used to close a by-pass con-

tactor through a pilot (interposing) relay and can be used to:

• Activate a valve after compressor has reached full speed.

• Signal, allowing for the loading of a conveyor after motor has

reached full speed, etc.

Terminal 19 External Fault 1

Input from a N.O contact connected between terminals 19 and 21. The

starter will trip 2 seconds after contact closes.

Page 43: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control Terminals

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 43 / 111

Terminal 20 External Fault 2

Input from a N.O contact connected between terminals 20 and 21. The

starter will trip 2 seconds after contact closes.

Terminal 21 Common B

Common for terminals 19, 20

Note

1. When control supply voltage and control input voltage are from

the same source, connect a jumper between terminals 3, 9, and

21.

2. If external inputs are not used, leave terminals 19, 20, and 21

open.

Fiberoptic

Output #1

Phase L1 firing control via fiber optic wire.

Output #3

Phase L2 firing control via fiber optic wire.

Output #5

Phase L3 firing control via fiber optic wire.

Input #7

Feedback signal from phase L1.

Input #8

Feedback signal from phase L2.

Input #9

Feedback signal from phase L3..

Page 44: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Option Boards

44 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

6 Option Boards

6.1 Possible options and settings

RS-485 communication Terminal 23 - 24

Terminal 22

No connection (optional)

Terminal 23

RS-485 communication (-) (optional)

Terminal 24

RS-485 communication (+) (optional)

• Standard RS485, half duplex with Modbus protocol, baud rate

1200, 2400, 4800, 9600 BPS.

• Twisted shielded pair should be used. Connect shield to ground

on the PLC/Computer side.

• Terminals 4 & 5 must be wired to Control Supply for operation in

communication mode (refer to section for wiring diagram).

• Up 32 units can be connected for Modbus RS485 communica-

tion. For reliable communication, units should be installed in the

vicinity of 200m maximum, from the first to the last unit.

• Refer to section for programming.

• Refer to the Modbus communication manual

PROFIBUS D-9 CONNECTOR

9 PIN D-sub connector is available for PROFIBUS.

Profibus DPV0 and DPV1, up to 12 MBPS.

Remarks

Terminal

22 - 24

Page 45: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Option Boards

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 45 / 111

• D type 9 pin connector is applied.

• Control, monitoring and setting parameters can be achieved via

the Profibus connection.

• Setting is possible only when DPV1 is implemented.

Terminal 25

Programmable Insulation Alarm Output relay (Common) (optional)

Terminal 26

Programmable Insulation Alarm Output relay (N.O.) (optional)

Terminal 27

Programmable Insulation Alarm Output relay (N.C.) (optional)

Voltage free 8A, 250VAC, 2000VA max. is energized when the motor

insulation level decreases below the Insulation Alarm level. The relay

is de-energized and the alarm will disappear if one of the following

occurs:

• The insulation level returns to normal for more

• than 60 seconds

• ISA-HD resets

• Control Supply disconnection Refer to section for more details

and programming.

Notes:

• Insulation test can be performed only when main voltage is not

connected to the ISA-HD, (upstream isolation device must be

opened.)

• For correct operation of Insulation test, it is important that the

ISA-HD is properly grounded and that the Control Module is

properly fastened to the Power Section.

• Insulation test option and analog output option cannot be applied

together.

Remarks

Terminal

25 - 27

Page 46: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Option Boards

46 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

ANALOG I/O TERMINALS 28 - 32

Terminals 28 - 29 leave open

Terminal 30 connect to ground (shield)

Terminal 31 - analog output (-)

Terminal 32 - analog output (+)

The analog card output incorporates two functions (voltage and cur-

rent outputs). Dip switches allow selection between:0 - 10 VDC, 0 - 20

mA and 4 - 20 mA

The analog value is related to the motor current and can be pro-

grammed to normal or inverted output. (default = normal)

Maximum value (20 mA or 10 VDC) is related to 2 x In.

Dip. Sch.S1

Aus

Dip. Sch.S2

Aus

32 31 30 29 28

Au

s

(+)

Au

s (-

) Gn

d

T1

T 2

Figure 8 DIP switches for analog card

Table 8 DIP switch settings analog card

Dip switch No. 4 - 20 mA* 0 - 20 mA 0 - 10 VDC

Dip switch S1 # 1 On On Off

Dip switch S1 # 2 On On Off

Dip switch S1 # 3 Off Off On

Dip switch S1 # 4 Off Off On

Dip switch S2 # 1 On Off Off

Dip switch S2 # 2 unused unused unused

Page 47: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Option Boards

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 47 / 111

RELAYS BOARD

Terminal 31

Start command output relay (N.O.) (optional)

Terminal 32

Start command output relay (N.O.) (optional)

Terminal 33

Up to Speed Output relay (N.O.) (optional)

Terminal 34

Up to Speed Output relay (N.C.) (optional)

Terminal 35

Up to Speed Output relay (Common) (optional)

Voltage free 8A, 250VAC, 2000VA max. closes upon start command

via communication. (Modbus or Profibus) The contact opens on SOFT

STOP or STOP commands via communication (Modbus or Profi-

bus).This contact is used to control the cabinet via the communication

(i.e. closing the Line Contactor). Voltage free 8A, 250VAC, 2000VA

max. changes its position at the end of acceleration, after current is

reduced below a programmable current and a time delay. The Up to

Speed relay remains latched until the Up to Speed relay is used to

control the excitation system of a synchronous motor. motor stops.

TACHO BOARD (ON REQUEST ONLY)

This option is suitable to use with incremental shaft encoder (on re-

quest only).

Remarks

Terminals

31-35

Page 48: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Control wiring

48 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

7 Control wiring

Description

Figure 9 Controlboard wiring diagram

Page 49: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 49 / 111

8 Start and Stop Parameters

8.1 Description of start curves

Start curves

Induction motors produce peak torque of up to 3 times the rated torque

towards the end of starting process. In some pump applications, this

peak may cause high pressure in the pipes.

The ISA-HD incorporates 5 different starting curves:

Start curve 0 - basic curve.

Start curve 1 - standard curve (default). The most stable and suitable

curve for the motor that prevents extended starting and motor over-

heating.

Pump control

Start curves 2, 3, 4 -

Pump Control - Induction motors produce peak torque of up to 3 times

the rated torque towards the end of starting process. In some pump

applications, this peak may cause pressure surge in the pipes. During

acceleration, before reaching peak torque, the Pump Control Program

automatically controls the voltage ramp-up, thus, reducing peak

torque.

Choice of three pump control acceleration curves

Speed

Time

Torque Voltage DOL

1

2

3 4

Figure 10 choice of three pump control curves (2,3,4)

Page 50: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

50 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Start Curve 5 - Torque curve. The most suitable curve for the motor

that provides linear acceleration and deceleration curves according to

the torque.

Figure 11 start curve 5, torque curve

Note

Consult factory for additional information

Note

Always start with start curve 1. If towards the end of acceleration, the

peak torque is too high (pressure is too high), proceed to curve 2 then

3 or 4 if necessary.

Pulse start

Sets PULSE LEVEL and PULSE START TIME. Intended to break free

high friction loads requiring high starting torque for a short time or for

pedestal start by holding the current at a predefined level for prede-

fined time period. The pulse is defined by its current level and time

length (width). After this pulse the voltage is ramped down to INITIAL

VOLTAGE setting before ramping up again to full voltage according to

the START PARAMETERS settings.

Page 51: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 51 / 111

For PULSE TIME<1SEC. PULSE LEVEL can be set to 70-700% of

FLA; For PULSE TIME≥1SEC. PULSE LEVEL can be set to 70-400%

of FLA; In EXTENDED SETTING. PULSE LEVEL can be set to 70-

700% with the limitation of: 440 x (FLC/FLA).

+10Vdc 0 - 2 Sec.

Un

80%

Figure 12 pulse start

Notes:

Note

• PULSE START is not effective in SOFT START CURVE 0.

For better control of the current withdrawn from the network (mainly

from generators), the following settings applies (applies from software

versions newer than MVSTMB.GN-010509):

Initial voltage

Determines the motor initial starting torque (the torque is directly pro-

portional to the square of the voltage).Range: 10 - 50 % UN (consult

factory for extended range) This adjustment also determines the in-

rush current and the resulting mechanical shock. A setting, which is

too high may cause high initial mechanical shock and high inrush cur-

rent (even if current limit is set low as the initial voltage setting over-

rides current limit setting).

Page 52: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

52 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

A setting too low may result in prolonged time until motor begins to

turn. In general, this setting should ensure that the motor begins turn-

ing immediately after start signal.

Figure 13 initial voltage

Note:

When INITIAL VOLTAGE is set its maximum value, this displays

changes to INITIAL CURRENT. When INITIAL CURRENT is set the

ISA-HD causes current ramp instead of voltage ramp.

Current limit

Determines the motor highest current during starting.

Range 100 - 400 % of FLA setting (consult factory for extended range).

A too high setting will cause higher current drawn from the mains and

faster acceleration. A setting too low may prevent motor from complet-

ing acceleration process and reaching full speed.

In general, this setting should be set to a value high enough to prevent

stalling.

Note

Current limit is not operating during RUN and SOFT STOP.

U%

10%

50%

100%

Page 53: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 53 / 111

Figure 14 current limit

Acceleration time

Determines the motor voltage ramp-up time from initial to full voltage.

Range 1 - 30 sec. (consult factory for extended range). It is recom-

mended to set acceleration time to the minimum acceptable value (ap-

prox. 5 sec).

Figure 15 acceleration time

Note

1. Since current limit overrides acceleration time when current limit is

set low, starting time will be longer than the preset acceleration

time.

2. When motor reaches full speed before voltage has reached nomi-

nal voltage, acceleration time setting is overridden and causes the

voltage to ramp-up quickly to nominal.

3. Starting curves 1, 2, 3 prevents quick ramp up

I%

400%

100%

U%

1

100%

30 sec

Page 54: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

54 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Maximum start time

The maximum allowable starts time from start signal to the end of ac-

celeration. If voltage does not reach full voltage during this time (for

example, because of low current limit setting), the starter will trip the

motor. LCD displays “Long Start Time” message.

Range: 1 - 30 sec (consult factory for extended range).

Number of starts

Sets NUMBER OF STARTS permitted during STARTS PERIOD.

Limits the number of starts during the period of time defined by

STARTS PERIOD.

If you try to start even one more time within that period the START

INHIBIT period will take effect.

Start Period

Sets STARTS PERIOD during which NUMBER OF STARTS is being

counted.

Start Inhibit

Sets START INHIBIT time which starting is disabled after TOO

MANY STARTS trip. During the START INHIBIT period the WAIT BE-

FORE RST XX MIN message will be displayed.

Contact delay and Turn Bypass on

0-120sec. After reaching 120 seconds, keep pressing for 10 seconds

the ▲ key and only if optional Relay PCB is installed the display

changes to: TURN BYPASS ON AT 120-300%.

Sets time delay for End of Acceleration relay to close after completion

of starting process. End of Acceleration relay can signal that motor is

at its RUN position which can be used for motor loading.

Page 55: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 55 / 111

8.2 Description of stop curves

Pump control - stop curve

Intended to prevent water hammer during stopping. In pump applica-

tions, load torque decreases in square relation to the speed and re-

ducing the voltage will reduce torque so motor will smoothly decelerate

to stop.SOFT STOP initiation opens the End of Acceleration contact

and opens the Bypass Contactor. Load will be transferred to the ISA-

HD thyristors and voltage begins to ramp down. The ISA-HD incorpo-

rates 5 stopping curves that enable you to select the suitable torque

curve:

The following stop curves can be selected:

Stop curve 0 - basic curve.

Stop curve 1 - Standard default curve - voltage is linearly reduced

from nominal to zero. The most stable and suitable curve for prevent-

ing prolonged stopping and motor overheating.

Stop curves 2, 3, 4 - In some pump applications, when pumping to

higher elevation a considerable part of the torque is constant and does

not decrease with speed. It may happen that during the deceleration

process when voltage decreases the motor torque abruptly falls below

load torque (instead of smoothly decreasing speed to zero), thus clos-

ing the valve and causing water hammer. Curves 2, 3 and 4 eliminate

the water hammer phenomenon. In pump application the load torque

decreases in square relation to the speed, thus correcting control of

voltage to reduce torque adequately and to smooth deceleration to a

stop.

Figure 16 pump control stop curves

Voltage Deceleration

1!!

0

2!!

3!!

Page 56: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

56 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Note

It is recommended that SOFT STOP CURVE 1 be used for all standard

applications (not pumps).

To reduce water hammer, select SOFT STOP CURVE 2, then 3, then

4 in that order. Curves 2, 3, 4 designed to prevent stall condition..

Stop curve 5 (Torque curve) - Provides linear deceleration of the

torque. In certain loads, linear torque deceleration can result in close

to linear speed deceleration, thus eliminating stall conditions.

Figure 17 torque control

Tacho feedback, incremental shaft encoder (on request only)

Provides linear acceleration and deceleration curves according to

speed feedback. 12 tacho gain levels can be selected for closed loop

control starting and stopping

Figure 18 tacho feedback

Motor Voltagae

+10VdcSpeed RPM

Un

Page 57: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 57 / 111

Note

Consult factory for additional information.

Deceleration time - soft stop

Used for controlled deceleration of high friction loads. Determines mo-

tor voltage ramp down time.Range: 1 - 30 sec. (consult factory for ex-

tended range).

Figure 19 deceleration time

Note

Soft stop initiation opens the END OF ACCELERATION contact and

opens the by-pass contactor. Load will be transferred to the ISA-HD

and voltage begins to ramp down.

Final Torque

Determines torque towards the end of soft stop. If current is still flowing

after speed is softly reduced to zero, increase the final torque setting

U%

2

100%

30 sec

Figure 20 final torque

U%

2

100%

30 sec

Page 58: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Start and Stop Parameters

58 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Dual Adjustment

A second set of parameters used for varying loads, two speed motors,

etc. Connecting control supply to terminal 8 transfers to dual adjust-

ment settings.

Initial voltage 10 - 50 % of UN.

Current limit 100 - 400 % of motor's FLA.

Acceleration time 1 - 30 sec.

Decceleration time 1 - 30 sec.

Motor FLA (full load ampere)

Figure 21 dual adjustment

Note

Consult factory for extended range.

U%

100%

sec2- -302- -10

40%

100%

20%

Page 59: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 59 / 111

9 Motor and Starter Protection

Too Many Starts

Please see chapter 8

LONG START TIME - (stall protection)

Trips the starter if the motor does not reach full speed during “MAXI-

MUM START TIME”.

Range: 1 - 30 sec. (consult factory for extended range).

Over Current Shear-pin trip

Operational when starter is energized and has two functions:

Trips the starter when current exceeds 850 % of starter's FLC

setting in 1 cycle or less.

850 % FLA with delay during start (850 % overrides O\L settings).

During run (after RUN LED is on) it trips the starter if current ex-

ceeds set level and time delay.

Range: 100 - 850 % of motor FLA setting

Delay: 0 - 5 sec. (0 = up to 200 msec)

Note

The O/C shear-pin trip is not intended to replace the fast acting fused.

Overload (O/L)

Sets OVERLOAD CLASS characteristics Sets OVERLOAD PRO-

TECT functionality. The ISA-HD allows motor protection according to

IEC class 5, 10, 15, 20, 25 or 30 or according to NEMA class 5, 10,

15, 20, 25 or 30. Tripping curves are shown on section 4.8 and 4.9.

The OVERLOAD protection incorporates a THERMAL CAPACITY

register that calculates heating minus dissipation of the motor. The

Page 60: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

60 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

ISA-HD trips when the register fills up. (THERMAL CAPACITY=100%)

The time constant, in seconds, for cool down after overload trip is:

Class 5 10 15 20 25 30

IEC 160 320 480 640 510 960

NEMA 140 280 420 560 700 840

The overload protection can be set to protect the motor as set in the

OVERLOAD PROTECT parameter:

ENABLE – motor is protected at all time.

ENABLE WHILE RUN – motor is protected only when in Run.

DISABLE – motor is not overload protected by the soft starter.

Note:

In order to restart after OVERLOAD trip, the thermal register should

be 50% or less.

Under Current

Operational when motor is running. Trips the starter when motor cur-

rent drops below under current trip (UCT) set point for a period of time

longer than under current delay (UCD).

Under current trip range: 0 = Off, 20 - 90 % of FLA

Under current delay range: 1 - 40 sec.

Auto Reset

A special feature enables auto reset after an adjustable time delay.

Range: Off, 10 - 120 min.

Under Voltage / No Voltage

Operational after start signal. It trips the starter when main voltage

drops below the under voltage trip set point for a period of time longer

Page 61: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 61 / 111

than under voltage delay. Auto reset can be activated via fault param-

eters. Auto reset is activated 60 sec after trip occurred.

Under voltage trip range: 70 - 90 % UN (phase to phase)

Under voltage delay range: 1 - 10 sec.

Note

1. When voltage drops to zero (voltage outage) the starter will trip im-

mediately, overriding the delay.

2. Auto reset cannot be activated if start signal is still connected.

Over Voltage

Operational after start signal. It trips the starter when main voltage ex-

ceeds the over voltage trip set point for an adjustable period of time

longer than over voltage delay.

Range: 110 - 125% of UN (phase to phase)

Over voltage delay range: 1 - 10 sec.

Phase loss (with programmable auto reset)

Operational when starter is energized and protects motor from loss of

phase.

It trips the starter when one or two phases are missing. Auto reset can

be activated via fault parameters. Auto reset is activated 60 sec after

trip occurred.

Note

3. Phase loss might not be detected for lightly loaded motors.

4. Auto reset cannot be activated if start signal is still connected.

Page 62: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

62 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Phase Sequence

It trips the starter when starter is energized and phase sequence is

wrong.

Heat-sink Over Temperature

Thermal sensors are mounted on the heat-sinks and trip the starter

when temperature exceeds 85°C.

External fault 1 and 2

Operational when starter is energized. It trips the starter when an ex-

ternal contact closes for more than 2 sec.

Unbalance Current Trip

Operational after start signal. It trips the starter when current unbal-

ance increases above the preset “UNBALANCE TRIP” for more than

the “UNBALANCE DLY” set-point.

Range: 10 - 100 %. Delay: 1 - 60 sec.

Ground Fault Trip

Operational after start signal. It trips the starter when ground current

increases above the preset “GND FAULT TRIP” for more than “GND

FAULT DLY” set point.

Range: 10 - 100 %. Delay: 1 - 60 sec.

Set to curve 0

Trip occurs if the Soft Starter starts with a non-adequate starting

curve to the network.

Motor insulation

(Optional) Trips the ISA-HD when the motor insulation level decreases

below the trip level set..

Power ON and No start

Page 63: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 63 / 111

Operational upon main voltage connection. It trips the motor when

main voltage is connected to the ISA-HD for more than 30 sec. without

a start signal.

Modbus Time out

If no valid Modbus communication during MODBUS TIME OUT, the

ISA-HD will trip. Trip occurs only if the following conditions exist:

• SER. LINK CONTROL is set to ENABLE

• SERIAL LINK NO. is not set to OFF

By-pass Open

If the by-pass is located in a separate cabinet and after by-pass is

closed, current measurement reads “0” the soft starter trips and dis-

plays “BP TRIP”. It is possible to disable this protection by setting BP

open trip to disable (on fault setting page).

Note

Most of the protections after BYPASS IS CLOSED can be disable by

respective settings on the fault page

Non Adjustable Protection Functions

UNDER / OVER FREQEUNCY

Trips the ISA-HD if frequency is not in the range of 44-65Hz

Check that frequency variations are between 44-65Hz.

PHASELOSS

Trips the starter if 1 or 2 phases are missing.

Check lines voltages and correct connection.

Page 64: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

64 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

WRONG PARAMETER

After power up parameters not transferred from RAM to EEPROM or

vice versa. Press Reset then load DEFAULT PARAMETERS. Refer to

section 10 for more details on loading default parameters. Note that

obtaining DEFAULT PARAMETERS erases all previously modified

settings and requires the operator to reprogram all parameters that

differ from the factory default.

Note:

It is especially important to reprogram the RATED LINE VOLTAGE

and STARTER FLC (as shown on the label of the ISA-HD) and all

other parameters in the MAIN & PROTECT mod page.

Wrong Connections and Shorted SCR

Operational after start signal. It trips the starter if motor is not properly

connected to starter's load terminals, or if:

• Internal disconnection in the motor winding is detected.

• one or more SCRs are shorted.

• a fiber - optic lead is not properly inserted.

This protection is not active when SOFT START CURVE 0 is selected.

Check with an ohmmeter between L1-U, L2-V, L3-W; resistances are

listed on section xxx..

Check for no voltage on terminals U, V, W (from parallel system or an

independent bypass).

OVERTEMPERATURE

Thermal sensors are mounted on the heat-sinks of the Power Section

and trip the ISA-HD when the temperature rises above 85ºC.

Page 65: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 65 / 111

Caution

The over temperature protection is designed to operate under normal

conditions e.g. in the event of extended low overload.

Incorrect starter selection or operations frequent starting at maximum

conditions or repeated starting under fault conditions can cause SCRs

to overheat and fail before the heat-sink reaches 85°C to trip the ther-

mal sensors.

STORAGE ERROR

When trying to store parameters at the end of a mode page or after

lading DEFAULT PRAMETERS. Press Reset and try again. If this

does not succeed load DEFAULT PARAMETERS. Refer to section 10

for more details on loading default parameters. Note that obtaining DE-

FAULT PARAMETERS erases all previously modified settings and re-

quires the operator to reprogram all parameters that differ from the

factory default.

Note: It is especially important to reprogram the RATED LINE VOLT-

AGE and STARTER FLC (as shown on the label of the ISA-HD) and

all other parameters in MAIN & PROTECT mod page.

COMM. PORT FAILED

Trips the ISA-HD if, when controlled via Profibus communication link,

the communication cable is torn or the communication from the PLC

is lost.

Note that the occurrence of this fault depends on then “Watch Dog”

function of the Profibus controller. You must reconnect the wiring

and/or the communication with the PLC and wait for a start command

initiated by the PLC. Trips the ISA-HD if, when controlled via Profibus

communication link, the communication cable is torn or the communi-

cation from the PLC is lost.

Note that the occurrence of this fault depends on then “Watch Dog”

function of the Profibus controller. You must reconnect the wiring

and/or the communication with the PLC and wait for a start command

initiated by the PLC.

Page 66: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

66 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Fault and reset

When any of the above protection operates, the starter locks in a fault

condition and disables thyristors firing.

Fault LED turns ON, fault description is displayed on the LCD and fault

relay operates.

• For local resetting, after fault has been removed, press <RE-

SET> key.

• Remote resetting can be done through terminals 7 or 8 (refer to

I/O programming ).

When a fault occurs followed by a voltage outage, fault condition is

latched and re-appears upon voltage restoration.

Note

Resetting is not possible when a start command is active.

Auto reset under voltage and phase loss

Under-voltage and phase-loss faults can be set to Auto-Reset (see

fault parameters). The starter will reset itself 60 sec after the trip, pro-

vided that no start signal is active.

Auto reset under -current

Under-current fault can be set to Auto-reset (see fault parameters).

The starter will reset itself after the adjustable “UNDER CUR. RESET”

provided that no start signal is active.

Page 67: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 67 / 111

Table 9 timing and occurrence

timing and occurrence

active during

start run stop soft stop

too many starts X

electronic overload X

shear pin (jam) * default setting

starter protection - trip function at 850 % FLC in less than 1 cycle

X X X

motor protection - trip function

during start - factory set at 850 % FLA in less than 1 cycle

X X

during run - adjustment 200 - 850 % FLA with adj. time delay

X

programmable setting (Dip switch # 2 On)

starter protection - trip function at 850 % FLC X X X

motor protection - alarm and trip functions on fault “Immediate Relay” acts as alarm w / ad-justable delay. Trip will not occur if fault is cleared within the time delay.

During start - preset at 850 % FLA, adjust. delay (imm. relay)

X X

During run - adjust. 200 - 850 % FLA adjust. delay (imm. relay)

X

Under current X

Page 68: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Motor and Starter Protection

68 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

timing and occurrence

active during

start run stop soft stop

Unbalance Current X X X

Ground fault current X X X

Phase loss X X X

Phase sequence X X X

Under voltage Time delay is overridden in case of“ No-Volt”.

X X X

Over voltage with adjustable time delay

X X X

Long start time (Stall protection)

X

Shorted SCR and wrong connection (load shedding)

X X

External fault 1 and 2 X X X X

SCR protection by Metal Oxide Varistors (MOV) X X X X

Starter over-temperature X X X X

Starter internal test when supply voltage is connected and LED is “On” .

X X X X

PWR ON and NO STRT X

By-Pass Open X

Page 69: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 69 / 111

10 Front Panel

10.1 Overview of the front panel

Figure 22 LED arrangement

LED arrangement

On ON when control supply voltage is connected to the

starter.

Start ON during start process, indicating that motor ter

minal voltage is ramping up.

Run ON after completion of starting process to indicate

that motor is receiving full voltage.

S. Stop ON during soft stop process to indicate that motor

supply voltage is ramping down.

Stop ON when motor is stopped.

Test ON when in “TEST MODE”.

D. Adj. ON when dual adjustment is in operation.

Fault ON upon operation of any of the built-in protection.

Lights upon operation of any of the built-in protec

tions.

Page 70: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

70 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Flashes when:

• Date and time are not set

• INSULATION ALARM optional relay is activated.

• Fault was detected but TRIP AFTER BYPASS is set to DISABLE.

Keypad description

Note

Provides selection of the following modes: When Dip switch #1 is in

“On”, gray zone shows maximized list of parameters).

Figure 23 mode selection (full / limited set of parameters)

Scrolls through the display and programming menus of the ISA-HD.

Note: Pressing Mode continuously increases the speed at which the

parameters change.

Figure 24 selection key

When a mode name is displayed, pressing this button drills down to

the parameters for that mode. When a parameter is displayed, press-

ing this button scrolls to the next parameter.

Figure 25 key to increase a parameter value

Page 71: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 71 / 111

Allows the operator to increment adjusted values shown in the display.

Operator should press this button once to increment one value, or con-

tinuously to rapidly increment values up to the maximum value.

Figure 26 key to decrease a parameter value

Allows the operator to decrement adjusted values shown in the dis-

play. Operator should press this button once to decrement one value,

or continuously to rapidly decrement values up to the minimum value.

Figure 27 key to store a parameter

Stores modified parameters only when you have scrolled through all

parameters and STORE ENABLE XXXXXX PARAMETERS is dis-

played. After you store a parameter successfully DATA SAVED OK

message will display.

Note: Pressing this button at any other time has no effect.

Figure 28 key to reset after fault has been removed

Resets the ISA-HD after a fault has been dealt with and the start com-

mand has been removed (except for UNDERCURR. TRIP – Refer to

parameter UNDER CUR. RESET). This cancels the fault displayed

and allows you to restart the motor.

Page 72: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

72 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

10.2 Display Mode

LCD arrangement

Two lines of 16 characters display:

System parameters, starter settings, motor current, insulation and fault

identification.

Five selectable languages - English, French, German, Turkish and

Spanish (Russian as option please contact factory)

(see DIP switch settings).

Display readout:

CURRENT LIMIT

390%

Figure 29 text display arrangement

• Upper line displays functions.

• Lower line displays setting and measured values.

Modifying parameters

5. Press <mode> key several times until you reach the required mode

page.

6. Press <Select> to review parameters of this mode.

7. When reaching the required parameter, modify its values with:

Figure 30 down / up keys

Page 73: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 73 / 111

8. To store the new parameters, press <Select> until “Store Enable”

appears and then press <Store> key

Note

Pressing <Mode> or <Select> keys continuously increases parameter

scrolling speed.

MODE pages

Upon control supply connection, the LCD displays motor's operating

current. When Dip switch # 1 is set to On (refer to display options -

page 21) All mode pages can be reviewed by pressing the <Mode>

key. When Dip switch # 1 is set to off, the following mode pages

marked ** will not appear.

START PARAMETERS

Figure 31 display start parameters

STOP PARAMETERS

Figure 32 display stop parameters

DUAL ADJUSTMENT

PARAMETERS

Figure 33 display dual adjustment parameters

**

Page 74: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

74 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

FAULT PARAMETERS

Figure 34 display fault parameters

I/O PROGRAMMING

PARAMETERS

Figure 35 I/O programming parameters

COMM. DATA

Figure 36 display communication parameters

STATISTICAL DATA

Figure 37 display statistical data

In this mode, parameters are not adjustable.

% OF MOTOR FLA

Figure 38 operating current display

Displays operating current as a percentage of motor's FLA.

**

**

**

Page 75: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 75 / 111

Note

Starter's default display. A time delay is initiated after pressing

<MODE> or <SELECT>. Following the delay, the LCD defaults back

to display “% OF MOTOR FLA”. Five minutes after programming the

LCD it returns to the current display.

Press <SELECT> - When analog card is incorporated.

When option cards are not incorporated, the LCD displays

OPTION CARD

Not Installed

Figure 39 option card not installed

When incorporated, the LCD displays

OPTION CARD

ANALOG OUTPUT

Figure 40 analog output card installed

Displays analog card preset.

This concludes the “DISPLAY MODE”

Pressing <SELECT> key at this point returns to the first display.

Obtaining “DEFAULT PARAMETERS”

1. Press <MODE> and keys simultaneously and the LCD will display

„STORE ENABLE DEFAULT PARAMETERS.“

Figure 41 Restore default parameters

2. Press <STORE> and <MODE> keys simultaneously.

Page 76: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Front Panel

76 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Caution

Obtaining default parameters will erase all previously modified set-

tings.

ISA-HD FLC must be set to the rated starter current as specified on

the starter label.

10.3 Remote Display

Figure 42 Remote Display

Page 77: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 77 / 111

11 Parameter Setting

Instruction

Table 10 List of parameters

Instruction Display

Press <Mode>

To proceed to:

MAIN and PROTECT. PARAMETERS

Press <SELCET>

Press ▲ or ▼ to set Line voltage

Range: 2300-15000

RATED LINE VOLTAGE

6000V

Description: Sets ISA-HD’s rated voltage. ISA-HD’s rate voltage should be as shown on its label.

Note: Setting RATED LINE VOLTAGE to other than the value on the label will cause a wrong operation and wrong readings of the soft starter.

Press <SELCET>

Press ▲ or ▼ keys to set starter FLC.

Range: 20 - 1800

STARTER FLC 250 AMP

Description: Sets ISA-HD’s FLC (Full Load Current). ISA-HD’s FLC should be as shown on its label.

Note: Setting FLC to other than the value on the label will cause a wrong operation and wrong readings of the soft starter.

Press <SELCET>

Press ▲ or ▼ keys to set motor FLA.

Range: 30 - 100 % of „STARTER FLC“

MOTOR FLA 150 AMP

Description: Sets motor’s FLA (Full load Ampere)

Should be programmed as shown on the motor’s name plate.

Press <SELCET>

Press ▲ or ▼ keys to set motor power.

Range: 50 – 40000KW

RATED MOTOR PWR

3560KW

Description: Sets motor rated power as indicated on its name plate.

Page 78: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

78 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Press <SELCET>

Press ▲ or ▼ keys to set motor service factor.

Range: 100 – 130%

SERVICE FACTOR

100%

Description: Sets motor rated service factor as indicated on its name plate.

Press <SELCET>

Press ▲ or ▼ keys to under current trip set point.

Range: 0 = OFF, 20 - 90 % of FLA

UNDERCURR. TRIP 0 % of FLA

Press <SELCET>

Press ▲ or ▼ keys to under current trip time de-lay set point.

Range: 1 - 40 sec

UNDERCURR. DELAY 10 SEC.

Description: Sets UNDER CURRENT TRIP protection. Sets the time delay for UN-DER CURRENT TRIP protection. Trips the ISA-HD when the motor current drops below the level that was set for a time period longer than UNDER CURRENT DE-LAY.

Note: • Operational when the motor is running (the RUN LED is lit).

• Can be set to AUTO RESET.

Press <SELCET>

Press ▲ or ▼ keys to over current shear-pin set point.

Range: 100 - 850 % of FLA

O/C - SHEAR PIN 850 % OF FLA

Press <SELCET>

Press ▲ or ▼ keys to set O/C shear-pin time de-lay.

Range: 0.5 - 5 sec.

Note: When set to 0.0 it is practically up to 200msec

O/C DELAY 1.5 SEC.

Description: Sets OVER CURRENT SHEAR PIN protection. Sets O/C – SHEAR PIN DELAY time. Operational when ISA-HD is energized and has three trip func-tions:

At all time - If I > 850% of FLC it trips the ISA-HD within 1 cycle (overrides the value of the O/C – SHEAR PIN setting).

Page 79: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 79 / 111

Instruction Display

At starting process - If I > 850% of FLA it trips the ISA-HD after O/C DELAY (see here after)

At run time - If I > O/C – SHEAR PIN setting of FLA it trips the ISA-HD after O/C DELAY.

Note: The OVER CURRENT SHEAR PIN protection is not intended to replace fast acting fuses to protect from short current!

Press <SELCET>

Press ▲ or ▼ keys to set overload class.

Range:

IEC CLASS 5/ IEC CLASS 10/ IEC CLASS 15/ IEC CLASS 20/ IEC CLASS 25/ IEC CLASS 30/ NEMA CLASS 5 NEMA CLASS 10 NEMA CLASS 15/ NEMA CLASS 20 NEMA CLASS 25/ NEMA CLASS 30

OVERLOAD CLASS

IEC CLASS 10

Description: Sets OVERLOAD CLASS characteristics Sets OVERLOAD PRO-TECT functionality. The ISA-HD allows motor protection according to IEC class 5, 10, 15, 20, 25 or 30 or according to NEMA class 5, 10, 15, 20, 25 or 30. Tripping curves are shown on section 4.8 and 4.9. The OVERLOAD protection incorporates a THERMAL CAPACITY register that calculates heating minus dissipation of the motor. The ISA-HD trips when the register fills up. (THERMAL CAPACITY=100%) The time constant, in seconds, for cool down after overload trip is:

Class 5 10 15 20 25 30

IEC 160 320 480 640 510 960

NEMA 140 280 420 560 700 840

The overload protection can be set to protect the motor as set in the OVERLOAD PROTECT parameter:

ENABLE – motor is protected at all time.

ENABLE WHILE RUN – motor is protected only when in Run.

DISABLE – motor is not overload protected by the soft starter.

Note: In order to restart after OVERLOAD trip, the thermal register should be 50% or less.

Press <SELCET>

Press ▲ or ▼ keys to over current shear-pin set point.

Range: Disable/Enable while run/ Enable

OVERLOAD PROTECT

ENABLE WHILE RUN

Page 80: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

80 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Description The overload protection can be set to protect the motor as set in the OVERLOAD PROTECT parameter:

ENABLE – motor is protected at all time.

ENABLE WHILE RUN – motor is protected only when in Run.

DISABLE – motor is not overload protected by the soft starter.

Press <SELCET>

Press ▲ or ▼ keys to set unbalance trip.

Range: 10 - 100 % of motor FLA

UNBALANCE TRIP 20%

Press <SELCET>

Press ▲ or ▼ keys to set unbalance trip time de-lay.

Range: 1 - 60 sec.

UNBALANCE DELAY 5 SEC.

Description: Sets UNBALANCE TRIP level. Sets UNBALANCE TRIP DELAY.

Trips the ISA-HD when current unbalance increases above level that was set for a time longer than UNBALANCE DELAY.

Notes: Becomes operational after the start signal.

Press <SELCET>

Press ▲ or ▼ keys to set ground fault trip.

Range: 10 – 100 %

GND FAULT TRIP 20 % OF FLA

Press <SELCET>

Press ▲ or ▼ keys to set ground fault trip delay.

Range: 1 – 60 sec.

GND FAULT DELAY 5 SEC.

Description: Sets GND FAULT TRIP level. Sets GND FAULT TRIP DELAY.

Trips the ISA-HD when ground current increases above level that was set for a time longer than

GND FAULT DLY.

Note: Becomes operational after the start signal.

Press <SELCET>

Press ▲ or ▼ keys to set under voltage trip.

Range: 70 – 90 % of UN.

UNDERVOLT. TRIP 75% of UN

Page 81: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 81 / 111

Instruction Display

Press <SELCET>

Press ▲ or ▼ keys to set under voltage trip time delay,

Range: 1 – 10 sec.

UNDERVOLT.DELAY 5 SEC.

Description:

Sets UNDER VOLTAGE TRIP level. Sets UNDERVOLT TRIP DELAY.

Trips the ISA-HD when mains voltage drops below the level that was set for a time longer than UNDERVOLT DELAY.

Notes:

• Becomes operational only after the start signal.

• When voltage drops to zero (voltage outage) the ISA-HD will trip immediately, thus overriding the delay.

• Can be set to AUTO RESET.

Press <SELCET>

Press ▲ or ▼ keys to set over voltage trip.

Range: 110 - 125 % of UN (cannot be set below under voltage)

OVERVOLT. TRIP 120 % of UN.

Press <SELCET>

Press ▲ or ▼ keys to set over voltage trip time delay.

Range: 1-10 sec.

OVERVOLTAGE DELAY 2 SEC

Description: Sets OVER VOLTAGE TRIP. Sets OVERVOLT TRIP DELAY. Trips the ISA-HD when mains voltage increases above the level that was set for a time longer than OVERVOLT DELAY.

Cannot be set lower than the UNDER VOLTAGE setting.

Note: Becomes operational only after the start signal.

Press <SELCET>

Press <STORE> key to store select parameters.

Note: Storing selected parameters is possible only when stop or run LED are on. Storing is inhib-ited, if start, soft stop or fault LED is on.

STORE ENABLE MAIN PARAMETERS

Page 82: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

82 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

When parameters have been correctly stored the LCD displays

DATA SAVED OK

This concludes “Main and Protection Parameter” settings.

Pressing <SELCET> key after „DATA SAVED OK“ returns to the first display in this mode.

In case of a failure in parameter storing the LCD displays:

Press <SELCET> button again until „Store Enable Main Parameters“ returns then press <STORE> key until „Data save OK“ ap-pears

STORAGE ERROR

Press <MODE>

To proceed to:

START PARAMETERS

Press <SELCET>

Then press ▲ or ▼ keys to set soft start curve:

0 = Basic 1 = standard curve 2 = pump control curve # 1 3 = pump control curve # 2 4 = pump control curve # 3 5 = torque control

SOFTSTART CURVE 1 (STANDARD)

Note: Please see start and stop Parameter

When setting dip switch # 2 to on for tacho mode press <SELCET> <%> <&>, curve message changes to:

Then press <%> <&> keys to set tacho gain:

0 = minimum gain tacho control. 1 = second level tacho gain. 2 = third level tacho gain. 3 = fourth level tacho gain. 4 = fifth level tacho gain. 5 = sixth level tacho gain.

Note: tacho feedback is operational in its basic form. Additional curves except for the basic lin-ear curve are optional. Consult factory for correct tacho selection and mechanical installation.

START TACHO. GAIN 0 (MIN. GAIN)

Page 83: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 83 / 111

Instruction Display

Description:

1!! represents the 2nd level TACHO GAIN

2!! represents the 3rd level TACHO GAIN

5!! represents the 6th level TACHO GAIN.

Notes:

(1) This parameter will appear only if the optional PCB is installed and dip switch # 2 is set to on. Refer to section for dip switch setting details.

(2) Tacho Feedback is operational in its basic form. Additional curves except for the basic linear curve are optional. Consult the factory for the correct tacho selec-tion and mechanical installation.

Press <SELCET>

Press ▲ or ▼ keys to set pulse level.

Range: 70% - 100 %)

PULSE LEVEL

70% of FLA

Description: Sets PULSE LEVEL and PULSE START TIME. Intended to break free high friction loads requiring high starting torque for a short time or for pedestal start by holding the current at a predefined level for predefined time period. The pulse is defined by its current level and time length (width). After this pulse the voltage is ramped down to INITIAL VOLTAGE setting before ramping up again to full voltage

according to the START PARAMETERS settings. For PULSE TIME<1SEC. PULSE LEVEL can be set to 70- 700% of FLA; For PULSE TIME≥1SEC. PULSE LEVEL can be set to 70- 400% of FLA; In EXTENDED SETTING; PULSE LEVEL can be set to 70-700% with the limitation of: 440x(FLC/FLA).

Notes:

• PULSE START is not effective in SOFT START CURVE 0. For better control of the current withdrawn from the network (mainly from generators), the following set-tings

applies (applies from software versions newer than MVSTMB.GN-010509):

PULSE TIME T slope

[seconds]

≤ 1 Approx. 0.1 second.

x.0, x.5 (1) Very short

x.1, x.6 (2) short

> 1 x.2, x.7 (3) Medium length

x.3, x.8 (4) long

x.4, x.9 (5) Very long

Page 84: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

84 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

(1) x.0, x.5 applies to PULSE TIME: 1.5, 2.0, 2.5, 3.0, 3.5, 4.0,

4.5, 5.0, 5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0, 9.5, 10.0 seconds

(2) x.1, x.6 applies to PULSE TIME: 1.1, 1.6, 2.1, 2.6, 3.1, 3.6,

4.1, 4.6, 5.1, 5.6, 6.1, 6.6, 7.1, 7.6, 8.1, 8.6, 9.1, 9.6 seconds

(3) x.2, x.7 applies to PULSE TIME: 1.2, 1.7, 2.2, 2.7, 3.2, 3.7,

4.2, 4.7, 5.2, 5.7, 6.2, 6.7, 7.2, 7.7, 8.2, 8.7, 9.2, 9.7 seconds

(4) x.3, x.8 applies to PULSE TIME: 1.3, 1.8, 2.3, 2.8, 3.3, 3.8,

4.3, 4.8, 5.3, 5.8, 6.3, 6.8, 7.3, 7.8, 8.3, 8.8, 9.3, 9.8 seconds

(5) x.4, x.9 applies to PULSE TIME: 1.4, 1.9, 2.4, 2.9, 3.4, 3.9,

4.4, 4.9, 5.4, 5.9, 6.4, 6.9, 7.4, 7.9, 8.4, 8.9, 9.4, 9.9 seconds

Press <SELCET>

Press ▲ or ▼ keys to set pulse start time.

Range: 0 - 2 sec. (pulse level at 80 %UN)

PULSE TIME 0 SEC.

Press <SELCET>

Press ▲ or ▼ keys to set Initial Voltage.

Range: 10 - 50 % of UN. (extended Setting 5-80%)

INITIAL VOLTAGE 30 %

Press <SELCET>

Press ▲ or ▼ keys to set Initial CURRENT.

Range: 100 - 500 % of UN. (only when use)

INITIAL CURRENT

100%

Description: Sets motor’s INITIAL STARTING VOLTAGE. The motor’s torque is di-rectly proportional to the square of the voltage. This adjustment also determines the inrush current and mechanical shock. A setting that is too high may cause high initial mechanical shock and high inrush current. This can

occur even if CURRENT LIMIT is set low because the INITIAL VOLTAGE setting overrides the CURRENT LIMIT setting. A setting that is too low may result in pro-longed time until the motor starts to turn. In general, this setting should ensure that the motor starts turning immediately after start signal.

Page 85: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 85 / 111

Instruction Display

Note:

When INITIAL VOLTAGE is set its maximum value, this displays changes to INI-TIAL CURRENT.

When INITIAL CURRENT is set the ISA-HD causes current ramp instead of volt-age ramp.

Press <SELCET>

Press ▲ or ▼ keys to set current limit.

Range: 100 - 400 % of motor FLA. (extended settings 100-700%)

CURRENT LIMIT 400 % OF FLA

Description: Sets motor’s CURRENT LIMIT during starting. A setting that is too high will increase the current drawn from mains and faster acceleration. A setting that is too low may prevent the motor from completing acceleration process and reaching full speed. In general, this setting should be set to a value that is high enough to prevent stalling.

Note: CURRENT LIMIT does not operate during RUN and SOFT STOP.

Press <SELCET>

Press ▲ or ▼ keys to set acceleration time.

Range: 1 - 30 sec.

ACC. TIME 10 SEC.

Description: Sets ACCELERATION TIME of the motor. Determines the motor’s voltage ramp-up time, from initial to full voltage. It is recommended to set ACCEL-ERATION TIME to the minimum acceptable value (approx. 5 sec).

Notes:

• Since CURRENT LIMIT overrides ACC. TIME, when CURRENT LIMIT is set low, the starting time will be longer than the ACC. TIME setting.

• When the motor reaches full speed before voltage reaches nominal, ACC. TIME setting is overridden, causing voltage to quickly ramp-up to nominal.

• Using starting curves 2, 3, 4 prevents quick ramp up.

Page 86: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

86 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Press <SELCET>

Press ▲ or ▼ keys to maximum start time.

Range: 1 - 30 sec. (extended Setting 1 – 250 sec.)

MAX. START TIME 30 SEC.

Description: Sets MAXIMUM START TIME. The maximum allowable start time, from the start signal to the end of the acceleration process. If voltage/speed does not reach nominal during MAX. START TIME then ISA-HD will trip the motor and create a fault. The LCD will display the LONG START TIME fault message. For example, this can occur when the CURRENT LIMIT setting is too low.

Press <SELCET>

Press ▲ or ▼ keys to set the number of starts permitted (during start period below).

Range: 1 – 10, Off

NUMBER OF STARTS 1

Description: Sets NUMBER OF STARTS permitted during STARTS PERIOD. Lim-its the number of starts during the period of time defined by STARTS PERIOD. If you try to start even one more time within that period the START INHIBIT period will take effect.

Press <SELCET>

Press ▲ or ▼ keys to set number of starts time period.

Range: 1 – 60 min

STARTS PERIOD 30 MIN.

Description: Sets STARTS PERIOD during which NUMBER OF STARTS is being counted.

Press <SELCET>

Press ▲ or ▼ keys to set start inhibit period.

Range: 1 – 60 min

START INHIBIT 15 MIN.

Description: Sets START INHIBIT time which starting is disabled after TOO MANY STARTS trip.

During the START INHIBIT period the WAIT BEFORE RST XX MIN message will be displayed.

Press <SELCET>

Press ▲ or ▼ keys to set time delay for the end of acceleration contact.

RUN CONTACT DEL. 5 SEC.

Page 87: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 87 / 111

Instruction Display

Range:1 – 120 sec.

Description: Sets time delay for End of Acceleration relay to close after completion of starting process.

End of Acceleration relay can signal that motor is at its RUN position which can be used for motor loading.

Press <SELCET>

Press ▲ or ▼ keys to set Bypass ON at.

Range: 100 – 150 % of FLA (only when use)

TURN BYPASS ON AT

120% FLA

Press <SELCET>

Press ▲ or ▼ keys to set min time to Bypass ON (only when use)

MIN TIME TO BYPASS

3 sec.

Press <SELCET>

To store selected parameters, press <STORE> key.

STORE ENABLE START PARAMETERS

When parameters have been correctly stored the LCD reads:

This includes START PARAMETERS settings.

DATA SAVED OK

Press <MODE>

To proceed to

STOP PARAMETERS

Press <SELCET>

Then press ▲ or ▼ keys to set soft start curve:

0 = basic 1 = standard curve 2 = pump control curve # 1 3 = pump control curve # 2 4 = pump control curve # 3 5 = torque control

SOFT STOP CURVE 1 (STANDARD)

Page 88: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

88 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

When setting dip switch #2 to on for tacho mode, press <SELCET> ▲ or ▼ curve message changes to:

Then press ▲ or ▼ keys to set tacho gain:

0 = minimum gain tacho control. 1 = second level tacho gain. 2 = third level tacho gain. 3 = fourth level tacho gain. 4 = fifth level tacho gain. 5 = sixth level tacho gain.

STOP TACHO GAIN 0 (MIN GAIN)

Description: 1!! represents the 2nd level TACHO GAIN

2!! represents the 3rd level TACHO GAIN…..

5!! represents the 6th level TACHO GAIN.

Notes:

(1) This parameter will appear only if the optional PCB is installed and dip switch # 2 is set to on. Refer to section for dip switch setting details.

(2) Tacho Feedback is operational in its basic form. Additional curves except for the basic linear curve are optional.

(3) Consult the factory for the correct tacho selection and mechanical installation.

Press <SELCET>

Then press ▲ or ▼ keys set deceleration time.

Range: 1 - 30 sec. (1-90 sec with extended Set-ting)

DEC. TIME 10 SEC.

Description: Sets DECELERATION TIME of the motor. Used for controlled decel-eration of high friction loads. Determines the motor’s voltage ramp down time.

Note:

The ISA-HD operates with a Bypass Contactor. The Bypass Contactor is con-trolled by the ISA-HD End of Acceleration relay. Upon soft stop initiation the End of Acceleration relay is de-energized, the load is transferred to the ISA-HD, and voltage begins ramping down.

Press <SELCET>

Then press ▲ or ▼ keys set Final torque during soft stop.

Range : 0 – 10 (0 = min., 10 = max.).

FINALE TORQUE 0 (MIN)

Page 89: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 89 / 111

Instruction Display

Description: Sets FINAL TORQUE during soft stop. Determines torque towards the end of a soft stop. If the current still flows after speed is softly reduced to zero, you should increase the FINAL TORQUE setting.

Sets an Off delay timer that prevents the ISA.HD to start When COAST DOWN DELAY is set to OFF:

If start command is initiated momentarily (via push button, for example, to terminal 6 of the control module) before 3 seconds after stop are elapsed, it is ignored.

If start command is initiated and maintained (via closing a switch, for example, to terminal 6 of the control module), start occurs after 3 seconds (from stop) are elapsed. When COAST DOWN DELAY is set to a value (10-3600 seconds):

If start command is initiated momentarily (via push button, for example, to terminal 6 of the control module ) before 3 seconds after stop are elapsed, it is ignored (same as if COAST DOWN DELAY is set to OFF).

If start command is initiated and maintained or if pressed after 3 seconds and before the set time of COAST DOWN DELAY, the HRVSDN trips (same as for TOO MANY STARTS), displaying a fault message COAST DOWN TIME. Reset is possible im-mediately.

COAST DOWN DELAY OFF

OFF, 10 –3600 Sec.

Press <SELECT>

To store selected parameters, press <STORE> key.

STORE ENABLE STOP PARAMETERS

When parameters have been correctly stored the LCD displays:

This concludes STOP PARAMETERS setting.

DATA SAVED OK

Press <MODE>

To proceed to dual adjustments when Dip switch # 1 is set ON:

DUAL ADJUSTMENTS PARAMETERS

When selecting „Generator Mode“ (Dip switch # 3 is On) the following display appears instead of the above.

D:ADJ: GENERATOR PARAMETERS

Page 90: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

90 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Press <SELCET>

Then press ▲ or ▼ keys set DA Initial Voltage.

Range:.10 - 50 % of UN with initial current 100 - 400 %.

DA: INIT. VOLT. 30%

Press <SELCET>

Then press ▲ or ▼ keys set DA Initial CUR-RENT.

Range:. initial current 100 - 400 %.

DA: INIT. CURRENT 100%

(only when use)

Description: Sets motor’s INITIAL STARTING VOLTAGE in DA mode. (Motor’s torque is directly proportional to the square of the voltage) Refer to parameter: INI-TIAL VOLTAGE

Note: The range of the DA: INITIAL VOLTAGE can be extended to 10-80% by us-ing the EXTENDED SETTING

Press <SELCET>

Then press ▲ or ▼ keys set DA Current Limit.

Range: 100 - 400 % of motor FLA. (100-500% with extended settings)

DA: CUR. LIMIT 400% OF FLA

Description: Sets motor’s highest current during starting in DA mode. Refer to pa-rameter: CURRENT LIMIT.

Press <SELCET>

Then press ▲ or ▼ keys set DA: Acceleration Time.

Range: 1 - 30 sec. (1-90 sec with extended Set-ting)

DA: ACC. TIME 10 SEC.

Description: Sets ACCELERATION TIME of the motor in DA mode. Refer to pa-rameter: ACC. TIME.

Press <SELCET>

Then press ▲ or ▼ keys set DA: deceleration time.

Range: 0 - 30 sec. (0-90 sec with extended Set-ting)

DA: DEC: TIME 10 SEC.

Description: Sets DECELERATION TIME of the motor in DA mode. Refer to pa-rameter: DEC. TIME.

Page 91: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 91 / 111

Instruction Display

Press <SELCET>

Then press ▲ or ▼ keys set DA: motor FLA.

Range: 33 - 100 % of „STARTER FLC“.

DA: MOTOR FLA 150 AMP:

Description: Sets motor’s FLA (Full load Ampere) in DA mode. Refer to parameter: MOTOR FLA.

Press <SELCET>

To store selected parameters, press <STORE> key.

STORE ENABLE D.ADJ. PARAMETERS

When parameters have been correctly stored the LCD displays:

This concludes DUAL ADJUSTMENT PARAMETERS setting.

DATA SAVED OK

Press <MODE>

Set Dip switch # 1 to ON, to proceed to:

FAULT PARAMETERS

Press <SELCET>

Then press ▲ or ▼ keys to set Auto Reset for under voltage and phase loss faults. Range: Yes / No.

UV and PL AUTO RST NO

Description: Sets UNDERVOLTAGE and PHASE LOSS AUTO RESET. If UV & PL AUTO RST is set to NO then ISA-HD will not automatically reset after an UN-DER VOLTAGE or PHASE LOSS faults occur.

If you set the UV & PL AUTO RST setting to YES then ISA-HD will automatically reset.

Notes:

• Reset is performed only after the start signal is removed. To restart the motor re-commence the start command.

• Refer to section for details on setting of UNDERVOLT. TRIP.

Press <SELCET>

Then press ▲ or ▼ keys to set Under Current Auto Reset.

Range: 10 - 120 min / Off.

UNDER CUR: RESET OFF

Page 92: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

92 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Description: Sets UNDER CURRENT RESET time delay. If the UNDER CUR. RE-SET setting is OFF then ISA-HD will not automatically reset after an UNDER CURRENT TRIP fault occurs. If you set the UNDER CUR. RESET setting to a time value then ISA-HD will automatically reset with a delay (the time defined for UNDER CUR. RESET). If the start command is not removed, motor will restart au-tomatically after the delay time. During the delay time a message U/C TRIP.RST IN: XX MIN. is displayed.

Notes:

• If the start command is not removed, motor will restart automatically after the de-lay time!!

• Refer to section for details on setting of UNDER CURRENT TRIP.

Press <SELCET>

Then press ▲ or ▼ keys to set By Pass open trip.

Range: Enable \ Disable.

BY PASS OPEN TRIP ENABLE

Description: Sets BYPASS OPEN TRIP protection. Becomes operational when the Bypass Contactor does not close after EOA contact command the pilot (interpos-ing) relay to close. Set to ENABLE when motor current is running through the in-ternal CTs. Set to DISABLE when motor current is not running through the internal CTs.

Press <SELCET>

Then press ▲ or ▼ keys to set trip after By-Pass.

Range: Enable \ Disable.

TRIP AFTER BY PASS ENABLE

Description: Sets TRIP AFTER BYPASS trip. TRIP AFTER BYPASS can be set to DISABLE if motor is protected by an additional relay usually upstream to the soft starter. If during operation a fault occurs, Fault LED will flash and soft starter will display the fault but will not trip the motor until the soft starter is stopped.

Press <SELCET>

Then press ▲ or ▼ keys to set By- Pass auto re-set.

Range: yes \ no.

BY PASS AUTO RESET NO

Description: Sets BY-PASS AUTO RST reset. When TRIP AFTER BYPASS is DISABLE and if during operation a fault occurs, Fault LED will flash and soft starter will display the fault but will not trip the motor until the soft starter is

Page 93: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 93 / 111

Instruction Display

stopped. In this case the soft starter will go to Trip position. If BY-PASS AUTO RE-SET is set to YES, the soft starter will be automatically reset the fault.

Note: Reset is performed only after the start signal is removed. To restart the mo-tor recommence the start command.

Press <SELCET>

Then press ▲ or ▼ keys to set SET CURVE 0 FLT.

Range: Enable \ Disable

SET CURVE 0 FLT

Enable

Description: SET CURVE TO 0 message may occur seldom during starting with special conditions of mains and load. Change start (and stop, if used) curve to SOFT START CURVE 0 and SOFT STOP CURVE 0. Set SET CURVE 0 FLT to DISABLE, only if SET CURVE TO 0 FLT fault occurs during starting and if SOFT START CURVE 0 is not good enough for the application. When set to DISABLE verify that motor starts normally in the selected curve.

Press <SELCET>

Then press ▲ or ▼ keys to set PWR ON & NO STRT.

Range: Enable \ Disable

ON & NO STRT.

Enable

Description: Sets POWER ON & NO STRT trip POWER ON & NO START is oper-ational upon mains voltage connection. It trips the ISA-HD when mains voltage is connected to the ISA-HD for more than 30 seconds without a start signal. Set to DISABLE only in special occurrences. (Consult factory!)

Press <SELCET>

Then press ▲ or ▼ keys to set INSULATION ALARM.

Range: ON \ OFF

INSULATION ALARM

ON

Press <SELCET>

Then press ▲ or ▼ keys to set INSULATION TRIP.

Range: ON \ OFF

INSULATION TRIP

OFF

Description: Sets INSULATION ALARM level. Activates INSULATION ALARM trip. Applicable only if optional insulation PCB and resistor unit are installed and con-nected. Insulation testing is enabled only when motor is not running and after 60

Page 94: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

94 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

seconds in the Stop state. While motor is running the value of the insulation re-sistance shown in the display is the last measured value prior to starting of the motor. While testing, if the insulation level drops below Alarm level-a message: MOTOR INSULATION ALARM will display and the insulation alarm relay will be energized. The Fault LED on the control keypad of the

ISA-HD will blink. If insulation level will return to normal for more than 60 seconds the alarm will automatically reset. While testing, if the insulation level drops below Fault level – a message: INSULATION TRIP will display and the fault relay of the ISA-HD will go to the fault position (as programmed in the I/O PROGRAMMING PARAMETERS). The Fault LED on the front of the ISA-HD will light. In this status motor can not be started. If insulation level will return to normal the ISA-HD will not automatically reset.

Press <SELCET>

Then press ▲ or ▼ keys to set PHASE SE-QUENCE.

Range: positive \ negative

PHASE SEQUENCE

POSITIV

Description: Sets PHASE SEQUENCE protection of the soft starter. Allows to start the motor in POSITIVE sequence of the mains OR in the NEGATIVE sequence of the mains or, when set to IGNORE, in both sequences.

Press <SELCET>

To store selected parameters press <STORE> key.

STORE ENABLE FAULT PARAMETERS

When parameters have been correctly stored, the LCD displays:

This concludes FAULT PARAMETERS setting.

DATA SAVED OK

Press <MODE>

Set Dip switch # 1 to ON to proceed to:

I/O PROGRAMMING PARAMETERS

Press <SELCET>

Then press ▲ or ▼ keys to set terminal # 7 func-tion.

PROG: INPUT # 7 RESET

Page 95: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 95 / 111

Instruction Display

Range: Test \ Reset. Default: Reset.

Description: Refer to: set terminal 7 function

Press <SELCET>

Then press ▲ or ▼ keys to set terminal # 8 func-tion

Range: Dual Adjustments \ Reset.

PROG: INPUT # 8 DUAL ADJUSTMENT

Description: Refer to: set terminal 8 function

Press <SELCET>

Then press ▲ or ▼ keys to set fault relay func-tion.

Range: Fault \ Fault-Fail Safe.

FAULT RELAY TYPE FAULT

Description: Sets FAULT RELAY mode of operation. When configured to FAULT the internal relay is

energized upon fault. When configured to FAULT FAIL SAFE the relay is de-ener-gized upon fault. In this mode, while normal operation, the contacts are open. Re-lay will also de-energize upon control power outage.

Press <SELCET>

Then press ▲ or ▼ keys to set immediate relay function.

Range: Immediate \ Shear-Pin.

IMM / S.PIN RELAY IMMEDIATE

Description: Sets IMM/ # STRT PREAL mode of operation. When configured to IMMEDIATE the relay is energizes at the start signal after the programmed RE-LAY ON DELAY time has elapsed. It de-energizes at the end of the deceleration time (if any) after the programmed RELAY OFF DELAY time has elapsed.

When configured to # STRTS PREALARM the relay is energized if a start com-mand will cause the soft starter to trip on TOO MANY STARTS.

Press <SELCET>

Press ▲ or ▼ keys to set immediate / shear pin relay on delay.

Range: Immediate 0 - 3600 sec. / Shear-Pin 0 - 5 sec.

RELAY ON DELAY 0 SEC.

Press <SELCET> RELAY OFF DELAY 0 SEC.

Page 96: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

96 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Press ▲ or ▼ keys to set immediate / shear pin relay Off delay.

Range: Immediate 0 – 3600 sec. \ Shear-pin 0 – 5 sec.

Press <SELCET>

Then press ▲ or ▼ keys to set Normal or In-verted output.

Range: Normal \ Inverted.

ANALOG OUTPUT NORMAL

Description: When set to RELATIVE CURRENT the full scale of the optional ana-log PCB output is related to 200% of FLA (2x< Motor rated current>). Or, when set to RELATIVE POWER the full scale of

the analog PCB output is related to 200% of motor power (2x< Motor rated power>). Motor rated power is set in the MAIN & PROTECT parameter.

Press <SELCET>

To store selected parameters press <STORE> key.

STORE ENABLE I/O PARAMETERS

When parameters have been correctly stored the LCD displays:

This concludes I/O PARAMETERS setting.

DATA SAVED OK

Press <MODE>

Set Dip switch # 1 to ON to proceed to:

Communication is optional and operates only when starter incorporates this feature.

Note: Hardware and software are installed in the factory.

Note: The last command determines the function when using communication and local commands.

COMM. PARAMETERS

Press <SELCET>

Then press ▲ or ▼ keys to set the protocol:

For PROFIBUS parameters see „COMM. PROTOCOL PROFIBUS“.

COMM. PROTOCOLL MODBUS

Description:

Page 97: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 97 / 111

Instruction Display

Sets ISA-HD’s communication PROTOCOL. Operational when the optional com-munication PCB is installed.

Press <SELCET>

Then press ▲ or ▼ keys to set communication baud rate.

Range: 1200 - 9600 BPS.

BAUD RATE 9600

Description:

Sets ISA-HD’s BAUD RATE.

Press <SELCET>

Then press ▲ or ▼ keys to set “Communication Parity Check”.

Range: Even \ Odd.

PARITY CHECK EVEN

Description:

Sets ISA-HD’s communication PARITY CHECK.

Press <SELCET>

Then press ▲ or ▼ keys to set comm. serial link number.

Range: 1 - 248 (for up to 32 starters on one twisted pair).

SERIAL LINK NO. 248 (OFF)

Description: Sets ISA-HD’s communication SERIAL LINK NO.

Note: serial link number must be set to 248 (Off) if communication is not in use.

Press <SELCET>

Then press ▲ or ▼ keys to set S. LINK PAR. SAVE.

Range: Enable / Disable

S.LINK PAR SAVE

Disable

Description: Enables parameters modification via serial communication

Press <SELCET>

Then press ▲ or ▼ keys to set SER. LINK CON-TROL.

Range: Enable / Disable

SER. LINK CONTROL

Disable

Page 98: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

98 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Description: Enables start, stop, reset etc… via serial communication

Press <SELCET>

Then press ▲ or ▼ keys to set MODBUS TIME OUT.

Range: off / xx sec./ xx min.

MODBUS TIME OUT

off

Description: Sets MODBUS TIME OUT. If no valid Modbus communication during MODBUS TIME OUT, the ISA-HD will trip. Trip occurs only if the following condi-tions exist:

• SER. LINK CONTROL is set to ENABLE

• SERIAL LINK NO. is not set to OFF

If MODBUS TIME OUT is set to OFF protection is disabled.

Press <SELCET>

Then press ▲ or ▼ keys to set FRONT COM ADDRES.

Range: 1-127 / Off

FRONT COM ADDRES

off

Description: future enhancement

Press <SELCET>

To store selected parameters press <STORE> key.

STORE ENABLE COMM. PARAMETERS

When parameters have been correctly stored the LCD displays:

This concludes COMMUNICATION PARAME-TERS setting.

DATA SAVED OK

Press <SELCET>

Then press ▲ or ▼ keys to set the protocol:

For MODBUS see parameters above.

COMM. PROTOCOL PROFIBUS

Press <SELCET>

Then press ▲ or ▼ keys to set communication baud rate.

Range: auto (Profibus)

BAUD RATE

AUTO (profibus)

Page 99: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 99 / 111

Instruction Display

Press <SELCET>

Then press ▲ or ▼ keys to set number of inputs.

NUMBER OF INPUTS 1

Description: Only in old version

Press <SELCET>

Then press ▲ or ▼ keys to set number of out-puts.

NUMBER OF OUTPUTS 1

Description: only in old version

Press <SELCET>

Then press ▲ or ▼ keys to set communication serial link number.

Range: 1 - 127 (for up to 32 starters on one twisted pair).

PROFI.NETWORK ID

(SERIAL LINK NO). 127 (OFF)

Description: Sets the Profibus network ID. When set to OFF the Profibus PCB will not function.

Note: serial link number must be set to 127 (Off) if communication is not in use.

Press <SELCET>

Then press ▲ or ▼ keys to set S. LINK PAR. SAVE.

Range: Enable / Disable

S.LINK PAR SAVE

Disable

Description: Enables parameter modification via serial communication

Press <SELCET>

Then press ▲ or ▼ keys to set SER. LINK CON-TROL.

Range: Enable / Disable

SER. LINK CONTROL

Disable

Description: Enables start, stop, reset etc… via serial communication

Press <SELCET>

Then press ▲ or ▼ keys to set MODBUS TIME OUT.

Range: off / xx sec./ xx min.

MODBUS TIME OUT

OFF

Description: Do not change this parameter! Must be set to OFF.

Page 100: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Parameter Setting

100 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Instruction Display

Press <SELCET>

Then press ▲ or ▼ keys to set FRONT COM ADDRES.

Range: 1-247 / Off

FRONT COM ADDRES

off

Description: Future enhancement

Press <SELCET>

To store selected parameters press <STORE> key.

STORE ENABLE COMM. PARAMETERS

When parameters have been correctly stored the LCD displays:

This concludes COMMUNICATION PARAME-TERS setting.

DATA SAVED OK

Press <MODE>

To proceed to

Note: it is possible to scroll with the arrow but-tons.

STATISTICAL DATA -****-

Press <SELCET>

Displays Time since last starting

T SINCE L SRT

No data

Press <SELCET>

Displays last starting time in seconds. (Time duration until motor current has reached nominal).

LAST START PERIOD NO DATA

Press <SELCET>

Displays the maximum current at last starts.

LAST START MAXI NO DATA

Press <SELCET>

Displays the motor running time in hours since commencement or since „Statistical Data“ was last reset.

TOTAL RUNTIME 0 HOURS

Press <SELCET>

Displays the total numbers of starts since com-mencement or since „Statistical Data“ was last reset.

TOTAL # OF START 0

Page 101: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Menu Description

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 101 / 111

Instruction Display

Press <SELCET>

Displays the total Energy in KWH.

TOTAL ENERGY

0 KWA

Press <SELCET>

Displays the total Reactive Power in KVAR

TOTAL R. ENERGY

0 KVARH

Press <SELCET>

Describes last fault.

LAST TRIP NO DATA

Press <SELCET>

Displays the current at the last fault.

TRIP CURRENT 0% OF FLA

Press <SELCET>

Displays the total numbers of trips since com-mencement or since „Statistical Data“ was last reset.

With time stamp mm.hh dd.mm.yy

TOTAL # OF TRIPS 0

PREVIOUS TRIP - 1

Through

PREVIOUS TRIP - 9

Press <MODE>

to return to display only mode.

% OF MOTOR FLA

12 Menu Description

Menu Description

MODE MODE MODE MODE MODE

UPON INITIATION

PARAMETERS DIS-

PLAY

PAGE 1 PAGE 2 PAGE 3 PAGE 4

I1 I2 I3 (%)

MAIN & PROTECT.

PARAMETERS

START PARA-

METERS

STOP PARAME-

TERS

DUAL ADJUST-

MENT PARAME-

TERS

Page 102: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Menu Description

102 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

SELECT SELECT SELECT SELECT SELECT

PRESS KEYS TO CHANGE PARAMETER VALUE

I1 I2 I3

(A)

RATED LINE VOLT.

6600 VOLT

S. START CURVE

1 (STANDARD)

SOFT STOP

CURVE

1 (STANDARD)

DA: INIT. VOLT.

30%

VOLTAGE FREQ.

3,300V 49.9Hz

STARTER FLC

150 AMP

S.START CURVE

1 (STANDARD)

STOP TACHO.GAIN

0(MIN. GAIN)

DA: INIT.CURRENT

100%

POWER

1,500 KW

MOTOR FLA

150 AMP.

STRT TACHO.GAIN

0(MIN. GAIN)

DEC. TIME

0 SEC.

DA: CUR. LIMIT

400% OF FLA

REACTIVE POWER

500 KVAR

RATED MOTOR PWR

1000 KW

PULSE LEVEL

70% OF FLA

FINAL TORQUE

0 (MIN.)

DA: ACC. TIME

10 SEC.

POWER FACTOR

0.85

UNDERCURR. TRIP

0% OF FLA

PULSE TIME

0.0 SEC.

STORE ENABLE

STOP PARAME-

TERS

DA: DEC. TIME

0 SEC.

THERMAL CAPACITY

0 %

UNDERCURR. DELAY

10 SEC.

INITIAL VOLTAGE

30 %

DA: MOTOR FLA

150 AMP

MOTOR INSULATION

52.8Mohm

O/C – SHEAR PIN

850% OF FLA

INITIAL CUR-

RENT (2)

100 %

STORE ENABLE

D. ADJ. PARAME-

TERS

OPTION CARD

NOT INSTALLED

O/C DELAY

0.5 SEC.

CURRENT LIMIT

400% OF FLA

OVERLOAD CLASS

IEC CLASS 10

ACC. TIME

10 SEC.

OVERLOAD PROTECT

ENABLE WHILE RUN

MAX. START TIME

30 SEC.

UNBALANCE TRIP

20% OF FLA

NUMBER OF STRT

1

1.1.1.1.1.1.1.31.1.1.1.1.1.1.1

Page 103: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Menu Description

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 103 / 111

UNBALANCE DELAY

5 SEC.

STARTS PERIOD

20 MIN.

GND FAULT TRIP

20% OF FLA

START INHIBIT

15 MIN.

GND FAULT DELAY

5 SEC.

RUN CONTACTDLY

5 sec.

UNDERVOLT. TRIP

70% OF Vn

TURN BYPS ON AT

120% OF FLA

UNDERVOLT. DELAY

5 SEC.

MIN TIME TO BYPS

3 SEC.

OVERVOLT. TRIP

120% OF Vn

STORE ENABLE

STRT PARAMETER

OVEERVOLT.

DELAY

2 SEC.

STORE ENABLE

MAIN & PROTECT.

Page 104: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Menu Description

104 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

MODE MODE MODE MODE MODE

PAGE 5 PAGE 6 PAGE 7 PAGE 8 PAGE 9

FAULT PARA-

METERS

I/0 PROGRAMING

PARAMETERS

COMM. PARA-

METERS

STATISTICAL DATA

--

FIRING TEST

DISCONNECT

MAINS

SELECT SELECT SELECT SELECT SELECT

Parameter changes are not applicable here

Note

Program input # 7 to test then <STORE>. Connect control power to

terminal 7 not 3 PHASE. Time is limited to 30 sec.

FOR MODBUS

UV& PL AUTO RE-

SET NO

PROG. INPUT # 7

RESET

COMM. PROTO-

COL

MODBUS

T SINCE LST STRT

NO DATA

RUN SELF TEST?

PUSH UP ARROW

UNDER CUR. RE-

SET

OFF

PROG. INPUT #8

DUAL ADJUST-

MENT

BAUD RATE

9600 (MODBUS)

LAST STRT PE-

RIOD

NO DATA

PROGRAM VER-

SION

MVSTMB.GN-110808

BYPASS OPEN

TRIP

ENABLE

FAULT RELAY

TYPE

FAULT

PARITY CHECK

EVEN

LAST STRT MAX I

NO DATA

STORE ENABLE

DEFAULT PARA-

MET.

TRIP AFTER BY-

PASS

ENABLE

IMM. RELAY TYPE

IMMEDIATE

SERIAL LINK NO.

OFF

TOTAL RUN TIME

0 HOURS

RESET STATISTICS

Page 105: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Menu Description

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 105 / 111

BY-PASS AUTO

RST

NO

RELAY ON DELAY

0 SEC.

S. LINK PAR.

SAVE

DISABLE

TOTAL # OF

START

0

VOLTAGE ADJUST.

15 % OF Vn

SET CURVE 0 FLT

ENABLE

RELAY OFF

DELAY

0 SEC.

SER. LINK CON-

TROL

DISABLE

TOTAL ENERGY

0 KWH

CURRENT ADJUST

99% OF FLC

PWR ON & NO

STRT

ENABLE

ANALOG OUTPUT

RELATIVE CUR-

RENT

MODBUS TIME

OUT

OFF

TOTAL R. ENERGY

0 KVARH

hh.mm mm.dd.yy

00:00 01/01/00

INSULATION

ALARM

OFF

STORE ENABLE

I/O PROG.PARAM.

FRONT COM

ADDRES

OFF

LAST TRIP

NO DATA

INSULATION TRIP

OFF

STORE ENABLE

COMM. PARA-

METERS

TRIP CURRENT

0 % OF FLA

PHASE SE-

QUENCE

POSITIVE

▲Applicable

when Modbus op-

tional PCB in-

stalled

TOTAL # OF TRIPS

0

STORE ENABLE

FAULT PARAME-

TERS

▼Applicable

when

profibus op-

tional

PCB installed

LAST 10 TRIPS

hh.mm mm.dd.yy

COMM. PROTO-

COL

PROFIBUS

.

.

BAUD RATE

AUTO (PROFI-

BUS)

.

.

PROFI.NET-

WORK ID

OFF

PREVIOUS TRIP -

10

hh.mm mm.dd.yy

S. LINK PAR.

SAVE

DISABLE

Page 106: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Menu Description

106 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

SER. LINK CON-

TROL

DISABLE

MODBUS TIME

OUT

OFF

FRONT COM

ADDRES

OFF

STORE ENABLE

COMM. PARA-

METERS

+ MODE

STORE

ENABLE

DEFAULT PA-

RAMET.

SELECT RESET STA-

TISTICS SELECT

PROGRAM VER-

SION MVSTRT

.DN-311298

MODE +

STORE

RESET +

STORE

SELECT

SAVE DEFAULT

PARAMETERS

& BACK TO PA-

RAMETERS

DISPLAY PAGE

SAVE STA-

TISTICAL

DATA & BACK

TO PAGE 9

VOLTAGE AD-

JUST.

1% OF Vn

CURRENT AD-

JUST.

X% OF FLC

% OF MOTOR

FLA

STATISICAL

DATA

--

BACK TO:

STORE ENABLE

DEFAULT PARA-

MET.

1.1.1.1.1.1.1.5

Page 107: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Contents of figures

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 107 / 111

13 Contents of figures

Figure 1 ESD-notes ......................................................................... 8

Figure 2 Power section up to 6600V .............................................. 17

Figure 3 control board ................................................................... 19

Figure 4 DIP-switches ................................................................... 27

Figure 5 analog card ...................................................................... 30

Figure 6 operator panel, display, I/O terminals ............................. 36

Figure 7 processor board with operator panel / display ................ 40

Figure 8 DIP switches for analog card .......................................... 46

Figure 9 Controlboard wiring diagram .......................................... 48

Figure 10 choice of three pump control curves (2,3,4) ................... 49

Figure 11 start curve 5, torque curve .............................................. 50

Figure 12 pulse start ....................................................................... 51

Figure 13 initial voltage ................................................................... 52

Figure 14 current limit ..................................................................... 53

Figure 15 acceleration time ............................................................ 53

Figure 16 pump control stop curves ............................................... 55

Figure 17 torque control ................................................................. 56

Figure 18 tacho feedback ............................................................... 56

Figure 19 deceleration time ............................................................ 57

Figure 20 final torque ...................................................................... 57

Figure 21 dual adjustment .............................................................. 58

Figure 22 LED arrangement ........................................................... 69

Figure 23 mode selection (full / limited set of parameters) ............. 70

Figure 24 selection key ................................................................... 70

Figure 25 key to increase a parameter value ................................. 70

Page 108: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Contents of figures

108 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

Figure 26 key to decrease a parameter value ................................ 71

Figure 27 key to store a parameter ................................................. 71

Figure 28 key to reset after fault has been removed ...................... 71

Figure 29 text display arrangement ................................................ 72

Figure 30 down / up keys ............................................................... 72

Figure 31 display start parameters ................................................. 73

Figure 32 display stop parameters ................................................. 73

Figure 33 display dual adjustment parameters ............................... 73

Figure 34 display fault parameters ................................................. 74

Figure 35 I/O programming parameters ......................................... 74

Figure 36 display communication parameters ................................ 74

Figure 37 display statistical data..................................................... 74

Figure 38 operating current display ................................................ 74

Figure 39 option card not installed .................................................. 75

Figure 40 analog output card installed ............................................ 75

Figure 41 Restore default parameters ............................................ 75

Figure 42 Remote Display .............................................................. 76

Page 109: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Contents of tables

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 109 / 111

14 Contents of tables

Table 1 PIV rating ......................................................................... 12

Table 2 Dip switch settings (PC2050 type) ................................... 27

Table 3 Display modes ................................................................. 28

Table 4 DIP switch settings switch 4 and 6 .................................. 29

Table 5 DIP switch settings analog card ...................................... 31

Table 6 Terminal 7 programming ................................................. 34

Table 7 Terminal 8 programming ................................................. 34

Table 8 DIP switch settings analog card ...................................... 46

Table 9 timing and occurrence ..................................................... 67

Table 10 List of parameters ............................................................ 77

Page 110: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Notice

110 / 111 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual

15 Notice

Page 111: IGEL Electric GmbH - ISA-HD ISA-HD... · 2016. 6. 13. · 20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 11 / 111 2.3 Storage The soft starter is designed for indoor use and must

Notice

20140512_RevL_gb_kq_MV-C ISA-HD Instruction manual 111 / 111

IGEL® Electric GmbH IGEL® Electric Dubai

Industrieweg 13-15 Dubai Creek Tower, Office No 22-B

48324 Sendenhorst Dubai

Deutschland U.A.E

Fon + 49 2526 9389 - 0 Fon +971 429456-05

Fax + 49 2526 9389 – 22 Fax +971 294561-0

e-Mail [email protected]

http://www.igelelectric.de

Copyright IGEL Electric GmbH

All rights reserved.

This document shall not be transmitted or reproduced, nor shall its contents be exploited or disclosed to third per-

sons without prior written consent from IGEL Electric. Infringements will be subject to damage claims. All rights

reserved, in particular in case of a patent grant of utility model registration.

Disclaimer of liability

Although we have carefully checked the contents of this publication for conformity with the hardware and software

described, we cannot guarantee complete conformity since errors cannot be excluded. The information provided in

this manual is checked at regular intervals and any corrections which might become necessary will be included in

the next editions.